Loading...
narritive service net stamped FIRE PROTECTION SYSTEMS NARATIVE REPORT BASIS (METHODOLOGY) OF DESIGN Section 1 – Building Description a. Building "Use Group: (B) Business offices, meeting rooms, employee cafe b. Type(s) of occupancies (hazards within the building):offices c. TWO story above grade high point of building roof is 27'-0" d. Zero stories below grade. e. First floor is 8,800 SF +8,250 SF SECOND FL = 17,050 SF. f. Storage: In accordance with NFPA-13 for miscellaneous storage under 12-0” feet in height. The highest wet sprinkler flow requirement is .10 GPM over the most remote 900 square feet which requires 142.5 GPM@ 51.5 PSI at the base of the riser and 242.5 GPM@61.7 PSI at the connection to the city main. Water flow test is 106 PSI Static, 91 PSI Residual with 1247 GPM flowing. Section 2 – Applicable Laws, Regulations and Standards a. 780 CMR code sections "Fire Protection System Requirements" 903.2.0 Fire Suppression Systems 903.4.2 Requires audio visual alarm devices 903.4.1 Monitoring b. NFPA Standards and Editions used for the design of each specific fire protection system, NFPA 13, 2013; NFPA 72, 2010; NFPA 24, 2007 Section 3 –Design Responsibility for the Fire Protection Systems JFV Engineering, LLC develops a full system layout, design criteria and calculations and certifies the system installation for code compliance at completion. Section 4 –Fire Protection Systems to be installed a. Water supply will be taken from the existing 8” City main in Village hill b. Sprinkler systems and components. c. Fire alarm systems and components- audio and visual appliances installed throughout in accordance with NFPA 72. d. Manual suppression systems are not required. e. Seismic isn’t required in accordance with NFPA 13. f. Siamese fire department connection provided on the west side of the building. All of the above items are required by regulations (780 CMR) all systems are new 901.2.1(1.a.ii) Sequence of Operation Section 1 Wet sprinkler system: System operates automatically upon the fusing of a single fire sprinkler. Operational Sequence: a. Wet system operates automatically on water flow from a single sprinkler. Closed contacts on the flow switch will provide alarm contact for the fire control panel and activate the local audible visual panels. 901.2.1(1.a.iii) Testing Criteria Section 1- Testing Criteria in accordance with NFPA 13 System piping: 1. Hydrostatically test wet and dry system piping at a pressure of 200 psi for two hours without a loss of pressure. 2. Conduct a full forward flow test of the backflow preventer at a rate of 430.9 GPM through the wet 2” main drain. 3. A 2" main drain test shall be conducted. Record static and residual pressures on the test certificates. 4. Conduct system operational and alarm test on the system from the inspector's test connection in accordance with NFPA 13. 5. Central station must receive the alarm and trouble signals. Warehouse Mechanical is in charge of setting up and conducting the testing. Warehouse Mechanical will provide test certificates Section 2- Equipment and Tools a. Manufacturer's instructions b. Approved narrative report, sequence of operations section c. Flow measuring devices- pitot tube for backflow preventer full forward flow test d. Gauges- main riser for 2" drain and hydrostatic testing e. Fire hose is required to direct backflow flushing Section 3- Approval Requirements a. Certification from JFV Engineering, LLC. stating that the fire protection sprinkler system has been installed in accordance with the approved fire protection construction documents and that he has reviewed the as-built drawings for conformance to 780 CMR 901.7.4 and has identified deviations if any, from the approved fire protection construction documents. b. Confirmation by the building owner/developer or authorized representative that they have received the as-built sprinkler system shop drawings from the installing contractor c. Material Test, Performance and Completion Certificates, properly executed by the installing contractor in accordance with the applicable NFPA Standards. d. Satisfactory functional test of all fire protection systems witnessed by the Building official and the head of the fire department or their designees.