Loading...
32C-107 32 Smith Fire Narrative-2 FIRE PROTECTION SYSTEMS NARATIVE REPORT BASIS (METHODOLOGY) OF DESIGN Section 1 – Building Description a. Building "Use Group: Mixed (F-2) Low Hazard Factory (B) Business, Offices. b. Type(s) of occupancies (hazards within the building): Metal Worker. c. Two stories above grade high point of building roof is 23'-0". d. Zero stories below grade. e. First floor existing 17,388 S.F., Second floor existing 3,654 SF, new addition 5,600 S.F. Total = 26,642 Square feet. f. Storage: In accordance with NFPA-13 ordinary hazard occupancy. Storage of Flammable/Combustible liquids shall be in accordance with the exempt quantity limitations of 780 CMR Table 307.7 (1) & (2) and 527 CMR 14 and its referenced sections of NFPA 30. The building is protected by a wet pipe system and the two exterior canopies are protected by a dry pipe system. Factory wet sprinkler flow requirement is .20 GPM over the most remote 1500 square feet which requires 431.1 GPM@ 47.0 PSI at the base of the riser and 681.1 GPM @ 54.5 PSI at the connection to the city main. These are preliminary Design pressures and flow. Water flow test is 145 PSI Static, 120 PSI Residual with 1,503 GPM flowing. Section 2 – Applicable Laws, Regulations and Standards 780 CMR code sections "Fire Protection System Requirements" Fire Suppression Systems Requires audio visual alarm devices Monitoring NFPA Standards and Editions used for the design of each specific fire protection system, NFPA 13, 2013; NFPA 72, 2010; NFPA 24, 2007 Section 3 –Design Responsibility for the Fire Protection Systems Warehouse Mechanical the installing contractor completely designs and specifies (develops a full system layout, design criteria and calculations) installs the system and certifies system installation for code compliance at completion. Exempt from Requirement for seal of Massachusetts Registered Professional engineer in accordance With MGLC 112 section 81R. Section 4 –Fire Protection Systems to be installed The new six inch sprinkler main will tie into the existing eight main in Smith street. Sprinkler systems and components. Fire alarm systems and components- audio and visual appliances installed throughout in accordance with NFPA 72. Manual suppression systems are not required. Seismic isn’t required in accordance with NFPA 13. Storz fire department connection provided on the front of the building. All of the above items are required by regulations (780 CMR) all systems are new 901.2.1(1.a.ii) Sequence of Operation Section 1 Wet sprinkler system: System operates automatically upon the fusing of a single fire sprinkler. Operational Sequence: Wet system operates automatically on water flow from a single sprinkler. Closed contacts on the flow switch will provide alarm contact for the fire control panel and activate the local audible visual panels. Dry system operates automatically. Air exhausted through a single sprinkler head allows water to flow operating the closed contact on the pressure switch. 901.2.1(1.a.iii) Testing Criteria Section 1- Testing Criteria in accordance with NFPA 13 System piping: Hydrostatically test wet and dry system piping at a pressure of 200 psi for two hours without a loss of pressure. 2. Conduct a full forward flow test of the backflow preventer at a rate of 431.1 GPM through both the wet and dry main drain. 3. A 2" main drain test shall be conducted. Record static and residual pressures on the test certificates. Conduct system operational and alarm test on the system from the inspector's test connection in accordance with NFPA 13. Central station must receive the alarm and trouble signals. Warehouse Mechanical is in charge of setting up and conducting the testing. Warehouse Mechanical will provide test certificates Section 2- Equipment and Tools Manufacturer's instructions Approved narrative report, sequence of operations section Flow measuring devices- pitot tube for backflow preventer full forward flow test Gauges- main riser for 2" drain and hydrostatic testing Fire hose is required to direct backflow flushing Section 3- Approval Requirements Certification from Warehouse Mechanical Contractors stating that the fire protection sprinkler system has been installed in accordance with the approved fire protection construction documents and that he has reviewed the as-built drawings for conformance to 780 CMR 901.7.4 and has identified deviations if any, from the approved fire protection construction documents. Confirmation by the building owner/developer or authorized representative that they have received the as-built sprinkler system shop drawings from the installing contractor Material Test, Performance and Completion Certificates, properly executed by the installing contractor in accordance with the applicable NFPA Standards. Satisfactory functional test of all fire protection systems witnessed by the Building official and the head of the fire department or their designees.