Hall, Adam Plansedt 76 North Meadowbrook Drive Scott E. Wyssling, PE Alpine, UT 84004 Coleman D. Larsen, SE, PE office (201) 874-3483 Gregory T. Elvestad, PE swyssling@wysslingconsulting.com April 25, 2023 Current Insight 2852 W. Amini Way South Jordan, UT 84095 Re: Engineering Services Hall Residence 107 Whittier Street, Northampton, MA 8.800 kW System To Whom It May Concern: We have received information regarding solar panel installation on the roof of the above referenced structure. Our evaluation of the structure is to verify the existing capacity of the roof system and its ability to support the additional loads imposed by the proposed solar system. A. Site Assessment Information 1. Site visit documentation identifying attic information including size and spacing of framing for the existing roof structure. 2. Design drawings of the proposed s ystem including a site plan, roof plan and connection details for the solar panels. This information will be utilized for approval and construction of the proposed system. B. Description of Structure: Roof Framing: 16” TJIs at 24” on center. Roof Material: Metal Roofing Roof Slope: 07 degrees Attic Access: Accessible Foundation: Permanent C. Loading Criteria Used • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 PSF • Dead Load o Existing Roofing and framing = 7 psf o New Solar Panels and Racking = 3 psf o TOTAL = 10 psf • Live Load = 20 psf (reducible) – 0 psf at locations of solar panels • Ground Snow Load = 40 psf • Wind Load based on ASCE 7-10 o Ultimate Wind Speed = 117 mph (based on Risk Category II) o Exposure Category C Analysis performed of the existing roof structure utilizing the above loading criteria is in accordance with the 2015 IRC, including provisions allowing existing structures to not require strengthening if the new loads do not exceed existing design loads by 105% for gravity elements and 110% for seismic elements. This analysis indicates that the existing framing will support the additional panel loading without damage, if installed correctly. Page 2 of 2 D. Solar Panel Anchorage 1. The solar panels shall be mounted in accordance with the most recent S -5! Installation manual. If during solar panel installation, the roof framing members appear unstable or deflect non-uniformly, our office should be notified before proceeding with the installation. 2. System will be attached to the metal roofing material utilizing the patented S -5! Connection. Installation of the connections shall be in accordance with the manufacturer’s recommendations. 3. Considering the wind speed, roof slopes, size and spacing of framing members, and condition of the roof, the panel supports shall be placed no greater than 48” on center. Based on the above evaluation, this office certifies that with the racking and mounting specified, the existing roof system will adequately support the additional loading imposed by the solar system. This evaluation is in conformance with the 2015 IRC, current industry standards, and is based on information supplied to us at the time of this report. Should you have any questions regarding the above or if you require further information do not hesitate to contact me. Very truly yours, Scott E. Wyssling, PE MA License No. 50507 Massachusetts COA # 1629764 GENERAL NOTES1.1.1PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRICCODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATIONINSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVINGJURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEMINSPECTED PRIOR TO PARALLEL OPERATION1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED WITHTHE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B)1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, ANDSOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE INPHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENTFOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7.1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCECIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BEIDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLEDACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3].1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IFEXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILLBE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THEGRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BERESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THEPHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.*NEC2020M1.3.1 WORK INCLUDES:1.3.2 PV ROOF ATTACHMENTS - S!5 PROTEA BRACKET1.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE AIRE A1 RAIL1.3.4 PV MODULE AND INVERTER INSTALLATION - REC REC400NP3 BLACK / ENPHASEIQ8PLUS-72-2-US1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED SOLADECK JUNCTION BOX1.3.7 PV INSTALLING SYSTEM MONITORING EQUIPMENT1.3.8 PV LOAD CENTERS (IF INCLUDED)1.3.9 PV METERING (IF INCLUDED)1.3.10 PV DISCONNECTS1.3.11 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.12 PV FINAL COMMISSIONING1.3.13 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PVOWNERNAME:ADAM HALLAUTHORITIES HAVING JURISDICTIONBUILDING: TOWN OF NORTHAMPTONZONING: TOWN OF NORTHAMPTONUTILITY: NATIONAL GRIDDESIGN SPECIFICATIONSOCCUPANCY: ІІCONSTRUCTION: SINGLE-FAMILYZONING:RESIDENTIALGROUND SNOW LOAD: 40 PSFWIND EXPOSURE: CWIND SPEED: 117 MPHUTILITY METER #39698531APPLICABLE CODES & STANDARDSBUILDING: MASSACHUSETTS BUILDING CODE, 9THEDITION, AS AMENDED (780 CMR)RESIDENTIAL: MASSACHUSETTS RESIDENTIONAL BUILDINGCODE, 9TH EDITION, AS AMENDED (780 CMR)ELECTRICAL: NEC 2023FIRE:MASSACHUSETTS COMPREHENSIVE FIRESAFETY CODE (527 CMR 1.00)NFPA 1 FIRE CODE - 2021 (SETBACKS)PROJECT INFORMATIONPROJECT MANAGERNAME: PHONE: CONTRACTORNAME: PHONE: PATRICK RONDEAU413-588-8185VALLEY SOLAR LLC413-584-8844BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338T-001.00COVER PAGE(SHEET 1)01AERIAL PHOTONOT TO SCALENEWS02PLAT MAPNOT TO SCALESHEET LIST TABLESHEET NUMBERSHEET TITLET-001COVER PAGEG-001NOTESA-101SITE PLANA-102ELECTRICAL PLANA-103SOLAR ATTACHMENT PLANА-104INSTALLER REFERENCE PAGEE-601LINE DIAGRAME-602DESIGN TABLESE-603PLACARDSS-501ASSEMBLY DETAILSR-001RESOURCE DOCUMENTR-002RESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004RESOURCE DOCUMENTR-005RESOURCE DOCUMENTR-006RESOURCE DOCUMENTWHITTIER STNEW PV SYSTEM: 8.800 kWpHALL RESIDENCE107 WHITTIER STNORTHAMPTON, MA 01062ASSESSOR'S #: 43 -110-001SCOPE OF WORKSYSTEM SIZE:ATTACHMENT TYPE:MSP UPGRADE:STC: 22 X 400W = 8.800KWPTC: 22 X 379.2W = 8.342KW(22) REC REC400NP3 BLACK(22) ENPHASE IQ8PLUS-72-2-USS!5 PROTEA BRACKETNOSigned 4/25/2023 1.1.11.1.21.1.31.1.41.1.51.1.61.1.71.1.81.2.1 1.2.22.1.1SITE NOTES:2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITYINTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDINGROOF VENTS.2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICALEQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITHTHIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOFCOVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1EQUIPMENT LOCATIONS:2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATINGTEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC690.34.2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHINSIGHT OF THE AC SERVICING DISCONNECT.2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TONEC APPLICABLE CODES.2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHENAPPROPRIATE.2.3.1STRUCTURAL NOTES:2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANTINSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THEARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IFROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVEDCHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCESPECIFIED BY THE RACKING MANUFACTURER.2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGSTTHE ROOF FRAMING MEMBERS.2.4.1WIRING & CONDUIT NOTES:2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT ANDWIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANTTO LIMIT UP-SIZING.2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.4.4 VOLTAGE DROP LIMITED TO 1.5%.2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS SHALL BELOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS.2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAYIN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKEDORANGE [NEC 110.15].2.5.1GROUNDING NOTES:2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDINGDEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE250.122.2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDEREDGROUNDED IN ACCORD WITH 250.134 AND 250.136(A).2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45 ANDMICROINVERTER MANUFACTURERS' INSTRUCTIONS.2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN INMANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLESPER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVALOF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN ORMARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODESYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) THROUGH (3) TO REDUCEFIRE HAZARDS2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THECONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINESIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE AVISIBLE-BREAK SWITCH2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWNFUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH690.12(A) THROUGH (D).2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES INACCORDANCE WITH NEC 110.3(B).2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TONEC 690.11 AND UL1699B.2.7.1INTERCONNECTION NOTES:2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH NEC 705.122.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THERATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BELOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALLOVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THECOMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)2.7.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCECONDUCTORS IN ACCORDANCE WITH NEC 230.422.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROMADDITIONAL FASTENING [NEC 705.12 (E)].*NEC2020M *NEC2020M 1.3.5 PV EQUIPMENT GROUNDING1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED 1.3.7 PV INSTALLING SYSTEM MONITORING EQUIPMENT1.3.8 PV LOAD CENTERS (IF INCLUDED)1.3.9 PV METERING (IF INCLUDED)1.3.10 PV DISCONNECTS1.3.11 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.12 PV FINAL COMMISSIONING1.3.13 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PVBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338G-001.00NOTES(SHEET 2)Signed 4/25/2023 A-101.00SITE PLAN(SHEET 3)ENTRANCEBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-884418633801/48" = 1'-0"SITE PLAN0124' 48'NEWSNEWSAREA OF WORKPROPERTY LINEGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEAC DISCONNECTUTILITY METERWHITT IER STNOTE: READILY ACCESSIBLE OPEN BLADE ACSYSTEM DISCONNECT VISIBLE FROM APPROACHTO RESIDENCE 60A 240V LOCATED EXTERIOR ONWALL NEAR METER NEMA 3RAC COMBINER BOX269'-2"70'-0"63'-3"48'-4"Signed 4/25/2023 MODULE:RECREC400NP3 BLACK400 WATTS40.9"74.8"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338A-102.00ELECTRICAL PLAN(SHEET 4)03/32" = 1'-0"ELECTRICAL PLAN015'-4" 10'-8" N E W S AMODULE STRINGINGBMODULE STRINGINGGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGE(N) (1) AC DISCONNECTINTERIOR PV EQUIPMENT(N) (1) AC COMBINER BOX(E) (1) MAIN ELECTRICAL PANEL(N) (1) SOLADECKJUNCTION BOXARRAY 1 - 1.600 KW[x4] (N) MODULESTILT: 7 DEGREESROOF PITCH: 1:12AZIMUTH: 155 DEGREESFIRE CLEARANCENOTE: READILY ACCESSIBLE OPEN BLADE ACSYSTEM DISCONNECT VISIBLE FROM APPROACHTO RESIDENCE 60A 240V LOCATED EXTERIOR ONWALL NEAR METER NEMA 3REXTERIOR PV EQUIPMENTAAAAAAВAВВAВВAВВAВВAВВ3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATH3 FT. FIRE ACCESS PATHARRAY 2 - 7.200 KW[x18] (N) MODULESTILT: 7 DEGREESROOF PITCH: 1:12AZIMUTH: 245 DEGREES(E) (1) UTILITY METERNOTE: PERCENTAGE OF MODULES COVERINGROOF : 22.25% MODULE:RECREC400NP3 BLACK400 WATTS40.9"74.8"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338A-103.00SOLAR ATTACHMENT PLAN(SHEET 5)03/32" = 1'-0"SOLAR ATTACHMENT PLAN015'-4" 10'-8" N E W S METAL SEAMSGENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEFLUSH MOUNT SOLAR MODULESATTACHED TO ROOF SURFACE (SEESHEET S-501 FOR MOUNTING DETAILS)ROOF MATERIAL IS STANDING SEAM METAL20'-7"13'-8"Signed 4/25/2023 MODULE:RECREC400NP3 BLACK400 WATTS40.9"74.8"BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338А-104.00INSTALLER REFERENCEPAGE(SHEET 6)03/32" = 1'-0"INSTALLER REFERENCE PAGE015'-4" 10'-8" N E W S GENERAL NOTES1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGESigned 4/25/2023 PV SYSTEM EQUIPPED WITH RAPIDSHUTDOWN DISCONNECT PER NEC 690.12SYSTEM COMPLIANT WITH NEC 690.13EQUIPMENT LEFTOF LINE IS (N) NEWUNLESS OTHERWISE NOTED.EQUIPMENT RIGHTOF LINE IS (E) EXISTINGUNLESS OTHERWISE NOTED.(N) AC COMBINER BOX, 125AENPHASE IQ COMBINER 4(X-IQ-AM1-240-4)120/240V, 1Ø, 3WMAX. CONTINUOUS CURRENT: 65AMAX. OCPD: 90AL1N L2ENPHASE ENVOYCOMMUNICATIONSGATEWAYGCB315ACB120ACB220A2(E) GROUNDINGELECTRODEGROUNDRODTO UTILITYGRID (UG)L1L2N3L2L1NL2L1N(N)35A/2PCB4GSW1(N) AC DISCONNECT, 60ABLACKREDGBLACKREDIN BRANCHIN BRANCH1(N) (22) RECREC400NP3 BLACK400 WATTS(N) (22) ENPHASEIQ8PLUS-72-2-USRATED POWER: 290W(N) SOLADECKJUNCTION BOXA11B11NOTE: READILY ACCESSIBLE OPEN BLADE ACSYSTEM DISCONNECT VISIBLE FROM APPROACHTO RESIDENCE 60A 240V LOCATED EXTERIOR ONWALL NEAR METER NEMA 3R(E)UTILITYMETERGNTO (E)LOADS(E) MAIN200A(Е) MAIN ELECTRICAL PANEL240/120 V 1Ø, 3WMAIN BUSS: 200AMAX BREAKER SIZE:(200A X 1.2) - 200A = 40AUTILITY METER # 39698531CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONSID TYPICALCONDUCTORCONDUITCURRENT-CARRYINGCONDUCTORS IN CONDUITOCPDEGCTEMP. CORR.FACTORCONDUIT FILLFACTORCONT.CURRENTMAX. CURRENT(125%)BASE AMP.DERATEDAMP.TERM. TEMP. RATINGAMP. @ TERMINAL1 110 AWG THWN-2, COPPER0.75'' DIA EMT220A10 AWG THWN-2, COPPER0.96 (32.7 °C)113.31A 16.64A40A38.4A75°C35A2 18 AWG THWN-2, COPPER0.75'' DIA EMT2N/A8 AWG THWN-2, COPPER0.96 (32.7 °C)126.62A 33.28A55A52.8A75°C50A3 16 AWG THWN-2, COPPER0.75'' DIA EMT235A6 AWG THWN-2, COPPER0.96 (32.7 °C)126.62A 33.28A75A72A75°C65ABFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-601.00LINE DIAGRAM(SHEET 7)MODULE STRINGINGMODULE STRINGINGAB SYSTEM SUMMARYBRANCH #1BRANCH #2INVERTERS PER BRANCH1111MAX AC CURRENT13.31A13.31AMAX AC OUTPUT POWER3,190W3,190WARRAY STC POWER8,800WARRAY PTC POWER8,342WMAX AC CURRENT26.620AMAX AC POWER6,380WDERATED (CEC) AC POWER6,380WDISCONNECTSINVERTERSOCPDSMODULESASHRAE EXTREME LOW-25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°)ASHRAE 2% HIGH32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)REF.QTY.RATED CURRENTMAX VOLTAGECB1 120A240VACCB2 115A240VACCB3 135A240VACREF.QTY.MAKE AND MODELRATED CURRENT MAX RATED VOLTAGESW1 1EATON DG222URB OR EQUIV.60A240VACREF.QTY.MAKE AND MODELPMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATINGPM1-22 22REC REC400NP3 BLACK400W 379.2W 11.39A 10.64A 45V 37.6V-0.117V/°C (-0.26%/°C)25AREF.QTY.MAKE AND MODELACVOLTAGEGROUNDOCPDRATINGRATEDPOWERMAX OUTPUTCURRENTMAX INPUTCURRENTMAX INPUTVOLTAGECEC WEIGHTEDEFFICIENCYI1-22 22ENPHASE IQ8PLUS-72-2-US240VFLOATING20A 290W1.21A15A 60V97.0%BILL OF MATERIALSCATEGORYMAKEMODEL NUMBERREFQTYUNITQTY/UNITDESCRIPTIONMODULERECREC400NP3 BLACKPM1-22 22 PIECES 1REC REC400NP3 BLACK 400W 144 HALF-CELLS, MONOCRYSTALLINE SILICONINVERTERENPHASEIQ8PLUS-72-2-USI1-2222 PIECES 1ENPHASE IQ8PLUS-72-2-US 290W INVERTERDISCONNECTEATONDG222URBSW11 PIECE 1EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENTMISC ELECTRICAL EQUIPMENTGEN-CABLE-CLIPHDWR25-135 110PIECES 1 GENERIC CABLE CLIPAC COMBINER PANELENPHASE-IQ4-PANELEP11 PIECE 1ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4)WIRINGENPHASEQ-12-20-200EN1-22 22PIECES1ENPHASE ENGAGE (TM) TRUNK CABLEWIRINGENPHASEQ-TERM-10EN231BUNDLE 10ENPHASE ENGAGE (TM) BRANCH TERMINATORWIRINGENPHASEQ-SEAL-10EN241BUNDLE 10ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAPWIRINGGEN-10-AWG-THWN-2-CU-RDWR145FEET 110 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-10-AWG-THWN-2-CU-BLKWR145FEET 110 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-10-AWG-THWN-2-CU-GRWR145 FEET110 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-8-AWG-THWN-2-CU-RDWR210FEET 18 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-8-AWG-THWN-2-CU-BLKWR210FEET 18 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-8-AWG-THWN-2-CU-WHWR210 FEET 18 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-8-AWG-THWN-2-CU-GRWR210FEET 18 AWG THWN-2, COPPER, GREEN (GROUND)WIRINGGEN-6-AWG-THWN-2-CU-RDWR310 FEET16 AWG THWN-2, COPPER, RED (LINE 1)WIRINGGEN-6-AWG-THWN-2-CU-BLKWR310FEET 16 AWG THWN-2, COPPER, BLACK (LINE 2)WIRINGGEN-6-AWG-THWN-2-CU-WHWR310FEET 16 AWG THWN-2, COPPER, WHITE (NEUTRAL)WIRINGGEN-6-AWG-THWN-2-CU-GRWR310 FEET16 AWG THWN-2, COPPER, GREEN (GROUND)WIREWAYENPHASEET-SPLK-05EN41BUNDLE 5ENPHASE ENGAGE (TM) ENGAGE COUPLERWIREWAYGEN-EMT-0.75'' DIAWW1-3 65FEET 1EMT CONDUIT, 0.75'' DIAOCPDGENERIC MANUFACTURERGEN-CB-20A-240VACCB11 PIECE 1CIRCUIT BREAKER, 20A, 240VACOCPDGENERIC MANUFACTURERGEN-CB-15A-240VACCB21 PIECE 1CIRCUIT BREAKER, 15A, 240VACOCPDGENERIC MANUFACTURERGEN-CB-35A-240VACCB31PIECE1CIRCUIT BREAKER, 35A, 240VACTRANSITION BOXGENERIC MANUFACTURERGEN-AWB-TB-4-4XJB11 PIECE 1TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKSBFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3 UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-602.00DESIGN TABLES(SHEET 8) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338E-603.00PLACARDS(SHEET 9)NEWS!CAUTION!POWER TO THIS BUILDING IS ALSO SUPPLIEDFROM ROOF MOUNTED SOLAR ARRAYS WITHSAFETY DISCONNECTS AS SHOWN:MAIN DISTRIBUTIONUTILITY DISCONNECTFRONTBACKLABELING NOTES1.1 LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRICAL CODE,INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z5351.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVINGJURISDICTION.1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENTINVOLVED.1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE REDBACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVEYELLOW BACKGROUND. [ANSI Z535]ELECTRICAL SHOCK HAZARDTERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZEDIN THE OPEN POSITIONWARNINGLABEL 1AT EACH DISCONNECTING MEANS FORPHOTOVOLTAIC EQUIPMENT (2" X 4").[NEC 690.13].POWER SOURCEOUTPUT CONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICEWARNINGLABEL 2AT POINT OF INTERCONNECTIONOVERCURRENT DEVICE (2" X 4").[NEC 705.12(B)(2)(3)(B)].LABEL 3AT POINT OF INTERCONNECTION, MARKEDAT DISCONNECTING MEANS (4" X 3").[NEC 690.54]LABEL 4AT EACH AC DISCONNECTING MEANS(4" X 1").[NEC 690.13(B)].DIRECTORYPERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICEDISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTINGMEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").[NEC 690.56(B)]WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, ADIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PVSYSTEM DISCONNECTING MEANS.PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED INBATHROOMS[NEC 690.4(D),(E)]PHOTOVOLTAIC POWER SOURCELABEL 9AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRINGMETHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERESEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,OR FLOORS (5 3/4" X 1 1/8").[NEC 690.31(G)]LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;REFLECTIVE[IFC 605.11.1.1]SOLAR PV SYSTEMEQUIPPED WITHRAPID SHUTDOWNTURN RAPID SHUTDOWN SWITCH TOTHE "OFF" POSITION TO SHUT DOWNPV SYSTEM AND REDUCE SHOCKHAZARD IN ARRAYSOLAR ELECTRICPV PANELSLABEL 6AT RAPID SHUTDOWN SYSTEM(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].WARNINGLABEL 7AT POINT OF INTERCONNECTION(2 3/4" X 1 5/8").[NEC 705.12(B)(3)]WARNINGSOLAR ELECTRICCIRCUIT BREAKERIS BACKFEEDLABEL 8AT POINT OF INTERCONNECTION(2" X 1").[NEC 705.12(B)(3)]CAUTIONSOLAR ELECTRIC SYSTEM CONNECTEDLABEL 10AT UTILITY METER (5 3/4" X 1 1/8")[NEC 690.56(B)]RAPID SHUTDOWNSWITCH FORSOLAR PV SYSTEMLABEL 5AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").[NEC 690.56(C)(3)].AC DISCONNECTPHOTOVOLTAIC SYSTEMPOWER SOURCERATED ACOUTPUT CURRENTNOMINAL OPERATINGAC VOLTAGEAMPSVOLTSPHOTOVOLTAIC SYSTEMDISCONNECTINTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTEDPHOTOVOLTAIC SYSTEM DISCONNECT LOCATEDEAST SIDE OF THE HOUSE26.62240DUAL POWER SUPPLYSOURCES: UTILITY GRID AND PV SOLARELECTRIC SYSTEMPV ARRAY 20201212141413131515181822221111S-501D51111332727548252423S-501D42SHEET KEYNOTES1. ROOF MATERIAL: STANDING SEAM METAL2. ROOF STRUCTURE: TJI3. ATTACHMENT TYPE: S!5 PROTEA BRACKET4. MODULE MANUFACTURER: REC5. MODULE MODEL: REC400NP3 BLACK6. MODULE LENGTH: 74.8''7. MODULE WIDTH: 40.9''8. MODULE WEIGHT: 48 LBS.9. SEE SHEET A-103 FOR DIMENSION(S)10. FIRE OFFSET: 18" OR 36" RIDGE SETBACKS, 36"PATH FROM EAVE TO RIDGE11. TJI SPACING: 24 IN. O.C.12. TJI SIZE: 16 IN.13. LAG BOLT DIAMETER: BOLT/SCREW SUPPLIEDWITH RACKING.14. LAG BOLT EMBEDMENT: 3 IN.15. TOTAL # OF ATTACHMENTS: 4916. TOTAL AREA: 467.4 SQ. FT.17. TOTAL WEIGHT: 1173.75 LBS.18. WEIGHT PER ATTACHMENT: 23.95 LBS.19. DISTRIBUTED LOAD: 2.51 PSF20. MAX. HORIZONTAL STANDOFF: 48 IN.21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITHMODULE MANUFACTURER'S INSTRUCTIONS.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE24. RAIL MODEL (OR EQUIVALENT): AIRE A1 RAIL25. RAIL WEIGHT: 0.436 PLF26. MAX. SPAN: N/A.27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.1. FIELD VERIFY ALL MEASUREMENTS2. ITEMS BELOW MAY NOT BE ON THIS PAGEGENERAL NOTESROOF SLOPE 991010101066212177BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338RACKING DETAIL (TRANSVERSE)D1SCALE: NOT TO SCALERACKING DETAIL (LONGITUDINAL)D2SCALE: NOT TO SCALERACKING DETAIL (TOP)D3SCALE: NOT TO SCALEDETAIL (LONGITUDINAL)D5SCALE: NOT TO SCALEDETAIL (TRANSVERSE)D4SCALE: NOT TO SCALES-501.00ASSEMBLY DETAILS(SHEET 10)Signed 4/25/2023 BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-001.00RESOURCE DOCUMENT(SHEET 11) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-002.00RESOURCE DOCUMENT(SHEET 12) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-003.00RESOURCE DOCUMENT(SHEET 13) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-004.00RESOURCE DOCUMENT(SHEET 14) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-005.00RESOURCE DOCUMENT(SHEET 15) BFADE23DESIGN BY:ACDEGHBCFGH1456DATE:CHECKED BY:REVISIONS S.G.M.M.04.23.2023PAPER SIZE: 11" x 17" (ANSI B)V.2.3UNAUTHORIZED USE OF THISDRAWING SET WITHOUT WRITTENPERMISSION FROM CONTRACTOR IS INVIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVILDAMAGES AND PROSECUTIONS.ENGINEER OF RECORDNEW PV SYSTEM: 8.800 kWpHALLRESIDENCE107 WHITTIER ST NORTHAMPTON, MA 01062APN: 43 -110-001CONTRACTORPHONE:LIC. NO.:HIC. NO.:ELE. NO.:ADDRESS:VALLEY SOLAR LLC116 PLEASANT ST SUITE 321EASTHAMPTON, MA 01027664A1413-584-8844186338R-006.00RESOURCE DOCUMENT(SHEET 16)