41 -016 13-016 1253 Westhampton Rd Northampton Final Air Leakage ReportAir Leakage Property Fierst 1253 Westhampton Rd Northampton, MA 01062 Weather:Northampton, MA 1253 Westhampton Rd 13-016 1253 Westhampton Rd final.blg Organization Center for EcoTechnology 413-586-7350 John Saveson Builder Teagno Construction, Inc. Whole House Infiltration ASHRAE 62.2 - Ventilation Requirements The ASHRAE 62.2 flow rates shown above are the CONTINUOUS mechanical fresh air ventilation which will meet the 'whole-building' requirement under that version of the standard. Both values incorporate any appropriate 'infiltration credit'. Intermittent mechanical ventilation may be used if the flow rate is adjusted accordingly. For example, the runtime can be reduced to 12 hours per day using a doubled flow rate, as long as the system provides ventilation at least once every 3 hours. For more detail, refer to the appropriate standard. REM/Rate - Residential Energy Analysis and Rating Software v14.6 This information does not constitute any warranty of energy cost or savings. © 1985-2015 Noresco, Boulder, Colorado. HERS Confirmed 4/3/15 Rating No:13-016 Rater ID:1911963 Duct Leakage Ventilation Blower Door Test Heating Cooling Natural ACH 0.14 0.10 ACH @ 50 Pascals 2.29 2.29 CFM @ 25 Pascals 797 797 CFM @ 50 Pascals 1251 1251 Eff. Leakage Area (sq.in) 68.7 68.7 Specific Leakage Area 0.00014 0.00014 ELA/100 sf shell (sq.in) 0.95 0.95 Leakage to Outside Units cooling CFM @ 25 Pascals 132 CFM25 / CFMfan 0.0802 CFM25 / CFA 0.0377 CFM per Std 152 N/A CFM per Std 152 / CFA N/A CFM @ 50 Pascals 207 Eff. Leakage Area (sq.in) 11.37 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.0377 Mechanical Balanced ASHRAE Sensible Recovery Eff. (%) 71.0 62.2-2010 Total Recovery Eff. (%) 48.0 Rate (cfm) 115 65 Hours/Day 14.4 24.0 Fan Watts 102.0 Cooling Ventilation Natural Ventilation