Anderson, Kathy Stamped Planset 01.30.24
76 North Meadowbrook Drive
Scott E. Wyssling, PE Alpine, UT 84004
Coleman D. Larsen, SE, PE office (201) 874-3483
Gregory T. Elvestad, PE swyssling@wysslingconsulting.com
January 16, 2024
Revised January 30, 2024
Greenlancer Energy Inc.
500 Woodward Avenue, Suite 2125
Detroit, MI 48226
Re: Engineering Services
Anderson Residence
50 Water Street, Leeds MA
7.695 kW System
To Whom It May Concern:
We have received information regarding solar panel installation on the roof of the above referenced
structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability
to support the additional loads imposed by the proposed solar system.
A. Site Assessment Information
1. Site visit documentation identifying attic information including size and spacing of framing
for the existing roof structure.
2. Design drawings of the proposed system including a site plan, roof plan and connection
details for the solar panels. This information will be utilized for approval and construction
of the proposed system.
B. Description of Structure:
Roof Framing: 2x4 rough sawn lumber at 24” on center. (Array 2)
Roof Framing: 2x4 rough sawn lumber at 25” on center. (Array1) (upgrade is required by
adding an additional 2 x 6 to the existing rafters with glue and screws
every 24” staggered)
Roof Material: Composite Asphalt Shingles
Roof Slope: 38 degrees
Attic Access: Accessible
Foundation: Permanent
C. Loading Criteria Used
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 PSF
• Dead Load
o Existing Roofing and framing = 7 psf
o New Solar Panels and Racking = 3 psf
o TOTAL = 10 psf
• Live Load = 20 psf (reducible) – 0 psf at locations of solar panels
• Ground Snow Load = 40 psf
• Wind Load based on ASCE 7-10
o Ultimate Wind Speed = 116 mph (based on Risk Category II)
o Exposure Category C
Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance
with the 2015 IRC, including provisions allowing existing structures to not require strengthening if
the new loads do not exceed existing design loads by 105% for gravity elements and 110% for
seismic elements. This analysis indicates that the existing framing will require sistering a new 2x6
the full length from the ridge to the load bearing wall in the area of the solar panel installation (Array
1) to support the additional panel loading without damage, if installed correctly.
Page 2 of 2
D. Solar Panel Anchorage
1. The solar panels shall be mounted in accordance with the most recent Ironridge installation manual.
If during solar panel installation, the roof framing members appear unstable or deflect non -
uniformly, our office should be notified before proceeding with the installation.
2. The maximum allowable withdrawal force for a 5/16” lag screw is 229 lbs per inch of penetration as
identified in the National Design Standards (NDS) of timber construction specifications. Based on
a minimum penetration depth of 2½”, the allowable capacity per connection is greater than the
design withdrawal force (demand). Considering the variable factors for the existing roof framing
and installation tolerances, the connection using one 5/16” diameter lag screw with a minimum of
2½” embedment will be adequate and will include a sufficient factor of safety.
3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of
the roof, the panel supports shall be placed no greater than 25” on center for Array 1 and no greater
than 48” on center for Array 2)
Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing
roof system with the structural upgrade identified (sistering existing rafters with an additional 2 x 6 at Array 1),
will adequately support the additional loading imposed by the solar system. This evaluation is in conformance
with the 2015 IRC, current industry standards, and is based on information supplied to us at the time of this
report.
Should you have any questions regarding the above or if you require further information do not hesitate to
contact me.
Very truly yours,
Scott E. Wyssling, PE
MA License No. 50507
Massachusetts COA # 001629764
24" MAX.
10d COMMON NAILS, STAGGERED
EXISTING RAFTER
NEW SISTER.
SAME SIZE AS EXISTING, UNLESS NOTED OTHERWISE.
SHALL BE NAILED AND GLUED TO EXISTING.
EXISTING RIDGE BOARD
NOTES:
1. NEW SISTER SHALL BE LUMBER GRADE
No. 2 OR BETTER.
2. ATTACH TO EXISTING RAFTERS WITH
GLUE AND NAILS SPECIFIED OR 14" x 3"
WOOD SCREWS.
3. IF CONTRACTOR IS UNABLE TO INSTALL
FULL LENGTH SISTER RAFTER DUE TO
ACCESS, A SPLICE CAN BE UTILIZED. SEE
DETAIL BELOW.
30" MIN, TYP.
NEW SPLICE BOARD (ONE PIECE),
12" PLYWOOD, SAME DEPTH AS SISTERING
EXISTING AND SISTERED
RAFTER ASS'Y
(8) 14"x3" WOOD SCREWS TYP. EACH SIDE OF SPLICE
A
A
EXISTING RAFTER
SISTERED RAFTER
SPLICE BOARD (IF NECESSARY)
SECTION A-A
RAFTER SISTERING DETAIL
NOT TO SCALE
SISTERED SPLICE DETAIL (IF NECESSARY)
NOT TO SCALE
NOTES:
1. NEW SPLICE BOARD SHALL
12" PLYWOOD,
SAME DEPTH AS SISTERING.
2. ATTACH TO NEW SISTERS WITH GLUE
AND 14" x 3" WOOD SCREWS.
3. USE OF CONSTRUCTION ADHESIVE IS
RECOMMENDED.
JOINT IN SISTERING. SPLICE TO BE
CONTINUOUS OVER JOINT.
IF CONTRACTOR IS UNABLE TO INSTALL
FULL LENGTH SISTER RAFTER DUE TO ACCESS,
A SPLICE CAN BE UTILIZED. SEE DETAIL BELOW.
(201) 874-3483
swyssling@wysslingconsulting.com
Wyssling Consulting
76 N. Meadowbrook Dr.
Alpine, UT 84004
Signed 1/30/2024
GENERAL NOTES
1.1.1 PROJECT NOTES:
1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION
INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY
HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.
1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM
INSPECTED PRIOR TO PARALLEL OPERATION
1.1.4 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN
PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703,
IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED,
IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY
1.1.5 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP
COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED
ACCORDING TO NEC 690.7.
1.1.6 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE
CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL
BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE
INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC
110.3].
1.1.7 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF
EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE
WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
1.2.1 SCOPE OF WORK:
1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF
THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE
RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,
SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE
PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.
1.3.1 WORK INCLUDES:
1.3.2 PV ROOF ATTACHMENTS - IRONRIDGE FLASH VUE
1.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE A2
1.3.4 PV MODULE AND INVERTER INSTALLATION -
REC SOLAR REC405AA PURE BLACK /TESLA 7.6 KW
1.3.5 PV EQUIPMENT GROUNDING
1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX
1.3.7 PV LOAD CENTERS (IF INCLUDED)
1.3.8 PV METERING/MONITORING (IF INCLUDED)
1.3.9 PV DISCONNECTS
1.3.10 PV FINAL COMMISSIONING
1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE
*NEC2020I
OWNER
NAME: ELIZABETH KILDUFF
PHONE:
E-MAIL:
PROJECT MANAGER
NAME: PATRICK RONDEAU
PHONE: 413-584-8844
CONTRACTOR
NAME: VALLEY SOLAR LLC
PHONE: 413-584-8844
AUTHORITIES HAVING JURISDICTION
BUILDING: VILLAGE OF LEEDS
ZONING: VILLAGE OF LEEDS
UTILITY: NATIONAL GRID
DESIGN SPECIFICATIONS
OCCUPANCY: II
CONSTRUCTION: SINGLE-FAMILY
ZONING: RESIDENTIAL
GROUND SNOW LOAD: 40 PSF
WIND EXPOSURE: C
WIND SPEED: 116 MPH
APPLICABLE CODES & STANDARDS
BUILDING: MASSACHUSETTS BUILDING CODE, 9TH
EDITION, AS AMENDED (780 CMR),
MASSACHUSETTS RESIDENTIONAL BUILDING
CODE, 9TH EDITION, AS AMENDED (780 CMR)
ELECTRICAL: NEC 2023
FIRE: MASSACHUSETTS COMPREHENSIVE FIRE
SAFETY CODE (527 CMR 1.00)
PROJECT INFORMATION
NEW PV SYSTEM: 7.695 kWp
ELIZABETH KILDUFF RESIDENCE
50 WATER ST,
LEEDS, MA 01053
ASSESSOR'S #: 10B-078-001
SCOPE OF WORK
PROJECT INFORMATION
SCOPE OF WORK
SYSTEM SIZE:
ATTACHMENT TYPE:
MSP UPGRADE:
IRONRIDGE FLASH VUE
NO
SCOPE OF WORK
PROJECT INFORMATION: SERVICE PHASE: SINGLE
SERVICE SIZE (AMPS): 100A
DISTANCE FROM UTILITY METER TO TRANSFORMER ___FT
CONNECTIVITY TYPE: OVERHEAD
UTILITY METER NUMBER 68668854
INVERTER: (1) TESLA 7.6 KW
PANELS: (19) REC SOLAR REC405AA PURE BLACK
DC-STC RATING OF SYSTEM: 7.695 KW
AC SYSTEM DESIGN CAPACITY (NOMINAL): 7.600 KW
AC SYSTEM DESIGN CAPACITY (MAXIMUM): 7.680 KW
STC: 19 X 405W = 7.695KW
PTC: 19 X 385.9W = 7.332KW
(19) REC SOLAR REC405AA PURE BLACK
(1) TESLA 7.6 KW
SYSTEM SIZE:
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS, MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLAT MAP
NOT TO SCALEWATER STSHEET LIST TABLE
SHEET NUMBER SHEET TITLE
T-001.00 COVER PAGE
G-001.00 NOTES
A-101.00 SITE PLAN
A-102.00 ELECTRICAL PLAN
A-103.00 SOLAR ATTACHMENT PLAN
A-104.00 STICKER MAP
E-601.00 LINE DIAGRAM
E-602.00 DESIGN TABLES
E-603.00 PLACARDS
S-501.00 ASSEMBLY DETAILS
S-502.00 ASSEMBLY DETAILS
R-001.00 RESOURCE DOCUMENT
R-002.00 RESOURCE DOCUMENT
R-003.00 RESOURCE DOCUMENT
R-004.00 RESOURCE DOCUMENT
R-005.00 RESOURCE DOCUMENT
T-001.00
COVER PAGE
Signed 1/30/2024
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY
INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL,OR BUILDING
ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).
2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC
690.34.
2.2.5 ADDITIONAL AC DISCONNECT(S)SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN
SIGHT OF THE AC SERVICING DISCONNECT.
2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO
NEC APPLICABLE CODES.
2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN
APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM &PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT
INSTALLATION MANUAL.TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE
ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS'SPECIFICATIONS.IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/APPROVED
CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE
SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE,ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST
THE ROOF FRAMING MEMBERS.
2.4.1 GROUNDING NOTES:
2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING
DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR.ALL METAL ELECTRICAL
EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND,IN ACCORDANCE WITH
250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED.
2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE
250.122.
2.4.5 METAL PARTS OF MODULE FRAMES,MODULE RACKING,AND ENCLOSURE CONSIDERED
GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ.IF WEEBS ARE NOT USED,
MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES
PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.
2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL
OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.
2.4.8 GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLORED GREEN OR
MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH
250.106.IF EXISTING SYSTEM IS INACCESSIBLE,OR INADEQUATE,A GROUNDING ELECTRODE
SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.
2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THE
REQUIREMENTS OF 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS
2.5.1 INTERCONNECTION NOTES:
2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12]
2.5.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE
RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120
PERCENT OF THE AMPACITY OF THE BUSBAR,PV DEDICATED BACKFEED BREAKERS MUST BE
LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].
2.5.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL,TOTAL RATING OF ALL
OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR.HOWEVER,THE
COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).
2.5.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)
2.5.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCE
CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.5.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM
ADDITIONAL FASTENING [NEC 705.12 (E)].
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE
CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE
SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL,BE LOCKABLE,AND BE A
VISIBLE-BREAK SWITCH.
2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED.THEREFORE BOTH MUST
OPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13.
2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITS
CONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT,OR WITHIN SIGHT AND
WITHIN 10 FT.OF THE EQUIPMENT.AN EQUIPMENT DISCONNECTING MEANS SHALL BE
PERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING
MEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT.OF THE EQUIPMENT,ACCORDING
TO NEC 690.15 (A).
2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN
FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH
690.12(A) THROUGH (D)
2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.
2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED,THEREFORE BOTH
REQUIRE OVER-CURRENT PROTECTION,ACCORDING TO NEC 240.21.(SEE EXCEPTION IN NEC
690.9)
2.6.9 IF REQUIRED BY AHJ,SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO
NEC 690.11 AND UL1699B.
2.7.1 WIRING & CONDUIT NOTES:
2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE.CONDUIT AND
WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT
TO LIMIT UP-SIZING.
2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED AND
IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALL
BE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A).
2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(5)].
2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY.
2.7.7 ACCORDING TO NEC 200.7,UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKED
AS FOLLOWS:
DC POSITIVE-RED, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GRAY AND GREEN
2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION
NEUTRAL- WHITE OR GRAY
*IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED
ORANGE [NEC 110.15].
*NEC2020I
*NEC2020I
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
G-001.00
NOTES
Signed 1/30/2024
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
A-101.00
SITE PLAN
N
EW
S
01/24" = 1'-0"
SITE PLAN01 12'24'
PROPERTY LINE
ENTRANCE
UTILITY METER
AREA OF WORK
SOLAR REC METER -
CUSTOMER OWNEDWATER STNOTE: CONDUIT WILL NOT BE PLACED
WITHIN FIRE SETBACKS AS PER NFPA 12021
AC DISCONNECT
28'-1"
37'-3"191'-7"
8'-6"
TOTAL SYSTEM KWAC SIZE: 7.600 KWAC
SOLAR REC METER - CUSTOMER OWNED:
TOP LUGS TO SOLAR GENERATION (LOAD)
BOTTOM LUGS TO UTILITY (LINE) LOCATED
EXTERIOR
READILY ACCESSIBLE OPEN BLADE AC
SYSTEM DISCONNECT VISIBLE FROM
APPROACH TO RESIDENCE 60A 240V
LOCATED EXTERIOR ON WALL NEAR
METER NEMA 3R
Signed 1/30/2024
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
MODULE:
REC SOLAR
REC405AA PURE BLACK
405 WATTS
40''
71.7''
SQUARE FOOTAGE OF ROOF: 1576.75 SQ. FT.
SQUARE FOOTAGE OF ARRAY: 378.42 SQ. FT.
PERCENTAGE OF ROOF COVERED BY THE ARRAYS: 24.00%
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
A-102.00
ELECTRICAL PLAN
N
E
W
S
03/16" = 1'-0"
ELECTRICAL PLAN012'-8"5'-4"
FIRE CLEARANCE
A MODULE STRINGING
B MODULE STRINGING
C MODULE STRINGING
(E) (1) UTILITY METER
EXTERIOR PV EQUIPMENT
(E) (1) MAIN ELECTRICAL PANEL
INTERIOR PV EQUIPMENT
A
(N) (1) CIRCUIT BREAKER DISCONNECT
ARRAY 1 - 5.670 KW
[x14] (N) MODULES
TILT: 38 DEGREES
ROOF PITCH: 9:12
AZIMUTH: 174 DEGREES
NOTE: CONDUIT WILL NOT BE PLACED
WITHIN FIRE SETBACKS AS PER NFPA 12021
(N) (1) SOLAR REC METER -
CUSTOMER OWNED
(N) (1) AC DISCONNECT
3 FT. FIRE ACCESS PATH
18 IN. FIRE ACCESS PATH
18 IN. FIRE ACCESS PATH
(N) (1) INVERTER
(N) (1) SOLADECK JUNCTION BOX
18 IN. FIRE ACCESS PATH
18 IN. FIRE ACCESS PATH
3 FT. FIRE ACCESS PATH
3 FT. FIRE ACCESS PATH
3 FT. FIRE ACCESS PATH
A A A A A A
B B B B B B B
C
C C C C
ARRAY 2 - 2.025 KW
[x5] (N) MODULES
TILT: 38 DEGREES
ROOF PITCH: 9:12
AZIMUTH: 173 DEGREES
TOTAL SYSTEM KWAC SIZE: 7.600 KWAC
SOLAR REC METER - CUSTOMER OWNED:
TOP LUGS TO SOLAR GENERATION (LOAD)
BOTTOM LUGS TO UTILITY (LINE) LOCATED
EXTERIOR
READILY ACCESSIBLE OPEN BLADE AC
SYSTEM DISCONNECT VISIBLE FROM
APPROACH TO RESIDENCE 60A 240V
LOCATED EXTERIOR ON WALL NEAR
METER NEMA 3R
Signed 1/30/2024
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
MODULE:
REC SOLAR
REC405AA PURE BLACK
405 WATTS
40''
71.7''
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
A-103.00
SOLAR ATTACHMENT PLAN
03/16" = 1'-0"
SOLAR ATTACHMENT PLAN012'-8"5'-4"
N
E
W
S
ROOF RAFTERS
FLUSH MOUNT SOLAR MODULES
ATTACHED TO ROOF SURFACE (SEE
SHEET S-502.00 FOR MOUNTING DETAILS)
ROOF MATERIAL IS ASPHALT SHINGLE
NOTE: CONDUIT WILL NOT BE PLACED
WITHIN FIRE SETBACKS AS PER NFPA 12021
23'-6"
13'-5"
FLUSH MOUNT SOLAR MODULES
ATTACHED TO ROOF SURFACE (SEE
SHEET S-501.00 FOR MOUNTING DETAILS)
ROOF MATERIAL IS ASPHALT SHINGLE
ROOF RAFTERS
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
Signed 1/30/2024
GENERAL NOTES
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
3.THE SOLAR PANELS ARE LESS THAN 4 FEET
MODULE:
REC SOLAR
REC405AA PURE BLACK
405 WATTS
40''
71.7''
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
A-104.00
STICKER MAP
03/16" = 1'-0"
STICKER MAP01 2'-8"5'-4"
N
E
W
S
ARRAY 1
ARRAY 2
ARRAY 1 - 5.670 KW
(N) MODULES 14
TILT:38 DEGREES
ROOF PITCH 9:12
AZIMUTH:174 DEGREES
ARRAY 2 - 2.025 KW
(N) MODULES 5
TILT:38 DEGREES
ROOF PITCH 9:12
AZIMUTH:173 DEGREES
Signed 1/30/2024
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
EQUIPMENT LEFT
OF LINE IS (N) NEW
UNLESS OTHERWISE NOTED.
EQUIPMENT RIGHT
OF LINE IS (E) EXISTING
UNLESS OTHERWISE NOTED.
L2
L1
NNN
TAP
PV SYSTEM EQUIPPED WITH RAPID
SHUTDOWN DISCONNECT PER NEC 690.12
SYSTEM COMPLIANT WITH NEC 690.13
A7
B7
C5
(N) (19) REC405AA PURE
BLACK
(N) (11) TESLA
SOLAR SHUTDOWN DEVICE
(N) SOLADECK
JUNCTION BOX
1 2
3
L2N
GG
L1
(N) (1) TESLA 7.6 KW
G
SW1
(N) (1) AC DISCONNECT
EATON DG222URB,
NON-FUSED,
2-POLE,60A, 240VAC
3 4
V
M1
(N) (1) SOLAR REC
METER - CUSTOMER
OWNED
READILY ACCESSIBLE
OPEN BLADE AC SYSTEM
DISCONNECT VISIBLE FROM
APPROACH TO RESIDENCE
60A 240V LOCATED
EXTERIOR ON WALL NEAR
METER NEMA 3R
NOTE: TOP LUGS TO SOLAR
GENERATION (LINE) BOTTOM
LUGS TO UTILITY (LOAD)
LOCATED EXTERIOR
TO UTILITY
GRID (OH)
L2
N
L1
(Е) MAIN ELECTRICAL PANEL
240/120 V 1Ø, 3W
MAIN BUSS: 125A
UTILITY
METER #:68668854
G
(N) (1) CIRCUIT
BREAKER
DISCONNECT
OCPD RATING: 40A
MLO BUSS: 125A
5
CB1
TOP LUGS
BOTTOM LUGS
(E)
UTILITY
METER
GN
TO (E)
LOADS
(E) MAIN
100A
(E) GROUNDING
ELECTRODE
GROUND
ROD
N
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING
CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR.
FACTOR
CONDUIT FILL
FACTOR
CONT.
CURRENT
MAX. CURRENT
(125%)BASE AMP.DERATED
AMP.TERM. TEMP. RATING AMP. @ TERMINAL
1 3 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.96 (32.7 °C)1 12.68A 15.84A 55A 52.8A 75°C 50A
21 10 AWG THWN-2, COPPER 0.75'' DIA EMT 6 N/A 10 AWG THWN-2, COPPER 0.96 (32.7 °C)0.8 12.68A 15.84A 40A 30.72A 75°C 35A
3 2 8 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 8 AWG THWN-2, COPPER 0.96 (32.7 °C)1 32A 40A 55A 52.8A 75°C 50A
41 8 AWG THWN-2, COPPER 0.75'' DIA EMT 2 40A 8 AWG THWN-2, COPPER 0.96 (32.7 °C)1 32A 40A 55A 52.8A 75°C 50A
5 1 6 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 6 AWG THWN-2, COPPER 0.96 (32.7 °C)1 32A 40A 75A 72A 75°C 65A
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS, MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
E-601.00
LINE DIAGRAM
A MODULE STRINGING
B MODULE STRINGING
C MODULE STRINGING
Signed 1/30/2024
SYSTEM SUMMARY
INVERTER #1
MPPT #1 MPPT #2 MPPT #3
MODULES IN SERIES 7 7 5
ARRAY VMP 296.8V 296.8V 212V
ARRAY IMP 9.56A 9.56A 9.56A
ARRAY VOC 342.3V 342.3V 244.5V
ARRAY MAX VOC 384V 384V 274.3V
ARRAY ISC 10.14A 10.14A 10.14A
ARRAY STC POWER 7,695W
ARRAY PTC POWER 7,332W
MAX AC CURRENT 32A
MAX AC POWER 7,600W
DERATED (CEC) AC POWER 7,149W
DISCONNECTS
INVERTERS
OCPDS
MODULES
ASHRAE EXTREME LOW -25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)
ASHRAE 2% HIGH 32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1 1 40A 240VAC
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 EATON DG222URB OR EQUIV.60A 240VAC
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-19 19 REC SOLAR REC405AA PURE BLACK 405W 385.9W 10.14A 9.56A 48.9V 42.4V -0.117V/°C (-0.24%/°C)25A
REF.QTY.MAKE AND MODEL AC
VOLTAGE GROUND OCPD
RATING
RATED
POWER
MAX OUTPUT
CURRENT
MAX INPUT
CURRENT
MAX INPUT
VOLTAGE
CEC WEIGHTED
EFFICIENCY
I1 1 TESLA 7.6 KW 240V FLOATING 40A 7600W 32A 4x11A 600V 97.5%
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE REC SOLAR REC405AA PURE BLACK PM1-19 19 PIECES 1 REC SOLAR REC405AA PURE BLACK 405W
INVERTER TESLA 7.6 KW I1 1 PIECE 1 TESLA 7.6 KW 7600W INVERTER
DISCONNECT EATON DG222URB SW1 1 PIECE 1 EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENT
PRODUCTION METER GENERIC MANUFACTURER GEN-METER-80A M1 1 PIECE 1 ELECTRICAL METER, OWNER APPROVED
WIRING GEN-10-AWG-PV-WIRE-CU WR1 270 FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE)
WIRING GEN-6-AWG-BARE-CU WR1 135 FEET 1 6 AWG BARE, COPPER (GROUND)
WIRING GEN-10-AWG-THWN-2-CU-RD WR2 60 FEET 1 10 AWG THWN-2, COPPER, RED (POSITIVE)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 60 FEET 1 10 AWG THWN-2, COPPER, BLACK (NEGATIVE)
WIRING GEN-10-AWG-THWN-2-CU-GR WR2 20 FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR3-4 20 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR3-4 20 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR3-4 20 FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-8-AWG-THWN-2-CU-GR WR3-4 20 FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-6-AWG-THWN-2-CU-RD WR5 10 FEET 1 6 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-6-AWG-THWN-2-CU-BLK WR5 10 FEET 1 6 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-6-AWG-THWN-2-CU-WH WR5 10 FEET 1 6 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-6-AWG-THWN-2-CU-GR WR5 10 FEET 1 6 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY GEN-EMT-0.75'' DIA WW2-5 50 FEET 1 EMT CONDUIT, 0.75'' DIA
OCPD GENERIC MANUFACTURER GEN-CB-40A-240VAC CB1 1 PIECE 1 CIRCUIT BREAKER, 40A, 240VAC
TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
E-602.00
DESIGN TABLES
Signed 1/30/2024
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
LABEL 1
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT (2" X 4").
[NEC 690.13].
POWER SOURCE
OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING
LABEL 2
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE (2" X 4").
[NEC 705.12(B)(2)(3)(B)].
LABEL 4
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS (5 3/4" X 1 1/8").
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
LABEL 5
AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").
[NEC 690.56(C)(3)].
LABEL 9
AT EACH AC DISCONNECTING MEANS
(4" X 1").
[NEC 690.13(B)].
LABEL 10
AT EACH DC DISCONNECTING MEANS
(4" X 1").
[NEC 690.13(B)].
SOLAR PV SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
TURN RAPID SHUTDOWN SWITCH TO
THE "OFF" POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE SHOCK
HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 3
AT RAPID SHUTDOWN SYSTEM
(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRICAL CODE,
INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED
BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE
YELLOW BACKGROUND. [ANSI Z535]
1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER
RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B)
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV
SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN
BATHROOMS
[NEC 690.4(D),(E)]
PHOTOVOLTAIC SOLAR
AC DISCONNECT
CAUTION
MULTIPLE SOURCES OF POWER
LABEL 6
AT UTILITY METER (5 3/4" X 1 1/8")
[NEC 690.56(B)]
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR
ELECTRIC SYSTEM
LABEL 7
AT POINT OF INTERCONNECTION
(2 3/4" X 1 5/8").
[NEC 705.12(B)(3)]
WARNING
SOLAR ELECTRIC
CIRCUIT BREAKER
IS BACKFED
LABEL 8
AT POINT OF
INTERCONNECTION
(2" X 1").
[NEC 705.12(B)(3)]
PHOTOVOLTAIC SOLAR
DC DISCONNECT
PHOTOVOLTAIC POWER SOURCE
LABEL 11
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS (4" X 2").
[NEC 690.54]
AC DISCONNECT
PHOTOVOLTAIC SYSTEM
POWER SOURCE
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
AMPS
VOLTS
LABEL 12
AT EACH DC DISCONNECTING
MEANS (3" X 4").
[NEC 690.53].
MAXIMUM VOLTAGE
MAX CIRCUIT CURRENT
VDC
AMPS
DIRECT CURRENT
PHOTOVOLTAIC POWER SOURCE
INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE HOUSE
32
240
10.14
384
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
E-603.00
PLACARDS
FRONT BACK
N
E
W
S
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
MAIN DISTRIBUTION
UTILITY DISCONNECT
(INSIDE)
UTILITY METER
MAIN ELECTRICAL
PANEL (INSIDE)
PV ARRAYS
PROUDLY INSTALLED BY VALLEY SOLAR 413-584-8844
SOLAR REC METER -
CUSTOMER OWNEDWATER STCIRCUIT BREAKER
DISCONNECT (INSIDE)
AC DISCONNECT
INVERTER (INSIDE)
Signed 1/30/2024
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
13
S-501
D4
54 8
252423
2
27
ROOF SLOPE910
10
6 21
7
20
12141315182211
S-501
D5
SHEET KEYNOTES
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: COLLAR TIE
3. ATTACHMENT TYPE: RAFTER
4. MODULE MANUFACTURER: IRONRIDGE FLASH VUE
5. MODULE MODEL: REC405AA PURE BLACK
6. MODULE LENGTH: 71.7''
7. MODULE WIDTH: 40''
8. MODULE WEIGHT: 45 LBS.
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 18" FROM RIDGE, AT LEAST 2 PATHWAY
TO A STREET OR DRIVEWAY MINIMUM 3' WIDE
11. RAFTER SPACING: 24 IN. O.C.
12. RAFTER SIZE: 2X4 IN. ROUGH SAWN
13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITH
RACKING.
14.LAG BOLT EMBEDMENT: 2.5 IN.
15. TOTAL # OF ATTACHMENTS: 13.
16. TOTAL AREA: 99.59 SQ. FT.
17. TOTAL WEIGHT: 267.76 LBS.
18. WEIGHT PER ATTACHMENT: 20.6 LBS.
19. DISTRIBUTED LOAD: 2.69 PSF
20. MAX. HORIZONTAL STANDOFF: 48 IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH
MODULE MANUFACTURER'S INSTRUCTIONS.
22. STANDOFF STAGGERING: YES
23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE
24. RAIL MODEL (OR EQUIVALENT): AIRE A2
25. RAIL WEIGHT: 0.68 PLF
26. MAX. SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS, MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
S-501.00
ASSEMBLY DETAILS
D4 DETAIL (TRANSVERSE)
NOT TO SCALE D5 DETAIL (LONGITUDINAL)
NOT TO SCALE
D1 RACKING DETAIL (TRANSVERSE)
NOT TO SCALE
D3 RACKING DETAIL (TOP)
NOT TO SCALE
D2 RACKING DETAIL (LONGITUDINAL)
NOT TO SCALE
Signed 1/30/2024
13
S-502
D4
54 8
252423
2
27
ROOF SLOPE910
10
6 21
7
20
S-502
D5
12141315182211
S-501
D5
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
3. THE SOLAR PANELS ARE LESS THAN 4 FEET
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: SINGLE SPAN RAFTER
3. ATTACHMENT TYPE: RAFTER
4. MODULE MANUFACTURER: IRONRIDGE FLASH VUE
5. MODULE MODEL: REC405AA PURE BLACK
6. MODULE LENGTH: 71.7''
7. MODULE WIDTH: 40''
8. MODULE WEIGHT: 45 LBS.
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 18" FROM RIDGE, AT LEAST 2 PATHWAY
TO A STREET OR DRIVEWAY MINIMUM 3' WIDE
11. RAFTER SPACING: 25 IN. O.C.
12. RAFTER SIZE: 2X4 IN. ROUGH SAWN
13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIED WITH
RACKING.
14.LAG BOLT EMBEDMENT: 2.5 IN.
15. TOTAL # OF ATTACHMENTS: 44.
16. TOTAL AREA: 278.83 SQ. FT.
17. TOTAL WEIGHT: 739.67 LBS.
18. WEIGHT PER ATTACHMENT: 16.81 LBS.
19. DISTRIBUTED LOAD: 2.65 PSF
20. MAX. HORIZONTAL STANDOFF: 25 IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH
MODULE MANUFACTURER'S INSTRUCTIONS.
22. STANDOFF STAGGERING: NO
23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE
24. RAIL MODEL (OR EQUIVALENT): AIRE A2
25. RAIL WEIGHT: 0.68 PLF
26. MAX. SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
SHEET KEYNOTES
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS, MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
D4 DETAIL (TRANSVERSE)
NOT TO SCALE D5 DETAIL (LONGITUDINAL)
NOT TO SCALE
D1 RACKING DETAIL (TRANSVERSE)
NOT TO SCALE
D3 RACKING DETAIL (TOP)
NOT TO SCALE
D2 RACKING DETAIL (LONGITUDINAL)
NOT TO SCALE
S-502.00
ASSEMBLY DETAILS
NOTE: ALL RAFTERS UNDER ARRAY 1 WILL NEED
TO BE SISTERED WITH 2X6 RAFTERS
Signed 1/30/2024
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
R-001.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
R-002.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
R-003.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
R-004.00
RESOURCE DOCUMENT
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
ENGINEER OF RECORD
O.Z.DESIGN BY:
01.12.2024
M.M.
ELIZABETH
KILDUFF
RESIDENCE
50 WATER ST,
LEEDS,MA 01053
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VALLEY SOLAR LLC
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
413-584-8844
116 PLEASANT ST SUITE 321,
EASTHAMPTON, MA 01027
ADRESS:
APN: 10B-078-001
186338
664A1
NEW PV SYSTEM: 7.695 kWp
R-005.00
RESOURCE DOCUMENT