24A-242 (2) BP-2023-1790
21 TERRACE LN COMMONWEALTH OF MASSACHUSETTS
Map:Block:Lot:
24A-242-001 CITY OF NORTHAMPTON
Permit: Solid Fuel
Appliance
PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
BUILDING PERMIT
Permit# BP-2023-1790 PERMISSION IS HEREBY GRANTED TO:
Project# PELLET STOVE 2023 Contractor: License:
Est. Cost: DOUGLAS L'ABBEE CSL99401
Const.Class: Exp.Date:01/06/2024
Use Group: Owner: KELLY ST MARTIN DEVON &
Lot Size (sq.ft.)
Zoning: URB Applicant: THE FIRE PLACE
Applicant Address Phone: Insurance:
100 STATE RD (413)397-3463 6) IOOSo 30))7 6
WHATLEY, MA 01093
ISSUED ON: 12/26/2023
TO PERFORM THE FOLLOWING WORK:
PELLET STOVE
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter: Footings:
Rough: Rough: House# Foundation:
Final: Final: Final: Rough Frame:
Gas: Fire Department Driveway Final: Fireplace/Chimney:
Rough: Oil: Insulation:
Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Signature:
` � ► IM
Il
Fees Paid: $40.00
212 Main Street,Phone(413)587-1240,Fax: (413)587-1272
Office of the Building Commissioner
/ /9N \N 7.f e-rn al/
O C1 tr of Northampton
r"H ti m:.sr
?:Y f" Fc �, Massachusetts Hwy * '4,e�
l g .,0 ��PART2 N'1' O BUILDING INSPECTIONS yS , �1
r is ;;L \'S' G%i Mai Street • Municipal Building •vo a+
�\\ r.r ��;1^ f North npton, MA 01060 dSr ''r").
N)6 oON N /
S
/
APPLICATION FOR:SOLID FUEL APPLIANCE INSTALLATION
Property Information
Owners Name: - errn 5 I m iS f o
Address: Zi /car,act Ian(
(No.) (Street Address)
Phone: "/./•5Yp• 13ZP Cell: Email: ,/sitn►•,irn e /-121�r.cicM
•
Owners Signature: ` Date: iot13/ 4
Contractor's Information (IfApplicable)
Name: )o fei L ake - i(c Lr_i?/,tc.<_ Phone: //3 //V 516'S
Construction Supervisor's License #: e5-51- '7? '/ Expiration: 7- 21
Home Impr, Contractor License #: /PGY77 Expiration: /( /7._it
Stove Information
Type of Fuel (check all that apply): Wood Pellet i - Coal
Location: i . _ 6ejenV11.71- Freestanding ' Insert
Manufacturer: /-�fi n Model: `75/3-C. e r/e i 5101"
,'/75,1er/ie, .✓r/-c4 /cr\71- ?(lC7 eArrnn1 - S��l he&a-0)
r FOR BUILDING DEPARTMENT USE ONLY
Permit# t'i , "/7 l Q Date Applied: • Total all Fees: $ 110 ( 1'13 76
Building Official: Date Issued: 1 /1,P,C./9-.3
(P .00) i I
1 4 I
Signature of Building Official: EN: ' % • 4 .' 1
p� The Commonwealth of Massachusetts
i Department of Industrial Accidents
Pli);: ��r Office of Investigations
:� �s Lafayette City Center
-~ � rr 2 Avenue de Lafayette, Boston, MA 02111-1750
c'-'-,- www.mu , ov/dia
v ss.g
Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers
Applicant Information Please Print Legibly
Name (Business/Organization/Individual): THE FIRE PLACE
Address:100 STATE ROAD
City/State/Zip:WHATELY, MA 01093 Phone #:413.397.3463
Are you an employer? Check the appropriate box: Type of project(required):
1.I I am a employer with 10 4. ❑ I am a general contractor and I 6. ❑New construction
employees (full and/or part-time).* have hired the sub-contractors
listed on the attached sheet, 7. ElRemodeling
2,El I am a sole proprietor or partner_
ship and have no employees These sub-contractors have 8. 0 Demolition
working for me in any capacity, employees and have workers' 9. ❑ Building addition
[No workers' comp. insurance comp. insurance,
required.] 5. ❑ We are a corporation and its 10.❑ Electrical repairs or additions
officers have exercised their 11.❑ Plumbing repairs or additions
3,❑ I am a homeowner doing all work
myself. [No workers' comp. right of exemption per MGL
y t c. 152, §1(4),and we have no 12.❑ Roof repairs
insurance required.] 13.❑ Other
employees. [No workers'
comp. insurance required.]
*Any applicant that checks box#1 must also fill out the section below showing their workers'compensation policy information.
i Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such.
;Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have
employees. If the sub-contractors have employees,they must provide their workers'comp.policy number.
I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site
information.
Insurance Company Name: MA RETAIL MERCHANTS WC GROUP INC
Policy#or Self-ins. Lic. #:0140000503301116 Expiration Date:1-1-24
' Job Site Address: ,c,7/ /etric.c Gsnc City/State/Zip: /VortAervofon Ad woe()
Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a
fine up to $1,500,00 and/or one-year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage verification.
I do hereby certify and the pains and p nalties of perjury that the information provided above is true and correct.
Signature: ',A1 44( /'"/P�3
Date:
Phone#; 413.397.3463
Official use only. Do not write in this area, to be completed by city or town official.
City or Town: Permit/License #
Issuing Authority (check one):
11:Board of Health 20 Building Department 3.0City/Town Clerk 4.0 Electrical Inspector 50'lumbing
Inspector 6.❑Other
Contact Person: Phone#:
3 Clearances
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only.
P43-C Freestanding Pellet Stove P61-C Freestanding Pellet Stove
nIndO �Air ln4ks II
•
M1I ( M /I III `a�4�.,_.,,, •la f tim
. . ....,
_........
5 1/8" 5 1/8"
22" 23 1/2" 0
s s 0 0 s 0
CO 00
M
N O•
N
I r -. . -I
8 L ____1
20 3/4" I 1 r If
P68-C Freestanding Pellet Stove
111
Outside
Airintake N
El ��•��``
e0._ /, � I III
M
-i ----
5 1/4"
23-1/2" / 0
s
t vvvvvvv�� 'v
���
0
m
M
CO3
r v
- - -
I 1
6
' NAMMIIMIF
I I I
Figure 3.1
8 Harman® • P-Series Installation Manual_R4 • 2018-_ • 04/21 8390-0441
B. Clearances to Combustibles Place the stove away from combustible walls at least as far
When selecting a location for the appliance it is important to as shown in Figure 3.2. Please note the difference in side
consider the required clearances to walls, Figure 3.2. wall clearance with and without side shields.
Note that the clearances shown are minimum for safety but do
A WARNING not leave much room for access when cleaning or servicing.
Please take this into account when placing the stove.
RISK OF FIRE OR BURNS! Provide adequate Due to high temperatures, the stove should be placed out of
clearance around air openings and for service traffic and away from furniture and draperies.
access. Due to high temperatures, the appliance should Children and adults should be alerted to the hazards of high
be located out of traffic and away from furniture and surface temperatures and should stay away to avoid burns
draperies. to skin and/or clothing.
Young children should be carefully supervised when they are
ACAUTION in the same room as the stove.
Clothing and other flammable materials should not be placed
THIS APPLIANCE MUST BE VENTED TO THE OUTSIDE. on or near this unit.
NOTICE:Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.Actual installation may vary due
to individual design preference.
P61-C & P68-C Freestanding Pellet Stove P43-C Freestanding Pellet Stove
1 y
2"(51 mm) 2"(51 mm)
14"(355mm)with , "10"(254mm)with '_` ,
side shields / side shields /-� '
20"(508mm) *16"(406mm)
without side shields LimmaJolimumro 14"(355mm) without side shields L ° J
"10"(254mm)
20"(508mm) *16"(406mm)
idj-
•
36"(914mm) 36"(914mm)
9"(228mm)- --1‘411119"(228mm)
13"(330mm)
j I
*\,. Nh.
-Co' CO
wnNi 3
ww S
9"(228mm)With Side Shields 3
13"(330mm) Without Side Shields 3 9"(228mm) With or Without Side Shields
Figure 3.2
9 Harman® • P-Series Installation Manual_R4 • 2018- • 04/21 8390-0441
C. Floor Protection Corner Installation:
Parallel Installation: Minimum size floor protection for a corner installation hearth
pad is:
Place the stove on a noncombustible type floor or floor P43-C - Minimum size floor protection is 25-7/16" Wide by
protector that extends a minimum of 6 inches (152mm) to 26-3/4" Deep (646mm X 680mm).
the front of the load door opening, 6 inches (152mm)to the
sides of the door opening, and 6 inches to the rear. P61-C - Minimum size floor protection is 25-1/8" Wide by
The P-Series does not require R value floor protection. 27-3/4" Deep (638mm X 705mm).
The minimum floor protector material is 20 gauge sheet metal. P68-C - Minimum size floor protection is 25-3/16" Wide by
Other floor protector materials that can be used include Type 27-3/4" Deep (640mm X 705mm).
I hearth pads, ceramic tile, stone, brick, etc. Figure 3.3 Note: Floor protector WILL NOT touch the wall using
`Floor protection dimensions for the front and sides are minimum clearances.
measured from the appliance door opening in The United If corner floor protection is desired to touch the wall, the
States. In Canada,the side dimension is measured from the floor protection will need to be at least 40" x 40" (1016mm
widest part of the appliance. x 1016mm). Note: This will allow the floor protection to
P43-C - Minimum size rectangular floor protection is 25- touch the wall as shown. Figure 3.4.
7/16"Wide by 26-3/4" Deep (646mm X 680mm). Alternate floor protector dimension may be used as long as
P61-C-Minimum size rectangular floor protection is 25-1/8" they satisfy the measurement requirements shown below.
Wide by 27-3/4" Deep (638mm X 705mm).
P68-C - Minimum size rectangular floor protection is 25-
3/16"Wide by 27-3/4" Deep (640mm X 705mm).
Venting:
lj-Follow PL vent manufacturers recommendations when
configuring vent pipe installation.
Canada- Must extend 2" (51mm) beyond each side of any
horizontal flue pipe. O
O
L
0
Figure 3.4
D. Mobile Home Installation
When installing this unit in a mobile home, several
requirements must be followed:
J Floor Protector 1. The unit must be bolted to the floor. This can be done
K using an appropriate fastener for the application.
Figure 3.3 2. The unit must also be connected to outside air. See
"Termination Location and Vent Information"Section D.
Floor Protection US Canada 3. Floor protection and clearances must be followed as
Requirements shown.
J Sides 6" 152mm 4. The appliance must be properly grounded to the frame of
K Front 6" 152mm the mobile home using a minimum of 8AWG copper solid
L Rear 6" 152mm or stranded, insulated or bare wire or equivalent.
10 Harman® • P-Series Installation Manual_R4 • 2018-_ • 04/21 8390-0441
. . .
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances Note: Follow venting manufacturer's recommendations for
sealing pipe joints.
#1 Preferred method (Figure 4.1)
This method provides excellent venting for normal operation
and allows the stove to be installed closest to the wall. Two
inches from the wall is safe; however, four inches allows
better access to remove the rear panel.The vertical portion of
the vent should be three to five feet high.This vertical section
will help provide natural draft in the event of a power failure.
Do not place joints within wall pass-through.
#11W
3
1,04/
to
CombustFt.ibles
liii
/71:0:10
'I�rl�■i■111111111
3 Ft.
to Combustibles
Figure 4.1
#2 Preferred method (Figure 4.2)
This method also provides excellent venting for normal
operation but requires the stove to be installed farther from
the wall. The vertical portion of the vent should be three to
five feet high and at least 1" from a combustible wall. This
vertical section will provide natural draft in the event of a
I power failure.
If the stove is installed below grade be sure the vent
termination is at least 12"above grade. The outlet must also
be 1 foot from the house/building.
3tot' Do not place joints within wall pass-through.
Combustibles
A CAUTION
511
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the flue outlet on the
/ outside of the building.
�
HI3 Ft.
to Combustibles
Figure 4.2
11 Harman® • P-Series Installation Manual_R4 • 2018- • 04/21 8390-0441