Loading...
24C-013 NORTHAMPTON_SURVIVAL_CENTERCERTIFIED TEST, ADJUST AND BALANCE REPORT DATE:4/12/2011 PROJECT:NORTHAMPTON SURVIVAL CENTER LOCATION:NORTHAMPTON, MASSACHUSETTS CUSTOMER:M. J. MORAN CONTRACTOR:LABCO Air & Water Balancing, LLC ADDRESS:PO BOX 316 West Suffield, Connecticut 06093 PHONE 860-668-1329 FAX 860-668-7089 #TB0338407C T.A.B.B. CERTIFICATION EXP. 12/2011 SUPPLY FAN REPORT PROJECT NAME DATE 4/5/2011 UNIT DATA TEST DATA SYSTEM #RTU 1 CFM DESIGN 4,000 AREA SERVED STORAGE AREA CFM DELIVERED 3,988 UNIT LOCATION ROOF E.S.P. DESIGN .75" VOLTAGE 208 / 3 E.S.P. DELIVERED .51'' FAN MFR'R TRANE FAN DESIGN RPM 1,233 FAN MODEL #YHC120E3RHAOBH FAN DELIVERED RPM 4.8 VDC = 1,126 MOTOR MFR'R INACCESSABLE AMPS RATED 8.5 MOTOR HP 3.8 AMPS DELIVERED 2 / 2.4 / 2.4 MOTOR RPM INACCESSABLE S.P.C.P.NOT APPLICABLE MOTOR S.F.INACCESSABLE V.F.D./VORTEX POS.NOT APPLICABLE MOTOR FRAME INACCESSABLE SUCTION S.P.-.19'' DRIVE DATA DISCHARGE S.P..32'' MOTOR SHEAVE DIRECT DRIVE FAN PULLEY DIRECT DRIVE O.A. DESIGN 620 CFM BELTS DIRECT DRIVE O.A. ACTUAL 637 CFM SHEAVE POSITION DIRECT DRIVE O.A. CONTROL POS.NOT APPLICABLE CENTER TO CENTER DIRECT DRIVE NOTES : NORTHAMPTON SURVIVAL CENTER 4/12/2011 LAB.CO. AIR AND WATER BALANCING 2 SUPPLY FAN REPORT PROJECT NAME DATE 4/5/2011 UNIT DATA TEST DATA SYSTEM #AHU 1 CFM DESIGN 1,600 AREA SERVED SEMINAR AREA CFM DELIVERED 1,531 UNIT LOCATION CEILING E.S.P. DESIGN .75" VOLTAGE 120 / 1 E.S.P. DELIVERED .53'' FAN MFR'R TRANE FAN DESIGN RPM 973 FAN MODEL #TUHMC100ACV4 FAN DELIVERED RPM COOL MODE HIGH MOTOR MFR'R EMERSON AMPS RATED 9.6 MOTOR HP 3/4 AMPS DELIVERED 4.8 MOTOR RPM ECM MOTOR S.P.C.P.NOT APPLICABLE MOTOR S.F.NOT LISTED V.F.D./VORTEX POS.NOT APPLICABLE MOTOR FRAME NOT LISTED SUCTION S.P.-.13'' DRIVE DATA DISCHARGE S.P..4'' MOTOR SHEAVE DIRECT DRIVE FAN PULLEY DIRECT DRIVE O.A. DESIGN 600 CFM BELTS DIRECT DRIVE O.A. ACTUAL 637 CFM SHEAVE POSITION DIRECT DRIVE O.A. CONTROL POS.NOT APPLICABLE CENTER TO CENTER DIRECT DRIVE NOTES : NORTHAMPTON SURVIVAL CENTER 4/12/2011 LAB.CO. AIR AND WATER BALANCING 3 AIR OUTLET TEST REPORT LOCATION:GR.OUTLET AREA K (AK)% OF NORHTAMPTON SURVIVAL CENTER NO.SIZE (ft2)CFM FPM FPM CFM DESIGN RTU 1 SUPPLY OFFICE CUBICAL 1 14X12 1.17 0.64 0.749 500 668 656 491 STORAGE 2 14X12 1.17 0.64 0.749 500 668 696 521 STORAGE 3 14X12 1.17 0.64 0.749 500 668 621 465 RECYCLING / TRASH 4 10X10 0.69 0.64 0.442 150 340 341 151 STAFF TOILET 5 9X9 100 99 STAFF AREA 6 9X9 100 94 VESTIBULE 7 10X10 0.69 0.64 0.442 150 340 338 149 DISTRIBUTION 8 14X12 1.17 0.64 0.749 500 668 641 480 DISTRIBUTION 9 14X12 1.17 0.64 0.749 500 668 671 502 WAITING 10 14X12 1.17 0.64 0.749 400 534 541 405 VESTIBULE 11 10X10 0.69 0.64 0.442 150 340 333 147 CONTROL 12 14X12 1.17 0.64 0.749 400 534 521 390 TOILET 13 6X6 100 93 4,050 3,988 98% RTU 1 RETURN PLENUM RETURN 1 34X20 4.72 1 4.72 3,430 727 710 3,351 98% AHU 1 SUPPLY OFFICE / INTERVIEW 1 9X9 150 134 ENTRY 2 9X9 100 93 OFFICE / INTERVIEW 3 9X9 150 155 DIRECTOR'S OFFICE 4 12X12 200 201 ZONE DAMPER FOR SEMINAR ROOM SEMINAR WORKSHOP / CONFERENCE 5 9X9 125 126 SEMINAR WORKSHOP / CONFERENCE 6 9X9 125 134 SEMINAR WORKSHOP / CONFERENCE 7 9X9 125 126 SEMINAR WORKSHOP / CONFERENCE 8 9X9 125 123 OPEN OFFICE 9 9X9 125 111 FILE / COPY 10 9X9 125 121 OFFICE 11 9X9 125 117 TOILET 12 6X6 100 90 1,575 1,531 97% AHU 1 RETURN OFFICE / INTERVIEW 1 9X9 90 OFFICE / INTERVIEW 2 9X9 92 DIRECTOR'S OFFICE 3 9X9 110 SEMINAR WORKSHOP / CONFERENCE 4 22X22 249 OPEN OFFICE 5 9X9 180 FILE / COPY 6 9X9 85 OFFICE 7 9X9 88 894 NOTE: AHU1 RETURN HAS NO DESIGN CFM'S ON PRINT. DESIGN ACTUAL 4/12/2011 LAB.CO. AIR AND WATER BALANCING 4 EXHAUST FAN REPORT PROJECT NAME DATE 4/5/2011 SYSTEM NO.EF 1 EF 3 EF 4 EF 5 AREA SERVED TOILET TOILET STAFF TOILET STAFF AREA FAN LOCATION TOILET TOILET STAFF TOILET STAFF AREA CFM DESIGN 200 200 450 250 CFM DELIVERED 184 181 182 200 T.S.P. DESIGN .25".25".25".25" T.S.P. DELIVERED .33".32"0.64".66" FAN DES. RPM 1,300 1,300 1,000 980 FAN DEL. RPM NOT LISTED NOT LISTED NOT LISTED NOT LISTED VOLTAGE/PHASE 115 / 1 115 / 1 115 / 1 115 / 1 AMPS RATED 1.7 1.7 2 2 AMPS DEL. 1.7 1.7 1.8 1.8 FAN MFR'R BROAN BROAN BROAN BROAN FAN MODEL #L200 L200 L250 L250 MOTOR MFR'R BROAN BROAN BROAN BROAN MOTOR HP NOT LISTED NOT LISTED NOT LISTED NOT LISTED MOTOR RPM NOT LISTED NOT LISTED NOT LISTED NOT LISTED MOTOR S.F.NOT LISTED NOT LISTED NOT LISTED NOT LISTED MOTOR FRAME NOT LISTED NOT LISTED NOT LISTED NOT LISTED MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE FAN PULLEY DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE SHEAVE POS.DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE NORTHAMPTON SURVIVAL CENTER 4/12/2011 LAB.CO. AIR AND WATER BALANCING 5 EXHAUST FAN REPORT PROJECT NAME JOB #DATE 4/5/2011 SYSTEM NO.EF 6 AREA SERVED SERVER FAN LOCATION SERVER CFM DESIGN 250 CFM DELIVERED 198 T.S.P. DESIGN .25" T.S.P. DELIVERED .35" FAN DES. RPM 980 FAN DEL. RPM NOT LISTED VOLTAGE/PHASE 115 / 1 AMPS RATED 1.7 AMPS DEL. 1.7 FAN MFR'R BROAN FAN MODEL #L200 MOTOR MFR'R BROAN MOTOR HP NOT LISTED MOTOR RPM NOT LISTED MOTOR S.F.NOT LISTED MOTOR FRAME NOT LISTED MOTOR SHEAVE DIRECT DRIVE FAN PULLEY DIRECT DRIVE BELTS DIRECT DRIVE SHEAVE POS.DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE NORTHAMPTON SURVIVAL CENTER 4/12/2011 LAB.CO. AIR AND WATER BALANCING 6 AIR OUTLET TEST REPORT LOCATION:GR.OUTLET AREA K (AK)% OF NORTHAMPTON SURVIVAL CENTER NO.SIZE (ft2)CFM FPM FPM CFM DESIGN EXHAUST FAN 1 TOILET 1 CEF 200 184 92% EXHAUST FAN 2 TOILET 1 CEF 200 DELETED EXHAUST FAN 3 TOILET 1 CEF 200 181 91% EXHAUST FAN 4 STAFF TOILET 1 CEF 450 182 40% EXHAUST FAN 5 STAFF AREA 1 CEF 250 200 80% EXHAUST FAN 6 SERVER ROOM 1 CEF 250 198 79% DESIGN ACTUAL NOTE: EXHAUST FAN # 4 IS THE SAME MODEL NUMBER AS EXHAUST FAN # 5. NOT RATED FOR 450 CFM 4/12/2011 LAB.CO. AIR AND WATER BALANCING 7 VELOCITY PRESSURE TRAVERSE REPORT LOCATION:AREA STATIC % OF NORTHAMPTON SURVIVAL CENTER WIDTH HEIGHT (ft2)CFM FPM FPM CFM PRESS.DESIGN RTU 1 BRANCH DIFFUSER 8 - 13 18 RD 1.767 2,050 1160 1157 2,045 100% RTU 1 BRANCH DIFFUSER 2 - 6 18 RD 1.767 1,350 764 771 1,362 101% DESIGN ACTUALDUCT 4/12/2011 LAB.CO. AIR AND WATER BALANCING 8