Loading...
32A-162 33 HAWLEY IBC CODE REVIEWCode Review Thomas Douglas Architects, Inc. The Northampton Community Arts Trust, 33 Hawley St, Northampton, MA 196 Pleasant St. Northampton,MA 413-585-0641 1 of 5       CODE  REVIEW            September  22,  2015     The  Arts  Trust  Building   33  Hawley  Street,  Northampton,  MA  01060   Applicable  Building  Code:  MA  780  CMR  Eighth  Addition   IBC,  IEBC  International  EXISTING  Building  Code,  2009   ZONING  DISTRICT:         PROPOSED  RENOVATIONS:   PROJECT  DESCRIPTION:   • Renovations  of  the  building  will  include   1. Remove  all  interior  partitions  shown  on  demo  plan   2. Remove  exterior  wall  and  roof  cladding   3. Reinstall  exterior  roof  and  wall  cladding  to  high  performance  standards   4. Renovate  the  interior  of  the  building  to  a  performing  arts  center   5. Construct  a  new  exterior  entry  vestibule.     Use  Groups,  Section  310   • Change  the  entire  building  from  B,  Business  use  group  to  A1,  Assembly,  theater  use  group.     Construction  Type   • 5B     Sprinkler  System   • The  entire  building  will  be  fully  sprinkled.  There  is  an  existing  sprinkler  system  in  the  building.   It  will  be  reconfigured  for  the  new  use.       Fire  and  Smoke  Alarm  &  Detection   • A  manual  fire  alarm  system  and  an  automatic  smoke  detection  system  will  be  installed   throughout  the  building.   •   Seismic  Zone   • See  structural  code  review     According  to  the  IEBC  this  renovation  is  being  reviewed  as:   Prescriptive  Compliance  Method,  Chapter  3   Code Review Thomas Douglas Architects, Inc. The Northampton Community Arts Trust, 33 Hawley St, Northampton, MA 196 Pleasant St. Northampton,MA 413-585-0641 2 of 5 303  Alterations:  Alterations  to  any  building  or  structure  shall  comply  with  the  requirements  of  the  IBC   code  for  new  construction.   303.3  Existing  Structural  elements:  see  attached  structural  review.   307  Change  of  Occupancy:  This  section  requires  that  the  provisions  of  the  IBC  code  for  new   construction  be  applied  to  an  existing  structure  having  a  new  occupancy.         Fire  Resistive  Required  Types  of   Construction,  Table  601  &  602   Building  Element Type  5B Primary  Structural   Frame   0 Bearing  walls,  Exterior 0 Bearing  walls,  Interior 0 Nonbearing  walls  and   partitions,  exterior 0 Nonbearing  walls  and   partitions,  interior 0 Floor  construction  and   secondary  members 0 Roof  construction  and   secondary  members 0     Maximum  Allowable  Height/Area  (section  503-­‐506)   Table  503,  508.4.2:Allowable  building  area:   506.1  Building  area  modifications:  Building  areas  from  Table  503  shall  be  permitted  to  be  increased   due  to  frontage  and  sprinklers.     • Maximum  allowable  area  per  floor:  19,403  s.f.   •   • Proposed  maximum  floor  area  (1st  floor):  12,546  s.f.     505  Mezzanine:   There  is  a  mezzanine  above  the  1st  floor  and  it  is  open  to  the  lobby  below.  It  is  less  than  1/3  of  the  area  of   the  lobby  space  below.   The  mezzanine  occupancy  is  less  than  50  and  only  requires  one  means  of  egress.  (1015.1)   The  mezzanine  is  accessible  via  the  new  elevator.   The  travel  distance  from  the  most  remote  spot  on  the  mezzanine  to  the  bottom  of  the  stairs  at  the   lobby  level  is  72  feet.  The  maximum  allowable  travel  distance  is  75  feet.  (1028.8,  1014.3)   Ceiling  height  requirements  above  and  below  the  mezzanine  comply  with  the  code.  (7  feet)   The  stair  leading  from  the  mezzanine  to  the  lobby  is  not  considered  an  exit  stairway,  but  is  part  of  exit   access  and  is  not  required  to  be  a  vertical  exit  enclosure.     Code Review Thomas Douglas Architects, Inc. The Northampton Community Arts Trust, 33 Hawley St, Northampton, MA 196 Pleasant St. Northampton,MA 413-585-0641 3 of 5 The  adjacent  mechanical  space  will  have  a  1-­‐hour  fire  rated  wall  and  will  be  for  employee-­‐only  access.     FIRE  SEPARATIONS:   707      712        508.4  707.3.8  Separated  Occupancies   Table  508.4  Required  Separation  of  Occupancies   Table  508.2.5  Incidental  Accessory  Occupancies   1022  Exit  Enclosures     • There  is  1  proposed  occupancy  in  this  building.  It  is  A1   • There  is  1  proposed  tenant  in  this  building.   • There  are  no  required  separations  for  any  spaces  in  this  building  other  than  mechanical  rooms,   elevator  machine  rooms,  and  exit  stairs.     • Interior  Stairway  enclosures  (1019):  There  are  no  enclosed  interior  stairs.  Each  floor  has   multiple  exits  leading  directly  to  the  exterior.  The  interior  stairs  are  supplemental,  only   connect  2  floors,  and  can  be  open  to  the  floor  below.     • Elevator  Machine  rooms:  1  hour   • Elevator  Hoistway,  shaft  enclosure,  fire  barrier:  1  hour  when  connecting  4  stories  or  less   (section  708.4  Fire  Resistance  rating)   • Mechanical  Room:  Furnace  room:  Where  any  piece  of  equipment  is  over  400,000  BTU  per   hour  input,  a  1  hour  fire  separation  or  sprinklers  are  required.  The  mechanical  rooms  on  the   mezzanine  and  basement  levels  will  have  1-­‐hour  fire  barrier  walls  separating  them  from  the   adjacent  spaces.     •   410  Stages  and  Platforms   • There  are  no  raised/fixed  stages  or  platforms  proposed  in  this  building.   • There  are  no  proscenium  walls  or  fly  galleries  in  this  building.   • Dressing  rooms  do  not  need  to  be  separated  from  the  stage  because  there  are  no  fixed  stages.   • There  are  no  property  rooms,  scene  docks,  or  workshops  appurtenant  to  the  stage.       1018  Corridors   • No  fire  rated  corridors  are  proposed  in  this  building.     Means  of  Egress     1018.4  Dead  ends   With  an  automatic  sprinkler  system,  dead  end  corridors  are  limited  to  50  feet.  This  project  does  not   have  dead  end  corridors  exceeding  50  feet.     1012.2  Handrail  height     1012.9  Intermediate  handrails   Code Review Thomas Douglas Architects, Inc. The Northampton Community Arts Trust, 33 Hawley St, Northampton, MA 196 Pleasant St. Northampton,MA 413-585-0641 4 of 5 The  new  entry  stair  at  the  front  sidewalk  entry  is  a  “monumental  stair.  It  exceeds  60  inches  in  width.   Intermediate  handrails  shall  be  constructed.     1010.9  Edge  protection  for  ramps  is  required     805.2  Means  of  Egress  Lighting   Means  of  egress  lighting  will  be  installed  throughout  the  entire  building     805.3  Exit  signs   Means  of  egress  throughout  the  entire  building  will  have  new  exit  signs  installed.     705.4.2  Door  swing.     All  means  of  egress  doors  will  swing  in  the  direction  of  travel.     705.4.4  Panic  hardware:   Panic  hardware  is  required  for  this  project.     Exits  Required   Exits   required Exits   provided Exit  Width   stair   .3”  per   occupant Exit  Width  other   components   .2”  per  occupant Basement  Floor 1 1 135”  min   90”  min   First  Floor 1 1 114”  min   76”  min   Second  Floor 2 2 44”  min 44”   Section  1009.1  prescribes  that  the  width  of  an  interior  stairway  cannot  be  less  than  44  inches     Travel   Distance   (1016.1)   With  NO   sprinkler     System With  sprinkler     System Proposed  max  travel   distance A  use  Bsmt  &  1st   floors 250’   74  feet     Chapter  9  Fire  Protection  Systems:   • An  automatic  sprinkler  system  will  be  provided  throughout  the  entire  building.     • Fire  alarm  and  smoke  alarm  systems.  See  narrative  from  Mechanical  Engineer,  Lindgren  and   Sharples.   Code Review Thomas Douglas Architects, Inc. The Northampton Community Arts Trust, 33 Hawley St, Northampton, MA 196 Pleasant St. Northampton,MA 413-585-0641 5 of 5   711  Energy  Conservation   Required  values  according  to  the  MA  stretch  code  that  this  project  will  exceed:   MA:  climate  zone  5A   Roofs:  R-­‐38   Walls  above  grade:  R-­‐13+R-­‐7.5  ci=  R20.5   Walls  below  grade:  R-­‐7.5   Slab  on  grade  Floors,  unheated:  R-­‐10     806  Accessibility   CMR  521     3.3.1  b.  If  the  work  costs  $100,000  or  more,  then  the  work  being  performed  is  required  to  comply  with   521  CMR.  In  addition,  an  accessible  public  entrance  and  an  accessible  toilet  room  shall  be  provided.     3.3.2  If  the  work  performed,  including  the  exempted  work,  amounts  to  30%  or  more  of  the  full  and  fair   cash  value  of  the  building,  the  entire  building  is  required  to  comply  with  521  CMR.     This  project’s  construction  costs  will  exceed  30%  of  the  assessed  value  of  the  entire  building.     The  building  will  be  designed  to  be  fully  accessible.     A  new  elevator  and  front  entry  ramp  will  be  constructed.     All  toilet  rooms  will  be  accessible.