Loading...
Chapter 34 review Henshaw B & C Archimetrics Design Studio 53 South Union Street, Plainfield, MA 01070 Peter Lapointe, Architect 413-634-0091 archimetricsdesign@verizon.net September 15, 2016 Louis Hasbrouck, Building Commissioner City of Northampton Northampton, MA 01060 RE: Enabling Neilson – 5 Building Renovations CHAPTER 34 REVIEW Henshaw B – 10 Henshaw Avenue 1st Floor 2640sf 2nd floor 3024 sf Henshaw C – 10 Henshaw Avenue 1st floor 1320sf 2nd floor 1512 sf Existing Use R-2 Proposed Use B Construction Type 5B – Fully sprinklered Overview: Henshaw B & C are existing multifamily town house units constructed in the 1970’s being converted to faculty offices. Four units will be converted to separate six faculty office clusters with accessible entrances, accessible toilet facilities and accessible student conference space. Of the six offices, the two new offices created on the first floor will be accessible. Limited construction involves modifications on the first floor. Second floor layouts remain largely unchanged. In Henshaw B, the accessible six bedroom dwelling unit, common laundry and second floor head resident dwelling unit are being combined to create a single 12 office cluster. The change in occupancy classification requires compliance with IEBC Chapter 9 as follows: 903 through 906 require compliance with Section 912. 907: The existing floor framing (2x12 joists) is adequate for office loading (50 psf) as defined in IBC Table 1607.1. Snow and wind loads are unchanged and no seismic upgrades are required. 908: Electrical service upgrades, rewiring and new devices and LED lighting upgrades are proposed throughout both buildings. Archimetrics Design Studio 53 South Union Street, Plainfield, MA 01070 Peter Lapointe, Architect 413-634-0091 archimetricsdesign@verizon.net 909: Heating, ventilating and A/C upgrades are proposed throughout both buildings. 910: Plumbing facilities for both sexes, drinking fountains and service sinks are being provide for each unit within each building consistent with plumbing code requirements for the new occupancy. 911: Light and ventilation requirements for new construction are met by proposed exterior changes to doors and windows. 912.1.1: Compliance with Chapter 8 will be discussed by Section following the Chapter 9 review. 912.4: The Change in Occupancy reduces the Means of Egress Hazard Index from 3 to 4 requiring compliance with 912.4.2. The egress capacity meets requirements for new construction and modifications to the existing open risers, handrails and guards are proposed. Open riser will be eliminated and new closure panels will be added to the open railing system. 912.5 & 6: The change of use to a lower hazard index deems the existing building height and area and exterior wall construction to be acceptable. 912.7.2: Stairways: Changes to the existing open stairways are not required since there is no increase in Egress Hazard Index. IBC Section 1022.1 exception 1 allows unenclosed stairways when the occupant load for the stair is less than 10. The existing stairways meet this requirement. Number of Exits: IBC 1021.1 Table 1021.2 allows one exit from the second floor in Use B from the first and second floor. 912.8: Accessibility requirements are met by proposed improvements to entrances and the addition of an accessible restroom. Proposed first floor changes include dimensional compliance for all doors. Chapter 8: The limited scope of alterations, no structural changes other than new headers at new openings and proposed exit and emergency lighting is consistent with the requirements of Chapter 8. The proposed fire alarm system and existing fire protection system exceed the requirements for new construction. Archimetrics Design Studio 53 South Union Street, Plainfield, MA 01070 Peter Lapointe, Architect 413-634-0091 archimetricsdesign@verizon.net Chapters 6 & 7: Existing construction and proposed construction without exception meet or exceed the requirements of these chapters for Repairs and Alterations. Respectfully submitted, Peter Lapointe