31B-282 NPD+Construction+Meeting+#49+(06-21-2012)[1]Meeting Minutes Detailed Northampton Police Headquarters Barr & Barr, Inc.Project # 08264 29 Center Street Northampton, MA 01060 Tel: (413) 727-3487 Fax: (413) 727-3489 Weekly Construction Meeting 49 Date Start End Next Meeting Next Time Prepared By Company 6/21/2012 11:00 AM 12:30 PM 6/27/2012 11:00 AM Jason Boudreau Barr & Barr, Inc. Purpose Location General Notes Review Progress of Construction Northampton Police Dept. 29 Center Street Non-Attendees ARCADIS U.S., Inc. - Ray Kinghorn Barr & Barr - Gregg Sutherland Barr & Barr, Inc. - Bill Aquadro Caolo & Bieniek Associates, Inc. - Rudi Hall Caolo & Bieniek Associates, Inc. - Jim Hanifan Northampton Building Department - Louie Hasbrouck Attended By ARCADIS U.S., Inc. - Ron Rickey Barr & Barr, Inc. - Jason Boudreau Barr & Barr, Inc. - Jared Moriarty Barr & Barr, Inc. - Tim Senecal Caolo & Bieniek Associates, Inc. - Curtis Edgin City of Northampton - David Pomerantz City of Northampton - David Tripp Northampton Police Department - Russell Sienkiewicz Northampton Police Department - Joseph Koncas Compl'dDue DateStatusRespMeeting Item DescriptionItem General Business Old Business Demo/Abatement Status 6/21/12: NPD noted they needed another week for moving equipment/supplies out of the existing PD; demolition start date has been changed to 7/2. NPD noted basement in existing PD will be ready Wed/Thur. City to remove AC split systems by next Friday. B&B to submit revised demo/abatement plan for record. 6/13/2012: B&B to submit abatement plan for record. B&B noted some selective demolition needs to be completed prior to starting abatement. Selective demolition targeted for 6/25. Abatement targeted for 6/27. Dave Pomerantz to notify Green Environmental of revised dates. 6/6/2012: Abatement plan returned with comments from Green Environmental; start date and quantities to be revised; plan to be resubmitted for record. B&B Ongoing 6/21/2012001-002 Site Utilities & Rebates 6/21/12: B&B/NGrid met with Urban Outfitters property manager to discuss power outages. Outages tentatively scheduled on 7/11 & 7/12 at 8:00 PM; expected to last 8 hours. T&M to install hand hole next week. CBA/CES to review if Comcast required inner-duct. B&B/NGrid coordinated connection of Main St. street lights. B&B received e-mail from G4S (state fiber contractor) stating fiber is planned to be pulled from Gothic St.; B&B to forward contact information to NPD. 6/13/2012: NGrid to be on site today to review dates/coordination for CBA; T&B Ongoing 6/21/2012001-003 Prolog Manager Printed on: 6/25/2012 Page 1 Meeting Minutes Detailed Northampton Police Headquarters Barr & Barr, Inc.Project # 08264 29 Center Street Northampton, MA 01060 Tel: (413) 727-3487 Fax: (413) 727-3489 Compl'dDue DateStatusRespMeeting Item DescriptionItem Urban Outfitter power shut down. B&B to schedule power outage with Urban Outfitters property manager; NGrid to confirm gear rotation. CBA to confirm if inner-duct is acceptable to Comcast for separation. City confirmed lights on Main St. are fed from poles on Gothic St.; NGrid/B&B to coordinate. 6/6/2012: Gothic St. backfilling to be complete this week. NGrid/Comcast to be scheduled to pull wires. B&B to schedule/coordinate power shut down for Urban Outfitters w/ NGrid and property manager when new handhole is being installed. B&B to confirm who checks gear rotation at Urban Outfitters. Comcast/Verizon have been on site to confirm quantities of handholes for conduits. Comcast reviewing if inner-duct is required within 4 inch conduit. City to review if Main St. lights are fed from Gothic St. utility poles. MEP Coordination & Commissioning 6/21/12: Cx meeting scheduled for next Wednesday. ATC training to be scheduled with the city. ATC graphics, alarm, notifications, and set points will also be loaded/programmed. CBA/CES to review if boiler is to be controlled by ATC controls. VOC testing complete, all areas passed test; B&B to forward results. CES to issue formal report on chiller power outage. CES reviewing cooling options for 1st floor server room and AV closet. 6/13/2012: Next Cx meeting to be scheduled once PD network is live; Yankee needs IP addresses active in order to set alarms and notifications. NPD is waiting for Valley Communications to confirm VLAN relocation date; PO has been issued. B&B/NPD/WSP to review set points during ATC training; CBA noted that set points may need to be adjusted again during the heating season. VOC retest was on Monday; results to be forwarded next week. CES to issue formal report on Chiller outage. CES reviewing 1st floor server & AV room cooling; CBA noted equipment in AV room can be turned off while not in use. Security training has been schedule for 6/20 @ 10:00. 6/6/2012: Cx meeting held today w/ WSP to review open items. Updated balancing report was reviewed. B&B addressing alarms and notifications w/ Yankee. PD noted ATC access to be ready early next week; Yankee will set up remote access when ready. One of (3) rooms passed VOC test; test to be rescheduled. B&B to deliver O&M's to City. Chiller Contactors were replaced last Friday; CES noted that failure was likely due to the chiller conducting electricity from an outside event (i.e., lightning). CES noted Chiller does not run on emergency power; CES to confirm if split A/C's do. CES recommended adding ventilation and under cutting the doors to the 1st floor server room and AV closet; PD directed CES to provide supplemental A/C. CBA noted gas meter needs to be locked; CBA reviewing gas meter protection CO. B&B; CBA Ongoing 6/21/2012001-006 Monthly Requisitions 6/21/12: June pencil req to be reviewed next week. B&B received April payment last week. 6/13/2012: NPD to forward April payment this week. 6/6/2012: May req. issued this week. NPD; B&B Ongoing 6/21/2012001-007 Precast Parking Deck 6/21/12: B&B received precast shop drawings from CBA. MEP coordination is ongoing. Mock-up date TBD. 6/13/2012: Footing/Wall rebar shop drawing review returned by CBA/T&B. B&B noted precast drawing review is required quickly. First CBA; B&B; T&B Ongoing 6/21/2012007-002 Prolog Manager Printed on: 6/25/2012 Page 2 Meeting Minutes Detailed Northampton Police Headquarters Barr & Barr, Inc.Project # 08264 29 Center Street Northampton, MA 01060 Tel: (413) 727-3487 Fax: (413) 727-3489 Compl'dDue DateStatusRespMeeting Item DescriptionItem plumbing coordination drawing has been submitted to B&B; start to coordinate with other MEP trades. 6/6/2012: Submittals being reviewed by CBA/T&B; CBA noted they should be returned this week. Drainage is currently being coordinated; balance of MEP coordination to follow. Coordination expected to be completed by end of month. 5/30/2012: Parking garage and rebar shop drawings have been submitted for approval. MEP coordination has begun. Phasing 6/21/12: AHU curb set yesterday. Roof opening protection in place until AHU delivery in mid Aug. Signage to be delivered in 2-3 weeks. 6/13/2012: AHU curb being delivered next week; roof to be opened Tuesday; start blocking Wednesday. AHU ship date is 8/14. Signage has been released for fabrication; B&B to forward ship date. 6/6/2012: Curb scheduled to be delivered within the next 1-2 weeks; B&B noted install date depends on weather. AHU delivery targeted for mid August. CBA completed signage proof review and noted submittal will be returned today. B&B Ongoing 6/21/2012011-001 FF&E Status 6/21/12: Inter. table delivered to PD; B&B to install. W.B. Mason reviewing chair legs. NPD to forward quote for radio repeater system to B&B; B&B to invoice PD by 6/30 in order to process work; B&B to issue contract to WPCS. 6/13/2012: CBA completed punch list last week. Chairs in rooms with resilient flooring have wrong legs. Donnegan released gun locker doors; takes (5) days to ship. 6/6/2012: CBA completing FF&E punchlist today. PD ordered inter. table; legs to be field cut. Final cleaning schedule for Thur/Friday. NPD reviewing radio repeater system. CBA/NPD reviewing gun locker lock options. CBA Ongoing 6/21/2012012-001 Logistics 6/21/12: B&B reviewed dumpster locations with Urban Outfitters; final location TBD. NPD pulled permits with DPW to put dumpsters on street. Construction fence behind Urban Outfitters to start next week. NPD to coordinate temporary police parking. B&B to contact Eric Suher and church to review parking and Phase 2 construction. Balance of stair treads delivered; install to follow. Temporary power has been relocated to new PD. B&B to schedule water shut off to existing PD with DPW. 6/13/2012: Dave Pomerantz to coordinate trash/recycling locations and removal of split AC systems. Dumpsters to be kept on Gothic St. in metered spots; targeting 6/25; NPD to coordinate size/quantities. Neighbors to be notified parking lot behind Urban Outfitters will be closed; B&B to review dates and set up construction fence. Balance of stair treads to be installed.; temporary trades have been installed. Temporary power to be relocated; required 1 hours shut down of old police station: B&B to coordinate with NPD. 6/6/2012: Stair treads being installed this week. B&B; NPD Ongoing 6/21/2012013-001 Security Systems 6/21/12: Security training held yesterday; Officer Tripp to meet with Bob from Icon next Thursday to review admin. control. CBA/NPD to B&B; NPD; CBA Ongoing 6/21/2012029-001 Prolog Manager Printed on: 6/25/2012 Page 3 Meeting Minutes Detailed Northampton Police Headquarters Barr & Barr, Inc.Project # 08264 29 Center Street Northampton, MA 01060 Tel: (413) 727-3487 Fax: (413) 727-3489 Compl'dDue DateStatusRespMeeting Item DescriptionItem review audio control for Cardinal Peak System; currently the audio can only be turned off from the control room. CBA to issue COR for adding camera to room 129. CBA/CES reviewing paging/duress CO. 6/13/2012: Training scheduled next Wednesday at 10:00. B&B to confirm status of hooking security network to PD network and Paging/Duress changes. 6/6/2012: PD noted the fob programming is complete. Training for Vicon, Cardinal Peak, and AV systems to be scheduled; B&B to forward dates. B&B forwarded PD phone system info to Griffin for paging system changes. Camera to be relocated in interview room. NPD to notify B&B when VLAN has been moved to new building. Punch Lists 6/21/12: B&B noted building is ready for punch list review with CBA. Service slider to be reinstalled today. B&B to forward window test results to CBA. B&B noted windows are ready for cosmetic inspection; CBA to review repairs. NPD noted data port connection in room 114 is not working. 6/13/2012: B&B issued update completion punch list to CBA on Tuesday. Lizotte to adjust service slider. Final window test was last Friday; all passed with weep holes being covered, awaiting inspection report from T&L. CBA noted that Lizotte was looking into weep hole covers, B&B to follow up. Cosmetic repairs have been made; B&B/CBA/ NPD to review. 6/6/2012: CBA reviewed punch list completion last week and issued updated punch list on Monday; B&B to review open items. B&B will add punch list items to CBA punch list Painters and carpet installers to be onsite this week. NPD noted service slider needs to be adjusted. Window retest scheduled for Friday morning; (3) windows to be tested. CBA/B&B/Lizotte to review window cosmetic repairs after window testing. B&B; CBA Ongoing 6/21/2012035-002 New Business RFI Status 6/21/2012: The following RFI are under review by the design team: - N/A 049-001 Submittal Status 6/21/2012: Updated submittal log was issued for review. B&B noted the following are the highest priority submittals: - 051200-013: Door 023-2 Structural Header (7/2) - 055000-008: Door 023-4 Steel Jambs (7/2) - 033000-004: LEED - CIP Concrete Calculator Phase 1 (5/15) - 260573-002: Acceptance Testing Report (3/27) 049-002 Change Order Status 6/21/2012: PCO Log was issued for review, with the following Change Orders under review: - PCO-008 Parking Deck Precast Revisions - PCO-029R Canopy Steel Revisions (ASI #36) - PCO-043 ASI #45 Kitchen Disposals - PCO-056 Various Electrical & Sprinkler Dir. - PCO-063 Gas Meter Protection (COR #15) - PCO-068R Temporary Heat Allowance - PCO-069 Front Workstation Upgrade (ASI #43R1) - PCO-071 HC Cell Fixture Modifications - PCO-073 Paging & Duress Revisions (COR #17) 049-003 Prolog Manager Printed on: 6/25/2012 Page 4 Meeting Minutes Detailed Northampton Police Headquarters Barr & Barr, Inc.Project # 08264 29 Center Street Northampton, MA 01060 Tel: (413) 727-3487 Fax: (413) 727-3489 Compl'dDue DateStatusRespMeeting Item DescriptionItem Schedule Update 6/21/2012: Schedule Update and Look Ahead: - Parking garage conduit installation/backfill ongoing - Gothic Street utility work ongoing - Parking Garage coordination ongoing - Construction fence @ parking lot next week - Abatement/Demo to start 7/2 - Urban Outfitters power outages 7/10 & 7/11 049-004 Cc:Company Name Contact Name Copies Notes Should you take exception to any of the minutes, please notify the author within three (3) business days of receipt. Otherwise the minutes shall be considered true and accurate and will be come part of the project record. Prolog Manager Printed on: 6/25/2012 Page 5