Loading...
HERS-236 123 Moser St air leakageAir Leakage Property 123 Moser St Northampton, MA 01060 Weather:Northampton, MA HERS-236 123 Moser St registered.blg Organization Power House Energy Consulting 413-835-5162 Matt Turcotte Builder Pecoy Companies Whole House Infiltration ASHRAE 62.2 - 2010 Ventilation Requirements For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, a minimum of 48 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjusted accordingly. For example, a 96 cfm mechanical ventilation system would need to operate 12 hours per day, as long as the system operates to provide required average ventilation once each hour. REM/Rate - Residential Energy Analysis and Rating Software v14.5.1 This information does not constitute any warranty of energy cost or savings. © 1985-2014 Architectural Energy Corporation, Boulder, Colorado. HERS Confirmed 10/8/14 Rating No:HERS-236 Rater ID:1497133 Duct Leakage Ventilation Blower Door Test Heating Cooling Natural ACH 0.07 0.05 Leakage to Outside Units ducts Mechanical Balanced ACH @ 50 Pascals 1.19 1.19 CFM @ 25 Pascals 0 Sensible Recovery Eff. (%)67.0 CFM @ 25 Pascals 261 261 CFM25 / CFMfan 0.0000 Total Recovery Eff. (%)52.0 CFM @ 50 Pascals 409 409 CFM25 / CFA 0.0000 Rate (cfm)112 Eff. Leakage Area (sq.in)22.5 22.5 CFM per Std 152 N/A Hours/Day 12.0 Specific Leakage Area 0.00009 0.00009 CFM per Std 152 / CFA N/A Fan Watts 60.0 ELA/100 sf shell (sq.in)0.42 0.42 CFM @ 50 Pascals 0 Cooling Ventilation Natural Ventilation Eff. Leakage Area (sq.in)0.00 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.1471