Tousey, Joyce Planset Revision 04-11-24 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Coleman D. Larsen, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com January 29, 2024 Revised April 11, 2024 Greenlancer Energy Inc. 500 Woodward Avenue, Suite 2125 Detroit, MI 48226 Re: Engineering Services Tousey Residence 7 Perkins Avenue, Northampton MA 7.290 kW System To Whom It May Concern: We have received information regarding solar panel installation on the roof of the above referenced structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability to support the additional loads imposed by the proposed solar system. A. Site Assessment Information 1. Site visit documentation identifying attic information including size and spacing of framing for the existing roof structure. 2. Design drawings of the proposed system including a site plan, roof plan and connection details for the solar panels. This information will be utilized for approval and construction of the proposed system. B. Description of Structure: Roof Framing: 2x6 dimensional lumber at 24” on center. Roof Framing: 2x4 dimensional lumber at 28” on center. Roof Material: Metal Slate Tile Roof Slope: 30 and 34 degrees Attic Access: Accessible Foundation: Permanent C. Loading Criteria Used • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 PSF • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 psf • Live Load = 20 psf (reducible) – 0 psf at locations of solar panels • Ground Snow Load = 40 psf • Wind Load based on ASCE 7-10 o Ultimate Wind Speed = 117 mph (based on Risk Category II) o Exposure Category C Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance with the 2015 IRC, including provisions allowing existing structures to not require strengthening if the new loads do not exceed existing design loads by 105% for gravity elements and 110% for seismic elements. This analysis indicates that the existing framing will support the additional panel loading without damage, if installed correctly. Page 2 of 2 D. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent QuickMount PV installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non- uniformly, our office should be notified before proceeding with the installation. 2. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as identified in the National Design Standards (NDS) of timber construction specifications. Based on two screws with a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the design withdrawal force (demand). Considering the variable factors for the existing roof framing and installation tolerances, the connection using two 5/16” diameter lag screw with a minimum of 2½” embedment will be adequate and will include a sufficient factor of safety. 3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 28” on center for Arrays 2 & 3, and no greater than 48” on center for Array 1. Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing roof system will adequately support the additional loading imposed by the solar system. This evaluation is in conformance with the 2015 IRC, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE MA License No. 50507 Massachusetts COA # 001629764 GENERAL NOTES1.1.1PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRICCODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATIONINSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVINGJURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEMINSPECTED PRIOR TO PARALLEL OPERATION1.1.4 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, ANDSOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE INPHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730,AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547,929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.5 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENTFOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7.1.1.6 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCECIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BEIDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLEDACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3].1.1.7 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IFEXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILLBE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THEGRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BERESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.*NEC2020I1.3.1 WORK INCLUDES:1.3.2 PV ROOF ATTACHMENTS - QUICK MOUNT PV QMNC: QBASE COMPOSITION MOUNT1.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE A2 RAIL1.3.4 PV MODULE AND INVERTER INSTALLATION - REC SOLAR REC420AA PURE-R / TESLA SOLAR INVERTER 7.6 (240V)1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED SOLADECK1.3.7 PV INSTALLING SYSTEM MONITORING EQUIPMENT1.3.8 PV LOAD CENTERS (IF INCLUDED)1.3.9 PV METERING (IF INCLUDED)1.3.10 PV DISCONNECTS1.3.11 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.12 PV FINAL COMMISSIONING1.3.13 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PVOWNERNAME: JOYCE TOUSEYAUTHORITIES HAVING JURISDICTIONBUILDING: CITY OF NORTHAMPTONZONING: CITY OF NORTHAMPTONUTILITY: NATIONAL GRIDDESIGN SPECIFICATIONSOCCUPANCY: ІІCONSTRUCTION: SINGLE-FAMILYZONING:RESIDENTIALGROUND SNOW LOAD: 40 PSFWIND EXPOSURE: CWIND SPEED: 117 MPHUTILITY METER #86111265 (LEFT METER)APPLICABLE CODES & STANDARDSBUILDING: MASSACHUSETTS BUILDING CODE, 9THEDITION, AS AMENDED (780 CMR)RESIDENTIAL: MASSACHUSETTS RESIDENTIONAL BUILDINGCODE, 9TH EDITION, AS AMENDED (780 CMR)ELECTRICAL: NEC 2023FIRE:MASSACHUSETTS COMPREHENSIVE FIRESAFETY CODE (527 CMR 1.00)NFPA 1 FIRE CODE - 2021PROJECT INFORMATIONPROJECT MANAGERNAME:PHONE:CONTRACTORNAME:PHONE:PATRICK RONDEAU413-584-8844VALLEY SOLAR LLC413-584-8844PROJECT DESIGNED BY TIMOTHY SOBERANOPROJECT SUPERVISED BY JESSE BREKELBAUMBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338T-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALENEW PV SYSTEM: 7.140 kWpJOYCE TOUSEY RESIDENCE7 PERKINS AVENUENORTHAMPTON, MA 01060ASSESSOR'S #: NHAMM024DB0217L0001SCOPE OF WORKSYSTEM SIZE:ATTACHMENT TYPE:MSP UPGRADE:STC: 17 X 420W = 7.140KWPTC: 17 X 402.5W = 6.843KW(17) REC SOLAR REC420AA PURE-R(1) TESLA SOLAR INVERTER 7.6 (240V)QUICK MOUNT PV QMNC:QBASE COMPOSITION MOUNTNO-SERVICE PHASE: SINGLE-SERVICE SIZE (AMPS): 200A-DISTANCE FROM UTILITY METER TO TRANSFORMER: 45 FT.-CONNECTIVITY TYPE: OVERHEAD-UTILITY METER NUMBER: # 86111265 (LEFT METER)-INVERTER: (1) TESLA SOLAR INVERTER 7.6 (240V)-PANELS: (17) REC SOLAR REC420AA PURE-R-DC-STC RATING OF SYSTEM: 7.140 KWP-AC SYSTEM DESIGN CAPACITY (NOMINAL): 7.600 KWP-AC SYSTEM DESIGN CAPACITY (MAXIMUM): 7.680 KWPSHEET LIST TABLESheet NumberSheet TitleT-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANА-104INSTALLER REFERENCE PAGEE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSS-501ASSEMBLY DETAILSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTPERKINS AVER-005RESOURCE DOCUMENTS-502ASSEMBLY DETAILSSigned 4/11/2024 1.1.11.1.21.1.31.1.41.1.51.1.61.1.71.2.1 1.2.22.1.1SITE NOTES:2.1.2A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.2.1.3THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITYINTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDINGROOF VENTS.2.1.5PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICALEQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.2.1.6ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITHTHIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOFCOVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS2.2.2ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.2.3WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATINGTEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).2.2.4JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC690.34.2.2.5ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHINSIGHT OF THE AC SERVICING DISCONNECT.2.2.6ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TONEC APPLICABLE CODES.2.2.7ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHENAPPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANTINSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THEARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.2.3.3JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.2.3.4ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVEDCHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.2.3.5ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCESPECIFIED BY THE RACKING MANUFACTURER.2.3.6WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGSTTHE ROOF FRAMING MEMBERS.2.4.1GROUNDING NOTES:2.4.2GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDINGDEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.2.4.3PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICALEQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED.2.4.4PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE250.122.2.4.5METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDEREDGROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.4.6EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN INMANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLESPER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.2.4.7THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVALOF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.2.4.8GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN ORMARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.4.9THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODESYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.2.4.10DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THEREQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS2.5.1INTERCONNECTION NOTES:2.5.2LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12]2.5.3THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THERATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BELOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].2.5.4AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALLOVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THECOMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).2.5.5FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)2.5.6SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCECONDUCTORS IN ACCORDANCE WITH NEC 230.422.5.7BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROMADDITIONAL FASTENING [NEC 705.12 (E)].2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THECONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINESIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE AVISIBLE-BREAK SWITCH.2.6.4BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUSTOPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13.2.6.5ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITSCONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT, OR WITHIN SIGHT ANDWITHIN 10 FT. OF THE EQUIPMENT. AN EQUIPMENT DISCONNECTING MEANS SHALL BEPERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTINGMEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT. OF THE EQUIPMENT, ACCORDINGTO NEC 690.15 (A).2.6.6PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWNFUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH690.12(A) THROUGH (D)2.6.7ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.2.6.8BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTHREQUIRE OVER-CURRENT PROTECTION, ACCORDING TO NEC 240.21. (SEE EXCEPTION IN NEC690.9)2.6.9IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TONEC 690.11 AND UL1699B.2.7.1WIRING & CONDUIT NOTES:2.7.2ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT ANDWIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANTTO LIMIT UP-SIZING.2.7.3ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.7.4EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED ANDIDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALLBE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A).2.7.5PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(5)].2.7.6MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.2.7.7ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKEDAS FOLLOWS: DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREENDC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN2.7.8AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAY*IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKEDORANGE [NEC 110.15].*NEC2020I *NEC2020I 1.3.4 PV MODULE AND INVERTER INSTALLATION - 1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED SOLADECK1.3.7 PV INSTALLING SYSTEM MONITORING EQUIPMENT1.3.8 PV LOAD CENTERS (IF INCLUDED)1.3.9 PV METERING (IF INCLUDED)1.3.10 PV DISCONNECTS1.3.11 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.12 PV FINAL COMMISSIONING1.3.13 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PVBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338G-001.00NOTES(SHEET 2)Signed 4/11/2024 A-101.00SITE PLAN(SHEET 3)ENTRANCEBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-884418633801/16" = 1'-0"SITE PLAN018'16'NEWSNEWSAREA OF WORKPROPERTY LINEGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEAC DISCONNECTCUSTOMER OWNED METERUTILITY METER #1PERKINS AVEUTILITY METER #2PROSPECT ST9'-0"21'-8"44'-3"13'-0"Signed 4/11/2024 MODULE:REC SOLARREC420AA PURE-R420 WATTS44"68.1"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338A-102.00ELECTRICAL PLAN(SHEET 4)01/8" = 1'-0"ELECTRICAL PLAN014'8'NEWSAMODULE STRINGINGBMODULE STRINGINGCMODULE STRINGINGDMODULE STRINGINGGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEINTERIOR PV EQUIPMENT(E) (1) MAIN ELECTRICAL PANEL #1(N) (1) SOLADECKFIRE CLEARANCESQUARE FOOTAGE OF ROOF: 1629.54 SQ. FT.SQUARE FOOTAGE OF ARRAY: 353.74 SQ. FT.PERCENTAGE OF ROOF COVEREDBY THE ARRAYS: 21.71%A(N) (1) INVERTER(N) (1) CUSTOMER OWNED METEREXTERIOR PV EQUIPMENT(N) (1) AC DISCONNECTCONDUIT WILL NOT BE PLACED WITHINFIRE SETBACKS AS PER NFPA 1 2021AВВ(N) (1) UTILITY METER #2ARRAY 2 - 1.260 KW[x3] (N) MODULESTILT: 30 DEGREESROOF PITCH: 7:12AZIMUTH: 237 DEGREESARRAY 1 - 4.620 KW[x11] (N) MODULESTILT: 34 DEGREESROOF PITCH: 8:12AZIMUTH: 148 DEGREES(N) (1) UTILITY METER #1(E) (1) MAIN ELECTRICAL PANEL #2СС3 FT. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH18 IN. FIRE ACCESS PATH18 IN. FIRE ACCESS PATHDD3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATHARRAY 3 - 1.260 KW[x3] (N) MODULESTILT: 30 DEGREESROOF PITCH: 7:12AZIMUTH: 57 DEGREES3 FT. FIRE ACCESS PATH MODULE:REC SOLARREC420AA PURE-R420 WATTS44"68.1"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338A-103.00SOLAR ATTACHMENT PLAN(SHEET 5)01/8" = 1'-0"SOLAR ATTACHMENT PLAN014'8'NEWSROOF RAFTERSGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEFLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILS)ROOF MATERIAL IS METAL SLATE TILE31'-3"11'-1"ROOF MATERIAL IS METAL SLATE TILEFLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-502 FOR MOUNTING DETAILS)13'-0"ROOF MATERIAL IS METAL SLATE TILESigned 4/11/2024 MODULE:REC SOLARREC420AA PURE-R420 WATTS44"68.1"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338А-104.00INSTALLER REFERENCEPAGE(SHEET 6)03/16" = 1'-0"INSTALLER REFERENCE PAGE012'-8"5'-4"NEWSGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGESigned 4/11/2024 EQUIPMENT RIGHTOF LINE IS (E) EXISTINGUNLESS OTHERWISE NOTED.PV SYSTEM EQUIPPED WITH RAPIDSHUTDOWN DISCONNECT PER NEC 690.12SYSTEM COMPLIANT WITH NEC 690.13NOTE: READILY ACCESSIBLE OPEN BLADE ACSYSTEM DISCONNECT VISIBLE FROM APPROACHTO RESIDENCE 60A 240V LOCATED EXTERIOR ONWALL NEAR METER NEMA 3R(N) (17) REC SOLARREC420AA PURE-R420W(N)SOLADECK(N) TESLA SOLARINVERTER 7.6 (240V)(N) (10) TESLAPOWER OPTIMIZER SOLAR SHUTDOWN DEVICE(E) GROUNDINGELECTRODEGROUNDRODTO UTILITYGRID (OH)L2NL1(E) MAIN ELECTRICAL PANEL #1240/120 V 1Ø, 3WMAIN BUSS: 125A(N)UTILITYMETERGNTO (E)LOADSL2L1NNNTAPUTILITY METER # 82445696 (LEFT METER) MAIN100A (N)NOTE: TOP LUGS TO SOLARGENERATION (LOAD)BOTTOM LUGS TO UTILITY(LINE) LOCATED EXTERIOREQUIPMENT LEFTOF LINE IS (N) NEWUNLESS OTHERWISE NOTED.64VBOTTOM LUGSTOP LUGS(N) SOLAR REC METER -CUSTOMER OWNEDM1LOADLINEG(N) CIRCUIT BREAKER DISCONNECT OCPD RATING: 60A MLO BUSS: 70ACB1GSW1 (N) 60AAC DISCONNECTEATON DG222URB53200A SERVICE6BC3D35A21GL1L2NCONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSID TYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL1 410 AWG PV WIRE, COPPERFREE AIR2N/A6 AWG BARE, COPPER0.96 (32.7 °C)111.1A13.88A55A52.8A75°C50A2 110 AWG THWN-2, COPPER0.75'' DIA EMT8N/A10 AWG THWN-2, COPPER0.96 (32.7 °C)0.711.1A 13.88A40A 26.88A75°C35A318 AWG THWN-2, COPPER0.75'' DIA EMT2N/A8 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A4 18 AWG THWN-2, COPPER0.75'' DIA EMT2N/A8 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A518 AWG THWN-2, COPPER0.75'' DIA EMT240A8 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A55A52.8A75°C50A6 16 AWG THWN-2, COPPER0.75'' DIA EMT2N/A6 AWG THWN-2, COPPER0.96 (32.7 °C)132A40A75A72A75°C65ABFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-601.00LINE DIAGRAM(SHEET 7)MODULE STRINGINGMODULE STRINGINGABMODULE STRINGINGCMODULE STRINGINGD DISCONNECTSINVERTERSOCPDSMODULESASHRAE EXTREME LOW-25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)ASHRAE 2% HIGH32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)REF.QTY.RATED CURRENTMAX VOLTAGECB1160A240VACREF.QTY.MAKE AND MODELRATED CURRENTMAX RATED VOLTAGESW11EATON DG222URB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAXPTCISCIMPVOCVMPTEMP. COEFF. OF VOCFUSE RATINGPM1-1717REC REC420AA PURE-R420W402.5W8.88A8.4A59.4V50V-0.143V/°C (-0.24%/°C)25AREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI11TESLA 7.6 KW240VFLOATING40A7600W32A4x11A600V97.5%SYSTEM SUMMARYINVERTER #1INVERTER #2MPPT #1MPPT #2MPPT #3MPPT #1MODULES IN SERIES5633ARRAY VMP250V300V150V150VARRAY IMP8.4A8.4A8.4A8.4AARRAY VOC297V356.4V178.2V178.2VARRAY MAX VOC333.4V400.1V200V200VARRAY ISC8.88A8.88A8.88A8.88AARRAY STC POWER7,140WARRAY PTC POWER6,843WMAX AC CURRENT32AMAX AC POWER7,600WDERATED (CEC) AC POWER6,672WARRAY STC POWER7,140WARRAY PTC POWER6,843WMAX AC CURRENT32AMAX AC POWER7,600WDERATED (CEC) AC POWER6,672WBILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULERECREC420AA PURE-RPM1-1717PIECES1REC REC420AA PURE-R 420W 144 HALF-CELLS, MONOCRYSTALLINE SILICONINVERTERTESLA7.6 KWI11PIECE1TESLA 7.6 KW 7600W INVERTERDISCONNECTEATONDG222URBSW11PIECE1EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTPRODUCTION METERGENERIC MANUFACTURERGEN-METER-80AM11PIECE1ELECTRICAL METER, OWNER APPROVEDWIRINGGEN-10-AWG-PV-WIRE-CUWR1360FEET110 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)WIRINGGEN-6-AWG-BARE-CUWR1180FEET16 AWG BARE, COPPER (GROUND)WIRINGGEN-10-AWG-THWN-2-CU-RDWR280FEET110 AWG THWN-2, COPPER, RED (POSITIVE)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR280FEET110 AWG THWN-2, COPPER, BLACK (NEGATIVE)WIRINGGEN-10-AWG-THWN-2-CU-GRWR220FEET110 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-8-AWG-THWN-2-CU-RDWR3-530FEET18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR3-530FEET18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR3-530FEET18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-8-AWG-THWN-2-CU-GRWR3-530FEET18 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-6-AWG-THWN-2-CU-RDWR610FEET16 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-6-AWG-THWN-2-CU-BLKWR610FEET16 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-6-AWG-THWN-2-CU-WHWR610FEET16 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-GRWR610FEET16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYGEN-EMT-0.75'' DIAWW2-660FEET1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-60A-240VACCB11PIECE1CIRCUIT BREAKER, 60A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11PIECE1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-602.00DESIGN TABLES(SHEET 8) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-603.00PLACARDS(SHEET 9)NEWS!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:MAIN DISTRIBUTIONUTILITY DISCONNECTBACKFRONTAMPSVOLTSPV SOLARDISCONNECTELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(2)(3)(B)].LABEL 4AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].LABEL 9AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].LABEL 10AT EACH DC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWITCH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 3AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].LABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVINGJURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTINVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE REDBACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVEYELLOW BACKGROUND. [ANSI Z535]1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHERRESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B)INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDNW SIDE OF THE HOUSEDIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]"DIRECTORY STICKER WILL BE PRINTED IN RED WITH WHITE LETTERING."PHOTOVOLTAIC SOLARAC DISCONNECTCAUTIONMULTIPLE SOURCES OF POWERLABEL 6AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]WARNINGDUAL POWER SUPPLYSOURCES: UTILITY GRIDAND PV SOLARELECTRIC SYSTEMLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEDLABEL 8AT POINT OFINTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]PHOTOVOLTAIC SOLARDC DISCONNECTPHOTOVOLTAIC POWER SOURCELABEL 11AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 2").[NEC 690.54]AC DISCONNECTPHOTOVOLTAIC SYSTEMPOWER SOURCERATED ACOUTPUT CURRENTNOMINAL OPERATINGAC VOLTAGEAMPSVOLTS32240LABEL 12AT EACH DC DISCONNECTINGMEANS (3" X 4").[NEC 690.53].MAXIMUM VOLTAGEMAX CIRCUIT CURRENTVDCAMPSDIRECT CURRENTPHOTOVOLTAIC POWER SOURCE8.88400.1INVERTER(INTERIOR)PV ARRAYUTILITY METER #1PV ARRAYUTILITY METER #2CUSTOMER OWNED PV METERPV ARRAYPROUDLY INSTALLEDBY VALLEY SOLAR413-584-8844PERKINS AVE SHEET KEYNOTESSHEET KEYNOTESSHEET KEYNOTES1. ROOF MATERIAL: METAL SLATE TILE2. ROOF STRUCTURE: COLLAR TIE3. ATTACHMENT TYPE: QUICK MOUNT PV QMNC:QBASE COMPOSITION MOUNT4. MODULE MANUFACTURER: REC SOLAR5. MODULE MODEL: REC420AA PURE-R6. MODULE LENGTH: 68.1"7. MODULE WIDTH: 44"8. MODULE WEIGHT: 47.4 LBS.9. SEE SHEET S-501 FOR DIMENSION(S)10. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE11. RAFTER SPACING: 24 IN. O.C.12. RAFTER SIZE: 2X6 IN. NOMINAL.13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITH RACKING.14. LAG BOLT EMBEDMENT: 2.5 IN.15. TOTAL # OF ATTACHMENTS: 4216. TOTAL AREA: 228.89 SQ. FT.17. TOTAL WEIGHT: 567.08 LBS.18. WEIGHT PER ATTACHMENT: 13.5 LBS.19. DISTRIBUTED LOAD: 2.48 PSF20. MAX. HORIZONTAL STANDOFF: 48 IN.21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULEMANUFACTURER'S INSTRUCTIONS.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24. RAIL MODEL (OR EQUIVALENT): AIRE A2 RAIL25. RAIL WEIGHT: 0.436 PLF.26. MAX. RAFTER SPAN: N/A.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-501D52011121413151822ROOF SLOPE 910106217S-501D415438272524232FIELD VERIFY ALL MEASUREMENTS1.GENERAL NOTESBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338S-501.00ASSEMBLY DETAILS(SHEET 10)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALENOTE: A HOLE MUST BE CUT IN THE TILE AND THE MOUNTS ARE TO BE FLUSH WITH THE SHEATHING.Signed 4/11/2024 SHEET KEYNOTESSHEET KEYNOTESSHEET KEYNOTES1. ROOF MATERIAL: METAL SLATE TILE2. ROOF STRUCTURE: SINGLE SPAN RAFTER3. ATTACHMENT TYPE: QUICK MOUNT PV QMNC:QBASE COMPOSITION MOUNT4. MODULE MANUFACTURER: REC SOLAR5. MODULE MODEL: REC420AA PURE-R6. MODULE LENGTH: 68.1"7. MODULE WIDTH: 44"8. MODULE WEIGHT: 47.1 LBS.9. SEE SHEET S-501 FOR DIMENSION(S)10. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE11. RAFTER SPACING: 28 IN. O.C.12. RAFTER SIZE: 2X4 IN. NOMINAL.13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITH RACKING.14. LAG BOLT EMBEDMENT: 2.5 IN.15. TOTAL # OF ATTACHMENTS: 2216. TOTAL AREA: 124.85 SQ. FT.17. TOTAL WEIGHT: 290.94 LBS.18. WEIGHT PER ATTACHMENT: 13.22 LBS.19. DISTRIBUTED LOAD: 2.33 PSF20. MAX. HORIZONTAL STANDOFF: 28 IN.21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULEMANUFACTURER'S INSTRUCTIONS.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24. RAIL MODEL (OR EQUIVALENT): AIRE A2 RAIL25. RAIL WEIGHT: 0.436 PLF.26. MAX. RAFTER SPAN: N/A.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.S-502D52011121413151822ROOF SLOPE 910106217S-502D4154382725242321.FIELD VERIFY ALL MEASUREMENTSGENERAL NOTESBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338S-502.00ASSEMBLY DETAILS(SHEET 11)D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALENOTE: A HOLE MUST BE CUT IN THE TILE AND THE MOUNTS ARE TO BE FLUSH WITH THE SHEATHING.Signed 4/11/2024 BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-001.00RESOURCE DOCUMENT(SHEET 12) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-002.00RESOURCE DOCUMENT(SHEET 13) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-003.00RESOURCE DOCUMENT(SHEET 14) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-004.00RESOURCE DOCUMENT(SHEET 15) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS O.L.M.M.01.25.2024PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 7.140 kWp7 PERKINS AVENUE NORTHAMPTON, MA 01060APN: NHAMM024DB0217L0001JOYCETOUSEYRESIDENCECONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-005.00RESOURCE DOCUMENT(SHEET 16)