[NEW] Patrick Manning Letter SSVSE Project Number: U1991.0724.211 May 6, 2021 All Energy Solar ATTENTION: Brian Allen 1264 Energy Lane St Paul, MN 55108 REFERENCE: Patrick Manning Residence (40306): 73 Loudville Road, Northampton, MA 01062 Solar Array Installation To Whom It May Concern: Per your request,we have reviewed the existing structure at the above referenced site.The purpose of our review was to determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on the panel layout plan. Based upon our review, we conclude that the existing structure is adequate to support the proposed solar panel installation. Design Parameters Code: Massachusetts State Residential Code (780 CMR Chapter 51, 9th Edition (2015 IRC)) Risk Category: II Design wind speed: 117 mph (3-sec gust) per ASCE 7-10 Wind exposure category: C Ground snow load, Pg: 40 psf Flat roof snow load, Pf: 35 psf Existing Roof Structure Roof structure: 2x12 rafters @ 16" O.C. Roofing material: metal seam Roof slope: 34° Connection to Roof Mounting connection: (1) S-5! N Clamp to min. 24 ga steel at max. 32" o.c. along rails (2) rails per row of panels, evenly spaced; panel length perpendicular to the rails not to exceed 78 in. Rail cantilever shall not exceed 50% of connection spacing. Conclusions Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation. See attached calculations. 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com VSE Project Number: U1991.0724.211 Patrick Manning Residence 5/6/2021 The solar array will be flush-mounted (no more than 10"above the roof surface)and parallel to the roof surface.Thus,we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case.Because the increase in lateral forces is less than 10%,this addition meets the requirements of the exception in Section 807.5 of the 2015 IEBC as referenced in 780 CMR Chapter 34,9th Edition.Thus the existing lateral force resisting system is permitted to remain unaltered. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations.All work performed must be in accordance with accepted industry-wide methods and applicable safety standards.The contractor must notify Vector Structural Engineering,LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found.Connections to existing roof framing must be staggered,except at array ends,so as not to overload any existing structural member.The use of solar panel support span tables provided by others is allowed only where the building type,site conditions,site-specific design parameters,and solar panel configuration match the description of the span tables.The design of the solar panel racking (mounts,rails,etc.)and electrical engineering is the responsibility of others.Waterproofing around the roof penetrations is the responsibility of others.Vector Structural Engineering assumes no responsibility for improper installation of the solar array. VECTOR STRUCTURAL ENGINEERING, LLC 05/06/2021 _______________________________________________________ Jacob Proctor, P.E. MA License: 54953 - Expires: 06/30/2022 Project Engineer Enclosures JSP/fdh 05/06/2021 651 W. Galena Park Blvd., Ste. 101 / Draper, UT 84020 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com JOB NO.:U1991.0724.211 SUBJECT:WIND PRESSURE PROJECT:Patrick Manning Residence Label:Note: Calculations per ASCE 7-10 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]:117 Notes: Exposure Category:C Risk Category:II Importance Factor, I: ADDITIONAL INPUT & CALCULATIONS: Height of Roof, h [ft]:15 (Approximate) Comp/Cladding Location:No Enclosure Classification: Zone 1 GCp:1.0 Figure 30.4-2C (enter negative pressure coefficients) Zone 2 GCp:1.0 Zone 3 GCp:1.0 α:9.5 Table 26.9-1 zg [ft]:900 Table 26.9-1 Kh:0.85 Table 30.3-1 Kzt:1 Equation 26.8-1 Kd:0.85 Table 26.6-1 Velocity Pressure, qh [psf]:25.3 Equation 30.3-1 GCpi:0 Table 26.11-1 PRESSURES:Equation 30.9-1 Zone 1, p [psf]:25.3 psf (1.0 W, Interior Zones, beyond 'a' from roof edge) Zone 2, p [psf]:25.3 psf (1.0 W, End Zones, within 'a' from roof edge) Zone 3, p [psf]:25.3 psf (1.0 W, Corner Zones, within 'a' from roof corner) (a= 3 ft) Solar Panel Array Gable Roofs 27° < θ ≤ 45° Enclosed Buildings Components and Cladding Wind Calculations piphGCGCqp JOB NO.:U1991.0724.211 SUBJECT:CONNECTION PROJECT:Patrick Manning Residence Calculate Uplift Forces on Connection Pressure (0.6 Dead -0.6 Wind) (psf) Max Connection Spacing1 (ft) Max Trib. Area2 (ft2) Max Uplift Force (lbs) Zone 1 13.4 2.7 8.7 116 Zone 2 13.4 2.7 8.7 116 Zone 3 13.4 2.7 8.7 116 Calculate Connection Capacity Roof Connector: Additional Connection Info: Ultimate Capacity3 [lbs/in]:1005 Factor of Safety:3 Qty. of Connectors:1 Prying Coefficient:1 Total Capacity [lbs]:335 Determine Result Maximum Demand:116 Connection Capacity:335 Result:Capacity > Demand, Connection is adequate. Notes 1. 'Max Connection Spacing' is the spacing between connections along the rails. 3. Ultimate capacity values are from manufacturer testing. Metal gauge has been verified in field. Roof deck model is unknown or has not been tested for this connector. The capacity used is based on conservative values from testing of the connector on similar roof deck model. 4. Install metal roof connector per manufacturer's written instructions with recommended fasteners when indicated. 2. 'Max Trib Area' is the product of the 'Max Connection Spacing' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 78". S-5! N Clamp to min. 24 ga steel VECTOR STRUCTURAL ENGINEERS JOB NO.:U1991.0724.211 SUBJECT:GRAVITY LOADS PROJECT:Patrick Manning Residence GRAVITY LOADS Roof Pitch: 8.1 :12 ROOF DEAD LOAD (D) Increase due to pitch Material weight [psf] Metal Seam 1.21 2.5 1/2" Plywood 1.21 1.0 Framing 1.00 3.0 Insulation 1.00 0.0 1/2" Gypsum Clg.1.21 0.0 M, E & Misc 1.00 2.0 Total Existing Roof DL PV Array DL 1.21 3 DL:1.21 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf]20 ASCE 7-10 Table 4-1 Roof Live Load With PV Array [psf]0 SNOW LOAD (S):w/ Solar Array Roof Slope [x:12]:8.1 Roof Slope [°]:34 Ground Snow Load, pg [psf]:40 ASCE 7-10, Section 7.2 Terrain Category:C ASCE 7-10, Table 7-2 Exposure of Roof:Fully Exposed ASCE 7-10, Table 7-2 Exposure Factor, Ce:0.9 ASCE 7-10, Table 7-2 Thermal Factor, Ct:1.1 ASCE 7-10, Table 7-3 Risk Category:II ASCE 7-10, Table 1.5-1 Importance Factor, Is:1.0 ASCE 7-10, Table 1.5-2 Flat Roof Snow Load, pf [psf]:35 ASCE 7-10, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]:0 ASCE 7-10, Section 7.3.4 Unobstructed Slippery Surface?No ASCE 7-10, Section 7.4 Slope Factor Figure:Figure 7-2b ASCE 7-10, Section 7.4 Roof Slope Factor, Cs:1.00 ASCE 7-10, Figure 7-2 Sloped Roof Snow Load, ps [psf]:35 ASCE 7-10, Equation 7.4-1 Design Snow Load, S [psf]:3521 8.1 34 40 C Fully Exposed 0.9 1.1 II 1.0 35 0 Yes Figure 7-2b 0.60 21 Design material weight [psf] 3.0 1.2 3.0 0.0 0.0 2.0 9.2 3.6 #VALUE! Massachusetts State Building Code (780 CMR Chapter 16, 9th Edition (2015 IBC)), Section 1607.12.5 Existing Abbrev GRADES Fbxx (psi) Fvxx (psi) g (lb/ft3) JOB NO.:U1991.0724.211 DFL#1 DFL#1 1,000 180 32 DFL#2 DFL#2 900 180 32 DF1 (5X)DFL#1 5X5 & LARGER 1,350 170 32 SPF#2 SPF#2 875 135 26.2 SP#2 SP#2 1,100 175 34.3 PROJECT:Patrick Manning Residence SUBJECT:BEAMS 24F-V4 24F-V4 2,400 240 32 24F-V8 24F-V8 2,400 240 40 LVL (1.9)LVL (1.9X106E)2,600 285 40 DESIGN LOADS:Load Types:Snow Live Dead LVL (2.0)LVL (2.0X106E)2,200 285 42 Roof 35 20 9 CRITERIA (L/)DTL DLL DDL LSL LSL (1.3X106E)1,700 400 42 Solar 3.6 A(BLANK)120 180 STL36 GRADE 36 STEEL 21,600 14,400 490 STL46 GRADE 46 STEEL 27,700 16,500 490 STL50 GRADE 50 STEEL 30,000 20,000 490 Label Length 'L' (ft) Roof Trib (ft) Floor Trib (ft) Wall Trib (ft) Add'l Live Load (plf) Add'l Solar Load (plf) Point Load From React (A,B)Dist 'a' (ft) Point Live Load 'PLL' (lb) Point Dead Load 'PDL' (lb)# PLIESGrade Size "BM/HDR"D CRITERIACr CD CF,V Ra (lb)Rb (lb) Mmax (ft-lb) Mallow (ft-lb) Vmax (lb) Vallow (lb) DTL (in) DTLallow (in) DLL (in) DLLallow (in) 1.5DL GLB Camb Check Rafter 11 1.33 4.8 (1)SPF#2 2x12 1.15 1.15 1.00 356 356 994 3051 296 1747 0.090 1.117 0.066 0.744 0.33 M Exx (psi) 1,800,000 29,000,000 29,000,000 1,700,000 1,800,000 1,900,000 1,400,000 1,600,000 1,600,000 1,400,000 29,000,000 2,000,000 1,300,000 VECTOR STRUCTURAL ENGINEERS JOB NO.:U1991.0724.211 SUBJECT:SOLAR LAYOUT PROJECT:Patrick Manning Residence LOUDVIL ARRAY 1