Loading...
Stamped PV Plans v2 - Powers, Myles (1)SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES218 DRURY LN, NORTHAMPTON, MA 01060413-695-15579/16/20GREGPV-1F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075 PHOTOVOLTAIC SYSTEMPV SYSTEM SUMMARY: 13.050 KWSITE LOCATION:HOUSE AERIAL VIEW:SITE LOCATION ANDHOUSE AERIAL VIEWROOF MOUNT RESIDENTIAL PHOTOVOLTAIC SYSTEMSYSTEM SIZE (DC): STC: 45 X 290.00= 13050W DC: PTC: 45 X 266.10 = 11974.50W DCSYSTEM SIZE (AC):10000W AC @ 240VMODULES:45 X HANWHA QCELLS: Q.PLUS BFR-G4.1 290, 290WOPTIMIZERS: 45 X SOLAR EDGE: P340INVERTER:SOLAREDGE: SE10000H-USRGM [SI1]ROOF: COMPOSITION SHINGLETILT:22° PITCHAZIMUTH:100° & 280°RAFTER/TRUSS SIZE :2"X6" RAFTERS @ 24" O.C.ATTACHMENT TYPE : UNIRAC: SFM MICRORAILMAIN SERVICE PANEL :EXISTING 200 AMPS MSP WITH 200 AMPS MAINBREAKER ON END FEEDINTERCONNECTION : LINE SIDE TAPOCPD RATING: 60 AMPSUTILITY: NATIONAL GRIDTABLE OF CONTENTSPV-1 SITE LOCATION AND HOUSE AERIAL VIEWPV-2SITE PLANPV-2A ROOF PLAN WITH MODULES LAYOUTPV-3ROOF MOUNTING DETAILSPV-4 ELECTRICAL LINE DIAGRAMPV-5EXISTING SERVICE PANELPV-6NOTES AND EQUIPMENT LISTPV-7 LABELSPV-8 OPTIMIZER CHARTPV-9 SAFETY PLANMODULE LOCATIONCITY NOTES:·PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESSINVERTERS.·INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK.·EMT CONDUIT ATTACHED TO THE ROOF USING CONDUIT MOUNTS·DIG ALERT (811) TO BE CONTACTED AND COMPLIANCE WITH EXCAVATION SAFETYPRIOR TO ANY EXCAVATION TAKING PLACETHIS PROJECT COMPLIES WITH THE FOLLOWING:2018 INTERNATIONAL BUILDING CODE (IBC)2018 INTERNATIONAL RESIDENTIAL CODE (IRC)2018 INTERNATIONAL MECHANICAL CODE (IMC)2018 INTERNATIONAL PLUMBING CODE (IPC)2018 INTERNATIONAL FUEL GAS CODE (IFGC)2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC)2018 INTERNATIONAL SWIMMING POOL AND SPA CODE (ISPSC)2020 NATIONAL ELECTRICAL CODE (NEC)AS ADOPTED BY TOWN OF NORTHAMPTONCONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS.ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THE MAXIMUM EXTENT POSSIBLE.INSTALLATION NOTES:SITE LOCATION UM AC INV PM MSP JB SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-2F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075SITE PLANSCALE: 1/32" = 1'-0"1(N)45 HANWHA QCELLS: Q.PLUSBFR-G4.1 290, 290WROOF LINEPROPERTY LINESITE PLANROOF AREA : 1953.05 SQ FTDRIVEWAY(E) MAIN SERVICE PANEL(E) UTILITY METERDRURY LN 258'-1"182'-7"104'-3"123'-6"182'-7"66'-8"66'-8"88'-5"120'-7"(N) SMART PRODUCTION METER218 DRURY LN, NORTHAMPTON, MA 01060 UM AC INVPMMSPJBSHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-2AF060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075ROOF PLAN WITH MODULES LAYOUTSCALE: 1/8" = 1'-0"1LEGEND:OBSTRUCTIONPIPE VENT(N)45 HANWHA QCELLS: Q.PLUSBFR-G4.1 290, 290WROOF PLAN WITHMODULES LAYOUTMODULESCONDUITNOTES:1. EMT CONDUIT ATTACHED TOTHE ROOF USING CONDUITMOUNTS2. ATTACHED CLAMPS AT 25%FROM THE EDGE AND 50% FROMTHE CENTER OF THE MODULES3. JUNCTION BOX IS MOUNTED TOTHE RAIL.SETBACKMSP AC JBACDISCONNECTMSPJUNCTIONBOXINVINVERTERPMPRODUCTIONMETERROOF AREA : 1953.05 SQ FTUMUTILITY METERROOF AREA STATEMENTROOFMODULESQTYPITCH AZIMUTHROOF AREAARRAY AREAARRAYCOVERAGE %SYSTEMDISTRIBUTEDWEIGHT12322°100°596.91 SQ FT 413.31 SQ FT41.40%2.50 LBS2 22 22°280°596.91 SQ FT 395.34 SQ FT(N) SMART PRODUCTION METER218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-3F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075ROOF MOUNTINGDETAILSMOUNTING DETAILSScale: NTSATTACHMENT DETAILScale: NTSROOF DECK /MEMBRANESFM SLIDER ANDTRIMRAIL ROOFATTACHMENTBUILDING STRUCTURE5/16" STAINLESS STEEL LAGBOLT OR STRUCTURAL SCREWWITH 2-1/2" MIN. EMBEDMENTAND FLAT WASHER2.5"SFM TRIMRAIL2.5" MIN. EMBED.FLASHINGROOF / DECK MEMBRANEUNIRAC SLIDERSBUILDING STRUCTURE5/16" STAINLESS STEELLAG BOLT ORSTRUCTURAL SCREWWITH 2-1/2" MIN.EMBEDMENT AND FLATWASHER2.5"SFM MICRORAILFLASHING2.5" MIN. EMBED.PV MODULEPV MODULEUNIRAC SLIDERSSFM MICRORAIL2.5" M IN . EMBED .5/16" STAINLESS STEEL LAGBOLT OR STRUCTURAL SCREWWITH 2-1/2" MIN. EMBEDMENTAND FLAT WASHERSFM TRIMRAIL2.5" MIN. EMBED.PV MODULEFLASHINGFLASHINGSFM SLIDER AND TRIMRAILROOF ATTACHMENT(E)2"X6" RAFTERS @ 24"O.C.ROOF / DECK MEMBRANE3" MIN.3" MAX.MAX ATTACHMENT SPAN - 4'218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREG3AF060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS287 Bay Drive, Sudbury, MA 01776Tel: (800) 385-1075SISTERINGDETAILEXISTING CEILING JOISTMINIMUM SISTERING LENGTH (D)6 EA. MINIMUM ATTACHMENTSON EACH END WITH 1''MAXIMUM EDGE DISTANCENEW SISTEREDFRAMING MEMBER (B)EXISTING LOADBEARING WALL1SIDE VIEWSCALE : NTSSISTERING DIAGRAMSCALE : NTSEXISTING RAFTERNEW SISTER RAFTER#9 3-1/8'' STAR DRIVE BUGLEHEAD FRAMING SCREW OR16-d 3.5'' FRAMING NAIL2TOP VIEWSCALE : NTSRAFTER SIZE (B)MINIMUM SISTERINGLENGTH (D)MAXIMUM DISTANCEFROM RIDGE (C)EQUIVALENT TOEXISTING FRAMING1' MAXIMUMFULL LENGTHSPAN OF RAFTERSISTERING SPECIFICATIONS#9 3-1/8'' STAR DRIVE BUGLEHEAD FRAMING SCREW16-d 3.5'' FRAMING NAILSPACING (A)12'' O.C.6'' O.C.ATTACHMENT OPTIONSATTACHMENT TYPE(A)DISTANCE FROM RIDGE (C)3FRAMING DETAILSCALE : NTSFRAMING SPACING AT 24'' OCATTACHMENT SPACING AT 48'' STAGGERED**EACH FRAMING MEMBER WITH ATTACHMENTS (SFM MICRORAIL 2'') WILL REQUIRE SISTERING**218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-4F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075ELECTRICALLINE DIAGRAM- CONNECT TO PREMISES GEC SYSTEMSTRING-315 HANWHA QCELLS: Q.PLUSBFR-G4.1 290, 290WJUNCTIONBOX2 - #10 AWG, PV WIRE1 - #6 AWG IN FREE AIR OR#8 AWG MUST BE IN EMTCONDUITSTRING-115 HANWHA QCELLS: Q.PLUSBFR-G4.1 290, 290WSTRING-215 HANWHA QCELLS: Q.PLUSBFR-G4.1 290, 290WSOLAREDGE P340POWER OPTIMIZERSSOLAREDGE P340POWER OPTIMIZERS4 - #10 AWG,PV WIREUM(E) 200A / 2PMAIN BREAKER(END FED)(E) 200A RATEDMAIN SERVICE PANEL1PH, 120/240V 60HZ(E) UTILITYMETER(N) NEMA 3RRATED LOCKABLEJUNCTION BOX(N) LINESIDE TAPVIA UL LISTEDCONNECTORS3 - #6 AWG, THWN-21 - #8 EGC, THWN-2IN 3/4" OR LARGER EMT CONDUIT(N) MILBANK U5929-XL-INSSINGLE PHASE NEMA 3R600V/100A FORM 2S SMARTPRODUCTION METER(N) 60A RATEDAC DISCONNECTSQUARE D:D222NRB2 - 60 AMPFUSESFUSES SIZINGMAX. CONTINUOUS OUTPUT 42.0A @ 240V42.0X1.25= 52.50AMPS 60A FUSES - OKPV SYSTEM13.050 kW-DC10.000 kW-ACNOTE:CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASEDON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANTTO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS(N) INVERTERSOLAREDGE:SE10000H-USRGM [SI1]6 - #10 AWG, THWN-21 - #8 EGC, THWN-2IN 3/4" ORLARGER EMT CONDUITCONDUCTOR AMPACITY DE-RATE CALCULATIONWireLocationCONDUCTORQUANTITYCircuitConductor SizeNEC Factors Table310.15(B)(16)Allowable AmpacityNEC Factors Table310.15(B)(2)(a)AmbientTemperatureCorrectionAdj. ConductorAmpacity @ 90°CConduit FillCorrection Per310.15(B)(3)(a)INVERTER TOAC DISCONNECTWALL36751.0075.001.00AC DISCONNECTTO POIWALL36751.0075.001.00RAPIDSHUTDOWNSWITCH218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-5F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075EXISTINGSERVICE PANEL218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-6F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075NOTES ANDEQUIPMENT LISTMATERIAL LIST1SOLAREDGE:SE10000H-USRGM [SI1]45SOLAR EDGEP340 POWEROPTIMIZERSQTY EQUIPMENTDESCRIPTION45HANWHAQCELLS: Q.PLUSBFR-G4.1 290,290W39.48V32.29V9.52A8.98A266.1WOPEN CIRCUIT VOLTAGE (Voc) :MAX. POWER VOLTAGE (Vmp) :SHORT CIRCUIT CURRENT (Isc) :MAX. POWER CURRENT (Imp) :PTC RATING :DC MAX SYSTEM VOLTAGE :AC OUTPUT VOLTAGE RANGE :MAX. AC OUTPUT CURRENT :MAX. AC POWER OUPUT :WEIGHTED EFFICIENCY :480V211-240V42.0A10000W99%GENERAL NOTES :1.(45) HANWHA QCELLS: Q.PLUS BFR-G4.1 290, 290W WIRED AND LISTED TO UL1703 STANDARDS2. THE SOLAREDGE: SE10000H-USRGM [SI1] INVERTER WITH INTEGRATED DC DISCONNECT AND ARC FAULT PROTECTION.ATTACHED WITH SYSTEM ELECTRICAL SPECIFICATIONS, GROUND FAULT PROTECTION & LISTED TO UL 1741STANDARDS.3. PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE AS PER NEC SEC.250.166(A).4. SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF ART. 690OF THE NEC5. CONDUIT ABOVE ROOF SHALL BE NO LESS THAN 1" FROM TOP OF THE ROOF TO BOTTOM OF RACEWAY. TABLE NEC310.15(B)(3)(C)6. PHOTOVOLTAIC DC CONDUCTORS ENTERING THE BUILDING SHALL BE INSTALLED IN METALLIC RACEWAY AND SHALL BEIDENTIFIED EVERY 10 FEET -- AND WITHIN 1 FOOT ABOVE AND BELOW PENETRATIONS OF ROOF/CEILING ASSEMBLIES,WALLS, OR BARRIERS -- WITH MINIMUM 3/8-INCH-HIGH WHITE LETTERING ON RED BACKGROUNDREADING: “WARNING: PHOTOVOLTAIC POWER SOURCE"7. SYSTEM GROUNDING ELECTRODE CONDUCTOR FOR PV SYSTEM TO BE SIZED TO MEET THE REQUIREMENTS OF NECTABLE 250.66.8. THE EXISTING MAIN SERVICE PANEL WILL BE EQUIPPED WITH A GROUND ROD OR UFER.9. UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM.10. TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION.11. SOLAREDGE INVERTERS ARE LISTED TO UL 1741 AND UL 1699B STANDARDS.12. SOLAREDGE OPTIMIZERS ARE LISTED TO IEC 62109-1 (CLASS II SAFETY) AND UL 1741 STANDARDS.RATED DC INPUT POWER :MAXIMUM INPUT VOLTAGE :MPPT RANGE :MAX. INPUT CURRENT :MAX. OUTPUT CURRENT :340W48VDC8-48VDC13.75ADC15ADC2FUSES60A FUSES1JUNCTION BOX600VDC, NEMA 3R, UL LISTED1AC DISCONNECT 60A RATED, 240VAC, NEMA 3RUL LISTED, FUSED100 FTCONDUIT 3/4" OR LARGER EMT CONDUIT218 DRURY LN, NORTHAMPTON, MA 01060 UM AC INV PM MSP JB SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-7F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075JUNCTION BOX 45 PV MODULELABELSCAUTION:POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECT(S) LOCATED AS SHOWN.DANGEROUS VOLTAGE MAY BE PRESENT AT ALL TIMESNOTES:1. NEC ARTICLES 690 AND 705 AND IRC SECTION R324 MARKINGSSHOWN HEREON2.ALL MARKING SHALL CONSIST OF THE FOLLOWING:A. UV RESISTANT SIGN MATERIAL WITH ENGRAVED ORMACHINE PRINTED LETTERS OR ELECTRO-PLATING.B. RED BACKGROUND COLOR WHITE TEXT AND LINE WORK.C. AERIAL FONT.3. ALL SIGNS SHALL BE SIZED APPROPRIATELY AND PLACED INTHE LOCATIONS SPECIFIED. SIGNAGE CANNOT BEHAND-WRITTEN.4. SIGNS SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITHPOP-RIVETS OR SCREWS.DRURY LN6X8" TYP - NEC 705.10ARRAYMACINVERTERJ/BDCEVERY 10' ON CONDUIT AND ENCLOSURESTURN RAPID SHUTDOWNSWITCH TO THE "OFF"POSITION TO SHUTDOWN PV SYSTEM ANDREDUCE SHOCKHAZARD IN THE ARRAY"WARNING"ELECTRICAL SHOCK HAZARD.TERMINALS ON BOTH LINE AND LOAD SIDESMAY BE ENERGIZED IN THE OPEN POSITION690.54 690.15, 690.54690.13 (B)690.53PV SYSTEM DC DISCONNECTMAXIMUM VOLTAGE: 480VMAXIMUM CIRCUIT CURRENT: 42.0AMAX RATED OUTPUT CURRENT OFTHE CONTROLLER OR DC-TO-DCCONVERTER: 15A690.56(C)(1)(A)RAPID SHUTDOWN SWITCH FORSOLAR PV SYSTEM690.56(C)(3)SOLAR PV SYSTEM EQUIPPED WITHRAPID SHUTDOWNSOLAR ELECTRICPV PANELSNEC 690.31(G)(3) & (4)705.12(B)(2)(3)(b)"WARNING"DUAL POWER SOURCESSECOND SOURCE IS PHOTO- VOLTAIC SYSTEM RATED AC OUTPUT CURRENT - 42.0 AMPSAC NORMAL OPERATING VOLTAGE - 240 VOLTSPV SYSTEM AC DISCONNECT RATED AC OUTPUT CURRENT - 42.0 AMPSAC NORMAL OPERATING VOLTAGE - 240 VOLTSWARNING:POWER SOURCE OUTPUTCONNECTIONDO NOT RELOCATE THISOVERCURRENT DEVICE"WARNING"PHOTOVOLTAIC POWER SOURCEAC DISCONNECTPRODUCTION METERINVERTER EQUIPPEDWITH RAPID SHUTDOWNUTILITY METERMAIN SERVICE PANEL218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-8F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075OPTIMIZERCHART123456789101-10 11-20 21-30 31-40 41-50 51-60SOLAREDGE OPTIMIZER CHART218 DRURY LN, NORTHAMPTON, MA 01060 SHEET:TITLE:CLIENT:REVISIONS:DATE:DESIGNBY:JOB NO.:DESCRIPTIONDATEREVISIONPOWERS, MYLES413-695-15579/16/20GREGPV-9F060986Electrical Contractor No:HIC 198080902-EL-A1MATTHEW MARKHAMFREEDOM FOREVER MASSACHUSETTS35 Robert Treat Paine Dr. Tauton, MA 02780Tel: (800) 385-1075SAFETYPLANCREW SIGNATURES:MEDICAL INFORMATION:PPE INFORMATIONHAZARDSSAFETY PLANSCALE: NTS1218 DRURY LN, NORTHAMPTON, MA 01060 LOW ELECTRICITY GENERATION COSTSHigher yield per surface area, lower BOS costs, higher power classes, and an efficiency rate of up to 17.7 %.INNOVATIVE ALL-WEATHER TECHNOLOGYOptimal yields, whatever the weather with excellent low-light and temperature behaviour.ENDURING HIGH PERFORMANCELong-term yield security with Anti LID Technology, Anti PID Technology1, Hot-Spot Protect and Traceable Quality Tra.Q™.EXTREME WEATHER RATINGHigh-tech aluminium alloy frame, certified for high snow (5400 Pa) and wind loads (4000 Pa).MAXIMUM COST REDUCTIONSUp to 10 % lower logistics costs due to higher module capacity per box.A RELIABLE INVESTMENTInclusive 12-year product warranty and 25-year linear performance warranty2. THE IDEAL SOLUTION FOR:Rooftop arrays on residential buildingsRooftop arrays on commercial / industrial buildingsYIELD SECURITYANTI PID TECHNOLOGY(APT)HOT-SPOT PROTECT(HSP)TRACEABLE QUALITY(TRA.QTM)ANTI LID TECHNOLOGY(ALT)MOD:27898photon.info/laboratoryQ.PRO-G2 235174 modules testedBest polycrystalline solar module 20141 APT test conditions according to IEC/TS 62804-1:2015, method B (−1500 V, 168 h)2 See data sheet on rear for further information.Q.PLUS BFR-G4.1280-290www.VDEinfo.comID. 40032587Quality Testedhigh reliabilitylow degradationoptimized durabilitycontinous line monitoring999911/2016ENDURING HIGHPERFORMANCEĮ[% / K] +0.04ȕ[% / K] −0.28Ȗ[% / K] −0.39 NMOT [°F] 109 ± 5.4 (43 ± 3 °C)Hanwha Q CELLS America Inc.400 Spectrum Center Drive, Suite 1400, Irvine, CA 92618, USA | TEL +1 949 748-5996 | EMAIL inquiry@us.q-cells.com | WEB www.q-cells.com/na[V]1000 (IEC) / 1000 (UL)II[A DC]20C / TYPE 2[lbs / ft2] 75 (3600 Pa) / 55 (2667 Pa) −40 °F up to +185 °F(−40 °C up to +85 °C)[lbs / ft2] 113 (5400 Pa) / 84 (4000 Pa) 3 See Installation Manual32302668.7 × 45.3 × 46.1 in (1745 × 1150 × 1170 mm)1435 lbs (651 kg)CertifiedUL 1703(254141)280285290[W]280285290[A]9.419.469.52[V]38.9739.2239.48[A]8.848.918.98[V]31.6731.9932.29[%]≥ 16.8≥ 17.1≥ 17.4[W]209.2213.0216.7[A]7.587.637.67[V]36.6636.9037.14[A]6.936.997.05[V]30.1830.4630.73MECHANICAL SPECIFICATIONFormat65.7 in × 39.4 in × 1.26 in (including frame)(1670 mm × 1000 mm × 32 mm)Weight40.8 lbs (18.5 kg)Front Cover0.13 in (3.2 mm) thermally pre-stressed glass with anti-reflection technologyBack CoverComposite filmFrameBlack anodized aluminumCell6 × 10 Q.ANTUM solar cellsJunction Box3.35-4.53 in × 2.36-3.15 in × 0.59-0.75 in(85-115 mm × 60-80 mm x 15-20 mm), IP67, with bypass diodesCable4 mm² Solar cable; (+) ≥ 39.37 in (1000 mm), (−) ≥ 39.37 in (1000 mm)ConnectorStäubli MC4; IP68Note: Installation instructions must be followed. See the installation and operating manual or contact our technical service department for further information on approved installation and useof this product.Specifications subject to technical changes © Q CELLS Q.PLUS BFR-G4.1_280-290_2019-03_Rev01_NAELECTRICAL CHARACTERISTICSPOWER CLASSMINIMUM PERFORMANCE AT STANDARD TEST CONDITIONS, STC1 (POWER TOLERANCE +5 W / −0 W)MinimumPower at MPP1PMPPShort Circuit Current1ISCOpen Circuit Voltage1VOCCurrent at MPPIMPPVoltage at MPPVMPPEfficiency1ȘMINIMUM PERFORMANCE AT NORMAL OPERATING CONDITIONS, NMOT2MinimumPower at MPPPMPPShort Circuit CurrentISCOpen Circuit VoltageVOCCurrent at MPPIMPPVoltage at MPPVMPP1Measurement tolerances PMPP ± 3 %; ISC; VOC ± 5 % at STC: 1000 W/m2, 25 ± 2 °C, AM 1.5 G according to IEC 60904-3 • 2800 W/m², NMOT, spectrum AM 1.5 GQ CELLS PERFORMANCE WARRANTYPERFORMANCE AT LOW IRRADIANCEAt least 97 % of nominal power during first year. Thereafter max. 0.6 % degradation per year. At least 92 % of nominal power up to 10 years. At least 83 % of nominal power up to 25 years.All data within measurement toleranc-es. Full warranties in accordance with the warranty terms of the Q CELLS sales organisation of your respective country.Typical module performance under low irradiance conditions in comparison to STC conditions (25 °C, 1000 W/m²)TEMPERATURE COEFFICIENTSTemperature Coefficient of ISCTemperature Coefficient of VOCTemperature Coefficient of PMPPNormal Module Operating TemperaturePROPERTIES FOR SYSTEM DESIGNMaximum System Voltage VSYSSafety ClassMaximum Series Fuse Rating Fire RatingMax. Design Load, Push / Pull3Permitted Module Temperature on Continuous DutyMax. Test Load, Push / Pull3QUALIFICATIONS AND CERTIFICATESPACKAGING INFORMATIONVDE Quality Tested, UL 1703, CE-compliant, IEC 61215:2016, IEC 61730:2016, Application Class II, U.S. Patent No. 9,893,215 (solar cells)Number of Modules per Pallet Number of Pallets per 53' ContainerNumber of Pallets per 40' ContainerPallet Dimensions (L × W × H)Pallet WeightRELATIVE EFFICIENCYCOMPARED TO NOMINAL POWER [%]10095908580751552520010YEARS97Q CELLSIndustry standard for tiered warranties*Industry standard for linear warranties**Standard terms of guarantee for the 10 PV companieswith the highest production capacity in 2014 (as at: September 2014) 200400 600800 10001101009080RELATIVE EFFICIENCY [%]IRRADIANCE [W/m²]DETAIL A0.630" (16 mm)0.335" (8.5 mm)0.965" (24.5 mm)Junction bo×38.58" (980 mm)65.7" (1670 mm) 4 × Mounting slots (DETAIL A)Cable withconnectorsFrame5.90" (150 mm)39.4" (1000 mm)37.44" (951 mm)1.26" (32 mm)8 × Drainage holes4 × Grounding points ø 0.177" (4.5 mm)•39.37" (•1000 mm)13.6“ (345 mm)4 × Drainage holes Take your business to the next level with SFM INFINITY, UNIRAC’s rail-less PV mounting system for flush mount installations on comp shingle and tile roofs. An advanced 3rd generation product platform in use by top solar contractors nationwide, SFM INFINITY optimizes your operations on and off the roof, with approximately 40% less labor, 30% logistics savings, and 20% fewer roof attachments than traditional solar racking. Plus, 87% of homeowners prefer SFM INFINITY’s aesthetics.SUPERIOR PERFORMANCEEnhance your business with two installs per dayand 30% less cost.EASY INSTALLATIONPre-assembled components, 20% fewer roof attachments, and level array in seconds with post height adjustment. HOMEOWNER PREFERREDMore than 4 out of 5 homeowners prefer SFM INFINITY’S aesthetics over a leading rail brand.SFM INFINITYFRONT TRIM AND END CAPSUNIVERSAL COMPONENTSFIT 32 – 40MM MODULESEOWNERPREFERRED25 YEAR FULL-SYSTEM WARRANTYONE SKU FITS 32 TO 40mmREVOLUTIONIZING ROOFTOP SOLARFOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.COM OR CALL (505) 248-2702REVOLUTIONIZING ROOFTOP SOLARFOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.COM OR CALL (505) 248-2702SFM INFINITYDESIGN GUIDELINESAPPLICATION GUIDEWhile you will see advantages simply from switching to SFM INFINITY, the following guidelines will help you to maximize its benefits.When possible, design in landscape orientation in order to fit more modules on the roof and minimize roof attachments.DEFAULT TO LANDSCAPESFM INFINITY is easily configured in mixed array shapes and module orientations to maximize array density and to avoid vent pipes and other obstacles. Because mounting locations are not constrained by rails, SFM INFINITY has unmatched flexibility to enhance your projects.MIX MODULE ORIENTATIONSVisit UNIRAC’s mobile-friendly library of short, topic-specific videos which answer common questions and demonstrate how simple it is to install SFM INFINITY.CONSULT THE QUICK TIPS VIDEOSQuick Tips Videos: https://unirac.com/SFM-Infinity/ Layout your arrays in U-Builder, UNIRAC’s free solar design software, to optimize SFM INFINITY’S capabilities, including mixing module orientations and minimizing roof attachments. Quickly create layouts on Google or Bing Maps and generate project documents.DESIGN IN U-BUILDERU-Builder: https://design.unirac.com/ Report No. 102393982LAX-002Unirac, IncPage 2 of 107Issued: 11-Apr-2016Revised: 20-Mar-2019Product Brand nameModelsUnirac SFM2.0 Product DescriptionPhotovoltaic Mounting System, Sun Frame Microrail - Installed Using Unirac Installation Guide, Rev PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20UniracDescriptionThe product covered by this report is the Sun Frame Micro Rail roof mounted Photovoltaic Rack Mounting System. This system is designed to provide bonding and grounding to photovoltaic modules. The mounting system employs anodized or mill finish aluminum brackets that are roof mounted using the slider, outlined in section 4 of this report. There are no rails within this product, whereas the 3" Micro Rail, Floating Splice, and 9" Attached Splice electrically bond the modules together forming the path to ground.The Micro Rails are installed onto the module frame by using a stainless steel bolt anodized with black oxide with a stainless type 300 bonding pin, torqued to 20 ft-lbs, retaining the modules to the bracket. The bonding pin of the Micro Rail when bolted and torqued, penetrate the anodized coating of the photovoltaic module frame to contact the metal, creating a bonded connection from module to module.The grounding of the entire system is intended to be in accordance with the latest edition of the National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Photovoltaic Systems. Any local electrical codes must be adhered in addition to thenational electrical codes. The Grounding Lug is secured to the photovoltaic module, torqued in accordance with the installation manual provided in this document. Other optional grounding includes the use of the Enphase UL2703 certified grounding system, which requires a minimum of 2 micro-inverters mounted to the same rail, and using the same engage cable.ED 16.3.15 (20-Apr-17) MandatoryReport No. 102393982LAX-002Unirac, IncPage 3 of 107Issued: 11-Apr-2016Revised: 20-Mar-20192.0 Product DescriptionModel SimilarityOther RatingsNAFuse Rating: 30AModule Orientation: Portrait or LandscapeMaximum Module Size: 17.98 ftϸUL2703 Design Load Rating:33 PSF Downward, 33 PSF Upward, 10 PSF Down-SlopeTested Loads - 50 psf/2400Pa Downward, 50psf/2400Pa Uplift, 15psf/720Pa Down SlopeTrina TSM-255PD05.08 and Sunpower SPR-E20-327 used for Mechanical LoadingIncreased size ML test:Maximum Module Size: 22.3 ft²UL2703 Design Load Rating: 113 PSF Downward, 50 PSF Upward, 30 PSF Down-SlopeLG355S2W-A5 used for Mechanical Loading test. Mounting configuration: Four mountings on each long side of panel with the longest span of 24"UL2703 Design Load Rating: 46.9 PSF Downward, 40 PSF Upward, 10 PSF Down-Slope LG395N2W-A5, LG360S2W-A5 and LG355S2W-A5 used for used for Mechanical Loading test. Mounting configuration: Six mountings for two modules used with the maximum span of 74.5" Fire Class Resistance Rating:- Class A for Steep Slope Applications when using Type 1 Modules. Can be installed at anyinterstitial gap. Installations must include Trim Rail.- Class A for Steep Slope Applications when using Type 2 Modules. Can be installed at anyinterstitial gap. Installations must include Trim Rail.- Class A Fire Rated for Low Slope applications with Type 1 or 2 listed photovoltaic modules.This system was evaluated with a 5” gap between the bottom of the module and the roof’ssurfaceSee section 7.0 illustraction # 1 and 1a for a complete list of PV modules evaluated with these racking systemsRatingsNAED 16.3.15 (20-Apr-17) Mandatory AUTHORIZATION TO MARK Applicant:Manufacturer: Address:Address: Country:Country: Contact:Contact: Phone:Phone: FAX:FAX: Email:Email: Standard(s): Product: Brand Name: Models: This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this Authorization to Mark. Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety. Use of Intertek’s Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark. Any further use of the Intertek name for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement, they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 545 East Algonquin Road, Arlington Heights, IL 60005 Telephone 800-345-3851 or 847-439-5667 Fax 312-283-1672 Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat- Plate Photovoltaic Modules and Panels [UL 2703: 2015 Ed.1] Photovoltaic Mounting System, Sun Frame Microrail - Installed Using Unirac Installation Guide, Rev PUB2019MAR01 with Annex North Row Extension Installation Guide Rev PUB2019FEB20 Unirac SFM Unirac Control Number:5003705 Authorized by: for Dean Davidson, Certification Manager This document supersedes all previous Authorizations to Mark for the noted Report Number. klaus.nicolaedis@unirac.com toddg@unirac.com jia.liu@cxymj.com buwan.luo@cxymj.com Party Authorized To Apply Mark:Same as Manufacturer Report Issuing Office:Lake Forest, CA U.S.A. Klaus Nicolaedis Tom Young Jia Liu Robin Luo 505-462-2190 505-843-1418 +86-15267030962 +86-13621785753 NA NA Unirac, Inc Cixi Emeka Aluminum Co. Ltd 1411 Broadway Blvd NE Albuquerque, NM 87102 No. 688 ChaoSheng Road Cixi City Zhejiang Province 315311 USA China This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be applied only at the location of the Party Authorized To Apply Mark. Page 1 of 1 ATM for Report 102393982LAX-002 ATM Issued: 9-Apr-2019 ED 16.3.15 (20-Apr-17) Mandatory Address: Intertek 3933 US 11 Cortland NY 13045 Telephone: 607-758-6516 www.intertek.com This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense, or damage occasioned by the use of this information. Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and distribute this information and only then in its entirety. © 2018 Intertek Version: 8-September-2016 Page 1 of 3 GFT-OP-10a Subject: ETL Evaluation of SolarEdge Products to NEC 2017 Rapid Shutdown Requirements To, whom it may concern This letter represents the testing results of the below listed products to the requirements contained in the following standards: National Electric Code, 2017, Section 690.12 requirement for rapid shutdown. UL 1741, UL 1741 CRD for rapid shutdown The evaluation was done on the PV Rapid Shutdown System (PVRSS), and covers installations consisting of optimizers and inverters with part numbers listed below. The testing done has verified that controlled conductors are limited to: x Not more than 30 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation outside the array. x Not more than 80 volts and 240 voltamperes within 30 seconds of rapid shutdown initiation inside the array. The rapid shutdown initiation is performed by either disconnecting the AC feed to the inverter, or – if the inverter DC Safety switch is readily accessible – by turning off the DC Safety switch. Applicable products: x Power optimizers: o PB followed by 001 to 350; followed by -AOB or -TFI. OP followed by 001 to 500; followed by -LV, -MV, -IV or -EV. P followed by 001 to 850. SP followed by 001 to 350. *When optimizers are connected to 2 or more modules in series, the max input voltage may exceed 80V. Following the implementation of the NEC 2017 rapid shutdown value of 80V max inside of the array at the beginning of 2019 , modules exceeding this combined input max voltage will be required to use optimizers with parallel inputs. x 1-ph Inverters: Address: Intertek 3933 US 11 Cortland NY 13045 Telephone: 607-758-6516 www.intertek.com This information is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense, or damage occasioned by the use of this information. Any observations and results in this report are relevant only to the sample evaluated. Only the Client is authorized to copy and distribute this information and only then in its entirety. © 2018 Intertek Version: 8-September-2016 Page 2 of 3 GFT-OP-10a o SE3000A-US / SE3800A-US / SE5000A-US / SE6000A-US / SE7600A-US / SE10000A-US / SE11400A-US / SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US when the following label is labeled on the side of the inverter: Inverter part number may be followed by a suffix x 3-ph Inverters: o SE9KUS / SE10KUS / SE14.4KUS / SE20KUS / SE30KUS / SE33.3KUS /SE43.2KUS / SE66.6KUS / SE100KUS ; when the following label is labeled on the side of the inverter: Inverter part number may be followed by a suffix If there are any questions regarding the results contained in this report, or any of the other services offered by Intertek, please do not hesitate to contact the undersigned. :ƵůLJϭ͕ϮϬϮϬhŶŝƌĂĐϭϰϭϭƌŽĂĚǁĂLJůǀĚ͘EůďƵƋƵĞƌƋƵĞ͕EDϴϳϭϬϮƚƚŶ͗͘hŶŝƌĂĐͲŶŐŝŶĞĞƌŝŶŐĞƉĂƌƚŵĞŶƚZĞ͗ŶŐŝŶĞĞƌŝŶŐĞƌƚŝĨŝĐĂƚŝŽŶĨŽƌƚŚĞhŶŝƌĂĐ^ƵŶĨƌĂŵĞDŝĐƌŽƌĂŝů͕^&D/ŶĨŝŶŝƚLJhͲďƵŝůĚĞƌ^ŽĨƚǁĂƌĞW^͕/ŶĐ͘Ͳ^ƚƌƵĐƚƵƌĂůŶŐŝŶĞĞƌƐŚĂƐƌĞǀŝĞǁĞĚƚŚĞhŶŝƌĂĐ͛Ɛ^ƵŶĨƌĂŵĞDŝĐƌŽƌĂŝů͕ƉƌŽƉƌŝĞƚĂƌLJŵŽƵŶƚŝŶŐƐLJƐƚĞŵĐŽŶƐƚƌƵĐƚĞĚĨƌŽŵŵŽĚƵůĂƌƉĂƌƚƐǁŚŝĐŚŝƐŝŶƚĞŶĚĞĚĨŽƌƌŽŽĨƚŽƉŝŶƐƚĂůůĂƚŝŽŶŽĨƐŽůĂƌƉŚŽƚŽǀŽůƚĂŝĐ;WsͿƉĂŶĞůƐ͖ĂŶĚŚĂƐƌĞǀŝĞǁĞĚƚŚĞhͲďƵŝůĚĞƌKŶůŝŶĞƚŽŽů͘dŚŝƐhͲƵŝůĚĞƌƐŽĨƚǁĂƌĞŝŶĐůƵĚĞƐĂŶĂůLJƐŝƐĨŽƌƚŚĞϮ͟DŝĐƌŽƌĂŝů͕ϴ͟ƚƚĂĐŚĞĚ^ƉůŝĐĞ͕ϲ͟ƐƉůŝĐĞ͕ĂŶĚĨƌŽŶƚƚƌŝŵƌĂŝů͘ůůŝŶĨŽƌŵĂƚŝŽŶ͕ĚĂƚĂĂŶĚĂŶĂůLJƐŝƐĐŽŶƚĂŝŶĞĚǁŝƚŚŝŶĂƌĞďĂƐĞĚŽŶ͕ĂŶĚĐŽŵƉůLJǁŝƚŚƚŚĞĨŽůůŽǁŝŶŐĐŽĚĞƐĂŶĚƚLJƉŝĐĂůƐƉĞĐŝĨŝĐĂƚŝŽŶƐ͗ϭ͘DŝŶŝŵƵŵĞƐŝŐŶ>ŽĂĚƐĨŽƌƵŝůĚŝŶŐƐĂŶĚŽƚŚĞƌ^ƚƌƵĐƚƵƌĞƐ͕^ͬ^/ϳͲϬϱ͕^ͬ^/ϳͲϭϬ͕^ͬ^/ϳͲϭϲϮ͘DĂƐƐĂĐŚƵƐĞƚƚƐ^ƚĂƚĞƵŝůĚŝŶŐŽĚĞ͕ϳϴϬDZϵƚŚĚŝƚŝŽŶ͘ϯ͘ϮϬϬϲͲϮϬϭϴ/ŶƚĞƌŶĂƚŝŽŶĂůƵŝůĚŝŶŐŽĚĞ͕ďLJ/ŶƚĞƌŶĂƚŝŽŶĂůŽĚĞŽƵŶĐŝů͕/ŶĐ͘ǁͬWƌŽǀŝƐŝŽŶƐĨƌŽŵ^KWsͲϮϮϬϭϳ͘ϰ͘ϮϬϬϲͲϮϬϭϴ/ŶƚĞƌŶĂƚŝŽŶĂůZĞƐŝĚĞŶƚŝĂůŽĚĞ͕ďLJ/ŶƚĞƌŶĂƚŝŽŶĂůŽĚĞŽƵŶĐŝů͕/ŶĐ͘ǁͬWƌŽǀŝƐŝŽŶƐĨƌŽŵ^KWsͲϮϮϬϭϳ͘ϱ͘ϰϮϴ͕ĐĐĞƉƚĂŶĐĞƌŝƚĞƌŝĂĨŽƌDŽĚƵůĂƌ&ƌĂŵŝŶŐ^LJƐƚĞŵƐhƐĞĚƚŽ^ƵƉƉŽƌƚWŚŽƚŽǀŽůƚĂŝĐ;WsͿWĂŶĞůƐ͕EŽǀĞŵďĞƌϭ͕ϮϬϭϮďLJ/Ͳ^͘&ŽůůŽǁŝŶŐĂƌĞƚLJƉŝĐĂůƐƉĞĐŝĨŝĐĂƚŝŽŶƐƚŽŵĞĞƚƚŚĞĂďŽǀĞĐŽĚĞƌĞƋƵŝƌĞŵĞŶƚƐ͗ĞƐŝŐŶƌŝƚĞƌŝĂ͗ 'ƌŽƵŶĚ^ŶŽǁ>ŽĂĚсϬͲϭϬϬ;ƉƐĨͿĂƐŝĐtŝŶĚ^ƉĞĞĚсϵϬͲϭϴϬ;ŵƉŚͿZŽŽĨDĞĂŶ,ĞŝŐŚƚсϬͲϯϬ;ĨƚͿ ZŽŽĨWŝƚĐŚсϬͲϰϱ;ĚĞŐƌĞĞƐͿ džƉŽƐƵƌĞĂƚĞŐŽƌLJс͕ΘƚƚĂĐŚŵĞŶƚ^ƉĂĐŝŶŐ͗ WĞƌhͲďƵŝůĚĞƌŶŐŝŶĞĞƌŝŶŐƌĞƉŽƌƚ͘ĂŶƚŝůĞǀĞƌ͗ DĂdžŝŵƵŵĐĂŶƚŝůĞǀĞƌůĞŶŐƚŚŝƐ>ͬϯ͕ǁŚĞƌĞ͞>͟ŝƐƚŚĞƐƉĂŶŶŽƚĞĚŝŶƚŚĞhͲƵŝůĚĞƌŽŶůŝŶĞƚŽŽů͘ůĞĂƌĂŶĐĞ͗ Ϯ͟ƚŽϭϬ͟ĐůĞĂƌĨƌŽŵƚŽƉŽĨƌŽŽĨƚŽƚŽƉŽĨWsƉĂŶĞů͘dŽůĞƌĂŶĐĞ;ƐͿ͗ ϭ͘Ϭ͟ƚŽůĞƌĂŶĐĞĨŽƌĂŶLJƐƉĞĐŝĨŝĞĚĚŝŵĞŶƐŝŽŶŝŶƚŚŝƐƌĞƉŽƌƚŝƐĂůůŽǁĞĚĨŽƌŝŶƐƚĂůůĂƚŝŽŶ͘/ŶƐƚĂůůĂƚŝŽŶKƌŝĞŶƚĂƚŝŽŶ͗ ^ĞĞ^&D/ŶƐƚĂůůĂƚŝŽŶ'ƵŝĚĞ͘>ĂŶĚƐĐĂƉĞͲWsWĂŶĞůůŽŶŐĚŝŵĞŶƐŝŽŶŝƐƉĂƌĂůůĞůƚŽƌŝĚŐĞͬĞĂǀĞůŝŶĞŽĨƌŽŽĨĂŶĚƚŚĞWsƉĂŶĞůŝƐŵŽƵŶƚĞĚŽŶƚŚĞůŽŶŐƐŝĚĞ͘ WŽƌƚƌĂŝƚͲWsWĂŶĞůƐŚŽƌƚĚŝŵĞŶƐŝŽŶŝƐƉĂƌĂůůĞůƚŽƌŝĚŐĞͬĞĂǀĞůŝŶĞŽĨƌŽŽĨĂŶĚƚŚĞWsƉĂŶĞůŝƐŵŽƵŶƚĞĚŽŶƚŚĞƐŚŽƌƚƐŝĚĞ͘1478 Stone Point Drive, Suite 190, Roseville, CA 95661T 916.961.3960 F 916.961.3965 W www.pzse.comExperience | Integrity | Empowerment ƚƚĂĐŚŵĞŶƚƐŚĂůůďĞƐƚĂŐŐĞƌĞĚǁŚĞƌĞŐƌŽƵŶĚƐŶŽǁůŽĂĚĞdžĐĞĞĚƐϭϬW^&͘dĞƐƚŝŶŐ͗sĂůƵĞƐǁĞƌĞďĂƐĞĚŽŶhdZͲϮϵϵƚĞƐƚŝŶŐƉƌŽǀŝĚĞĚďLJhŶŝƌĂĐ͘ŽŵƉŽŶĞŶƚƐĂŶĚůĂĚĚŝŶŐZŽŽĨŽŶĞƐ͗dŚĞŽŵƉŽŶĞŶƚƐĂŶĚůĂĚĚŝŶŐZŽŽĨŽŶĞƐƐŚĂůůďĞĚĞƚĞƌŵŝŶĞĚďĂƐĞĚŽŶ^ϳͲϬϱ͕^ϳͲϭϬΘϳͲϭϲŽŵƉŽŶĞŶƚĂŶĚůĂĚĚŝŶŐĚĞƐŝŐŶ͘EŽƚĞƐ͗ ϭͿhͲďƵŝůĚĞƌKŶůŝŶĞƚŽŽůĂŶĂůLJƐŝƐŝƐŽŶůLJĨŽƌhŶŝƌĂĐ^&D^ƵŶĨƌĂŵĞDŝĐƌŽƌĂŝůƐLJƐƚĞŵŽŶůLJĂŶĚĚŽŶŽƚŝŶĐůƵĚĞƌŽŽĨĐĂƉĂĐŝƚLJĐŚĞĐŬ͘ ϮͿZŝƐŬĂƚĞŐŽƌLJ//ƉĞƌ^ϳͲϭϲ͘ ϯͿdŽƉŽŐƌĂƉŚŝĐĨĂĐƚŽƌ͕ŬnjƚŝƐϭ͘Ϭ͘ ϰͿƌƌĂLJĚŐĞ&ĂĐƚŽƌװсϭ͘ϱ ϱͿǀĞƌĂŐĞƉĂƌĂƉĞƚŚĞŝŐŚƚŝƐϬ͘ϬĨƚ͘ ϲͿtŝŶĚƐƉĞĞĚƐĂƌĞ>Z&ǀĂůƵĞƐ͘ ϳͿƚƚĂĐŚŵĞŶƚƐƉĂĐŝŶŐ;ƐͿĂƉƉůLJƚŽĂƐĞŝƐŵŝĐĚĞƐŝŐŶĐĂƚĞŐŽƌLJŽƌůĞƐƐ͘ĞƐŝŐŶZĞƐƉŽŶƐŝďŝůŝƚLJ͗dŚĞhͲƵŝůĚĞƌĚĞƐŝŐŶƐŽĨƚǁĂƌĞŝƐŝŶƚĞŶĚĞĚƚŽďĞƵƐĞĚƵŶĚĞƌƚŚĞƌĞƐƉŽŶƐŝďůĞĐŚĂƌŐĞŽĨĂƌĞŐŝƐƚĞƌĞĚĚĞƐŝŐŶƉƌŽĨĞƐƐŝŽŶĂůǁŚĞƌĞƌĞƋƵŝƌĞĚďLJƚŚĞĂƵƚŚŽƌŝƚLJŚĂǀŝŶŐũƵƌŝƐĚŝĐƚŝŽŶ͘/ŶĂůůĐĂƐĞƐ͕ƚŚŝƐhͲďƵŝůĚĞƌƐŽĨƚǁĂƌĞƐŚŽƵůĚďĞƵƐĞĚƵŶĚĞƌƚŚĞĚŝƌĞĐƚŝŽŶŽĨĂĚĞƐŝŐŶƉƌŽĨĞƐƐŝŽŶĂůǁŝƚŚƐƵĨĨŝĐŝĞŶƚƐƚƌƵĐƚƵƌĂůĞŶŐŝŶĞĞƌŝŶŐŬŶŽǁůĞĚŐĞĂŶĚĞdžƉĞƌŝĞŶĐĞƚŽďĞĂďůĞƚŽ͗ͻǀĂůƵĂƚĞǁŚĞƚŚĞƌƚŚĞhͲƵŝůĚĞƌ^ŽĨƚǁĂƌĞŝƐĂƉƉůŝĐĂďůĞƚŽƚŚĞƉƌŽũĞĐƚ͕ĂŶĚͻhŶĚĞƌƐƚĂŶĚĂŶĚĚĞƚĞƌŵŝŶĞƚŚĞĂƉƉƌŽƉƌŝĂƚĞǀĂůƵĞƐĨŽƌĂůůŝŶƉƵƚƉĂƌĂŵĞƚĞƌƐŽĨƚŚĞhͲƵŝůĚĞƌƐŽĨƚǁĂƌĞ͘dŚŝƐůĞƚƚĞƌĐĞƌƚŝĨŝĞƐƚŚĂƚƚŚĞhŶŝƌĂĐ^&D^ƵŶĨƌĂŵĞDŝĐƌŽƌĂŝů͕ǁŚĞŶŝŶƐƚĂůůĞĚĂĐĐŽƌĚŝŶŐƚŽƚŚĞhͲƵŝůĚĞƌĞŶŐŝŶĞĞƌŝŶŐƌĞƉŽƌƚĂŶĚƚŚĞŵĂŶƵĨĂĐƚƵƌĞƐƉĞĐŝĨŝĐĂƚŝŽŶƐ͕ŝƐŝŶĐŽŵƉůŝĂŶĐĞǁŝƚŚƚŚĞĂďŽǀĞĐŽĚĞƐĂŶĚůŽĂĚŝŶŐĐƌŝƚĞƌŝĂ͘dŚŝƐĐĞƌƚŝĨŝĐĂƚŝŽŶĞdžĐůƵĚĞƐĞǀĂůƵĂƚŝŽŶŽĨƚŚĞĨŽůůŽǁŝŶŐĐŽŵƉŽŶĞŶƚƐ͗ϭͿdŚĞƐƚƌƵĐƚƵƌĞƚŽƐƵƉƉŽƌƚƚŚĞůŽĂĚƐŝŵƉŽƐĞĚŽŶƚŚĞďƵŝůĚŝŶŐďLJƚŚĞĂƌƌĂLJ͖ŝŶĐůƵĚŝŶŐ͕ďƵƚŶŽƚůŝŵŝƚĞĚƚŽ͗ƐƚƌĞŶŐƚŚĂŶĚĚĞĨůĞĐƚŝŽŶŽĨƐƚƌƵĐƚƵƌĂůĨƌĂŵŝŶŐŵĞŵďĞƌƐ͕ĨĂƐƚĞŶŝŶŐĂŶĚͬŽƌƐƚƌĞŶŐƚŚŽĨƌŽŽĨŝŶŐŵĂƚĞƌŝĂůƐ͕ĂŶĚͬŽƌƚŚĞĞĨĨĞĐƚƐŽĨƐŶŽǁĂĐĐƵŵƵůĂƚŝŽŶŽŶƚŚĞƐƚƌƵĐƚƵƌĞ͘ϮͿdŚĞĂƚƚĂĐŚŵĞŶƚŽĨƚŚĞ^&DϮ͟DŝĐƌŽƌĂŝůŽƌϴ͟ƚƚĂĐŚĞĚ^ƉůŝĐĞƚŽƚŚĞĞdžŝƐƚŝŶŐƐƚƌƵĐƚƵƌĞ͘ϯͿdŚĞĐĂƉĂĐŝƚLJŽĨƚŚĞƐŽůĂƌŵŽĚƵůĞĨƌĂŵĞƚŽƌĞƐŝƐƚƚŚĞůŽĂĚƐ͘dŚŝƐƌĞƋƵŝƌĞƐĂĚĚŝƚŝŽŶĂůŬŶŽǁůĞĚŐĞŽĨƚŚĞďƵŝůĚŝŶŐĂŶĚŝƐŽƵƚƐŝĚĞƚŚĞƐĐŽƉĞŽĨƚŚĞĐĞƌƚŝĨŝĐĂƚŝŽŶŽĨƚŚŝƐƌĂĐŬŝŶŐƐLJƐƚĞŵ͘/ĨLJŽƵŚĂǀĞĂŶLJƋƵĞƐƚŝŽŶƐŽŶƚŚĞĂďŽǀĞ͕ĚŽŶŽƚŚĞƐŝƚĂƚĞƚŽĐĂůů͘WƌĞƉĂƌĞĚďLJ͗W^͕/ŶĐ͘ʹ^ƚƌƵĐƚƵƌĂůŶŐŝŶĞĞƌƐZŽƐĞǀŝůůĞ͕EXP. 06/30/2022PAUL K.ZACHERSTRUCTURALNo. 50100