Adams Fire Alarm Narrative 2018-09-11 Fire Alarm System Narrative Report Adams House 40-42 Round Hill Northampton, MA. Prepared By: Fire Equipment Inc 42 NORMAN STREET WEST SPRINGFIELD, MA 01090 Fire Alarm Designer/Supplier Fire Equipment Inc. 42 Norman Street West Springfield, MA 01089 Contact: Dana Ploof Tel: 413-734-6500 Fax: 413-734-6700 Cell: 413-333-7490 Email: dploof@feinewengland.com Fire Alarm Installer Palmeri Electric, LLC 679C Mohawk Trail Shelburne Falls, MA 01370 Contact: Matt Palmeri Tel: 413-625-6356 Email: matthew@palmerielectric.com Section 1-Basis of Design 1.1 Applicable Laws, Regulations and Standards: NFPA 72, 2013 National Fire Alarm and Signaling Code Ninth Edition of the Massachusetts Building Code 1.2 Design Responsibility a.) The design responsibility of the: a. Fire alarm system is the fire alarm designer/supplier 1.3 Fire Protection Systems to be Installed a.) Fire Alarm System The proposed fire alarm system will consist of manual pull stations at each exit. Smoke detection will be provided above the fire alarm control panel, in the basement, and stairs. Combination smoke and carbon monoxide detection will be installed in corridors outside each bedroom. Heat detectors will be provided in each dwellings kitchen and weatherproof heat detectors will be provided on each exterior covered porch. System connected low frequency sounder base smoke detectors will be provided in each bedroom. Monitor modules will be provided to monitor one sprinkler system tamper and flow switch each in the basement. Combination horn and strobe notification appliances will be provided in the basement, common corridors, and in each dwelling unit. The fire alarm system has been designed to operate in the absence commercial power, on batteries, for 24 hours followed by a full system alarm activation for 5 minutes. Section 2- Sequence of Operations 2.1 Fire Sprinkler System Water flow Upon sprinkler system water flow, the following functions shall be performed. Indicate alarm condition at the Fire Alarm Control Unit Initiate building evacuation through building alarm system Transmit alarm signal to central stations as described in Section 2.3. 2.2 Fire Sprinkler Control Valve Fire sprinkler system control valve equipped with tamper switche to indicate either partial or complete closure will be monitored by the fire alarm system with a monitor module. Upon fire sprinkler system control valve partial or complete closure, the following functions shall be performed. Indicate supervisory condition at the Fire Alarm Control Unit Transmit supervisory signal to central stations as described in Section 2.3. 2.3 Fire Alarm System In the event of a fire initiation, be it manual or automatic, occupants will be notified by means of horns sounding temporal three pattern and visual notification throughout the common spaces. Low frequency sounder bases will activate in bedrooms. An exterior visible notification appliance will continuously flash at the fire department response point and an alarm signal will be sent to central monitoring station. In the event that carbon monoxide is detected, temporal 4 pattern audible notification will be generated throughout and a supervisory notification will be indicated on the panel and will be sent to the central monitoring station. In the event that the tamper switch is activated on a sprinkler control valve, a supervisory signal will activate on the fire alarm control panel and a supervisory signal will be sent to the central monitoring station. Section 3-Testing Criteria 3.1 Personnel General: The installing contractor shall notify the owner's representative and the local fire department of the testing schedule for the installation of fire suppression systems so that each may be represented at the time of testing. Fire alarm testing shall be in compliance with the requirements of NFPA72, 2013. 3.2 Testing Equipment and Tools As-built drawings Notification announcement Canned smoke and carbon monoxide 3.3 Approval Requirements A signed Contractor's Test and Material Certificate shall be given to each party as outlined in section 3.1b to document system operation and testing.