36-334 Jones_Tina_-_Florence_MA_--_FA_LAYOUTPV-A01 N.T.S.
Cover Page
Roof Mount Grid Tied Photovoltaic ("PV") System
Tina Jones
8.00 kW DC at STC
CLIENTPROJECTDRAWING SCALE(11x17")VersDateCommentDRAWN BY:SOLAR LIVING SINCE 1978CONFIDENTIALITY NOTICE: These Plans and any documents transmitted with them may contain PRIVILEGED or CONFIDENTIAL information and may be read or used only by the intended recipient.
If you are not the intended recipient, please be advised that you have received this in error and that any unauthorized review, distribution, printing, or copying of these Plans or any attached files is strictly prohibited.
PERSPECTIVE VIEW
AERIAL VIEW
Jones Residence
Jennifer BacaTina Jones23 Cardinal Way Florence, MA 010628.00 kWRoof Mount Grid Tied Photovoltaic ("PV") System32 CS5P-250M ModulesInitial Draft103-29-2012Job #: 58138InitJLBInstall Office32 Taugwonk Spur, A12Stonington, CT 06378Tel: 860-535-3370FOR APPROVAL
Table Of Contents
•PV-A01 Cover Page
•PV-A02 Site Plan
•PV-A03 Roof Plan
•PV-E01 Electrical Diagram
System Specifications:
•32 Canadian Solar CS5P-250M Modules
•2 SMA SB4000US Inverters
•Mounted On UniRac Solarmount
•Roof Pitch 20 °
•Roof Azimuth 160 ° True
Site Conditions:
•Ground Snow Load = 55 PSF
•Design Wind Speed = 100 MPH and Exposure C
•Building Occupancy = II
•Mean Roof Height = 15 ft.
•Roofing Material is Asphalt Shingle
•Framing is 2 X 10 Rafters every 16 in. O.C.
Securement Method:
•Quantity of Attachments = 116 @ 24 in. O.C. (Limited by Structural/Wind Characteristics)
•Maximum UniRac Span = 48 in. O.C. (Maximum Allowable Cantilever is 1/3 the Maximum Rail Span)
•UniRac L-Feet with Green-Fasten GF1-CP-SQ Flashing and a 5/16" X 3.5" SSTL Lag Screw
•UniRac SolarMount Rails require 1 in. Spacing between Modules and an extra 3 in. beyond end Module
edges.
•Array Installed according to the UniRac SolarMount Code-Compliant Installation Manual ver. 227.3, Pub
110616-1cc, June 2011
PV-A02 1" = 20' Site Plan
CLIENTPROJECTDRAWING SCALE(11x17")VersDateCommentDRAWN BY:SOLAR LIVING SINCE 1978CONFIDENTIALITY NOTICE: These Plans and any documents transmitted with them may contain PRIVILEGED or CONFIDENTIAL information and may be read or used only by the intended recipient.
If you are not the intended recipient, please be advised that you have received this in error and that any unauthorized review, distribution, printing, or copying of these Plans or any attached files is strictly prohibited.
32 Canadian Solar
CS5P-250M Modules
Conduit Run to
follow the gutter
Main Panel (Interior/Basement)
Utility Meter
Inverters/Disconnect
Location (Exterior)
PV-A02 1/8" = 1' 0"
Site Plan
Jennifer BacaTina Jones23 Cardinal Way Florence, MA 010628.00 kWRoof Mount Grid Tied Photovoltaic ("PV") System32 CS5P-250M ModulesInitial Draft103-29-2012Job #: 58138InitJLBInstall Office32 Taugwonk Spur, A12Stonington, CT 06378Tel: 860-535-3370FOR APPROVAL
PV-A03 3/16" = 1'-0" Normal to Roof View
CLIENTPROJECTDRAWING SCALE(11x17")VersDateCommentDRAWN BY:SOLAR LIVING SINCE 1978CONFIDENTIALITY NOTICE: These Plans and any documents transmitted with them may contain PRIVILEGED or CONFIDENTIAL information and may be read or used only by the intended recipient.
If you are not the intended recipient, please be advised that you have received this in error and that any unauthorized review, distribution, printing, or copying of these Plans or any attached files is strictly prohibited.Jennifer BacaTina Jones23 Cardinal Way Florence, MA 010628.00 kWRoof Mount Grid Tied Photovoltaic ("PV") System32 CS5P-250M ModulesInitial Draft103-29-2012Job #: 58138InitJLBInstall Office32 Taugwonk Spur, A12Stonington, CT 06378Tel: 860-535-3370FOR APPROVAL
Module Height: 63.1 inches
Module Width:41.8 inches
Module Thickness:1.57 inches
60' 6"
18' 6"
10' 7"
57' 0"
PV-E01 N.T.S. Electrical Diagram
CLIENTPROJECTDRAWING SCALE(11x17")VersDateCommentDRAWN BY:SOLAR LIVING SINCE 1978CONFIDENTIALITY NOTICE: These Plans and any documents transmitted with them may contain PRIVILEGED or CONFIDENTIAL information and may be read or used only by the intended recipient.
If you are not the intended recipient, please be advised that you have received this in error and that any unauthorized review, distribution, printing, or copying of these Plans or any attached files is strictly prohibited.Jennifer BacaTina Jones23 Cardinal Way Florence, MA 010628.00 kWRoof Mount Grid Tied Photovoltaic ("PV") System32 CS5P-250M ModulesInitial Draft103-29-2012Job #: 58138InitJLBInstall Office32 Taugwonk Spur, A12Stonington, CT 06378Tel: 860-535-3370FOR APPROVAL
LEGEND
DC Pos, AC Hot
DC Neg, AC Neutral
Ground
Bonding To Building Grounding
ElectrodeSystem
1.All Conductors to be copper unless noted otherwise.
2.Module type is negatively grounded and inverter(s) to be so set.
3.Installation to meet mimimum requirements of the 2008 NEC Except where
required otherwise by local code specifications.
4.Interconnect breaker shall be within visual proximity of inverter.
5.Maximum voltage calculated with temperature coefficient of -0.35% /°K
6.All grounding electrode conductors shallbe installed in single continuous
lengths except where spliced by irreversible connector or exothermic weld.
NOTES LABELINGDC Maximum: 550.97 V, 27.15 A (@ -20° C)
DC Operating: 387.20 V, 20.20 A
AC Operating: 240 V, 16.67 A
10A Fuses
Integrated DC Disconnect
SMA Inverter
SB 4000US
4.0kW, 16.67A,240VAC
UL 1741 Listed
IEEE 1547 CompliantDC Ground Fault Protection
DC
AC
10A Fuses
Integrated DC Disconnect
SMA Inverter
SB 4000US
4.0kW, 16.67A,240VAC
UL 1741 Listed
IEEE 1547 CompliantDC Ground Fault Protection
DC
ACJ-Box8-#10
USE-2, #8G
¾" EMT, 8-#10
THWN-2, #10G
Locus
Lgate 100
Datalogger
Internet Connection
120V Outlet
30A
2P
AC Combiner Panel
Sq. D QO612L100DS
100A Rating
30A
2P
Lockable
Utility Meter
240V, 200A
Utility Service
240VAC,200A
Main Load Center
Line Tie
Within
Junction
Box
Fusible, NEMA-3R
Sq. D D222RB
60A Rating
Utility Disconnect
60A Fuses
32 Canadian Solar
CS5P-250M Modules
Voc=59.5 V
Isc=5.43 A
4 Strings of 8 Modules
Roof Mounted
Revenue Grade
PV Meter
¾" EMT, 6-#10
THWN-2, #10G
¾" EMT, 3-#6
THWN-2, #10G
¾" EMT, 3-#6
THWN-2