Loading...
One Line (clean)EQUIPMENT GROUNDING CONDUCTORS 30A NEW PV PANELBOARD 480Y/277V $‘:.$ NEMA 3R OUTDOOR 30A 30A 30A 30A 30A DC AC TO INVERTERS #2-#8 SIMILAR TO INVERTER #1. ALL BREAKERS 3-POLE/30A 35KA 15A DC DISC PV SUB-ARRAY 50 X 340W (17,000W DC) SUNPOWER P17 340W MODULES 5 STRINGS, 10 MODULES PER STRING INVERTER #1 1000V DC RATED PV CABLE EQUIPMENT GROUNDING CONDUCTORS DC ACDC DISC M.L.O. INVERTERS #2-#5 SIMILAR TO INVERTER #1 1-#10AWG XHHW-2 CU EGC (TYP) INVERTER #6 (1) 2" CONDUIT EACH WITH (4) #2/0AWG XHHW-2 AL AND (4) #1AWG XHHW-2 CU EGC, 600V WIRE. UL-LISTED IEEE1547 INVERTER SETTINGS PROPOSED INVERTER SETTINGS: DEVICE PICKUP TIME DELAY 27-1 50% (240V) 0.16 SEC 27-2 88% (422V) 2.0 SEC 59-1 110% (528V) 1.0 SEC 59-2 120% (576V) 0.16 SEC 81U-1 57.0HZ 0.16 SEC 81U-2 58.0HZ 32.0 SEC 81O-1 60.5HZ 0.16 SEC VOLTAGE SETTINGS ARE BASED ON A 480V BASE FLA=18A FLA=18A FLA=108A SMA TRIPOWER 15000TL-US 15KW AC INVERTER 1000 VDC INPUT 480V 3 PHASE OUTPUT NON FUSED (1) 1" CONDUIT WITH (4) #8AWG XHHW-2 AL & (1) #10AWG XHHW-2 CU EGC. (TYP. OF ALL) COMBINER SMA CU 1000-US-10 (TYP. OF 6) SMA TRIPOWER 15000TL-US 15KW AC INVERTER 1000 VDC INPUT 480V 3 PHASE OUTPUT PV SUB-ARRAY 50 X 340W (17,000W DC) SUNPOWER P17 340W MODULES 5 STRINGS, 10 MODULES PER STRING FROM NATIONAL GRID POLE-MOUNT TRANSFORMER BANK 3-50KVA UNITS POLE #9 EXISTING BUILDING DISTRIBUTION EXISTING SWITCHBOARD MDP, $9‘: 600A/3P MCB PROPOSED LINE SIDE TAP POINT OF INTERCONNECTION (PCC) NEW TAP DISCONNECT $9‘: VISIBLE BREAK, LOCKABLE LOCATED ON INTERIOR WALL (NEMA 1) 150A FUSED FLA=108A @480V INSIDE OUTSIDE EXISTING UTILITY METER#05103724, CLASS 200, FORM 9S, 3-PHASE, 4-WIRE, TO REMAIN CT'S 600:5 NEW PRODUCTION PV METER, CLASS 200, FORM 9S, 3-PHASE, 4-WIRE, 480/277 EXISTING SECONDARY CONDUCTORS TO REMAIN (1) 2" CONDUIT EACH WITH (4) #2/0AWG XHHW-2 AL AND (4) #1AWG XHHW-2 CU EGC, 600V WIRE, LESS THAN 25' NEW PV DISCONNECT $9‘: VISIBLE BREAKER, LOCKABLE AND ACCESSIBLE TO UTILITY 24/7 (MOUNTED OUTSIDE) GND PLACARD NOTES 1. PLACARDS SHALL BE APPLIED ACCORDING TO THE REGULATIONS OF THE NEC. 2. SOLAR MODULES SHALL BE PROVIDED WITH APPROPRIATE MARKINGS TO MEET NEC REQUIREMENTS. 3. INVERTERS ALSO SHALL BE SUPPLIED WITH MARKINGS TO MEET NEC REQUIREMENTS. CONDUIT NOTES: 1. ALL OUTDOOR CONDUIT TO BE RGS OR IMC AND HAVE RAIN-TIGHT CONNECTORS AND COUPLINGS UNLESS OTHERWISE NOTED. 2. ALL NEW CONDUIT TO BE EMT, OR RGS UNLESS OTHERWISE NOTED. 3. ALL NEW CONDUITS AT ROOF ARE TO BE SURFACE MOUNTED, WHERE ATOP THE ROOF THE CONDUITS SHALL BE SUPPORTED BY C-PORT DEVICES OR EQUIVALENT. CONDUIT SUPPORTS SHALL BE LOCATED WITHIN 1' OF EVERY COUPLING FOR ALL HORIZONTAL CONDUIT RUNS ON ROOF. CONDUIT LOCATED IN OPEN WALKING SECTIONS OF THE ROOF SHALL BE MARKED WITH REFLECTIVE CAUTION TAPE. 4. THE EXACT ROUTING OF THE CONDUIT SHALL ACCOMMODATE EXISTING CONDITIONS AND OBSTACLES. CONTRACTOR TO OBTAIN OWNER APPROVAL OF PROPOSED ROUTING PRIOR TO COMMENCING INSTALLATION. 5. CONTRACTOR SHALL WATERPROOF SEAL ALL PENETRATIONS AND CORING THROUGH WALLS AND FLOORS WITH FIRE RETARDANT MATERIALS. ALL PENETRATIONS TO BE SEALED ACCORDINGLY. ELECTRICAL NOTES: 1. THIS PHOTOVOLTAIC INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2014 & 2017 EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) AND LOCAL ELECTRICAL CODES CURRENTLY BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION (AHJ), PARTICULARLY ARTICLE 690, SOLAR PHOTOVOLTAIC (DC) SYSTEMS. 2. A GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED WITH THE INVERTER IN ACCORDANCE WITH NEC 690.5(A)(B)(C). 3. DISCONNECT SWITCH SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAIN LIVE. CONDUCTORS TOWARDS MAIN SWITCHGEAR REMAIN LIVE AND SHOULD BE CONNECTED TO TERMINALS MARKED "LINE SIDE". CONDUCTORS TOWARDS PV MODULES SHOULD BE CONNECTED TO TERMINALS MARKED "LOAD SIDE". 4. PHASE AND NEUTRAL CONDUCTORS SHALL BE COPPER, MINIMUM #12 AWG, SOLID WIRE MAY BE USED. EXPOSED PHASE AND NEUTRAL CONDUCTORS SHALL BE USE-2 INSULATED. ALL OTHER PHASE AND NEUTRAL CONDUCTORS SHALL BE THWN-2 INSULATED UNLESS OTHERWISE NOTED. 5. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, MINIMUM #10AWG, SOLID OR STRANDED WIRE MAY BE USED. EXPOSED GROUNDING AND BONDING CONDUCTORS SHALL BE UNINSULATED. ALL OTHER GROUNDING AND BONDING CONDUCTORS SHALL BE THWN-2 INSULATED UNLESS OTHERWISE NOTED. 6. DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS 6.1. DC POSITIVE - BLACK (OR MARKED BLACK) 6.2. DC NEGATIVE - RED ON UNGROUNDED INVERTER SYSTEM, OTHERWISE WHITE 7. AC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS (OR MARKED AS SUCH IF #4 AWG OR GREATER) 208V 480V 7.1. PHASE A - BLACK BROWN 7.2. PHASE B - RED ORANGE 7.3. PHASE C - BLUE YELLOW 7.4. NEUTRAL - WHITE GRAY 8. GROUNDING AND BONDING CONDUCTORS IF INSULATED SHALL BE COLOR CODED GREEN (OR MARKED GREEN IF #4 AWG OR GREATER) 9. CONDUIT SIZES INDICATED ARE MINIMUMS IN ACCORDANCE WITH APPLICABLE CODES AND MAY BE INCREASED IF REQUIRED. 10. MARKING OF THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS SHALL BE PROVIDED IN ACCORDANCE WITH NEC 690.17. (SEE DETAIL C) 11. MARKING OF THE DIRECT CURRENT PHOTOVOLTAIC POWER SOURCE SHALL BE PROVIDED IN ACCORDANCE WITH NEC 690.53. 12. MARKING OF THE INTERACTIVE SYSTEM POINT OF CONNECTION SHALL BE PROVIDED IN ACCORDANCE WITH NEC 690.54. 13. INSTALLATION OF THE GEC FROM THE INVERTERS TO THE SERVICE SHALL BE PROVIDED IN ACCORDANCE WITH NEC 250.64 14. PANEL PV1 SHALL BE PROVIDED IN NEMA 1 ENCLOSURE. 15. FUSED AC DISCONNECT TO BE PROVIDED WITH THE INVERTER. 16. SYSTEM SHALL BE EQUIPPED WITH REMOTE SHUT DOWN AND ARC FAULT DETECTION AND INTERRUPTION PROTECTION, IN ACCORDANCE WITH NEC 2014 ARTICLE 690.11. 17. PHOTOVOLTAIC SYSTEMS WITH DC SOURCE CIRCUITS, DC OUTPUT CIRCUITS, OR BOTH, OPERATING AT A PV SYSTEM MAXIMUM SYSTEM VOLTAGE OF 80 VOLTS OR GREATER, SHALL BE PROTECTED BY A LISTED (DC) ARC-FAULT CIRCUIT INTERRUPTER. PV TYPE, OR OTHER SYSTEM COMPONENTS LISTED TO PROVIDE EQUIVALENT PROTECTION. THE PV ARC-FAULT PROTECTION MEANS SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: (1) THE SYSTEM SHALL DETECT AND INTERRUPT ARCING FAULTS IN DC PV SOURCE AND OUTPUT CIRCUITS. (2) THE SYSTEM SHALL REQUIRE THAT THE DISABLED OR DISCONNECTED EQUIPMENT BE MANUALLY RESTARTED. 18.DISCONNECT SHALL BE UTILITY LOCKABLE AND IN ACCORDANCE WITH ALL UTILITY REQUIREMENTS. (1) 1" CONDUIT WITH (4) #8AWG XHHW-2 AL & (1) #10AWG XHHW-2 CU EGC. (TYP. OF ALL) COMBINER SMA CU 1000-US-10 (TYP. OF 6) INPUT A INPUT B 15A 1000V DC RATED PV CABLE INPUT A INPUT B 07-24-2017 SEAL No. 0 REVISIONS DATE 6/28/2017 DESCRIPTION ISSUED FOR REVIEW & INT APPLICATION DESCRIPTIONNo. DATE REVISIONS REVIEWED BY: CHIEF DESIGNER: PROJ. MANAGER: DATE NORTHEAST SOLAR / VCA INC. 209 EARLE STREET - PV PROJECT 90.0KW AC ONE-LINE DIAGRAM NORTHAMPTON MASSACHUSETTS 361F JUNE 2017 E-1 NONE POWER ENGINEERS, LLC 37 Fox Den Road Kingston, MA 02364-2150 (508) 612-0382 www.PowerEngineersLLC.com Electrical Engineering, Power, Lighting, Technical Studies and Utility Consulting SCALE: DATUM: VERT.: HORZ.: VERT.: HORZ.: PROJ. No.: DATE: SIZE: D REV:2 1 7/17/2017 REVISED PER CLIENT COMMENTS 2 7/24/2017 REVISED PER CLIENT COMMENTS