Description: CalcB1 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.00" 1 294 Live
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.00" 552 0 Snow
1 2
6 3 0
6 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 2628# --
2 6' 3.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 2628# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 5# 1696# 932#
2 5# 1696# 932#
Design spans
6' 1.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 4038.'# 16051.'# 25% 3.12' Total Load D+S
Shear 1951.# 7265.# 26% 5.58' Total Load D+S
TL Deflection 0.0549" 0.3073" L/999+ 3.12' Total Load D+S
LL Deflection 0.0354" 0.2049" L/999+ 3.12' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
2 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB3 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 5' 6.69" 1 174 Live
Replacement Uniform (PLF) Top 0' 0.00" 5' 6.69" 350 0 Snow
Replacement Uniform (PLF) Top 5' 6.69" 6' 6.69" 1 176 Live
Replacement Uniform (PLF) Top 5' 6.69" 6' 6.69" 350 0 Snow
Replacement Uniform (PLF) Top 6' 6.69" 7' 6.69" 1 180 Live
Replacement Uniform (PLF) Top 6' 6.69" 7' 6.69" 350 0 Snow
Replacement Uniform (PLF) Top 7' 6.69" 8' 3.00" 1 182 Live
Replacement Uniform (PLF) Top 7' 6.69" 8' 3.00" 350 0 Snow
1 2
8 3 0
8 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 2176# --
2 8' 3.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 2186# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 4# 1426# 751#
2 4# 1426# 760#
Design spans
8' 1.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 4435.'# 16051.'# 27% 4.12' Total Load D+S
Shear 1757.# 7265.# 24% 7.55' Total Load D+S
TL Deflection 0.1059" 0.4073" L/922 4.12' Total Load D+S
LL Deflection 0.0693" 0.2715" L/999+ 4.12' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
3 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB4 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 9.75" 42 348 Live
Replacement Uniform (PLF) Top 0' 0.00" 2' 9.75" 630 0 Snow
Replacement Uniform (PLF) Top 2' 9.75" 9' 0.00" 42 348 Live
Replacement Uniform (PLF) Top 2' 9.75" 9' 0.00" 630 0 Snow
1 2
9 0 0
9 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.932" 4394# --
2 9' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.932" 4394# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 186# 2802# 1592#
2 186# 2802# 1592#
Design spans
8' 10.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Minimum 1.93" bearing required at bearing # 1
Minimum 1.93" bearing required at bearing # 2
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 9773.'# 16051.'# 60% 4.5' Total Load D+S
Shear 3612.# 7265.# 49% 0.06' Total Load D+S
TL Deflection 0.2783" 0.4448" L/383 4.5' Total Load D+S
LL Deflection 0.1775" 0.2965" L/601 4.5' Total Load S
Control: TL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
4 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB16 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.00" 2 339 Live
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.00" 662 0 Snow
1 2
6 3 0
6 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3103# --
2 6' 3.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3103# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 6# 2034# 1070#
2 6# 2034# 1070#
Design spans
6' 1.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 4768.'# 16051.'# 29% 3.13' Total Load D+S
Shear 2304.# 7265.# 31% 5.58' Total Load D+S
TL Deflection 0.0648" 0.3073" L/999+ 3.13' Total Load D+S
LL Deflection 0.0425" 0.2049" L/999+ 3.13' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
5 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB17 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 9.00" 79 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 6' 9.00" 240 104 Live
1 2
6 9 0
6 9 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 1162# --
2 6' 9.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 1162# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 798# 264# 364#
2 798# 264# 364#
Design spans
6' 7.750"
Product: Spruce-Pine-Fir #2 2 x 10 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1930.'# 3431.'# 56% 3.38' Total Load D+L
Shear 892.# 2498.# 35% 6.03' Total Load D+L
LL Deflection 0.0380" 0.2215" L/999+ 3.38' Total Load L
TL Deflection 0.0554" 0.3323" L/999+ 3.38' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
6 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB18 Member Type: Beam Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 2.50" 79 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 6' 2.50" 240 104 Live
Replacement Uniform (PLF) Top 6' 2.50" 6' 9.00" 79 0 Snow
Replacement Uniform (PLF) Top 6' 2.50" 6' 9.00" 240 104 Live
Point (LBS) Top 4' 7.50" 8 1063 Live
Point (LBS) Top 4' 7.50" 2743 0 Snow
1 2
6 9 0
6 9 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 2149# --
2 6' 9.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3325# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 800# 1120# 709#
2 803# 2151# 1109#
Design spans
6' 7.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 6344.'# 16051.'# 39% 4.63' Total Load D+S
Shear 3108.# 7265.# 42% 6.03' Total Load D+S
TL Deflection 0.0850" 0.3323" L/937 3.71' Total Load D+0.75(L+S)
LL Deflection 0.0567" 0.2215" L/999+ 3.71' Total Load 0.75(L+S)
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
7 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB21 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 12.0 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 9 2 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 1 159 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 455 0 Snow
1 2
9 9 0
9 9 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3063# --
2 9' 9.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3063# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 179# 2194# 868#
2 179# 2194# 868#
Design spans
9' 7.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7386.'# 24466.'# 30% 4.87' Total Load D+S
Shear 2434.# 9081.# 26% 0.06' Total Load D+S
TL Deflection 0.1266" 0.4823" L/914 4.87' Total Load D+S
LL Deflection 0.0907" 0.3215" L/999+ 4.87' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
8 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB29 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 12.0 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 1 159 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 455 0 Snow
1 2
9 9 0
9 9 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3059# --
2 9' 9.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3059# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 163# 2194# 864#
2 163# 2194# 864#
Design spans
9' 7.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7376.'# 24466.'# 30% 4.88' Total Load D+S
Shear 2431.# 9081.# 26% 8.73' Total Load D+S
TL Deflection 0.1265" 0.4823" L/915 4.88' Total Load D+S
LL Deflection 0.0907" 0.3215" L/999+ 4.88' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
AudetteLarryCooke - Level 8 6- 2-17
9:23am
9 of 9
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB30 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 12.0 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 9' 5.75" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 1 159 Live
Replacement Uniform (PLF) Top 0' 0.00" 9' 9.00" 455 0 Snow
Replacement Uniform (PLF) Top 9' 5.75" 9' 9.00" 27 7 Live
1 2
9 9 0
9 9 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3059# --
2 9' 9.000" Wall SPF #3/Stud 2x or 4x End-Grain (650psi) N/A 1.500" 3059# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 163# 2194# 864#
2 163# 2194# 864#
Design spans
9' 7.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7376.'# 24466.'# 30% 4.88' Total Load D+S
Shear 2431.# 9081.# 26% 0.06' Total Load D+S
TL Deflection 0.1265" 0.4823" L/915 4.88' Total Load D+S
LL Deflection 0.0907" 0.3215" L/999+ 4.88' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives