Loading...
3145-74001-124093-411-SEStampedReviewLetter (1)1/6 RE:CERTIFICATION LETTER Project Address: BRICKER RESIDENCE 64 MEADOW STREET NORTHAMPTON, MA 01062 Design Criteria: - Applicable Codes = 2015 IBC/IEBC W/(780 CMR) 9th Edition, 2015 IRC W/(780 CMR) 9th Edition, ASCE 7-10 and 2015 NDS - Risk Category = II - Wind Speed = 117 mph, Exposure Category B, Partially/Fully Enclosed Method - Ground Snow Load = 40 psf - ARRAY 1 : 2 x 4 @ 24" OC, Roof DL = 10 psf, Roof LL/SL = 35 psf (Non-PV), Roof LL/SL = 35 psf (PV) - ARRAY 2 : 2 x 4 @ 24" OC, Roof DL = 7 psf, Roof LL/SL = 35 psf (Non-PV), Roof LL/SL = 25.1 psf (PV) To Whom It May Concern, For ARRAY 1, the rafter size and spacing of 2 x 4 @ 24" O.C. can span up to 6.4 ft between bearing supports. Sincerely, December 28, 2021 Yuri Yurianto, S.E., P.E. A structural evaluation of loading was conducted for the above address based on the design criteria listed above. Existing roof structural framing has been reviewed for additional loading due to installation of PV Solar System on the roof. The structural review applies to the sections of roof that is directly supporting the solar PV system. Based on this evaluation, I certify that the alteration to the existing structure by installation of the PV system meets the prescriptive compliance requirements of the applicable existing building and/or new building provisions adopted/referenced above. Additionally, the PV module assembly including attachment hardware has been reviewed to be in accordance with the manufacturer’s specifications and to meet and/or exceed the requirements set forth by the referenced codes. Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com By Yuri at 6:45:07 PM, 12/28/2021 2/6 ARRAY 1 NG. See attached pages for qualification. ARRAY 2 OK ROOF ARRAY 1 ARRAY 2 RESULTS SUMMARYBARUN CORP BRICKER RESIDENCE, 64 MEADOW STREET, NORTHAMPTON, MA 01062 ROOF MOUNTING PLANE STRUCTURAL EVALUATION (BASED ON IEBC 5% IMPACT CHECK) STANDOFF HARDWARE EVAULATION FOR WIND UPLIFT UPLIFT DCR RESULT 20.4% 20.5% ROOF PITCH (deg.) 9° 27° Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 3/6 PV module weight 2.5 psf Hardware assembly weight 0.5 psf PV-DL 3.00 psf Existing Roofing Material 1 layers 2.5 psf Underlayment 0.5 psf Plywood Sheathing 1.5 psf Framing Weight 2 x 4 @ 24 in. O.C.0.73 psf Vaulted ceiling Yes 3 psf Miscellaneous 1.5 psf Total Roof Dead Load R-DL 9.73 psf EXPRESSION Roof Live Load Lo 20.0 psf Member Tributary Area At < 200 sf ARRAY 1 Pitch 2/12 or 9° Trubutary Area Reduction R1 1 Slope Roof Reduction R2 1 Reduced Roof Live Load Lr = Lo (R1) (R2)20.00 psf Ground Snow Load pg 40 Effective Roof Slope 9° Snow Importance Factor Is 1.0 Snow Exposure Factor Ce 1.0 Snow Thermal Factor Ct 1.1 Minimum Flat Roof Snow Load pf-min 35 Flat Roof Snow Load pf 35.00 Roof Slope Factor Cs-roof 1.00 ps-roof 35.00 Roof Slope Factor Cs-pv 1.00 ps-pv 35.00 REDUCED ROOF LIVE LOAD (Lr) (All other surfaces) MATERIALROOF DEAD LOAD (R-DL) PV SYSTEM DEAD LOAD (PV-DL) BARUN CORP ARRAY 1 LOAD CALCULATION BRICKER RESIDENCE, 64 MEADOW STREET, NORTHAMPTON, MA 01062 VALUE VALUE Comp Roof SLOPED ROOF SNOW LOAD ON PV PANEL SLOPED ROOF SNOW LOAD ON ROOF SNOW LOAD (Unobstructed slippery surfaces) Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 4/6 EXISTING 9.73 psf 20.00 psf 35.00 psf EXISTING 23.78 psf 38.89 psf 38.89 psf 6.71%NG. See attached pages for qualification. 2015 12.73 Roof Live Load (Lr) =0.00 BARUN CORP IEBC 5% IMPACT CHECK ARRAY 1 BRICKER RESIDENCE, 64 MEADOW STREET, NORTHAMPTON, MA 01062 Roof Snow Load (SL) = The requirements of section 807.4 of 2015 IEBC are met and the structure is permitted to remain unaltered. IEBC Provision : Load Increase (%) = (DL + Lr) / Cd =14.14 (DL + SL) / Cd =41.50 Maximum Gravity Load =41.50 35.00 WITH PV PANEL WITH PV PANEL Roof Dead Load (DL) = Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 5/6 PV module weight 2.5 psf Hardware assembly weight 0.5 psf PV-DL 3.00 psf Existing Roofing Material 1 layers 2.5 psf Underlayment 0.5 psf Plywood Sheathing 1.5 psf Framing Weight 2 x 4 @ 24 in. O.C.0.73 psf Vaulted ceiling No 0 psf Miscellaneous 1.5 psf Total Roof Dead Load R-DL 6.73 psf EXPRESSION Roof Live Load Lo 20.0 psf Member Tributary Area At < 200 sf ARRAY 2 Pitch 6/12 or 27° Trubutary Area Reduction R1 1 Slope Roof Reduction R2 0.9 Reduced Roof Live Load Lr = Lo (R1) (R2)18.00 psf Ground Snow Load pg 40 Effective Roof Slope 27° Snow Importance Factor Is 1.0 Snow Exposure Factor Ce 1.0 Snow Thermal Factor Ct 1.1 Minimum Flat Roof Snow Load pf-min 35 Flat Roof Snow Load pf 35.00 . Roof Slope Factor Cs-roof 1.00 ps-roof 35.00 Roof Slope Factor Cs-pv 0.72 ps-pv 25.10 BARUN CORP LOAD CALCULATION ARRAY 2 BRICKER RESIDENCE, 64 MEADOW STREET, NORTHAMPTON, MA 01062 REDUCED ROOF LIVE LOAD (Lr) Comp Roof VALUE PV SYSTEM DEAD LOAD (PV-DL) ROOF DEAD LOAD (R-DL)MATERIAL VALUE (All other surfaces) (Unobstructed slippery surfaces) SNOW LOAD SLOPED ROOF SNOW LOAD ON ROOF SLOPED ROOF SNOW LOAD ON PV PANEL Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com 6/6 EXISTING 6.73 psf 18.00 psf 35.00 psf EXISTING 19.78 psf 36.29 psf 36.29 psf -16.54%OK 2015 BRICKER RESIDENCE, 64 MEADOW STREET, NORTHAMPTON, MA 01062 BARUN CORP IEBC 5% IMPACT CHECK ARRAY 2 Roof Snow Load (SL) =25.10 WITH PV PANEL (DL + Lr) / Cd =10.81 WITH PV PANEL Roof Dead Load (DL) =9.73 Roof Live Load (Lr) =0.00 IEBC Provision : The requirements of section 807.4 of 2015 IEBC are met and the structure is permitted to remain unaltered. (DL + SL) / Cd =30.29 Maximum Gravity Load =30.29 Load Increase (%) = Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com COMPANY BARUN CORP Philadelphia, PA Dec. 28, 2021 23:31 PROJECT ARRAY 1 Design Check Calculation Sheet WoodWorks Sizer 2019 (Update 4) Loads: Load Type Distribution Pat- Location [ft] Magnitude Unit tern Start End Start End DL Dead Full Area No 9.73(24.0") psf DL-PV Dead Partial Area No 1.50 7.50 3.00(24.0") psf SL-PV Snow Partial Area No 1.50 7.50 35.00(24.0") psf SL1 Snow Partial Area No 0.00 1.50 35.00(24.0") psf SL2 Snow Partial Area No 7.50 7.90 35.00(24.0") psf Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in) : 1.5' 8 .0 0 9 ' 7.879'0' Unfactored: Dead 115 77 Snow 340 213 Factored: Total 456 290 Bearing: F'theta 433 433 Capacity Joist 569 325 Support 586 586 Des ratio Joist 0.80 0.89 Support 0.78 0.49 Load comb #2 #2 Length 0.50* 0.50* Min req'd 0.40 0.50* Cb 1.75 1.00 Cb min 1.75 1.00 Cb support 1.25 1.25 Fcp sup 625 625 *Minimum bearing length setting used: 1/2" for end supports and 1/2" for interior supports Lumber n-ply, S-P-F, No.1/No.2, 2x4, 1-ply (1-1/2"x3-1/2") Supports: All - Lumber n-ply Beam, D.Fir-L No.2 Roof joist spaced at 24.0" c/c; Total length: 8.06'; Clear span(horz): 1.5', 6.313'; Volume = 0.3 cu.ft.; Pitch: 2/12 Lateral support: top = continuous, bottom = at supports; Repetitive factor: applied where permitted (refer to online help); This section PASSES the design code check. Analysis vs. Allowable Stress and Deflection using NDS 2018 : Criterion Analysis Value Design Value Unit Analysis/Design Shear fv = 82 Fv' = 155 psi fv/Fv' = 0.53 Bending(+) fb = 1716 Fb' = 1736 psi fb/Fb' = 0.99 Bending(-) fb = 396 Fb' = 1649 psi fb/Fb' = 0.24 Live Defl'n 0.31 = L/250 0.43 = L/180 in 0.72 Total Defl'n 0.43 = L/181 0.65 = L/120 in 0.66 WoodWorks® Sizer SOFTWARE FOR WOOD DESIGN WoodWorks® Sizer 2019 (Update 4)ARRAY 1 Page 2 Additional Data: FACTORS: F/E(psi) CD CM Ct CL CF Cfu Cr Cfrt Ci LC# Fv' 135 1.15 1.00 1.00 - - - - 1.00 1.00 2 Fb'+ 875 1.15 1.00 1.00 1.000 1.500 - 1.15 1.00 1.00 2 Fb'- 875 1.15 1.00 1.00 0.950 1.500 - 1.15 1.00 1.00 2 Fcp' 425 - 1.00 1.00 - - - - 1.00 1.00 - E' 1.4 million 1.00 1.00 - - - - 1.00 1.00 2 Emin' 0.51 million 1.00 1.00 - - - - 1.00 1.00 2 CRITICAL LOAD COMBINATIONS: Shear : LC #2 = D + S Bending(+): LC #2 = D + S Bending(-): LC #2 = D + S Deflection: LC #2 = D + S (live) LC #2 = D + S (total) Bearing : Support 1 – LC #2 = D + S Support 2 – LC #2 = D + S D=dead S=snow All LC's are listed in the Analysis output Load combinations: ASD Basic from ASCE 7-16 2.4 / IBC 2018 1605.3.1 CALCULATIONS: V max = 317, V design = 288 lbs; M(+) = 438 lbs-ft; M(-) = 101 lbs-ft EIy = 7.50 lb-in^2 "Live" deflection is due to all non-dead loads (live, wind, snow…) Total deflection = 1.0 dead + "live" Bearing: Allowable bearing at an angle F'theta calculated for each support as per NDS 3.10.3 Lateral stability(-): Lu = 6.44' Le = 10.19' RB = 13.8; Lu based on full span Design Notes: 1. Analysis and design are in accordance with the ICC International Building Code (IBC 2018) and the National Design Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement. 2. Please verify that the default deflection limits are appropriate for your application. 3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the middle 2/3 of 2 span beams and to the full length of cantilevers and other spans. 4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1. 5. SLOPED BEAMS: level bearing is required for all sloped beams. 6. FIRE RATING: Joists, wall studs, and multi-ply members are not rated for fire endurance. 7. The critical deflection value has been determined using maximum back-span deflection. Cantilever deflections do not govern design.