Stern - Stamped Plan SetGENERAL NOTES 1.1.1 PROJECT NOTES: 1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES. 1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION 1.1.4 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY 1.1.5 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7. 1.1.6 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3]. 1.1.7 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ. 1.2.1 SCOPE OF WORK: 1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT. 1.3.1 WORK INCLUDES: 1.3.2 PV ROOF ATTACHMENTS - SNAP-N-RACK ULTRA RAIL COMP KIT 1.3.3 PV RACKING SYSTEM INSTALLATION - SNAPNRACK UR-40 1.3.4 PV MODULE AND INVERTER INSTALLATION - HANWHA Q CELLS Q.PEAK DUO BLK ML-G9+ 380 / SOLAR EDGE SE6000H-US (240V) 1.3.5 PV EQUIPMENT GROUNDING 1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX 1.3.7 PV LOAD CENTERS (IF INCLUDED) 1.3.8 PV METERING/MONITORING (IF INCLUDED) 1.3.9 PV DISCONNECTS 1.3.10 PV FINAL COMMISSIONING 1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV 1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE SCOPE OF WORK SYSTEM SIZE: STC: 19 X 380W = 7.220KW PTC: 19 X 351.3W = 6.675KW (19) HANWHA Q CELLS Q.PEAK DUO BLK ML-G9+ 380 (1) SOLAR EDGE SE6000H-US (240V) ATTACHMENT TYPE: SNAP-N-RACK ULTRA RAIL COMP KIT MSP UPGRADE: NO OWNER NAME: JILL STERN PROJECT MANAGER NAME: ERIC WILSON PHONE: 413-338-7555 CONTRACTOR NAME: INSIGHT SOLAR PHONE: 413-338-7555 AUTHORITIES HAVING JURISDICTION BUILDING: NORTHAMPTON, MA ZONING: NORTHAMPTON, MA UTILITY: NATIONAL GRID DESIGN SPECIFICATIONS OCCUPANCY: II CONSTRUCTION: SINGLE-FAMILY ZONING: RESIDENTIAL GROUND SNOW LOAD: 40 PSF WIND EXPOSURE: В WIND SPEED: 117 MPH APPLICABLE CODES & STANDARDS BUILDING: MASSACHUSETTS BUILDING CODE, 9TH EDITION, AS AMENDED (780 CMR) MASSACHUSETTS RESIDENTIONAL BUILDING CODE, 9TH EDITION, AS AMENDED (780 CMR) ELECTRICAL: NEC 2020 FIRE: MASSACHUSETTS COMPREHENSIVE FIRE SAFETY CODE (527 CMR 1.00) PROJECT INFORMATION NEW PV SYSTEM: 7.220 kWp STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 ASSESSOR'S #: NHAMM:031BB:0089L:0001 B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 T-001.00 COVER PAGE (SHEET 1) 01 AERIAL PHOTO NOT TO SCALE N EW S 02 PLAT MAP NOT TO SCALE STATE STSHEET LIST TABLE SHEET NUMBER SHEET TITLE T-001 COVER PAGE G-001 NOTES A-101 SITE PLAN A-102 ELECTRICAL PLAN A-103 SOLAR ATTACHMENT PLAN E-601 LINE DIAGRAM E-602 DESIGN TABLES E-603 PLACARDS S-501 ASSEMBLY DETAILS R-001 RESOURCE DOCUMENT R-002 RESOURCE DOCUMENT R-003 RESOURCE DOCUMENT R-004 RESOURCE DOCUMENT R-005 RESOURCE DOCUMENT 4-28-2021 2017M 2.1.1 SITE NOTES: 2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. 2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. 2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26. 2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.2.1 EQUIPMENT LOCATIONS 2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26. 2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C). 2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC 690.34. 2.2.4 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.5 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. 2.2.6 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. 2.3.1 STRUCTURAL NOTES: 2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. 2.4.1 GROUNDING NOTES: 2.4.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 2.4.3 PV SYSTEMS REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR. ALL METAL ELECTRICAL EQUIPMENT AND STRUCTURAL COMPONENTS BONDED TO GROUND, IN ACCORDANCE WITH 250.134 OR 250.136(A). ONLY THE DC CONDUCTORS ARE UNGROUNDED. 2.4.4 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE 250.122. 2.4.5 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURE CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A). 2.4.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 2.4.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 2.4.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119] 2.4.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ. 2.4.10 DC PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT PROTECTION MEETING THE REQUIREMENTS OF 690.41(B)(1) AND (2) TO REDUCE FIRE HAZARDS 2.5.1 INTERCONNECTION NOTES: 2.5.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH [NEC 705.12 (B)] 2.5.3 THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS OUTPUT MAY NOT EXCEED 120% OF BUSBAR RATING [NEC 705.12(B)(2)(3)]. 2.5.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(2)(3)]. 2.5.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C). 2.5.6 FEEDER TAP INTERCONECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(2)(1) 2.5.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.12 (A) WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42 2.5.8 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)]. 2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: 2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. 2.6.4 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED. THEREFORE BOTH MUST OPEN WHERE A DISCONNECT IS REQUIRED, ACCORDING TO NEC 690.13. 2.6.5 ISOLATING DEVICES OR EQUIPMENT DISCONNECTING MEANS SHALL BE INSTALLED IN CIRCUITS CONNECTED TO EQUIPMENT AT A LOCATION WITHIN THE EQUIPMENT, OR WITHIN SIGHT AND WITHIN 10 FT OF THE EQUIPMENT. AN EQUIPMENT DISCONNECTING MEANS SHALL BE PERMITTED TO BE REMOTE FROM THE EQUIPMENT WHERE THE EQUIPMENT DISCONNECTING MEANS CAN BE REMOTELY OPERATED FROM WITHIN 10 FT OF THE EQUIPMENT, ACCORDING TO NEC 690.15 (A). 2.6.6 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D) 2.6.7 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240. 2.6.8 BOTH POSITIVE AND NEGATIVE PV CONDUCTORS ARE UNGROUNDED, THEREFORE BOTH REQUIRE OVER-CURRENT PROTECTION, ACCORDING TO NEC 240.21. (SEE EXCEPTION IN NEC 690.9) 2.6.9 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO NEC 690.11 AND UL1699B. 2.7.1 WIRING & CONDUIT NOTES: 2.7.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 2.7.3 ALL CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7. 2.7.4 EXPOSED PV SOURCE CIRCUITS AND OUTPUT CIRCUITS SHALL USE WIRE LISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE [690.31 (C)]. PV MODULES WIRE LEADS SHALL BE LISTED FOR USE ON PV ARRAYS, ACCORDING TO NEC 690.31 (A). 2.7.5 PV WIRE BLACK WIRE MAY BE FIELD-MARKED WHITE [NEC 200.6 (A)(6)]. 2.7.6 MODULE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY. 2.7.7 ACCORDING TO NEC 200.7, UNGROUNDED SYSTEMS DC CONDUCTORS COLORED OR MARKED AS FOLLOWS: DC POSITIVE- RED, OR OTHER COLOR EXCLUDING WHITE, GREY AND GREEN DC NEGATIVE- BLACK, OR OTHER COLOR EXCLUDING WHITE, GREY AND GREEN 2.7.8 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE*, OR OTHER CONVENTION NEUTRAL- WHITE OR GREY * IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [NEC 110.15]. NEC2019S B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 G-001.00 NOTES (SHEET 2) 4-28-2021 GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE PROPERTY LINE N EW S 01/32" = 1'-0" SITE PLAN01 16' 32' B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 A-101.00 SITE PLAN (SHEET 3) AREA OF WORK METER UTILITY REVENUE MA SMART METER ENTRANCE STATE STINVERTER AC DISCONNECT 33'-2" 17'-3" 87'-11" 82'-11" ENTRANCE 4-28-2021 MODULE: HANWHA Q-CELLS Q.PEAK DUO BLK ML-G9+ 380 380 WATTS 40.6" 72.4 GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE MODULE STRINGING MODULE STRINGING B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 03/16" = 1' ELECTRICAL PLAN012'-8" 5'-4"A-102.00 ELECTRICAL PLAN (SHEET 4) A N E W S INTERIOR PV EQUIPMENT (N) (1) JUNCTION BOX (E) (1) MAIN ELECTRICAL PANEL (E) (1) METER (N) (1) UTILITY REVENUE MA SMART METER (N) (1) INVERTER EXTERIOR PV EQUIPMENT ARRAY 2 - 3.800 kW [x10] (N) MODULES TILT: 50 DEGREES ROOF PITCH: 14:12 AZIMUTH: 170 DEGREES (N) (1) AC DISCONNECT B A A A A A A A A A A B B B B B BBBB ARRAY 2 - 3.420 kW [x9] (N) MODULES TILT: 50 DEGREES ROOF PITCH: 14:12 AZIMUTH: 170 DEGREES 4-28-2021 GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE ROOF RAFTERS MODULE: HANWHA Q-CELLS Q.PEAK DUO BLK ML-G9+ 380 380 WATTS 40.6" 72.4 B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 N E W S 03/16" = 1' SOLAR ATTACHMENT PLAN012'-8" 5'-4"A-103.00 SOLAR ATTACHMENT PLAN (SHEET 5) FLUSH MOUNT SOLAR MODULES ATTACHED TO ROOF SURFACE (SEE SHEET S-501 FOR MOUNTING DETAILS) ROOF MATERIAL IS ASPHALT SHINGLE 18'-1" 24'-4" ROOF MATERIAL IS ASPHALT SHINGLE 4-28-2021 SOLAR EDGE SE6000H-US (240V) 2 L1 L2 N GG IN BRANCH 1IN BRANCH 9 10 B 3 JUNCTION BOX HANWHA Q-CELLS Q.PEAK DUO BLK ML-G9+ 380 380W SOLAR EDGE P505 POWER OPTIMIZER A N G (E) UTILITY METER TO (E) LOADS UTILITY REVENUE MA SMART METER VTOP LUGS BOTTOM LUGS LOAD LINE EQUIPMENT LEFT OF LINE IS (N) NEW EQUIPMENT RIGHT OF LINE IS (E) EXISTING UNLESS OTHERWISE NOTED. L1 L2 A/2P (N)NN 35 TO UTILITY GRID (OH) L2 N L1 (E) GROUNDING ELECTRODE GROUND ROD (E) MAIN ELECTRICAL PANEL 240/120 V 1Ø, 3W MAIN BUSS:A200 MAX BREAKER SIZE: (200A x 1.2 ) - 200A = 40A (E) MAIN 200A CB1 G 5 AC DISCONNECT,60A SW1 4 CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL 12 10 AWG PV WIRE, COPPER FREE AIR 2 N/A 6 AWG BARE, COPPER 0.96 (32.7 °C)1 15A 18.75A 55A 52.8A 75°C 50A 21 10 AWG THWN-2, COPPER 0.75'' DIA EMT 4N/A6 AWG THWN-2, COPPER 0.96 (32.7 °C)0.8 15A 18.75A 40A 30.72A 75°C 35A 31 8 AWG THWN-2, COPPER 0.75'' DIA EMT 3 N/A 6 AWG THWN-2, COPPER 0.96 (32.7 °C)1 25A 31.25A 55A 52.8A 75°C 50A 41 8 AWG THWN-2, COPPER 0.75'' DIA EMT 3 N/A 6 AWG THWN-2, COPPER 0.96 (32.7 °C)1 25A 31.25A 55A 52.8A 75°C 50A 5 1 8 AWG THWN-2, COPPER 0.75'' DIA EMT 3 35A 6 AWG THWN-2, COPPER 0.96 (32.7 °C)1 25A 31.25A 55A 52.8A 75°C 50A E-601.00 LINE DIAGRAM (SHEET 6) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 A MODULE STRINGING B MODULE STRINGING 4-28-2021 BILL OF MATERIALS CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION MODULE HANWHA Q CELLS Q.PEAK DUO BLK ML-G9+ 380 PM1-19 19 PIECES 1 HANWHA Q CELLS Q.PEAK DUO BLK ML-G9+ 380 380W 144 HALF-CELLS, MONOCRYSTALLINE SILICON INVERTER SOLAR EDGE SE6000H-US (240V)I1 1 PIECE 1 SOLAR EDGE SE6000H-US (240V) 6000W INVERTER MODULE OPTIMIZER SOLAR EDGE P505 PO1-19 19 PIECES 1 SOLAR EDGE P505 OPTIMIZER (REQUIRED PART OF INVERTER'S DISTRIBUTED DC ARCHITECTURE) DISCONNECT EATON DG222URB SW1-2 2 PIECES 1 EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENT PRODUCTION METER GENERIC MANUFACTURER GEN-METER-80A M1 1 PIECE 1 ELECTRICAL METER, OWNER APPROVED WIRING GEN-10-AWG-PV-WIRE-CU WR1 200 FEET 1 10 AWG PV WIRE, COPPER (POSITIVE AND NEGATIVE) WIRING GEN-6-AWG-BARE-CU WR1 100 FEET 1 6 AWG BARE, COPPER (GROUND) WIRING GEN-10-AWG-THWN-2-CU-RD WR2 140 FEET 1 10 AWG THWN-2, COPPER, RED (POSITIVE) WIRING GEN-10-AWG-THWN-2-CU-BLK WR2 140 FEET 1 10 AWG THWN-2, COPPER, BLACK (NEGATIVE) WIRING GEN-8-AWG-THWN-2-CU-RD WR3-5 30 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1) WIRING GEN-8-AWG-THWN-2-CU-BLK WR3-5 30 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2) WIRING GEN-8-AWG-THWN-2-CU-WH WR3-5 30 FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL) WIRING GEN-6-AWG-THWN-2-CU-GR WR2-5 100 FEET 1 6 AWG THWN-2, COPPER, GREEN (GROUND) WIREWAY GEN-EMT-0.75'' DIA WW2-5 100 FEET 1 EMT CONDUIT, 0.75'' DIA OCPD GENERIC MANUFACTURER GEN-CB-35A-240VAC CB1 1 PIECE 1 CIRCUIT BREAKER, 35A, 240VAC TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS DISCONNECTS INVERTERS OCPDS POWER OPTIMIZERS MODULES ASHRAE EXTREME LOW -25.9°C (-14.6°F), SOURCE: BARNES MUNI (42.16°; -72.72°) ASHRAE 2% HIGH 32.7°C (90.9°F), SOURCE: BARNES MUNI (42.16°; -72.72°)REF.QTY.RATED CURRENT MAX VOLTAGE CB1 1 35A 240VAC REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING PM1-19 19 HANWHA Q CELLS Q.PEAK DUO BLK ML-G9+ 380 380W 351.3W 10.5A 10.04A 45.04V 37.85V -0.122V/°C (-0.27%/°C)20A REF.QTY.MODEL RATED INPUT POWER MAX OUTPUT CURRENT MAX INPUT ISC MAX DC VOLTAGE WEIGHTED EFFICIENCY PO1-19 19 SOLAR EDGE P505 505W 15A 14A 83V 98.6% REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD RATING RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1 1 SOLAR EDGE SE6000H-US (240V)240V FLOATING 35A 6000W 25A 16.5A 480V 99.0% SYSTEM SUMMARY INVERTER #1 STRING #1 STRING #2 POWERBOX MAX OUTPUT CURRENT 15A 15A OPTIMIZERS IN SERIES 10 9 NOMINAL STRING VOLTAGE 380V 380V ARRAY OPERATING CURRENT 10A 9A ARRAY STC POWER 7,220W ARRAY PTC POWER 6,675W MAX AC CURRENT 25A MAX AC POWER 6,000W DERATED (CEC) AC POWER 6,000W E-602.00 DESIGN TABLES (SHEET 7) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 4-28-2021 GRADE TO PV ARRAY TO (E) MEP (INSIDE) (N) INVERTER (E) UTILITY METER (E) UTILITY (N) UTILITY REVENUE MA SMART METER (N) AC DISCONNECT !CAUTION! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN:NEWSE-603.00 PLACARDS (SHEET 8) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWSAND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 MAIN DISTRIBUTION UTILITY DISCONNECT FRONTBACK 01 EQUIPMENT ELEVATION NOT TO SCALE PV ARRAY ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL 1 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (2" X 4"). [NEC 690.13]. POWER SOURSE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING LABEL 2 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE (2" X 4"). [NEC 705.12(B)(2)(3)(B)]. LABEL 4 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS (5 3/4" X 1 1/8"). [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL 5 AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2"). [NEC 690.56(C)(3)]. LABEL 9 AT EACH AC DISCONNECTING MEANS (4" X 1"). [NEC 690.13(B)]. LABEL 10 AT EACH DC DISCONNECTING MEANS (4" X 1"). [NEC 690.13(B)]. SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWICH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SOLAR ELECTRIC PV PANELS LABEL 3 AT RAPID SHUTDOWN SYSTEM (3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)]. LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] 1.6 ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED NORTH SIDE OF THE HOUSE DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8"). [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] PHOTOVOLTAIC SOLAR AC DISCONNECT CAUTION SOLAR ELECTRIC SYSTEM CONNECTED LABEL 6 AT UTILITY METER (5 3/4" X 1 1/8") [NEC 690.56(B)] WARNING DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM LABEL 7 AT POINT OF INTERCONNECTION (2 3/4" X 1 5/8"). [NEC 705.12(B)(3)] WARNING SOLAR ELECTRICCIRCUIT BREAKERIS BACKFED LABEL 8 AT POINT OF INTERCONNECTION (2" X 1"). [NEC 705.12(B)(3)] PHOTOVOLTAIC SOLAR DC DISCONNECT PHOTOVOLTAIC POWER SOURCE LABEL 12 AT EACH DC DISCONNECTING MEANS (3" X 4"). [NEC 690.53]. MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX. RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED) LABEL 11 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS (4" X 2"). [NEC 690.54] AC DISCONNECT PHOTOVOLTAIC SYSTEM POWER SOURCE RATED AC OUTPUT CURRENT NOMINAL OPERATING AC VOLTAGE AMPS VOLTS 25 240 480 16.5 30 4-28-2021 SHEET KEYNOTES 1. ROOF MATERIAL: ASPHALT SHINGLE 2. ROOF STRUCTURE: SINGLE SPAN RAFTERS 3. ATTACHMENT TYPE: SNAP N RACK ULTRA RAIL COMP KIT 4. MODULE MANUFACTURER: HANWHA Q-CELLS 5. MODULE MODEL: Q.PEAK DUO BLK ML-G9+ 380 6. MODULE LENGTH: 72.4 IN. 7. MODULE WIDTH: 40.6 IN. 8. MODULE WEIGHT: 43 LBS. 9. SEE SHEET A-103 FOR DIMENSION(S) 10. MIN. FIRE OFFSET: NO FIRE CODE ENFORCED 11. RAFTER SPACING: 24 IN. O.C. 12. RAFTER SIZE: 2"X6" NOMINAL 13. LAG BOLT DIAMETER: 5/16 IN. 14. LAG BOLT EMBEDMENT: 4 IN. 15. TOTAL # OF ATTACHMENTS: 48 16. TOTAL AREA: 387.84 SQ. FT. 17. TOTAL WEIGHT: 921.38 LBS. 18. WEIGHT PER ATTACHMENT: 19.2 LBS. 19. DISTRIBUTED LOAD: 2.38 PSF 20. MAX. HORIZONTAL STANDOFF: 48 IN. 21. MAX. VERTICAL STANDOFF: LANDSCAPE: 26 IN., PORTRAIT: 33 IN. 22. STANDOFF STAGGERING: YES 23. RAIL MANUFACTURER (OR EQUIV.): SNAP N RACK 24. RAIL MODEL (OR EQUIVALENT): UR-40 RAIL 25. RAIL WEIGHT: 0.42 PLF 26. MAX. RAFTER SPAN: N/A 27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX. S-501 D5 20 11 121413151822 ROOF SLOPE910 10 6 21 7 S-501 D4 3 1 54 252423 8 27 2 1. FIELD VERIFY ALL MEASUREMENTS GENERAL NOTES B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 S-501.00 ASSEMBLY DETAILS (SHEET 9) D4 DETAIL (TRANSVERSE) NOT TO SCALE D5 DETAIL (LONGITUDINAL) NOT TO SCALE D1 RACKING DETAIL (TRANSVERSE) NOT TO SCALE D3 RACKING DETAIL (TOP) NOT TO SCALE D2 RACKING DETAIL (LONGITUDINAL) NOT TO SCALE 4-28-2021 B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 R-001.00 RESOURCE DOCUMENT (SHEET 10) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 R-002.00 RESOURCE DOCUMENT (SHEET 11) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 R-003.00 RESOURCE DOCUMENT (SHEET 12) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 R-004.00 RESOURCE DOCUMENT (SHEET 13) B F A DE 2 3 MA 192102 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 7.220 kWp ENGINEER OF RECORD 04.25.2021 DESIGN BY:V.S. M.M. STERN RESIDENCE 152 STATE ST, NORTHAMPTON, MA 01060 APN: NHAMM:031BB:0089L:0001 PAPER SIZE: 11" x 17" (ANSI B) A CDE GH BC FGH 1 4 5 6 CONTRACTOR INSIGHT SOLAR PHONE:413-338-7555 LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:89 MARKET ST NORTHAMPTON, MA 01060 R-005.00 RESOURCE DOCUMENT (SHEET 14)