Loading...
32C-229 Orenstein duct test reults 474 Easthampton Rd. PO Box 1570 Northampton, MA 01060 413-584-3317 Duct Work Installation Worksheet 5-12-2016 Project: Denise Orenstein 8 Hancock St Northampton, MA 413-320-2581 Indoor Unit: Lennox Air Handler Unit (AHU), model CBX27UH-030-230-6-03, with TXV Fan Speed: Medium Outdoor Unit: 2 ½ ton Lennox XC14-030-230A10, with R410 refrigerant Outdoor unit’s Sub Cool Goal: 6 Air filter- 5” Merv 11 made by Lennox AHRI Certificate: 7513763, 16 SEER and 13 EER Copper Line Set: ¾ and 3/8, approximately 34’, AHU approximately 20 feet above the outdoor unit. Scope: An older home is being retro-fitted with a newly designed and installed 2 ½ ton central AC system. The new system is installed in the walk-up attic.  New system has one central return duct that pulls air from the entire home. The return grille is located at the top of the stairwell on the second floor. There are 4 Supply grilles at the second floor ceiling and 2 metal duct runs were installed to offer partial cooling to the 1st floor. There are a total of 6 supplies.  The AHU has a rugged safe pan under it and it has a water sensing shut off switch that will break the power to the AHU fan call and the outdoor unit’s call for AC if water is sensed.  All of the duct work is 26gg metal except very small sections of R8 Flex at the end of the run-outs (maybe 4 to 6’ approximately). Test Equipment: Retrotec DU 200 duct tester, Retrotec DM2 manomater, TSI model 8371 Flow Hood Duct Blast (pressure test) The home is 1920 sq ft. At the required minimum of 4% duct leakage at 25 Pascals, the duct system is allowed 76.8 cfm loss. This new duct system was tested at 26 Pascals and the leakage rate was 74.45, which is a PASS. We did have small leaks that we simply couldn’t address to make the system tighter (namely the return box where it connects at the second floor ceiling) Duct Balancing: Due to the old plaster and lath walls and ceiling we did not go the every area of the home with our new duct routes. We had a total of 6 supplies: Second Floor- FRONT BED 168 CFM MIDDLE BEDROOM 166 CFM REAR BEDROOM 130 CFM BATHROOM 65 CFM First Floor LIVING ROOM (FRONT) 197 CFM KITCHEN 305 CFM Total CFM measured is 1031 Gary Wilson, Owner Wilson Services, Inc. Northampton, MA 413-584-3317 413-626-5548 gary@wilsonph.com www.wilsonph.com