15B-050 SLP098 specsGAS FURNACESSLP98UHV DAVE LENNOX SIGNATURE® COLLECTION Upflow / Horizontal - Variable Capacity - Variable Speed Blower Bulletin No. 210577 November 2016 Supersedes July 2016 AFUE - Up To 98.7%Input - 66,000 to 132,000 Btuh Nominal Add-on Cooling - 2 to 5 Tons MODEL NUMBER IDENTIFICATION SL P 98 UH 070 x V 36 B Unit Type SL = Dave Lennox Signature® Collection Stages P = Precise Comfort Technology™ Nominal Gas Heat Input 070 = 66,000 Btuh 090 = 88,000 Btuh 110 = 110,000 Btuh 135 = 132,000 Btuh Blower V = Variable Speed Blower Motor Nominal Add-On Cooling Capacity 36 = 2-3.5 tons 48 = 4 tons 60 = 4-5 tonsConfiguration UH = Upflow/Horizontal 1 Indoor coils with the same letter designation will physically match the furnace. AFUE 98 = 98% Low NOx X = Units meet California Nitrogen Oxides Standard (40ng/J) 1 Cabinet Width B = 17-1/2 in. C = 21 in. D = 24-1/2 in. PRODUCT SPECIFICATIONS SLP98UHV UPFLOW/HORIZONTAL GAS FURNACES SLP98UHV / Page 2 FEATURES WARRANTY Duralok Plus™ Aluminized Steel Heat Exchanger - Limited lifetime warranty in residential applications (twenty year transferable), ten years in non-residential applications. All Other Covered Components - Limited ten year warranty in residential applications, one year in non- residential applications. Refer to Lennox Equipment Limited Warranty certificate included with equipment for details. APPROVALS Units are certified by AHRI. Units tested and rated according to US DOE test procedures and FTC labeling regulations. Blower data from unit tests conducted in Lennox Laboratory air test chamber. Approved by the California Energy Commission and meets California Nitrogen Oxides Standard (NOx) limits of 40 ng/J. EnErgy Star® certified units are designed to use less energy, help save money on utility bills, and help protect the environment. ISO 9001 Registered Manufacturing Quality System. APPLICATIONS Input capacities of 66,000, 88,000, 110,000 and 132,000 Btuh. Variable heat capacity in increments as small as 1% or as large as needed within minimum/maximum input range. Energy efficiency up to (AFUE) 98.7%. Compact cabinet for upflow, horizontal-right or horizontal-left applications without any internal modifications to the unit. Variable speed blower ideal for zoning applications. Lennox add-on indoor coils, high-efficiency air cleaners and humidifiers can easily be added to furnace. Shipped factory assembled with controls installed and wired. Each unit factory test operated to ensure proper operation. NOTE - FURNACES CANNOT BE TWINNED! Zoning Applications The SLP98UHV furnace is designed to work with the Lennox iHarmony® Zoning System with the iComfort® S30 or iComfort Wi-Fi® Thermostat. The iHarmony® Zoning System provides direct feedback to the SLP98UHV, controlling both airflow and heat output to precisely match the comfort requirements for up to four zones. HEATING SYSTEM SilentComfort™ Technology Patented burner sound enclosure and extra cabinet insulation reduces operating sound levels. Lennox Duralok Plus™ Heat Exchanger Assembly Lennox developed heat exchanger assembly consists of primary heat exchanger and secondary condenser coil assembly. Main multi-pass crimped seam design clamshell type heat exchanger. Constructed of heavy- gauge, aluminized steel. Designed for normal expansion and contraction with maximum efficiency and minimum resistance to air flow. Secondary heat exchanger condenser coil constructed of aluminum fins fitted to stainless steel tubes. Coil is factory tested for leaks. Condensate drain header box assembly located on front of coil. A B C D B C D E FG H I J K L M CONTENTS Blower Data ...............................................................21 Dimensions - Furnace/Coil Combined Dimensions ...17 Dimensions - Horizontal Position ...............................15 Dimensions - Upflow Position ....................................14 Features.......................................................................2 Gas Heat Accessories ...............................................11 Installation Clearances ...............................................9 Model Number Identification ........................................1 Optional Accessories - Order Separately...................11 Optional Accessory Dimensions ................................16 Specifications.............................................................10 Vent Lengths ..............................................................13 SLP98UHV / Page 3 HEATING SYSTEM (continued) Compact size of complete heat exchanger assembly permits low overall design of furnace cabinet. Heat exchanger assembly has been laboratory life cycle tested in excess of industry standards. Lennox Designed Header Box Header box on end of condenser coil collects flue condensate for disposal through condensate drains. The drains are located on each side of the cabinet for easy field installation of condensate drain trap. Only one drain is used, the other drain is sealed. Condensate drain trap is included with the unit for field installation. Lennox Designed Flue Condensate Trap Assembly Condensate trap assembly is mounted outside the conditioned air stream. Assembly can be mounted on either side of cabinet in upflow applications. Assembly is mounted below the cabinet in horizontal applications. See Dimension Drawing and Installation Instructions. Can also be mounted remotely (up to 5 ft. away) from unit. 90° street elbow furnished for ease of drain trap installation. Drain connection can be made with field provided PVC pipe or PVC coupling. Drain cap on trap allows easy cleaning and winterizing. Inshot Burners Aluminized steel inshot burners provide efficient, trouble-free operation. Burner venturi mixes air and gas in correct proportion for proper combustion. Burner assembly is removable from the unit as a single component for ease of service. Variable Capacity Gas Control Valve Variable capacity gas control valve adjusts capacity output in increments as small as 1% or as large as needed. 24 volt redundant combination valve combines manual shut off switch (On-Off), automatic electric valve (dual) and gas pressure regulation into a compact combination control. Flame Rollout Switch Manual reset switches are factory installed on burner box. Switch provides protection from abnormal operating conditions. SureLight® Hot Surface Ignitor Tough, reliable, long-life, trouble-free performance. Silicon nitride ignitor. Cemented to steatite block for protection against current leakage. Ignition leads are constructed of nickel plated copper and are enclosed in high temperature Teflon® insulation for dependable operation. E F FEATURES Variable Speed Combustion Air Inducer Three-phase variable speed inducer motor is controlled by the SureLight Control. Overload protected (auto-reset). Heavy-duty blower prepurges heat exchanger and safely vents flue products. Operates only during heating cycle. Pressure Switches (Two-Stage) Prove Combustion Air Inducer operation before allowing gas valve to open. Limit Control Automatic reset, primary limit is accurately located on vestibule panel on all units. Optional Accessories High Altitude Pressure Switch Kit Required for proper unit operation on installations above 7500 ft. Natural Gas to LPG/Propane Conversion Kit Required for field changeover from natural gas to LPG/ Propane. Includes gas valve and orifices. LPG/Propane to Natural Gas Conversion Kit Required for field changeover from LPG/Propane to natural gas. G H SLP98UHV / Page 4 DIRECT VENT SEALED COMBUSTION SYSTEM Furnace features a “sealed combustion” system and can only be installed in Direct Vent (two pipe) applications. In Direct Vent applications, combustion air is supplied from outdoors and flue gases are discharged outdoors. NOTE - Lennox has approved the use of DuraVent® PolyPro® and Centrotherm InnoFlue® manufactured vent pipe and terminations as an alternative to PVC vent pipe. Must be ordered separately. Tested and listed to the ULC S636 standard in Canada. The polypropylene venting system must follow the uninsulated and unconditioned space vent lengths listed in the table on Page 4. Refer to the Installation Instructions for additional details. Optional Accessories Termination Kits Facilitates installation of combustion air intake pipe and flue exhaust pipe. Refer to venting table in this bulletin to determine pipe size needed and proper termination kit required. See Optional Accessories table and dimension drawings. Termination Kit - Concentric 2 or 3 inch kit contains concentric termination assembly, reducer bushing and 45° elbow. 2 inch kit for -070 model contains an outdoor exhaust accelerator. Kit requires single hole penetration of roof or wall for installation. Roof Termination Flashing Kit is available for use with 2 inch Kits. CSA certified. Termination Kit - Flush-Mount Kit contains flush-mount termination, accelerator, mounting template and hardware. Kit may be used with 2, 2-1/2 or 3 in. pipe. Termination Kits - Wall Assembly Close Couple (US Only) 2 or 3 inch kit consists of close-couple, side-by-side PVC piping with galvanized steel wall cover plate for sealing and isolating piping penetration of the wall. Piping spacing and length is sized for proper wall installations. CSA certified. Close Couple WTK (Canada Only) 2 or 3 inch kit contains one insulated faceplate, one insulated exhaust pipe, elbow and fittings. Wall Ring 2 inch kit contains 2 stainless steel outside seal caps, 2 galvanized steel inside seal caps, 4 seal rings for the caps and 18 inch insulation sleeve for sealing and isolating intake and exhaust piping penetration of wall. Maintain a maximum of 6 inches between the inlet and outlet openings in the installation of the pipes. Roof Termination Flashing Kit 3 inch kit contains two neoprene rubber roof flashings for vertical venting through a roof. Vent pipe and insulation not furnished. Flashing Kit can also be used with 2 inch Concentric Vent Termination Kits used in vertical venting rooftop applications. BLOWER Variable Speed Direct Drive Blower Each blower assembly statically and dynamically balanced. Change in blower speeds is easily accomplished by simple DIP switch changes on the SureLight control. See Blower Performance tables. Blower assembly easily removed for servicing. Variable Speed Blower Motor Variable speed motor maintains specified air volume from 0 though 0.8 in. w.g. (heating) and 0 through 1.0 in. w.g. (Cooling) static range. Variable speed operation is achieved by the use of an ECM (Electronically Commutated Motor) motor. Motor is controlled by the SureLight® Control. Motor is equipped with ball bearings and is resiliently mounted. When furnaces are used with the iHarmony® Zoning System and the iComfort® S30 or iComfort Wi- Fi® Thermostat, the blower motor operates from predetermined minimum - maximum air volumes to satisfy zone requirements. I J FEATURES SLP98UHV / Page 5 CONTROLS Surelight® Control (iComfort™ Compatible) Advanced control communicates information about various operating parameters in the furnace to the optional iComfort® S30 or iComfort Wi-Fi® Thermostat to constantly maintain the highest level of comfort, performance and efficiency available. Auto Configuration - On start-up the control automatically sends a description of the unit to the optional iComfort® S30 or iComfort Wi-Fi® Thermostat to automatically configure the number of stages and features available. Connections for connecting a conventional heating/ cooling thermostat are also provided on the control. Control also features: Innovative AirFlex™ technology allows custom blower settings based on the application. Precise Comfort Technology™ automatically adjusts blower speed and heat input in increments as small as 1% or as large as needed for greater temperature control. Variable-speed combustion air inducer is controlled by the Surelight Control. Prior to ignition, a pre-purge cycle for 15 seconds is initiated. After the main burners are turned off, a post-purge cycle for 20 seconds is run. Thermostat Control - Designed to operate in a variable capacity mode. The unit will automatically adjust firing rate based on demand and changing conditions. For optimal performance, the use of a high-quality, digital two-stage thermostat with adjustable settings for first stage/second stage, on/off differentials and adjustable stage timers is recommended. Furnace Input Staging Options Thermostat Type Input Staging Available iComfort® S30 or iComfort Wi-Fi® Thermostat Variable Capacity (increments as small as 1%) Four Stage (35, 60, 80, 100%) Two-Stage (Conventional) Variable Capacity (increments as small as 1%) Two-stage (70% and 100%) Single-Stage (Conventional)Three-Stage (35%, 70% and 100%) SureLight® Ignition Control - Ignition control continuously monitors line voltage and maintains the igniter power at a constant level to provide consistent lighting and maximum igniter life. K Safety Controls - Flame sensor utilizes flame rectification for safe and reliable operation. Should flame fail to ignite, control will initiate 4 re- attempts at ignition before locking out unit operation for 60 minutes. Watchguard type circuit automatically resets ignition controls after one hour of continuous thermostat demand after unit lockout, eliminating nuisance calls for service. Display LED - Seven segment LED displays alpha- numeric information related to diagnostics as well as system operation and status. Diagnostic codes are held in non-volatile memory, immune from power interruptions. Holds up to ten diagnostic codes in order of occurrence for recall on demand. Port on blower door allows for easy viewing. DIP Switch Settings (Note - DIP switches settings are not used with iComfort® S30 or iComfort Wi-Fi® Thermostat) Select Thermostat used - Single-Stage or Two-Stage. Select Operation Mode - Two-Stage, Three-Stage or Variable Capacity. Two selectable second stage recognition times (7 and 12 minutes) are available on the control when the furnace is used with a single-stage thermostat. When used with a two-stage thermostat, furnace will only initiate second stage operation with a second stage thermostat demand. Heating Speeds - A combination of DIP swtich settings allow Normal, 7.5% increase, 15% increase, 7.5% decrease or 15% decrease motor speed selection within heating speed selected for fine tuning air volume. See Blower Performance tables. Cooling Speeds - A combination of DIP switch settings allow Normal, 10% increase or 10% decrease motor speed selection within cooling speed selected for fine tuning air volume. See Blower Performance tables. Blower Speed Ramping (Cooling Mode) - DIP switch settings allow one of four blower speed profiles during cooling operation. Profile A (factory setting) - Motor runs at 50% for 30 seconds, then at 82% for 7-1/2 minutes, then at 100% (if needed) until demand is satisfied. Once demand is met, motor runs at 50% for 30 seconds, then ramps down to stop. Profile B - Motor runs at 82% for 7-1/2 minutes and then at 100% (if needed) until demand is satisfied. Once demand is met,motor ramps down to stop. Profile C - Motor runs at 100% until demand is satisfied. Once demand is met, motor runs at 100% for 60 seconds, then ramps down to stop. Profile D - Motor runs at 100% until demand is satisfied. Once demand is met, motor ramps down to stop. FEATURES SLP98UHV / Page 6 CONTROLS (continued) Dehumidification (Active or Humiditrol® Option) - A jumper on the control control must be clipped to enable active dehumidification and/or operation with a Humiditrol® Whole-Home Dehumidification System. A humidity controlling thermostat or device is also required. During a call for cooling, air volume is automatically reduced, forcing humidity removal by the air conditioner or heat pump system. After the humidity has reached the desired set-point the cooling air volume returns to its designed rate. A dehumidification signal from the thermostat reduces the cooling cfm to 70% of the requested cooling cfm. Dual-Fuel Operation - A jumper on the control must be clipped to enable operation with a single or two-stage heat pump. The indoor blower is started without delay when a call for heat is received. Two-Stage Compressor Operation - A jumper on the control must be clipped to enable operation with a two-stage compressor. The cooling blower speeds for first and second stage cooling will be dictated by the applicable DIP switch settings. Lennox System Operations Monitor Connection - Monitors outdoor unit operation (communicating mode). Blower On Time (Heating) - Blower on time is fixed at 30 seconds, blower off time is adjustable from 60, 90, 120 and 180 seconds (factory setting - 90 seconds). Blower Off Time (Cooling) - For air-conditioning applications, blower on time is 2 seconds following thermostat demand for cooling. Blower off delay is 30 seconds at 50% of high cool cfm (factory default). Controls evaporator humidity by controlling blower and compressor speed on two-stage outdoor units when used with iComfort Wi-Fi® Thermostat or ComfortSense® 7000 thermostat. Continuous Blower Speed - Adjustable continuous blower speed is a percentage of the high cooling speed selection. There are four selectable options (via DIP switch settings) of 28%, 38% (default setting), 70% and 100%. Accessory Terminals - Two accessory terminals furnished for additional power supply requirements for 120 volt (less than 1 amp) power humidifiers and powered air cleaners. One 24 volt humidifier output furnished for non-powered humidifiers. Control is factory installed in the unit control box. 24 Volt Transformer Furnished and factory installed in control box. 40VA transformer has circuit breaker wired in series. FEATURES Field Wiring Make-up Box Furnished for line voltage wiring. Factory installed internally on left side of furnace. Box may be installed internally or externally on either side of furnace. Optional Accessories iComfort® S30 Thermostat (part of the iComfort® Residential Communicating Control System) The iComfort® S30 Thermostat recognizes and connects to all iComfort®-enabled products to automatically configure and control the heating/cooling system (based on user-specified settings) for the highest level of comfort, performance and efficiency. Also recognizes model and serial number information for iComfort®-enabled products to simplify system setup. Wi-Fi remote temperature monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets. Also displays service alerts and reminders. Dealer Dashboard features online real-time monitoring of installed iComfort® systems. A simple easy-to-use touchscreen allows complete system configuration. Scheduled maintenance alerts, system warnings and troubleshooting are also displayed on thermostat screen. Easy to read 7 in. high definition color display (measured diagonally). Conventional outdoor units (not iComfort®-enabled) can easily be added and controlled by the iComfort® S30 Thermostat. Installer setup screens allow quick and simple system configuration without a manual, Installer can also run tests on complete system or individual components for easy maintenance and troubleshooting. Serial communications bus (RSBus), with less wiring than a conventional heating/cooling system, allows system communication. Uses 4-wire, 18-gauge standard thermostat wiring. High Definition Color Display, Mag-Mount, Smart Hub Controller, wallplate (for retrofit installations) furnished for easy installation. See the iComfort® S30 Thermostat Product Specifications bulletin in the Controls section for more information. SLP98UHV / Page 7 CONTROLS (continued) Optional Accessories (continued) iComfort Wi-Fi® Thermostat (part of the iComfort® Residential Communicating Control System) The iComfort Wi-Fi® Thermostat recognizes and connects to all iComfort®-enabled products to automatically configure and control the heating/cooling system (based on user-specified settings) for the highest level of comfort, performance and efficiency. Also recognizes model and serial number information for iComfort®-enabled products to simplify system setup. Wi-Fi remote temperature monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets. Also displays service alerts and reminders. Dealer Dashboard features online real-time monitoring of installed iComfort® systems. A simple easy-to-use touchscreen allows complete system configuration. Scheduled maintenance alerts, system warnings and troubleshooting are also displayed on thermostat screen. Easy to read 7-inch color screen (measured diagonally). Conventional outdoor units (not iComfort®-enabled) can easily be added and controlled by the iComfort Wi-Fi® Thermostat. Installer setup screens allow quick and simple system configuration without a manual, Installer can also run tests on complete system or individual components for easy maintenance and troubleshooting. Serial communications bus (RSBus), with less wiring than a conventional heating/cooling system, allows system communication. Uses 4-wire, 18-gauge standard thermostat wiring. See the iComfort Wi-Fi® Thermostat Product Specifications bulletin in the Controls section for more information. Remote Outdoor Temperature Sensor Used with the iComfort®-enabled thermostats. When installed outdoors, sensor allows thermostat to display outdoor temperature. Sensor is auto-detected when connected to thermostat. NOTE - Sensor is required for Humiditrol® applications. NOTE - The outdoor sensor is furnished as standard with iComfort®-enabled outdoor units, optional for conventional units. FEATURES ComfortSense® 7500 Touchscreen Thermostat Electronic 7-day, universal, multi-stage, programmable, touchscreen thermostat. 4 Heat/2 Cool. Auto-changeover. Dual-fuel control with optional outdoor sensor. Controls dehumidification during cooling mode and humidification during heating mode. Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders. Easy-to-use, menu driven thermostat with a back-lit, LCD touchscreen. See the ComfortSense® 7500 Product Specifications bulletin in the Controls section for more information. Remote Outdoor Temperature Sensor for ComfortSense® 7500 Thermostat Allows the thermostat to display outdoor temperature. Required in dual-fuel and Humiditrol® applications. Thermostat Thermostat (iComfort® S30, iComfort Wi-Fi® Thermostat or programmable/non-programmable) is not furnished with unit. See Thermostat bulletins in Controls Section and Lennox Price Book for selection. Night Service Kit Contains most commonly used service parts: • Furnace control • Ignitor • Flame sensor • Gas valve • Transformer • Service Manual Universal Service Kit - Switches Kit contains: • Primary limits (for each model) • Pressure switches (for each model) • Flame rollout switches (for each model) SLP98UHV / Page 8 CABINET Low-profile, narrow width cabinet allows easy installation in upflow or horizontal applications. Heavy-gauge, cold rolled steel construction. Pre-painted cabinet finish. Flanges provided on supply air opening for ease of plenum connection or alignment with indoor coil. Fully insulated cabinet with foil faced insulation on sides and back of heating compartment and sealed mat faced insulation in blower compartment. Sealed blower compartment. Inner blower compartment access panel seals blower compartment from air leakage. Complete service access. Safety interlock switch automatically shuts off power to unit when inner blower compartment access panel is removed. Gas piping and electrical inlets are provided in both sides of cabinet. Return Air Entry: For bottom/end return-air entry, remove furnished bottom seal panel from cabinet. For side return-air entry (upflow applications only), corners are marked on either side of cabinet for return air cut-outs. On furnaces with side return air and condensate trap on the same side of the cabinet, a field fabricated transition or optional Return Air Base is required when using an IAQ product higher than 14-3/16 in. installed next to the unit and serviced from the front. IAQ products higher than 20 in. require a field fabricated transition. See dimension drawings. NOTE - 60C and 60D size units that require air volumes over 1800 cfm must have one of the following: 1. Single side return air with transition, to accommodate 20 x 25 x 1 in. cleanable air filter, required to maintain proper air velocity. 2. Single side return air with optional Return Air Base. 3. Bottom return air. 4. Return air from both sides. 5. Bottom and one side return air. See Blower Performance Tables for additional information. Coil Match-up All furnaces exactly match C33, C35, CX34 and CX35 cased upflow indoor coils and CH33 horizontal indoor coils with same letter designation in model number. No adaptor required. Engaging holes furnished on cabinet for alignment. L M C33 uncased coils match furnaces without any overhang but require an optional adaptor base or field fabricated transition to match furnace opening. See C33 coil bulletin for additional information. Low Leakage Cabinet All models have less than 2% air leakage and meet ANSI/ASHRAE Standard 193-2010 “Method of Test for Determining the Air Tightness of HVAC Equipment”. Optional Accessories Condensate Drain Heat Cable Kits Self-limiting wattage heat cable prevents condensate drain from freezing in unconditioned areas. Available in 6 or 24 ft. lengths. Crawl Space Vent Drain Kit Allows venting through a crawl space for upflow and horizontal applications. Includes 2 or 3 in. sanitary tee, 2 in. PVC assembly, PVC boot and clamp. Horizontal Suspension Kit Provides suspension of unit and indoor coil in horizontal applications. Allows complete service access. Consists of corner mounted hanging brackets with vibration isolators, return air end support rail and hardware for assembly. Metal hanging straps must be field provided. Return Air Base On furnaces with side return air and condensate trap on the same side of the cabinet, a field fabricated transition or Return Air Base is required when using an IAQ product higher than 14-3/16 in. installed next to the unit and serviced from the front. IAQ products higher than 20 in. require a field fabricated transition. Must be used for 60C and 60D models with air volumes over 1800 cfm in upflow applications when only one side return is required. Cabinet is shipped flat for easy field assembly and is pre-painted steel to match the furnace. Gasketed for tight seal. See Dimension Drawing. FEATURES SLP98UHV / Page 9 INSTALLATION CLEARANCES Sides 1 0 inches (0 mm) Rear 0 inches (0 mm) Top/Plenum 1 inch (25 mm) Front 0 inches (0 mm) Front (service/alcove)24 inches (610 mm) Floor 2 Combustible NOTE - Air for combustion must conform to the methods outlined in the National Fuel Gas Code (NFPA 54/ANSI-Z223.1) or the National Standard of Canada CAN/CSA-B149.1 “Natural Gas and Propane Installation Code”. NOTE - In the U.S. flue sizing must conform to the methods outlined in the current National Fuel Gas Code (NFPA 54/ANSI-Z223.1) or applicable provisions of local building codes. In Canada flue sizing must conform to the methods outlined in National Standard of Canada CAN/CSA-B149.1. 1 Allow proper clearances to accommodate condensate trap and vent pipe installation. 2 Do not install the furnace directly on carpeting, tile, or other combustible materials other than wood flooring. CABINET (continued) High Performance Economizer (Commercial Applications Only) Designed for applications requiring outdoor air to be utilized in a commercial HVAC system. Allows the entry of fresh outdoor air for free cooling, reducing the requirement for mechanical cooling. Heavy gauge galvanized steel cabinet lined with thick fiberglass insulation. Mixed air sensor, outdoor air sensor and 24VAC transformer furnished. Approved for California Title 24 building standards. ASHRAE 90.1-2010 compliant. See separate Product Specifications bulletin for additional information and available control and sensor options. NOTE - Economizer is not iComfort® compatible. FILTER (not furnished) Filter and provisions for external mounting must be field provided. Optional Accessories Air Filter and Rack Kit for Horizontal Return Air (End) Applications Washable or vacuum cleanable polyurethane frame type filter and external end return air rack available for field installation. Rack has filter door for easy filter servicing. Flanges on rack allow easy duct connection. See dimension drawing. Air Filter and Rack Kit for Upflow Side Return Air Applications - Not for use with Return Air Base Washable or vacuum cleanable polyurethane frame type filter and external side return air rack available for field installation. Available in single and ten pack kits. Rack has filter door for easy filter servicing. Flanges on rack allow easy duct connection. Field installs on either side of unit cabinet. See dimension drawing. INDOOR AIR QUALITY See Indoor Air Quality section and Lennox Price Book for a complete list of indoor air quality products (air purification systems, high efficiency air filters and filter cabinets, UV lights, humidifiers, fresh air ventilation system and heat/energy recovery systems). FEATURES SLP98UHV / Page 10 SPECIFICATIONS Gas Heating Performance Model No.SLP98UH070XV36B SLP98UH090XV36C SLP98UH090XV48C 1 AFUE 98.0%98.0%98.0% Maximum Input - Btuh 66,000 88,000 88,000 Output - Btuh 64,000 85,000 85,000 Temperature rise range - °F 50 - 80 60 - 90 50 - 80 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 3.5 / 10.0 3.5 / 10.0 3.5 / 10.0 Minimum Input - Btuh 23,000 31,000 31,000 Output - Btuh 22,000 30,000 30,000 Temperature rise range - °F 35 - 65 35 - 65 35 - 65 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 0.5 / 1.5 0.5 / 1.5 0.5 / 1.5 High static - in. w.g.0.8 0.8 0.8 Connections in. Intake / Exhaust Pipe (PVC)2 / 2 2 / 2 2 / 2 Gas pipe size IPS 1/2 1/2 1/2 Condensate Drain Trap (PVC pipe) - i.d.3/4 3/4 3/4 with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt with field supplied (PVC coupling) - o.d.3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT Indoor Blower Wheel nominal diameter x width - in.10 x 9 10 x 9 11 x 11 Motor output - hp 1/2 1/2 3/4 Tons of add-on cooling 2 - 3 2 - 3.5 2.5 - 4 Air Volume Range - cfm 339 - 1365 520 - 1360 528 - 1770 Electrical Data Voltage (Maximum Amps) 120 volts - 60 hertz - 1 phase Blower motor full load amps 7.7 7.7 10.1 Maximum overcurrent protection 15 15 15 Shipping Data lbs. - 1 package 138 155 165 NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. SPECIFICATIONS Gas Heating Performance Model No.SLP98UH090XV60C SLP98UH110XV60C SLP98UH135XV60D 1 AFUE 98.7%98.0%98.0% Maximum Input - Btuh 88,000 110,000 132,000 Output - Btuh 87,000 106,000 128,000 Temperature rise range - °F 50 - 80 50 - 80 55 - 85 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 3.5 / 10.0 3.5 / 10.0 3.5 / 10.0 Minimum Input - Btuh 31,000 39,000 46,000 Output - Btuh 30,000 38,000 45,000 Temperature rise range - °F 35 - 65 35 - 65 35 - 65 Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane 0.5 / 1.5 0.5 / 1.5 0.5 / 1.5 High static - in. w.g.0.8 0.8 0.8 Connections in.Intake / Exhaust Pipe (PVC)2 / 2 2 / 2 2 / 2 Gas pipe size IPS 1/2 1/2 1/2 Condensate Drain Trap (PVC pipe) - i.d.3/4 3/4 3/4 with furnished 90° street elbow 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt 3/4 slip x 3/4 Mipt with field supplied (PVC coupling) - o.d.3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT Indoor Blower Wheel nominal diameter x width - in.11 x 11 11 x 11 11 x 11 Motor output - hp 1 1 1 Tons of add-on cooling 3 - 5 3 - 5 3.5 - 5 Air Volume Range - cfm 375 - 2195 554 - 2125 634 - 2190 Electrical Data Voltage (Maximum Amps) 120 volts - 60 hertz - 1 phase Blower motor full load amps 12.8 12.8 12.8 Maximum overcurrent protection 20 20 20 Shipping Data lbs. - 1 package 165 175 190 NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces. SLP98UHV / Page 11 OPTIONAL ACCESSORIES - ORDER SEPARATELY NOTE - FURNACES CANNOT BE TWINNED! “B” Width Models “C” Width Models “D” Width Models CABINET ACCESSORIES Horizontal Suspension Kit - Horizontal only 51W10 51W10 51W10 Return Air Base - Upflow only 50W98 50W99 51W00 High Performance Economizer (Commercial Only)10U53 10U53 10U53 CONDENSATE DRAIN KITS Condensate Drain Heat Cable 6 ft. 26K68 26K68 26K68 24 ft.26K69 26K69 26K69 Crawl Space Vent Drain Kit 51W18 51W18 51W18 CONTROLS iComfort® S30 Thermostat 12U67 12U67 12U67 iComfort Wi-Fi® Thermostat 10F81 10F81 10F81 1 Remote Outdoor Air Temperature Sensor (for dual fuel and Humiditrol®) X2658 X2658 X2658 2 Discharge Air Temperature Sensor 88K38 88K38 88K38 ComfortSense® 7500 Thermostat 13H14 13H14 13H14 3 Remote Outdoor Air Temperature Sensor (for dual fuel and Humiditrol)X2658 X2658 X2658 FILTER KITS 4 Air Filter and Rack Kit Horizontal (end)Size of filter - in.87L96 - 18 x 25 x 1 87L97 - 20 x 25 x 1 87L98 - 25 x 25 x 1 Side Return Single 44J22 44J22 44J22 Ten Pack 66K63 66K63 66K63 Size of filter - in.16 x 25 x 1 16 x 25 x 1 16 x 25 x 1 NIGHT SERVICE KITS Night Service Kit 10U37 10U37 10U37 Universal Service Kit - Switches 89W20 89W20 89W20 TERMINATION KITS Direct Vent Applications Only. See Installation Instructions for specific venting information. Termination Kits Concentric US - 2 in.71M80 69M29 - - - 3 in.- - -60L46 60L46 Canada - 2 in.44W92 44W92 - - - 3 in.- - -44W93 44W93 Flush-Mount US - 2, 2-1/2 or 3 in.51W11 51W11 51W11 Canada - 2, 2-1/2 or 3 in.51W12 51W12 51W12 Wall - Close Couple US - 2 in.22G44 - - -- - - 3 in.44J40 44J40 44J40 Wall - Close Couple WTK Canada - 2 in.30G28 - - -- - - 3 in.81J20 81J20 81J20 Roof 2 in.15F75 15F75 - - - Wall Ring Kit 2 in.15F74 15F74 - - - Roof Termination Flashing Kit (2 flashings)3 in.44J41 44J41 44J41 1 Remote Outdoor Temperature Sensor is used with conventional (non-iComfort®-enabled) outdoor units (sensor is furnished with iComfort®-enabled outdoor units). Allows the thermostat to display outdoor temperature. Required in dual-fuel and Humiditrol® applications. 2 Optional for service diagnostics. 3 Remote Outdoor Temperature Sensor for ComfortSense 7500 Thermostat must be connected directly to the thermostat, Do not connect it to the SureLight® control. 4 Cleanable polyurethane frame type filter. NOTE - Termination Kits 44W92, 44W93, 30G28, 51W12, 81J20 are certified to ULC S636 standard for use in Canada only. GAS HEAT ACCESSORIES Input High Altitude Pressure Switch Kit Natural Gas to LPG/Propane Kit LPG/Propane to Natural Gas Kit 7501 - 10,000 ft.0 - 10,000 ft.0 - 10,000 ft. All Models 14T65 65W77 70W87 SLP98UHV / Page 12 OUTDOOR TERMINATION KIT USAGE Input Size Vent Pipe Diameter (in.) Standard Terminations Concentric Terminations Flush Mount Kit Wall Kit Wall Ring Kit Field Fabricated Exhaust Accelerator Size Required Concentric Kit 1-1/2 inch 2 inch 3 inch2 inch 3 inch 2 inch 51W11 (US) 4 51W12 (CA)22G44 (US) 4 30G28 (CA)44J40 (US) 4 81J20 (CA)15F74 71M80 (US) 4 44W92 (CA)69M29 (US) 4 44W92 (CA)60L46 (US) 4 44W93 (CA) 070 2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 2-1/2 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 3 3 YES YES 1 YES YES 1-1/2 in.2 YES - - -- - - 090 2 3 YES - - -YES 1 YES 2 in.- - -YES YES 2-1/2 3 YES - - -YES 1 YES 2 in.- - -YES YES 3 3 YES - - -YES 1 YES 2 in.- - -YES YES 110 2 YES - - -YES YES 2 in.- - -YES YES 2-1/2 YES - - -YES - - -2 in.- - -YES YES 3 YES - - -YES - - -2 in.- - -YES YES 135 3 YES - - -YES - - -2 in.- - -- - -YES NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See Vent Length Tables. 1 Requires field provided 1-1/2 in. outdoor exhaust accelerator. 2 Concentric Kits 71M80 and 44W92 include 1-1/2 in. outdoor exhaust accelerator, required when used with 045 and 070 input models. Accelerator is not used with 090, 110, 135 input models. 3 Flush Mount Kit 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models. Accelerator is not used with 110 or 135 input models. 4 Termination Kits 30G28, 44W92, 44W93, 51W12 and 81J20 are certified to ULC S636 standard for use in Canada only. VENT LENGTHS - UNINSULATED EXHAUST PIPE IN UNCONDITIONED SPACE 1 Winter Design Temperatures Vent Pipe Diameter Unit Input Size 070 090 110 135 Maximum Un-Insulated Exhaust Vent Length (ft.) PVC PolyPro InnoFlue PVC PolyPro InnoFlue PVC PolyPro InnoFlue PVC PolyPro InnoFlue 32 to 21°F 2 in.11 9 14 12 18 15 N/A N/A 2-1/2 in.7 N/A 10 N/A 12 N/A N/A N/A 3 in.N/A N/A 6 6 8 8 13 13 20 to 1°F 2 in.N/A N/A 6 4 8 6 N/A N/A 2-1/2 in.N/A N/A N/A N/A N/A N/A N/A N/A 3 in.N/A N/A N/A N/A N/A N/A N/A N/A 0 to –20°F 2 in.N/A N/A N/A N/A N/A N/A N/A N/A 2-1/2 in.N/A N/A N/A N/A N/A N/A N/A N/A 3 in.N/A N/A N/A N/A N/A N/A N/A N/A NOTE - Concentric terminations are equivalent to 5 ft. of straight pipe and should be included when measuring total pipe length. 1 Refer to 99% Minimum Design Temperature table provided in the current edition of ASHRAE Handbook-Fundamentals. PolyPro® poly-propylene vent pipe is a registered trademark of DuraVent®. Innoflue® is a registered trademark of Centrotherm Eco Systems. SLP98UHV / Page 13 VENT LENGTHS - FEET STANDARD TERMINATION AT ELEVATION 0 - 7500 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 070 090 110 135 070 090 110 135 070 090 110 135 No. of 90 ELL 1 91 69 14 N/A 140 93 43 N/A 162 143 118 114 2 86 64 9 N/A 135 88 38 N/A 157 138 113 109 3 81 59 N/A N/A 130 83 33 N/A 152 133 108 104 4 76 54 N/A N/A 125 78 28 N/A 147 128 103 99 5 71 49 N/A N/A 120 73 23 N/A 142 123 98 94 6 66 44 N/A N/A 115 68 18 N/A 137 118 93 89 7 61 39 N/A N/A 110 63 13 N/A 132 113 88 84 8 56 34 N/A N/A 105 58 N/A N/A 127 108 83 79 9 51 29 N/A N/A 100 53 N/A N/A 122 103 78 74 10 46 24 N/A N/A 95 48 N/A N/A 117 98 73 69 STANDARD TERMINATION AT ELEVATION 7501 - 10,000 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 070 090 110 135 070 090 110 135 070 090 110 135 No. of 90 ELL 1 66 44 N/A N/A 115 68 N/A N/A 137 118 93 89 2 61 39 N/A N/A 110 63 N/A N/A 132 113 88 84 3 56 34 N/A N/A 105 58 N/A N/A 127 108 83 79 4 51 29 N/A N/A 100 53 N/A N/A 122 103 78 74 5 46 24 N/A N/A 95 48 N/A N/A 117 98 73 69 6 41 19 N/A N/A 90 43 N/A N/A 112 93 68 64 7 36 14 N/A N/A 85 38 N/A N/A 107 88 63 59 8 31 N/A N/A N/A 80 33 N/A N/A 102 83 58 54 9 26 N/A N/A N/A 75 28 N/A N/A 97 78 53 49 10 21 N/A N/A N/A 70 23 N/A N/A 92 73 48 44 CONCENTRIC TERMINATION ELEVATION 0 - 7500 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 070 090 110 135 070 090 110 135 070 090 110 135 No. of 90 ELL 1 83 67 12 N/A 130 89 39 N/A 146 139 114 105 2 78 62 7 N/A 125 84 34 N/A 141 134 109 100 3 73 57 N/A N/A 120 79 29 N/A 136 129 104 95 4 68 52 N/A N/A 115 74 24 N/A 131 124 99 90 5 63 47 N/A N/A 110 69 19 N/A 126 119 94 85 6 58 42 N/A N/A 105 64 14 N/A 121 114 89 80 7 53 37 N/A N/A 100 59 N/A N/A 116 109 84 75 8 48 32 N/A N/A 95 54 N/A N/A 111 104 79 70 9 43 27 N/A N/A 90 49 N/A N/A 106 99 74 65 10 38 22 N/A N/A 85 44 N/A N/A 101 94 69 60 CONCENTRIC TERMINATION ELEVATION 7501 - 10,000 ft. Pipe Size 2 in.2-1/2 in.3 in. Input 070 090 110 135 070 090 110 135 070 090 110 135 No. of 90 ELL 1 58 42 N/A N/A 105 64 N/A N/A 121 114 89 80 2 53 37 N/A N/A 100 59 N/A N/A 116 109 84 75 3 48 32 N/A N/A 95 54 N/A N/A 111 104 79 70 4 43 27 N/A N/A 90 49 N/A N/A 106 99 74 65 5 38 22 N/A N/A 85 44 N/A N/A 101 94 69 60 6 33 17 N/A N/A 80 39 N/A N/A 96 89 64 55 7 28 12 N/A N/A 75 34 N/A N/A 91 84 59 50 8 23 N/A N/A N/A 70 29 N/A N/A 86 79 54 45 9 18 N/A N/A N/A 65 24 N/A N/A 81 74 49 40 10 13 N/A N/A N/A 60 19 N/A N/A 76 69 44 35 SLP98UHV / Page 14 DIMENSIONS - INCHES (MM) - UPFLOW POSITION Model No.A B C D in.mm in.mm in.mm in.mm SLP98UH070XV36B 17-1/2 446 16-3/8 416 16 406 7-5/8 194 SLP98UH090XV36C SLP98UH090XV48C SLP98UH090XV60C SLP98UH110XV60C 21 533 19-7/8 505 19-1/2 495 9-3/8 238 SLP98UH135XV60D 24-1/2 622 23-3/8 594 23 584 11-1/8 283 AIR FLOW 6-9/16 (167)Left9 (229)Right 23(584) (19)3/4(19)1 Bottom ReturnAir Opening GAS PIPING INLET(Either Side) Side ReturnAir Opening(Either Side) 1 Bottom ReturnAir Opening EXHAUST AIROUTLET ELECTRICALINLET(Either Side) SUPPLY AIROPENING FRONT VIEW SIDE VIEW TOP VIEW A B 9/16 (14) C3/4 27-3/4(705)19-7/16(494) 23-1/2(597) 1-1/2(38) 6-1/2 (165)(Either Side) 33(838) 3-1/4(83) 1-15/16 (49) 14(356) 9/16(14) 12-5/8 (321)(Either Side) 2 OPTIONALSIDE RETURNAIR FILTER KIT(Either Side) 16(406) 14-3/4(375) 2 OPTIONALSIDE RETURNAIR FILTER KIT(Either Side) 5/8(16) 1 3-1/4(83) 23-3/4(603) 25(635) D 1-1/2 (38)Front Panel COMBUSTIONAIR INTAKE 2 (51)(Either Side) 1-7/8 (48) CONDENSATETRAP CONNECTION(Either Side) 2 Optional Side Return Air Filter Kit is not for usewith the Optional Return Air Base. 1 NOTE - 60C and 60D size units that require second stageair volumes over 1800 cfm must have oneof the following:1.Single side return air with transition, to accommodate20 x 25 x 1 in. cleanable air filter.Required to maintain proper air velocity.2.Single side return air with Optional Return Air Base3.Bottom return air.4.Return air from both sides.5.Bottom and one side return air.See Blower Performance Tables for additional information. Flue Condensate Trap Assembly Furnished for external field installation on either side of unit.(See installation instructions for additional information.) 7 (178) SLP98UHV / Page 15 DIMENSIONS - INCHES (MM) - HORIZONTAL POSITION D A TOP VIEW 27-3/4(705)33(838) 27-3/4(705) 27-3/4(705) A GAS PIPING INLET(Top or Bottom) RETURNAIROPENING ELECTRICAL INLET(Top or Bottom) SUPPLYAIROPENING FRONT VIEW TOP VIEW CA END VIEWEND VIEW 33(838) 27-3/4(705) 19-7/16(494)9/16(14) B 23-1/2(591)3-1/4 (95) (19) 2 (51)Top or Bottom 6-1/2 (165)Bottom 3-1/4 (83) EXHAUST AIROUTLET LEFT-HAND AIR DISCHARGE FRONT VIEWEND VIEW END VIEW AIRFLOW ELECTRICAL INLET(Top or Bottom) RIGHT-HAND AIR DISCHARGE 9/16(14)3/4 AIR FLOW AIRFLOW 19-7/16(494)9/16(14)B 9/16(14) D A (83)3-1/4 SUPPLYAIROPENING RETURNAIROPENING C 23-1/2(591)3-1/4(95) (19)3/4 AIRFLOW COMBUSTIONAIR INTAKE EXHAUST AIROUTLET COMBUSTIONAIR INTAKE 1-7/8 (48) 1-7/8(48) 6-9/16 (167) Top9 (229) Bottom 12-5/8 (321)Bottom CONDENSATETRAP CONNECTION 6-9/16 (167) Bottom 9 (229) Top 12-5/8 (321)Bottom 2 (51)Top or Bottom 6-1/2 (165)Bottom (Bottom) GAS PIPING INLET(Top or Bottom) CONDENSATETRAP CONNECTION(Bottom) 1-1/2 (38)Front Panel 1-1/2 (38)Front Panel Model No.A B C D in.mm in.mm in.mm in.mm SLP98UH070XV36B 17-1/2 446 16-3/8 416 16 406 7-5/8 194 SLP98UH090XV36C SLP98UH090XV48C SLP98UH090XV60C SLP98UH110XV60C 21 533 19-7/8 505 19-1/2 495 9-3/8 238 SLP98UH135XV60D 24-1/2 622 23-3/8 594 23 584 11-1/8 283 SLP98UHV / Page 16 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) 1-1/4HORIZONTAL (END) FILTER KIT FRONT VIEW 24-3/4(629) A B 23-1/2(597) 5/8(16) RETURNAIROPENING SIDE VIEW AIR FLOW AIR FILTER(Furnished) (32) 5/8(16) 5/8(16) 5/8(16) Optional Return Air Base(Upflow Applications Only - For use with B, C and D cabinets) NOTE- Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return airopening. The size of the opening must not extend beyond the markings on the furnace cabinet.2 To minimize pressure drop, the largest opening height possible, up to 14 in. (356 mm), is preferred. FURNACEFRONT AIR FLOW 1 Unit side return airOpening SIDE VIEW 3-1/4(83) 1 23 (584)Overall(Maximum) (584)23 3/4(19) 1 22-7/16(570)Overall(Maximum) SIDE RETURNAIR OPENINGS(Either Side) 5-5/8(143) 1 Minimum11 (279) 2 Maximum14 (356) (683)26-7/8 7-1/4(184) IF BASEIS USEDWITHOUTIAQ CABINET,A SINGLERETURN AIRPLENUMMUSTCOVER BOTHUNIT ANDRETURNAIR BASEOPENINGS INDOOR AIRQUALITYCABINET(PCO, FilterCabinet, etc.) AIR BASE OPTIONALRETURN CONDENSATETRAP(Furnished) 17-1/2 (446) B Width (50W98) 21 (533) C Width (50W99)24-1/2 (622) D Width (51W00) Furnace Cabinet Width Catalog Number A B in.mm in.mm B 87L96 18 457 16-3/4 425 C 87L97 21 533 18-3/4 476 D 87L98 25 635 23-3/4 603 SLP98UHV / Page 17 DIMENSIONS - INCHES (MM) - FURNACE/COIL COMBINED DIMENSIONS 33(838) A B UPFLOW POSITION Model No Cased Uncased (C33 only) A B A B CX34 C35/CX35 C33 in.mm in.mm in.mm in.mm - - -- - -C33-18A 12-1/2 318 45-1/2 1156 9-3/4 248 42-3/4 1086 CX34-19A-6F - - -C33-19A 16-1/2 419 49-1/2 1257 9-3/4 248 42-3/4 1086 - - -- - -C33-24A 16-1/2 419 49-1/2 1257 14 356 47 1194 CX34-18/24A-6F CX34-18/24B-6F CX34-18/24C-6F C35/CX35-18/24A-6F C35/CX35-18/24B-6F C33-24B C33-24C 16-1/2 419 49-1/2 1257 13-7/8 352 46-7/8 1191 CX34-25A-6F C35/CX35-24A-6F C33-25A 18-1/2 470 51-1/2 1308 16-1/4 413 49-1/4 1251 CX34-25B-6F C35/CX35-24B-6F C33-25B 18-1/2 470 51-1/2 1308 15-7/8 403 48-7/8 1241 CX34-30B-6F CX34-30C-6F - - -C33-30B C33-30C 20-1/2 521 53-1/2 1359 17-3/4 451 50-3/4 1289 CX34-30A-6F - - -C33-30A 20-1/2 521 53-1/2 1359 18 457 51 1295 CX34-31A-6F C35/CX35-30A-6F C33-31A 22-1/2 572 55-1/2 1410 21-1/4 540 54-1/4 1378 CX34-31B-6F C35/CX35-30B-6F C33-31B 22-1/2 572 55-1/2 1410 20-1/4 514 53-1/4 1353 CX34-36A-6F C35/CX35-30/36A-6F C33-36A 24-1/2 622 57-1/2 1461 22-1/8 562 55-1/8 1400 CX34-36B-6F C35/CX35-30/36B-6F C33-36B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394 CX34-36C-6F C35/CX35-30/36C-6F C33-36C 24-1/2 622 57-1/2 1461 21-1/4 540 54-1/4 1378 CX34-38A-6F C35/CX35-36A-6F C33-38A 24-1/2 622 57-1/2 1461 22-1/4 565 55-1/4 1403 CX34-38B-6F C35/CX35-36B-6F C33-38B 24-1/2 622 57-1/2 1461 22 559 55 1397 CX34-42B-6F - - -C33-42B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394 CX34-43B-6F C35/CX35-48B-6F C33-43B 27-1/2 699 60-1/2 1537 26-1/4 667 59-1/4 1505 CX34-43C-6F C35/CX35-48C-6F C33-43C 27-1/2 699 60-1/2 1537 25-3/4 654 58-3/4 1492 - - -- - -C33-44C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384 CX34-44/48B-6F - - -C33-48B 24-1/2 622 57-1/2 1461 22-1/8 562 55-1/8 1400 CX34-44/48C-6F - - -C33-48C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384 CX34-49C-6F C35/CX35-49C-6F C33-49C 29-1/2 749 62-1/2 1588 28-1/2 724 61-1/2 1562 CX34-50/60C-6FC35/CX35-50/60C-6F C33-50/60C27-1/2 699 60-1/2 1537 24-3/4 629 57-3/4 1467 CX34-60D-6F - - -C33-60D 25-1/2 648 58-1/2 1486 24-3/4 629 57-3/4 1467 CX34-62C-6F CX35-60C-6F C33-62C 31-1/2 800 64-1/2 1638 30-5/8 778 63-5/8 1616 CX34-62D-6F CX35-60D-6F C33-62D 29-1/2 749 62-1/2 1588 28-3/4 730 61-3/4 1568 HORIZONTAL POSITION Model Number A B in.mm in.mm CH33-18A-2F 21-1/2 546 54-1/2 1384 CH33-24/30A-2F CH33-36A-2F CH33-36B-2F CH33-36C-2F CH33-42B-2F CH33-48C-2F CH33-60D-2F 26-1/2 673 59-1/2 1511 CH33-44/48B-2F CH33-50/60C-2F CH33-62D-2F 31-1/2 800 64-1/2 1638 33(838) A B SLP98UHV / Page 18 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) FLUSH-MOUNT VENT TERMINATION KIT 51W11 (US) or 51W12 (CANADA) With 2 or 2-1/2 in. (51 or 64 mm) PVC pipe With 3 in. (76 mm) PVC pipe 3 (76) PVC pipe2 (51) PVC pipe 2-1/2 (64) PVC pipe When required UseField Provided2-1/2 to 2 in. (64 to 51 mm)Coupling Seal all openings(typical) 2-3/8 (60) 12 (305) minimum(recommended) Intake (Behind Plate) Exhaust Intake (Behind Plate) Exhaust NOTE - PVC pipe and fittings are not furnished and must be field furnished. SLP98UHV / Page 19 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) CONCENTRIC WALLTERMINATION APPLICATIONS INTAKEAIREXHAUSTAIR INTAKEAIRINTAKEAIR EXHAUSTAIR OUTSIDEWALL 12 (305)MinimumAbove Gradeor Average Snow Accumulation 12 (305)MinimumAbove AverageSnowAccumulation SHEET METAL STRAP (Clamp and sheet metal strap must be field installed to supportthe weight of the termination kit.) FLASHING(Not Furnished) CLAMP GRADE 6-1/2(165) (Field Supplied)ELBOW INTAKE AIR EXHAUSTAIR TERMINATIONASSEMBLY(Furnished) 71M80 / 69M29 / 44W92 - 2 inch kits60L46 / 44W93 - 3 inch kitsSee Installation Instructions for additional information. CONCENTRIC ROOFTERMINATION APPLICATIONS CLAMP(Not Furnished) 6(152) A 3-1/2 (89) - 2 in. kits4-1/2 (114) - 3 in. kits Outdoor Exhaust Acceleratorincluded with 71M80/44W92 NOTE - Typical illustration for dimensions only. Design may vary depending on kit ordered. Cat. No.A B in.mm in.mm 71M80 69M29 33-3/8 848 16-3/4 425 44W92(Canada)29 737 15-1/2 394 60L46 38-7/8 987 21-3/16 538 44W93(Canada)36-1/8 918 19-1/2 495 Note - Field provided reducer may be required to adapt larger vent pipe size to termination. B 8 in. (203 mm)minimum 6 in. (152 mm) maximum DIRECT VENT APPLICATION WALL ASSEMBLY TERMINATION KIT - RING KIT 15F74 - 2 inch (51 mm)See Installation Instructions for additional information. 12 in. (305 mm) - 2 in. (51 mm) dia. exhaust pipe20 in. (508 mm) - 3 in. (76 mm) dia. exhaust pipe maximum length without support NOTE - 12 in. (305 mm) minimum height aboveaverage snow accumulation(from bottom of vent pipe). Note - Field provided reducer may be required to adapt larger vent pipe size to termination. SLP98UHV / Page 20 OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM) 12 (305) MinimumAbove Grade or AverageSnow Accumulation 1/2 (13)FOAM INSULATION(Field Furnished) 5(127) 5-1/2 (140) EXHAUSTAIR INTAKEAIR GRADE 12 (305) INTAKEAIR EXHAUSTAIR GRADE 8 (203) MIN. Between Ends of Exhaust and Intake Pipe 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. ExhaustWALL SUPPORT 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust 12 (305) MinimumAbove Grade or Average Snow Accumulation WALL TERMINATION KITS (CLOSE-COUPLE)EXTENDED VENT FOR GRADE CLEARANCE2 inch (51 mm) 22G44 (US) 3 inch (76 mm) 44J40 (US)See Installation Instructions for additional information. 6 (152) Maximum If Intake and Exhaust Pipe is less than12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed. 8 (203) MIN. Note - Field provided reducer may be required to adapt larger vent pipe size to termination. 12 (305) MinimumAbove Grade or AverageSnow Accumulation 1/2 (13)FOAM INSULATION(Field Furnished) 5(127) 5-1/2 (140) EXHAUSTAIR INTAKEAIR GRADE 12 (305) INTAKEAIR EXHAUSTAIR GRADE WALL SUPPORT 12 (305) MinimumAbove Grade or Average Snow Accumulation WALL TERMINATION KITS (CLOSE-COUPLE)EXTENDED VENT FOR GRADE CLEARANCE2 inch (51 mm) 30G28 (WTK Canada)3 inch (76 mm) 81J20 (WTK Canada) See Installation Instructions for additional information. 6 (152) Maximum If Intake and Exhaust Pipe is less than12 in. (305 mm) above snow accumulation or other obstructions,field fabricated piping must be installed. 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust 12 (305) MAX. for 2 (51) Dia. Exhaust20 (508) MAX. for 3 (76) Dia. Exhaust Note - Field provided reducer may be required to adapt larger vent pipe size to termination. 6 (152) MIN. 6 (152) MIN. SLP98UHV / Page 21 BLOWER DATA SLP98UH070XV36B BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 489 538 636 735 833 931 1030 1128 Increase (+7.5%) Heat CFM 450 496 588 680 772 864 956 1048 Default Heat CFM 410 453 539 624 710 796 881 967 Decrease (-7.5% ) Heat CFM 380 419 498 578 657 736 815 895 Decrease (-15% ) Heat CFM 349 385 458 531 604 676 749 822 SLP98UH070XV36B BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 22 36 51 60 80 95 101 117 138 68 88 105 129 152 169 198 214 231 244 274 Medium-Low 37 57 75 89 106 127 148 168 182 121 144 168 192 211 243 262 287 305 329 358 Medium-High 62 85 97 122 144 164 180 203 220 213 231 259 285 311 328 357 374 397 419 445 High 88 115 132 155 176 203 233 240 274 304 322 359 379 411 442 458 486 502 527 554 Default Cool CFM Low 16 29 42 55 71 82 98 112 120 52 69 86 107 122 146 165 183 199 212 229 Medium-Low 26 41 63 79 88 112 128 145 159 89 108 135 151 174 198 223 247 268 288 298 Medium-High 39 62 77 96 117 140 156 180 196 151 173 201 225 243 266 289 313 339 368 383 High 65 84 104 125 148 166 178 206 225 237 256 284 303 328 343 374 395 421 435 454 Decrease (-10%) Cool CFM Low 11 21 35 53 64 75 82 95 113 34 50 67 86 106 121 141 159 174 186 201 Medium-Low 21 36 51 66 81 92 107 127 141 64 85 100 114 145 160 182 206 219 237 251 Medium-High 35 48 66 82 104 118 137 146 159 101 125 143 171 193 211 242 258 282 304 330 High 43 60 82 100 123 144 159 174 197 161 188 211 229 258 277 307 327 354 379 404 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 600 740 840 970 860 1060 1215 1365 Default Cool CFM 555 665 770 855 810 960 1130 1265 Decrease (-10%) Cool CFM 500 600 680 790 705 840 1005 1140 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 22 BLOWER DATA SLP98UH070XV36B BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 484 531 625 718 812 906 999 1093 Increase (+7.5%) Heat CFM 446 490 579 667 756 845 933 1022 Default Heat CFM 407 449 533 616 700 784 867 951 Decrease (-7.5% ) Heat CFM 377 413 487 561 635 709 783 857 Decrease (-15% ) Heat CFM 346 378 442 506 571 635 699 763 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 590 705 805 955 840 1050 1205 1355 Default Cool CFM 540 640 725 820 750 945 1130 1230 Decrease (-10%) Cool CFM 500 580 665 720 685 805 990 1110 SLP98UH070XV36B BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 17 29 48 61 73 94 100 123 130 63 84 104 117 142 160 174 208 215 245 255 Medium-Low 30 50 66 79 107 128 137 159 178 121 137 165 195 213 239 257 283 303 329 342 Medium-High 51 70 92 106 127 150 170 184 207 195 214 243 268 290 324 348 370 387 409 434 High 88 109 134 150 184 201 221 243 265 290 309 344 372 399 421 445 474 495 520 532 Default Cool CFM Low 12 25 38 52 66 83 96 105 117 43 65 75 98 120 139 152 170 192 212 228 Medium-Low 22 41 55 70 86 103 123 141 154 88 106 130 150 173 197 220 239 259 276 297 Medium-High 36 55 75 90 107 129 152 167 184 142 161 187 211 239 263 287 307 332 352 369 High 57 76 99 116 135 153 176 197 213 220 236 267 294 323 342 364 382 411 436 455 Decrease (-10%) Cool CFM Low 8 22 32 50 60 77 86 100 116 31 48 63 83 102 122 137 150 166 188 203 Medium-Low 19 32 47 63 77 93 103 120 133 53 75 91 111 129 152 169 188 210 227 251 Medium-High 25 42 58 74 90 109 131 143 154 101 120 141 170 190 215 233 256 274 298 317 High 37 56 76 95 115 135 153 173 192 157 177 201 224 254 277 303 321 346 362 385 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 23 BLOWER DATA SLP98UH070XV36B BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 471 519 614 709 805 900 996 1091 Increase (+7.5%) Heat CFM 435 480 570 660 751 841 931 1021 Default Heat CFM 399 441 526 611 696 781 866 951 Decrease (-7.5% ) Heat CFM 369 408 486 564 643 721 799 877 Decrease (-15% ) Heat CFM 339 375 446 517 589 660 732 803 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 595 715 815 950 855 1045 1205 1350 Default Cool CFM 520 655 755 840 790 945 1090 1255 Decrease (-10%) Cool CFM 490 595 670 745 720 845 985 1130 SLP98UH070XV36B BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 18 32 46 61 76 89 104 115 133 64 83 95 120 141 159 175 203 208 234 246 Medium-Low 34 52 69 86 104 126 141 160 174 109 131 150 179 204 219 239 268 283 313 335 Medium-High 63 82 98 115 138 153 173 187 209 177 197 227 246 273 311 328 354 383 402 408 High 88 107 131 148 175 192 217 235 253 255 281 312 346 382 402 430 465 489 506 533 Default Cool CFM Low 12 25 37 55 66 82 94 105 121 43 61 76 99 121 133 162 169 189 211 224 Medium-Low 25 40 55 74 89 109 120 136 150 76 96 112 138 162 186 207 232 243 262 281 Medium-High 41 61 75 98 115 135 151 173 189 129 150 177 198 227 247 272 301 324 332 369 High 63 86 99 122 139 159 180 204 216 209 227 254 282 298 324 341 364 395 413 428 Decrease (-10%) Cool CFM Low 9 20 35 48 59 75 86 94 110 29 43 63 84 99 113 131 144 164 185 197 Medium-Low 16 32 45 62 75 90 103 119 138 56 71 101 112 131 158 168 184 207 235 245 Medium-High 28 43 63 77 98 115 132 145 162 88 107 129 154 183 204 214 245 263 281 308 High 46 61 86 100 121 136 153 172 193 142 163 187 216 236 261 279 301 325 356 375 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 24 BLOWER DATA SLP98UH090XV36C BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 687 734 827 921 1014 1108 1201 1295 Increase (+7.5%) Heat CFM 654 697 782 867 953 1038 1123 1209 Default Heat CFM 621 660 737 814 891 968 1045 1122 Decrease (-7.5% ) Heat CFM 581 616 687 757 828 899 970 1041 Decrease (-15% ) Heat CFM 540 572 637 701 766 830 895 959 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 625 710 830 950 875 1040 1210 1360 Default Cool CFM 565 670 760 860 800 945 1100 1240 Decrease (-10%) Cool CFM 520 610 685 785 720 840 970 1115 SLP98UH090XV36C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 19 33 51 67 81 97 113 128 144 47 64 90 111 127 153 174 193 215 234 250 Medium-Low 35 52 76 90 108 130 146 166 185 87 114 130 158 184 205 227 252 278 301 321 Medium-High 51 70 92 117 138 155 181 199 219 146 170 199 223 246 277 303 329 357 379 399 High 69 94 113 133 152 177 194 222 246 225 250 277 308 329 362 391 411 442 465 489 Default Cool CFM Low 14 31 44 59 75 88 104 125 137 37 54 74 94 114 135 152 175 187 209 223 Medium-Low 29 46 63 80 95 114 133 146 164 65 87 108 130 152 173 196 222 236 262 283 Medium-High 39 56 78 97 117 137 155 175 192 102 127 152 175 202 228 246 279 306 328 345 High 46 68 86 111 126 154 174 194 214 167 184 218 253 272 301 332 360 381 402 421 Decrease (-10%) Cool CFM Low 11 27 39 57 70 84 99 113 131 26 45 61 81 96 118 134 152 169 189 205 Medium-Low 23 39 53 71 87 103 118 133 148 44 60 85 107 127 150 169 186 207 226 247 Medium-High 24 43 56 79 97 111 129 149 165 75 101 117 140 160 182 215 235 255 275 296 High 33 51 69 94 111 131 150 170 186 112 134 160 186 220 236 264 293 311 335 363 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 25 BLOWER DATA SLP98UH090XV36C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 657 702 792 881 971 1061 1150 1240 Increase (+7.5%) Heat CFM 631 673 757 841 926 1010 1094 1178 Default Heat CFM 605 644 723 802 880 959 1037 1116 Decrease (-7.5% ) Heat CFM 574 608 676 745 814 882 951 1020 Decrease (-15% ) Heat CFM 542 571 630 689 747 806 864 923 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 610 705 795 920 840 1015 1165 1300 Default Cool CFM 560 640 715 810 770 910 1050 1190 Decrease (-10%) Cool CFM 525 605 665 725 695 795 945 1110 SLP98UH090XV36C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 13 30 46 62 75 93 110 129 143 42 60 83 101 122 144 163 181 206 219 241 Medium-Low 25 45 62 80 96 115 134 151 173 78 104 122 144 170 195 215 239 265 283 308 Medium-High 36 55 79 95 117 139 156 178 199 133 154 175 213 236 269 282 309 336 357 381 High 62 83 105 128 148 163 193 210 234 210 229 259 291 317 344 366 391 415 441 466 Default Cool CFM Low 9 28 38 55 71 83 100 116 135 28 48 65 86 104 124 142 164 182 199 219 Medium-Low 20 38 52 69 83 102 120 135 152 59 81 100 125 142 162 182 204 229 248 269 Medium-High 26 46 63 83 101 117 141 157 178 95 118 142 165 192 213 244 264 288 314 329 High 39 59 81 98 121 143 161 180 202 149 171 199 229 257 285 306 330 359 389 403 Decrease (-10%) Cool CFM Low 8 23 35 52 66 80 95 108 121 21 41 56 71 91 110 126 144 164 179 197 Medium-Low 12 29 44 59 75 92 111 126 140 35 56 73 95 115 137 155 176 198 216 235 Medium-High 20 37 56 71 86 104 122 143 155 70 89 114 135 157 175 199 225 242 266 282 High 27 47 67 82 102 124 142 160 181 104 125 150 178 207 232 251 273 297 321 350 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 26 BLOWER DATA SLP98UH090XV36C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 677 721 810 899 988 1076 1165 1254 Increase (+7.5%) Heat CFM 639 679 760 842 923 1004 1085 1167 Default Heat CFM 600 637 711 784 858 932 1005 1079 Decrease (-7.5% ) Heat CFM 573 606 673 740 806 873 939 1006 Decrease (-15% ) Heat CFM 546 576 635 695 754 814 873 933 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 605 715 810 930 850 995 1165 1305 Default Cool CFM 570 660 735 820 775 905 1050 1205 Decrease (-10%) Cool CFM 530 600 670 725 710 800 945 1070 SLP98UH090XV36C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 12 29 43 59 75 92 111 123 139 41 62 86 102 123 145 165 185 205 229 253 Medium-Low 24 42 61 76 97 112 132 150 169 79 108 126 148 174 190 218 248 273 294 316 Medium-High 38 56 81 99 115 138 157 176 199 131 152 184 208 237 264 289 320 339 361 390 High 61 85 104 127 144 171 192 212 239 205 226 258 283 312 344 365 393 410 437 466 Default Cool CFM Low 9 26 37 54 67 83 97 112 130 30 50 72 87 108 127 149 167 184 209 226 Medium-Low 19 37 53 67 83 101 119 135 153 62 86 101 129 144 165 189 215 232 251 275 Medium-High 27 48 65 82 101 119 139 161 177 91 114 140 163 195 220 239 265 289 315 339 High 42 62 85 99 121 143 162 183 203 149 167 201 228 258 289 316 333 355 389 403 Decrease (-10%) Cool CFM Low 8 23 35 51 62 77 91 104 119 25 45 61 75 91 112 131 147 166 184 198 Medium-Low 13 29 46 60 78 93 110 125 140 40 61 81 103 119 143 162 179 204 220 245 Medium-High 22 41 57 70 88 109 127 144 159 70 92 120 133 165 178 203 231 246 274 301 High 29 50 69 83 106 123 143 164 183 101 124 151 180 203 227 257 276 306 326 358 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 250 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 27 BLOWER DATA SLP98UH090XV48C BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 769 835 968 1101 1234 1367 1500 1633 Increase (+7.5%) Heat CFM 713 776 902 1028 1155 1281 1407 1534 Default Heat CFM 656 716 836 955 1075 1195 1314 1434 Decrease (-7.5% ) Heat CFM 595 652 767 882 997 1112 1227 1342 Decrease (-15% ) Heat CFM 534 589 699 809 919 1029 1139 1249 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 840 1005 1155 1315 1165 1375 1580 1770 Default Cool CFM 780 915 1045 1190 1075 1265 1440 1645 Decrease (-10%) Cool CFM 690 835 955 1070 935 1145 1320 1465 SLP98UH090XV48C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 50 67 83 108 127 134 163 175 192 111 132 163 199 222 256 278 310 335 354 384 Medium-Low 64 91 108 136 168 193 207 234 263 182 212 246 275 317 340 370 407 434 464 503 Medium-High 99 127 147 188 213 244 271 301 316 242 273 330 352 415 454 493 534 572 604 646 High 152 179 211 252 275 308 339 370 393 354 386 441 519 550 599 645 678 727 775 817 Default Cool CFM Low 39 52 72 88 111 118 142 149 169 85 110 134 154 190 218 236 259 298 316 327 Medium-Low 55 83 96 114 131 167 179 200 227 140 168 189 226 268 289 320 363 381 398 430 Medium-High 75 100 132 148 174 212 231 259 280 196 228 271 305 329 370 399 448 475 514 545 High 111 139 167 201 232 258 299 316 343 271 306 362 396 446 506 535 575 617 663 701 Decrease (-10%) Cool CFM Low 27 41 59 77 95 101 124 137 156 63 86 103 129 152 179 197 222 241 259 289 Medium-Low 47 62 84 101 124 139 154 173 191 104 132 149 182 220 242 276 290 316 351 371 Medium-High 57 85 103 118 148 165 183 219 242 150 173 205 245 278 318 351 374 411 424 455 High 79 105 135 162 182 220 238 271 296 206 242 284 319 363 385 424 467 520 541 581 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 28 BLOWER DATA SLP98UH090XV48C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 747 812 943 1073 1204 1334 1465 1595 Increase (+7.5%) Heat CFM 698 759 882 1005 1127 1250 1372 1495 Default Heat CFM 649 706 821 936 1051 1165 1280 1395 Decrease (-7.5% ) Heat CFM 589 644 755 867 978 1089 1200 1312 Decrease (-15% ) Heat CFM 528 582 690 797 905 1013 1120 1228 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 820 1005 1135 1290 1140 1340 1525 1725 Default Cool CFM 755 880 1025 1150 1040 1235 1395 1565 Decrease (-10%) Cool CFM 680 815 925 1065 910 1120 1275 1400 SLP98UH090XV48C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 43 65 85 96 119 134 156 179 199 102 131 155 189 216 249 282 304 331 359 387 Medium-Low 66 95 113 140 164 189 212 242 268 173 196 242 271 306 337 362 405 430 460 493 Medium-High 95 126 151 180 210 242 277 302 320 243 277 316 371 412 457 492 534 566 605 651 High 143 166 203 243 282 309 333 368 389 368 410 453 511 562 604 651 690 730 771 809 Default Cool CFM Low 36 48 73 86 108 120 140 152 168 75 101 125 156 178 215 244 259 288 320 339 Medium-Low 52 75 95 110 130 161 176 201 216 129 154 190 218 257 295 322 346 377 404 434 Medium-High 70 94 125 146 172 198 230 252 275 190 222 270 299 325 368 398 439 470 508 549 High 100 131 162 197 228 260 298 328 347 275 310 359 400 445 469 525 562 597 642 682 Decrease (-10%) Cool CFM Low 32 45 58 80 97 110 121 133 154 62 87 109 129 152 173 199 221 250 266 295 Medium-Low 45 63 82 99 119 137 150 171 193 95 124 150 180 207 240 269 297 325 356 375 Medium-High 55 82 101 119 145 167 192 213 239 148 177 205 244 286 309 346 370 402 431 467 High 76 101 137 160 188 218 245 271 302 198 239 274 308 349 384 426 471 500 542 576 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 29 BLOWER DATA SLP98UH090XV48C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 764 828 956 1084 1213 1341 1469 1597 Increase (+7.5%) Heat CFM 705 766 888 1010 1132 1255 1377 1499 Default Heat CFM 645 703 819 936 1052 1168 1285 1401 Decrease (-7.5% ) Heat CFM 594 650 762 874 986 1099 1211 1323 Decrease (-15% ) Heat CFM 542 596 704 812 921 1029 1137 1245 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 840 955 1120 1280 1160 1360 1530 1740 Default Cool CFM 775 910 1010 1170 1060 1240 1400 1590 Decrease (-10%) Cool CFM 695 815 930 1045 925 1130 1295 1440 SLP98UH090XV48C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 40 60 80 96 115 133 151 176 192 94 127 151 180 207 241 274 303 340 358 381 Medium-Low 58 87 108 132 158 188 212 240 264 166 195 233 269 300 328 356 394 426 455 496 Medium-High 91 126 145 169 205 228 255 288 320 234 273 314 354 403 431 484 514 571 599 632 High 134 163 195 231 264 297 320 359 381 337 378 426 470 518 557 604 654 684 722 768 Default Cool CFM Low 36 47 70 88 103 120 139 146 167 75 100 130 149 183 212 238 260 293 315 337 Medium-Low 51 75 93 115 135 158 187 201 222 132 156 192 220 259 284 319 343 376 404 423 Medium-High 59 92 112 141 166 200 228 259 281 183 215 262 284 315 348 387 427 464 494 523 High 97 130 156 191 215 256 283 310 343 253 292 331 379 414 462 497 546 575 613 661 Decrease (-10%) Cool CFM Low 26 41 55 73 88 104 120 134 149 56 84 104 123 149 174 199 224 248 268 290 Medium-Low 41 62 79 98 117 132 154 172 195 94 122 146 177 208 239 264 295 320 352 368 Medium-High 50 75 95 120 147 164 187 209 243 140 170 197 234 263 301 327 357 377 412 453 High 72 102 125 154 178 208 234 262 293 196 235 264 302 332 377 413 441 482 518 548 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 250 cfm. SLP98UHV / Page 30 BLOWER DATA SLP98UH090XV60C BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 583 665 830 995 1159 1324 1488 1653 Increase (+7.5%) Heat CFM 540 618 774 930 1085 1241 1397 1553 Default Heat CFM 497 571 718 865 1012 1159 1306 1453 Decrease (-7.5% ) Heat CFM 439 507 644 781 917 1054 1191 1328 Decrease (-15% ) Heat CFM 380 443 570 697 823 950 1076 1203 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1050 1270 1445 1620 1590 1815 2010 2195 Default Cool CFM 975 1120 1295 1460 1460 1645 1845 2010 Decrease (-10%) Cool CFM 865 1010 1120 1290 1320 1500 1645 1860 SLP98UH090XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 79 107 135 157 188 215 245 273 293 264 284 346 390 425 453 503 538 580 607 640 Medium-Low 120 152 188 220 264 298 328 365 389 393 422 484 554 582 629 690 737 778 805 859 Medium-High 191 221 272 304 333 372 414 452 481 582 604 679 726 778 839 887 921 970 1008 1039 High 264 284 346 390 425 453 503 538 580 805 845 888 949 1009 1048 1109 1133 1166 1196 1191 Default Cool CFM Low 60 86 112 129 152 179 202 232 252 202 218 270 315 351 387 419 452 479 512 546 Medium-Low 90 123 149 174 209 235 264 293 331 286 340 389 378 430 503 553 580 636 661 699 Medium-High 137 166 203 240 279 307 342 372 402 454 470 553 588 641 695 725 764 820 849 880 High 202 218 270 315 351 387 419 452 479 559 590 649 728 789 823 896 926 974 1030 1062 Decrease (-10%) Cool CFM Low 47 62 85 107 132 148 166 179 201 142 168 212 247 285 313 348 373 409 450 472 Medium-Low 69 97 119 139 165 189 214 244 265 226 245 295 339 374 410 451 474 497 549 566 Medium-High 90 123 149 174 209 235 264 293 331 301 335 385 430 471 510 557 607 632 677 713 High 133 167 200 232 274 311 340 371 405 454 470 553 588 641 695 725 764 820 849 880 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 31 BLOWER DATA SLP98UH090XV60C BLOWER PERFORMANCE (less filter) Single Side Return Air - Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in order to maintain proper air velocity across the filter. HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 609 684 835 986 1136 1287 1437 1588 Increase (+7.5%) Heat CFM 551 623 769 914 1059 1205 1350 1496 Default Heat CFM 492 562 702 842 983 1123 1263 1403 Decrease (-7.5% ) Heat CFM 436 502 633 765 896 1028 1159 1291 Decrease (-15% ) Heat CFM 380 441 564 687 810 932 1055 1178 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1040 1225 1380 1550 1555 1715 1920 2135 Default Cool CFM 960 1085 1225 1415 1430 1565 1790 1980 Decrease (-10%) Cool CFM 840 990 1085 1250 1280 1450 1580 1790 SLP98UH090XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 66 95 123 147 173 204 233 260 290 241 273 315 357 405 433 466 519 547 584 620 Medium-Low 108 139 173 210 248 283 315 342 376 332 374 428 489 518 568 631 665 719 762 813 Medium-High 159 192 233 272 314 359 386 421 457 518 557 601 675 713 772 819 873 913 949 987 High 241 273 315 357 405 433 466 519 547 713 750 822 866 946 986 1042 1085 1116 1144 1184 Default Cool CFM Low 55 81 101 126 144 165 194 217 243 181 204 251 292 323 369 403 444 474 496 525 Medium-Low 75 109 134 159 194 226 255 282 316 270 304 361 389 433 473 506 547 602 642 665 Medium-High 108 144 180 211 248 293 320 357 391 374 410 467 512 583 618 670 723 778 797 839 High 181 204 251 292 323 369 403 444 474 542 579 642 684 743 809 843 883 942 991 1019 Decrease (-10%) Cool CFM Low 36 56 71 102 119 141 161 179 198 113 142 181 221 255 300 325 352 395 424 456 Medium-Low 57 84 110 133 151 175 210 234 257 170 208 209 303 343 382 417 455 489 509 552 Medium-High 75 109 134 159 194 226 255 282 316 264 299 357 387 426 478 501 551 586 635 682 High 113 142 181 221 255 300 325 352 395 374 410 467 512 583 618 670 723 778 797 839 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 32 BLOWER DATA SLP98UH090XV60C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 611 686 837 987 1138 1288 1439 1589 Increase (+7.5%) Heat CFM 554 626 771 916 1060 1205 1349 1494 Default Heat CFM 497 566 705 844 983 1121 1260 1399 Decrease (-7.5% ) Heat CFM 436 502 633 764 895 1026 1157 1288 Decrease (-15% ) Heat CFM 375 437 560 683 806 930 1053 1176 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1035 1230 1390 1565 1560 1740 1940 2145 Default Cool CFM 950 1085 1235 1405 1410 1585 1785 1975 Decrease (-10%) Cool CFM 855 995 1085 1235 1260 1430 1595 1785 SLP98UH090XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 66 96 123 140 167 199 223 253 282 238 262 319 353 395 431 467 499 531 576 614 Medium-Low 106 136 174 202 240 269 305 335 364 331 375 420 463 523 564 610 661 719 742 780 Medium-High 153 194 224 265 302 340 379 412 453 502 533 602 651 714 772 809 856 899 952 989 High 238 262 319 353 395 431 467 499 531 703 745 799 877 932 969 1020 1070 1122 1142 1169 Default Cool CFM Low 53 76 101 120 143 162 187 208 238 172 203 240 278 316 354 394 420 459 489 519 Medium-Low 76 110 132 153 189 222 246 274 304 260 290 344 383 415 468 498 533 580 619 653 Medium-High 110 142 178 207 247 285 313 346 375 354 396 445 500 546 604 652 695 747 766 837 High 172 203 240 278 316 354 394 420 459 539 575 623 692 733 798 831 885 926 980 997 Decrease (-10%) Cool CFM Low 36 53 73 101 121 141 159 177 196 119 159 186 211 248 289 318 353 389 418 446 Medium-Low 54 83 106 129 148 175 204 231 258 185 215 250 294 334 377 407 450 472 503 545 Medium-High 76 110 132 153 189 222 246 274 304 263 302 351 383 419 474 497 548 587 636 663 High 119 159 186 211 248 289 318 353 389 379 422 472 519 571 623 659 716 759 804 841 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 33 BLOWER DATA SLP98UH110XV60C BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 767 861 1049 1237 1424 1612 1800 1988 Increase (+7.5%) Heat CFM 738 825 1000 1174 1349 1524 1699 1874 Default Heat CFM 708 789 951 1112 1274 1436 1597 1759 Decrease (-7.5% ) Heat CFM 655 731 883 1035 1187 1339 1491 1644 Decrease (-15% ) Heat CFM 602 673 816 958 1101 1243 1386 1528 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1060 1245 1345 1545 1560 1740 1930 2125 Default Cool CFM 970 1145 1265 1395 1405 1565 1775 1945 Decrease (-10%) Cool CFM 885 1025 1110 1250 1270 1425 1610 1770 SLP98UH110XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 81 113 135 165 200 228 251 280 315 220 254 300 346 385 432 472 511 560 600 610 Medium-Low 119 147 179 210 241 273 309 331 358 345 386 414 475 516 547 594 637 681 714 748 Medium-High 157 191 225 265 304 331 377 405 435 492 536 573 623 666 711 761 804 842 891 918 High 220 254 300 346 385 432 472 511 560 675 699 767 839 876 915 973 1033 1062 1115 1134 Default Cool CFM Low 60 88 114 137 167 187 219 244 276 163 196 231 266 309 348 388 421 451 489 512 Medium-Low 81 108 147 173 195 231 257 288 326 232 263 314 353 412 445 490 516 557 596 649 Medium-High 122 145 182 215 246 286 306 333 360 372 401 449 498 541 577 643 672 695 744 765 High 163 196 231 266 309 348 388 421 451 497 539 579 646 681 734 773 817 851 904 957 Decrease (-10%) Cool CFM Low 45 62 96 116 132 153 179 199 227 124 146 189 215 245 279 316 331 373 396 423 Medium-Low 56 85 115 134 159 185 215 251 270 163 195 243 270 314 353 397 414 470 496 535 Medium-High 80 114 141 161 203 230 256 294 318 248 274 324 386 416 470 494 539 583 620 652 High 124 146 189 215 245 279 316 331 373 377 413 457 502 548 583 629 684 705 753 783 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. BLOWER DATA SLP98UH110XV60C BLOWER PERFORMANCE (less filter) Single Side Return Air - Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in order to maintain proper air velocity across the filter. HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 733 825 1009 1194 1378 1562 1747 1931 Increase (+7.5%) Heat CFM 708 794 967 1139 1312 1484 1657 1829 Default Heat CFM 683 763 924 1085 1245 1406 1566 1727 Decrease (-7.5% ) Heat CFM 632 707 857 1007 1157 1307 1457 1608 Decrease (-15% ) Heat CFM 580 650 790 929 1069 1209 1348 1488 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1050 1195 1315 1495 1515 1710 1870 2065 Default Cool CFM 960 1095 1220 1355 1360 1555 1755 1890 Decrease (-10%) Cool CFM 850 985 1095 1220 1215 1400 1555 1755 SLP98UH110XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 67 95 124 148 172 212 241 260 287 215 247 287 338 378 412 448 497 535 557 600 Medium-Low 112 140 176 200 232 262 303 323 350 332 360 420 459 500 551 601 636 666 705 747 Medium-High 151 191 221 251 283 321 356 392 431 478 513 560 611 672 701 750 801 843 865 916 High 215 247 287 338 378 412 448 497 535 661 699 751 813 856 901 955 1005 1047 1088 1131 Default Cool CFM Low 53 82 99 128 153 172 199 231 251 156 198 217 270 297 328 371 403 440 474 515 Medium-Low 81 109 136 165 198 229 259 281 307 244 272 327 361 410 446 494 527 564 600 636 Medium-High 113 144 174 209 233 269 304 323 362 387 415 458 513 552 602 644 680 719 763 807 High 156 198 217 270 297 328 371 403 440 505 541 594 624 675 727 780 812 843 886 925 Decrease (-10%) Cool CFM Low 43 62 84 111 125 152 167 189 211 114 137 183 206 235 264 303 330 358 388 417 Medium-Low 62 86 115 134 162 187 219 238 262 165 199 236 281 308 357 381 426 466 492 531 Medium-High 81 109 136 165 198 229 259 281 307 239 269 326 354 413 463 498 523 573 601 656 High 114 137 183 206 235 264 303 330 358 387 415 458 513 552 602 644 680 719 744 776 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 35 BLOWER DATA SLP98UH110XV60C BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 805 893 1068 1243 1419 1594 1770 1945 Increase (+7.5%) Heat CFM 729 814 986 1157 1329 1500 1672 1843 Default Heat CFM 652 736 903 1071 1238 1406 1573 1741 Decrease (-7.5% ) Heat CFM 603 680 833 986 1139 1293 1446 1599 Decrease (-15% ) Heat CFM 554 623 762 901 1040 1179 1318 1457 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1020 1205 1305 1480 1485 1725 1885 2070 Default Cool CFM 955 1080 1205 1360 1365 1565 1720 1905 Decrease (-10%) Cool CFM 865 980 1080 1215 1220 1390 1545 1740 SLP98UH110XV60C BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 67 95 127 145 178 201 235 260 289 197 235 271 319 349 391 435 462 509 547 583 Medium-Low 111 139 173 194 228 259 288 314 343 316 348 399 440 485 523 571 604 646 689 717 Medium-High 142 179 207 237 275 305 340 378 407 463 499 549 579 628 674 721 758 803 840 859 High 197 235 271 319 349 391 435 462 509 618 641 712 776 818 857 914 963 992 1042 1079 Default Cool CFM Low 53 81 100 124 147 173 201 223 248 149 188 215 251 289 321 350 391 422 469 490 Medium-Low 77 104 135 160 193 217 246 276 302 229 259 303 347 391 427 462 501 532 576 605 Medium-High 110 141 170 200 230 256 292 322 346 334 363 419 459 510 546 586 635 679 704 739 High 149 188 215 251 289 321 350 391 422 480 523 558 607 651 707 740 782 838 863 899 Decrease (-10%) Cool CFM Low 45 64 89 106 129 148 173 191 211 111 140 171 202 231 259 291 320 347 379 410 Medium-Low 57 85 111 133 155 182 215 239 262 158 194 224 264 304 340 369 403 445 481 510 Medium-High 77 104 135 160 193 217 246 276 302 229 261 315 344 391 431 470 505 544 586 623 High 111 140 171 202 231 259 291 320 347 366 402 440 486 531 578 616 660 686 724 763 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 36 BLOWER DATA SLP98UH135XV60D BLOWER PERFORMANCE (less filter) BOTTOM RETURN AIR HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 949 1033 1200 1367 1534 1701 1868 2035 Increase (+7.5%) Heat CFM 879 957 1113 1269 1426 1582 1738 1895 Default Heat CFM 808 881 1026 1172 1317 1463 1608 1754 Decrease (-7.5% ) Heat CFM 748 817 956 1095 1235 1374 1513 1652 Decrease (-15% ) Heat CFM 687 753 886 1019 1152 1284 1417 1550 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1070 1260 1410 1555 1565 1750 1970 2190 Default Cool CFM 980 1115 1255 1430 1445 1615 1805 1985 Decrease (-10%) Cool CFM 865 1020 1115 1280 1290 1470 1650 1805 SLP98UH135XV60D BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 85 116 136 157 179 207 236 265 287 210 237 279 328 363 402 436 477 504 535 576 Medium-Low 104 134 173 201 230 274 301 332 363 308 341 399 432 481 515 561 606 648 688 722 Medium-High 154 185 221 263 299 326 367 396 430 440 479 516 587 634 690 735 771 821 868 889 High 206 237 279 328 363 402 436 477 504 526 570 624 676 747 793 839 892 921 971 999 Default Cool CFM Low 67 91 113 136 156 178 197 229 250 162 189 232 267 301 342 379 415 448 475 502 Medium-Low 90 119 147 170 199 229 252 284 312 246 264 316 365 399 443 469 498 540 562 605 Medium-High 104 141 173 190 232 274 301 329 369 330 376 408 462 507 555 593 647 687 730 759 High 155 189 232 267 301 342 379 415 448 389 428 489 518 580 619 669 717 756 808 842 Decrease (-10%) Cool CFM Low 44 64 87 109 127 151 173 189 213 113 147 175 204 235 274 304 333 362 396 426 Medium-Low 65 89 111 139 158 179 201 232 255 165 195 235 270 315 347 378 424 448 481 519 Medium-High 79 106 137 158 190 214 241 271 298 254 281 328 374 407 445 480 507 552 583 630 High 114 147 175 204 235 274 304 333 362 295 337 365 415 450 491 532 566 609 644 683 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 37 BLOWER DATA SLP98UH135XV60D BLOWER PERFORMANCE (less filter) Single Side Return Air - Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. cleanable air filter in order to maintain proper air velocity across the filter. HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 927 1010 1175 1340 1505 1671 1836 2001 Increase (+7.5%) Heat CFM 844 923 1081 1239 1398 1556 1714 1873 Default Heat CFM 760 836 987 1138 1290 1441 1593 1744 Decrease (-7.5% ) Heat CFM 703 775 919 1064 1208 1352 1496 1641 Decrease (-15% ) Heat CFM 646 715 852 989 1126 1263 1400 1537 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1070 1235 1385 1535 1550 1720 1925 2005 Default Cool CFM 985 1110 1245 1395 1415 1605 1755 1970 Decrease (-10%) Cool CFM 870 1010 1110 1260 1280 1435 1610 1755 SLP98UH135XV60D BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 77 104 132 154 177 212 238 266 286 223 247 295 331 378 414 448 486 517 539 582 Medium-Low 105 134 170 201 239 276 304 332 360 311 356 397 432 493 522 569 610 663 699 739 Medium-High 155 187 218 261 300 338 370 396 426 438 469 527 590 635 686 729 782 822 865 897 High 216 247 295 331 378 414 448 486 517 507 551 621 671 721 764 828 870 936 973 1015 Default Cool CFM Low 61 86 110 130 149 171 196 224 248 157 187 220 263 306 349 377 410 441 472 507 Medium-Low 89 117 145 172 198 227 252 284 310 248 275 318 369 402 451 478 509 556 579 623 Medium-High 115 146 179 211 242 279 304 340 370 325 365 414 453 504 552 593 641 688 717 759 High 152 187 220 263 306 349 377 410 441 382 428 466 524 576 622 719 719 770 812 852 Decrease (-10%) Cool CFM Low 40 58 83 103 127 147 165 187 204 118 150 177 212 236 281 311 339 361 398 431 Medium-Low 67 90 116 138 160 180 206 236 256 168 200 238 279 323 356 388 429 462 490 539 Medium-High 86 115 142 164 198 224 250 275 310 249 279 328 363 407 448 479 513 560 584 632 High 118 150 177 212 236 281 311 339 361 288 329 365 413 444 493 529 575 604 651 693 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. SLP98UHV / Page 38 BLOWER DATA SLP98UH135XV60D BLOWER PERFORMANCE (less filter) SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range Heating Adjust CFM Selections Heating Input Range and Blower Volume - CFM 35%40%50%60%70%80%90%100% Increase (+15%) Heat CFM 909 992 1157 1322 1487 1653 1818 1983 Increase (+7.5%) Heat CFM 828 907 1065 1224 1382 1541 1699 1858 Default Heat CFM 746 822 974 1125 1277 1429 1580 1732 Decrease (-7.5% ) Heat CFM 690 761 903 1046 1188 1330 1472 1615 Decrease (-15% ) Heat CFM 634 700 833 966 1099 1231 1364 1497 COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range Cooling Adjust CFM Selections Blower Speed Selections First Stage Cool Speed - cfm Second Stage Cool Speed - cfm Low Medium-Low Medium High High (Default)Low Medium-Low Medium High High (Default) Increase (+10%) Cool CFM 1060 1210 1350 1500 1535 1685 1900 2095 Default Cool CFM 960 1090 1210 1370 1380 1580 1740 1970 Decrease (-10%) Cool CFM 855 990 1090 1205 1250 1400 1585 1740 SLP98UH135XV60D BLOWER MOTOR WATTS - COOLING Blower Speed Options Motor Watts @ Various External Static Pressures - in. wg. First Stage Second Stage 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Increase (+10%) Cool CFM Low 67 95 121 145 165 200 224 252 278 207 235 280 318 364 396 433 469 510 533 575 Medium-Low 98 127 166 189 225 256 280 320 349 290 331 374 419 464 497 551 582 629 669 717 Medium-High 138 172 207 243 279 316 349 393 411 405 443 506 549 603 658 718 763 802 851 885 High 202 235 280 318 364 396 433 469 510 479 522 584 646 702 753 807 841 904 942 993 Default Cool CFM Low 59 82 106 126 145 171 190 215 242 150 181 216 252 291 342 368 397 435 468 492 Medium-Low 84 110 139 165 190 220 246 271 302 236 261 302 358 392 423 466 498 533 562 600 Medium-High 103 133 167 200 227 257 298 320 355 312 355 406 440 485 540 585 624 663 711 757 High 145 181 216 252 291 342 368 397 435 343 379 436 492 535 585 657 686 744 762 818 Decrease (-10%) Cool CFM Low 41 58 86 107 127 147 168 187 210 105 136 173 201 236 270 307 332 363 402 430 Medium-Low 61 85 112 131 157 177 201 230 252 164 198 240 271 308 340 384 425 453 488 525 Medium-High 76 107 136 153 188 213 243 272 302 231 259 301 350 396 426 463 495 533 575 604 High 105 136 173 201 236 270 307 332 363 278 312 359 414 439 470 514 558 608 642 675 The effect of static pressure is included in air volumes shown. The following control configurations are available. See Installation Instructions for details and DIP switch settings. Heat Modes Available (Heating Blower Performance Table): Single stage thermostat: - 35%, 70%, 100% input (three-stage) with time delays in-between. Two-stage thermostat: - Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times. - W1 demand at 70% input, W2 demand at 100% input. No delay between stages. Cool Mode Available (Cooling Blower Performance table): First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position. minimum 380 cfm. Lennox iHarmony® Zoning System Applications - Minimum blower speed is 450 cfm. NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2016 Lennox Industries, Inc. Visit us at www.lennox.com For the latest technical information, www.LennoxPROs.com Contact us at 1-800-4-LENNOX REVISIONS REVISIONS Sections Description of Change Vent Lengths Updated table.