30 Locust BC care 2016-08-26DRAWING LIST
A0.00 GENERAL NOTES, ABBREVIATIONS, LEGENDS
A0.10 LIFE SAFETY
A0.20 GROUND FLOOR EXISTING PLAN
A0.21 BASEMENT EXISTING PLAN
A0.30 PHASING PLAN
A1.00 DEMOLITION PLAN GENERAL NOTES, KEYS, LEGENDS
A2.00 FLOOR PLANS GENERAL NOTES, KEYS, LEGENDS
A2.10 NEW WORK PLAN
A2.11 NEW PLAN POWER COORDINATION
A2.12 ROOF PLAN
A4.00 FINISH PLAN GENERAL NOTES, KEYS, LEGENDS
A4.10 SEAMING DIAGRAM
A5.00 INTERIOR ELEVATIONS GENERAL NOTES, KEYS, LEGENDS
A5.10 INTERIOR ELEVATIONS
A5.11 INTERIOR ELEVATIONS
A5.12 INTERIOR ELEVATIONS
A6.00 REFLECTED CEILING GENERAL NOTES, KEYS, LEGENDS
A9.10 DOOR HARDWARE, FRAME TYPES & DETAILS
A9.20 CASEWORK MENU AND DETAILS
A9.30 CUSTOM CASEWORK DETAILS - TECH WORKROOM
A9.40 INTERIOR DETAILS
A9.50 HARDWOOD DOOR DETAILS
A9.60 LIAISON DESK DETAILS
A10.00 FF&E PLAN AND SCHEDULES
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
MEP/FP Engineer
Project Number:
Date Issued:
30 LOCUST STREET
NORTHAMPTON, MA 01060
COMPREHENSIVE BREAST CARE CENTER
185-01-00
8/15/16
COOLEY DICKINSON HOSPITAL
COMPREHENSIVE BREAST CARE
CENTER
ISSUED FOR CONSTRUCTION
S1.00 GENERAL NOTES, GROUND FLOOR PLAN
S2.00 FRAMING DETAILS
MEP-100 MEP GENERAL NOTES, ABBREVIATIONS, AND SYMBOL LISTS
MEP-101 MEP DETAILS
MEP-102 MEP SCHEDULES
FPD-101 GROUND FLOOR FIRE PROTECTION DEMOLITION PLAN
PD-100 BASEMENT PLUMBING DEMOLITION PLAN
PD-101 GROUND FLOOR PLUMBING / FIRE PROTECTION DEMOLITION PLAN
MGD-101 GROUND FLOOR MEDICAL GAS DEMOLITION PLAN
FP-101 GROUND FLOOR FIRE PROTECTION PLAN
PS-100 BASEMENT PLUMBING PLAN
PS-101 GROUND FLOOR PLUMBING SANITARY AND VENT PLAN
PW-101 GROUND FLOOR PLUMBING DOMESTIC WATER PLAN
MG-101 GROUND FLOOR MEDICAL GAS PLAN
P-400 PLUMBING / FIRE PROTECTION DETAILS
HD-101 GROUND FLOOR HVAC DEMOLITION PLAN
H-100 BASEMENT HVAC PLAN
H-101 GROUND FLOOR HVAC DUCTWORK PLAN
HP-101 GROUND FLOOR HVAC PIPING PLAN
H-400 HVAC DETAILS
ED-101 GROUND FLOOR ELECTRICAL DEMOLITION PLAN
E-100 BASEMENT ELECTRICAL PLAN
EL-101 GROUND FLOOR ELECTRICAL LIGHTING PLAN
EP-101 GROUND FLOOR ELECTRICAL POWER PLAN
ES-101 GROUND FLOOR ELECTRICAL SPECIAL SYSTEMS PLAN
E-400 ELECTRICAL DETAILS
T-101 GROUND FLOOR TECHNOLOGY PLAN
PROJECT LOCATION
PROJECT LOCATION: GROUND FLOOR
FOR GC COORDINATION:
ROOM G-105 SHEET 1.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 2.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 2.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 2.2 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 3.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 3.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 3.2 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 3.3 EQUIPMENT VENDOR DRAWINGS
ROOM G-105 SHEET 4.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 1.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 2.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 2.2 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 3.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 3.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-113 SHEET 4.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 1.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 2.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 2.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 3.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 3.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 3.2 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 4.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-120 SHEET 4.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 1.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 2.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 2.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 3.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 3.1 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 3.2 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 4.0 EQUIPMENT VENDOR DRAWINGS
ROOM G-122 SHEET 4.1 EQUIPMENT VENDOR DRAWINGS
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
& AND
L ANGLE
@ AT
CENTERLINE
Ø DIAMETER
# POUND
A/E ARCHITECT / ENGINEER
AB ANCHOR BOLT
ACBL ACCESSIBLE (ADA COMPLIANT)
ACOUS ACOUSTICAL
ACP ACOUSTICAL CEILING PANEL
AD ACCESS DOOR
ADA THE AMERICANS WITH DISABILITIES ACT
ADBL ADAPTABLE (ADA COMPLIANT)
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJUSTABLE
ADJC ADJACENT
AF ACCESS FLOOR
AFF ABOVE FINISHED FLOOR
AFI AIR FLOW INDICATOR
AGGR AGGREGATE
AL ALUMINUM
ALT ALTERNATE
ANOD ANODIZED
AP ACCESS PANEL
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASPH ASPHALT
AVAF AUDIO/VISUAL ALARM
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BUR BUILT-UP ROOFING
CA CARD ACCESS
CAB CABINET
CB CASING BEAD
CEM CEMENT
CEMTS CEMENTITIOUS
CER CERAMIC
CG CORNER GUARD
CGE CORNER END GUARD
CHAN CHANNEL
CHBD CHALKBOARD
CHFR CHAMFER
CJ CONSTRUCTION JOINT
CL CENTER LINE
CLG CEILING
CLJ CONTROL JOINT
CLO CLOSET
CLR CLEAR
CLRM CLASSROOM
CMPST COMPOSITE
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CASED OPENING
COL COLUMN
COMP COMPUTER
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPRS COMPRESSIBLE OR COMPRESSION
CR CHAIR RAIL
CRS COLD ROLLED STEEL
CS CAST STONE
CSK COUNTERSUNK
CSMT CASEMENT
CSWK CASEWORK
CYL CYLINDER
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DG DECORATIVE GLASS
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DIV DIVISION
DMBD DRY MARKER BOARD
DMPF DAMPPROOFING
DN DOWN
DO DITTO
DOP DOOR OPENING
DPG DECORATIVE PLASTIC GLAZING
DS DOWNSPOUT
DSP DRY STANDPIPE
DST DOOR STOP
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRIC
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENTR ENTRANCE
EO EMERGENCY POWER
EP ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EPRF EXPLOSION PROOF
EQ EQUAL
EQUIP EQUIPMENT
ESCAL ESCALATOR
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVATE
EXH EXHAUST
EXP EXPANSION
EXIST EXISTING
EXT EXTERIOR
F/F FACE TO FACE
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FB FLAT BAR
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
FGL FIBERGLASS
FHC FIRE HOSE CABINET
FHP FULL HEIGHT PARTITION
FH FULL HEIGHT
FIN FINISH
FL FLASHING
FLR FLOOR OR FLOORING
FLUOR FLUORESCENT
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FPRF FIREPROOFING
FS FULL SIZE
FSH FIRE SPRINKLER HEAD
FSTP FIRESTOPPING
FT FOOT OR FEET
FTG FOOTING
FURN FURNITURE
FURR FURRING
FUT FUTURE
G GAS
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GEN GENERATOR
GFRC GLASS FIBER REINFORCED CONCRETE
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GLMU GLASS MASONRY UNIT
GMMU GLASS MESH MORTAR UNIT
GND GROUND
GR GRADE
GRL GRILLE
GRTG GRATING
GSKT GASKET
GT GROUT
GVL GRAVEL
GWB GYPSUM WALL BOARD
GYP GYPSUM
HB HOSE BIBB
HC HOLLOW CORE
HDBD HARDBOARD
HDWD HARDWOOD
HDWE HARDWARE
HGR HANGER
HGT HEIGHT
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HPT HIGH POINT
HR HOUR
HSAFD HORIZONTAL SLIDING ACCORDION FIRE DOOR
HVAC HEATING, VENTILATION, AIR CONDITIONING
HYDR HYDRAULIC
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH OR INCHES
INSUL INSULATION
INTR INTERIOR
IWH INSTANTANEOUS WATER HEATER
JAN JANITOR
JST JOIST
JT JOINT
KIT KITCHEN
KO KNOCKOUT
KOP KNOCKOUT PANEL
KPL KICK PLATE
L LEFT
LAB LABORATORY
LAD LADDER
LAM LAMINATION
LAV LAVATORY
LB POUND
LBL LABEL
LF LINEAR FOOT
LG LENGTH
LG LENGTH
LH LEFT HAND
LHR LEFT HAND REVERSE
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LLH LONG LEG HORIZONAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LONG LONGITUDINAL
LP LIGHTPROOF
LPT LOW POINT
LT LIGHT
LTWT LIGHTWEIGHT
LTG LIGHTING
LVR LEVER OR LOUVER
MACH MACHINE
MAINT MAINTENANCE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MET METAL
MEZZ MEZZANINE
MFG MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOLDING
MLWK MILLWORK
MO MASONRY OPENING
MTD MOUNTED
MTR MORTAR
MULL MULLION
MVBL MOVABLE
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OFF OFFICE
OPNG OPENING
OPP OPPOSITE
OT ELECTRICAL OUTLET
OXY OXYGEN
PB PANIC BAR
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PGBD PED BOARD
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTIC
PLBG PLUMBING
PLYWD PLYWOOD
PNEU PNEUMATIC
PNL PANEL
PNT PAINT
PNTD PAINTED
POL POLISHED
POLY POLYETHYLENE
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PREFIN PREFINISHED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVG PAVING
QT QUARRY TILE
QTY QUANTITY
QUAL QUALITY
R RISER
RAD RADIUS
RBR RUBBER
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCED OR REINFORCING
REM REMOVEABLE
REQD REQUIRED
RESIL RESILIENT
RFG ROOFING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RLG RAILING
RM ROOM
RO ROUGH OPENING
RV ROOF VENT
RWL RAIN WATER LEADER
S SOUTH
SC SOLID CORE
SCHED SCHEDULE
SCRN SCREEN
SD SOAP DISPENSER
SECT SECTION
SGL SINGLE
SHR SHOWER
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SK SINK
SLV SLEEVE
SM SHEET METAL
SND SANITARY NAPKIN DISPENSER
SNR SANITARY NAPKIN RECEPTACLE
SPEC SPECIFICATION
SQ SQUARE
SSK SERVICE SINK
SSP SOLID SURFACE POLYMER
SST STAINLESS STEEL
ST STREET
STA STATION
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMBOL
SYMM SYMMETRICAL
SYS SYSTEM
T THERMOSTAT
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TOWEL BAR
TBM TOP OF BEAM
TC TOP OF CONCRETE
TD TEL / DATA
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TF TOP OF FOOTING
TFF TOP OF FINISHED FLOOR
THK THICKNESS
THRES THRESHOLD
THRU THROUGH
TKBD TACKBOARD
TMPD TEMPERED
TOL TOLERANCE
TP TOP OF PAVEMENT
TPH TOILET PAPER HOLDER
TS TACKABLE SURFACE
TSL TOP OF SLAB
TST TOP OF STEEL
TV TELEVISION
TW TOP OF WALL
TYP TYPICAL
U/C UNDER COUNTER
UNEX UNEXCAVATED
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UR URINAL
UV ULTRAVIOLET
VAC VACUUM
VAF VISUAL ALARM
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF CONTRACTOR TO VERIFY IN FIELD
VNR VENEER
VR VAPOR RETARDER
W WEST
W/ WITH
W/O WITHOUT
WC WATERCLOSET
WD WOOD
WLD WELDED
WSCT WAINSCOT
WT WEIGHT
WTRPRF WATERPROOFING
WWF WELDED WIRE FABRIC
CL
1
A1.01
SIM
A1.01
1 SIM
TOP OF SLAB
ELEV = 100'-0"
WINDOW / LOUVER SYMBOL
DOOR MARK
ELEVATION /
LEVEL MARKER
DATUM POINT ELEV = 100'-0"
1 View Name
1/8" = 1'-0"
1
2
3
4 A5.01
1
A1.01
SIM
1
A1.01
SIM
1
A1.01
SIM
ACCESSIBILITY
CLEARANCES
REVISION SYMBOL
ACCESSIBILITY SYMBOL
BUILDING SECTION
WALL SECTION
DETAIL
PLAN /
SECTION DETAIL
ELEVATION INTERIOR
ELEVATION EXTERIOR
SCALE:
1 View Name
1/8" = 1'-0"A1.01
VIEW NAME: PLAN,
SECTION, ELEVATION,
DETAILS
VIEW NAME WITH
REFERENCE
COLUMN GRIDS
PARTITION SYMBOL
FN-00FURNITURE SYSTEM SYMBOL
CURTAIN WALL PANEL SYMBOL
EQUIPMENT SYMBOL
#
ROOM TAG
/1 A1.01MATCH LINE
CEILING TYPE/HT.
ROOM NUMBER
FINISH KEY
APPROX ROOM AREA
SHEET REFERENCE
CEILING TYPE
CEILING HEIGHT
EQUIP. NUMBER
PARTITION TYPE
PANEL TYPE
WINDOW / LOUVER
MARK
COLUMN NUMBER
FURNITURE
NUMBER
CASEWORK TAG
CASEWORK TYPE
1
A5.01
COLUMN LETTER
CEILING
WALL
BASE
FLOOR
R 2 ' - 6 "FINISH TAG
1
001M
12'-6"
TYPE
EQ-00
PL
X1
Room Name
101
F B W C
123 SF
WIN
X
#
1541-A
ROOM # - PRIMARY, SECONDARY, ECT.
OVERHEAD (OVER
COUNTER AND SOFFITS)
CALLOUT
BREAK LINE
GRID LINE
BELOW OR BEYOND
(UNDERCOUNTER AND FOOTINGS)
SCOPE OF WORK
CASED OPENING
PAIR
TYPICAL DOOR
DOOR WITH SIDELIGHT
VARYING LEAF
SLIDING
DOUBLE ACTING
TYPICAL WINDOW
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EXISTING WALL
NEW WALL
DEMOLISHED WALL
ALUMINUM
WOOD FINISH
EXISTING BUILDINGS
STEEL
CONCRETE
EARTH
RIGID INSULATION
RUBBER
SAND
GYPSUM BOARD
INSULATION
CMU
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:27 AMA0.00
185-01-00
8/15/16
GENERAL NOTES,
ABBREVIATIONS, LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
ABBREVIATIONS SYMBOLS LINE TYPES
DOORS / WINDOWS / WALLS
MATERIALS
Issuance Schedule
Number Date Description
DN UP
FECFDVCDOWN 23R
UP 23R DN. 23RWFECFDVC
SCOPE OF WORK
MAX DISTANCE TRAVELED 120'-0"TWO HOUR FIRE SEPARATION ASSEMBLY
WITH 90 MINUTE OPENING PROTECTED
EGRESS ROUTE
(TRAVEL DISTANCE)
ONE HOUR FIRE SEPARATION ASSEMBLY
WITH 45 MINUTE OPENING PROTECTED
EGRESS STAIR
MAINTAIN 2 HOUR
CONSTRUCTION
SMOKE PARTITION ASSEMBLY WITH 20
MINUTE OPENING PROTECTED. (NFPA 101)
ELEVATOR
MAINTAIN 2 HOUR
CONSTRUCTION
SHAFT
MAINTAIN 2 HOUR
CONSTRUCTION
CODE REVIEW BASED ON MASSACHUSETTS 8TH EDITION BASE CODE: MASSACHUSETTS AMENDMENTS TO
THE INTERNATIONAL BUILDING CODE 2009, AND MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL
EXISTING BUILDING CODE 2009.
SCOPE
RENOVATION TO AN EXISTING SPACE TO CREATE A BREAST CARE CENTER. THE SPACE WAS PREVIOUSLY
CLASSIFIED AS BUSINESS (B) OCCUPANCY, AND WILL REMAIN BUSINESS (B) FOLLOWING THIS PROJECT.
EXTERIOR WALLS, EGRESS STAIRS, ELEVATORS AND COMMON CORRIDORS ARE TO REMAIN UNCHANGED
AND ARE OUTSIDE THE SCOPE OF THIS PROJECT.
CLASSIFICATION
WORK AREA CLASSIFICATION OF WORK:
ALTERATIONS - LEVEL 1 (IEBC CHAPTER 6)
THE EXISTING BUILDING OR PORTIONS THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING
BECOMES LESS SAFE THAN ITS EXISTING CONDITION, UNLESS THE PORTION ALTERED CONFORMS TO THE
REQUIREMENTS OF 780 CMR.
USE GROUP: BUSINESS (B)
CONSTRUCTION TYPE:
SINCE THE PROJECT DOES NOT INCLUDE A CHANGE OF USE OR ADDITION, THE PROPOSED WORK DOES
NOT TRIGGER COMPLIANCE WITH HEIGHT AND AREA LIMITATIONS OR MINIMUM CONSTRUCTION TYPE.
THEREFORE, THE RENOVATION IS ONLY REQUIRED TO MAINTAIN AND BE CONSISTENT WITH THE EXISTING
CONSTRUCTION TYPE.
FIRE RESISTANCE RATINGS:
THE PROJECT DOES NOT INCLUDE THE ALTERATION OR INSTALLATION OF ANY NEW BUILDING ELEMENTS
THAT REQUIRE A FIRE RESISTANCE RATING. THIS INCLUDES THE NEW CORRIDOR WALLS, AS THE
BUILDING IS PROVIDED WITH SPRINKLER PROTECTION THROUGHOUT (TABLE 1018.1). THEREFORE NO
FURTHER UPGRADES ARE TRIGGERED BY THE PROPOSED WORK.
VERTICAL OPENINGS
BECAUSE THE BUILDING IS PROVIDED WITH SPRINKLER PROTECTION THROUGHOUT, EXISTING
UNPROTECTED VERTICAL FLOOR OPENINGS ARE NOT REQUIRED TO BE ENCLOSED PER IEBC 703.2.1 EX.
5.2. NEW VERTICAL OPENINGS ARE REQUIRED TO COMPLY WITH 780 CMR 708.2.
INTERIOR FINISHES
THE INTERIOR FINISH OF WALLS AND CEILINGS IN THE WORK AREA MUST COMPLY WITH THE CODE
REQUIREMENTS FOR NEW CONSTRUCTION (IEBC 703.4).
MEANS OF EGRESS
MEANS OF EGRESS THROUGHOUT THE WORK AREA ARE REQUIRED TO COMPLY WITH CHAPTERS 6 & 7 OF
THE EXISTING BUILDING CODE; THE REMAINING PORTIONS OF THE BUILDING MUST MAINTAIN OR IMPROVE
THEIR CURRENT LEVEL OF EGRESS (IEBC 6.04.1 & 705.1).
-ALL ROOMS OR SPACES WITH A TRAVEL DISTANCE OVER 75 FEET OR WITH AN OCCUPANT LOAD
GREATER THAN 50 MUST BE PROVIDED WITH TWO REMOTE EGRESS DOORS (IEBC 705.4.1.1).
-THE WORK AREA EGRESS DOORS ARE NOT REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
SINCE THERE ARE FEWER THAN 50 OCCUPANTS (780 CMR 1008.1.2). PANIC HARDWARE IS NOT REQUIRED
(780 CMR 1008.1.10).
-IN THE WORK AREA, THE MAXIMUM DEAD-END CORRIDOR LENGTH IS 70 FEET (IEBC 705.6 EX. 3). NOTE:
NO DEAD END CORRIDORS IN THE WORK AREA EXCEED 35 FEET.
-SINCE THE PROJECT DOES NOT INCLUDE AN INCREASE IN THE NUMBER OF OCCUPANTS OR A REDUCTION
IN THE AVAILABLE EGRESS CAPACITY, THE EXISTING MEANS OF EGRESS CAPACITY IS ASSUMED TO BE
ADEQUATE.
ENERGY CODE PROVISIONS FOR EXISTING BUILDINGS
THE BUILDING IS SUBJECT TO THE 2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) INCLUDING
THE AMENDMENTS CONTAINED IN 780 CMR CHAPTER 13. LEVEL 2 ALTERATIONS TO EXISTING BUILDINGS
ARE PERMITTED WITHOUT REQUIRING THE ENTIRE BUILDING TO COMPLY WITH THE ENERGY
REQUIREMENTS OF THE IECC. THE NEW ELEMENTS SHALL CONFORM TO THE ENERGY REQUIREMENTS
OF THE IECC AS THEY RELATE T NEW CONSTRUCTION ONLY (IEBC 711.1).
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:47:28 AMA0.10
185-01-00
8/15/16
LIFE SAFETY
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1" = 20'-0"1 GROUND FLOOR - LIFE SAFETY
LIFE SAFETY LEGEND
LIFE SAFETY NOTES
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
DN UP
FECFDVCDOWN 23R
UP 23R
DN. 23R
700 SF ON-CALL
64
FD
FECMGAPMGCV FDVCFECMGCVFDVC
EXISTING TRANSPORT STORAGE
G12
EXISTING ED ADMIN CLINICAL
G13
EXISTING STORAGE
G14
ELEVATORELEVATORELEVATOR
EXISTING ED MEN'S LOCKERS
G15
EXISTING ED WORK &
LOCKERS
EXISTING ED DOCTOR LOUNGE
G06
EXISTING ED CONF ROOM
G05
EXISTING
OFFICE
EXISTING
STORAGE
EXISTING OFFICE
G16
EXISTING LINEN
EXISTING LINEN
EXISTING ED ADMIN
G04
EXISTING OFFICE
EXISTING EMERG
MGMT STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL
SLEEP
G19
EXISTING VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
CAFE
PUBLIC TOILETS
RADIOLOGY
WATER DISPENSER
EMERGENCY DEPARTMENT
MAIN ENTRANCE AT GRADE
CLEARLY MARKED
SCOPE OF WORK
CLASSROOM
CONFERENCE ROOM
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/16" = 1'-0"8/15/2016 9:47:29 AMA0.20
185-01-00
8/15/16
GROUND FLOOR EXISTING
PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
MGCVx x x x x
x x x xxx x xSHARPSPYXISPAT MONILL BOXPAT MON
PAT MONDEFIBCLOCK DEFIBCLOCK
PRINTER
CLOCK CLOCK CLOCK
SHAR
P
S
PYXISRESUS CARTPA T MO NILL BOXPA T MO N
PA T MO N
DEFIB
RESUS CARTCLOC
K
DEFIB
CLO CK
PRINTER
CLO CK CLO CK CLO CK
UP
UP
RAMP UP
1:12 SLOPE MAX. TYP.RAMP UP1:12 SLOPE MAX. TYP.MECHANICAL SPACE
LOADING DOCK
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/16" = 1'-0"8/15/2016 9:47:30 AMA0.21
185-01-00
8/15/16
BASEMENT EXISTING PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
7 8
910
1112131415
16
17
18 19 20 21 22
23
25
26
27
28
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
LARGE
MAMMOGRAPHY
G-120
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
EXAM 2
G-107
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
MAMMOGRAPHY
G-122
NURSE STATION
G-126
STAFF BREAK
ROOM
G-123
ULTRASOUND
G-121
STRETCHER
WAITING
G-127
OFFICE
G-108
EXAM 1
G-106
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
INTERVIEW 1
G-118
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
SUB WAITING
G-119
PATIENT TOILET
G-109
LIAISON
G-114C
CORRIDOR
G-115C
CORRIDOR
G-115B
CORRIDOR
G-111
CORRIDOR
G-115A
CORRIDOR
G-128
CORRIDOR
G-119B
SUB WAITING
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
MAINTAIN ACCESS
MAINTAIN ACCESS
SECONDARY ENTRANCE
PROPOSED CONSTRUCTION BARRIER
INTERIM ENTRANCE & PROPOSED CONSTRUCTION BARRIER
GC TO COORDINATE SCOPE OF WORK SUCH THAT THE CONSTRUCTION
BARRIER IS IN PLACE FOR NO MORE THAN ONE MONTHMIN5'-0"PRIMARY ENTRANCE
PROPOSED CONSTRUCTION BARRIER
1. WORK WITHIN PHASING AREA (BEHIND PROTECTION BARRIER) TO BE COMPLETED DURING NORMAL HOURS
UNLESS INDICATED OTHERWISE ON DRAWINGS.
2. ALL WORK OUTSIDE PHASING AREA TO BE COMPLETED DURING OFF-HOURS (NIGHTS AND WEEKENDS)
3. ALL WORK OUTSIDE PHASING AREA ON THE FLOOR ABOVE OR BELOW, TO BE COMPLETED DURING OFF HOURS
(NIGHTS AND WEEKENDS)
4. ALL SHUTDOWNS TO BE COMPLETED DURING OFF-HOURS (NIGHTS AND WEEKENDS).
5. ALL SCHEDULING OF WORK SHALL BE COORDINATED WITH THE CLIENT AND/OR AUTHORIZED
REPRESENTATIVE/PROJECT MANAGER.
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:31 AMA0.30
185-01-00
8/15/16
PHASING PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
PHASING NOTES
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
7 8
910
1112131415
16
17
18
50
50
50
50
50
5050
50
5050
50
10
10
10
10
10
10
10
10 10
10
10
10
10
10
10
10
10
10
10
1010
41
41
41
50
41 41
41
41
41
41
50
41
41
41
41
41
41
41
41
01
01
41
41
06
06
06
06
06
01
01
01
01
01
01
01
01
01
2020
20
20
20
20
20
20
2020
20
30
30
30 30
30
30
30
30
30
30
303030
30
20
71
71
14
20 30
06
42
42
01
ELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
14
01
02
02
02
02
02
02
02
02
02
02
02
02
02
02
0202 02
02
20
42
20 30
01
SCOPE OF WORK
19 20 21 22
23
25
26
27
28
02
02
02
10
10
10
50
41
50
50
01
30
10
41
50
01
50
50
41
50
01
01
01
01
50
50 5041
10
01
01
01
50
01
10
10
41
20 30
20 30
20 30
20
30
20 30 20
30
20 30
20
20
20 30
01
01
01
01
01 10
01
0101
01
01
0110
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
41
63
63
63
10
63
63
63
63
63
63
09
20 30
42
64
64
64
42
42
64
64
02
02
02 02
64
02
02
10
10
64
02
42 64
64
64
64
42
10
414141
64
41
01 64
64
64
64
64
14
01
64
64
42
42 41
50
41
41
64 64
64
64
42
09
64 64
64
64
41
41
41
64
64
64
64
64
64
64
6464
42
42
42
42
42
01
01
01
01
01
01 01
01 01
01
0101
01
01
01
01 01
01
01
01010101
01
0101
01
01
01
01
01
01
01
01
01
0101
01
01
01
01
0101
01
01
01
01
01
01
01
01
01
01
01
31
31
31
64
64
01
14
41
64
10
01
64
10 10
10
01
64 64 64
10
64
01
01
64
20 302030
EXTENT OF DEMO
01
10
01
01
64
64
01 01
64
64
42
20 30
10
10
64 64
64
01 42
01
02
05
0505
0505
05
05
02
05
05
05
05
05
05
05
05 05
05
09
09EXTENT OF DEMOEXTENT OF DEMO
30
20 30
27' - 0"
EXTENT OF FLOOR DEMO
90
90
91
1. SCOPE OF WORK LINE GENERALLY INDICATES THE AREA OF GREATEST IMPACT DURING RENOVATIONS. EXISTING
AREAS OUTSIDE THE SCOPE OF WORK LINE THAT ARE DISTURBED IN ORDER TO COMPLETE THIS AREA ARE
CONSIDERED TO BE PART OF THE SCOPE OF WORK WHETHER INDICATED SPECIFICALLY OR NOT. CONTRACTOR
SHALL ALLOW FOR REMOVAL AND REPLACEMENT OF EXISTING FINISHES OUTSIDE THE SCOPE OF WORK LINE IN
ORDER TO COMPLETE THE WORK.
2. SEE HOURS OF WORK REQUIREMENTS AND COORDINATE DEMOLITION ACTIVITIES ACCORDINGLY.
3. REFER TO ALL OTHER CONSULTANT AND VENDOR DRAWINGS AND SPECIFICATIONS FOR EXTENT AND
REQUIREMENTS OF REMOVAL/SALVAGE/RELOCATION OF STRUCTURAL, PLUMBING/FIRE PROTECTION,
MECHANICAL AND ELECTRICAL ITEMS. COORDINATE WITH ALL ASSOCIATED TRADES.
4. REFER TO DIV. 01 SECTION "CUTTING AND PATCHING" FOR REQUIREMENTS RELATED TO CUTTING AND PATCHING
DUE TO DEMOLITION ACTIVITIES.
5. REFER TO DEMOLITION SPECIFICATION (DIVISION 01) FOR REQUIREMENTS RELATED TO DEMOLITION ACTIVITIES.
6. DISPOSE OF ALL DEMOLITION ITEMS IN ACCORDANCE WITH PROJECT SPECIFICATIONS.
7. REMOVE ALL ITEMS SHOWN AS DASHED LINES ON THE DEMOLITION DRAWINGS, INCLUDING ALL ASSOCIATED
FITTINGS AND ACCESSORIES ASSOCIATED WITH ITEM(S) BEING REMOVED.
8. DEMOLITION KEYNOTES NOT SPECIFICALLY TAGGING AN INDIVIDUAL ITEM (NO LEADER ARROW) REFER TO ALL
ITEMS WITHIN THE ROOM OR AREA IN WHICH THE NOTE IS LOCATED.
9. WHERE A PARTITION IS SHOWN TO BE DEMOLISHED, CONTRACTOR TO REMOVE ALL WALL MOUNTED
FIXTURES/FITTINGS/EQUIPMENT.
10. FIRE RATINGS TO BE MAINTAINED AT ALL RATED ASSEMBLIES AT ALL TIMES.
11. FOR THE PURPOSES OF A COMPLETE SCOPE OF WORK THE CONTRACTOR IS TO ASSUME THAT ALL EXISTING
WALLS TO BE DEMOLISHED THAT ARE GREATER THAN 8" THICK ARE CHASE WALLS, CONTINUOUS TO ADJACENT
FLOORS AND WILL REQUIRE PATCHING.
12. RELOCATION OF ALL EQUIPMENT TO BE COORDINATED WITH OWNER.
13. PROVIDE TEMPORARY SUPPORTS FOR PORTION OF DEMOLISHED WALLS TO REMAIN.
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:32 AMA1.00
185-01-00
8/15/16
DEMOLITION PLAN GENERAL
NOTES, KEYS, LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SPECIFIC DEMOLITION NOTES
01 REMOVE PORTION OF GYPSUM BOARD PARTITION AS INDICATED.
02 REMOVE PORTION OF TILE FACED GYPSUM BOARD PARTITION.
05 REMOVE LAYERS OF GYPSUM BOARD AND/OR PLASTER LATH, EXISTING PARTITION FRAMING TO REMAIN.
06 REMOVE COLUMN ENCLOSURE.
09 REMOVE TOILET PARTITION AND ALL ASSOCIATED HARDWARE/FITTINGS.
10 REMOVE DOOR, FRAME, HARDWARE AND ALL ASSOCIATED FITTINGS/LIGHTS.
14 REMOVE BORROWED LIGHT, FRAME AND ALL ASSOCIATED FITTINGS.
20 REMOVE FLOORING TO SUBFLOOR OR FLOORING SUITABLE SURFACE FOR INSTALLATION OF NEW FLOOR
(COORDINATE WITH FINISH PLAN).
30 REMOVE CEILING/SOFFITS AND ALL ASSOCIATED FRAMING/FIXTURES/DEVICES/EQUIPMENT (COORDINATE
WITH MEP/FP/STRUCTURAL).
31 REMOVE CEILING/SOFFITS AND ALL ASSOCIATED FRAMING/FIXTURES/DEVICES/EQUIPMENT FOR CEILING
SUPPORTED EXAM LIGHTS (COORDINATE WITH MEP/FP/STRUCTURAL).
41 REMOVE COUNTER, CABINETS, SHELVES AND ALL ASSOCIATED HARDWARE/FIXTURES/FITTINGS.
42 REMOVE WALL PROTECTION AND ALL ASSOCIATED HARDWARE.
50 REMOVE PLUMBING FIXTURE AND ALL ASSOCIATED FITTINGS (COORDINATE WITH PLUMBING DRAWINGS).
63 REMOVE LOCKERS OR CASEWORK WITH CONCRETE BASE AND REMOVE CONCRETE BASE AND ALL
ASSOCIATED HARDWARE/FITTINGS.
64 REMOVE WALL MOUNTED EQUIPMENT AND ALL ASSOCAITED HARDWARE/FITTINGS.
71 REMOVE PORTION OF STOREFRONT/CURTAIN WALL ASSEMBLY AS INDICATED.
90 REMOVE AND SALVAGE DOME LIGHTS TO BE STORED AND REINSTALLED PER OWNER'S DIRECTION.
91 REMOVE AND REINSTALL SOILED LINEN CHUTE DOOR.
GENERAL DEMOLITION NOTES
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
CRASH RAILCR-1
CG-1
ACCENT CRASH RAILCR-2
PRIVACY CURTAIN
CORNER GUARDS
BLUE ACCENT CORNER GUARD
CG-2
RIGID SHEET
WP-1
GRAB BAR
BLUE ACCENT RIGID SHEET
WP-2
TAN ACCENT CORNER GUARD
CG-3
HARDWOOD CRASH RAIL
CR-3
HYDRAULIC CEMENT UNDERLAYMENT
CHASE AREA
FIRE EXTINGUISHER / FIRE EXTINGUISHER CABINET
FEC
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION AT
E1 AND E3 PARTITIONS ONLY
SUSPENDED CEILING
WHERE SCHEDULED
METAL STUDS
5/8" GYPSUM BOARD
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLAB
( 6 5/8")BASEPLANCEILINGHEADE
E1
E2
E3
NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
SINGLE SIDED (3 5/8" STUD)
SINGLE SIDED (3 5/8" STUD)
SINGLE SIDED (2 1/2" STUD)
SINGLE SIDED (2 1/2" STUD)
4 1/4"
NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
A2.00
31
MULTIPLE LAYERS OF GYPSUM BOARD (WHERE INDICATED)
MULTIPLE LAYERS OF JOINT SEALER AND BACKING WHERE
MULTIPLE LAYERS OF GYPSUM BOARD ARE SHOWN
FLOOR RUNNER
3/8" TYPICALJOINT SEALER AND BACKING
-PROVIDE FIRE STOPPING AT FIRE RATED PARTITIONS
- PROVIDE SMOKE STOPPING AT SMOKE PARTITIONS
- PROVIDE ACOUSTICAL SEALANT AT ACOUSTICAL
PARTITIONS
GYPSUM BOARD
SCHEDULED BASE
3/8"PARTITION AS SCHEDULEDADJACENT MATERIALS
JOINT SEALER AND BACKING
5/8" GYPSUM BOARD
WOOD BLOCKING
VINYL ACRYLIC EXTRUSION
CONTINUOUS VINYL RETAINER
WASHER & ALLIGATOR
NOTE: CRASH RAIL TO BE MOUNTED
AT 2'-8"TO C.L. AFF
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
DEFLECTION ALLOWANCE
SUSPENDED CEILING
WHERE SCHEDULED
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLABBASEPLANCEILINGHEAD
F NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
1 1/2" FURRED WALL 7/8" RIGID FURRING CHANNEL
1 1/2"
5/8" GYPSUM BOARD
NO FIRE RESISTANCE RATING
NO ACOUSTICAL RATING
RIGID FURRING CHANNEL OR "Z" FURRING
MEMBER
RIGID FURRING CHANNEL OR "Z" FURRING
MEMBER
EXTEND GYPSUM BOARD TO UNDERSIDE OF STRUCTURE
IF NO CEILING SCHEDULED
A2.00
31
5" UNLESS OTHERWISE NOTED
ACOUSTICAL INSULATION INFILL ABOVE RUNNER WHERE
WALL RUNS PERPENDICULAR TO DIRECTION OF DECK
AT B PARTITION
JOINT SEALER AND BACKING
EACH SIDE
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION
SUSPENDED CEILING
WHERE SCHEDULED
METAL STUDS
5/8" GYPSUM BOARD-
AT 1 HOUR PARTITION USE
5/8" TYPE X GYPSUM BOARD
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLAB
(7 1/4")BASEPLANCEILINGHEADB
B1
B2
B3
NO FIRE RESISTANCE RATING
STC = 51, TEST #: RAL-TL-90-166
1 HOUR FIRE - UL# U465
STC = 51, TEST #: RAL-TL-90-166
NO FIRE RESISTANCE RATING
STC = 51, TEST #: RAL-TL-90-166
1 HOUR FIRE - UL# U465
STC = 51, TEST #: RAL-TL-90-166
4 7/8" (3 5/8" STUD)
4 7/8" (3 5/8" STUD)
7 1/4" (6" STUD)
7 1/4" (6" STUD)
4 7/8"
UNDERSIDE OF STRUCTURE
A2.00
31
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
EACH SIDE
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION
SUSPENDED CEILING
WHERE SCHEDULED
METAL STUDS
5/8" GYPSUM BOARD-
L 1/16" LEAD THICKNESS (MIN. HEIGHT 7'-0")
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLAB
(7 1/4")BASEPLANCEILINGHEADL NO FIRE RESISTANCE RATING
STC = 41
4 7/8" GWB W/ LEAD (3 5/8" STUD)
4 7/8"
A2.00
31
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
EACH SIDE
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION
SUSPENDED CEILING
WHERE SCHEDULED
METAL STUDS
5/8" GYPSUM BOARD-
AT 1 HOUR PARTITION USE
5/8" TYPE X GYPSUM BOARD
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLABBASEPLANCEILINGHEAD
A NO FIRE RESISTANCE RATING VIF
STC = 41 LIMITING HEIGHT 15'-7"
WIDTH VIF (EXISTING STUD)
VIF
TOP RUNNER
METAL STUDS
5/8" GYPSUM BOARD
SCHEDULED BASE
FLOOR RUNNER
TOP OF SLABBASEPLANHEAD
Y NO FIRE RESISTANCE RATING
NO ACOUSTIC RATING
4 7/8" (3 5/8" STUD)
4 7/8"
CONTINUOUS WOOD BLOCKING
3/8" x 3/8" CONTINUOUS REVEAL
EACH SIDE AND AT EXPOSED ENDS
HEIGHT ABOVE FLOOR
SEE FLOOR PLANS AND
INTERIOR ELEVATIONS
CASING BEAD
A2.00
31
3'-0"1 1/2"5/8" GYPSUM BOARD
WOOD BLOCKING
HARDWOOD CRASH RAIL
NOTE: CRASH RAIL TO BE MOUNTED
AT 2'-4" TO C.L. AFF7 1/4"1 1/2"
ACOUSTICAL INSULATION INFILL ABOVE RUNNER WHERE
WALL RUNS PERPENDICULAR TO DIRECTION OF DECK
AT B PARTITION
JOINT SEALER AND BACKING
EACH SIDE
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION (3" MINERAL WOOL BATT)
SUSPENDED CEILING
WHERE SCHEDULED
EXISTING METAL STUDS
5/8" GYPSUM BOARD-
AT 1 HOUR PARTITION USE
5/8" TYPE X GYPSUM BOARD
SCHEDULED BASE
EXISTING FLOOR RUNNER
EXISTING JOINT SEALER AND BACKING
EACH SIDE
EXISTING TOP OF SLABBASEPLANCEILINGHEAD
G MAINTAIN FIRE RESISTANCE RATING
MAINTAIN ACOUSTICAL RATING
5/8" GYPSUM BOARD
UNDERSIDE OF STRUCTURE
A2.00
31
EXISTING
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
EACH SIDE
PROVIDE CASING BEAD
WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
SOUND ATTENUATION INSULATION
SUSPENDED CEILING
WHERE SCHEDULED
METAL STUDS
5/8" GYPSUM BOARD-
AT 1 HOUR PARTITION USE
5/8" TYPE X GYPSUM BOARD
SCHEDULED BASE
FLOOR RUNNER
JOINT SEALER AND BACKING
EACH SIDE
TOP OF SLABBASEPLANCEILINGHEAD
M NO FIRE RESISTANCE RATING
STC=
5 1/2" (3 5/8" STUD)
5 1/2"
STEEL ANGLE
EXTENDED BASE FLASHING
SHEET METAL COUNTERFLASHING
BASE FLASHING
CANT
PROTECTION BOARD ASSEMBLY
EXISTING ROOF MEMBRANE
COVER BOARD
ATTACHMENT BOLTS
BASE PLATE
NEOPRENE PAD SET IN SEALANT
1'-0"1. ALL WORK SHALL BE PERFORMED PER APPLICABLE CODES, ORDINANCES AND PER REQUIREMENTS OF ALL
APPLICABLE REGULATORY AGENCIES AND AUTHORITIES HAVING JURISDICTION.
2. ALTERATIONS/RENOVATIONS ON THIS AND OTHER FLOORS NOT SPECIFICALLY CALLED OUT AS RENOVATION AREAS
ARE TO BE DONE AS NECESSARY TO COMPLETE WORK SHOWN ON THE CONTRACT DOCUMENTS. REFER TO
ENGINEER CONSULTANT AND VENDOR DRAWINGS TO IDENTIFY THE SCOPE OF WORK IN AREAS IDENTIFIED OUTSIDE
THE ARCHITECTURAL DOCUMENTS. THE G.C. SHALL BE RESPONSIBLE FOR THE REMOVAL AND RESTORATION OF
ALL EXISTING FINISHES DISTURBED BY THE WORK. WHERE TEMPORARY M.E.P. CONNECTIONS ARE REQUIRED, ALL
FINISHES SHALL BE RESTORED IMMEDIATELY TO MAINTAIN OPERATION OF THE FACILITY, EVEN IF THE WORK WILL
REQUIRE TO BE REMOVED AGAIN DURING THIS PROJECT.
3. ALL OPENINGS, IN EXISTING FLOORS AND WALLS ABOVE AND BELOW THE CEILING PLENUM, BOTH EXISTING AND AS
A RESULT OF DEMOLITION ACTIVITIES SHALL BE PATCHED TO COMPLETE AND FINISH EXISTING WALLS AND FLOORS
CONSISTENT WITH NEW WORK. ALL PATCHES SHALL BE MADE WITH MATERIALS CONSISTENT WITH THE WALL IN
WHICH THE PATCH WILL BE LOCATED.
4. THE G.C. SHALL COORDINATE AND SCHEDULE ALL WORK WITH THE CLIENT AND/OR CLIENTS AUTHORIZED
REPRESENTATIVE/PROJECT MANAGER. WORK SCHEDULED IN OCCUPIED AREAS SHALL BE UNDERTAKEN IN A
MANNER SO AS NOT TO DISTURB THE OPERATION OF THE FACILITY.
5. WHERE A NEW SERVICE PENETRATES AN EXISTING WALL WHICH EXTENDS TO THE UNDERSIDE OF THE STRUCTURE,
THE G.C. WILL BE RESPONSIBLE FOR PATCHING AND FIRE SAFING THE WALL AND FOR PROVIDING THE REQUIRED
FIRE RATING AND FINISH.
6. PROVIDE BLOCKING IN WALL THROUGHOUT AS INDICATED ON DRAWINGS FOR ALL WALL MOUNTED ITEMS,
INCLUDING ITEMS FURNISHED BY OWNER.
7. ITEMS IDENTIFIED AS NOT IN CONTRACT (NIC) ARE TO BE PURCHASED AND INSTALLED BY THE OWNER. THE G.C.
SHALL COORDINATE INSTALLATION OF ALL ITEMS NIC WITH THE OWNER.
8. PROVIDE ALL HEADERS, LINTELS AND SUPPORTS AS NECESSARY FOR ALL WALLS AND PARTS OF WALLS SHOWN
TO BE REMOVED. ALL NEW MEMBERS SHALL BE IN CONFORMANCE WITH THE MASSACHUSETTS STATE BUILDING
CODE, 8TH EDITION. THE GC IS RESPONSIBLE FOR IDENTIFYING ANY STRUCTURAL BEARING CONDITIONS THAT
BECOME APPARENT DURING DEMOLITION. ANY FOUND STRUCTURAL CONDITIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT PRIOR TO REMOVAL OF STRUCTURAL MEMBERS.
9. IT IS THE INTENT OF THIS DOCUMENT THAT ALL NEW WIRING, PIPING FIXTURES, FITTINGS AND DEVICES BE
RECESSED INTO EXISTING WALLS. THE CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING, PATCHING, REPAIRING,
ETC. AS REQUIRED TO RECESS ITEMS IDENTIFIED ABOVE.
10. WHERE WALL MOUNTED ITEMS HAVE BEEN REMOVED, PATCH AND REPAIR EXISTING WALL.
1. ALL WALL PARTITIONS TO BE TYPE "B" UNLESS OTHERWISE NOTED.
2. WHERE NEW WALL IS NOT DIMENSIONED LAYOUT TO ASSUME NEW WALL IS ALIGNED WITH ADJACENT WALL.
3. ALL PARTITIONS ARE TO EXTEND TO THE UNDERSIDE OF THE EXISTING DECK AND TO BE SEALED ON BOTH SIDES.
4. ALL PENETRATIONS IN SMOKE AND FIRE RATED PARTITIONS ABOVE CEILING TO BE FIRE STOPPED.
5. ALL PENETRATIONS IN NON-RATED PARTITIONS ABOVE CEILING TO BE SEALED.
A2.00
31
3 3/4"
(5 1/4")
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING EACH LAYER
PROVIDE CASING BEAD WHERE EXPOSED TO VIEW
CEILING RUNNER
DEFLECTION ALLOWANCE
UL 3/8" - 1/2"
SUSPENDED CEILING
WHERE SCHEDULED
SCHEDULED BASE
CAVITY SHAFT WALL RUNNER
JOINT SEALER AND BACKING EACH LAYER
TOP OF SLAB
CAVITY SHAFT WALL RUNNER
BASE PLAN CEILING HEAD
SOUND ATTENUATION
INSULATION AT H1 AND H3
CAVITY SHAFT WALL STUDS
5/8" TYPE X GYPSUM BOARD
CORE BOARD
H
H1
H2
H3
2 HOUR FIRE - UL#U438
STC = 46
2 HOUR FIRE - UL# U438
STC = 49
2 HOUR FIRE - UL#U438
STC = 47
2 HOUR FIRE - UL# U438
STC = 50
SHAFT WALL (2 1/2" STUD)
SHAFT WALL (2 1/2" STUD)
SHAFT WALL (4" STUD)
SHAFT WALL (4" STUD)
SCHEDULED FLOORING
4' - 0" WALL PROTECTION
WALL BASE SEALANT
4"RESILIENT WALL BASE
WALL PROTECTION CAP
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:47:34 AMA2.00
185-01-00
8/15/16
FLOOR PLANS GENERAL
NOTES, KEYS, LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
ACCESSORY KEY
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 PARTITION TYPE E, E1, E2 & E3
SCALE:
SECTION DETAIL
3" = 1'-0"
31 TYPICAL PARTITION AT BASE DETAIL
SCALE:
SECTION DETAIL
3" = 1'-0"
22 TYPICAL GYPSUM BOARD PARTITION / ADJACENT MATERIAL
SCALE:
SECTION DETAIL
3" = 1'-0"
24 CRASH RAIL
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
13 PARTITION TYPE F
SCALE:
PLAN DETAIL
3/4" = 1'-0"
23 DOOR FRAME LOCATION
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 PARTITION TYPE B, B1, B2, AND B3
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
15 PARTITION TYPE L
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 PARTITION TYPE A
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
20 PARTITION TYPE Y
SCALE:
SECTION DETAIL
3" = 1'-0"
25 HARDWOOD CRASH RAIL
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
14 PARTITION TYPE G
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
21 PARTITION TYPE M
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
32 EQUIPMENT SUPPORT CURB DETAIL
GENERAL NOTES
PARTITION NOTES
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
33 PARTITION TYPE H, H1, H2, H3
SCALE:
SECTION DETAIL
3" = 1'-0"
34 TYPICAL RESILIENT BASE TO WALL PROTECTION TRANSITION
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
FECFDVCMGZV
7 8
910
1112131415
16
17
18
A5.10
8A
A5.10
11A
A5.10
A5.10
2A
A5.10
1A
A5.12
27A A5.12
26A
A5.12
29A
A5.11
25A
A5.1124B
A5.105D
A5.11
20A
A5.11
16A
A5.11
18A
A5.10
4A
A5.11
22A
8B
8C
8D
1B
1C
1D
2B
2C
2D
22B
22C
22D
4B
4C
4D
27B
27C
27D
26B
26C
26D
16B
16C
16D
29B
29C
29D
11B
11C
11D
20B
20C
20D
A5.11
17A
17B
17C
A5.10
13C
18B
18C
18D
19 20 21 22
23
25
26
27
28
5A
5B
5C
24C
24D
25B
25C
25D
A5.1228D 28B
28C 13B13D
A5.10
12A
12B
12C
12D
A5.10
14A
14B
14C
14D
A5.107D
7A
7B
7C
A5.10
15A
15C
A5.12
32C
A5.12
31C
A5.12
36A
A5.12
35A
A5.1234D
A5.12
33C
31B
31A
31D
32A
32B32D
A5.11
19A
19B
19C
19D
36B
36C
36D
33D
33A
34B
34C
35B
35C
35D
A5.10 3B
13A
3A
3C
3D28A
34A
33B
9B
9C
9D
9A
A5.1122H
A5.10
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
LARGE
MAMMOGRAPHY
G-120
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
ADJUSTABLE SHELVING
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
EXAM 2
G-107
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-1107'-4 3/4"7'-6 1/2"5'-4"7'-8"7'-5 1/2"
12'-0"
10'-5 1/4"22'-1 3/4"14'-0 3/4"12'-2 1/2"6'-6"ALIGN6'-0"9'-2"2'-3"9'-7"
ALIGNALIGN
CG-1
CG-1
CG-1
CG-1
CG-1 CG-1
CG-1
CG-1
E1
E1
E1 E1
E1
E1
E1
E1
E1
G
E1
E1
E1
E1
E1
E1
E1
E1
E1
F
E1
E1
E1
E1
E1
E1
1
E1
E1
WP-1
WP-1
WP-1
WP-1
CG-1
CG-2 CG-2
WP-1
WP-2
WP-1
WP-1 WP-1
WP-1
WP-1 WP-2
WP-1
WP-1
WP-1
WP-1
CG-1
WP-1
CG-1
MAMMOGRAPHY
G-122
WP-1
G
G
E1
E1
E1
E1
E1
ALIGN
CG-1CG-1
CG-1
NURSE STATION
G-126
CG-19'-5"11'-3 3/4"6'-4"
12'-1"
12'-11 3/4"
CLEAR
3'-3"
STAFF BREAK
ROOM
G-123
12'-3 1/2"6'-0"5'-7"
E1
E1
E1
E1
E1 E1
E1
E1
H
H
E1
CG-1 CG-1
ULTRASOUND
G-121
E1E1
WP-1
WP-1
WP-1
F
E1
E1
E1
E1
STRETCHER
WAITING
G-127
E1
E1
E1
E1
E1
E1
E1 E1
E1
E1
E1
E1
E1
E1
OFFICE
G-108
EXAM 1
G-106
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
INTERVIEW 1
G-118
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
SUB WAITING
G-119
PATIENT TOILET
G-109
G GALIGN
G
G
G
GG
E1
E1
E1
E1 H
H
H
E1 E1
G
F
F
F
F
F
F
EQEQEQEQ5'-9"2'-9 1/4"6'-8 3/4"
A5.10
5A
.
5B .5C
.
5D.A5.11
18A
.
18B .18C
.
18D.24A
CG-1
WP-2
WP-1
WP-1
WP-1
WP-1
WP-2 WP-1
WP-1
WP-1
CG-1
2
CG-3
CG-3
CG-3
WP-1
WP-1
WP-2
WP-1
WP-1
WP-1
WP-1 4'-2"EQ EQ
WP-2CLEAR5'-0"CLEAR5'-0"5'-3"WP-1
WP-1
WP-1
WP-1
WP-1
WP-1
WP-1
CG-1 7'-11 1/2" +/-EQEQ
19'-5"E1
4'-11"
7'-1"
1'-0"
5'-6"1'-6"E1
E1
FG
9'-11"5'-2 1/4" +/-5'-11"E1
LIAISON
G-114C
E1
A5.1010D
E1
CG-1
A9.30
22
A9.40
31 G-114-AG-119A-AG-119B-B
G-113A
G-111A-A
G-112-A
G-111D-AG-111C-AG-111B-A5'-9 1/4" +/-
CL
G-110-B
7'-1"
G-109-A
E1
G-108-ACL CL
EQ.G-106-AG-107-AFRAME TIGHT TO COLUMN
G-105-A
G-115B-A
CL
G
E1
E1 G-116-AG-117-AG-118-AG-121-AG-122-AG-124-AG-123-A
G-125-AG-127-AG-120-AG-126A-AG-130B-AG-130-AG-130A-AG-119-BG-119B-AG-119-AG-115A-B
H
H
E1
E1E1
E1
E1
E1
G-110-A
1E
1G
WP-1
E1
E1
E1
1'-9"
ALIGN
ALIGN
WP-1
1'-3"
WP-1 WP-1
E1
CG-2
WP-1
WP-2
WP-1
WP-1
WP-1
WP-1
WP-2
WP-1
CG-1
CG-1
CG-1
A9.20
32
CG-1
A9.60
10
L
A9.20
34
FEATURE WALL
FEATURE WALL
6'-8"CL
CG-1
CG-1
CG-1
CG-1
WP-1WP-1
WP-2
WP-2
WP-1
CG-1 CG-1
CG-1 CG-1
CR-2 CR-2
CG-1
CR-3
CR-3
CR-3
CR-1CR-1CR-1
CR-2
CR-1 CR-1
CR-1
CR-1
CR-3
A5.1230C A5.11
23A
A5.10 6B
A5.1121D
30A
30B
30D
23D
23C
6C
6D
21A
21B
A
EQEQ
CORRIDOR
G-115C
CORRIDOR
G-115B
CORRIDOR
G-111
CORRIDOR
G-115A
CORRIDOR
G-128
CORRIDOR
G-119B
A9.20
24
A9.20
24 ALIGNE2EQ
F
F
F
CR-1
CR-1CR-1
1' - 6"
CLEAR
3' - 0"CLEAR4'-0"3'-5 1/2" +/-
TECH WORKSTATION
A9.6012.A9.60
11
.
M
M
M
G
G
G
G G
A5.10 10B .7'-11"7'-1"
6' - 6"9'-7"SUB WAITING
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
CG-1 CG-1
Y
Y
9'-0"A5.12 36F
GG
E2
E2
E2
7'-8"7'-3"13'-2"
7'-7"3'-5"13'-0"18'-4"7'-0"10'-6"
7'-4 1/2"7'-4 1/4"20'-9 3/4"17'-11 1/2"12'-3 3/4"
20'-7"
7'-5"5'-4"7'-4"10'-6"CR-2 CR-2
G
PROVIDE 4'-0" HIGH, 3/4" FIRE RATED PLYWOOD WIDTH
OF CLOSET 24" AFF. PAINTED FIELD COLOR, TYP.CLEAR3'-6"CLEAR
7'-3"
FEC
FEC
H
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:36 AMA2.10
185-01-00
8/15/16
NEW WORK PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
MGZV
7 8
910
1112131415
16
18 19 20 21 22
23
25
26
27
28
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
LARGE
MAMMOGRAPHY
G-120
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
LIAISON
G-114C
STAFF TOILET
G-130A
EXAM 2
G-107
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STAFF BREAK
ROOM
G-123
STRETCHER
WAITING
G-127
NURSE STATION
G-126
MAMMOGRAPHY
G-122
ULTRASOUND
G-121
INTERVIEW 1
G-118
NAVIGATOR'S
OFFICE
G-116
STEREOTACTIC
G-105
SUB WAITING
G-119
PATIENT TOILET
G-109
OFFICE
G-108
EXAM 1
G-106
2'-5"
1'-11"3'-0"2'-6"3'-2"4'-3"5'-3"5'-7"5'-7"
CL CL
4'-9"1'-5"1'-7"CL
1'-9"
6'-0"
CL
CL
2'-8"
CL
3'-7"2'-3"4'-5"2'-6"2'-4"1'-11"CL
CL
4'-6"1'-6"3'-6"1'-2"4'-5"1'-7"CL
CL3'-3"1'-4"2'-4"CL
CL
10"
EQ EQ
1'-8"
EQ EQ
2'-0"2'-11"CL
EQEQCL
2'-0"2'-0"3'-5"2'-0"2'-0"
CL CL
CL
CL
CL
CL CL
CL
CL
CL
CL6'-7"1'-3"5'-3"3'-5"3'-2"5'-11"5'-10"2'-1"2'-0"5'-11"5'-5"5'-2"4'-2"5'-8"7'-1"2'-5"CL
2'-9"
CL
1'-6"4"EQEQEQ4'-9"
4'-3"4'-6"
1'-1"4'-3"4'-0"2'-0"CL
CL
SUB WAITING
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
1'-7"
3'-0"1'-6"8'-2"3'-6"1'-9"
LOCATED ABOVE
CEILING
LOCATED ABOVE
CEILING
1'-7"4'-8"1'-6"1'-6"1'-6"1'-9"1'-9"
CL
2'-11"3'-6 1/2"7"1'-2"
CL
CL
1'-0"1'-4"1'-0"CL
7'-0"8"CR
PO CR
PO
PO
CR
PO
NC NC
NC
NC
NC
NC
NC
NC
NCNC
NC
NC
NC
NC
NC
NC NC NC
1' - 6"1' - 6"1'-7"1'-6"1' - 0"1' - 0"2'-10"1'-0"
1'-0"3' - 11"3' - 8"1' - 7"CL
CL
CL3' - 8"3' - 11"2' - 11"2'-6 3/4"10'-3"1'-1"
2'-7"
1'-0"
11"2'-5"1'-6"8"1'-6"EQEQEQEQ3'-4"
6"6"3'-3"1'-10"1'-0"3'-11"2'-1"2'-4"3'-6"3'-4"2'-1"3'-4"9'-4"5'-3"9"7'-4"3'-5"
3'-4"2'-7 1/4"CL 4'-3"5'-4"1'-8"1'-7"1'-4"6"1'-3"2'-9"
3"
1'-6"
1'-8"1'-6"
1'-10"
4'-1"2'-3"1'-0"1'-0"EQEQ
CL
8"2'-3"1'-7"3'-0"
EQEQ4'-10"5'-0"CL
CL
5' - 0"NC
NC
1'-3"5'-9"NC
1' - 0"
NC
1' - 0"
NC
1' - 2"
ELECTRICAL
CLOSET
G-125
1'-0"1'-6"9'-5"10"1'-11"6'-10"2'-1"3'-2"7'-0"
1'-2"
DUPLEX OUTLET
DOUBLE DUPLEX OUTLET
T/D OUTLET
PO POWER OPERATOR
WALL PHONEW
NURSE CALLNC
NOTE: REFER TO AND COORDINATE WITH DETAILS ON
SHEET A5.00 FOR TYPICAL LIGHT SWITCH,
THERMOSTAT, OULET, AND NURSE CALL LOCATIONS.
LOCATIONS ARE TYPICAL UNLESS OTHERWISE NOTED.
LIGHT SWITCH
AUDIO VISUAL ALARMAVAF
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:37 AMA2.11
185-01-00
8/15/16
NEW PLAN POWER
COORDINATION
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
POWER COORDINATION NOTES
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
5
6 7 8
910
1112131415
16
17
18 19 20 21 22
23
24
25
26
27
28
ALTERNATE 1
32
A2.00
WEST BUILDING ROOF
SCOPE OF WORK BELOW
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:39 AMA2.12
185-01-00
8/15/16
ROOF PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
MGZV
AP ACRYLIC PANEL
CT CERAMIC TILE
GT GLASS TILE
PC PRIVACY CURTAIN
PL PLASTIC LAMINATE
PT PAINT
RB RESILIENT BASE
RSF RESILIENT SHEET FLOORING
SS SOLID SURFACE
TS TACKABLE SURFACE
HW HARDWOOD
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
LARGE
MAMMOGRAPHY
G-120
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
LIAISON
G-114C
STAFF TOILET
G-130A
EXAM 2
G-107
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
PT-1
PT-2
PT-3
RSF-1
RB
PL-1
SS
PT-1
PT-2
PT-3
RSF-1
RB
PL-1
SS
PC
SS
PT-1
PT-2
RSF-1
RB
PL-1
SS
PC
PL-1
PL-1
PC
PC
SS
PT-1
PT-2
PT-3
RSF-1
RB
PL-1
SS
PT-1
PT-2
PT-3
RSF-1
RB
PL-1
SS
PT-1
PT-2
PT-3
RSF-1
RB
SSPL-1
SS
PT-1
PT-2
PT-3
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PL-1
SS
PL-1
SS
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
PT-3
RSF-1
RB
PT-1
PT-2
PT-3
RSF-1
RB
PT-1
PT-2
PT-3
RSF-1
RB
PT-1
PT-2
PT-3
RSF-1
RB
PL-1
SS
PT-1
PT-2
RSF-1
RB
PL-1
SS
PL-1
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB PL-1
SS
PT-3
PL-1
PL-1
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-3
PT-1
PT-2
CT
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
CT
PT-1
PT-2
CT
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PT-1
PT-2
RSF-1
RB
PL-1
HW
PT-1
PT-2
RSF-1
RB
PL-1
PT-1
PT-2
RSF-1
RB
PL-1
PT-1
PT-2
CT
RSF-2
SS
PL-1 PL-1
STAFF BREAK
ROOM
G-123
MAMMOGRAPHY
G-122
ULTRASOUND
G-121
INTERVIEW 1
G-118
NAVIGATOR'S
OFFICE
G-116
STEREOTACTIC
G-105
EXAM 1
G-106
OFFICE
G-108
PATIENT TOILET
G-109
SUB WAITING
G-119
NURSE STATION
G-126
STRETCHER
WAITING
G-127
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
RSF-2
SS
RSF-2
RSF-2
SS
PT-2
PT-3
SS
PT-1
PT-2
RSF-1
RB
PT-2
SS
PT-1
PT-2
RSF-1
RB
SS
SS
SS
PT-3
PT-4
PT-4
PL-2
PL-2
PL-2
PL-2
HW
PL-1
PL-2
PL-1
PL-2 PL-2
PL-2
PL-2
PL-1
PL-2PL-2
PL-2
PL-2
GT GT
GT
GT
GT GT
GT
AP
TS
GT
PL-1
PL-1
SUB WAITING
PATIENT TOILET
G-119A
CORRIDOR
G-119B
MEN'S CHANGING &
WAITING
G-114
CORRIDOR
G-111
CORRIDOR
G-115A
CORRIDOR
G-115C
CORRIDOR
G-115DCORRIDOR
G-128
ELECTRICAL
CLOSET
G-125
RSF-1
RB
ACCENT WALL & SOFFIT
RSF-1
RB
PATCH EXISTING FLOORING
MATCH EXISTING PATTERN
LVT-1
LVT-2
HW
HW
HW
HW
HW
1. ALL WALLS AND SOFFITS TO BE PAINTED FIELD COLOR , UNLESS OTHERWISE NOTED.
2. ALL DOOR AND WINDOW FRAMES TO BE PAINTED TRIM COLOR.
3. PROVIDE MARBLE THRESHOLDS AT ALL TOILET LOCATIONS.
4. PROVIDE STAINLESS STEEL EDGE PROTECTOR TRIM WITH EASED EDGES AT TOP EDGE OF CERAMIC WALL TILE.
5. PROVIDE TRANSITION STRIPS AT ALL CHANGE IN FLOORING MATERIAL INTERSECTIONS.
6. WHERE CERAMIC TILE WALL BASE MEETS CERAMIC TILE FLOOR, USE SEALANT IN LIEU OF GROUT AT
INTERSECTION.
7. WALL BASE TO BE STRAIGHT BASE AT CARPET, COVE BASE AT TILE.
8. SOFFITS AT ACCENT PAINT WALLS TO BE PAINTED ACCENT COLOR.
9. ALL FLOORING TO CONTINUE UNDER MILLWORK/CASEWORK UNLESS OTHERWISE NOTED.
SCHEDULED RESILIENT SHEET
FLOORING
WALL TILE
TILE TRIM
TILE TRIM
INTEGRAL BASE CAP
4"GRAIN DIRECTION
ACCENT PAINT
RESILIENT SHEET FLOORING SEAM
LVT-2
LVT-1
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:47:40 AMA4.00
185-01-00
8/15/16
FINISH PLAN GENERAL
NOTES, KEYS, LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
ABBREVIATIONS - FINISHES
FINISH SCHEDULE
FINISH MANUFACTURER STYLE/NUMBER COLOR NOTES
AP 3-FORM CHROMA DENIM B31 + WHITE OUT W01
CT AMERICAN OLEAN INFUSION PORCELAIN TAUPE WENGE TOILET ROOM WET WALL, GROUT TO BE LATTE 40
GT CROSSVILLE EBB & FLOW SAND AND SURFACE BACKSPLASH, GROUT TO BE SAUTERNE 18
HW LIGHT MAPLE SCHEDULED CRASH RAIL, LIASON DESK, CHANGING ROOM BENCHES AND WAITING ROOM DETAILS
LVT-1 ARMSTRONG ARBOR ART EXOTIC CHERRY CHESTNUT EXISTING FLOORING
LVT-2 ARMSRONG EARTH CUTS HAVEN STONE GRAY PEARL EXISTING FLOORING
PC ARCHITEX INTERNATIONAL RX 6008 PULA PRIVACY CURTAIN
PL-1 WILSONART 4942-38 CRISP LINEN MILLWORK
PL-2 WILSONART 4944-38 CASUAL LINEN MILLWORK BASE CABINETS
PT-1 BENJAMIN MOORE WOOD ASH 1065 FIELD PAINT
PT-2 BENJAMIN MOORE BLOND WOOD 1067 TRIM PAINT & ACCENT PAINT
PT-3 BENJAMIN MOORE NORTHERN AIR 1676 BLUE ACCENT PAINT
PT-4 BENJAMIN MOORE MINERAL PROFILE PANELING FEATURE WALL WHITE PAINT
RB JOHNSONITE 49 BEIGE FIELD FLOORING BASE
RSF-1 FORBO MARMOLEUM STRIATO WHITE WASH 5230 NET FIT SEAMS WITH RUBBER BASE, FIELD FLOORING
RSF-2 FORBO MARMOLEUM STRIATO WHITE WASH 5230 HEAT WELDED SEAMS WITH INTEGRAL BASE, TOILET ROOMS
SS CORIAN BISQUE MILLWORK
TS FORBO BULLETIN BOARD 2185 - BLUE TACKABLE SURFACE
SCALE: 1/4" = 1'-0"1 FINISH PLAN
FINISH NOTES
SCALE:
SECTION DETAIL
3" = 1'-0"
10 RESILIENT SHEET FLOORING TO WALL TILE TRANSITION
FINISH FLOOR PATTERN KEY
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
MGZV
7 8
910
1112131415
16
18 19 20 21 22
23
25
26
27
28
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
LARGE
MAMMOGRAPHY
G-120
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
LIAISON
G-114C
STAFF TOILET
G-130A
EXAM 2
G-107
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
STAFF BREAK
ROOM
G-123
MAMMOGRAPHY
G-122
ULTRASOUND
G-121
INTERVIEW 1
G-118
NAVIGATOR'S
OFFICE
G-116
STEREOTACTIC
G-105
EXAM 1
G-106
OFFICE
G-108
PATIENT TOILET
G-109
SUB WAITING
G-119
NURSE STATION
G-126
STRETCHER
WAITING
G-127
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
GRAIN DIRECTION
6'-7"GRAIN DIRECTION GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION 6'-7"6'-7"GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTION
GRAIN DIRECTIONGRAIN DIRECTION6'-7"6'-7"6'-7"6'-7"6'-7"6'-7"6'-7"GRAIN DIRECTION
GRAIN DIRECTION
ELECTRICAL
CLOSET
G-125
CORRIDOR
G-115ACORRIDOR
G-128
CORRIDOR
G-115D
CORRIDOR
G-115C
CORRIDOR
G-115B
MEN'S CHANGING &
WAITING
G-114
SUB WAITING
PATIENT TOILET
G-119A
CORRIDOR
G-119B
STARTING POINT FOR SEAMING
CORRIDOR
G-115B6'-7"6'-7"PATCH EXISTING FLOORING
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:41 AMA4.10
185-01-00
8/15/16
SEAMING DIAGRAM
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
STANDARD CASEWORK TAG NUMBER
DESIGNATIONS REFER TO ARCHITECTURAL
WOODWORK STANDARDS (EDITION 1),
CABINET DESIGN SERIES, APPENDIX A,
PAGE 351 AND FOLLOWING. ("AWS CDS")
BASE CABINETS WITH
COUNTERTOP:
HEIGHT IS NOMINAL TO TOP OF
COUNTERTOP
WALL AND TALL CABINETS
HEIGHT IS ACTUAL
H
H
999= CASEWORK TAG
NUMBER OR LETTER
DESIGNATION FOUND IN
"AWS CDS"
M= INDICATES A
MODIFICATION TO "AWS
CDS" CASEWORK AS
DESCRIBED IN COMMENTS,
NOTES OR DETAILS
W= WIDTH
H=HEIGHT (SEE NOTES)
D=DEPTH (INCHES)
999M
W
H
D
COMMENT/
MODIFICATION
D
D
W
W
CASEWORK TAG DESIGNATIONS MAY ALSO
REFER TO ISGENUITY COMPONENTS AND
CUSTOM CASEWORK ELEMENTS FOR
CABINET TYPES THAT "AWS CDS" DOES NOT
COVER. THESE TAGS WILL CONTAIN
LETTERS. REFER TO CASEWORK MENU ON
THIS PAGE FOR MORE INFORMATION ON
THESE CUSTOM CABINETS.
"AWS CDS" NOTES:
THE CASEWORK DESIGN SYSTEM IS
SUBDIVIDED AS FOLLOWS:
100 SERIES BASE CABINETS W/O DRAWERS
200 SERIES BASE CABINETS WITH DRAWERS
300 SERIES WALL-HUNG CABINETS
400 SERIES TALL STORAGE CABINETS
500 SERIES TALL WARDROBE CABINETS
600 SERIES LIBRARY CABINETS
700 SERIES MOVEABLE CABINETS
FOR ISGENUITY CUSTOM CABINETS, FIRST
DIGIT OF TAG WILL FOLLOW THESE
CATEGORIES.
9C9
W
H
D
9C9= CASEWORK TAG
DESIGNATION FOR
CUSTOM CASEWORK NOT
FOUND IN "AWS CDS"
W= WIDTH
H=HEIGHT (SEE NOTES)
D=DEPTH (INCHES)
AS
W D
CT
W
H
D
REFER TO AWS CDS LEGEND GENERAL
NOTES AS WELL AS STANDARDS
PROMULGATED IN THE ENTIRE BOOK
FOR DETAILS OF CONSTRUCTION.
WALL AND TALL CABINETS
HEIGHT IS ACTUAL
H
D
W
999M
W
H
D
WITH FASCIA
THE FOLLOWING NOTES SHALL BE THE DEFAULT, EXCEPT AS NOTED OTHERWISE ON THE DRAWINGS.
1. PROVIDE LOCKS AT ALL DRAWERS AND CABINETS AS INDICATED ON THE ELEVATIONS
2. COUNTERTOPS AT ALL OUTSIDE CORNERS SHALL HAVE A 2” RADIUS CORNER IN PLAN VIEW.
3. AT TOPS AND EXPOSED SIDES OF ALL WOOD WALL, TALL, AND FULL HEIGHT CABINETS PROVIDE A
CONTINUOUS FASCIA PANEL ABOVE BANK OF CABINETS, FINISHED TO MATCH FACING OF ADJACENT
CABINETS. WHERE ACT CEILING IS ABOVE, CEILING TILES SHALL BE SCRIBED AROUND THE FASCIA PANEL
WHICH SHALL EXTEND AT LEAST 2” ABOVE THE CEILING . WHERE GWB SOFFIT IS ABOVE, FASCIA PANEL
SHALL BE 2” HIGH AND SCRIBED TO SOFFIT. GC TO COORDINATE SIZE AND LOCATION OF GWB SOFFIT WITH
FINAL CASEWORK SHOP DRAWINGS.
4. PROVIDE WIRE PULLS ON DRAWERS AND CABINETS TYPICALLY. OMIT THEM AT FIXED PANEL FRONTS.
WHERE SINK CABINETS HAVE A FIXED PANEL FRONT IN LIEU OF SWINGING DOORS, PROVIDE SCREWS AT
EACH CORNER OF PANEL.
5. ATTACH BACKER BOARD SCREWS WITH 1” DIAMETER STAINLESS STEEL ESCUTCHEONS.
6. UNDERNEATH WALL CABINETS, PROVIDE APRONS AT FRONT, AND POPLAR BLOCKING AT WALL.
7. PROVIDE GROMMETS AND COORDINATE LOCATIONS IN THE FIELD WITH OWNER.
8. ALIGN DRAWER / CABINET HEIGHTS ACROSS A TYPICAL ELEVATION WHETHER OR NOT COORDINATED AS
SUCH ON THE INTERIOR ELEVATION. LOCATE LOCKS IN A CONSISTENT AND ALIGNED MANNER ON CABINETS
AND DRAWERS.
9. TYPICAL DIMENSIONS: COUNTERTOPS 1-1/2” THICK, TOE KICK HEIGHT 4”, TOE KICK DEPTH 3”.
10. COUNTERTOP SUPPORT BRACKETS SHALL BE PROVIDED AT MINIMUM EVERY 36" OF UNSUPPORTED SPAN.
ALL SUPPORT BRACKETS TO BE SURFACE MOUNTED UNLESS OTHERWISE NOTED.
11. PROVIDE WALL BASE AT TOE KICK LOCATIONS AT EXPOSED SIDES AND FRONTS OF CASEWORK.
12. PROVIDE ADJUSTABLE FEET AT BASE OF ALL BASE AND TALL CABINETS.
13. PROVIDE 3/4 INCH THICK PLYWOOD SCRIBE BEHIND WALL BASE AT TOE KICK.
14. PROVIDE WOOD BLOCKING IN WALLS BEHIND ALL CASEWORK.
15. PRIOR TO INSTALLATION, GC TO ENSURE THAT FLOOR LEVEL TOLERANCE IN A GIVEN DESK OR RUN OF
CASEWORK SHALL NOT EXCEED 1/32 INCH IN 8 FEET.
16. HOLES FOR ADJUSTABLE SHELF CLIPS INSIDE CABINETS SHALL BE 1/4 INCH IN DIAMETER AND 2” OC
INTERVALS.
17. PROVIDE SECURITY PANEL ABOVE FILE DRAWERS.
18. ADJUSTABLE SHELVES SHALL HAVE LOCATOR CLIPS ATTACHED TO UNDERSIDE OF SHELVES.
19. SHELVING STANDARDS SHALL BE PROVIDED, TO BE SPACED ALONG SHELF SPAN AT INTERVALS OF 36" OR
LESS. PROVIDE 48> LONG SHELVING STANDARDS AND CUT TO SUIT LOCATIONS. STANDARDS NEAR ENDS
OF THE SHELF SHALL BE LOCATED 6" AWAY FROM END OF SHELF, AND BE SPACED EQUALLY AT INTERIM
LOCATIONS.
20. PROVIDE BOOKENDS AT ALL SIDES OF ALL ADJUSTABLE SHELVES EXCEPT AT LOCATIONS WHERE END
SHELF IS WITHIN 1" OF AN ADJACENT WALL OR CASEWORK SURFACE.
21. PROVIDE BACKSPLASHES AND SIDESPLASHES TO MATCH COUNTERTOP SURFACE. PROVIDE INTEGRAL
BACKSPLASHES AT SOLID SURFACE COUNTERTOPS.
TYP. VOICE / DATA
OUTLETS FIRE EXTINGUISHER/
FIRE EXTINGUISHER
CABINET
AREA ALARM PANEL /
ZONE VALVE BOX
CL AREA ALARM PANEL
ZONE VALVE BOX
3' - 6"CL
CL
2' - 6"4"3' - 0"4"3' - 6"4"1' - 6"3' - 2"COUNTER - DESK
(WITH BACKSPLASH)3' - 8"COUNTER - STANDING
(WITH BACKSPLASH)4' - 2"CL
CL
CL
CL
COUNTER - STANDING (HIGH)
(WITH BACKSPLASH)5' - 0"4' - 0"1' - 6"ELECTRICAL
OUTLET
ELECTRICAL OUTLET ELECTRICAL OUTLET
SCHEDULED WALL
BASESEE ELEVATIONCG / CGE
2"
BUMPER RAIL / CHAIR RAIL
(VARIOUS TYPES, REFER TO INT.
ELEVATIONS AND DETAILS FOR
MOUNTING HEIGHT)
WALL PROTECTION - CORNER GUARDS 5' - 6"CL
HOOK STRIP 6' - 8"CL
CLOCK
2' - 0"CL
TOILET TISSUE
DISPENSER
MAX.
1' - 0"
MIN.
3' - 6"
3' - 0"
GRAB BAR
4' - 0"PULL-CORD
STATION
ACCESSIBLE TOILET AND ACCESSORIES
CL
1' - 6"ACCESSIBLE LAVATORY
MIRROR
CL
DIAPER CHANGING STATION2' - 10"CL
NURSE CALL DUTY
STATION
7' - 2"3' - 6"CL
COMBINATION TOWEL DISPENSER /
WASTE RECEPTACLE 3' - 6"SEAT COVER DISPENSER
DOOR OPERATOR
PUSH PAD
CL
4' - 0"ACCESSIBLE GRAB BAR (BEHIND TOILET)
CL
1' - 6"
3' - 6"
GRAB BAR
CL
3' - 0"CL
CL
ROBE HOOK5' - 6"ADA
ROBE HOOK
CL
4' - 0"4' - 0"VARIES
VARIOUS LENGTHS
4' - 0"WALL PROTECTION - DOORS
6"
LIGHT FIXTURE
7' - 0"CL
4' - 8"THERMOSTAT
WALL PHONE
LIGHT SWITCH PLATE7' - 8"NURSE CALL LIGHT
AUDIO / VISUAL
ALARM 6' - 8"4' - 0"FIRE ALARM PULL
STATION
CLFAPSCL
4' - 0"LS
TYP. LIGHT SWITCH
CL
4' - 0"SLC
TYP. LIGHTING
CONTROL SENSOR 4' - 6"TELEPHONE OUTLET THERMOSTAT5' - 0"TO
TST
DSCS
NURSE CALL
STATION
SB
NURSE CALL STATUS
BUTTON 4' - 0"4' - 0"CLCL
AP
4' - 0"ANNUNCIATION
PANEL
EXIT SIGN
SUO
PULL CORD
STATION4' - 0"CL
1' - 6"TYP. ELECTRICAL
OUTLETS
CL
1' - 6"1' - 6"CL
CARD
ACCESS
CL
4' - 0"OF TP ROLL
3' - 0"CL
TOWEL DISPENSER
CL
3' - 6"1' - 0"4' - 6"CL
GENERAL NOTE: HEIGHTS INDICATED ARE FOR GENERAL CONDITIONS, UNLESS OTHERWISE NOTED. REFER TO INTERIOR ELEVATIONS FOR SPECIFIC MOUNTING HEIGHTS.2' - 8" C.L.4'-4" MINSHARPS CONTAINER4'-6" MAX2' - 10"3' - 4"6"6'-8" MIN8"NURSE CALL
CL
HAND SANITIZER
8"
MIRROR1'-3"L1
KEYING GROUP
LOCK REQUIRED
BLOCKING, TYP.
3/4" PLYWOOD WITH PLAM
2' - 6"2'-3"3/4" PLYWOOD WITH PLAM DOOR
3/4" PLYWOOD WITH PLAM
CLEAR
1'-2"2"UNDERCOUNTER LIGHT
2"
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:47:42 AMA5.00
185-01-00
8/15/16
INTERIOR ELEVATIONS
GENERAL NOTES, KEYS,
LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
CASEWORK KEY GENERAL CASEWORK NOTES
TYPICAL MOUNTING HEIGHTS
MILLWORK KEYING SCHEDULE
ROOM NUMBER ROOM NAME MILLWORK KEYING GROUP
G-105 STEREOTACTIC GROUP 1
G-106 EXAM 1 GROUP 1
G-107 EXAM 2 GROUP 1
G-113 BONE DENSITY GROUP 1
G-120 LARGE MAMMOGRAPHY GROUP 1
G-121 ULTRASOUND GROUP 1
G-122 MAMMOGRAPHY GROUP 1
G-126 NURSE STATION GROUP 2
G-126A CLEAN WORK AREA GROUP 2
G-127 STRETCHER WAITING GROUP 2
G-110 GOWNED SUB-WAITING GROUP 3
G-111 CORRIDOR GROUP 3
G-123 STAFF BREAK ROOM GROUP 4
G-130B MANAGER'S OFFICE GROUP 5
G-124 RADIOLOGIST WORKROOM GROUP 6
MILLWORK KEYING LEGEND
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
20 UNDERCOUNTER LIGHT
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
STANDING WATER
COOLER
CL
6"
PLUMBING CONNECTION
OPEN TO
BEYOND
1' - 6"
CL CL
1'-0"
25
A2.00
TYP
A9.50
11
MINERAL PROFILE PANELING
FEATURE WALL
LINE OF SOFFIT
A9.40
30
CL
6"
TOILET PAPER
FULL HEIGHT TILE
START WITH FULL TILE AT CORNER
WALL SCONCE, TYP.
PAPER SOAP
PURELL
OPEN TO
BEYOND
6"
12
A9.20
CT
48
36
25
14
A9.20
PURELL
CT
30
14
A9.20
CL
EQEQ
CHANGING ROOM BENCH
PURELL
CL 1'-8"
PURELL
CHANGING ROOM BENCH
CL1'-1"
PURELL
2'-0"CL
PURELL
PAPER
SOAP
TOILET PAPER
WALL SCONCE, TYP.FULL HEIGHT TILE
START WITH FULL TILE AT WALL
10
A4.00
PURELL
CL1'-2"
PURELL
SOILED LINEN BIN TRAY RACK
PAPER SOAP
WALL PROTECTION, TYP.
EQ EQCL
OPEN TO
BEYOND
3'-0"CL
OPEN TO
BEYOND
1'-1"
CL
PURELL
PHONE
CL 2'-2"4'-0"BONE DENSITY MACHINE
EMERGENCY POWER
AS
36
36
12
BONE DENSITY
WORKSTATION EMERGENCY
POWER
SOAPPAPER
WALL PROTECTION, TYP.
CT
121
36
25
302
WITH FASCIA
30
17
14
302
WITH FASCIA
30
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
302M
30
30
14
212
30 24
36
212
30 24
36
254
15 24
36
PANEL FRONT
151M
31 24
36
101M
15 24
36
21
A9.20
22
A9.20
11
A9.20
A9.20
31
L1
L1
PURELL
301
20
26
14
301
20
26
14
301
20
26
14
CT
63
40
25
16120 24
40
101
20 24
40
10120 24
40
SOILED LINEN
HAMPER
11
A9.20
OPEN TO
BEYOND
CLEQ EQ
L3 L3 L3
L3 L3
PLASTIC LAMINATE LOCKERS
CL 3' - 0"CLEQ EQ
X-RAY IN USE LIGHT
EQ EQCL
24
A2.00
TYP
EQEQCL
COAT HOOKS ON
HARDWOOD PANEL
4'-0"A9.40
10
EQ EQCL
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:50 AMA5.10
185-01-00
8/15/16
INTERIOR ELEVATIONS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
1/4" = 1'-0"1A SUB WAITING 1B 1C 1D 1/4" = 1'-0"2A PATIENT TOILET WAITING 2B 2C 2D
1/4" = 1'-0"3A LIAISON 3B 3C 3D4D4C4B 1/4" = 1'-0"4A NAVIGATOR'S OFFICE
7D7C7B 1/4" = 1'-0"7A MEN'S CHANGING & WAITING
11D11B11C 1/4" = 1'-0"11A CHANGING ROOM 112D12C12B 1/4" = 1'-0"12A CHANGING ROOM 213D13C13B 1/4" = 1'-0"13A CHANGING ROOM 3
14D14C14B 1/4" = 1'-0"14A PATIENT TOILET - CHANGING
9D9C9B 1/4" = 1'-0"9A SOILED HOLDING ROOM
15C 1/4" = 1'-0"15A CORRIDOR
8D8C8B 1/4" = 1'-0"8A BONE DENSITY
GC TO PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT, INCLUDING OFOI
1/4" = 1'-0"5A INTERVIEW 5B 5C 5D
10D 1/4" = 1'-0"10B PATIENT LOCKERS
1/4" = 1'-0"6B CORRIDOR G-115B 6C 6D
1E 1G
Issuance Schedule
Number Date Description
STEREOTACTIC MACHINE
EMERGENCY POWER
STEREOTACTIC GENERATOR
EMERGENCY POWER
SURFACE MOUNTED RACEWAY1'-0"CIRCUIT BREAKER
2'-9"
CL
SHARPS
BLACK BOX RED BOX
302
WITH FASCIA
30
26
14
3 SHELVES
101M
15 24
40
WALL PROTECTION TO UNDERSIDE
OF COUNTER
CORNER GUARDS TO UNDERSIDE
OF COUNTER
L1
GLOVES
3'-4"CL
SOAPPAPER
302M
39
26
14
SUCTION DEVICE
PANEL FRONT
151M
30 24
40
CT
40
12
A9.20
A9.20
31
WALL PROTECTION TO UNDERSIDE
OF COUNTER
422
37
84
25
422
37
84
25
212
30 24
36
211
15 24
36
101M
15 24
36
PANEL FRONT
151M
31 24
36
302
WITH FASCIA
30
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
11
A9.20
22
A9.20
302M30
30
14
A9.20
31
PAPER
SOAP
L1 L1 L1 L1
L1 L1
CT
91
36
25
SOAPPAPER
422
36
84
25
302
WITH FASCIA
30
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
101M
15 24
36
211
15 24
36
212
30 24
36
PANEL FRONT
151M
31 24
36
22
A9.20
302M
30
30
14
11
A9.20
A9.20
31
L1 L1
L1
SHARPS
WALL PROTECTION, TYP.
CT
92
36
25
PHONE
1'-5"
CL
VERTICAL SURFACE WIREWAY,
TYP.
CIRCUIT BREAKER
WALL MOUNTED
PADDLES
3'-0"1'-0"1'-10"CL
2" DIA. GROMMETED
CUTOUT, TYP.
HORIZONTAL
SURFACE
WIREWAY, TYP
12
A9.20
PURELL
CT
60
36
25
STEREO MONITOR
STAND
12
A9.203'-8"1'-10"CL
11"WALL PROTECTION, TYP.
SHARPS
PROVIDE BLOCKING IN
WALL
3'-0"4'-0"
CL 2'-6"6'-0"
PURELL
PHONE
SHARPS
1'-5"
CL
SOAP PAPER
302M
30
30
14
301
WITH FASCIA
15
30
14
301
WITH FASCIA
15
30
14
101M
15 24
36
PANEL FRONT
151M
30 24
36
211
15 24
36
254
24 24
36
421
24
54
25
22
A9.20
35
A9.20
11
A9.20
A9.20
31
STABLERISE14
A9.20
PURELL
6"
CL
CT
30
WALL PROTECTION, TYP.
SHARPS
PURELL
PHONE
3'-0"CL
SOAP
PAPER
302
WITH FASCIA
30
30
14
302
WITH FASCIA
30
30
14
302
WITH FASCIA
30
30
14
212
30 24
36
212
30 24
36
254
15 24
36
101M
15 24
36
PANEL FRONT
151M
31 24
36
CT
122
36
25
22
A9.20
22
A9.20
A9.20
31
302M30
30
14
L1 L1 L1
L1 L1 L1
PAPER
SOAP
WALL SCONCE, TYP.
TOILET PAPER
FULL HEIGHT TILE
START WITH FULL TILE AT WALL
PURELL
1'-2"
CL
MED GAS ZONE VALVE BOX (ALTERNATE)
EQ EQ
CLEQEQ LINE OF SOFFIT BEHINDEQEQEQEQCLCLCLX-RAY IN USE LIGHT
OPEN TO
BEYONDOPEN TO
BEYOND
EXISTING LAUNDRY CHUTE 24
A2.00
TYP
EQ EQ EQ EQ
CLCLX-RAY IN USE LIGHT
OPEN TO
BEYOND
OPEN TO
BEYOND OPEN TO
BEYOND
EQ EQ
CL
24
A2.00
TYP
OPEN TO
BEYOND
EQ EQCL EQ EQCLX-RAY IN USE LIGHT
OPEN TO
BEYOND
A9.50
12
6"
CL
101M
15 24
36
101
24 24
36
101
24 24
36
WATER
CT
65
36
25
11
A9.20
22
A9.20
MINERAL PROFILE PANELING
FEATURE WALL
LINE OF SOFFIT
A9.40
12
L3 L3
OPEN TO
BEYOND
18'-11"
25
A2.00
TYP
EQ EQ EQ EQ
CL CL
OPEN TO
BEYOND
OPEN TO BEYOND
EQ EQ
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:47:56 AMA5.11
185-01-00
8/15/16
INTERIOR ELEVATIONS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
22D22C22B 1/4" = 1'-0"22A STEROTACTIC
1/4" = 1'-0"25A MAMMOGRAPHY 25B 25C 25D
22H
GC TO PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT, INCLUDING OFOI
18D18C18B 1/4" = 1'-0"18A EXAM ROOM19D19C19B 1/4" = 1'-0"19A OFFICE
24D24C24B 1/4" = 1'-0"24A ULTRASOUND
1/4" = 1'-0"20A PATIENT TOILET 20B 20C 20D
1/4" = 1'-0"23A CORRIDOR G115 A A 23C 23D
21B 21D 1/4" = 1'-0"21A CORRIDOR G 115B
1/4" = 1'-0"16A GOWNED SUB-WAITING 16B 16C 16D 1/4" = 1'-0"17A CORRIDOR 17C17B
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
400
36
84
19
422
36
84
19
422
36
84
19
L5 L5
PRINTER, SM
AS
36
36
12
AS
36
36
12
COAT HOOKS
RECYCLEWASTEBASKET
EQ EQ
CL
TOILET PAPER
PAPER
SOAP
WALL SCONCE, TYP.
FULL HEIGHT TILE
START WITH FULL TILE AT WALL
PURELL
1'-1"
CL
MOBILE
PED
MOBILE
PEDMOBILE
PEDPRINTER
100M
TWO SHELVES
24.5 22
36
CT
25.6
36
25
COPIER
187M
24 22
28
CT
25.6
28
23
OPEN TO
BEYOND VIEW BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
EQ EQ
CL
5' - 6"FILM COPIER
9"CL
OPEN TO
BEYOND
EQ EQCL
PURELL
PHONE
COAT HOOKS
4'-2"CL
PLASTIC LAMINATE LOCKERS
LOCKER FILLER PANELS
EQ EQ
PURELL
3'-0"CL
CONFIDENTIAL
RECYCLE
CL 3'-8"
COAT HOOKS
PRINTER
SOAP
PAPER
PANEL FRONT
151M
31 24
36
101M
15 24
36
302
WITH FASCIA
30
17
14 300
WITH FASCIA
30
30
14
300
WITH FASCIA
30
30
14
300
WITH FASCIA
30
30
14
CT
47
36
25 CT
104
30
25
302
28
30
14
11
A9.20
22
A9.20
14
A9.20
L6
WALL SCONCES, TYP
3'-0"CL 10"
REFRIGERATOR
PAPER SOAP
MIRCROWAVE
KEURIG
301
15
28
14
302
30
28
14
326M
MICROWAVE SHELF
20"D
30
28
14 302
WITH FASCIA
30
17
14
PANEL FRONT
151M
31 24
36
CT
106
36
25
101M
15 24
36
11
A9.20
22
A9.20
254
20 24
36
254
20 24
36
254
20 24
36
WATER
L4 L4 L4L4
L4 L4 L4
PHONE
PURELL
1'-6"CL
SHARPS
PHONE
PURELL
SOAP PAPER
WALL PROTECTION, TYP.
CODE CART
302
WITH FASCIA
30
17
14
302
WITH FASCIA
30
30
14
301
21
30
14
PANEL FRONT
151M
30 24
36
DEFIBRILLATOR
CT
36
22
A9.20
11
A9.20
101M
15 24
36
212
25 24
36
L2 L2
L2
SHARPS
302
36
17
14
ICE
UC FRIDGE
WATER LINE AND DRAIN
L2
STRETCHER STRETCHER
A9.40
11
A9.40
11 .
CL CL
EQEQ EQEQ
3'-9"7'-7"
MEDICAL GASES ALTERNATE
4'-0"WALL PROTECTION, TYP.
301
WITH FASCIA
12
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
302
WITH FASCIA
30
30
14
3 SHELVES
25415 24
36
212
30 24
36
212
30 24
36
211
17 24
36
21
A9.20
11
A9.20
L1L1
L1L1
PAPERSOAP
301
WITH FASCIA
15
30
14
3 SHELVES
302M
30
30
14
301
WITH FASCIA
15
30
14
3 SHELVES
302
WITH FASCIA
31
30
14
3 SHELVES
212
36 24
36
PANEL FRONT
151M
30 24
36
101M
15 24
36
422
31
84
24
422
31
84
24
22
A9.20
CT
36
A9.20
31
L1 L1
WALL MOUNTED
PADDLES
3' - 0"1'-10"2" DIA. GROMMETED
CUTOUT, TYP.
HORIZONTAL
SURFACE
WIREWAY, TYP1'-0"PURELL
PHONE
CT
36
36
18
2'-0"
CL
VERTICAL SURFACE WIREWAY,
TYP.
CIRCUIT BREAKER
12
A9.20
CT
95
30
25
3'-2"10"
CL1'-6"
PAPER SOAP
PANEL FRONT
151M31 24
36
212
37 24
36
302
WITH FASCIA
37
30
14
302
WITH FASCIA
30
30
14
302
WITH FASCIA
30
17
14
CT
100
36
25
211
15 24
36
101M
15 24
36
22
A9.20
11
A9.20
L2 L2
L2 L2 L2OPEN TO
BEYOND
PURELL
PHONE
PURELL
METRO RACKMETRO RACK
WALL PROTECTION, TYP.
PAPERSOAP
212
30 24
36
211
15 24
36
302
WITH FASCIA
30
17
14
302
WITH FASCIA
30
30
14
302
WITH FASCIA
30
30
14
CT
110
36
25
PANEL FRONT
151M
31 24
36
101M
15 24
36
301
WITH FASCIA
18
30
14
211
18 24
36
22
A9.20
11
A9.20
L2 L2 L2
L2 L2 L2
EQ EQCL
A9.20
40
350
60
12
14
302
30
18
14
302
30
18
14
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:48:03 AMA5.12
185-01-00
8/15/16
INTERIOR ELEVATIONS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
34D34C34B 1/4" = 1'-0"34A MANAGER'S OFFICE A35D35C35B 1/4" = 1'-0"35A STAFF TOILET
36D36C36B 1/4" = 1'-0"36A TECH WORKROOM
33D33C33B 1/4" = 1'-0"33A STAFF LOCKERS
32D32C32B 1/4" = 1'-0"32A RADIOLOGIST WORKROOM
GC TO PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT, INCLUDING OFOI
1/4" = 1'-0"31A STAFF BREAK ROOM 31B 31C 31D
1/4" = 1'-0"29A STRETCHER WAITING 29B 29C 29D
26D26C26B 1/4" = 1'-0"26A LARGE MAMMOGRAPHY
28D28C28B 1/4" = 1'-0"28A NURSE STATION
1/4" = 1'-0"27A CLEAN STORAGE 27B 27C 27D
1/4" = 1'-0"30A CORRIDOR G-128 A 30B 30C 30D
CL
36F
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
1. ALL TYPICAL ACT CEILING HEIGHTS 8'-0" UNLESS OTHERWISE NOTED.
2. ALL TYPICAL ACT CEILING SHALL BE ACT-1, UNLESS OTHERWISE NOTED.
3. CEILINGS SHALL NOT BE INSTALLED WITHOUT REVIEWED MEP COORDINATION DRAWINGS AS
REQUIRED BY THE PROJECT SPECIFICATIONS.
4. AT NO TIME SHALL THE CONTRACTOR ADJUST THE CEILING HEIGHT AS INDICATED ON DOCUMENTS
WITHOUT REVIEW WITH ARCHITECT. ARCHITECT SHALL BE INFORMED OF ALL CEILING HEIGHT
CONFLICTS WHEN DISCOVERED FOR REVIEW.
5. COORDINATE ALL SOFFITS ABOVE CABINETS WITH INTERIOR ELEVATIONS AND CASEWORK DETAILS.
6. ALL DEVICES SHALL BE ALIGNED AND CENTERED WITHIN GRID UNLESS OTHERWISE NOTED.
7. REFER TO ALL ENGINEERING CONSULTANT AND VENDOR DRAWINGS FOR ALL RELATED SCOPE FOR
COORDINATION.
SEE CEILING PLAN
FOR HEIGHT6" MIN.VARIESCORNER BEAD
5/8" GYPSUM BOARD
ACOUSTICAL CEILING SYSTEM
5/8" GYPSUM BOARD
3 5/8" METAL STUD TO UNDERSIDE OF STRUCTURE
SEE CEILING PLAN
FOR HEIGHT
5/8" GYPSUM BOARD
CHANNELVARIESSEE CEILING PLAN
FOR HEIGHT
RIGID FURRING CHANNEL
5/8" GYPSUM BOARD
METAL ANGLE
CORNER BEAD
3 5/8" METAL STUD BRACE TO
UNDERSIDE OF STRUCTURE
3 5/8" METAL STUD BRACE TO
UNDERSIDE OF STRUCTURE
WOOD BLOCKING
ACOUSTICAL - CEILING SYSTEM
1/2" THREADED STEEL ROD
TO EXISTING STRUCTURE
EXISTING STRUCTURE
CURTAIN TRACK ATTACHED
TO BLOCKING ABOVE
SEE CEILING PLAN
FOR HEIGHT
5/8" GYPSUM BOARD
5/8" GYPSUM BOARD
SEE CEILING PLAN
FOR HEIGHT6" MIN.VARIES2" UON2" UON5/8" GYPSUM BOARD
CORNER BEAD
METAL CHANNEL
3 5/8" METAL STUD BRACE
TO UNDERSIDE OF STRUCTURE
3 5/8" METAL STUD BRACE
TO UNDERSIDE OF STRUCTURE
2'x2' SUPPLY DIFFUSER
NEW CEILING GRID WITH
NEW 2'x2' ACOUSTICAL
PANEL CEILING
NEW SOFFIT
1'x1' SUPPLY DIFFUSER
2'x2' RETURN REGISTER
1'x1' RETURN REGISTER EXIT SIGN
SMOKE DETECTOR 2'x2' RECESSED
LIGHT FIXTURE
SPRINKLER
EXISTING CEILING GRID WITH
EXISTING 2'x2' ACOUSTICAL
PANEL CEILING
EXISTING SOFFIT
LINEAR FLUSH MOUNTED
LIGHT FIXTURE
UNDER CABINET LIGHT FIXTURE
NURSE CALL
CURTAIN TRACK
MOTION SENSOR
SPEAKER
WIRELESS ACCESS POINT
1'x4' RECESSED
LIGHT FIXTURE
PENDANT LIGHT FIXTURE
INDIRECT WALL UPLIGHT/SCONCE
CEILING MOUNTED EXAM LIGHT
7' - 2"7' - 2"
EXAM 2
G-107
7' - 2"
7' - 2"
7' - 2"
7' - 2"
7' - 2"
7' - 2"
7' - 2"
GOWNED
SUB-WAITING
G-110
PATIENT CHANGING
ROOM 1
G-111D
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
PATIENT CHANGING
ROOM 2
G-111B
PATIENT CHANGING
ROOM 3
G-111C
BONE DENSITY
G-113
INTERVIEW 2
G-117
RADIOLOGIST
WORKROOM
G-124
CLEAN WORK AREA
G-126A
STAFF TOILET
G-130A
LIAISON
G-114C
LARGE
MAMMOGRAPHY
G-120
SCOPE OF WORK
7' - 2"
6' - 2"
ELECTRICAL
CLOSET
G-125
INTERVIEW 1
G-118 NAVIGATOR'S
OFFICE
G-116
EXAM 1
G-106
OFFICE
G-108
PATIENT TOILET
G-109
STEREOTACTIC
G-105
STAFF BREAK
ROOM
G-123
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127 NURSE STATION
G-126
SUB WAITING
G-119
7' - 2"
MAMMOGRAPHY
G-122
ULTRASOUND
G-121
6' - 2"
CORRIDOR
G-111
CORRIDOR
G-115C
8' - 6"
7' - 10"
7' - 10"
8' - 6"
4 7/8"
8 1/4"
4 7/8"
8 1/4"
12
A6.00
12
A6.00
7' - 2"
8' - 6"EQEQCORRIDOR
G-128
EQEQ
CORRIDOR
G-119B
SUB WAITING
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
CORRIDOR
G-115B
CORRIDOR
G-115B
CORRIDOR
G-115D
9"8' - 6"
7' - 6"
7' - 2"
7' - 2"
8' - 0"
ACT-2
7' - 6"
10
A6.00
10
A6.00 EQEQEQEQEQEQ
ALTERNATE 1
ALTERNATE 1
30
A6.00
TYP
30
A6.00
TYP
30
A6.00
TYP
EQEQ
CL
EQEQ
EQEQ
CL
CL
EQ EQ
CL
20
A6.00
20
A6.00
10
A6.00
7' - 2"
10
A6.00
7' - 6"
40
A6.00
40
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
40
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
40
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
10
A6.00
40
A6.00
10
A6.00
11
A6.00
SEE CEILING PLAN
FOR HEIGHT6" MIN.CORNER BEAD, TYP.
5/8" GYPSUM BOARD
ACOUSTICAL CEILING SYSTEM
5/8" GYPSUM BOARD
3 5/8" METAL STUD TO UNDERSIDE OF STRUCTURE
SEE CEILING PLAN
FOR HEIGHT
SCHEDULED LIGHT FIXTURE
SCHEDULED PARTITION
MINERAL PROFILE PANEL FEATURE WALL
SEE CEILING PLAN
FOR HEIGHT
SEE CEILING PLAN
FOR HEIGHT
5/8" GYPSUM BOARD
CHANNEL
SEE CEILING PLAN
FOR HEIGHT
ACOUSTICAL CEILING SYSTEM
METAL ANGLE
CORNER BEAD
3 5/8" METAL STUD BRACE TO
UNDERSIDE OF STRUCTURE
3 5/8" METAL STUD BRACE TO
UNDERSIDE OF STRUCTURE
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:05 AMA6.00
185-01-00
8/15/16
REFLECTED CEILING
GENERAL NOTES, KEYS,
LEGENDS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
GENERAL CEILING NOTES
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 CHANGE IN MATERIAL
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 CHANGE IN MATERIAL HEIGHT
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
30 CURTAIN TRACK
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
40 CHANGE IN CEILING
CEILING PLAN KEY
SCALE: 1/4" = 1'-0"1 REFLECTED CEILING PLAN
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 FEATURE WALL LIGHT FIXTURE POCKET
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
20 FEATURE CORRIDOR SOFFIT
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
2"3/4"1"1 15/16"1 15/16"VARIES4 7/8" AT 3 3/4" PARTITION6" AT 4 7/8" PARTITION6 5/8" AT 5 1/2" PARTITION6 3/4" AT 5 5/8" PARTITION7 1/4" AT 6 1/8" PARTITION8 1/4" AT 7 1/8" PARTITION8 3/8" AT 7 5/8" PARTITION8 3/4" AT 7 5/8" PARTITION9" AT 7 7/8" PARTITION9 5/8" AT 8 1/2" PARTITION9 3/4" AT 8 5/8" PARTITION-1/2" AT 1/4" GLASS
7/8" AT 5/8" GLASS
1 15/16"1 15/16"VARIES
4 7/8" AT 3 3/4" PARTITION
6" AT 4 7/8" PARTITION
6 5/8" AT 5 1/2" PARTITION
6 3/4" AT 5 5/8" PARTITION
7 1/4" AT 6 1/8" PARTITION
8 1/4" AT 7 1/8" PARTITION
8 3/8" AT 7 5/8" PARTITION
8 3/4" AT 7 5/8" PARTITION
9" AT 7 7/8" PARTITION
9 5/8" AT 8 1/2" PARTITION
9 3/4" AT 8 5/8" PARTITION
1/2"1/2"2"3/4"1 15/16"1 15/16"VARIES4 7/8" AT 3 3/4" PARTITION6" AT 4 7/8" PARTITION6 5/8" AT 5 1/2" PARTITION6 3/4" AT 5 5/8" PARTITION7 1/4" AT 6 1/8" PARTITION8 1/4" AT 7 1/8" PARTITION8 3/8" AT 7 5/8" PARTITION8 3/4" AT 7 5/8" PARTITION9" AT 7 7/8" PARTITION9 5/8" AT 8 1/2" PARTITION9 3/4" AT 8 5/8" PARTITION1/2"1/2"2"3/4"3/4"1"
1 15/16"1 15/16"VARIES
4 7/8" AT 3 3/4" PARTITION
6" AT 4 7/8" PARTITION
6 5/8" AT 5 1/2" PARTITION
6 3/4" AT 5 5/8" PARTITION
7 1/4" AT 6 1/8" PARTITION
8 1/4" AT 7 1/8" PARTITION
8 3/8" AT 7 5/8" PARTITION
8 3/4" AT 7 5/8" PARTITION
9" AT 7 7/8" PARTITION
9 5/8" AT 8 1/2" PARTITION
9 3/4" AT 8 5/8" PARTITION
1/2"1/2"
1/2" AT 1/4" GLASS
7/8" AT 5/8" GLASS
2"1"
1 15/16"1 15/16"VARIES
4 7/8" AT 3 3/4" PARTITION
6" AT 4 7/8" PARTITION
6 5/8" AT 5 1/2" PARTITION
6 3/4" AT 5 5/8" PARTITION
7 1/4" AT 6 1/8" PARTITION
8 1/4" AT 7 1/8" PARTITION
8 3/8" AT 7 5/8" PARTITION
8 3/4" AT 7 5/8" PARTITION
9" AT 7 7/8" PARTITION
9 5/8" AT 8 1/2" PARTITION
9 3/4" AT 8 5/8" PARTITION
1/2"1/2"
1/2" AT 1/4" GLASS
7/8" AT 5/8" GLASS2"3/4"3/4"1"
1 15/16"1 15/16"VARIES
4 7/8" AT 3 3/4" PARTITION
6" AT 4 7/8" PARTITION
6 5/8" AT 5 1/2" PARTITION
6 3/4" AT 5 5/8" PARTITION
7 1/4" AT 6 1/8" PARTITION
8 1/4" AT 7 1/8" PARTITION
8 3/8" AT 7 5/8" PARTITION
8 3/4" AT 7 5/8" PARTITION
9" AT 7 7/8" PARTITION
9 5/8" AT 8 1/2" PARTITION
9 3/4" AT 8 5/8" PARTITION
1/2"1/2"4"3/4"1/2" AT 1/4" GLASS
7/8" AT 5/8" GLASS1"1 15/16"1 15/16"VARIES4 7/8" AT 3 3/4" PARTITION6" AT 4 7/8" PARTITION6 5/8" AT 5 1/2" PARTITION6 3/4" AT 5 5/8" PARTITION7 1/4" AT 6 1/8" PARTITION8 1/4" AT 7 1/8" PARTITION8 3/8" AT 7 5/8" PARTITION8 3/4" AT 7 5/8" PARTITION9" AT 7 7/8" PARTITION9 5/8" AT 8 1/2" PARTITION9 3/4" AT 8 5/8" PARTITION1/2"1/2"3/4"-1/2" AT 1/4" GLASS
7/8" AT 5/8" GLASS
2"7' - 2"A
VARIES
SINGLE 7' - 2"B
VARIES
DOUBLE 7' - 2"C SINGLE WITH
SIDELITE
VARIES
4"2"2"VARIESD
VARIES
DOUBLE ACTING
OR CASED OPENING
21
A9.10
21
A9.10
21
A9.10
20
A9.10
20
A9.10
20
A9.10
24
A9.10
23
A9.10
11
A9.10
22
A9.10
10
A9.10
13
A9.10 VARIESW
VARIES
WOOD SINGLE
14
A9.10
15
A9.10 VARIESWC
VARIES
WOOD CASED OPENING
34
A9.50
42
A9.50
DOOR AND WINDOW CONSTRUCTION:
ACOUS ACOUSTICAL CORE WOOD
AC ALUMINUM CLAD WOOD
AL ALUMINUM
HC HOLLOW CORE WOOD
HM HOLLOW METAL
LL LEAD LINED FRAME
SC SOLID CORE WOOD
SS STAINLESS STEEL
TG TEMPERED SAFETY GLASS
DOOR GLASS TYPE:
-- NO GLASS REQUIRED
CR CLEAR WIRED
FR FIRE RATED PER SPECIFICATIONS
IG INSULATING GLASS
LG LAMINATED GLASS
TF CLEAR TEMPERED FLOAT
TI TEMPERED INSULATING
LE LEAD GLASS
FRAME CONSTRUCTION:
AC ALUMINUM CLAD WOOD
AL ALUMINUM
PS PRESSED STEEL
SS STAINLESS STEEL
WD WOOD
DOOR FACING AND FINISH:
AF ALUMINUM FACTORY FINISH
CC COPPER CLADDING
CL HARDWOOD, TRANSPARENT FINISH
MF METAL FACTORY FINISH
MP METAL PAINTED
WD WOOD PAINTED
FIRE RATING:
BLANK NO FIRE RATING REQUIRED
A180 3 HOUR RATING ('A' LABEL REQUIRED)
B60 1 HOUR RATING (B LABEL REQUIRED)
B90 1- 1/2 HOUR RATING ('B' LABEL REQUIRED)
C45 3/4 HOUR ('C' LABEL REQUIRED)
20 1/3 HOUR RATING
30 1/2 HOUR RATING
REMARKS:
1. TRANSOM OR SIDELIGHT ADJACENT
2. SPECIAL HEIGHT DOOR
3. SPECIAL ALUMINUM DOOR AND FRAME
4. SECURITY TIE IN REQUIREMENTS
5. SPECIAL WOOD DOOR AND FRAME
6. SOUND GASKETING
7. WEATHERING STRIP
8. MAGNETIC HOLD OPENS
9. LIGHT GASKET
10. FIELD MEASUREMENT REQUIRED
11. DOUBLE ACTING REMOVE FRAME STOP
12. LEAD LINING REQUIRED
13. AUTOMATIC DOORS
14. CODE ACCESS HARDWARE
15. EXISTING DOOR
16. STAINLESS STEEL KICK PLATE
17. ROTON HINGE
4 7/8" AT 3 3/4" PARTITION
6" AT 4 7/8" PARTITION
6 5/8" AT 5 1/2" PARTITION
6 3/4" AT 5 5/8" PARTITION
7 1/4" AT 6 1/8" PARTITION
8 1/4" AT 7 1/8" PARTITION
8 3/8" AT 7 5/8" PARTITION
8 3/4" AT 7 5/8" PARTITION
9" AT 7 7/8" PARTITION
9 5/8" AT 8 1/2" PARTITION
9 3/4" AT 8 5/8" PARTITION
1/2"1/2"2"4 7/8" AT 3 3/4" PARTITION6" AT 4 7/8" PARTITION6 5/8" AT 5 1/2" PARTITION6 3/4" AT 5 5/8" PARTITION7 1/4" AT 6 1/8" PARTITION8 1/4" AT 7 1/8" PARTITION8 3/8" AT 7 5/8" PARTITION8 3/4" AT 7 5/8" PARTITION9" AT 7 7/8" PARTITION9 5/8" AT 8 1/2" PARTITION9 3/4" AT 8 5/8" PARTITION1/2"1/2"2"
F FGFLUSH FULL
GLAZED
HG HALF
GLAZED
N NARROW
GLAZED
TEMPERED GLAZING
3' - 0"TEMPERED GLAZING
2' - 1"TEMPERED GLAZING4"
SCHEDULED LEAF
6"6"10"8"10"6"6"
1 WINDOW - NURSE STATION
21
A9.10
20
A9.10
2 WINDOW - STEREOTACTIC
21
A9.10
20
A9.10
TEMPERED GLAZING LEAD LINED GLAZING
1/16" EQUIVALENT6'-0"4'-6"3'-6"4'-0"1/4" WOOD REVEAL, TYP.
3/4" HARDWOOD, TYP.
6 1/2"
SCHEDULED PARTITION10"1/4" WOOD REVEAL, TYP.
3/4" HARDWOOD, TYP.6 1/2"SCHEDULED PARTITION
3"
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:07 AMA9.10
185-01-00
8/15/16
DOOR HARDWARE, FRAME
TYPES & DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
SECTION DETAIL
6" = 1'-0"
11 TYPICAL GLAZED DOOR JAMB
SCALE:
SECTION DETAIL
6" = 1'-0"
21 DOOR FRAME HEAD
SCALE:
SECTION DETAIL
6" = 1'-0"
20 DOOR FRAME JAMB
SCALE:
SECTION DETAIL
6" = 1'-0"
22 GLAZED OPENING FRAME HEAD
SCALE:
SECTION DETAIL
6" = 1'-0"
12 GLAZED OPENING FRAME SILL
SCALE:
SECTION DETAIL
6" = 1'-0"
10 GLAZED OPENING FRAME WITH 4" SILL
SCALE:
SECTION DETAIL
6" = 1'-0"
13 GLAZED OPENING JAMB
DOOR FRAME TYPES
DOOR ABBREVIATIONS
SCALE:
SECTION DETAIL
6" = 1'-0"
24 DOUBLE ACTING OR CASED DOOR FRAME HEAD
SCALE:
SECTION DETAIL
6" = 1'-0"
23 DOUBLE ACTING OR CASED DOOR FRAME JAMB
DOOR FRAME
HDWR COMMENTSMARK ROOM NAME OPERATION
OPENING PANEL
TYPE MATLWIDTH HEIGHT TYPE MATL THICK CONFIG
PANEL
WIDTH
LEAF
TYPE
LEAF
WIDTH
G-105-A STEREOTACTIC Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-106-A EXAM 1 Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4"SINGLE 3' - 6"A PS 19 PASSAGE LOCKSET, HOLD-OPEN CLOSER
G-107-A EXAM 2 Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4"SINGLE 3' - 6"A PS 19 PASSAGE LOCKSET, HOLD-OPEN CLOSER
G-108-A OFFICE Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4"SINGLE 3' - 0"A PS 05 OFFICE LOCKSET
G-109-A PATIENT TOILET Single - Double Acting 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"D PS 03 PRIVACY LOCKSET, DOUBLE ACTING, THUMB TURN INDICATOR, GASKETING
G-110-A GOWNED SUB-WAITING Cased Opening 3' - 6" 7' - 6"1 3/4"WC WD CASED OPENING, NO DOOR PANEL REQUIRED, REFER TO A9.50 HARDWOOD DOOR DETAILS
G-110-B GOWNED SUB-WAITING Cased Opening 3' - 6" 7' - 6"1 3/4"WC WD CASED OPENING, NO DOOR PANEL REQUIRED
G-111A-A CHANGING PATIENT TOILET Single - Double Acting 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"D PS 03 PRIVACY LOCKSET, DOUBLE ACTING, THUMB TURN INDICATOR, GASKETING
G-111B-A PATIENT CHANGING ROOM 2 Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"A PS 18 PRIVACY LOCKSET, THUMB TURN INDICATOR
G-111C-A PATIENT CHANGING ROOM 3 Single - Double Acting 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"D PS 03 PRIVACY LOCKSET, DOUBLE ACTING, THUMB TURN INDICATOR, GASKETING
G-111D-A PATIENT CHANGING ROOM 1 Single - Double Acting 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"D PS 03 PRIVACY LOCKSET, DOUBLE ACTING, THUMB TURN INDICATOR, GASKETING
G-112-A SOILED HOLDING ROOM Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 01 STORAGE LOCKSET
G-113A BONE DENSITY Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-114-A MEN'S CHANGING & WAITING Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"A PS 09 PRIVACY LOCKSET, THUMB TURN INDICATOR
G-115A-A CORRIDOR Double - Egress 6' - 0" 7' - 0" F SC 1 3/4" PAIR 3' - 0"B PS 10 NO LOCKING
G-115A-B CORRIDOR Cased Opening 3' - 0" 7' - 0" SC 1 3/4"D PS N/A
G-115B-A CORRIDOR Double - Egress 6' - 0" 7' - 0" F SC 1 3/4" PAIR 3' - 0"B PS 11 POWER OPERATOR WITH PROX CARD ACCESS
G-116-A NAVIGATOR'S OFFICE Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"A PS 06 OFFICE LOCKSET
G-117-A INTERVIEW 2 Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"A PS 06 OFFICE LOCKSET
G-118-A INTERVIEW 1 Single - Hinged 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"A PS 06 OFFICE LOCKSET
G-119-A SUB WAITING Single - Hinged 3' - 6" 7' - 6" FG SC 1 3/4" SINGLE 3' - 6"W WD 12 POWER OPERATOR WITH PROX CARD ACCESS, WOOD FRAME, REFER TO A9.50 HARDWOOD DOOR DETAILS
G-119-B SUB WAITING Single - Hinged 3' - 6" 7' - 0" N SC 1 3/4" SINGLE 3' - 6"A PS 03 PASSAGE LOCKSET, HOLD-OPEN CLOSER
G-119A-A SUB WAITING PATIENT TOILET Single - Double Acting 3' - 6" 7' - 0" F SC 1 3/4" SINGLE 3' - 6"D PS 21 PRIVACY LOCKSET, DOUBLE ACTING, THUMB TURN INDICATOR, GASKETING
G-119B-A CORRIDOR Cased Opening 3' - 6" 7' - 6"1 3/4"D PS CASED OPENING, NO DOOR PANEL REQUIRED
G-119B-B CORRIDOR Single - Hinged 3' - 6" 7' - 0" N SC 1 3/4" SINGLE 3' - 6"A PS 13 PASSAGE LOCKSET
G-120-A LARGE MAMMOGRAPHY Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-121-A ULTRASOUND Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-122-A MAMMOGRAPHY Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-123-A STAFF BREAK ROOM Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 02 CLASSROOM LOCKSET
G-124-A RADIOLOGIST WORKROOM Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 08 OFFICE LOCKSET, SOUND GASKETING
G-125-A ELECTRICAL CLOSET Double - Hinged 8' - 0" 7' - 0" F SC 1 3/4" PAIR 4' - 0"B PS 20 STORAGE LOCKSET, MANUAL FLUSH BOLT
G-126A-A CLEAN WORK AREA Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 04 STORAGE LOCKSET
G-127-A STRETCHER WAITING Double - Unequal 4' - 6" 7' - 0" F SC 1 3/4" UNEQUAL 3' - 6" F 1' - 0" B PS 17 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-128-A CORRIDOR Double - Egress 6' - 0" 7' - 0" F SC 1 3/4" PAIR 3' - 0"B PS 14 PROX CARD ACCESS
G-130-A TECH WORKROOM Single - Hinged 3' - 0" 7' - 0" N SC 1 3/4" SINGLE 3' - 0"A PS 15 CLASSROOM LOCKSET, HOLD-OPEN CLOSER
G-130A-A STAFF TOILET Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 16 PRIVACY LOCKSET, THUMB TURN INDICATOR
G-130B-A MANAGER'S OFFICE Single - Hinged 3' - 0" 7' - 0" F SC 1 3/4" SINGLE 3' - 0"A PS 07 OFFICE LOCKSET
DOOR PANEL TYPES
WINDOW SCHEDULE
SCALE:
SECTION DETAIL
6" = 1'-0"
14 WOOD CASED FRAME HEAD
SCALE:
SECTION DETAIL
6" = 1'-0"
15 WOOD CASED FRAME JAMB
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
BOOKENDS WHERE REQUIRED
3/4" PLYWOOD WITH PLAM
SCHEDULED
SHELVING BRACKET,
TYP.
LOCATER CLIP ATTACHED
TO SHELF (TYP.)
48" SCHEDULED SHELVING
STANDARD - CUT TO SUIT FIELD
CONDITIONS IF REQUIRED
CLEAR HEIGHT BETWEEN
SHELVES1' - 1" TYP.1' - 0" TYP.6" TYP.PROVIDE BLOCKING IN WALL
3/4" PLYWOOD WITH PLAM
1/2" SOLID SURFACE BACKSPLASH
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD SUBSTRATE
EASED EDGE, TYP
BLOCKING
1 1/2"SCHEDULED SUPPORT
BRACKETS
SCHEDULED WALL BASE
PROVIDE BLOCKING IN WALL
REFER TO CASEWORK TAG IN ELEVATIONREFER TO CASEWORK TAG IN ELEVATION
4"JOINT SEALANT
1/2" SOLID SURFACE
BACKSPLASH
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD BACKING
2" EASED EDGE, TYP
BLOCKING
1 1/2"REFER TO CASEWORK TAG IN ELEVATIONREFER TO CASEWORK TAG IN ELEVATION
4"JOINT SEALANT
TOE KICK HEIGHT
TOE KICK DEPTH
FACE OF CABINET BELOW
SCHEDULED WALL BASE
3"4"3/4" PLYWOOD WITH PLAM
(2) LAYERS OF 3/4" PLYWOOD WITH
PLAM
WOOD BLOCKING
SCHEDULED SUPPORT
BRACKETS
SCHEDULED WALL BASE
PROVIDE BLOCKING IN WALL4"T MOULDING PROFILE EDGE
REFER TO CASEWORK TAG IN ELEVATION1 1/2"REFER TO CASEWORK TAG IN ELEVATION
3/4" PLYWOOD WITH PLAM
(2) LAYERS OF 3/4" PLYWOOD WITH
PLAM
WOOD BLOCKING
PROVIDE BLOCKING IN WALL4"T MOULDING PROFILE EDGE
REFER TO CASEWORK TAG IN ELEVATION1 1/2"REFER TO CASEWORK TAG IN ELEVATION
TOE KICK HEIGHT
TOE KICK DEPTH
FACE OF CABINET BELOW
SCHEDULED WALL BASE
3"4"3/4"
SCHEDULED WALL BASE
ADJ. FOOT (TYP.)
3/4" PLYWOOD (SCRIBE TO FLOOR)4"3/4" PLYWOOD
3/4" PLYWOOD WITH PLAM8"7"3"5"1' - 8 1/2"
1/2" x 4" SOLID SURFACE
BACKSPLASH
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD BACKING
EASED EDGE, TYP
BLOCKING, TYP.3'-0"6"8"7"7"8"SCHEDULED WALL BASE
ADJ. FOOT (TYP.)
3/4" PLYWOOD (SCRIBE TO FLOOR)4"3/4" PLYWOOD
3/4" PLYWOOD WITH PLAM7' - 0"5"8"8"8"6"1'-9"7"7"7"SCHEDULED SINK
4"3"
3/4" x 4" SOLID SURFACE
BACKSPLASH
3/4" SOLID SUFACE COUNTERTOP
WITH 3/4" PLYWOOD BACKING
EASED EDGE, TYP
BLOCKING, TYP.
2'-1"
SCHEDULED WALL BASE
ADJ. FOOT (TYP.)
3/4" PLYWOOD (SCRIBE TO FLOOR)
3/4" PLYWOOD
3/4" PLYWOOD W/ PLAM
2'-10"1 1/2"5"FIXED PANEL
SCHEDULED WALL BASE
ADJ. FOOT (TYP.)
3/4" PLYWOOD (SCRIBE TO FLOOR)
3"4"1/2" x 4" SOLID SURFACE
BACKSPLASH
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD BACKING
EASED EDGE, TYP
BLOCKING, TYP.1 1/2"2'-10"2'-1"2"SCHEDULED WASTEBASKET
3/4" PLYWOOD
3/4" PLYWOOD WITH PLAMCLEAR5"1/4" ALUMINUM TRIM
SCHEDULED WALL BASE
ADJ. FOOT (TYP.)
3/4" PLYWOOD (SCRIBE TO FLOOR)4"3/4" PLYWOOD
3/4" PLYWOOD WITH PLAM8"7"3"5"1' - 8 1/2"
1/2" x 4" SOLID SURFACE
BACKSPLASH
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD BACKING
EASED EDGE, TYP
BLOCKING, TYP.3'-0"6"1'-4"1'-2"BLOCKING, TYP.
3/4" PLYWOOD WITH PLAM
2' - 6"WALL MOUNTED PAPER TOWEL
DISPENSER, SOAP DISPENSER AND
GLOVE HOLDER1'-4"1' - 1"3/4" PLYWOOD WITH PLAM DOOR
3/4" PLYWOOD WITH PLAM
CLEAR
1'-2"
SEE CEILING PLAN
FOR HEIGHT6" MIN.VARIESACOUSTICAL CEILING SYSTEM
5/8" GYPSUM BOARD
3 5/8" METAL STUD TO UNDERSIDE OF STRUCTURE
2"SCHEDULED TILE BACKSPLASH
1/4" SCHEDULED ALUMINUM TRIM
1/4" SCHEDULED ALUMINUM
TRIM
30
A9.20
SCHEDULED TILE
BACKSPLASH
3/4" HARDWOOD WITH 3/4"
PLYWOOD BACKING
HARDWOOD BULLNOSE POFILE EDGE
BLOCKING, TYP.1'-6"2'-0"
SCHEDULED WALL BASE, TYP.4"2'-0"4'-0"23
A9.20
3/4" HARDWOOD WITH 3/4"
PLYWOOD BACKING
2" RADIUS CORNER
1/2" SOLID SUFACE COUNTERTOP
WITH 1" PLYWOOD BACKING
EASED EDGE, TYP
BLOCKING, TYP.1 1/2"3'-4"2'-1"
SCHEDULED SOILED LINEN
3/4" PLYWOOD WITH PLAM
1/2"1'-3"
EQ EQCL
1'-1"1'-0"1'-3"1'-3"
CL
CL
33
A9.20
EASED CORNERS, TYP.
25
A9.20
3/4"3'-11"
3/4" SOLID SURFACE COUNTERTOP
WITH 3/4" PLYWOOD SUBSTRATE
COUNTERTOP BELOW
R 10"
2' - 1"2' - 6"1' - 3"ALIGN3/4" SOLID SURFACE DIVIDER 4"4"1'-2"1'-3"1'-3"1'-2"
1/4" TYP.1/4" TYP.2"CL CL CL
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1 1/2" = 1'-0"8/15/2016 9:48:08 AMA9.20
185-01-00
8/15/16
CASEWORK MENU AND
DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 ADJUSTABLE SHELVES- SECTION
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 SOILD SURFACE COUNTERTOP WITH BRACKETS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 SOILD SURFACE COUNTERTOP ABOVE CABINETS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
14 PLAM COUNTERTOP WITH BRACKETS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
13 PLAM COUNTERTOP ABOVE CABINETS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
20 4 DRAWER SECTION
SCALE:
EXTERIOR SECTION DETAIL
1 1/2" = 1'-0"
35 EXAM ROOM CABINET
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
15 FIXED FULL PANEL SINK FASCIA
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
22 WASTEBASKET CABINET
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
21 FILE CABINET DRAWERS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
30 GLOVE & PAPER TOWEL CABINETS
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
31 TILE WORK CALL OUT
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
23 CHANGING ROOM BENCH
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
24 CHANGING ROOM BENCH
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
33 SOILED LINEN HAMPER CABINET
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
32 SOILED LINEN COUNTER
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
34 RADIOLOGY WORKROOM FIN
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
25 RADIOLOGY WORKROOM FIN
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
40 TECH WORKROOM SHELF
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
11
A9.30
13
A9.30
CL
CL
CL
CL
5"5"
12
A9.30
2" RADIUS OUTSIDE CORNERS, TYP.
CLCENTERLINE OF PARTITION BELOW
A9.30 30
A9.3020
(2) LAYERS OF 3/4" PLYWOOD WITH PLAM COUNTER
PLYWOOD WITH PLAM BACK/SIDESPLASH, TYP.
CENTERLINE OF PARTITION BELOW
TACKABLE SURFACE DIVIDER, TYP.
CL
CL
CL
2' - 7 1/4" +/-4' - 2"4' - 2"1' - 3"1' - 3"4' - 2"4' - 2"2' - 7 1/4" +/-(2) LAYERS OF 3/4" PLYWOOD WITH PLAM COUNTER
(2) LAYERS OF 3/4" PLYWOOD WITH
PLAM
T-MOLDING EDGE, TYP
BLOCKING, TYP.
EQ EQCL
5/8" GYPSUM WALL BOARD
3'-0"SCHEDULED WALL BASE, TYP.
TACKABLE SURFACE ON 3/4" PLYWOOD
1/4" ALUMNIUM CHANNEL
4"4 5/8"
(1) LAYER OF 3/4" PLYWOOD WITH
PLAM
3/4" ALUMINUM CHANNEL
(2) LAYERS OF 3/4" PLYWOOD WITH PLAM
T-MOLDING EDGE, TYP
4"TACKABLE SURFACE ON 3/4" PLYWOOD WITH ALUMINUM FRAME
4"(1) LAYER OF 3/4" PLYWOOD WITH PLAM BACKSPLASH, TYP.
BLOCKING
3"
SCHEDULED WALL BASE
SCHEDULED BASE CABINET
CL
13
A9.30
11
A9.30
12
A9.30
COUTNER ABOVE
CENTERLINE OF PARTITION BELOW
3/4" PLYWOOD WITH PLAM.
CENTERLINE OF PARTITION BELOW
BLOCKING, TYP.5"5"
GROMMETS, TYP.4' - 0"4' - 0"SCHEDULED WALL BASE 4"4"FINISHED END PANEL
3"
SCHEDULED BASE CABINET
SCHEDULED PARTITION
(2) LAYERS OF 3/4" PLYWOOD WITH PLAM
T-MOLDING EDGE, TYP
TACKABLE SURFACE ON 3/4" PLYWOOD WITH ALUMINUM FRAME
(1) LAYER OF 3/4" PLYWOOD WITH PLAM BACKSPLASH, TYP.
BLOCKING
GROMMET, TYP.
CL 2"2"
MOBILE
PED
MOBILE
PED
MOBILE
PED
SCANNER
CPU
SCANNER
CPU
SCANNER
CPU
3/4"3' - 0"4"8"2' - 4"1' - 0"8"TACKABLE SURFACE DIVIDER
WITH FRAME
BACKSPLASH
SCHEDULED BASE CABINET 1"
1"
MOBILE
PED
MOBILE
PEDMOBILE
PED
SCANNER
CPU SCANNER CPU SCANNER
CPU
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:10 AMA9.30
185-01-00
8/15/16
CUSTOM CASEWORK
DETAILS - TECH WORKROOM
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
PLAN DETAIL
1" = 1'-0"22 TECH WORKSTATION COUNTERTOP
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
13 TECH WORKROOM WORKSTATION
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 TECH WORKROOM WORKSTATION
SCALE:
SECTION DETAIL
1" = 1'-0"21 TECH WORKSTATION FRAMING PLAN
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 TECH WORKROOM WORKSTATION AT COPIER
SCALE:
SECTION DETAIL
1" = 1'-0"
30 TECH WORKROOM B Copy 1
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 COPIER AREA
SCALE:
SECTION DETAIL
1" = 1'-0"20 TECH WORKROOM D Copy 1
Issuance Schedule
Number Date Description
9"6"
6"
CL3'-5"CL
CL
1'-2"1'-6"1'-0"1'-0"
3/4" HARDWOOD
2'-0"5'-2"
EQ EQ EQ EQ EQ EQ EQ 6"6"EQ EQ EQ EQ EQ EQ
SCHEDULED COAT HOOKS
EASED EDGES, TYP.
WALL MOUNTED WITH Z-CLIPS
20
A9.40
12
A6.00
20
A9.40
LINE OF SOFFIT
FINISHED FLOOR
GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION
12
A6.00
20
A9.40
LINE OF SOFFIT
GRAIN DIRECTION GRAIN DIRECTIONGRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION GRAIN DIRECTION
1/2" SOLID SURFACE
ON 3/4" PLYWOOD EASED EDGE
4"SCHEDULED PARTITION
MINERAL PROFILE PANEL FEATURE WALL
2"
FINISHED FLOOR
3/4" PLYWOOD WITH PLAM
(2) LAYERS OF 3/4" PLYWOOD WITH
PLAM
WOOD BLOCKING
SCHEDULED SUPPORT
BRACKETS
SCHEDULED WALL BASE
PROVIDE BLOCKING IN WALL4"T MOULDING PROFILE EDGE
2'-6"1 1/2"2'-1"2' - 1"2' - 1"4'-0"2' - 8"
R 2 ' - 0 "CL
CL
EQEQ3'-5"6"8"3'-9"3' - 0"
CL
CL
CL
CL
21
A9.40
10"
COUNTERTOP ABOVE
GROMMETS ABOVE, TYP.
SCHEDULED BRACKETS,
TYP.
HAFELE SUPPORT LEG,
SINGLE COLUMN 114
R 2' - 0"4'-0"2'-1"2'-1"21
A9.40
2'-8"
CL
CL
CL
CL
3"3"3"3"
(1) LAYER OF 3/4" PLYWOOD WITH PLAM
GROMMETS, TYP.
(2) LAYERS OF 3/4" PLYWOOD
WITH PLAM COUNTER 3'-5"2'-0"6'-0"Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:11 AMA9.40
185-01-00
8/15/16
INTERIOR DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 HEADWALL CALLOUT
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 COAT HOOKS
SCALE:
SECTION DETAIL
1" = 1'-0"
30 WAITING ROOM MODULAR ARTS WALL
SCALE:
SECTION DETAIL
1" = 1'-0"
12 GOWNED SUB WAITING MODULAR ARTS WALL
SCALE:
SECTION DETAIL
3" = 1'-0"
20 FEATURE WALL TYPICAL BASE
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
21 MANAGER'S OFFICE DESK
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
32 MANAGER'S OFFICE DESK
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
31 GROUND FLOOR - MANAGER'S DESK
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
31
A9.50
30
A9.50
10
A9.50
20
A9.50
32
A9.50
40
A9.50
41
A9.50
8' - 0"6'-7" +/-5' - 6 1/2"1' - 1 1/4"6 1/2"31
A9.50
30
A9.50
10
A9.50
34
A9.50
42
A9.50
33
A9.50
20
A9.50
OPEN TO BEYOND
8' - 10"8' - 0"1' - 1 1/4"5' - 6 1/2"6 1/2"1/4" WOOD REVEAL
3/4" HARDWOOD BASE
CL
1"1/4" CAULK JOINT, TYP.4"1/2"6 1/2"BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD5"2"4"EQEQCL
SCHEDULED PARTITION
BLOCKING, TYP.
1" PLYWOOD FILLER
HARDWOOD DOOR FRAME
3/4" HARDWOOD
1/4" CAULK JOINT, TYP.5"4"EQEQCL
2"
SCHEDULED PARTITION
BLOCKING, TYP.
1" PLYWOOD FILLER
HARDWOOD DOOR FRAME
3/4" HARDWOOD
1/4" CAULK JOINT, TYP.
SCHEDULED DOOR
CL
2 1/2" 2 1/2"
5"6"1/4" WOOD REVEAL
BLOCKING, TYP.
1/4" PLYWOOD FILLER
HARDWOOD FRAME
3/4" HARDWOOD
1/2"3 1/4"SCHEDULED CEILING
1/4" WOOD REVEAL
CL
2 1/2" 2 1/2"
BLOCKING, TYP.
1/4" PLYWOOD FILLER
SCHEDULED DOOR
HARDWOOD FRAME
3/4" HARDWOOD
1/2"3 1/4"6"SCHEDULED CEILING
BLOCKING, TYP.
1/4" WOOD REVEAL
1/4" PLYWOOD FILLER
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
CL
2 1/2" 2 1/2"
5"4"6"1/2"SCHEDULED CEILING
CL
2 1/2"2 1/2"2 1/2"5"
BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD1/2"1/4" WOOD REVEALCL2 1/2"2 1/2"6 1/4"5"2"
BLOCKING, TYP.
1/2" PLYWOOD FILLER
HARDWOOD DOOR FRAME
3/4" HARDWOOD
1/2" TEMPERED GLAZING
GLAZING CL2 1/2"2 1/2"5"2"
1/4" WOOD REVEAL
BLOCKING, TYP.
1/2" PLYWOOD FILLER
HARDWOOD DOOR FRAME
3/4" HARDWOOD
1/2" TEMPERED GLAZING
GLAZING
SCHEDULED DOOR
6 1/4"
CL5"2 1/2"2 1/2"4 1/2" +/- 3/4"
SCHEDULED PARTITION
WAITING ROOM
G-119
CORRIDOR
BLOCKING, TYP.
1/4" WOOD REVEAL
1" PLYWOOD FILLER
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
1/4" CAULK JOINT, TYP.
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:12 AMA9.50
185-01-00
8/15/16
HARDWOOD DOOR DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 SUB WAITING ROOM DOOR
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 GOWNED SUB-WAITING ROOM DOOR
SCALE:
SECTION DETAIL
3" = 1'-0"
10 WINDOW BASE
SCALE:
SECTION DETAIL
3" = 1'-0"
42 WAITING ROOM AT SIDE OF CASED OPENING
SCALE:
SECTION DETAIL
3" = 1'-0"
41 WAITING ROOM AT SIDE OF DOOR
SCALE:
SECTION DETAIL
3" = 1'-0"34 WAITING ROOM AT TOP OF CASED OPENING
SCALE:
SECTION DETAIL
3" = 1'-0"
40 WAITING ROOM AT TOP OF DOOR
SCALE:
SECTION DETAIL
3" = 1'-0"31 WINDOW HEAD
SCALE:
SECTION DETAIL
3" = 1'-0"30 WINDOW CASING
SCALE:
SECTION DETAIL
3" = 1'-0"33 WAITING ROOM IN BETWEEN WINDOWS AND CASED OPENING
SCALE:
SECTION DETAIL
3" = 1'-0"32 WAITING ROOM IN BETWEEN WINDOWS AND DOOR
SCALE:
SECTION DETAIL
3" = 1'-0"
20 WINDOW JAMB
Issuance Schedule
Number Date Description
20
A9.60
2" RADIUS OUTSIDE CORNERS, TYP.7'-5"EQEQEQACRYLIC COUNTERTOP
ALIGN
SLIDING GLAZED PANEL W/
RECESSED GUIDE/CHANNEL
CR LAWRENCE CRL 50 S2
FIXED GLAZED PANEL
SLIDING GLAZED PANEL W/
RECESSED GUIDE/CHANNEL
CR LAWRENCE CRL 50 S2
CL
CL 3 1/2"3 1/2"4'-1"
ACRYLIC COUNTERTOP SEAM
ACRYLIC COUNTERTOP SEAM
HARDWOOD FRAME, TYP.
TYP.
1/2"3' - 3 1/2"1' - 1 1/4"2' - 9"
10 1/2"2' - 6"23
A9.60
3'-10"
6"4"21
A9.60
31
A9.60
32
A9.60
31
A9.50
3/4" HARDWOOD PANEL1' - 1 1/4"EQ EQ EQCLCL
7'-0 1/2"
4"1'-4 1/2"
9'-0"
22
A9.60
30
A9.60
3/4" HARDWOOD PANEL
3/4" HARDWOOD PANEL
1/4" REVEAL 1/4" REVEAL
3 1/2"3 1/2"
1" ACRYLIC COUNTERTOP WITH 1"
PLYWOOD SUBSTRATE
EASED EDGE, TYP
SUPPORT BRACKETS
SCHEDULED WALL BASE
SCHEDULED PARTITION
CHAMFER PLYWOOD, PAINT SEMIGLOSS WHITE
FLUSH MOUNTED SUPPORT
BRACKETS
BLOCKING, TYP.
ATTACH FLUSH MOUNTED
SUPPORT BRACKET TO IN WALL
SOLID BLOCKING
SUB WAITING
G-119
LIAISON
G-114C
4'-1"2'-6"3/4" HARDWOOD PANEL ON Z-
CLIPS
3/4" THICK HARDWOOD WALL
BASE, TYP.
SCHEDULED PARTITION
RECESSED ALUMINUM CHANNEL
EASED EDGE, TYP.
1/4" CAULK JOINT, TYP.
5/8" GYPSUM WALL BOARD
1" ACRYLIC COUNTERTOP WITH 1"
PLYWOOD SUBSTRATE
CL
4"
6 1/4"
CHAMFER PLYWOOD, PAINT SEMIGLOSS
3/4" THICK HARDWOOD WALL
4"SUB WAITING
G-119
1/4" WOOD REVEAL
11 1/4"5"BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
SUB WAITING
G-119
CL
9 1/2" 2 1/2"7"LIAISON
G-114C
BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
1/4" WOOD REVEAL
1/4" PLYWOOD FILLER6"SCHEDULED CEILING
4"1'-0"
1/4" WOOD REVEAL
1/2" PLYWOOD FILLER5"2 1/2"2 1/2"6" 3/4"
1/4" CAULK JOINT, TYP.
SCHEDULED PARTITION
SUB WAITING
G-119
BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
CL
2 1/2"2 1/2"
5"3/4"SUB WAITING
G-119
7"BLOCKING, TYP.
1/2" TEMPERED GLAZING
GLAZING
HARDWOOD SILL AND WINDOW STOP
3/4" HARDWOOD
1/4" WOOD REVEAL
1/2" PLYWOOD FILLER
HARDWOOD SILL AND WINDOW
STOP
3/4" HARDWOOD
1/4" CAULK JOINT, TYP.
SCHEDULED PARTITION
CL
1'-4 1/2"
1/2" TEMPERED GLAZING
EXISTING COLUMN
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
As indicated
8/15/2016 9:48:13 AMA9.60
185-01-00
8/15/16
LIAISON DESK DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
10 LIAISON DESK CALLOUT
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
11 LIAISON DESK ELEVATION A
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
12 LIAISON DESK ELEVATION D
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"
20 LIAISON DESK COUNTERTOP SECTION
SCALE:
SECTION DETAIL
3" = 1'-0"
23 LIAISON DESK COUNTERTOP DETAIL
SCALE:
SECTION DETAIL
3" = 1'-0"
31 LIAISON DESK WINDOW CORNER
SCALE:
SECTION DETAIL
3" = 1'-0"
22 LIAISON DESK IN BETWEEN WINDOWS
SCALE:
SECTION DETAIL
3" = 1'-0"
21 LIAISON DESK TO WALL
SCALE:
SECTION DETAIL
3" = 1'-0"
32 LIAISON DESK IN BETWEEN WINDOWS
SCALE:
SECTION DETAIL
3" = 1'-0"
30 LIAISON DESK WINDOW TO SIDE WALL
Issuance Schedule
Number Date Description
7 8
910
1112131415
16
18 19 20 21 22
23
25
26
27
28
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELL
PURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
SUB WAITING
G-119
LIAISON
G-114C
CORRIDOR
G-119B
SUB WAITING
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
1/4" = 1'-0"8/15/2016 9:48:14 AMA10.00
185-01-00
8/15/16
FF&E PLAN AND SCHEDULES
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
EQUIPMENT SCHEDULE
MARK DESCRIPTION FURNISHED BY INSTALLED BY PLUMBING POWER T / D COMMENTS
5 MP MONITOR STAND 5 MP MONITOR STAND OWNER OWNER YES YES
5 MP MONITOR STAND FROM STEREOTATIC 5 MPG MONITOR STAND FROM STEREOTATIC OWNER OWNER YES YES ONLY 1 5MP MONITOR EXISTS, TO BE MOVED FROM STEREOTACTIC
AQUISITION WORKSTATION SELENIA AWS 800 OWNER VENDOR YES YES
BACKERBOARD BACKERBOARD OWNER OWNER
BIOPSY TABLE MULTICARE PLATINUM OWNER VENDOR YES YES
BLACK BOX 18 GALLON RCRA CONTAINER OWNER OWNER
BONE DENSITY TABLE HOLOGIC DISCOVERY TABLE OWNER VENDOR YES YES
BONE DENSITY WORKSTATION/CART HOLOGIC EXPLORER OWNER VENDOR YES YES
C-ARM SELENIA DIMENSIONS OWNER VENDOR YES YES
COAT HOOKS 4 COAT HOOKS OWNER OWNER
CODE CART CODE CART OWNER OWNER YES
COMPUTER HOSPITAL COMPUTER OWNER OWNER YES YES
COPIER COPIER OWNER OWNER YES YES
CPU CPU OWNER OWNER YES
DEFIBRILLATOR DEFIBRILLATOR OWNER OWNER YES
EXAM LIGHT, CEILING MOUNTED EXAM LIGHT OWNER OWNER YES REQUIRES JUNCTION BOX ABOVE CEILING
EXAM TABLE EXAM TABLE OWNER OWNER
FILM COPIER FILM COPIER OWNER OWNER YES YES
GLOVES TRIPLE WIRE GLOVE BOX HOLDER OWNER OWNER
ICE ICE MACHINE OWNER GENERAL CONTRACTOR YES YES
KEURIG KEURIG OWNER OWNER YES
LARGE BIOPSY CHAIR LARGE BIOPSY CHAIR OWNER OWNER
METRO RACK 4' METRO WIRE SHELVING OWNER OWNER
MIRCROWAVE MICROWAVE OWNER OWNER YES
MIRROR, TALL FULL LENGTH OWNER OWNER
PAPER PAPER TOWEL DISPENSER OWNER OWNER
PHONE OWNER OWNER
PRINTER PRINTER OWNER OWNER YES YES
PRINTER, SM PRINTER SMALL OWNER OWNER YES YES
PURELL HAND SANITIZER OWNER OWNER
RECYCLE DESKSIDE RECYCLING CONTAINER OWNER OWNER
RED BOX 18 GALLON PGII SHARPS CONTAINER OWNER OWNER
REFRIGERATOR REFRIDGERTAOR OWNER OWNER YES
SCALE SCALE OWNER OWNER
SCANNER SCANNER OWNER OWNER YES
SET UP TRAY SET UP TRAY OWNER OWNER
SHARPS SHARP3, 3 GAL OWNER OWNER
SOAP SOAP DISPENSER OWNER OWNER
SOILED LINEN BIN SOILED LINEN BIN OWNER OWNER
SOILED LINEN HAMPER SOILED LINEN HAMPER OWNER OWNER
STABLERISE STABLERISE OWNER OWNER
STADIOMETER STADIOMETER OWNER OWNER
STANDING WATER COOLER STANDING WATER COOLER OWNER GENERAL CONTRACTOR YES YES
STEREO GENERATOR STEREO GENERATOR OWNER VENDOR YES YES
STEREO MONITOR STAND MULTI PLATINUM DSM CART OWNER VENDOR YES YES
STERILE SUPPLY CART MULTICARE PLATNIUM ACCESSORY CART OWNER VENDOR
STRETCHER STRETCHER OWNER OWNER
SUCTION DEVICE SUCTION DEVICE OWNER VENDOR YES
TOILET PAPER TOILET PAPER DISPENSER OWNER OWNER
TRASH TRASH OWNER OWNER
TRAY RACK METRO TRAY RACK STORAGE OWNER OWNER
UC FRIDGE UNDERCOUNTER REFRIGERATOR OWNER OWNER YES
ULTRASOUND EQUIPMENT PHILIPS IU22 ULTRASOUND OWNER VENDOR YES YES
WALL MOUNTED PADDLES WALL MOUNTED PADDLES OWNER OWNER
WASTEBASKET WASTEBASKET OWNER OWNER
WATER WATER DISPENSER OWNER GENERAL CONTRACTOR YES YES
WHEELCHAIR WHEELCHAIR OWNER OWNER
WOW WORK STATION ON WHEELS OWNER OWNER YES YES
FURNITURE SCHEDULE
NEW / EXISTING MARK
NEW COFFEE TABLE
NEW DESK
NEW GUEST CHAIR
NEW LOUNGE CHAIR
NEW MOBILE PED
EXISTING RADIOLOGIST WORKSTATION (EXISTING)
NEW ROUND TABLE WITH 4 CHAIRS
NEW SETTEE
NEW SIDE TABLE
NEW SIDE TABLE - SMALL
NEW TASK CHAIR
EXISTING TASK CHAIR (EXISTING)
NEW TASK CHAIR WITHOUT ARMS
PHONE
Issuance Schedule
Number Date Description
1 7/8/2016 ADDENDUM 1
(VIF)1'-8" +/-(VIF)
2'-10" +/-
NEW SAWCUT OPENING IN
12"+/- (VIF) CONC SLAB BEAM -
SEE NOTE #6
NEW SAWCUT OPENING IN EXIST
6"+/- (VIF) CONC SLAB -
PROTECT EXIST WALL TO REMAIN
EXIST CONC FDN
WALL (TYP)
EXIST CONC
COL (TYP)
NEW SAWCUT OPENING IN
EXIST 6"+/- (VIF) CONC SLAB
(VIF)
2'-0" +/-(VIF)1'-6" +/-20 21 22
17
25
16
11121314
910
INFILL EXIST SLAB
OPENING (VIF) -
SEE "3/S2.00"
INFILL EXIST SLAB
OPENING (VIF) -
SEE "3/S2.00"
..*
*
....
*
*
*
*
3'-0" (MIN)
CORES IN EXIST 12"+/-
SLAB FOR MEP
ALTERNATE #2 -
SEE NOTE #5
EXIST CONC COL (VIF)
EXIST 12"+/- CONC
SLAB BEAM (VIF)
(VIF)
1'-6 1/2"+/-
EXIST SLAB
PENETRATION (VIF)
ALIGN
EXIST 12"+/- CONC
SLAB BEAM (VIF)1'-6" (MIN)2'-6" (MIN)
1'-6" (MIN)
EXIST CONC BEAM
LIGHT SUPPORT -
COORD W/ARCH DWGS
1
S2.00
# NUMBER OR POUND
& AND
@ AT
ARCH ARCHITECTURAL/ARCHITECT
B/S BOTH SIDES
BLDG BUILDING
BM BEAM
BOT BOTTOM
C CHANNEL
CANT CANTILEVER
CFMF COLD-FORMED METAL FRAMING
CJ CONTROL JOINT
CL CENTER LINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DWGS DRAWINGS
EA EACH
EF EACH FACE
EL ELEVATION
ELEC ELECTRICAL
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EX EXISTING
EXT EXTERIOR
FDN FOUNDATION
FF FINISHED FLOOR
FT FOOT/FEET
GR GRADE
IN INCH(ES)
INT INTERIOR
STRUCTURAL ABBREVIATIONS
K KIP(S)
L ANGLE
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NTS NOT TO SCALE
O/C ON CENTER
OF OUTSIDE FACE
OH OPPOSITE HAND
OPP OPPOSITE
PAF POWDER ACTUATED FASTENER
PEN PENETRATION
PIA POST-INSTALLED ANCHOR
PL PLATE
QTY QUANTITY
REINF REINFORCEMENT
REQ'D REQUIRED
SF SQUARE FOOT
SIM SIMILAR
SL SLOPE
SOG SLAB ON GRADE
SPEC SPECIFICATION
STR STRUCTURAL
T&B TOP AND BOTTOM
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
WWF WELDED WIRE FABRIC
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085
As indicated
8/15/2016 3:40:44 PMS1.00
185-01-00
8/15/16
GENERAL NOTES, GROUND
FLOOR PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
1. WITHIN (2)-WEEKS OF MOBILIZING TO SITE, AND PRIOR TO THE BEGINNING OF ANY FABRICATION, CONTRACTOR SHALL VERIFY ALL
REQUIRED EXISTING CONDITIONS IN THE FIELD. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY OF ANY DESCREPENCIES FOUND.
ALLOW (2)-WEEKS FOR REVIEW BY DESIGN TEAM TO ADJUST DESIGN AS REQUIRED.
2. CONTRACTOR TO COORDINATE SIZE AND LOCATION OF ALL OPENINGS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL AND
PLUMBING DRAWINGS AND MEP CONTRACTORS.
3. CONTRACTOR PERFORMING STRUCTURAL WORK SHALL BE RESPONSIBLE FOR ALL SHORING OF EXISTING CONSTRUCTION
REQUIRED TO SAFELY COMPLETE WORK.
4. IF EXISTING SLAB OPENINGS NOT SHOWN ON THESE DOCUMENTS ARE FIELD VERIFIED TO BE PRESENT IN THE VISCINITY OF
PROPOSED NEW SLAB OPENINGS, CONTACT ENGINEER IMMEDIATELY FOR REVIEW OF AS-BUILT CONDITIONS.
5. CONTRACTOR SHALL FIELD VERIFY LOCATION OF EXISTING TOP AND BOTTOM SLAB REINFORCING USING NON-DESTRUCTIVE TEST
METHODS. NEW CORES SHALL NOT CUT THROUGH ANY TOP OR BOTTOM EXISTING SLAB BEAM REINFORCING. CORES SHALL BE
LOCATED A MINIMUM OF 12" FROM THE FACE OF THE EXISTING CONCRETE COLUMN. PROVIDE 3" CLEAR MINIMUM BETWEEN
ADJACENT CORES. COORDINATE SIZE AND LOCATION WITH MEP DRAWINGS AND MEP CONTRACTORS.
6. CONTRACTOR SHALL FIELD VERIFY LOCATION OF EXISTING BOTTOM CONCRETE SLAB BEAM REINFORCING USING
NON-DESTRUCTIVE TEST METHODS. NEW OPENING SHALL ONLY INTERUPT (1)-EXISTING REINFORCING BAR MAXIMUM. EXISTING
STRUCTURAL DRAWINGS INDICATE SLAB BEAM IS REINFORCED WITH (9)-CONTINUOUS BOTTOM BARS. NOTIFY ENGINEER IMMEDIATE
IF ANY DISCREPENCIES ARE NOTED.
7. INDICATES COORDINATE FINAL DIMENSION WITH MEP DRAWINGS AND MEP CONTRACTORS.
1/4" = 1'-0"
GROUND FLOOR PLAN
STRUCTURAL GENERAL NOTES
GENERAL
1. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS AND DETAILS.
2. STRUCTURAL CONDITIONS WHERE SECTIONS OR DETAILS ARE CUT SHALL ALSO APPLY TO COMPARABLE SIMILAR
LOCATIONS ELSEWHERE ON THE PLANS REGARDLESS IF THE SECTION MARK IS NOT INDICATED. DETAILS SHOWN
APPLY TO ALL SIMILAR CONDITIONS UNLESS OTHERWISE NOTED. DO NOT SCALE DRAWINGS.
3. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ELEVATIONS, QUANTITIES, ETC., IN THE
FIELD PRIOR TO BEGINNING OF ANY NEW CONSTRUCTION. NOTIFY ENGINEER/ARCHITECT OF ANY
DISCREPANCIES FOUND IMMEDIATELY.
4. CONTRACTOR SHALL VERIFY AND COORDINATE THE DIMENSIONS, LAYOUT AND DETAILS OF ALL OPENINGS,
PENETRATIONS, ETC. CONTRACTOR SHALL REVIEW ALL OF THE CONTRACT DOCUMENTS AND CONSULT WITH THE
SUBCONTRACTORS AND SUPPLIERS TO OBTAIN THE REQUIRED INFORMATION. OPENINGS, PENETRATIONS, ETC.
THAT VARY FROM OR HAVE NOT BEEN INDICATED ON THE STRUCTURAL DOCUMENTS, SHALL BE INSTALLED AT NO
ADDITIONAL COST, ONLY AFTER APPROVAL BY THE STRUCTURAL ENGINEER HAS BEEN OBTAINED.CODES
1. ALLOWABLE UNIT STRESSES AND DESIGN CRITERIA IN ACCORDANCE WITH THE FOLLOWING -
A) 'THE 2009 INTERNATIONAL BUILDING CODE' WITH THE '2010 STATE OF MASSACHUSETTS AMENDMENT'.
B) 'MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES', ASCE/SEI 7-05.
C) 'SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS-', AISC 360-05
D) 'BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE', ACI 318-08.
DESIGN CRITERIA
1. WELDED WIRE FABRIC ASTM A 185 Fy=60 KSI
2. REINFORCING STEEL ASTM A 615 GRADE 60, Fy=60 KSI
3. CONCRETE FOR SLAB INFILLS f'c=4,000 PSI (UNLESS
OTHERWISE NOTED)
CONCRETE
21. TEST SLUMP IN ACCORDANCE WITH ASTM C 143. ONE TEST SHALL BE PERFORMED FOR EACH
COMPOSITE SAMPLE, BUT NOT LESS THAN ONE TEST FOR EACH DAY'S POUR OF EACH CONCRETE
MIXTURE.
22. TEST AIR CONTENT IN ACCORDANCE WITH ASTM C 231. ONE TEST SHALL BE PERFORMED FOR EACH
COMPOSITE SAMPLE, BUT NOT LESS THAN ONE TEST FOR EACH DAY'S POUR OF EACH CONCRETE
MIXTURE.
23. TEST CONCRETE TEMPERATURE IN ACCORDANCE WITH ASTM C 1064. ONE TEST SHALL BE
PERFORMED FOR EACH COMPOSITE SAMPLE, AND ONE TEST SHALL BE PERFORMED HOURLY WHEN
AIR TEMPERATURE IS 40 DEGREES F AND BELOW AND WHEN 80 DEGREES F AND ABOVE.
24. CONCRETE COMPRESSIVE TEST SPECIMENS SHALL BE TAKEN IN ACCORDANCE WITH ASTM C 31.
- CAST AND LABORATORY CURE ONE SET OF FOUR STANDARD CYLINDER SPECIMENS FOR EACH
COMPOSITE SAMPLE.
25. COMPRESSIVE-STRENGTH TESTS: ASTM C 39; TEST ONE SPECIMEN AT 7 DAYS AND TWO SPECIMENS
AT 28 DAYS, AND ONE SPECIMEN RETAINED IN RESERVE FOR THE LATER TESTING IF REQUIRED.
- STRENGTH OF EACH CONCRETE MIXTURE WILL BE CONSIDERED SATISFACTORY IF EVERY AVERAGE
OF ANY THREE CONSECUTIVE COMPRESSIVE-STRENGTH TESTS EQUALS OR EXCEEDS SPECIFIED
COMPRESSIVE STRENGTH AND NO COMPRESSIVE-STRENGTH TEST VALUE FALLS BELOW SPECIFIED
COMPRESSIVE STRENGTH BY MORE THAN 500 PSI.
- TEST RESULTS SHALL BE REPORTED IN WRITING TO THE STRUCTURAL ENGINEER, CONTRACTORS,
ARCHITECT, AND CONCRETE MANUFACTURER WITHIN 24 HOURS OF TESTING.
- ADDITIONAL TESTING AND INSPECTING, AT THE CONTRACTOR'S EXPENSE, WILL BE PERFORMED AT
THE ENGINEER'S DIRECTION IF WORK IS FOUND TO BE NOT IN COMFORMANCE WITH PROJECT
REQUIREMENTS.
CONCRETE
1. ALL CONCRETE REINFORCING SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED AND SPACED
IN FORMS AND SECURED IN PLACE IN ACCORDANCE WITH ACI PROCEDURES AND THE REQUIREMENTS
OF THE CODES IN THE PREVIOUSLY OUTLINED "CODES" SECTION AND THE 'MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES', ACI-315.
2. CHECKED SHOP DRAWINGS SHOWING REINFORCING DETAILS, INCLUDING CONSTRUCTION JOINTS,
OPENINGS, REINFORCING SIZES, SPACING AND PLACEMENT SHALL BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION. UNCHECKED SHOP DRAWINGS WILL BE
REJECTED WITHOUT REVIEW.
3. ALL WELDED WIRE FABRIC SHALL BE LAPPED TWO (2)-FULL MESH PANELS AND TIED SECURELY.
4. NO CALCIUM CHLORIDE SHALL BE USED IN ANY CONCRETE.
5. SUBMIT THE FOLLOWING:
- PRODUCT DATA FOR EACH PRODUCT INDICATED INCLUDING REINFORCEMENT, ADMIXTURES, AND
OTHERS IF REQUESTED BY THE ENGINEER.
- CONCRETE DESIGN MIXTURES FOR EACH CONCRETE MIXTURE USED.
- LABORATORY TEST REPORTS FOR CONCRETE MATERIALS AND MIX DESIGN TESTS.
- A WRITTEN DESCRIPTION OF CURING PROCEDURES FOR REVIEW AND APPROVAL A MINIMUM OF 15
DAYS PRIOR TO START OF WORK. DESCRIPTION TO INCLUDE CURING METHODS AND DURATION OF
CURING.
- STEEL REINFORCEMENT SHOP DRAWINGS: DRAWINGS THAT CLEARLY SHOW LOCATION, SPLICING,
COVER, SIZES AND SPACING OF ALL REINFORCING AND WIRE FABRIC. SCHEDULES AND DIAGRAMS
SHALL INDICATE BENDS, SIZES, LENGTHS OF REINFORCING MEMBERS AND SPLICE LENGTHS. INCLUDE
ANY SUPPLEMENT REINFORCEMENT REQUIRED INCLUDING BUT NOT LIMITED TO SLAB EDGE
REINFORCING, CORNER BARS, RE-ENTRY BARS AND SLAB OPENINGS.
- MATERIAL CERTIFICATES FOR CEMENTITIOUS MATERIALS, ADMIXTURES, STEEL REINFORCMENT AND
ACCESSORIES, AND MOISTURE VAPOR REDUCING ADMIXTURE (MVRA)
- NO REINFORCING SHALL BE CUT, FABRICATED, SHIPPED TO THE JOB SITE OR PLACED BEFORE SHOP
DRAWINGS HAVE BEEN APPROVED BY THE ENGINEER OF RECORD. ONLY SHOP DRAWINGS BEARING
THE APPROPRIATE ENGINEER'S STAMP MARKED "FURNISH AS SUBMITTED" OR "FURNISHED AS
CORRECTED" OR "FURNISHED AS CORRECTED AND RESUBMIT FOR RECORD" SHALL BE USED IN FIELD.
6. STRUCTURAL SLABS AND SLABS ON DECK SHALL NOT CONTAIN ANY ELECTRICAL CONDUITS OR
PIPING.
7. CONCRETE FOR SLAB INFILLS TO BE NORMAL WEIGHT CONCRETE WITH A 4,000PSI 28-DAY MINIMUM
COMPRESSIVE STENGTH, MINIMUM CEMENT CONTENT OF 6 SACKS PER CUBIC YARD, WATER-CEMENT
RATIO 0.45 MAXIMUM (WATER CONTENT SHALL INCLUDE SURFACE WATER IN AGGREGATES), MAXIMUM
3/4" AGGREGATE, FOUR PLUS OR MINUS 1 INCH SLUMP. NO ADDITIONAL AIR ENTRAINMENT IS TO BE
PROVIDED AT INTERIOR SLABS. PROVIDE MOISTURE VAPOR REDUCING ADMIXTURE (MVRA) IN ALL
INTERIOR SLABS. IF MIX IS TO BE PUMPED, ALLOWED SLUMP CAN BE INCREASED TO SIX PLUS OR
MINUS ONE INCH. SUBMIT SEPARATE MIX DESIGNS,INCLUDING ALL BACKUP DATA, FOR EACH PUMP
MIX FOR APPROVAL BY THE ENGINEER
8. ADJUSTMENTS TO CONCRETE MIXES: FIELD WATER IS NOT TO BE ADDED. MIX DESIGN ADJUSTMENTS
MAY BE REQUESTED BY THE CONTRACTOR WHEN CHARACTERISTICS OF MATERIALS, JOB
CONDITIONS, TEST RESULTS OR OTHER CIRCUMSTANCES WARRANT, AS ACCEPTED BY THE
ENGINEER. LABORATORY TEST DATA FOR REVISED MIX DESIGN AND STRENGTH RESULTS MUST BE
SUBMITTED TO AND ACCEPTED BY THE ENGINEER BEFORE USING IN WORK.
9. DO NOT AIR ENTRAIN CONCRETE AT INTERIOR SLABS. DO NOT ALLOW ENTRAPPED AIR CONTENT TO
EXCEED 3 PERCENT.
10. USE FLY ASH, POZZOLAN, GROUND GRANULATED BLAST-FURNACE SLAG AND SILICA FUME AS
NEEDED TO REDUCE THE TOTAL AMOUNT OF PORTLAND CEMENT WHICH WOULD OTHERWISE BE
USED, BY NOT LESS THAN 40 PERCENT.
11. USE ADMIXTURES ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS. ADMIXTURES ARE NOT
TO BE ADDED IN THE FIELD. FIELD WATER IS NOT BE TO ADDED.
12. CHEMICAL ADMIXTURES: PROVIDE ADMIXTURES CERTIFIED BY MANUFACTURER TO BE COMPATIBLE
WITH OTHER ADMIXTURES AND THAT WILL NOT CONTRIBUTE WATER-SOLUBLE CHLORIDE IONS
EXCEEDING 0.15 PERCENT BY MASS OF CEMENT MATERIAL. DO NOT USE CALCIUM CHLORIDE OR
ADMIXTURES CONTAINING CALCIUM CHLORIDE.
13. ADMIXTURES SHALL CONFORM TO THE FOLLOWING: WATER REDUCING ADMIXTURE: ASTM C 494/C
494M, TYPE A, RETARDING ADMIXTURE: ASTM C 494/C 494M, TYPE B, WATER-REDUCING AND
RETARDING ADMIXTURE: ASTM C 494/C 494M, TYPE D, MOISTURE VAPOR REDUCTION ADMIXTURE
(MVRA): ASTM C 494/C494M, TYPE S
14. CONCRETE MOISTURE VAPOR REDUCTION ADMIXTURE (MVRA): CONCRETE MOISTURE VAPOR
REDUCTION ADMIXTURE, PROVIDED FOR ALL INTERIOR SLABS SHALL BE A NON-TOXIC, LIQUID
ADMIXTURE THAT IS SPECIFICALLY DESIGNED TO HAVE A NATURAL CHEMICAL REACTION WITH
PRE-EXISTING ELEMENTS INSIDE THE CONCRETE ELEMENTS TO ELIMINATE THE ROUTE OF MOISTURE
VAPOR EMISSION THROUGH THE SLAB BY RESTRICTING THE INTEGRAL CAPILLARY SYSTEM. THE
CHEMICAL REACTION FORMS A PERMANENT BARRIER (CAPILLARY BREAK) THAT IS INTEGRAL TO THE
CONCRETE, INSOLUBLE AND IRREMOVABLE.
- BASIS-OF-DESIGN PRODUCT: "BARRIER ONE HIGH PERFORMANCE CONCRETE ADMIXTURE"
MANUFACTURED BY BARRIER ONE, INC.; 522 S. HUNT CLUB BLVD., #303, APOPKA, FL 32703. CONTACT
MANUFACTURER'S REPRESENTATIVE: P: 877.224.5850; F: 866.594.3490 OR EMAIL AT
INFO@BARRIERONE.COM.
- PROVIDE THE ABOVE NAMED PRODUCT, OR UPON APPROVAL OF THE ARCHITECT / STRUCTURAL
ENGINEER, PROVIDE A PRODUCT THAT MEETS OR EXCEEDS THE FOLLOWING PROJECT SPECIFIC
PERFORMANCE REQUIREMENTS AT THE EXPENSE OF THE CONCRETE MOISTURE VAPOR REDUCTION
ADMIXTURE MANUFACTURER. PERFORMANCE REQUIREMENTS INCLUDE BUT ARE NOT LIMITED TO:
INDEPENDENT PROCUREMENT OF ONE CYLINDER PER DAY OF PLACEMENT OF CONCRETE
CONTAINING MVRA; DO NOT PROCEED WITHOUT MVRA REPRESENTATIVE BEING PRESENT,
INDEPENDENT TESTING OF ALL CYLINDERS FOR HYDRAULIC CONDUCTIVITY PER ASTM D5084 AND
ASSESSING EACH CYLINDER FOR MAXIMUM FLOW OF 6.0 E-08 CM/SEC. SHOULD ANY CYLINDER
EXCEED MAXIMUM FLOW, PROCURE A CORE FROM THAT DAYS PLACEMENT AND TEST CORE FOR
HYDROLIC CONDUCTIVITY PER ASTM D5084. SHOULD ANY CORE EXCEED THE MAXIMUM FLOW,
PROVIDE A TOPICAL MOISTURE MITIGATION SYSTEM FOR ALL AREAS NOT MEETING THE STATED LIMIT.
MOISTURE MIGITATION SYSTEM TO INCLUDE ALL LABOR, MATERIAL AND WARRANTY THAT MEETS OR
EXCEEDS THE TERMS OF THE CONCRETE MOISTURE VAPOR REDUCTION ADMIXTURE
MANUFACTURER'S WARRANTY. ADDITIONALLY MVRA MANUFACTURER'S WARRANTY SHALL INCLUDE:
A TERM OF THE LIFE OF THE CONCRETE, REPAIR AND/OR REMOVAL OF FAILED FLOORING,
PLACEMENT OF A TOPICAL MOISTURE REMEDIATION SYSTEM AND REPLACEMENT OF FLOORING
MATERIALS LIKE THE ORIGINAL INSTALLED TO INCLUDE MATERIAL AND LABOR. MVRA MANUFACTURER
SHALL ALSO PROVIDE AN ADHESION WARRANTY TO MATCH THE TERM OF THE ADHESIVE
MANUFACTURER'S WARRANTY IN ACCORDANCE WITH THE MVRA MANUFACTURER'S REQUIREMENTS
FOR CONVEYANCE OF SUCH.
15. COLD WEATHER PLACEMENT: COMPLY WITH ALL REQUIREMENTS OF ACI306.1. PROTECT CONCRETE
FROM PHYSICAL DAMAGE OR REDUCED STRENGTH THAT COULD BE CAUSED BY FROST, FREEZING
ACTIONS, OR LOW TEMPERATURES. WHEN THE AVERAGE HIGH AND LOW TEMPERATURE IS EXPECTED
TO FALL BELOW 40 DEGREES F FOR THREE SUCCESSIVE DAYS, MAINTAIN DELIVERED CONCRETE
MIXTURE WITHIN THE TEMPERATURE RANGE REQUIRED BY ACI 301.
16. HOT WEATHER PLACEMENT: PLACE CONCRETE ACCORDING TO RECOMMENDATIONS IN ACI 305R
WHEN HOT WEATHER CONDITIONS EXIST. HOT WEATHER IS ANY COMBINATION OF HIGH AMBIENT
TEMPERATURE, HIGH CONCRETE TEMPERATURE, LOW RELATIVE HUMIDITY, WIND SPEED, OR SOLAR
RADIATION THAT WILL IMPACT THE QUALITY OF FRESHLY MIXED OR HARDENED CONCRETE. COOL
INGREDIENTS BEFORE MIXING TO MAINTAIN CONCRETE TEMPERATURE BELOW 90 DEGREES F AT TIME
OF PLACEMENT. CHILLED MIXING WATER OR CHOPPED ICE MAY BE USED TO CONTROL
TEMPERATURE, PROVIDED WATER EQUIVALENT OF ICE IS CALCULATED TOTAL AMOUNT OF MXIING
WATER.
17. OWNER WILL ENGAGE A SPECIAL INSPECTOR AND QUALIFIED TESTING AND INSPECTING AGENCY TO
PERFORM FIELD TESTS AND INSPECTIONS AND PREPARE TEST REPORTS.
18. CONCRETE TESTS: TESTING OF COMPOSITE SAMPLES OF FRESH CONCRETE OBTAINED ACCORDING
TO ASTM C172 SHALL BE PERFORMED ACCORDING TO THE FOLLOWING REQUIREMENTS.
19. OBTAIN ONE COMPOSITE SAMPLE FOR EACH DAY'S POUR OF CONCRETE, PLUS ONE SET FOR EACH
ADDITIONAL 50 CUBIC YARDS OR FRACTION THEREOF. CONTRACTOR SHALL NOTIFY THE OWNER'S
INSPECTION AGENCY 24 HOURS PRIOR TO PLACING CONCRETE TO INSPECT SECURED REINFORCING.
NO CONCRETE SHALL BE PLACED UNTIL REINFORCING HAS BEEN INSPECTED BY THE OWNER'S
TESTING AND INSPECTION AGENCY.
20. WHEN CONCRETE IS PUMPED, TEST CYLINDERS SHALL BE MADE FROM CONCRETE TAKEN AT
DISCHARGE END OF THE PUMPING TRAIN.
POST INSTALLED ANCHORS (PIA)
1. POST INSTALLED ADHESIVE ANCHORS SHALL BE INSTALLED USING HILTI RE-500SD OR
APPROVED EQUAL.
2. ALL POST INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
3. TESTING AGENCY SHALL RANDOMLY REVIEW ANCHORING INSTALLATION TO VERIFY
CONFORMANCE WITH CONTRACT DOCUMENTS AND MANUFACTURER'S INSTALLATION
REQUIREMENTS. INITIAL INSPECTIONS SHALL OCCUR AT FIRST APPLICATION FOR EACH
TYPE OF ANCHOR TO VERIFY CONFORMANCE. THE NUMBER OF POST INSTALLED
ANCHOR INSTALLATIONS TO BE WITNESSED BY THE OWNER'S TESTING AGENCY SHALL
MEET THE FOLLOWING CRITERIA:
3a. A MINIMUM OF 25% OF ADHESIVE ANCHOR INSTALLATIONS PER SUB CONTRACTOR SHALL
BE WITNESSED. THE PERCENTAGE WITNESSED MAY BE MODIFIED BY THE STRUCTURAL
ENGINEER OF RECORD, DEPENDING UPON INITIAL RESULTS.
4. LOAD TESTING OF POST INSTALLED ANCHORS MAY BE REQUESTED BY THE STRUCTURAL
ENGINEER OF RECORD FOLLOWING THE RESULT OF THE TESTING AGENCY'S
INSTALLATION REPORTS. LOAD TESTING SHALL BE PERFORMED AT NO ADDITIONAL COST
TO THE OWNER.
*
STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE
REFERENCED EDITION OF THE AISC 'SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS'.
2. ALL WELDING ELECTRODES SHALL BE E70XX UNLESS OTHERWISE NOTED.
3. ALL BOLTS, NUTS AND WASHERS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A 325 OR
ASTM A 490.
4. ALL WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM TO AWS 'CODE OF ARC
AND GAS WELDING IN BUILDING CONSTRUCTION', LATEST EDITION.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ERECTION PROCEDURES AND SEQUENCES
INCLUDING TEMPORARY BRACING AND SHORING.
6. THERE SHALL BE NO FIELD CUTTING OF STRUCTURAL STEEL MEMBERS WITHOUT THE PRIOR
APPROVAL OF THE ENGINEER.
7. ANY ADDITIONAL STEEL REQUIRED BY THE CONTRACTOR FOR ERECTION PURPOSES AND SITE
ACCESS OR MATERIALS FOR STOCKPILING STEEL SHALL BE PROVIDED AT NO COST TO THE
OWNER. ALL SUCH ADDITIONAL STEEL SHALL BE REMOVED BY THE CONTRACTOR UNLESS
APPROVED BY THE OWNER IN WRITING.
8. ALL FIELD WELDS SHALL BE SCRAPED AND CLEANED FREE OF SLAG BY WELDER/ERECTOR TO
ENABLE VISUAL WELD INSPECTION.
STRUCTURAL DRAWING LIST
S1.00 GENERAL NOTES, GROUND FLOOR PLAN
S2.00 FRAMING DETAILS
Grand total: 2
Issuance Schedule
Number Date Description
1/2" STEEL STIFFENER
PLATE -
SEE "A/S2.00"
EXIST CONC
SLAB (VIF)
LIGHT ASSEMBLY BY
LIGHT CONTRACTOR
(4)-1/2" DIA A36
THREADED RODS
FOR CEILING -
SEE ARCH DWGS
POWER BOX BY
LIGHT CONTRACTOR
NOTES:
1. INDICATES COORDINATE FINAL DIMENSION WITH EQUIPMENT SUPPLIER/CONTRACTOR AND ARCHITECT.
2. CONTRACTORS OPTION TO USE 3/4" DIA F1852 SLIP CRITICAL BOLTS IN LIEU OF FIELD WELDING.
3. CONTRACTOR TO FIELD LOCATE EXISTING SLAB REINFORCING USING NON-DESTRUCTIVE
TESTING METHODS. ADJUST LOCATION OF PIA AS REQUIRED TO AVOID DAMAGING EXISTING
SLAB REINFORCING.
4. FOR ADDITIONAL INFORMATION AND REQUIREMENTS, SEE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS AND LIGHT SUPPLIER/CONTRACTOR DOCUMENTS.6" +/-*.(VIF).*
*
(4)-L3x3x5/16 KICKERS
PROVIDE DOUBLE NUTS
TIGHTEN NUTS &
DAMAGE THREADS
1
1
CUT VERT LEG & BEND
HORIZ LEG @ STIFFENER
PLATE TO ALLOW FOR CONN
@ THREADED ROD (TYP)(VIF)6" +/-L4x4x5/16 x 0'-6" LONG
@ EA KICKER
1/4 2
TYP SEE
NOTE #2
5/8" DIA HILTI KWIK BOLT 3
EMBEDDED 4" INTO EXIST
CONC SLAB (TYP) SEE NOTE #3
5/8" DIA HILTI KWIK BOLT
3 EMBEDDED 4" INTO
EXIST CONC SLAB (TYP) -
SEE NOTE #3
L4x4x5/16 & L4x3x5/16 (LLV) x 0'-
6" LONG @ EA HANGER.
PROVIDE 1 1/2" VERT SLOTTED
HOLE IN L4x3 FOR FIELD ADJ
3/4" DIA F1852 SLIP
CRITICAL BOLT (TYP)
*
9"9"5"x5"
OPNG
NOTES:
1. COORDINATE FINAL PLATE DIMENSIONS AND
HOLE LOCATIONS WITH LIGHT CONTRACTOR.6.313".6.313".
HOLE FOR THREADED
ROD (TYP)
PROVIDE RADIUSED
CORNERS (TYP)
EXISTING CONC SLAB (VIF)
SAW CUT OPENING FROM
CORE DRILLED CORNER
HOLES AS REQ'D. NO OVER
CUTS ALLOWED (TYP)
CORE DRILL ALL NEW
OPENING CORNERS W/3"
(MIN) DIA HOLES (TYP)
NEW OPENING -
SEE PLAN & COORD
W/MEP & ARCH DWGS
NOTES:
1. COORDINATE SIZE AND LOCATION OF OPENINGS WITH MEP DRAWINGS
AND MEP CONTRACTORS.
2. CONTRACTOR TO PROTECT ALL EXISTING CONSTRUCTION TO REMAIN.
EXIST CONC SLAB (VIF)(VIF)6" +/-FORM AND SUPPORT INFILL
AS REQ'D. INFILL TO BE
SUPPORTED UNTIL
CONCRETE ATTAINS FULL
DESIGN STRENGTH.
(VIF)
EXIST SLAB OPENING
NOTES:
1. CONTRACTOR TO FIELD VERIFY SIZE OF EXISTING OPENINGS IN THE FIELD
PRIOR TO BEGINNING ANY FABRICATION.
2. IF SIZE OF OPENING TO BE INFILLED EXCEEDS 36" IN ANY DIMENSION,
NOTIFY ENGINEER IMMEDIATELY TO REVIEW CONDITION.
NEW CONC INFILL
REINFORCED W/(2)-LAYERS
OF W2.9xW2.9-6x6 WWF
(TOP & BOT)
#5 REBAR PIA x 1'-8" LONG @
6" O/C W/STD 90 DEGREE
HOOK EMBEDDED 6" INTO
EXIST CONC SLAB (TYP)CLR3/4"EQEQCLR3/4"Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
As indicated
8/15/2016 3:40:44 PMS2.00
185-01-00
8/15/16
FRAMING DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
1 1/2" = 1'-0"S2.00
1 LIGHT SUPPORT DETAIL
1 1/2" = 1'-0"S2.00
A STIFFENER PLATE DETAIL
NOT TO SCALES2.00
2 TYPICAL NEW OPENING IN EXISTING SLAB
3/4" = 1'-0"S2.00
3 TYPICAL EXISTING SLAB PENETRATION INFILL DETAIL
Issuance Schedule
Number Date Description
A GENERAL SERVICE COMPRESSED AIR
a 48" ABOVE FINISHED FLOOR
A/AMP AMPERE
AC AIR COMPRESSOR
AC ALTERNATING CURRENT
ACD AUTOMATIC COOLING CONDENSATE PUMP
ACF AIRFLOW CENTRIFUGAL FAN
ACU AIR CONDITIONING UNIT(S)
AD ACCESS DOOR
AD AREA DRAIN
AF ARC FAULT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CURRENT
AMB AMBIENT
ANN ANNUNCIATOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APD AIR PRESSURE DROP
APPROX APPROXIMATE
ARV AXIAL ROOF VENTILATOR
AS AIR SEPARATOR
ATC AUTOMATIC TEMPERATURE CONTROL
ATS AUTOMATIC TRANSFER SWITCH
AV ACID VENT (CHEMICAL)
AVG AVERAGE
AVTR ACID VENT THRU ROOF
AW ACID WASTE
AWG AMERICAN WIRE GAUGE
AWT AVERAGE WATER TEMPERATURE
b 42" ABOVE FINISHED FLOOR
BCT BONDING CONDUCTOR FOR TELECOMMUNICATIONS
BDD BACK DRAFT DAMPER
BFW BOILER FEED WATER
BHP BRAKE HORSEPOWER
BICF BACKWARD INCLINED CENTRIFUGAL FAN
BICSI BUILDING INDUSTRY CONSULTING SERVICE
INTERNATIONAL
BNC BAYONET NEIL-CONCELMAN
BSMT BASEMENT
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS/HOUR
c CEILING MOUNTED
C CONDUIT(S)
C/B CIRCUIT BREAKER
CAT CATEGORY ETHERNET CABLE
CATV COMMUNITY ANTENNA TELEVISION
CC COOLING COIL
CCTV CLOSED CIRCUIT TELEVISION
CER/CEG CEILING EXHAUST REG./GRILLE
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMPS
CHP CONSOLE HEAT PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CI CAST IRON
CKT CIRCUIT
CLG CEILING
CLGWTR COOLING WATER
CLPS CLEAN LOW PRESSURE STEAM
CMPS CLEAN MEDIUM PRESSURE STEAM
CMV CEILING MOUNTED VENTILATOR
CO CLEANOUT
CO2 CARBON DIOXIDE
COAX COAXIAL CABLING
COMP COMPRESSOR
COND CONDENSER
CONV CONVECTOR
COP COPPER CABLING
CP CONDENSATE PUMP
CPU CENTRAL PROCESSING UNIT
CRU COMPUTER ROOM UNIT
CRV CENTRIFUGAL ROOF VENTILATOR
CT CABLE TRAY
CT COOLING TOWER
CT CURRENT TRANSFORMER
CU CONDENSING UNIT
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CV COEFFICIENT, VALVE FLOW
CV CONSTANT VOLUME
CVP CEILING VIDEO PRESENTATION
CW COLD WATER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CWV CENTRIFUGAL WALL VENTILATOR
D DATA
D DEPTH
DA DISTRIBUTOR A
DB DISTRIBUTOR B
DB DRY BULB TEMPERATURE
dB DECIBEL
DC DIRECT CURRENT
DC DISTRIBUTOR C
DCV DOUBLE CHECK VALVE
DE DEIONIZED PROCESS WATER
DEG or ° DEGREE
DEMARC DEMARCATION
DET DOMESTIC EXPANSION TANK (PLUMBING)
DI DISTILLED WATER
DIA or Ø DIAMETER
DN DOWN
DP DIFFERENTIAL PRESSURE
DSA DUCT SOUND ATTENUATORS
DWBP DOMESTIC WATER BOOSTER PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EBR ELECTRIC BASEBOARD RADIATION
EDR EQUIVALENT DIRECT RADIATION
EF ENTRANCE FACILITY
EF EXHAUST FAN
EFF EFFICIENCY
EHC ELECTRICAL HEATING CABLES
EIA ELECTRONICS INDUSTRIES ALLIANCE
ELEC ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EM/NL EMERGENCY/NIGHT LIGHT WALK-THRU
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ER EQUIPMENT ROOM
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK (HVAC)
ETP ELECTRIC TRAP PRIMER
EUH ELECTRIC UNIT HEATER
EVAP EVAPORATOR
EWB ENTERING WET BULB TEMPERATURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION
F FAHRENHEIT
FA FIRE ALARM
FC FOOT CANDLE
FCCF FORWARD CURVE CENTRIFUGAL FAN
FCU FAN COIL UNIT
FD FIRE DAMPER
FD FLOOR DRAIN
FD/SB FIRE DAMPER WITH INTEGRAL SECURITY BARS
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FHC FIRE HOSE CABINET
FM FLOW METER
FMC FLEXIBLE METALLIC TUBING
FOB FLAT ON BOTTOM
FOF FUEL OIL FILL
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FLAT ON TOP
FOV FUEL OIL VENT
FP FIRE PUMP
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FT FOOT OR FEET
FVC FIRE VALVE CABINET
G GAS
GA GAUGE
GAL GALLONS
GCC GRAVITY COOLING CONDENSATE
GE GROUNDING EQUALIZER
GEC GROUNDING ELECTRODE CONDUCTOR
GF GROUND FAULT
GND GROUND
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRAINS
GRU GREASE RECOVERY UNIT
GW GREASE WASTE
GWA GREASE WASTE ABOVE GRADE
GWB GREASE WASTE BURIED
GWH GAS WATER HEATER
H HEIGHT
H/C HEATING/COOLING
HC HEATING COIL
HC HORIZONTAL CROSS-CONNECT
HD HEAD
HDCP HANDICAP
HP HORSEPOWER
HPC HIGH PRESSURE CONDENSATE
HPG HIGH PRESSURE GAS
HPS HIGH PRESSURE SODIUM
HPS HIGH PRESSURE STEAM
HR HOUR(S)
HT HEAT
HTHW HIGH TEMPERATURE HOT WATER
HTHWR HIGH TEMPERATURE HOT WATER RETURN
HTHWS HIGH TEMPERATURE HOT WATER SUPPLY
HTR HEATER
HUM HUMIDIFIER
HV HEATING/VENTILATION UNIT
HVAC HEATING, VENTILATION AND AIR CONDITIONING
HW HOT WATER
HWR HOT WATER RETURN
HWRP HOT WATER RETURN PUMP
HWRR HOT WATER REVERSE RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ FREQUENCY (CYCLES PER SECOND)
IC INTERMEDIATE CROSS-CONNECT
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IDC INSULATION DISPLACEMENT CONNECTOR
IEF IN-LINE EXHAUST FAN
IG ISOLATED GROUND
IN INCHES
IN WG INCHES OF WATER, GAUGE (PRESSURE)
IW INDIRECT WASTE
JB JUNCTION BOX
JP JOCKEY PUMP
KEF KITCHEN EXHAUST FAN
KHWST KITCHEN HOT WATER STORAGE TANK
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KITCHEN WATER HEATER
L LENGTH
L/LS LOCAL SOUND SPEAKER
LA LABORATORY COMPRESSED AIR
LAN LOCAL AREA NETWORK
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LF LINEAR FEET
LG LABORATORY GAS
LIQ LIQUID
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
LV LABORATORY VACUUM
LVP LOW VIDEO PRESENTATION
LWT LEAVING WATER TEMPERATURE
MA MEDICAL COMPRESSED AIR
MA MILLIAMPERE
MA MIXED AIR
MAGP MASTER ALARM GAS PANEL
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MC MAIN CROSS-CONNECT
MC METAL CLAD CABLE
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MECH MECHANICAL
MFF MIXED FLOW FAN
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MULTI-MODE
MPC MEDIUM PRESSURE CONDENSATE
MPS MEDIUM PRESSURE STEAM
MUAU MAKE UP AIR UNIT
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
N/A NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NL NIGHT LIGHT WALK-THRU
NTS NOT TO SCALE
O OXYGEN
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
OF OPTICAL FIBER
ORD OVERFLOW ROOF DRAIN
ORWL OVERFLOW RAIN WATER LEADER
P POLE
PA PUBLIC ADDRESS
PBX PRIVATE BRANCH EXCHANGE
PCD PUMPED CONDENSATE DRAIN (COOLING)
PCR PUMPED CONDENSATE RETURN (STEAM)
PD PRESSURE DROP
PE PRIMARY ELECTRIC SERVICE
PF POWER FACTOR
PF PROPELLER FAN
PH / Ø PHASE
PIV POST INDICATOR VALVE
PLEF PLENUM FAN
PLUF PLUG FAN
PNL PANELBOARD
POE POWER OVER ETHERNET
PP PATCH PANEL
PR PAIR
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RELAY
RA RETURN AIR
RAF RETURN AIR FAN
RD ROOF DRAIN
RE EXISTING EQUIPMENT TO BE DISCONNECTED
AND REMOVED
REF REFRIGERANT PIPING (MULTIPLE PIPES)
REF ROOF EXHAUST FAN
REG REGISTER
RF RELIEF FAN
RGS RIGID GALVANIZED STEEL CONDUIT
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL EXISTING EQUIPMENT TO BE DISCONNECTED,
REMOVED AND RELOCATED
RM ROOM
RMS ROOT MEAN SQUARED
RO REVERSE OSMOSIS WATER
RPD REDUCED PRESSURE DEVICE
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
RU RACK UNIT
RV RADON VENT
RWL RAIN WATER LEADER
s SWITCHED RECEPTACLE
S SLEEVE(S)
S SOIL
S&R SUPPLY AND RETURN
SA SUPPLY AIR
SAC SHOP AIR COMPRESSOR
SCC SPRINKLER CONTROL CABINET
SCP STEAM CONDENSATE PUMP
SD SMOKE DAMPER
SE SECONDARY ELECTRIC SERVICE
SEP SEWAGE EJECTOR PUMP
SG STEAM GENERATOR
SM SINGLE-MODE
SP STANDPIPE
SP STATIC PRESSURE
SP SUMP PUMP
SPDT SINGLE POLE DOUBLE THROW
SPEC SPECIFICATION
SPK SPRINKLER
SPK/SP COMBINED SPRINKLER/ STANDPIPE
SPST SINGLE POLE SINGLE THROW
SQ SQUARE
SS STAINLESS STEEL
ST STORM
STD STANDARD
STP SHIELDED TWISTED PAIR
SUCT SUCTION
SW SWITCH
SWBD SWITCHBOARD
SWH STEAM WATER HEATER
T'STAT THERMOSTAT
TAF TUBEAXIAL FAN
TAG IDENTIFICATION OF EQUIPMENT
TBB TELECOMMUNICATIONS BONDING BACKBONE
TD TEMPERATURE DIFFERENCE
TE TELECOMMUNICATIONS ENCLOSURE
TEBC TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR
TEL TELECOMMUNICATIONS SERVICE
TEMP TEMPERATURE
TGB TELECOMMUNICATIONS GROUNDING BUSBAR
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
TMV THERMOSTATIC MIXING VALVE
TP TAMPERPROOF
TP TRAP PRIMER
TR TELECOMMUNICATIONS ROOM
TS TELEPHONE SERVICE
TSP TOTAL STATIC PRESSURE
TV TELEVISION
TVS TRANSIENT VOLTAGE SUPPRESSOR
TW TEMPERED WATER
TWR TEMPERED WATER RETURN
TX TRANSFORMER
TYP TYPICAL
U USB
UF UNFUSED
UH UNIT HEATER
UPF UPBLAST PROPELLER ROOF EXHAUST FAN
UPS UNINTERRUPTIBLE POWER SUPPLY
UR URINAL
USF UTILITY SET FAN
UTP UNSHIELDED TWISTED PAIR
V VENT
V VOICE
V VOLTAGE
VA VOLT AMPERE
VAC VACUUM
VAF VANEAXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFC VARIABLE FREQUENCY CONTROLLER
VIF VERIFY IN FIELD
VOIP VOICER OVER INTERNET PROTOCOL
VOL VOLUME
VTR VENT THRU ROOF
W WALL TELEPHONE
W WASTE
W WATT
WAO WORK AREA OUTLET
WAP WIRELESS ACCESS POINT
WB WET BULB TEMPERATURE
WC WATER CLOSET
WEF WALL EXHAUST FAN
WG WIREGUARD
WH WALL HYDRANT (HOSE BIBB)
WHA WATER HAMMER ARRESTER
WI WIDTH
WP WEATHERPROOF
WPD WATER PRESSURE DROP
WTG WALL TRANSFER GRILLE
WTR WATER
WV WASTE AND VENT COMBINATION
WWM WELDED WIRE MESH
ZVB MEDICAL GAS ZONE VALVE BOX
MEPT ABBREVIATIONSMEPT ABBREVIATIONS
GENERAL
1. THE PROJECT DRAWINGS AND SPECIFICATIONS ARE BASED ON THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) DOCUMENTATION FORMAT. SPECIFICATION AND DRAWING
CONTENTS ARE ARRANGED BY TOPIC AND CATEGORY AND ARE NOT INTENDED TO AWARD DIVISION OF WORK.
2. THE INTENT OF THESE DOCUMENTS IS FOR THE MEP TRADES TO FURNISH AND INSTALL COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS. THE SPECIFIED FIRE PROTECTION,
PLUMBING, HVAC, ELECTRICAL AND SPECIAL SYSTEMS SHALL BE COMPLETE IN ALL RESPECTS; OPERATIONAL, TESTED, ADJUSTED, CALIBRATED, APPROVED BY THE AUTHORITIES
HAVING JURISDICTION AND READY FOR BENEFICIAL USE BY THE OWNER.
3. UTILIZING THE DESIGN INTENT MODEL: THE CONTRACT DOCUMENTS ARE SOLELY A TWO DIMENSIONAL SET OF DOCUMENTS. IF UTILIZED, THE DESIGN INTENT MODEL HAS BEEN
DEVELOPED TO A LEVEL OF DEVELOPMENT LOD 200 AND LOD 300 MODEL CONTENT REQUIREMENTS AS DEFINED BY AIA G-202-2013. THE DESIGN INTENT MODEL IS A THREE
DIMENSIONAL TOOL UTILIZED TO CREATE A TWO DIMENSIONAL CONTRACT DOCUMENT. A TWO DIMENSIONAL CONTRACT DOCUMENT REQUIRES, FOR REASON OF CLARITY AND
OTHERWISE, THAT COMPONENTS OF THE DESIGN NOT BE MODELED IN THREE DIMENSIONS AND/OR THAT THE MODEL BE FORMED IN A WAY THAT CONSTRUCTION MEANS AND
METHODS WILL DICTATE OTHER WAYS OF PERFORMING THE INSTALLATION. THE DESIGN INTENT MODEL IS NOT A SUBSTITUTE FOR THE CONTRACTORS’ COORDINATION
PROCESS AS OUTLINED IN THE CONTRACT DOCUMENTS; FULL COORDINATION REMAINS THE RESPONSIBILITY OF THIS CONTRACTOR AND THEIR SUB-CONTRACTORS. THE
CONTENTS OF THE MODEL ARE NOT TO BE USED FOR THE BASIS OF DETAILED COST ESTIMATING, COORDINATING EQUIPMENT LOCATIONS AND SYSTEMS ROUTING WITH ALL
OTHER TRADES. THE CONTRACTOR MAY USE THE DESIGN INTENT MODEL TO HELP ESTABLISH THE BACKGROUNDS AND/OR STARTING POINT FOR THE COORDINATION DRAWINGS
BASED ON THE STIPULATIONS OF THE RELEASE FORM THAT CAN BE PROVIDED IF AND WHEN THE MODEL IS REQUESTED.
4. CREATION OF THE CONSTRUCTION COORDINATION MODEL: CREATE A CONSTRUCTION COORDINATION MODEL. THE CONSTRUCTION COORDINATION MODEL SHALL BE
DEVELOPED TO A MINIMUM LEVEL OF DEVELOPMENT LOD 400 MODEL CONTENT REQUIREMENTS AS DEFINED BY AIA G-202-2013. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE
FOR CREATING AND MAINTAINING A CONSTRUCTION COORDINATION MODEL AND COORDINATION DRAWINGS AS REQUIRED FOR DETAILED CONSTRUCTION INSTALLATION AND
COORDINATION WITH ALL OTHER TRADES.
5. DIFFERENCES BETWEEN THE DESIGN INTENT MODEL AND THE CONSTRUCTION COORDINATION MODEL AND/OR ACTUAL INSTALLATION LOCATION, MEANS AND METHODS ARE
INCLUDED IN THIS CONTRACT AND SHALL NOT CONSTITUTE A CHANGE ORDER ON THE BASIS OF DRAWING, ENGINEERING AND/OR COORDINATION TIME.
6. THE TRADES SHALL OBTAIN AND REVIEW ALL CONTRACT DOCUMENTS BEFORE SUBMITTING A BID. INFORMATION IS PROVIDED ON THE VARIOUS DRAWINGS, SCHEDULES,
SPECIFICATIONS AND ALL OF THE VARIOUS DOCUMENTS IN THE BIDDING PACKAGE. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY AND FORM A TOTAL PROJECT DESIGN
AND INFORMATION SOURCE FOR CONSTRUCTION PURPOSES.
7. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. COORDINATE LOCATIONS OF EQUIPMENT
WITH OTHER TRADES BEFORE AND DURING CONSTRUCTION. ANY MODIFICATION TO THE EQUIPMENT LAYOUT, REQUIRED FOR INSTALLATION, IS TO BE PERFORMED UNDER THE
CONTRACT AGREEMENT, AT NO ADDITIONAL COST.
8. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION AND MOUNTING HEIGHTS OF VARIOUS EQUIPMENT. ALL SUCH EQUIPMENT AND EQUIPMENT COLORS AND
FINISHES SHALL BE COORDINATED WITH THE ARCHITECT. MOUNTING HEIGHTS SHALL BE APPROVED BY THE ARCHITECT.
9. PERFORM ALL WORK IN COMPLIANCE WITH THE SPECIFICATIONS, APPLICABLE CODES, ORDINANCES AND THE REGULATORY AGENCIES HAVING JURISDICTION. THE
SPECIFICATIONS MAY EXCEED THE REQUIREMENTS OF THE CODE, IN WHICH CASE, THE SPECIFICATION MUST BE FOLLOWED.
10. INSTALL ALL EQUIPMENT IN ACCESSIBLE LOCATIONS. WHERE EQUIPMENT MUST BE INSTALLED ABOVE AN INACCESSIBLE CEILING OR BEHIND A WALL, AN APPROPRIATE ACCESS
DOOR SHALL BE PROVIDED AND THE LOCATION SHALL BE COORDINATED WITH THE ARCHITECT.
11. COORDINATE PIPING AND CONDUITS ENTERING OR LEAVING THE BUILDING WITH THE SITE CONTRACTOR(S) BEFORE INSTALLATION. COORDINATE INVERTS WITH THE STRUCTURE
AND SYSTEM REQUIREMENTS PRIOR TO INSTALLATION.
12. WHERE A CONFLICT OCCURS BETWEEN THE DOCUMENTS, IT SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. CARRY AS PART OF THE BID THE LARGER QUANTITY
AND/OR MORE EXPENSIVE ITEM(S).
13. BEFORE INSTALLATION, COORDINATE THE WORK WITH OWNER-FURNISHED EQUIPMENT, INCLUDING REQUIRED SERVICE CONNECTIONS, FACTORY START UPS AND INSTALLATION
OF FIELD DEVICES.
14. PROVIDE THE REQUIRED/SPECIFIED SLEEVES AND SEALS FOR PIPES OR CONDUIT PENETRATING INTERIOR AND EXTERIOR WALLS OR FLOOR SLABS.
15. INSTALL FLOOR-MOUNTED EQUIPMENT ON A CONCRETE HOUSEKEEPING PAD.
16. SEISMICALLY SUPPORT THE EQUPMENT AS REQUIRED BY CODE, THE AUTHORITY HAVING JURISDICTION, AND/OR AS SPECIFIED. SUBMIT ENGINEERED INSTALLATION DETAILS PER
THE SPECIFICATIONS. THE CONTRACTOR'S SEISMIC ENGINEER SHALL REVIEW THE INSTALLATION AND PROVIDE A REPORT ON THE FINDINGS.
17. PROVIDE MEP COORDINATION DRAWINGS AS REQUIRED BY THE SPECIFICATIONS.
18. ENCLOSED CONTROLLERS SHALL BE PROVIDED BY THE CONTRACTOR PROVIDING THE EQUIPMENT REQUIRING AN ENCLOSED CONTROLLER. REQUIREMENTS ARE SPECIFIED
UNDER DIVISION 26: "ENCLOSED CONTROLLERS". MOTOR EFFICIENCIES SHALL BE AS INDICATED IN THE SPECIFICATIONS.
19. PROVIDE PIPING, DUCTWORK, CONDUIT AND ALL OTHER ACCESSORIES AS REQUIRED FOR PROPER AND PROFESSIONAL SYSTEMS INSTALLATION.
20. TEST AND BALANCE ALL MECHANICAL AND ELECTRICAL SYSTEMS. PROVIDE ADDITIONAL TESTS AS REQUIRED BY THE SPECIFICATIONS.
21. DO NOT INSTALL PIPING OR DUCTWORK OVER ELECTRICAL PANELS, TRANSFORMERS, SPECIAL EQUIPMENT, ELEVATOR MACHINE ROOMS OR SHAFTS.
22. DO NOT INSTALL ANY SYSTEMS IN OR THROUGH ELEVATOR MACHINE ROOMS THAT DO NOT SERVE THE ROOM. MAINTAIN A MINIMUM OF SEVEN (7) FOOT HEAD CLEARANCE IN THE
ELEVATOR MACHINE ROOM.
23. DO NOT INSTALL IN STAIRWELL OR STAIRWELL WALLS, PIPING, DUCTWORK, CONDUIT OR OTHER DEVICES OR EQUIPMENT NOT ASSOCIATED WITH OR SERVING THE RESPECTIVE
STAIR.
24. PROVIDE PIPE EXPANSION COMPENSATION FOR THE VARIOUS PIPING SYSTEMS. SUBMIT ENGINEERED DETAILS FOR APPROVAL AND VERIFY INSTALLATION IS IN ACCORDANCE
WITH CODE. THE CONTRACTOR'S CONSULTING ENGINEER SHALL REVIEW THE INSTALLATION AND PROVIDE A REPORT OF THE FINDINGS.
25. PROVIDE ADDITIONAL TRANSITIONS AND OFFSETS IN ALL PIPING, DUCTWORK OR CONDUIT FOR COORDINATION WITH BUILDING STRUCTURE AND CONSTRUCTION.
26. NO MECHANICAL OR ELECTRICAL SYSTEM COMPONENTS MAY BE SUPPORTED FROM STRUCTURAL BRACED FRAMES.
RENOVATION
1. THIS PROJECT INVOLVES THE RENOVATION OF AN EXISTING FACILITY; BEFORE SUBMITTING THE BID, CONTRACTORS SHALL VISIT THE SITE AND BECOME THOROUGHLY FAMILIAR
WITH THE EXISTING CONDITIONS UNDER WHICH THE PROJECT IS TO BE COMPLETED.
2. CONTRACTORS SHALL BE HELD RESPONSIBLE FOR ASSUMPTIONS, OMISSIONS OR ERRORS MADE AS A RESULT OF FAILURE TO BECOME FULLY FAMILIAR WITH THE EXISTING
CONDITIONS.
3. IT IS NOT THE INTENT OF THESE DOCUMENTS TO SHOW EVERY DEVICE, APPURTENANCE, PIPE, WIRE OR CONDUIT TO BE REMOVED. MEP EQUIPMENT, UNITS, AND SYSTEMS NOT
BEING REUSED, SHALL BE REMOVED IN THEIR ENTIRETY INCLUDING ASSOCIATED HANGERS, SUPPORTS, BASES, PADS, PIPES, DUCTS, CONDUITS, WIRES, INSULATION, AND
CONTROLS BACK TO THE POINT OF ORIGIN.
4. EQUIPMENT, PIPING, OR CONDUIT SHALL NOT BE ABANDONED IN-PLACE UNLESS SPECIFICALLY SO NOTED.
5. PROPERLY DISPOSE OF DEMOLISHED EQUIPMENT IN COMPLIANCE WITH CODES, REGULATIONS, AND DEEP STANDARDS. TURN OVER TO THE OWNER EQUIPMENT SO INDICATED.
6. RELOCATE EXISTING EQUIPMENT, DEVICES, PIPING, WIRING, AND RELATED SYSTEMS AS REQUIRED FOR CONSTRUCTION PURPOSES. ALL EXISTING SYSTEMS SHALL BE FULLY
OPERATIONAL, INCLUDING RECONNECTION TO SERVICES AND UPGRADED SYSTEMS. ALL RELOCATED EQUIPMENT SHALL BE PROTECTED DURING CONSTRUCTION.
7. PROVIDE TEMPORARY CONNECTIONS AND SYSTEM MODIFICATIONS AS REQUIRED FOR CONSTRUCTION AND PHASING PURPOSES.
8. INCLUDE ALL WORK REQUIRED TO ALLOW PHASED CONSTRUCTION WHEN NECESSARY. COORDINATE WITH GENERAL CONTRACTOR/CONSTRUCTION MANAGER FOR PHASING
REQUIREMENTS.
9. ALL EXISTING EQUIPMENT, FIXTURES, AND DEVICES TO BE REMOVED AND RELOCATED SHALL BE FIELD VERIFIED FOR EXACT QUANTITY AND CONDITION. KEEP AN ACCURATE
RECORD OF STORED EQUIPMENT AND ITS CONDITION.
10. REBALANCE NEW AND EXISTING MECHANICAL AND ELECTRICAL SYSTEMS ASSOCIATED WITH THE RENOVATION, INCLUDING RENOVATED AREAS AND AREAS AFFECTED BY SYSTEM
MODIFICATIONS.
11. SYSTEMS REQUIRING TO REMAIN IN OPERATION DURING DEMOLITION SHALL BE CAREFULLY PROTECTED FROM DAMAGE AND CONTAMINATION BY THE CONSTRUCTION PROCESS.
FIRE PROTECTION
1. PROVIDE ALL PIPING, SUPPORTS, AND EQUIPMENT NECESSARY FOR A FULL COVERAGE SYSTEM IN CONFORMANCE WITH NFPA, STATE AND LOCAL CODES, THE OWNER'S
INSURANCE COMPANY, AND THE AUTHORITY HAVING JURISDICTION.
2. COORDINATE SPRINKLER HEAD LOCATIONS WITH THE LATEST ARCHITECTURAL REFLECTED CEILING PLANS, HOWEVER, FULL SPRINKLER COVERAGE REMAINS THE
RESPONSIBILITY OF THE INSTALLING PROFESSIONAL.
3. REFER TO THE LATEST ARCHITECTURAL PLANS FOR CEILING CONSTRUCTION, ELEVATIONS, SECTIONS, DETAILS, LOCATIONS OF SOFFITS, CEILING POCKETS, STEPPED CEILING,
SKYLIGHT, ETC. PROVIDE ADDITIONAL PIPING AND SPRINKLER HEADS AS THE CONDITION WARRANTS.
4. WHERE SPRINKLER HEADS ARE SHOWN ON CONTRACT DOCUMENTS, THEY ARE INDICATED FOR GENERAL COORDINATION PURPOSES ONLY AND DO NOT RELIEVE THE
CONTRACTOR FROM FULL COMPLIANCE WITH APPLICABLE CODES AND GOOD INSTALLATION PRACTICE.
5. ALL EQUIPMENT MAIN DRAINS AND INSPECTOR TEST DRAINS SHALL BE PIPED TO THE EXTERIOR OF THE BUILDING. PROVIDE CONCRETE SPLASH GUARDS AT EACH DRAIN
LOCATION TO AVOID SOIL EROSION OR OTHER DAMAGE.
6. BRANCH PIPING TO SPRINKLER HEADS SHALL NOT BE INSTALLED DIRECTLY FROM THE BOTTOM OF HORIZONTAL SPRINKLER MAINS OR BRANCH LINES. ALL CONNECTIONS TO
SPRINKLER HEADS SHALL BE MADE FROM THE TOP OR SIDES OF THE MAIN OR BRANCH LINES.
7. LOCATIONS OF FIRE DEPARTMENT CONNECTIONS AND FIRE PROTECTION SERVICE CONTROL VALVES SHALL BE COORDINATED WITH THE AUTHORITY HAVING JURISDICTION PRIOR
TO INSTALLATION.
PLUMBING
1. IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW INDIVIDUAL BRANCH PIPING TO EACH PLUMBING FIXTURE; ONLY THE BRANCH PIPING TO GROUPS OF FIXTURES IS INDICATED.
EACH AND EVERY FIXTURE SHALL BE PROPERLY PIPED TO WATER, WASTE, AND VENT PIPING SYSTEMS. REFER TO THE PLUMBING SCHEDULES FOR INDIVIDUAL PIPE SIZES TO
EACH FIXTURE.
2. INSTALL TRAP PRIMERS FOR ALL FLOOR DRAINS AND WATER HAMMER ARRESTORS AT ALL QUICK CLOSING VALVES (FLUSH VALVES, SOLENOID VALVES, ETC.); SIZE SHALL BE
BASED ON FIXTURE UNITS PER PDI STANDARDS.
3. INCLUDE NECESSARY PIPING OFFSETS AND TRANSITIONS AS REQUIRED TO INSTALL THE PLUMBING FIXTURES AND EQUIPMENT. PIPING, DRAINS AND VENTS SHALL BE
THOROUGHLY CLEANED AND FLUSHED IMMEDIATELY BEFORE PROJECT COMPLETION. PROVIDE CERTIFICATION ON CONTRACTOR'S LETTER HEAD THAT THIS WORK HAS BEEN
COMPLETED.
4. DOMESTIC WATER DROPS AND RISERS INSTALLED IN EXTERIOR WALLS SHALL BE INSTALLED ON THE WARM SIDE OF INSULATION AND THE LOCATION SHALL BE MADE
INFILTRATION FREE.
5. PROVIDE COOLING COIL CONDENSATE TRAPS AND DRAIN PIPING FOR ALL MECHANICAL EQUIPMENT REQUIRING SAME; PIPE CONDENSATE DRAINS BY GRAVITY TO INDIRECT WASTE
FLOOR DRAIN OR OTHER APPROVED LOCATION.
6. COORDINATE EXACT LOCATION OF UNDERGROUND UTILITIES (WATER, GAS, SANITARY, ETC.) EXITING OR ENTERING THE BUILDING WITH THE SITE CONTRACTOR, GENERAL
CONTRACTOR OR CONSTRUCTION MANAGER.
HVAC
1. PROVIDE THROTTLING VALVES AND SHUT-OFF VALVES AS SPECIFIED IN ADDITION TO THOSE INDICATED ON THE DOCUMENTS.
2. PROVIDE DUCT TAKE-OFF TYPES AND VOLUME DAMPERS PER THE SPECIFICATIONS AND DUCT TAKE-OFF DETAILS ON DRAWINGS. TAKE-OFFS SHOWN ON FLOOR PLANS DO NOT
REPRESENT THE SPECIFIC TYPE OF TAKE-OFF REQUIRED. CONSULT THE DETAILS AND SPECIFICATIONS.
3. INSTALL SMOKE DETECTORS FOR AIR HANDLING EQUIPMENT PER THE MEP DETAILS. PROVIDE SMOKE DAMPERS AND INSTALL ASSOCIATED SMOKE DETECTORS AT DUCT
PENETRATIONS OF SMOKE-BARRIERS, AT AIR HANDLING UNITS, AND AT ELEVATOR SHAFT VENTS PER THE MEP DETAILS AND CODE REQUIREMENTS.
4. PROVIDE AN AUTOMATIC TEMPERATURE CONTROL SYSTEM COMPLETE IN ALL REGARDS. ALL ZONES, VAV'S AND SYSTEMS SHALL BE THERMOSTATICALLY CONTROLLED. REVIEW
THE PLANS AND SPECIFICATIONS OF ALL MEP TRADES FOR A COMPLETE SCOPE OF THE WORK.
5. PIPING SHALL BE SUPPORTED FROM STRUCTURE ABOVE. TO MAXIMIZE HEAD ROOM, INSTALL TIGHT TO BOTTOM OF BEAMS WHEN RUNNING PERPENDICULAR TO BEAM. INSTALL
PIPING TIGHT TO FLOOR SLAB WHEN RUNNING PARALLEL TO BEAM. PROVIDE ALL NECESSARY FITTINGS AND TRANSITIONS.
6. PROVIDE AIR VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS.
7. PROVIDE FIRE DAMPERS AT DUCT PENETRATIONS OF FIRE-RATED CONSTRUCTION, INCLUDING WALLS, SHAFTS AND FLOOR PENETRATIONS. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
8. PAINT AND INTERNALLY INSULATE ALL EXPOSED DUCTWORK PER THE SPECIFICATIONS.
9. PROVIDE PRESSURE RELIEF DOORS FOR AIR SYSTEMS PER THE SPECIFICATIONS.
10. PROVIDE MOTORIZED DAMPERS AT ALL PERMANENT OPENINGS (EXHAUST, SUPPLY, RELIEF, O.A. INTAKES, MAKE-UP AIR, SMOKE VENTS, ETC.) EXCEPT DRYER, KITCHEN, AND FUME
EXHAUST AND PROVIDE A MEANS TO CONTROL THE DAMPER OPERATION.
ELECTRICAL
1. IT IS NOT THE INTENTION TO SHOW EVERY FITTING, WIRE, OR DEVICE. ALL SUCH ITEMS SHALL BE FURNISHED AND INSTALLED AS NECESSARY FOR A COMPLETE SYSTEM.
2. CONCEAL RACEWAYS IN FINISHED AREAS. RACEWAYS WITHIN MECHANICAL AND ELECTRICAL ROOMS MAY BE SURFACE-MOUNTED.
3. DO NOT INSTALL CONDUIT IN CONCRETE SLABS, UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER.
4. EACH INDIVIDUAL ELECTRICAL HOMERUN SHOWN ON FLOOR PLANS, DETAILS, OR SCHEDULES SHALL BE PROVIDED IN A DEDICATED RACEWAY.
5. SERIES RATING OF PROTECTIVE/ISOLATION DEVICES AND/OR ELECTRICAL EQUIPMENT IS UNACCEPTABLE. ALL ELECTRICAL EQUIPMENT AND PROTECTIVE DEVICES SHALL BE
“FULLY” RATED.
6. PROVIDE POWER TO MECHANICAL EQUIPMENT SHOWN ON MECHANICAL PLANS, RISERS, SCHEDULES, OR IN SPECIFICATIONS. MECHANICAL EQUIPMENT IS NOT NECESSARILY
SHOWN ON ELECTRICAL PLANS. REFER TO MECHANICAL PLANS AND SCHEDULES ON MEP DRAWINGS FOR LOCATIONS AND SPECIFIC ELECTRICAL REQUIREMENTS. COORDINATE
EXACT LOCATION AND ORIENTATION OF EQUIPMENT WITH OTHER TRADES.
7. PROVIDE INTERFACE CONNECTIONS TO THE FIRE ALARM SYSTEM AND FIRE PROTECTION SYSTEM EQUIPMENT SHOWN ON PLANS, SCHEDULES, RISERS, OR IN SPECIFICATIONS.
THIS EQUIPMENT IS NOT NECESSARILY SHOWN ON ELECTRICAL PLANS. COORDINATE EXACT LOCATION AND QUANTITY WITH THE FIRE PROTECTION CONTRACTOR.
8. FURNISH AND COORDINATE THE LOCATION OF DUCT SMOKE DETECTORS. PROVIDE AND WIRE DEVICES TO THE FIRE ALARM SYSTEM; FURNISH DETECTORS TO THE MECHANICAL
CONTRACTOR FOR INSTALLATION.
9. MAKE CONNECTIONS TO LUMINAIRES IN ACCORDANCE WITH THE DETAILS SHOWN ON THE DRAWINGS. PROVIDE SWITCHING, AND OCCUPANCY SENSORS AND NORMAL CIRCUIT
MONITORING AS PER THE DETAILS.
10. EXIT SIGNS ARE NOT NECESSARILY SHOWN WIRED ON THE DRAWINGS. PROVIDE SINGLE CIRCUIT EXIT SIGNS WITH BATTERY BACKUP; CONNECT POWER TO THE UN-SWITCHED
LIGHTING CIRCUIT IN THE AREA SERVED BY THE EXIT SIGN.
11. CONNECT EMERGENCY FLUORESCENT POWER UNITS (BATTERY BALLAST(S)) OR EMERGENCY LIGHTING UNITS TO LINE SIDE OF SWITCHING. THESE UNITS MUST MONITOR THE
NORMAL LIGHTING CIRCUIT WITHIN THE SPACE.
12. INSTALL WIRING FROM AN EMERGENCY SOURCE OR EMERGENCY DISTRIBUTION OVERCURRENT PROTECTION TO EMERGENCY LOADS ENTIRELY INDEPENDENT OF ALL OTHER
WIRING AND EQUIPMENT EXCEPT WITHIN THE EQUIPMENT, EXIT SIGNS, AND EMERGENCY LUMINAIRES.
13. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR THE EXACT LOCATION OF ALL CEILING MOUNTED LUMINAIRES SHOWN ON ELECTRICAL PLANS.
14. BOND ALL OF THE FOLLOWING SERVICES TOGETHER PER THE NEC: POWER, TELECOMMUNICATIONS, CATV AND LIGHTNING PROTECTION.
15. PROVIDE BRANCH CIRCUITS FROM ELECTRICAL PANELS WITH SUFFICIENT CAPACITY AND SPACE FOR MISCELLANEOUS SYSTEMS. THESE SYSTEMS SHALL INCLUDE, BUT ARE NOT
LIMITED TO, MONITORING SYSTEMS, CONTROL PANELS, ANNUNCIATOR PANELS, PLUMBING ACCESSORIES, ETC. FURNISH AND INSTALL ALL BRANCH CIRCUIT WIRING AND CIRCUIT
BREAKERS FOR THE EQUIPMENT SHOWN.
16. PROVIDE GROUND FAULT RECEPTACLES WITHIN SIX FEET (6') OF SINK OR OTHER WATER SOURCE; PROVIDE GROUND FAULT WEATHER PROOF RECEPTACLES AT ALL EXTERIOR
LOCATIONS.
TECHNOLOGY
1. COORDINATE WITH CONSTRUCTION MANAGER, OTHER TRADES AND THE OWNER DURING ALL PHASES. ALL COMMUNICATIONS MUST BE MAINTAINED AT ALL TIMES UNLESS
PHASING REQUIRES OTHERWISE. INTERRUPTIONS AND SHUTDOWNS SHALL BE SCHEDULED IN ADVANCE AND APPROVED FOR TIME TO COMPLETE WORK. TAG CABLES TO
REMAIN DURING ALL PHASES TO PROPERLY KEEP THE TELECOMMUNICATIONS ACTIVE. UPON COMPLETION OF CONSTRUCTION, ANY CABLES THAT ARE NOT ACTIVE OR TAGGED
TO REMAIN FOR FUTURE USE SHALL BE REMOVED PER THE NEC.
2. BEFORE CONSTRUCTION CAN BEGIN IN ANY TELECOMMUNICATIONS ROOM (TR) OR TELECOMMUNICATIONS EQUIPMENT ROOM (ER) THE CONTRACTOR SHALL COORDINATE
LAYOUT LOCATIONS AND CLEARANCES OF ALL EQUIPMENT WITH THE TECHNOLOGY OWNER TO APPROVE THE INSTALLATIONS AND ANY FUTURE SPACE.
3. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION AND MOUNTING HEIGHTS OF EQUIPMENT. ALL SUCH EQUIPMENT AND COLORS SHALL BE COORDINATED
WITH THE ARCHITECT. CONTACT ARCHITECT FOR ANY CLARIFICATION.
4. REFER TO REFLECTED CEILING PLANS FOR FLUSH MOUNTED CEILING DEVICES.
5. PROVIDE SEPARATION BETWEEN RACEWAY, CABLES AND OTHER SOURCES (EMI) PER ANSI/TIA-569-B.
6. ELBOW RADIUS FOR RACEWAYS SMALLER THAN 2" TO BE (6) SIX TIMES THE RACEWAY DIAMETER. ELBOW RADIUS FOR CONDUITS 2" OR LARGER TO BE (10) TEN TIMES THE
RACEWAY DIAMETER.
7. ALL EMPTY RACEWAYS SHALL BE PROVIDED WITH A (PLENUM RATED, IF PLENUM CEILING SPACE) NYLON PULL CORD.
8. COORDINATE PROPER METHODS FOR PENETRATIONS WITH FIRESTOPPING AS REQUIRED THROUGH FIRE/SMOKE RATED CONSTRUCTION PER DIVISION 07 SPECIFICATIONS.
9. NO PENETRATIONS ARE PERMITTED INTO ANY STAIRWELLS EXCEPT FOR SYSTEMS SERVING THAT STAIRWELL.
10. CONDUITS AND CABLING FOR SERVICE ENTRANCE SHALL BE PROVIDED PER SITE UTILITY DRAWINGS, TECHNOLOGY/ELECTRICAL POWER DRAWINGS AND DIVISION 26
SPECIFICATIONS. COORDINATE LOCATION OF DEMARCATION POINT.
11. LADDER RACKS, CONDUITS, D-RINGS, ETC. FOR CABLE SUPPORT IN ANY TELECOMMUNICATIONS ROOM (TR) OR TELECOMMUNICATIONS EQUIPMENT ROOM (ER) SHALL BE
PROVIDED PER PLANS AND DIVISION 26 SPECIFICATIONS.
12. CABLE TRAYS, CONDUITS, SLEEVES AND J-HOOKS FOR FIBER BACKBONE CABLING AND OTHER BACKBONE CABLING SHALL BE PROVIDED PER DIVISION 26 SPECIFICATIONS.
13. CABLE TRAY, SURFACE MOUNTED RACEWAYS, CONDUITS, SLEEVES AND J-HOOKS FOR HORIZONTAL CABLING FROM COMMUNICATIONS EQUIPMENT ROOM TO THE
TELECOMMUNICATIONS OUTLETS/CONNECTORS SHALL BE PROVIDED PER DIVISION 26 SPECIFICATIONS.
14. COORDINATE THE INSTALLATION OF ALL CABLE TRAYS, SURFACE MOUNTED RACEWAYS, CONDUITS, SLEEVES AND J-HOOKS PER DIVISION 26 SPECIFICATIONS.
15. COORDINATE OUTLET INSTALLATIONS, WALL: RECESSED OR SURFACE; CEILING; FLOOR: SLEEVE OR INFLOOR SYSTEM; UTILITY COLUMN; PER TECHNOLOGY/ELECTRICAL POWER
DRAWINGS AND DIVISION 26 SPECIFICATIONS.
16. COORDINATE EXACT LOCATION(S) FOR MECHANICAL EQUIPMENT ETHERNET CONNECTION TERMINATION(S) WITH DIVISION 23.
MEPT GENERAL NOTESMEPT GENERAL NOTES
CODES LISTED BELOW APPLY TO ALL DRAWINGS AND SPECIFICATIONS ON THIS PROJECT
● MASSACHUSETTS BASIC BUILDING CODE - EIGHTH EDITION
● THE FOLLOWING AS REFERENCED AND MODIFIED BY THE ABOVE CODE:
○ 2009 INTERNATIONAL BUILDING CODE (IBC) WITH MASSACHUSETTS AMENDMENTS PER 780 CMR
○ 780 CMR 9.00 - FIRE PROTECTION SYSTEMS
▪ 527 CMR CHAPTER MASS FIRE PENETRATION REGULATIONS
▪ 2009 INTERNATIONAL FIRE CODE
▪ MASSACHUSETTS GENERAL LAW CHAPTER 148 - FIRE PREVENTION - SECTION 26
○ 780 CMR 13.00 - ENERGY EFFICIENCY AMENDMENTS
▪ 2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
▪ 2010 ANSI/ASHRAE/IESNA STANDARD 90.1 - ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS
○ 780 CMR CHAPTER 27.00 - ELECTRICAL
▪ 527 CMR CHAPTER 12 - MASSACHUSETTS ELECTRICAL CODE (AMENDMENTS)
▪ 527 CMR CHAPTER 27 - EMERGENCY AND STANDBY POWER SYSTEMS
▪ 2014 NFPA 70 - NATIONAL ELECTRICAL CODE (NEC)
▪ NFPA 110 - 2002
○ 780 CMR 28.00 - MECHANICAL SYSTEMS
▪ 2009 INTERNATIONAL MECHANICAL CODE (IMC)
○ 780 CMR 29.00 - PLUMBING SYSTEMS
▪ 248 CMR CHAPTER 10 - MASSACHUSETTS UNIFORM STATE PLUMBING CODE
○ ACCESSIBILITY
▪ 521 CMR - MASSACHUSETTS ARCHITECTURAL ACCESS BOARD REGULATIONS
▪ MASSACHUSETTS GENERAL LAWS CHAPTER 22
▪ 2004 ICC/ANSI A117.1 - GUIDELINES FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
● 2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES
● THE JOINT COMMISSION
● THE AMERICANS WITH DISABILITY ACT, TITLE II, INCLUDING THE AMERICANS WITH DISABILITIES ACT ACCESSIBILITYGUIDELINES (ADAAG) AND ADA REGULATIONS
● OCCUPATIONAL SAFETY AND HEALTH ACT, TITLE 29/LABOR
● GENERAL LAWS OF MASSACHUSETTS
EHC
XXX
XXX
FDC
PRE
DRY
SP
SPK
SP/SPK
F
O
MV
N2O
TWR
TW
CD
ST
RWL
ORWL
IW
S
S
A
2
3
4
P
L
E
R
D
D3
T
K
K3
K4
SC
MC
OC
OC
VS
VC
T
OC
(1) 20A- 1P
LV-1MFSVFCVDFDZONE VALVE BOX
HOME RUN
CIRCUIT BREAKER SIZE
PANEL DESIGNATION
ALARM PANEL
SLIDE
VACUUM OUTLET
OXYGEN OUTLET
NITROUS OXIDE
MEDICAL VACUUM
OXYGEN
SHOWER HEAD - LOCATION
T&P RELIEF VALVE
ROOF DRAIN
FLOOR DRAIN
TEMPERED WATER RETURN
TEMPERED WATER
CONDENSATE DRAIN
STORM BURIED
RAIN WATER LEADER
OVERFLOW RAIN WATER LEADER
INDIRECT WASTE
SOIL OR WASTE BURIED
SOIL OR WASTE ABOVE GRADE
HOT WATER RECIRCULATING
HOT WATER
POINT OF NEW TO EXISTING CONNECTION,
INCLUDING TRANSITIONS
THICK, DASHED LINES INDICATE EXISTING
ITEMS TO BE REMOVED
THIN, LIGHT LINES INDICATE EXISTING ITEMS
OR RACEWAY TO REMAIN IN PLACE AND BE
REUSED
THICK, DARK SOLID LINES INDICATE NEW
OR RELOCATED ITEMS OR NEW RACEWAY
AND WIRING
FIRE SERVICE
COMBINATION SP / SPK MAIN
WET SPRINKLER MAIN
STANDPIPE MAIN
DRY SPRINKLER MAIN
PREACTION SPRINKLER MAIN
FIRE DEPT. CONNECTION SUPPLY LINE
FIRE HOSE VALVE
RISER (SPRINKLER OR STANDPIPE)
PENDANT SPRINKLER HEAD CONCEALED
PENDANT SPRINKLER HEAD SEMI-RECESSED
UPRIGHT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
EXISTING SPRINKLER HEAD TO REMAIN
EXISTING SPRINKLER HEAD TO BE REMOVED
DRY PENDANT SPRINKLER
DRY SIDEWALL SPRINKLER
WIRE GUARD OVER SPRINKLER HEAD
EXTENDED COVERAGE SPRINKLER
HIGH TEMPERATURE SPRINKLER
FULLY SPRINKLERED SPACE
PARTIALLY SPRINKLERED SPACE
NON-SPRINKLERED SPACE
DP
DS
WG
EC
H
RECTANGULAR, FLAT OVAL OR ROUND
AIR DUCT
AIR DUCT WITH ACOUSTICAL LINING
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
EXHAUST AIR DUCT UP
EXHAUST AIR DUCT DOWN
ACCESS DOOR
FLEXIBLE DUCT CONNECTION
CEILING SUPPLY DIFFUSERS
CEILING RETURN / EXHAUST GRILLE
HARD DUCTED DIFFUSER OR GRILLE WITH
FULL SIZE BOTTOM TAKE-OFF
DIRECTION OF SUPPLY OR OUTDOOR
AIRFLOW
DIRECTION OF RETURN OR EXHAUST
AIRFLOW
DOOR UNDERCUT
VOLUME DAMPER
FIRE DAMPER
VAV BOX W / UNIT TYPE
SUPPLY PIPING. REFER TO ABBREVIATION
LIST FOR DESIGNATION (XXX)
RETURN PIPING. REFER TO ABBREVIATION
LIST FOR DESIGNATION (XXX)
ELECTRICAL HEATING CABLE. REFER TO
ABBREVIATION LIST FOR DESIGNATION (XXX)
SMOKE DAMPER SYSTEM AND
ASSOCIATED DEVICES PER
SPECIFICATIONS AND MEP DETAILS
COMBINATION FIRE AND SMOKE DAMPER
MOTORIZED DAMPER
HUMIDIFIER TUBE / PANEL
DUCT SMOKE DETECTOR WITH REMOTE
INDICATING LIGHT AND TEST SWITCH
DUCT STATIC PRESSURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
VARIABLE FREQUENCY CONTROLLER
ROOM THERMOSTAT OR TEMPERATURE
SENSOR
ROOM TEMPERATURE WITH CARBON
DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
FINNED TUBE RADIATION
VAV PERFORMANCE TAG
FIN TUBE TAG
PIPE ANCHOR
BACKFLOW PREVENTER
STRAINER OR STRAINER WITH BLOW-
DOWN VALVE HOSE END, CAP AND CHAIN
WALL CLEANOUT OR BLIND FLANGE
"P" TRAP
PIPE TEE DOWN
IN-LINE EXPANSION COMPENSATOR
FLOOR CLEANOUT
STEAM TRAP ASSEMBLY
STEEL PENETRATION / PIPE SLEEVE
PIPE ELBOW UP OR PIPE TEE UP
PIPE ELBOW DOWN
COMPANION FLANGE
PIPE CAP OR CAPPED END OF PIPE
UNION
PIPE GUIDES
PUMP
WATER HAMMER ARRESTOR
TAKEOFF FROM TOP OF MAIN PIPE
TAKEOFF FROM BOTTOM OF MAIN PIPE
DIRECTION OF FLUID FLOW
VALVE ON RISER
VALVE ON DROP
METERING ORIFICE
AIR VENT
FLOW SENSOR
PIPE DROP WITH VALVE
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
BALL VALVE
CALIBRATED BALANCING VALVE
SHUT-OFF VALVE (SEE SPECIFICATIONS
FOR APPLICATION TYPE)
BUTTERFLY VALVE
CHECK VALVE
THERMOSTATIC MIXING VALVE
GLOBE VALVE
GATE VALVE
PRESSURE REDUCING VALVE
GAS COCK
TRIPLE DUTY VALVE
OS&Y VALVE
FUSOMATIC VALVE (FIREMATIC)
DRAIN VALVE WITH HOSE END, CAP &
CHAIN OR WALL HYDRANT / HOSE BIBB
MOTORIZED BUTTERFLY VALVE
PRESSURE RELIEF SAFETY VALVE
AQUASTAT
SOLENOID VALVE
TEMPERATURE SENSOR WITH SEPARABLE
SOCKET IN IMMERSIBLE WELL
TEMPERATURE GAUGE WITH SEPARABLE
SOCKET IN IMMERSIBLE WELL
THERMOMETER WITH SEPARABLE SOCKET
IN IMMERSIBLE WELL
PRESSURE GAUGE
PRESSURE SENSOR WITH SYPHON
(STEAM)
FLEXIBLE CONNECTOR
RECTANGULAR DUCT
ROUND DUCT
20x12
20Ø
PENDANT LIGHT FIXTURE
ELECTRICAL SYMBOLS
LINEAR LIGHT FIXTURE
PENDANT MOUNTED LIGHT FIXTURE
RECESSED DOWNLIGHT FIXTURE
RECESSED WALL WASH DOWNLIGHT
FIXTURE
SURFACE-MOUNTED LIGHT FIXTURE
WALL-MOUNTED LIGHT FIXTURE
RECESSED OR SURFACE-MOUNTED
FIXTURE
OPEN LAMP LIGHT FIXTURE
LIGHTING TRACK (NUMBER OF FIXTURES
INDICATED ON PLANS)
CEILING OR WALL-MOUNTED EXIT LIGHT
FIXTURE
CEILING OR WALL-MOUNTED EMERGENCY
LIGHT UNIT
LIGHT FIXTURE (PART OF EMERGENCY
ILLUMINATION SYSTEM)
SINGLE-POLE SWITCH
DOUBLE-POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
SINGLE-POLE SWITCH
(TOGGLE LIGHTED - LOAD ON)
LOW VOLTAGE SWITCH
EMERGENCY OFF SWITCH
EMERGENCY LIGHTING RELAY
SINGLE-POLE DIMMER SWITCH
THREE-WAY DIMMER SWITCH
SINGLE-POLE TIMER SWITCH
SINGLE-POLE KEYED SWITCH
KEYED, 3-WAY SWITCH
KEYED, 4-WAY SWITCH
SPEED CONTROL SWITCH
MOMENTARY CONTACT SWITCH
OCCUPANCY SENSOR W / POWER PACK
(CEILING / WALL)
OCCUPANCY SENSOR SWITCH
VACANCY SENSOR SWITCH
VACANCY SENSOR CONTROL SWITCH
MARK TIME SWITCH
DAYLIGHTING SENSOR
TIME CLOCK
PHOTOCELL
EMERGENCY OFF SWITCH WITH COVER
SURFACE MOUNTED FACTORY PRE-WIRED
MULTI-OUTLET RACEWAY
SURFACE MOUNTED RACEWAY. SEE PLANS
OR SCHEDULE FOR QUANTITY OF DEVICES
ELECTRICAL HEATING CABLE
POWER WIRING
SWITCH LEG WIRING
CONTROL WIRING
FURNITURE PARTITION WHIP CONNECTION
FLOOR SERVICE FITTING WITH OUTLET(S);
REFER TO SCHEDULE (X)
POKE-THRU ASSEMBLY WITH OUTLET(S);
REFER TO SCHEDULE (X)
WALL BOX WITH PLATE FOR FURNITURE
POWER WITH WHIP CONNECTIONS
WALL BOX WITH PLATE FOR FURNITURE
TELECOMMUNICATIONS WITH WHIP
CONNECTIONS
FEEDER TAG
SURFACE ELECTRICAL PANEL,
480Y/277 OR 480 VOLT
SURFACE ELECTRICAL PANEL,
208Y/120 OR 208 VOLT
SURFACE SPECIAL-PURPOSE PANEL OR
CABINET
FLUSH ELECTRICAL PANEL, 480Y/277 VOLT
FLUSH ELECTRICAL PANEL, 208Y/120 VOLT
FLUSH SPECIAL-PURPOSE PANEL OR
CABINET
TRANSFORMER
TRAP PRIMER
COLD WATER
H
SP
DP
NS
AS
AS
S
V
O
E
*
XXX
XXX
T
H
Tc
CO
CO2
TC
PC
DL
FB-X
PT-X
T
P
EHC
TX
TX
FITTINGS AND VALVES
HVAC SYMBOLSFIRE PROTECTION SYMBOLSGENERAL SYMBOLS
PLUMBING SYMBOLS
MEDICAL GAS SYMBOLS
DUCT SIZING
DS
VENT
PCD PUMPED CONDENSATE DRAIN
-N -G
---A
999
999
999
WIRING - REFER TO ABBREVIATION LIST (XXX)XXX
FLAT OVAL DUCT20/12
EMERGENCY EYEWASH / DELUGE SHOWER
SUB LETTERS "EX" INDICATES EXISTING
EQUIPMENT TO REMAIN INTACT
SUB LETTER "RE" INDICATES EXISTING
EQUIPMENT TO BE DISCONNECTED AND
REMOVED
SUB LETTER "RL" INDICATES EXISTING
EQUIPMENT TO BE DISCONNECTED,
REMOVED AND RELOCATED
SUB LETTER "NL" INDICATES NEW
LOCATION OF RELOCATED EQUIPMENT
SUB LETTER "NR" INDICATES NEW
EQUIPMENT TO REPLACE EXISTING
SUB LETTER "RR" INDICATES REMOVE
EQUIPMENT AND REPLACE ON NEW
SURFACE
EX
RE
RL
NL
NR
RR
TP
M
COMMUNICATIONS SYMBOLS
CARD READER
ELECTRONIC DOOR LATCH RETRACTION
ELECTRONIC DOOR STRIKE
MAGNETIC DOOR LOCK
ACCESS CONTROL PANEL
ML
ES
CR
SECURITY SYMBOLS
ACCESS CONTROL
INTRUSION DETECTION
SURVEILLANCE
DOOR CONTACT SWITCH
KEYPAD
GLASS BREAK ALARM
AUDIBLE SIREN/HORN
VOICE OUTLET(S);
REFER TO ABBREVIATIONS (X)
REQUEST TO EXITREX
MASTER INTERCOM STATION
MOTION DETECTOR
SOUND DETECTOR
AS
GB
KP
M
SD
DATA AND VOICE OUTLET(S);
REFER TO ABBREVIATIONS (X)
DATA OUTLET(S);
REFER TO ABBREVIATIONS (X)
SPECIALTY OUTLET(S);
REFER TO ABBREVIATIONS (X)
TELEVISION CATV OUTLET
X
X/X
X
X/X
TV
FLOOR SERVICE FITTING WITH OUTLET(S);
REFER TO SCHEDULE (X)
POKE-THRU ASSEMBLY WITH OUTLET(S);
REFER TO SCHEDULE (X)
TELEPOWER POLE WITH OUTLET(S);
REFER TO SCHEDULE (X)
CABLE TRAY
SOUND SYSTEM VOLUME CONTROLLERVC
AUDIO AMPLIFIER UNITAMP
PUBLIC ADDRESS SPEAKER WITH CLOCK IN
COMMON ENCLOSURE
CEILING OR WALL-MOUNTED SPEAKER.
REFER TO ABBREVIATIONS (X)
FLOOR OR WALL-MOUNTED SOUND
SYSTEM MICROPHONE
FLUSH WALL-MOUNTED CLOCK
PLYWOOD BACKBOARD
TELECOMMUNICATIONS EQUIPMENT RACK
(FOUR POST)
TELECOMMUNICATIONS EQUIPMENT RACK
(TWO POST)
TELECOMMUNICATIONS GROUNDING BUSBAR
(TGB)
RACEWAY UP / DOWN
S S
M M
C
X X
G
C S
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE SPLIT WIRED
DOUBLE DUPLEX RECEPTACLE
SINGLE RECEPTACLE
SPECIAL PURPOSE RECEPTACLE; VERIFY
NEMA CONFIGURATION WITH EQUIPMENT
*
*
*
*
*
* = a, b, clg, AF, GF IG OR TP. WHEN
TAGGED IN THE ELECTRICAL SYMBOL LIST,
REFER TO THE ABBREVIATION LIST
*
AD
AD
T
ELR
MIC
INTERCOM STATIONIC
ACP
DOOR OPERATORDO
PUSH PLATEPP
ELECTRONIC DOOR HARDWIRINGEH
INTRUSION DETECTION PANELIDP
FLOW METERFM
LV-1
HOME RUN
PANEL DESIGNATION
20A-1P HOME RUN (TYPICAL)
LV-1
XP/XXA HOME RUN
PANEL DESIGNATION
POLES/AMPERAGE
HOME RUN
LV-1
1,2,3
PANEL DESIGNATION
CIRCUIT NUMBERS
P
P
T
T
A
TP-X TELEPOWER POLE WITH OUTLET(S);
REFER TO SCHEDULE (X)
FB-X
PT-X
TP-X
VIDEO SURVEILLANCE FIXED CAMERA WITH
HARDWARE
VIDEO SURVEILLANCE PAN/TILT/ZOOM DOME
CAMERA WITH HARDWARE
VIDEO SURVEILLANCE FIXED DOME CAMERA
WITH HARDWARE
VIDEO MONITOR
NETWORK VIDEO RECORDER
DIGITAL VIDEO RECORDER
VIDEO SURVEILLANCE FIXED CORNER CAMERA
WITH HARDWARE
VM
NVR
DVR
BACKBONE COAX CABLING
BACKBONE FIBER CABLING
BACKBONE UTP COPPER CABLING
HORIZONTAL COAX CABLING
HORIZONTAL UTP COPPER CABLING
CROSS-CONNECT
EQUIPMENT RACK
XXX
X
RISER DIAGRAM SYMBOLS
180° VIDEO SURVEILLANCE DOME CAMERA
WITH HARDWARE
360° VIDEO SURVEILLANCE DOME CAMERA
WITH HARDWARESDGROUNDING BUSBARG
DOOR OPERATOR
PUSH PLATE
ENCLOSED SWITCH
ELECTRIC MOTOR
JUNCTION BOX
MASTER FIRE ALARM PULL BOX
VOICE FIRE ALARM CONTROL PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR
SMOKE DETECTOR
HEAT DETECTOR
REMOTE INDICATOR
FIRE ALARM MANUAL PULL STATION
FIRE ALARM HORN / STROBE
FIRE ALARM SPEAKER / STROBE
FIRE ALARM CHIME / STROBE
FIRE ALARM STROBE
FIRE ALARM CEILING-MOUNTED SPEAKER
FIREFIGHTER'S TELEPHONE JACK
PP
DO
C
H
F
H
S
J
F
F
F
RI
ANN
FACP
VFACP
WALL CLOCK WITH HANGER TYPE OUTLET
B PROGRAM BELL
C
CODE BLUE STATION
NURSE CALL PATIENT STATION
NURSE CALL DUTY STATION
NURSE CALL STAFF STATION
NURSE CALL EMERGENCY STATION
NURSE CALL STAFF ASSISTANT STATION
NURSE CALL AUXILIARY ALARM INPUT
STATION
MASTER NURSE CALL STATION
MAIN NURSE CALL EQUIPMENT STATION
NURSE CALL CORRIDOR LIGHT (CEILING
OR WALL-MOUNTED)
CB
NP
ND
NS
NC
NA
NI
MNS
MNC
N N
NURSE CALL SYMBOLS
CALL-FOR-AID SWITCH W/ CORDE
CALL-FOR-AID LIGHT AND BUZZER
MAGNETIC DOOR LOCKML
COMBINATION SMOKE/CARBON MONOXIDE
DETECTIRS CO
ELECTRICAL SYMBOLS
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085
NONE
8/16/2016 11:26:05 AMMEP-100
185-01-00
8/15/16
MEP GENERAL NOTES,
ABBREVIATIONS, AND
SYMBOL LISTS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
1 2016.07.08 ADDENDUM #1
NOTE:
THIS DETAIL IS FOR ALL EQUIPMENT SPECIFIED WITH VARIABLE FREQUENCY
CONTROLLERS, CONTRACTOR TO PROVIDE WIRING BETWEEN REMOTE DISCONNECTS,
STARTERS AND MOTORS. SEE EQUIPMENT SCHEDULES AND SPECIFICATIONS.
TYPICAL MOTOR CONTROLLER AND VFC DETAIL
NOT TO SCALE
EQUIPMENT MOTOR
(NOT SPECIFICALLY
INDICATED ON FLOOR
PLANS)
EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
TERMINAL BOX
EQUIPMENT TAG
BRANCH CIRCUIT PER DIVISION 26
SPECIFICATIONS. RACEWAY MUST
BE METALLIC. PVC NOT ALLOWED
THE CONTRACTOR WHO FURNISHES
EQUIPMENT REQUIRING A VARIABLE
FREQUENCY CONTROLLER TO FURNISH
THE VARIABLE FREQUENCY
CONTROLLER WITH ALL OPTIONS AND
ACCESSORIES PER DIVISION 26.
"VARIABLE FREQUENCY CONTROLLERS."
MOUNT ADJACENT TO EQUIPMENT IN
SIGHT OF MOTOR
SEE DIVISION 26
SPECIFICATIONS FOR
BRANCH CIRCUIT
REQUIREMENTS AND MEP
SCHEDULES FOR SIZING
CONTROL WIRING
NON-FUSED ENCLOSED
SWITCH PER DIVISION 26
SPECIFICATIONS WITH
AUXILIARY CONTACTS. MOUNT
IN SIGHT OF EQUIPMENT
MOTOR. PROVIDE ONLY
WHENEVER CONTROLLER AND
SWITCH CANNOT BE MOUNTED
WITHIN SIGHT OF EQUIPMENT
VFC
TYPICAL MOTOR CONTROLLER AND VFC DETAIL TYPICAL MOTOR, SWITCH AND CONTROLLER DETAIL
EQUIPMENT TAG
NOT TO SCALE
BRANCH CIRCUIT PER DIVISION 26
SPECIFICATIONS. PROVIDE ADDITIONAL
WIRING AS REQUIRED TO MATCH
CONTROLLER
THE CONTRACTOR WHO FURNISHES
EQUIPMENT REQUIRING A MOTOR
CONTROLLER TO FURNISH MOTOR
CONTROLLERS FOR ALL MOTORS
WITH ALL SPECIFIED OPTIONS AND
ACCESSORIES PER DIVISION 26
SPECIFICATIONS. MOUNT ADJACENT
TO EQUIPMENT
FUSED ENCLOSED SWITCH PER
DIVISION 26 SPECIFICATIONS.
MOUNT IN SIGHT OF MOTOR
CONTROLLER.
EQUIPMENT MOTOR
(NOT SPECIFICALLY
INDICATED ON FLOOR
PLANS)
SEE DIVISION 26
SPECIFICATIONS FOR BRANCH
CIRCUIT REQUIREMENTS AND
MEP SCHEDULES FOR SIZING
BRANCH CIRCUIT PER
DIVISION 26
SPECIFICATIONS
NON-FUSED ENCLOSED
SWITCH PER DIVISION 26
SPECIFICATIONS WITH
AUXILIARY CONTACTS. MOUNT
IN SIGHT OF EQUIPMENT
MOTOR. PROVIDE ONLY
WHENEVER CONTROLLER
AND SWITCH CANNOT BE
MOUNTED WITHIN SIGHT OF
EQUIPMENT
NOTE:
THIS DETAIL IS FOR ALL EQUIPMENT MOTORS. CONTRACTOR TO PROVIDE WIRING
BETWEEN REMOTE DISCONNECTS, STARTERS AND MOTORS. SEE EQUIPMENT SCHEDULES
AND SPECIFICATIONS. IF NOT NOTED OTHERWISE IN EQUIPMENT SCHEDULES,
CONTRACTOR SHALL PROVIDE A COMBINATION MOTOR CONTROLLER/DISC. SWITCH.
EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
TERMINAL BOX
TYPICAL MOTOR, SWITCH AND CONTROLLER DETAIL TYPICAL EQUIPMENT CONNECTION DETAIL
NOT TO SCALE
FUSED ENCLOSED
SWITCH PER DIVISION 26
SPECIFICATIONS. MOUNT
IN SIGHT OF EQUIPMENT
MOTOR
NOTE:
THIS DETAIL IS FOR ALL EQUIPMENT WHERE EQUIPMENT REQUIRES POWER AND WHERE
THERE ARE NO MOTORS INVOLVED OR WHERE SPECIFICATIONS OR SCHEDULES FOR
MULTIPLE MOTOR EQUIPMENT SPECIFICALLY INDICATE ONE POINT POWER CONNECTION.
CONTRACTOR TO PROVIDE WIRING BETWEEN REMOTE DISCONNECTS, STARTERS AND
MOTORS. SEE EQUIPMENT SCHEDULES AND SPECIFICATIONS.
EQUIPMENT TAG EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
BRANCH CIRCUIT PER DIVISION
26 SPECIFICATIONS
SEE DIVISION 26 SPECIFICATIONS
FOR BRANCH CIRCUIT
REQUIREMENTS AND MEP
SCHEDULES FOR SIZING
TERMINAL BOX
TYPICAL EQUIPMENT CONNECTION DETAIL TYPICAL UNIT SMOKE/EMERGENCY SHUTDOWN CONTROL DETAIL
EQUIPMENT TAGAIR DISTRIBUTION UNIT
OR EXHAUST FAN
MOTOR CONTROL INTERLOCK
WIRING, PER DIVISION 23 "HVAC
INSTRUMENTATION AND CONTROL"
NOT TO SCALE
EQUIPMENT MOTOR (NOT
SPECIFICALLY INDICATED
ON FLOOR PLANS).
FIRE ALARM SYSTEM WIRING PER
DIVISION 28 "FIRE ALARM"
NOTE:
APPLY THIS DETAIL TO THE SYSTEM DIAGRAMS ON THIS DRAWING FOR A COMPLETE SYSTEM.
FACP
EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
MOTOR CONTROLLER (UNIT
OR REMOTE MOUNTED)
FIRE ALARM SYSTEM ADDRESSABLE
INTERFACE DEVICE PER DIVISION 28
"FIRE ALARM". LOCATE WITHIN 3 L.F.
OF CONTROLLER.
FIRE ALARM CONTROL PANEL PER
DIVISION 28 "FIRE ALARM". PROVIDE
MANUAL EMERGENCY SHUT DOWN
SWITCH FOR EACH UNIT REQUIRING
EMERGENCY SHUT DOWN
AID
TYPICAL UNIT SMOKE/EMERGENCY SHUTDOWN CONTROL DETAIL
DS
NOT TO SCALE
TYPICAL SMOKE DAMPER ISOLATION CONTROL DETAIL
SMOKE DAMPER
POWER WIRING PER
DIVISION 23 "HVAC
INSTRUMENTATION
AND CONTROL"
SMOKE DAMPER OR COMBINATION
SMOKE/FIRE DAMPER PER DIVISION
23 "DUCT ACCESSORIES"
SMOKE DAMPER INTERLOCK
WIRING PER DIVISION 23 "HVAC
INSTRUMENTATION AND
CONTROL"
NOTE:
APPLY THIS DETAIL TO THE SYSTEM DIAGRAMS ON THIS DRAWING FOR A COMPLETE SYSTEM.
DAMPER END SWITCHES PER
DIVISION 23 "DUCT ACCESSORIES"
(OPEN AND CLOSED DAMPER
POSITIONS)
ATC SYSTEM WIRING FROM END
SWITCHES PER DIVISION 23 "HVAC
INSTRUMENTATION AND CONTROL"
FIRE ALARM SYSTEM DUCT SMOKE
DETECTOR WITH ADDRESSABLE
RELAY PER DIVISION 28 "FIRE
ALARM", LOCATE WITHIN 3 L.F. OF
DAMPER
FIRE ALARM SYSTEM
WIRING PER DIVISION
28 "FIRE ALARM"
HVAC DUCT
END SWITCH INTERLOCK WIRING
PER DIVISION 23 "HVAC
INSTRUMENTATION AND CONTROL"
SD
AID
AID
TYPICAL SMOKE DAMPER ISOLATION CONTROL DETAIL
EF
EXHAUST FAN EMERGENCY SHUTDOWN SYSTEM DIAGRAM
FACP
NOTES:
1. SEE UNIT EMERGENCY SHUTDOWN CONTROL DETAILS FOR ADDITIONAL INFORMATION.
2. THIS DIAGRAM APPLIES TO ALL EXHAUST FANS 2000 CFM AND GREATER, EXCEPT
SPECIALTY EXHAUST FANS SUCH AS GREASE, FUME, HAZARDOUS AND INDUSTRIAL.
3. SEE LISTED CFM IN EQUIPMENT SCHEDULES TO DETERMINE EXHAUST FANS OVER 2000 CFM.
EXHAUST DUCT
MOTOR CONTROL
INTERLOCK WITH
FIRE ALARM
FIRE ALARM SYSTEM
WIRING PER DIVISION
28 "FIRE ALARM"
NOT TO SCALE
MOTOR CONTROLLER
(UNIT OR REMOTE MOUNTED)
FIRE ALARM SYSTEM
ADDRESSABLE
INTERFACE DEVICE
FIRE ALARM CONTROL
PANEL W/ MANUAL
EMERGENCY SHUT
DOWN SWITCH
AID
EXHAUST FAN EMERGENCY SHUTDOWN SYSTEM DIAGRAM
EQUIPMENT MOTOR
(NOT SPECIFICALLY
INDICATED ON FLOOR
PLANS)
NON-FUSED ENCLOSED
SWITCH PER DIVISION 26
SPECIFICATIONS WITH
AUXILIARY CONTACTS.
MOUNT IN SIGHT OF
EQUIPMENT MOTOR.
PROVIDE ONLY WHENEVER
CONTROLLER AND SWITCH
CANNOT BE MOUNTED WITHIN
SIGHT OF EQUIPMENT
SEE DIVISION 26 SPECIFICATIONS
FOR BRANCH CIRCUIT
REQUIREMENTS AND MEP
SCHEDULES FOR SIZING
TYPICAL COMBINATION MOTOR CONTROLLER/DISC SWITCH DETAIL
NOTE:
THIS DETAIL IS FOR ALL EQUIPMENT MOTORS. CONTRACTOR TO PROVIDE
WIRING BETWEEN REMOTE COMBINATION MOTOR CONTROLLER/ DISC SWITCH
AND MOTORS. SEE EQUIPMENT SCHEDULES AND SPECIFICATIONS. IF NOT
NOTED OTHERWISE IN EQUIPMENT SCHEDULES, CONTRACTOR SHALL
PROVIDE A COMBINATION MOTER CONTROLLER/DISC. SWITCH.
EQUIPMENT TAG
NOT TO SCALE
EQUIPMENT TAG REFERENCES
MEP AND OWNER SCHEDULES
BRANCH CIRCUIT PER DIVISION 26
SPECIFICATIONS. PROVIDE
ADDITIONAL WIRING AS REQUIRED
TO MATCH CONTROLLER
THE CONTRACTOR WHO FURNISHES
EQUIPMENT REQUIRING A COMBINATION
MOTOR CONTROLLER/DISC SWITCH TO
FURNISH MOTOR CONTROLLERS FOR ALL
MOTORS WITH ALL SPECIFIED OPTIONS
AND ACCESSORIES PER DIVISION 26
SPECIFICATIONS. MOUNT ADJACENT TO
EQUIPMENT. DEVICE TO BE FUSED
TERMINAL BOX
TYPICAL COMBINATION MOTOR CONTROLLER/DISC SWITCH DETAIL
SIDE ELEVATIONFRONT ELEVATION
REDUCED PRESSURE
ZONE BACKFLOW
PREVENTER
STRAINER
MIN 30"MAX 60"MIN 18"UNION (TYPICAL)
BALL VALVE (TYPICAL)
OUTLET
PIPE DISCHARGE
LINE TO OUTSIDE
F.D. OR RECEPTOR
TEST COCK (TYPICAL)
AIR GAP FITTING
FINISH FLOOR
MAINTAIN 8" (MINIMUM)
CLEAR SPACE OFF THE
WALL TO THE RPD
MAINTAIN 12" (MINIMUM)
CLEAR SPACE ABOVE RPD
MAINTAIN A 30" (MIN.) DEEP X THE
LENGTH OF THE RPD ASSEMBLY -
CLEAR SPACE IN FRONT OF RPD
OUTLET
INLET
NOT TO SCALE
TYPICAL REDUCED PRESSURE ZONE BACKFLOW PREVENTER INSTALLATION DETAIL
NOTES:
1. REFER TO DRAWINGS FOR UNIT SIZE(S).
2. THE RPD MOUNTING HEIGHT AND CLEARANCES INDICATED ABOVE SHALL BE MAINTAINED FOR PROPER ACCESS TO UNIT FOR
MAINTENANCE, TESTING AND INSPECTION PURPOSES.
3. THE LOCATION AND MOUNTING HEIGHT OF THE RPD SHALL BE APPROVED BY THE WATER COMPANY PRIOR TO INSTALLATION.
4. ACCESS TO THIS UNIT SHALL NOT REQUIRE THE USE OF A LADDER OR REMOVAL OF CEILING TILES OR OTHER PERMANENT OR SEMI-
PERMANENT CONSTRUCTION.
5. DO NOT INSTALL UNIT ABOVE A CEILING.
6. THE AREA WHERE THE RPD IS TO BE INSTALLED SHALL BE WELL LIT, PROVIDED WITH ADEQUATE DRAINAGE AND SHALL NOT BE SUBJECT
TO FLOODING.
NOTE:
ALL ASSEMBLIES SHALL BE ADEQUATELY SUPPORTED AND/OR RESTRAINED TO PREVENT LATERAL MOVEMENT. PIPE HANGERS, BRACES, SADDLES,
STANCHIONS, PIERS, ETC., SHOULD BE USED TO SUPPORT THE DEVICE AND SHOULD BE PLACED IN A MANNER THAT WILL NOT OBSTRUCT THE FUNCTION
OF OR ACCESS TO THE RELIEFT VALVE, TEST PORTS OR VALVES.
0
0
0
0
0
TYPICAL REDUCED PRESSURE ZONE BACKFLOW PREVENTER INSTALLATION DETAIL TYPICAL DOUBLE CHECK VALVE BACKFLOW PREVENTER INSTALLATION DETAIL
INLET
FRONT ELEVATION SIDE ELEVATION
NOT TO SCALE
DOUBLE CHECK VALVE FOR
FIRE PROTECTION SERVICE -
WHERE NO CHEMICALS ARE
USED (USE RPD WHERE
CHEMICALS ARE USED)
OS&Y GATE
VALVE (TYPICAL)
MAINTAIN 12" (MINIMUM)
CLEAR SPACE ABOVE DCV
MAINTAIN A 30" (MINIMUM)
DEEP X THE LENGTH OF THE
DCV ASSEMBLY - CLEAR
SPACE IN FRONT OF DCV
FINISH FLOOR MAX 60"MIN 30"MAINTAIN 8"
MINIMUM CLEAR
SPACE OFF THE
WALL TO DCV
NOTES:
1. REFER TO DRAWINGS FOR UNIT SIZE(S).
2. THE DCV MOUNTING HEIGHT AND CLEARANCES INDICATED ABOVE SHALL BE MAINTAINED FOR PROPER ACCESS TO UNIT FOR
MAINTENANCE, TESTING AND INSPECTION PURPOSES.
3. THE LOCATION AND MOUNTING HEIGHT OF THE DCV SHALL BE APPROVED BY THE WATER COMPANY PRIOR TO INSTALLATION.
4. ACCESS TO THIS UNIT SHALL NOT REQUIRE THE USE OF A LADDER OR REMOVAL OF CEILING TILES OR OTHER PERMANENT OR SEMI-
PERMANENT CONSTRUCTION.
5. DO NOT INSTALL UNIT ABOVE A CEILING.
6. THE AREA WHERE THE DCV IS TO BE INSTALLED SHALL BE WELL LIT, PROVIDED WITH ADEQUATE DRAINAGE AND SHALL NOT BE SUBJECT
TO FLOODING.
NOTE:
ALL ASSEMBLIES SHALL BE ADEQUATELY SUPPORTED AND/OR RESTRAINED TO PREVENT LATERAL MOVEMENT. PIPE HANGERS, BRACES, SADDLES,
STANCHIONS, PIERS, ETC., SHOULD BE USED TO SUPPORT THE DEVICE AND SHOULD BE PLACED IN A MANNER THAT WILL NOT OBSTRUCT ACCESS TO
THE TESTING PORTS OR VALVES.
OUTLET
0
000
TYPICAL DOUBLE CHECK VALVE BACKFLOW PREVENTER INSTALLATION DETAIL
FIRE ALARM SYSTEM WIRING
PER DIVISION 28 "FIRE ALARM"
NOTE:
APPLY THIS DETAIL TO THE SYSTEM DIAGRAMS ON THIS DRAWING
FOR A COMPLETE SYSTEM.
TYPICAL DUCT SMOKE DETECTOR DETAIL
HVAC DUCT
DUCT SMOKE DETECTOR
W/SAMPLING TUBES PER
DIVISION 28 FIRE ALARM,
MOUNTED PER DIVISION
23/28 "METAL DUCTS"
NOT TO SCALE
DS
TYPICAL DUCT SMOKE DETECTOR DETAIL
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085
NOT TO SCALE
8/16/2016 11:26:07 AMMEP-101
185-01-00
8/15/16
MEP DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
SHUT OFF SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
TAG SIZE CFM RANGE
HEATING COIL PERFOMANCE
NOM. CFM ROWS LAT GPM PIPE SIZE
A 06 0-400 300 2 90 1 3/4"
A1 06 0-400 NONE NONE NONE NONE NONE
B 08 401-800 600 2 90 2 3/4"
B1 08 401-800 NONE NONE NONE NONE NONE
C 10 801-1200 900 2 90 3 1"
C1 10 801-1200 NONE NONE NONE NONE NONE
D 12 1201-1700 1275 2 90 4 1"
D1 12 1201-1700 NONE NONE NONE NONE NONE
E 14 1701-2300 1725 2 90 6 1"
E1 14 1701-2300 NONE NONE NONE NONE NONE
F 16 2301-3100 2325 2 90 8 1-1/4"
F1 16 2301-3100 NONE NONE NONE NONE NONE
GENERAL NOTES:
AIR TERMINAL UNITS ARE BASED ON ENVIRO-TEC
0.5% MAXIMUM ALLOWABLE STATIC PRESSURE DROP FOR BOX AND REHEAT COIL
HEATING COIL PERFORMANCE BASED ON NOMINAL CFM LISTED IN THE SCHEDULE @ 50° DEGREE F. ENTERING TEMPERATURE,
180° DEGREE F. ENTERING WATER TRMPERATURE, 150° DEGREE F. LEAVING WATER TEMPERATURE
PERFORMANCE DATA TAG AIR TERMINAL UNIT TAG
MAXIMUM COOLING CFM A ID TYPE
MINIMUM COOLING CFM
HEATING CFM
GRILLE AND DIFFUSER SCHEDULE
CEILING SUPPLY DIFFUSER DUCTED CEILING RETURN
/ EXHAUST GRILLE
NON-DUCTED CEILING
RETURN / EXHAUST
GRILLE
FLEXIBLE DUCT SIZES TO
SUPPLY DIFFUSERS
CFM SQUARE
NECK SIZE
ROUND
NECK SIZE CFM NECK SIZE CFM NECK SIZE CFM SIZE
0-100 6 x 6 6"Ø 0-150 6 x 6 0-350 12 x 12 0-100 6"Ø
101-250 9 x 9 8"Ø 151-350 351-1200 22 x 22 101-250 8"Ø
251-400 12 x 12 10"Ø 351-650 251-400 10"Ø
401-600 15 x 15 12"Ø 651-1000 401-600 12"Ø
601-800 18 x 18 14"Ø 601-800 14"Ø
TYPE MODEL DESCRIPTION
A1 TDC SQUARE LOUVER FACE CEILING SUPPLY DIFFUSER WITH REMOVABLE CORE, LAY-IN, 1-WAY
THROW. TRANSITIONAL ADAPTER.
A2 TDC SQUARE LOUVER FACE CEILING SUPPLY DIFFUSER WITH REMOVABLE CORE, LAY-IN, 2-WAY
CORNER THROW. TRANSITIONAL ADAPTER.
A3 TDC SQUARE LOUVER FACE CEILING SUPPLY DIFFUSER WITH REMOVABLE CORE, LAY-IN, 3-WAY
THROW. TRANSITIONAL ADAPTER.
A4 TDC SQUARE LOUVER FACE CEILING SUPPLY DIFFUSER WITH REMOVABLE CORE, LAY-IN, 4-WAY
THROW. TRANSITIONAL ADAPTER.
A5 TDC SQUARE LOUVER FACE CEILING SUPPLY DIFFUSER WITH REMOVABLE CORE, LAY-IN, 2-WAY
OPPOSITE THROW. TRANSITIONAL ADAPTER.
AA 122 RL EXTRUDED ALUMINUM DOUBLE DEFLECTION SIDEWALL SUPPLY GRILLE. 2" ADJUSTABLE
(AIRFLOW) SPACING. FRONT BLADES PARALLEL TO LONG DIMENSION.
B 355 RL LOUVER TYPE CEILING/WALL RETURN OR EXHAUST GRILLE, 35° FIXED DEFLECTION, 1/2"
SPACING WITH BLADES PARALLEL TO THE LONG DIMENSION.
BB 112 RL EXTRUDED ALUMINUM DOUBLE DEFLECTION SIDEWALL SUPPLY GRILLE. 1-1/4" ADJUSTABLE
(AIRFLOW) SPACING. FRONT BLADES PARALLEL TO LONG DIMENSION.
PLUMBING FIXTURE SCHEDULE
TYPE FIXTURE SOIL VENT COLD HOT MOUNT DESCRIPTION
WC-1 WATER CLOSET -
PATIENT - ADA
4" 2" 1" - WALL AMERICAN STANDARD "AFWALL MILLENNIUM FLOWISE
ELONGATED" #3351.101, WALL HUNG WATER CLOSET.
TOTO #TET1GNC-32 HYDROPOWER SELF GENERATING
ELECTRONIC FLUSHOMETER, WITH 1" ANGLE STOP AND
1 1/2" VACUUM BREAKER, 1.6 GPF, MANUAL OVERRIDE,
24 HOUR AUTOMATIC FLUSH FOR TRAP SEAL
PROTECTION. OLSONITE #95SSC WHITE OPEN FRONT
SEAT LESS COVER, SELF-SUSTAINING CHECK HINGE.
PROVIDE ADJUSTABLE VERTICAL SIPHON JET 500 LB
NO-HUB CARRIER WITH HEAVY DUTY REAR ANCHOR TIE
DOWN ZURN #Z1204-N4-X.
WC-2 WATER CLOSET -
STAFF - ADA
4" 2" 1" - WALL AMERICAN STANDARD "AFWALL MILLENNIUM FLOWISE
ELONGATED" #3351.101, WALL HUNG WATER CLOSET.
SLOAN #111-1.6 MANUAL FLUSH VALVE. OLSONITE
#95SSC WHITE OPEN FRONT SEAT LESS COVER,
SELF-SUSTAINING CHECK HINGE. PROVIDE ADJUSTABLE
VERTICAL SIPHON JET 500 LB NO-HUB CARRIER WITH
HEAVY DUTY REAR ANCHOR TIE DOWN ZURN
#Z1204-N4-X.
WC-3 WATER CLOSET -
PATIENT - ADA
4"2" 1"-FLOOR AMERICAN STANDARD "RIGHT WIDTH FLOWISE
ELONGATED" #3641.001, FLOOR MOUNTED WATER
CLOSET. TOTO #TET1GNC-32 HYDROPOWER SELF
GENERATING ELECTRONIC FLUSHOMETER, WITH 1"
ANGLE STOP AND 1 1/2" VACUUM BREAKER, 1.6 GPF,
MANUAL OVERRIDE, 24 HOUR AUTOMATIC FLUSH FOR
TRAP SEAL PROTECTION. OLSONITE #95SSC WHITE
OPEN FRONT SEAT LESS COVER, SELF-SUSTAINING
CHECK HINGE.
LV-1 LAVATORY -
PATIENT & STAFF -
ADA
1 1/2" 1 1/2" 1/2" 1/2"WALL AMERICAN STANDARD LUCERNE WALL HUNG LAVATORY
#0355.012, WITH FAUCET HOLES 4" CENTERS. CHICAGO
FAUCETS #895-317GN2FCAB HOT AND COLD WATER
FAUCET, 1.5 GPM LAMINAR FLOW CONTROL INSERT IN
SPOUT OUTLET, 5 1/4" RIGID / SWING GOOSENECK
FAUCET, 4" WRISTBLADE HANDLES. SUPPLY RISERS
SHALL BE 1/2"THD TYPE "L" COPPER WITH KEYSTOPS.
PROVIDE CAST BRASS 17 GAUGE P- TRAP.TRUEBRO
#82525 "SOFT-GUARD PLUS" INSULATION KIT. PROVIDE
CONCEALED ARM CARRIER ZURN #1231 TO SUPPORT
250 LB LOAD CAPACITY.
SK-1 HAND WASH SINK -
VARIOUS AREAS
1 1/2" 1 1/2" 1/2" 1/2" COUNTER ELKAY "LUSTERTONE" GOURMET STAINLESS STEEL
SINGLE BOWL TOP MOUNT QUICK-CLIP SINK
#LRADQ172055, OVERALL DIMENSIONS 17"x20"x5-1/2", 18
GAUGE 304 STAINLESS STEEL, REAR CENTER DRAIN.
CHICAGO FAUCETS #786-GN8FCXKABCP, DECK
MOUNTED 8" FIXED CENTERS CONCEALED HOT AND
COLD WATER FAUCET, 8" FLOW CONTROL RIGID / SWING
GOOSENECK SPOUT, 4" WRISTBLADE HANDLES, 1/4
TURN OPERATING CARTRIDGE, 1.5 GPM LAMINAR FLOW
CONTROL INSERT IN SPOUT OUTLET. SUPPLY RISERS
SHALL BE 1/2"THD TYPE "L" COPPER WITH KEYSTOPS.
PROVIDE CAST BRASS 17 GAUGE P- TRAP.
SK-2 SOILED
WORKROOM SINK
1 1/2" 1 1/2" 1/2" 1/2" FLOOR AMERICAN STANDARD LUCERNE WALL HUNG LAVATORY
#0356.015, WITH FAUCET HOLES 8" CENTERS. CHICAGO
FAUCETS #786-GN2FCXKABCP HOT AND COLD WATER
FAUCET, 1.5 GPM LAMINAR FLOW CONTROL INSERT IN
SPOUT OUTLET, 5 1/4" RIGID / SWING GOOSENECK
FAUCET, 4" WRISTBLADE HANDLES. SUPPLY RISERS
SHALL BE 1/2"THD TYPE "L" COPPER WITH KEYSTOPS.
PROVIDE CAST BRASS 17 GAUGE P- TRAP.TRUEBRO
#82525 "SOFT-GUARD PLUS" INSULATION KIT. PROVIDE
CONCEALED ARM CARRIER ZURN #1231 TO SUPPORT
250 LB LOAD CAPACITY.
SK-3 STAFF BREAK
ROOM &
STRETCHER
WAITING ROOM
SINK
1 1/2" 1 1/2" 1/2" 1/2" COUNTER ELKAY "LUSTERTONE" GOURMET STAINLESS STEEL
SINGLE BOWL TOP MOUNT QUICK-CLIP SINK
#LRADQ172055, OVERALL DIMENSIONS 17"x20"x5-1/2", 18
GAUGE 304 STAINLESS STEEL, REAR CENTER DRAIN.
CHICAGO FAUCETS #786-GN8FCXKABCP, DECK
MOUNTED 8" FIXED CENTERS CONCEALED HOT AND
COLD WATER FAUCET, 8" FLOW CONTROL RIGID / SWING
GOOSENECK SPOUT, 4" WRISTBLADE HANDLES, 1/4
TURN OPERATING CARTRIDGE, 1.5 GPM LAMINAR FLOW
CONTROL INSERT IN SPOUT OUTLET. SUPPLY RISERS
SHALL BE 1/2"THD TYPE "L" COPPER WITH KEYSTOPS.
PROVIDE CAST BRASS 17 GAUGE P- TRAP.
PLUMBING SPECIALTIES SCHEDULE
TYPE SPECIALTY ITEM DESCRIPTION
WB-1 WATER / WASTE
CONNECTION BOX
GUY GRAY MODEL #MWB26 CENTER DRAIN 20 GAUGE STEEL RECESSED BOX WITH POWDER
COATED FINISH, 1/2" QUARTER TURN WATER SUPPLY VALVE WITH HOSE CONNECTION AND
2" SLIPNUT DRAIN CONNECTION.
ZVB ZONE VALVE BOX BEACON MEDAES ZVB2-EF-ENG #4107219442 TWO VALVE BOX 1 1/2" & 2" (MV, O2) GAUGES
AND SENSORS REQUIRED SHALL BE BEACON MEDAES (1) #4107655177 & (1) #4107655178.
V, O, S MEDICAL GAS WALL
OUTLETS/INLETS &
SLIDES
BEACON MEDAES GEMINI 3-QUICK CONNECT OUTLETS, INLETS AND SLODES AS FOLLOWS:
OXYGEN-#234510-00 ROUGH-IN ASSEMBLY AND #234610-00 FINAL ASSEMBLY
MED VAC-#234513-00 ROUGH-IN ASSEMBLY AND #234613-00 FINAL ASSEMBLY
SLIDE-#234500-00 ROUGH-IN ASSEMBLY AND #234500-00 FINAL ASSEMBLY
SA-1 WATER HAMMER
ARRESTOR
PRECISION PLUMBING PRODUCTS MODEL #SC-750B SYSTEM RATED WATER HAMMER
ARRESTOR
SA-2 WATER HAMMER
ARRESTOR
PRECISION PLUMBING PRODUCTS MODEL #SC-500A SYSTEM RATED WATER HAMMER
ARRESTOR
PUMP SCHEDULE
TAG MFR TYPE
SERIES / SIZE
MODEL NO.
MINIMUM
EFFICIENCY GPM FT OF HEAD
(TDH)
P-1 BELL & GOSSETT END SUCT. 1510 2 1/2 BB 75.5 225 75
P-2 BELL & GOSSETT END SUCT. 1510 2 1/2 BB 75.5 225 75
TAG RPM
MOTOR
HP VFC SERVES OPERATION
P-1 1750 7.5 YES HEATING HOT WATER RUN
P-2 1750 7.5 YES HEATING HOT WATER STANDBY
ELECTRICAL
TAG VOLTS /
PHASE HOME RUN BRANCH CIRCUIT SIZE SW / FUSE
P-1 480/3 SEE FLOOR PLANS SEE FLOOR PLANS -
P-2 480/3 SEE FLOOR PLANS SEE FLOOR PLANS -
PROVIDE MAXIMUM IMPELLER DIAMETER FOR NON-OVERLOADING PERFORMANCE FOR SPECIFIED HORSEPOWER.
TRIM AND BALANCE IMPELLER AFTER SYSTEM HAS BEEN INSTALLED AND OPERATED
AIR COOLED CONDENSING UNIT SCHEDULE
TAG MFR MODEL
AMBIENT
TEMP (°F)
CAPACITY
(TONS)
REFRIGERANT
TYPE
SUCTION
TEMP (°F)
CU-S1 TRANE TTA120H4 95 10 R-410A 45
CU-S2 TRANE TTA073G4 95 6 R-410A 45
TAG NUMBER OF REFRIG.
CIRCUITS
NUMBER OF
STEPS UNLOADING EER MCA MDP SERVES
CU-S1 2 2 11.5 21.9 X DX-S1
CU-S2 2 2 13 15 X DX-S2
ELECTRICAL
TAG VOLTS / PHASE HOME RUN BRANCH CIRCUIT SIZE SW / FUZE
CU-S1 460/3 SEE FLOOR PLANS SEE FLOOR PLANS 30A/25A
CU-S2 460/3 SEE FLOOR PLANS SEE FLOOR PLANS 20A/20A
REFRIGERANT COILS CHEDULE
TAG MFR / MODEL CFM
EAT
DB / WB (°F)
LAT
DB / WB (°F)
HEIGHT
(IN)
LENGTH
(IN)
DX-S1 TRANE / DFDB33 5600 71 / 62 55 / 55 33 90
DX-S2 TRANE / DFDB24 3000 71 / 62 55 / 55 24 60
TAG CAPACITY MBH
TOTAL/SENSIBLE
MAX VELOCITY
(FPM)
MAX APD
(IN WC)
NUMBER OF
CIRCUITS
REFRIGERANT
TYPE
MINIMUM
ROWS
DX-S1 126 / 98 265 0.201 QUARTER R-410A 4
DX-S2 71 / 53 288 0.202 HALF R-410A 4
PANELBOARD SCHEDULE
GENERAL NOTES:
1. SEE SPECIFICATION SECTION "PANELBOARDS" FOR FEATURES OF PANELBOARDS
2. VERIFY SIZE, QUANTITY AND TYPES OF CIRCUIT BREAKERS IN PANELBOARDS WITH PLANS, RISERS, SCHEDULES AND SPECIFICATION.
3. ALL PANELBOARDS ARE LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARDS UNLESS LISTED OTHERWISE.
NOTES:
A. SPD PANELBOARD.
B. DISTRIBUTION PANELBOARD.
C. PROVIDE PANELBOARD WITH ISOLATED EQUIPMENT GROUND BUS BAR.
D. PROVIDE PANELBOARD WITH STAINLESS STEEL TRIM AND DOOR.
E. PROVIDE PANELBOARD WITH INTEGRAL LIGHTING CONTACTOR.
F. PROVIDE PANELBOARD WITH AUXILIARY GUTTER.
G. PROVIDE 30 MA GROUND FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKERS.
H. PROVIDE 5 MA GROUND FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKERS.
I. PROVIDE PANELBOARD WITH NEMA 4X ENCLOSURE.
J. LIGHTING CONTROL PANEL WITH ABILITY TO TAKE INPUT FROM LOW VOLTAGE DEVICES (SWITCHES, OCCUPANCY SENSORS, ETC.).
PANELBOARD
NAME VOLTAGE MAIN OCPD
SIZE
MAIN BUS
SIZE MOUNTING POLE
CAPACITY
MIN. AISC
RATING NOTES CIRCUITS
AMPS POLES BRANCH FEEDER SPARE NOTES
SL1 208/120V 100A
MCB
100A SURFACE 60 22K 20 1 54 6
SL2 208/120V 200A
MCB
200A SURFACE 84 22K 40 2 3
20 1 16 16
30 2 3
20 2 2
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-0858/16/2016 11:26:08 AMMEP-102
185-01-00
8/15/16
MEP SCHEDULES
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
GENERAL NOTES:
1. BIDS SHALL BE BASED ON THE LUMINAIRE SCHEDULE BELOW AND THE SPECIFICATIONS. REFER TO THE ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
2. ALL LUMINAIRES BELOW ARE LED.
LUMINAIRE SCHEDULE
TYPE MANUFACTURER FIXTURE DESCRIPTION VOLTS
LAMPING
KELVIN OUTPUT
A1 METALUMEN "SCENE" SERIES
SCE2L40K22SDWL41T1NN OR APPROVED
EQUAL
2X2 RECESSED LED FLAT PANEL TROFFER. DIMMING DRIVER 120 V 4000 K 2290 LUMENS 24
WATTS
A2 METALUMEN "SCENE" SERIES
SCE2L40K22SDWL51T1NN OR APPROVED
EQUAL
2X2 RECESSED LED FLAT PANEL TROFFER. DIMMING DRIVER 120 V 4000 K 3280 LUMENS 37
WATTS
A3 METALUMEN "SCENE" SERIES
SCE2L40K22SDWL51T1NN OR APPROVED
EQUAL
2X2 RECESSED LED FLAT PANEL TROFFER. DIMMING DRIVER 120 V 4000 K 3280 LUMENS 37
WATTS
A4 KENALL "MAC" SERIES
MAC14G67L40KDCC1120IBHDAMF OR
APPROVED EQUAL
1X4 RECESSED LED LUMINAIRE WITH MATT WHITE REFLECTOR. DIMMING
DRIVER
120 V 4000 K 2095 LUMENS 72
WATTS
B1 H.E. WILLAMS '50' SERIES
50G-S22-L20/840-S-AF12125-X-DIM-UNV OR
APPROVED EQUAL
2X2 RECESSED LENSED LED TROFFER WITH 0.125" ACRYLIC DIFFUSER,
MATT WHITE REFLECTOR. DIMMING DRIVER
120 V 4000 K 2000 LUMENS 22
WATTS
C1 H.E. WILLIAMS "75L" SERIES
75L-4-L20/840-A12125-DRV-120 OR APPROVED
EQUAL
4' SURFACE MOUNTED LED STRIP LIGHT WITH ACRYLIC LENS 120 V 4000 K 2000 LUMENS 23
WATTS
D1 H.E. WILLAMS 'L60' SERIES
L60-L11/840-CS-MWT-DIM-120 OR APPROVED
EQUAL
6" RECESSED ROUND LED DOWNLIGHT INTEGRAL DIMMING DRIVER 120 V 4000 K 1100 LUMENS 17
WATTS
U1 H.E. WILLIAMS "1SF" SERIES
1SF-2-L12/840-AF12125-WRS/120-DRV-120OR
APPROVED EQUAL
UNDERCABINET TASK LIGHT. EXTRUDED WRAPAROUND OPAL DIFFUSER
ACRYLIC LENS. ROCKER SWITCH
120 V 4000 K 14 WATTS
W1 EUREKA 'MOONRISE PLUS 3540' SERIES
354023LED.11.40120VDVSCWH3980 OR
APPROVED EQUAL
WALL MOUNTED LED FIXTURE WITH ACRYLIC DIFFUSER 120 V 4000 K 1300 LUMENS 12
WATTS
W2 LEDALITE "TRUE GROOVE" SERIES
2923LAENW0411EW OR APPROVED EQUAL
WALL MOUNTED INDIRECT LED FIXTURE WITH EXTRUDED ACRYLIC LENS 120 V 4000 K 3200 LUMENS 25.8
WATTS
X1 PHILIPS CHLORIDE 'CXX' SERIES CXL3RW OR
APPROVED EQUAL
LED POLYCARBONATE TYPE EXIT SIGN. HOUSING SHALL HAVE 6" HIGH
LETTERING TO MEET CODE.
120 V 1.2 WATTS
X2 PHILIPS CHLORIDE 'CXX' SERIES CXL3RW OR
APPROVED EQUAL
LED POLYCARBONATE TYPE EXIT SIGN. HOUSING SHALL HAVE 6" HIGH
LETTERING TO MEET CODE.
120 V 1.2 WATTS
X3 PHILIPS CHLORIDE 'AMS' SERIES
AMS120RWX-RAY IN USE OR APPROVED EQUAL
LED POLYCARBONATE TYPE SIGN (X-RAY IN USE). 120 V 9 WATTS
Issuance Schedule
Number Date Description
FEC**
*
*
* *
* *
*
*
*
*
*
*
*
*
*
*
*
* *
*
*
* * * * * * *
*
*
*
*
*
* *
**
*
*
*
*
*
*
*
*
*
*
*
**
* *
* *
***
* **
**
*
*
**
* *
EE
ELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
SCOPE OF WORK
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
EXTENT OF DEMO
EXTENT OF DEMOEXTENT OF DEMO
EXTENT OF FLOOR DEMO
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
1
2
2
2 2
2
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:48 AMFPD-101
185-01-00
8/15/16
GROUND FLOOR
FIRE PROTECTION
DEMOLITION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLUMBING / FIRE PROTECTION DEMOLITION PLAN
DEMOLITION NOTES
REMOVE EXISTING SPRINKLER HEADS AND ASSOCIATED
BRANCH PIPING AND MAINS. INSTALL NEW UPRIGHT HEADS FOR
FULL SPRINKLER COVERAGE TROUGHOUT CONSTRUCTION.
TEMPORARY HEADS AND ASSOCIATED PIPING TO BE REMOVED
AFTER NEW ARE INSTALLED. PHASING TO BE COORDINATED
WITH CONSTRUCTION MANAGER.
EXISTING SPRINKLER HEADS IN THIS AREA TO REMAIN.
1
DEMOLITION NOTES
2
Issuance Schedule
Number Date Description
5.9
5.1
AREAWAY
TRANS.
VAULT
STORAGE
ROOM
CORRIDOR
SOILED LINEN
GENERATOR
ROOM
STAIRS
EQUIPMENT ROOM
EQUIPMENT
ROOM
EL.
217.9
CORR.
EL. 217.9
SOILED
LINEN
PHYSICIST
OFFICE
CORRIDOR
LOUNGE
T.LKRS
T.
DARK CONTROL
CORRIDORX-RAY
ROOM
RAD
STOR
CORRIDORCOMMUNICATIONS
ELEV.ELEV.
CLEAN
PLANNING
PASS.
FD
4
8
10
6
1
2
1
2
3
3
4
4
4
7
6
4
6
6
6
6
6
2
10
11
2
1
32
3
2
2
1
5
4
1
2
3
4
8 9
EX. 4" S
EX. 4" DCW EX. 3/4"
DHWR
EX. 4" DCW
EX. 3"
DCW
EX. 2" DCW
EX. 1/2"
DHW
EX. 2 1/2"
DCW
EX. 2"
DCW
EX. 2"
DCW
EX. 2" DCW
EX. 1/2"
DHWR
EX. 1/2"
DHWR
EX. 1/2"
DHWR
EX. 2" DCW
EX. 1 1/2" DHW
EX. 2" DCW
EX. 1 1/4"
DHW
EX. 2" DCW
EX. 1/2"
DHW
EX. 2 1/2" DCW
EX. 1" HW
EX. 2 1/2" DCW
EX. 1/2" DHWR
EX. 2 1/2" DCW
EX. 1" DHWR
EX. 3" DHW
EX. 1"
EX. 1 1/4"
HWR
EX. 1"
HWR
EX. 1" HWR
EX. 4"
DCW
EX. 1"
DHWR
EX. 3" DCW
EX. 1" DHWR
EX. 1 1/2" CW
EX. 1" HW
EX. 4" S
12
8
CUT AND CAP STEAM AND
CONDENSATE PIPING. REMOVE
STANDPIPE AND TRAP AND CAP
SANITARY
EXISTING COLD WATER PIPE
RUNNING BETWEEN DUCTS
WILL OBSTRUCT NEW DUCT,
CUT AT POINTS SHOWN
13
14
15
EX. 2" V EX. 2" V
17
16
EX. MV
EX. MV
EX. MV EX. O2
EX. N2O
MV
O
N2O
N2O
O
MV
S
SDCW
DHW
DCW
DHWR
DCW
DHWR
N2ODHW
DHWDCWSDCWS
DHWR MVDCW
S
DHW
DCW
DCW
DHWRDCWMV
MV
N2O
O
DHWS
DCW
DCWDCW8
9
8
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:16 AMPD-100
185-01-00
8/15/16
BASEMENT PLUMBING
DEMOLITION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 BASEMENT PLUMBING DEMOLITION PLAN
DEMOLITION NOTES
REMOVE EXISTING S, V & CW UP TO WATER CLOSET. CAP PIPING
BACK AT MAINS AND/OR RISERS.
REMOVE EXISTING W, HW & CW UP TO LAVATORY. CAP PIPING
BACK AT MAINS AND/OR RISERS.
REMOVE EXISTING S, V, HW & CW UP TO SHOWER. CAP PIPING
BACK AT MAINS AND/OR RISERS.
EXISTING SANITARY & HOT & COLD WATER RISERS TO REMAIN.
3" HW RISER TO REMAIN.
REMOVE EXISTING W, HW & CW UP TO SINK. CAP PIPING BACK AT
MAINS AND/OR RISERS.
REMOVE EXISTING S, V, HW & CW UP TO MOP SINK. CAP PIPING
BACK AT MAINS.
EXISTING SANITARY RISER TO REMAIN.
EXISTING COLD WATER RISER TO REMAIN.
EXISTING TANKLESS WATER HEATER TO REMAIN.
EXISTING RECIRCULATING PUMP TO REMAIN.
EXISTING 4" RISE TO REMAIN
REMOVE EXISTING NITROUS OXIDE FEED TO EXISTING SURGERY
SUITE
EXISTING NITROUS OXIDE MANIFOLD TO REMAIN
EXISTING NITROUS OXIDE FEED TO MATERNITY TO REMAIN
CAPPED EXISTING NITROUS OXIDE & NITROGEN FEEDS TO REMAIN.
REMOVE EXISTING PORTION OF VENT PIPING THAT INTERFERES
WITH NEW DUCTWORK. REROUTE AS INDICATED ON NEW PLAN.
1
2
3
4
5
6
7
8
9
10
11
DEMOLITION NOTES
12
13
14
15
16
17
Issuance Schedule
Number Date Description
FECELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
SCOPE OF WORK
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
EXTENT OF DEMO
EXTENT OF DEMOEXTENT OF DEMO
EXTENT OF FLOOR DEMO
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
6
9
4
6
12
12
3
3
6
6
610
4
9
4
4
4
4
2
2
1
32
2
2
1
6
1
2
9
6 8
3
3
4
97
5
5
5
5
69
7
6
6
9
5
11
11
9
9
9
7
12
6
8
7
13
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:18 AMPD-101
185-01-00
8/15/16
GROUND FLOOR PLUMBING /
FIRE PROTECTION
DEMOLITION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLUMBING / FIRE PROTECTION DEMOLITION PLAN
DEMOLITION NOTES
DISCONNECT & REMOVE EXISTING WATER CLOSET & ALL
ASSOCIATED PIPING. CAP SANITARY & COLD WATER PIPING
BACK AT MAINS IN BASEMENT. CAP VENT PIPING AT VENT RISER.
DISCONNECT & REMOVE EXISTING LAVATORY & ALL
ASSOCIATED PIPING. CAP SANITARY, HOT & COLD WATER
PIPING BACK AT MAINS IN BASEMENT. CAP VENT PIPING AT
VENT RISER.
DISCONNECT & REMOVE EXISTING SHOWER & ALL ASSOCIATED
PIPING. CAP SANITARY, HOT & COLD WATER PIPING BACK AT
MAINS IN BASEMENT. CAP VENT PIPING AT VENT RISER.
DISCONNECT & REMOVE EXISTING SINK & ALL ASSOCIATED
PIPING. CAP SANITARY, HOT & COLD WATER PIPING BACK AT
MAINS IN BASEMENT. CAP VENT PIPING AT VENT RISER.
DISCONNECT & REMOVE ALL EXISTING VENT PIPING MADE
OBSOLETE BY NEW CONTRUCTION BACK AT VENT RISER.
EXISTING SANITARY RISER TO REMAIN.
EXISTING VENT RISER TO REMAIN.
EXISTING COLD WATER RISER TO REMAIN.
EXISTING HOT & COLD WTER RISERS TO REMAIN.
DISCONNECT & REMOVE EXISTING MOP SINK & ALL ASSOCIATED
PIPING. CAP SANITARY, HOT & COLD WATER PIPING BACK AT
MAINS IN BASEMENT. CAP VENT PIPING AT VENT RISER.
DISCONNECT EXISTING VENT PIPING AND VENT PIPE UP.
EXISTING 3" HW RISER TO REMAIN
DISCONNECT & REMOVE ALL EXISTING PLUMBING ASSOCIATED
WITH STERILIZER. CAP SANITARY, HOT & COLD WATER PIPING
BACK AT MAINS IN BASEMENT. CAP VENT PIPING AT VENT
RISER.
1
2
3
4
5
6
7
8
9
10
11
DEMOLITION NOTES
12
13
Issuance Schedule
Number Date Description
FECELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
SCOPE OF WORK
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
EXTENT OF DEMO
EXTENT OF DEMOEXTENT OF DEMO
EXTENT OF FLOOR DEMO
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
1 3 4
56
7
12
8
8
23
23
9
10
12
12
12
8
11
11
2
3
8
23 2 3
13
23
2
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:14 AMMGD-101
185-01-00
8/15/16
GROUND FLOOR MEDICAL
GAS DEMOLITION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 GROUND FLOOR MEDICAL GAS DEMOLITION PLAN
DEMOLITION NOTES
DISCONNECT & REMOVE EXISTING MED VAC ZONE CONTROL
VALVE AND ALL ASSOCIATED PIPING. CAP PIPING BACK AT
RISER AND MAIN.
DISCONNECT & REMOVE EXISTING OXYGEN ZONE CONTROL
VALVE AND ALL ASSOCIATED PIPING. CAP PIPING BACK AT
RISER AND MAIN.
DISCONNECT & REMOVE EXISTING NITROUS OXIDE ZONE
CONTROL VALVE AND ALL ASSOCIATED PIPING. CAP PIPING
BACK AT RISER AND MAIN.
DISCONNECT & REMOVE EXISTING EMERGENCY SHUT-OFF
VALVE AND OXYGEN ALARM PANEL AND ALL ASSOCIATED
PIPING, WIRING AND ACCESSORIES. SEE MED GAS PIPING
GENERAL NOTES FOR MAINTAINING EXISTING SERVICE TO
UPPER FLOORS.
EXISTING MED VAC RISER TO REMAIN.
EXISTING OXYGEN RISER TO REMAIN.
EXISTING NITROUS OXIDE RISER TO REMAIN.
DISCONNECT & REMOVE EXISTING O2, N2O & MV OUTLETS AND
ALL ASSOCIATED PIPING.
CUT & CAP GROUND FLOOR OXYGEN & MED VAC FEED MAINS AT
RISERS AS INDICATED. SEE MEDICAL GAS GENERAL NOTES ON
THIS DWG.
CUT & CAP GROUND FLOOR NITROUS OXIDE FEED MAINS AT
RISERS AS INDICATED. SEE MEDICAL GAS GENERAL NOTES ON
THIS DWG.
CAP EXISTING MAINS TO BE ABANDON IN PLACE HERE. ALL
CONNECTED VALVES & OUTLETS TO THE SYSTEM SHOULD BE
MARKED "NOT IN SERVICE".
DISCONNECT & REMOVE EXISTING MV OUTLETS AND ALL
ASSOCIATED PIPING.
REMOVE EXISTING MED GAS PIPING THAT WAS MADE OBSOLETE
BY PREVIOUS CONSTRUCTION. MED GAS OUTLETS HAVE
ALREADY BEEN CAPPED AND BLANKED OFF. REMOVE ALL
PIPING BACK TO ZONE VALVES.
1
2
1. REMOVAL OF THE EXISTING MEDICAL GAS PIPING ON
THIS FLOOR WILL REQUIRE A COMPLETE SHUTDOWN OF
THE ENTIRE MV, O2, AND N2O RISERS AS THERE ARE NO
SERVICE VALVES AT THIS FLOOR LEVEL.
2. TEMPORARY MV, O2, AND N2O EQUIPMENT WILL BE
REQUIRED FOR PATIENT USE DURING THE SHUTDOWN
PERIOD.
3. SYSTEM SHUTDOWN AND TEMP MV, O2, AND N20
EQUIPMENT REQUIREMENTS SHALL BE COORDINATED
WITH THE HOSPITAL FACILITIES ENGINEERING
PERSONNEL AND HOSPITAL STAFF ON FLOOR LEVELS
AFFECTED BY THIS SHUTDOWN PRIOR TO THE START OF
ANY WORK.
MED GAS PIPING GENERAL NOTES
3
4
5
6
7
8
9
10
11
12
DEMOLITION NOTESMED GAS PIPING GENERAL NOTES
13
Issuance Schedule
Number Date Description
1 2016.07.08 ADDENDUM #1
FECEE
SD
DS
M
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:46 AMFP-101
185-01-00
8/15/16
GROUND FLOOR
FIRE PROTECTION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
INSTALL NEW CONCEALED PENDENT QUICK RESPONSE SPRINKLER
HEADS WITHIN THE OUTLINED AREA. CONNECT NEW SPRINKLER
DROPS TO EXISTING CAPPED DROPS PROVIDED UNDER THE
DEMOLITION SCOPE OF WORK.
REFER TO THE GENERAL FIRE PROTECTION NOTES ON THIS DRAWING
FOR ADDITIONAL FIRE PROTECTION REQUIREMENTS.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR FIRE PROTECTION PLAN
1. THIS DRAWING DEPICTS A PROPOSED FIRE PROTECTION SYSTEM LAYOUT WHICH IS
INDICATED FOR COORDINATION PURPOSES ONLY. THIS DOES NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH NFPA, STATE, & LOCAL CODES, THE OWNER'S
INSURANCE COMPANY, AND THE AUTHORITY HAVING JURISDICTION.
2. REFER TO THE FIRE PROTECTION SPECIFICATIONS FOR DESIGN CRITERIA AND
INSTALLATION REQUIREMENTS.
3. FIRE PROTECTION SYSTEM CONTRACTOR SHALL COORDINATE LOCATIONS OF
SPRINKLERS AND PIPING WITH HVAC DUCTS, EQUIPMENT, BEAMS, COLUMNS,
LIGHTS, AND ANY OTHER OBSTRUCTIONS IN ACCORDANCE WITH NFPA.
4. THIS CONTRACT INCLUDES A PERFORMANCE SPECIFICATION FOR THE ENTIRE FIRE
PROTECTION SYSTEM.
5. PROVIDE ALL PIPING, SUPPORTS, AND EQUIPMENT FOR A COMPLETE FULL
COVERAGE SYSTEM IN CONFORMANCE WITH NFPA, STATE & LOCAL CODES, THE
OWNER'S INSURANCE COMPANY, AND THE AUTHORITY HAVING JURISDICTION.
ADVISE ARCHITECT OF ANY CONFLICTS WHICH MUST BE RESOLVED PRIOR TO
INSTALLATION.
6. PROVIDE CHROME PLATED ESCUTCHEONS AT EXPOSED PIPING PENETRATIONS OF
WALLS, CEILINGS, AND FLOORS.
7. ALL NEW SPRINKLER HEADS SHALL BE OF QUICK RESPONSE TYPE WITH
TEMPERATURE RATING BASED ON AMBIENT TEMPERATURE CONDITIONS FOR EACH
PROTECTED SPACE.
8. USE UPRIGHT SPRINKLER HEADS IN AREAS WITHOUT CEILINGS AND WHERE
SPRINKLER PIPING MUST BE RUN EXPOSED. USE CONCEALED PENDENT SPRINKLER
HEADS IN AREAS WITH FINISHED AND/OR ACCESSIBLE CEILINGS.
9. ALL SPK VALVES SHALL BE LABELED TO IDENTIFY WHAT AREAS THEY CONTROL.
10. PIPE SIZES SHOWN ON THE PLANS ARE APPROXIMATE AND CAN BE INCREASED OR
DECREASED BASED ON FINAL HYDRAULIC CALCULATIONS PERFORMED BY THE
CONTRACTOR. ALL PIPE SIZES SHALL BE IN ACCORDANCE WITH NFPA AND
INSURANCE UNDERWRITER.
11. FIRE PROTECTION HAZARD CLASSIFICATION AND DESIGN CRITERIA SHALL BE AS
FOLLOWS:
A. SOILED UTILITY & STORAGE ROOMS: ORDINARY HAZARD GROUP 1, DESIGN
AREA = ENTIRE SPACE, DENSITY = 0.15 GPM/SF, HEAD SPACING = 130 SF,
INSIDE/OUTSIDE HOSE = 250 GPM
B. REMAINDER OF FINISHED OCCUPIED SPACES: LIGHT HAZARD, DESIGN
AREA = 1500 SF, DENSITY = 0.10 GPM/SF, HEAD SPACING = 168 SF,
INSIDE/OUTSIDE HOSE = 100 GPM
12. COORDINATE ANY NECESSARYSLEEVES FOR PIPING PASSING THRU LEAD-LINED
WALLS WITH INSTALLER.
GENERAL FIRE PROTECTION NOTES DRAWING NOTESGENERAL FIRE PROTECTION NOTES
Issuance Schedule
Number Date Description
1 2016.07.08 ADDENDUM #1
5.9
5.1
AREAWAY
TRANS.
VAULT
STORAGE
ROOM
CORRIDOR
SOILED LINEN
GENERATOR
ROOM
STAIRS
EQUIPMENT ROOM
EQUIPMENT
ROOM
EL.
217.9
CORR.
EL. 217.9
SOILED
LINEN
PHYSICIST
OFFICE
CORRIDOR
LOUNGE
T.LKRS
T.
DARK CONTROL
CORRIDORX-RAY
ROOM
RAD
STOR
CORRIDORCOMMUNICATIONS
ELEV.ELEV.
CLEAN
PLANNING
PASS.
FD
DS
1
4" S
11
8
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
8
3" W
2
3" W
2" W
3" W
2" W
2" W
8
8
C.O.
8 8
7
8
8
8
3
3
2" W
2" W
8
7
7
9
9
8
9
C.O.
10
4
5
6
2" W
4" S
1 1/4" DHW
2" W
4" S
2" W
8
2" W
EXTEND NEW COLD
WATER PIPING AROUND
NEW SUPPLY DUCT
RISER
C.O.
12
13
14
15
EX. 4" DCW EX. 3/4"
DHWR
EX. 4" DCW
EX. 3"
DCW
EX. 2" DCW
EX. 1/2"
DHW
EX. 2 1/2"
DCW
EX. 2"
DCW
EX. 2"
DCW
EX. 2" DCW
EX. 1/2"
DHWR
EX. 1/2"
DHWR
EX. 1/2"
DHWR
EX. 2" DCW
EX. 1 1/2" DHW
EX. 2" DCW
EX. 1 1/4" DHW
EX. 2" DCW
EX. 1/2"
DHW
EX. 2 1/2" DCW
EX. 1" HW
EX. 2 1/2" DCW
EX. 1/2" DHWR
EX. 2 1/2" DCW
EX. 1" DHWR
EX. 3" DHW
EX. 1"
EX. 1 1/4"
HWR
EX. 1"
HWR
EX. 1" HWR
EX. 4"
DCW
EX. 1"
DHWR
EX. 3" DCW
EX. 1" DHWR
EX. 4" S
EX. 2" V EX. 2" V
EX. MV
EX. MV
EX. MV EX. O2
EX. N2O
9
MV
O
N2O
DHWRDHWDCW
DHWR
MV
O
N2O
DCW
DHWR
N2O
SSW W8 DHWRDCWS WDCW
DCW
W
WDCWDHWRN2OW
MVMVVV
W
WSS
WDHW
1
16
1
C.O.
C.O.
C.O.SS
W
DHWC.O.
2
H-100
2" W
8
2" W 4" S
4" S
4" S
2" W
4" S
3" W
77
2" W
2" W 2" W
C.O.
2" W
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:19 AMPS-100
185-01-00
8/15/16
BASEMENT PLUMBING PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
CONNECT NEW 4" S TO EXISTING STACK HERE
CONNECT NEW 3" W TO EXISTING STACK HERE
CONNECT NEW 2" W TO EXISTING STACK HERE
CONNECT NEW 1 1/4" HW TO EXISTING 3" HERE
CONNECT NEW 2" CW TO EXISTING 2 1/2" HERE
CONNECT NEW 3/4" HWR TO EXISTING 1" HERE
CONNECT NEW CW TO EXISTING HERE
2" W UP
4" S UP
1 1/4" HW, 2" CW & 3/4" HWR UP
CONNECT NEW 3" W TO EXISTING 4" RISE HERE
CONNECT NEW 3/4" N2O TO EXISTING 3/4" HERE
CONNECT NEW 3/4" N2O TO EXISTING 3/4" HERE WITH NEW VALVE
- NORMALLY CLOSED. SEE DETAIL ON DRAWING P400 FOR
CONNECTIONS TO EXISTING MANIFOLD.
EXISTING N2O MANIFOLD TO REMAIN
EXISTING 1/2" N2O TO MATERNITY TO REMAIN
2" V UP
1
2
SCALE: 1/4" = 1'-0"1 BASEMENT PLUMBING PLAN
DRAWING NOTES
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Issuance Schedule
Number Date Description
FECSD
DS
M
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
SK-1
SK-3
SK-1
SK-3
SK-1
SK-1
SK-1
SK-1
SK-1
SK-1
LAV-1
WC-1
LAV-1
LAV-1
WC-1
WC-3
SK-2
LAV-1
WC-2
SK-1
5
5
5
5
3
3
2
1
3
3
3
2
1
2
3
3
1
2
5
3
3
3
2" V
1 1/2" V
2" V
2" V
2" V
2" V
SK-1
3
2" V
2" V
2" V
2" V
2" V
2" V
2" V
3
8
9 10
2
H-100
SK-1
WB-1
11
C.O.ACCESS
PANEL
2" V
2" V
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:22 AMPS-101
185-01-00
8/15/16
GROUND FLOOR PLUMBING
SANITARY AND VENT PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
4" S DN; 2" V RISE - FINAL CONNECT TO WATER CLOSET
2" W DN; 2" V ROSE - FINAL CONNECT TO LAVATORY
2" W DN; 2" V RISE - FINAL CONNECT TO SINK
2" W DN; 2" V RISE - FINAL CONNECT W&V TO EACH SINK
CONNECT NEW 2" V TO EXISTING STACK HERE
NOT USED
NOT USED
CONNECT EXISTING VENT FROM MOP SINK TO NEW VENT IN
PLUMBING CHASE
2" V DN; 2" V RISE
2" W DN - RUN IN WALL TO SINK
2" W DN & 2" V RISE - FINAL CONNECT TO ICE MACHINE WATER-
DRAIN BOX (WB-1) WITH 2" TRAP.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLUMBING SANITARY AND VENT PLAN
DRAWING NOTES
3
4
5
6
7
8
9
10
11
Issuance Schedule
Number Date Description
FECSD
DS
M
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
SK-1
SK-3
SK-1 SK-1
SK-1
SK-1
SK-1
SK-1
SK-1
SK-1
SK-1
LAV-1
WC-1
LAV-1
LAV-1
WC-1
WC-3
SK-2
LAV-2
WC-2
1
4
5
3
2
3/4" DHWR
1 1/2" DHW
2" DCW
7
7
7
6
3
3
6
7
3
6
3
8
7
7
8
2" DCW
1 1/2" DHW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW 1/2" DCW
2" DCW
1 1/4" DHW1 1/4" DHW
2" DCW
2" DCW1 1/4" DHW
2" DCW
1 1/4" DHW
1 1/4" DHW
2" DCW
1/2" DHW
1/2" DCW
3/4" DHWR
1/2" DHW
1/2" DCW
1" DCW
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW
1" DCW
1/2" DHW
1/2" DCW
SK-1
3/4" DHW
3/4" DCW
1 1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DCW
7
7 7
1" DHW1" DCW
3/4" DCW
3/4" DHW
SK-1
9
7
9
9
10
WB-1
1" DCW
1" DHW
3/4" DHWR
11
12
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:26 AMPW-101
185-01-00
8/15/16
GROUND FLOOR PLUMBING
DOMESTIC WATER PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
1 1/2" HW, 2" CW & 3/4" HWR DROPS WITH SHUT OFF VALVES
EXTEND 1 1/4" CW & 1/2" HW IN CHASE FOR FINAL CONNECTION TO
WATER CLOSET & LAVATORY
1/2" H&CW DROP - FINAL CONNECT TO LAVATORY
1" CW DROP - FINALL CONNECT TO WATER CLOSET
SHOCK ABSORBER (SA-1) AT ACCESS PANEL
1" CW DROP w/ SHOCK ABSORBER (SA-2) AT ACCESS PANEL - FINAL
CONNECT TO WATER CLOSET.
1/2" H&CW DROP - FINAL CONNECT TO SINK
1/2" H&CW DROP - FINAL CONNECT TO EACH SINK
1/2" CW DROP WITH ANGLE STOP FOR CONNECTION TO WATER
COOLER. PROVIDE WATER FILTER: AQUAPURE MODEL #BREW110-MS
WITH SPARE CARTRIDGE #HF10-MS.
1/2" CW DROP TO ICE MACHINE WATER-DRAIN BOX (WB-1). PROVIDE
WITH WATTS #9D DUAL CHECK VALVE ON CONNECTION TO ICE
MACHINE. PIPE RELIEF VENT TO DRAIN IN WB-1. PROVIDE WATER
FILTER: AQUAPURE MODEL #ICE120-S WITH SPARE CARTRIDGE #HF20-S.
1 1/2" CW, 1" HW & 3/4" HWR VALVED AND CAPPED FOR FUTURE
THIS VALVE TO BE CLOSED UNTIL FUTURE.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR PLUMBING DOMESTIC WATER PLAN
3
4
5
6
7
8
9
10
11
12
Issuance Schedule
Number Date Description
FECOVSOVSSCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28 ZVB-1
3/4" O
3/4" MV
1/2" O
3/4" MV
1/2" O
3/4" MV
1
2
3
4
4
5
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:12 AMMG-101
185-01-00
8/15/16
GROUND FLOOR MEDICAL
GAS PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
EXISTING MEDICAL VACUUM & OXYGEN RISERS TO REMAIN.
EXTEND 3/4" MED VAC & OXYGEN TO HOLDING / RECOVERY ROOM.
3/4" MV & 3/4" O DROP TO ZONE VALVE BOX.
3/4" MV & 1/2" O DROP AND CONNECT TO MED GAS INLETS /
OUTLETS.
TIE IN LOCATION OF MED VAC & OXYGEN WITHIN THIS AREA
OUTLINED. CONFIRM EXACT LOCATION WITH OWNER AND VERIFY
EXACT SIZES IN FIELD. CONNECT TO EXISTING RISERS AND INSTALL
NEW 3/4" MV & O SERVICE VALVES FOR THIS FLOOR.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR MEDICAL GAS PLAN
DRAWING NOTES
3
4
5
Issuance Schedule
Number Date Description
1 2016.07.08 ADDENDUM #1
DROP NIPPLE TO
ACCOMMODATE NEW
CEILING ELEVATION NEW SPRINKLER
BRANCH LINE SPRINKLER MAIN
OR BRANCH LINE
ELBOW
REDUCER
CEILINGCONCEALED
SPRINKLER HEAD
NOT TO SCALE
SPRINKLER HEAD DETAILS
MV02MV02PRESS
GAUGE
(TYP.)
BALL VALVE
(TYP)
ZONE VALVE BOX W/SEE
THRU PLASTIC COVER &
PULL RING - SEE ARCH.
ELEVATIONS FOR
MOUNTING HEIGHT
NOT TO SCALE
ZONE VALVE BOX DETAIL - ALTERNATE BID #4
TO & FROM SYSTEM
DISTRIBUTION MAINS
TO & FROM OUTLETS/INLETSN2O EXISTING 3/4" N2O
FEED FROM ER
PRESSURE GAUGE NEW NITROUS OXIDE
MAIN LINE SHUTOFF
VALVE - NORMALLY
CLOSED
EXISTING NITROUS
OXIDE MANIFOLD
CONTROL CABINET
EXISTING
3/4" N2O
EXISTING
CYLINDERS
NOT TO SCALE
NITROUS OXIDE (N2O) PIPING AT EXISTING MANIFOLD DETAIL
EXISTING
PRESSURE
SWITCH
EXISTING
PRESSURE
SWITCH
EXISTING 1/2" N2O
TO MATERNITY
REMOVE EXISTING 3/4" N2O
TO EXISTING SURGERY
CONNECT NEW 3/4" N2O
TO EXISTING CAPPED
LINE
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
NOT TO SCALE
8/16/2016 11:26:15 AMP-400
185-01-00
8/15/16
PLUMBING / FIRE
PROTECTION DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
FECELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
SCOPE OF WORK
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
EXTENT OF DEMO
EXTENT OF DEMOEXTENT OF DEMO
EXTENT OF FLOOR DEMO
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
1
1
1
2
(TYP.)
2
(TYP.)
2
(TYP.)
2
(TYP.)
2
(TYP.)
2
(TYP.)
2
(TYP.)
8
(TYP.)
3
REMOVE EXISTING LOW EXHAUST
DROP AND CAP AND SEAL
4
8
(TYP.)
7
5
(TYP.)
5
(TYP.)
3
SCOPE
2
(TYP.)
2
(TYP.)
REMOVE EXISTING LOW EXHAUST DROP
AND SAVE DUCT FOR REUSE ON NEW
CEILING EXHAUST GRILLE
REMOVE EXISTING FROM CURRENT
SPOT AND SAVE TO RELOCATE TO NEW
CHASE. CUT BACK EXISTING SUPPLY TO
POINT SHOWN. COORDINATE WITH
CEILING SPACE BELOW IN BASEMENT
STORAGE ROOM. MEASURE EXISTING
AIRFLOW PRIOR TO DEMOLITION AND
RESTORE UPON COMPLETION
FD
FD
CUT BACK AND CAP
AND SEAL EXISTING
EXHAUST DUCT
FD
CUT BACK EXISTING
RETURN DUCT TO
POINT SHOWN, CAP
AND SEAL
CUT BACK EXISTING
RETURN DUCT TO
POINT SHOWN, CAP
AND SEAL
CUT BACK EXISTING
SUPPLY DUCT TO
POINT SHOWN, CAP
AND SEAL
2
(TYP.)
8
(TYP.)
8
(TYP.)
2
8
(TYP.)
8
(TYP.)
8
(TYP.)
8
(TYP.)
6
6
6
(TYP.)
2
(TYP.)
2
(TYP.)
2
(TYP.)
8
(TYP.)6
6
6
6
2
H-100
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:59 AMHD-101
185-01-00
8/15/16
GROUND FLOOR HVAC
DEMOLITION PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DEMOLITION NOTES
REMOVE EXISTING LAMINAR FLOW SUPPLY DIFFUSERS.
REMOVE ALL EXISTING SUPPLY DUCTWORK SHOWN DASHED
AND EXISTING DIFFUSERS, HANGERS, SUPPORTS, AND
DAMPERS BACK TO POINTS SHOWN. RISERS FROM BASEMENT
LEVEL SUPPLYING UP TO FIRST FLOOR TO REMAIN FOR REUSE.
EXISTING SUPPLY DUCT TO REMAIN.
REMOVE EXISTING HAZARDOUS EXHAUST. CONTRACTOR
SHALL UTILIZE CERTIFIED TESTING AND ABATEMENT
CONTRACTOR FOR SAFE REMOVAL AND DISPOSAL. VERIFY IN
FIELD.
REMOVE ALL EXISTING RETURN DUCTWORK SHOWN DASHED
AND ASSOCIATED GRILLES, HANGERS, SUPPORTS, AND
DAMPERS FROM POINTS SHOWN. EXISTING RISERS UP FROM
BASEMENT LEVEL TO REMAIN.
EXISTING EXHAUST DUCTS TO REMAIN.
REMOVE EXISTING RETURN / EXHAUST BRANCHES SHOWN
DASHED AND CAP AND SEAL TAKE OFFS.
REMOVE ALL EXISTING EXHAUST DUCTWORK SHOWN DASHED
AND ASSOCIATED GRILLES, HANGERS, SUPPORTS, AND
DAMPERS FROM POINTS SHOWN. EXISTING RISERS UP TO
REMAIN. CAP AT RISERS WHERE SHOWN.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR HVAC DEMOLITION PLAN
GENERAL NOTES
PRIOR TO DEMOLITION, MEASURE AND RECORD AIRFLOW AT
EXISTING AIR HANDLING UNITS S-1 AND S-2 AND ALL EXISTING
BRANCH DUCTS TO REMAIN. RESTORE AIRFLOW TO EXISTING
BRANCHES UPON COMPLETION.
1.
3
4
5
6
7
DEMOLITION NOTESGENERAL NOTES
8
Issuance Schedule
Number Date Description
5.1
AREAWAY
TRANS.
VAULT
STORAGE
ROOM
CORRIDOR
SOILED LINEN
GENERATOR
ROOM
STAIRS
EQUIPMENT ROOM
CORR.
EL. 217.9
SOILED
LINEN
LOUNGE
T.CORRIDORRAD
STOR
CORRIDORELEV. LOBBY
SERVICE ELEV.
COMMUNICATIONS
ENVIRO SERV
STORAGE
PASS.
FD
FD
DS
VFC VFC
M
M
M
S1
S2
S3
FD
FD
NOTE:
NEW FLOOR PENETRATION TO BE
CONFIRMED WITH STRUCTURAL
ENGINEER
NOTE:
NEW FLOOR PENETRATION TO BE
CONFIRMED WITH STRUCTURAL
ENGINEER
NOTE:
NEW FLOOR PENETRATION TO BE
CONFIRMED WITH STRUCTURAL
ENGINEER
FD
OLD HEAT LOOP PIPE
LOW PRESSURE
CONDENSATE
UNKNOWN PIPE
P-1P-2HEAT EXCHANGER
S4
FD
2
H-100
1
2
3 4
5
6
8
9
10
11
12
CU-S2
CU-S1
DX-S1
DX-S2 REF
REFREF
REFREFINSTALL NEW DX COOLING COILS IN EXISTING
AHU-S1 AND IN AHU-S2 IN SPACE WHERE OLD
COILS WERE INSTALLED. RUN PIPING THROUGH
ACCESSIBLE CEILING AREAS, RUN PIPING UP TO
ROOF, CONNECT TO NEW CONDENSING UNITS.
NEW CONDENSING UNITS MOUNTED
ON ROOF
REFRIGERANT PIPING UP TO LOW
ROOFTOP
REMOVE EXISTING HOT
WATER PUMPS P-1 AND P-2
AND INSTALL NEW PUMPS, P-1
& P-2, ON EXISTING PAD.
REPLACE ANY EXISTING
VALVES AND TRIM PER DETAIL
P-2P-1
REFREF7
7
2" HWR
2" HWS
NEW 2" HOT WATER SUPPLY
AND RETURN TO SERVE NEW
VAV REHEAT COILS IN SCOPE
OF WORK
CONTRACTOR TO VERIFY EXACT SIZE
OF NEW DX COOLING COILS NEEDED
IN EXISTING AHU-S1 AND AHU-S2 IN
THE SECTION WHERE THE OLD COILS
WERE INSTALLED, IN THE FIELD.
26
EXISTING SUPPLY
DUCT AND RISER
NEW SUPPLY
DUCT AND RISER
STEAM COIL
12x18
FD
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:49 AMH-100
185-01-00
8/15/16
BASEMENT HVAC PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
REMOVE EXISTING SUPPLY DUCT SECTION INSIDE ROOM
INCLUDING, STEAM COIL AND ASSOCIATED PIPING WHICH NEEDS
TO BE CAPPED. DISCONNECT EXISTING SUPPLY RISER FROM
ELBOW IN GROUND FLOOR LEVEL CEILING SPACE ABOVE AND
REMOVE. REMOVE EXISTING FIRE DAMPER AND SAVE FOR RE-USE.
PATCH HOLE IN CEILING / FLOOR TO MATCH EXISTING.
RUN NEW SUPPLY DUCT SECTION FROM INSIDE ROOM, MATCH
EXISTING SIZE, (V.I.F.). OFFSET UP AFTER SPRINKLER MAIN AND
ELBOW OVER EXISTING RELIEF AIR DUCT, ELBOW UP, ADD FIRE
DAMPER, TRANSITION TO 20x20 AND RISE UP THROUGH NEW CHASE
IN NEW OFFICE TO CEILING SPACE.
OFFSET EXISTING PIPES RUNNING UP HIGH AROUND NEW RETURN
DUCT PENETRATION. VERIFY SERVICE, SIZE AND MATERIALS IN
FIELD. VERIFY SHUT-DOWN WITH HOSPITAL.
NEW 26x14 RETURN DUCT UP TO GROUND FLOOR, OFFSET OVER
O.A. PLENUM AND 90 ELBOW DOWN TO EXISTING BLANKED OFF
MIXING AIR SECTION ON EXISTING AHU-S2.
CUT EXISTING LOW PRESSURE STEAM CONDENSATE PAST
CLOSEST DROP AND RUN OFFSET PIPE AROUND NEW RETURN
DUCT DROP AND RECONNECT TO LPC ON OTHER SIDE OF NEW
DUCT UP. CUT AND OFFSET OLD HEAT LOOP PIPE AROUND NEW
RETURN DUCT DROP AND RECONNECT.
REMOVE EXISTING OUTSIDE AIR DAMPER, PNEUMATIC ACTUATOR,
AND ALL ASSOCIATED PIPING AND DEVICES BACK TO SOURCE.
PROVIDE NEW RETURN AIR DAMPER AND MIN/MAX OUTSIDE AIR
DAMPERS WITH ELECTRONIC ACTUATORS. LOCATE ACTUATORS ON
THIS SIDE OF UNIT FOR ACCESS.
REMOVE EXISTING PNEUMATIC STEAM CONTROL VALVES AND ALL
ASSOCIATED CONTROL PIPING AND DEVICES. PROVIDE NEW
STEAM CONTROL VALVES WITH ELECTRONIC ACTUATORS. CONFIRM
EXISTING SIZING AND OPERATION. (E.G. 50/50, 1/3 - 2/3).
REMOVE EXISTING SUPPLY DUCT ELBOW AND FIRE DAMPER
SECTION FROM UP NEAR CEILING AND EXISTING SUPPLY DUCT
BACK TO TRANSITION BEFORE STEAM COIL. REMOVE DUCT RISER
GOING UP. PATCH HOLE IN CEILING TO MATCH EXISTING.
STEAM COIL AND ASSOCIATED PIPING TO REMAIN IN PLACE.
ATTACH NEW DUCT TO EXISTING TRANSITION AND RUN STRAIGHT
ACROSS TOP OF EXISTING DUCT AND 90 ELBOW DOWN BETWEEN
EXISTING DUCTS AS SHOWN IN DETAIL ON THIS SHEET.
RUN NEW SUPPLY DUCT UNDER EXISTING DUCTWORK AND ELBOW
UP TO RELOCATED RISER IN NEW CHASE UPSTAIRS. ADD FIRE
DAMPER SAVED FROM DEMOLITION.
REMOVE SECTION OF EXISTING STEAM CONDENSATE PIPE AND
OFFSET AROUND NEW DUCT ROUTE AND RECONNECT TO
CONDENSATE MAIN.
1
2
DRAWING NOTES
SCALE: 1/4" = 1'-0"1 BASEMENT HVAC PLAN
SCALE: 1/4" = 1'-0"2 NEW RISER SECTION DETAIL
3
4
5
6
7
8
9
10
11
12
Issuance Schedule
Number Date Description
FECT
T
T
TT
T
T
T
T T T
T
T
SD
DS
M
T
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
A4-130
A3-300
A3-300
A3-225
A2-120
A2-110
A2-120
A3-260
A3-260
A3-220
A4-500 B-75
A3-125
A3-110
A3-110
A4-200
A4-125
A3-300
A3-300
B-75
A4-185
A4-185
A3-100
A3-200
B-125
B-125
B-95
B-50 B-50
A2-50
A2-145
A2-60
A2-50 A2-50
B-75
A4-230
A3-110
A3-110
A2-185
A2-90
A2-65
A2-75
SCOPE
B
555
690
155
B
A
400
500
100
105
130
30
B
560
700
140
B
740
740
740
B-130
A2-90
B
600
600
600
B
385
470
95
20x1018x818x8
18x8
18x8 10x86x8
14x108ø
14x88x810ø
8x8
6x6
A4-60
B
12x10
12x1012x108x6
8x68ø10x106ø10x8 16x88ø12x1020x810x1010x8
8x6
8x68x6
8x6A
FD
FD
16x8
10x88øB
600
600
600 6ø10x8A
195
225
195 10x8370
370
370
400
500
100
12x10
8x8
8ø
18x6 8x8
6x6 8x6
6x6
8ø 14x1014x88x6
8x6
8x6
6x66x6
B
8x6
8x88x68x614x108x8 8ø
8ø14x12
12x108x6
8x614x1010x810x8
10x8
8x88x6
350
440
90
A3-500
B-675
16x108x6B-65
B-5206x6
6x6B-100
B-145 8x814x10
14x106x6
10x810x6
10x6
B-20014x812x8
8x6
B-110
B-120B-120 8x6B-80
8x68x68x6B-600
B-225
10x10
10x10
B-100
B-600
14x12 14x108x6
6x6B-55
B-150
B-220
14x12
10x612x10
B-425
12x10
12x108
x
6 8x626x148x8
24x12
22x1222x12
14x12NEW 26x14 RETURN DUCT
DROP TO S-2 AHU IN
BASEMENT BELOW
24x14
B-400
12x12
12x12 14x14
12x12
B-125
12x12
12x12
12x12
12x12
12x12
10x8 12x12 12x12
12x12
12x12
12x12
12x12
14x14 12x1012x12
B-110B-110
12x12 12x12
12x12
12x12
12x1212x12
12x12
12x12
12x12
12x12
12x12
18x12
12x12
12x12 26x1424x14
2
12x1012x10
A
260
325
100
B-145
12x128x610x6
8x610x88x8
10x610x814x810x810x8 3
FD
ALTERNATE #1
DX PIPING UP TO LOW
ROOF FROM BASEMENT
FD
10x68x610x814x810x10
6x6
6x610x10 A
100
125
25
FD
8x8
A2-60
B-60 6x612x12
6x6
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:55 AMH-101
185-01-00
8/15/16
GROUND FLOOR HVAC
DUCTWORK PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 GROUND FLOOR HVAC DUCTWORK PLAN
DRAWING NOTES
NEW SUPPLY RISER CONNECTED TO EXISTING SUPPLY DUCT.
NEW SUPPLY DUCT RISER IN NEW CHASE DROPPED DOWN TO
BASEMENT LEVEL AND RE-CONNECT TO EXISTING SUPPLY
FROM AHU-3. COORDINATE MOVE WITH OWNER. WORK TO BE
PERFORMED ON PREMIUM TIME IN ORDER TO MINIMIZE
DISRUPTION.
INSTALL NEW RELIEF AIR DUCT AND CONNECT TO NEW
RETURN DUCT TO S2. ADD MOTORIZED DAMPERS TO CONTROL
RETURN AND RELIEF AIR.
NEW 20x20 SUPPLY RISER TRANSITIONED TO 28x14
CONNECTED TO EXISTING SUPPLY DUCT.
1
2
DRAWING NOTES
3
Issuance Schedule
Number Date Description
FECT
T
T
TT
T
T
T
T T T
T
T
SD
DS
M
T
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
EXISTING PIPE DROPS IN
CHASE TO REMAIN
B
B
A
B
B
B
B
B
A
B
A
B
NEW 2" HWS&R PIPE
DROPS IN NEW
CHASE
3/4" HWS3/4" HWR1" HWR
1" HWS
1" HWR
1" HWS
3/4" HWR 3/4" HWS
3/4" HWR 3/4" HWS
3/4" HWR 3/4" HWS
3/4" HWS
3/4" HWS
3/4" HWS
3/4" HWR
3/4" HWS
1" HWR
1" HWS
1" HWR
1" HWS
3/4" HWR
3/4" HWS
1 1/4" HWS1 1/4" HWR1 1/4" HWS1" HWS3/4" HWR1" HWR3/4" HWR
3/4" HWR
A
A
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:03 AMHP-101
185-01-00
8/15/16
GROUND FLOOR HVAC
PIPING PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 GROUND FLOOR HVAC PIPING PLAN
Issuance Schedule
Number Date Description
BAL DAMPER
MIN. R = W
OTHERWISE USE
VANED ELL
W
R
5
1
3
1
FLOWMAX SLOPE OF TRANSITIONS MIN RADIUS OF
CURVED ELBOW
DOUBLE VANE
5xW
MIN
.5WMINW/5W
BRANCH TAKE-OFF VANED SQUARE ELBOWFLOWFLOW0
00
00
NOT TO SCALE
DUCT CONSTRUCTIONDUCT CONSTRUCTION
- 1:7 SLOPE FOR HIGH VELOCITY
- 1:4 SLOPE FOR LOW VELOCITY
NOTES:
REDUCTION OF DUCT AREA
NOT TO EXCEED 20%
PLAN
SEE NOTE
ELEVATION
ROUND DUCT TRANSFORMATION TO AVOID OBSTRUCTION
CEILING
PLAN
ELEVATION
AIR
FLOW
AIR
FLOW
RECTANGULAR DUCT TRANSFORMATION TO AVOID OBSTRUCTION
AIR
FLOW
AIR
FLOW
OBSTRUCTION
NOT TO SCALE
DUCT OBSTRUCTION TRANSFORMATION DETAILS
CEILING
REDUCTION OF DUCT AREA
NOT TO EXCEED 20%
SEE NOTE OBSTRUCTION
DUCT OBSTRUCTION TRANSFORMATION DETAILS
45° SIDE TAKE-OFF
RECTANGULAR TO
ROUND OR FLAT OVAL
RECTANGULAR DUCT
AIR FLOW
VOLUME DAMPER
(DO NOT INSTALL IN SUPPLY
TO AIR TERMINAL UNITS)
SUPPLY DUCT TO
AIR TERMINAL UNIT
OR SUPPLY DIFFUSER
VD
NOT TO SCALE
45° SUPPLY AIR TAKEOFF DETAIL45° SUPPLY AIR TAKEOFF DETAIL
ROUND OR
FLAT OVAL
DUCT
SUPPLY DUCT TO
AIR TERMINAL UNIT
CONICAL TEE
BELLMOUTH
TAKE-OFF
SUPPLY DUCT TO
AIR TERMINAL UNIT
RECTANGULAR DUCT
NOT TO SCALE
VAV LOOP PRIMARY SUPPLY AIR TAKEOFF DETAILVAV LOOP PRIMARY SUPPLY AIR TAKEOFF DETAIL
RECTANGULAR
BRANCH DUCT
RECTANGULAR MAIN DUCT
45° TAKE-OFF
VD
PROVIDE VOLUME DAMPER
UPSTREAM/ DOWNSTREAM
OF ALL BRANCH MAIN
TAKEOFFS AND AT LAST
TERMINAL RUNOUT AND
EXCEPT AT LOCATIONS
EXCLUDED IN
SPECIFICATIONS
INSTALL VOLUME
DAMPER MINIMUM
TWO DUCT WIDTHS
FROM TAKEOFF
PROVIDE VOLUME DAMPER
EXCEPT AT LOCATIONS
EXCLUDED IN SPECIFICATIONS
VD
NOT TO SCALE
RECTANGULAR BRANCH DUCT TAKEOFF DETAIL0RECTANGULAR BRANCH DUCT TAKEOFF DETAIL
PROVIDE 4' MINIMUM,
5' MAXIMUM STRAIGHT
DUCT BETWEEN
TRANSITION AND BOX
SERVICE ACCESS PER
MANUFACTURERS
RECOMMENDATIONS, 18"
MINIMUM
PRIMARY
AIR DUCT
TRANSITION
SHUTOFF VAV BOX
NOT TO SCALE
SUPPORT UNIT
FROM STRUCTURE
SHUTOFF VAV BOX
UNION (TYP)MODULATING CONTROL VALVE
MANUAL AIR VENT BALANCING VALVE
HWR
HWS
SHUTOFF VALVE
(TYP)
STRAINER WITH
BLOWDOWN VALVE
HOSE BIBB, GASKETED
CAP AND CHAIN
HOT WATER
REHEAT COIL
HOSE END DRAIN VALVE
WITH GASKETED CAP
AND CHAIN
TEST PLUG (TYP)
NOTE:
ALL RUNOUTS TO BE 3/4" UNLESS NOTED OTHERWISE.
RUNOUTS LESS THAN 3/4" WILL NOT BE ACCEPTED.
VAV HOT WATER REHEAT COIL PIPING DETAIL
NOT TO SCALE
VAV HOT WATER REHEAT COIL PIPING DETAIL
YES
NO
ALLOWABLE FLOW CONFIGURATIONS IN PIPING TEES - HVAC SYSTEMS
NOT TO SCALE
YES
NO
ALLOWABLE FLOW CONFIGURATIONS IN PIPING TEES - HVAC SYSTEMS
W
1-1/2W DOUBLE THICKNESS
TURNING VANES
AIRFLOW
D1
D+D1
SLOPE
1" IN 7"
1"R
2"R
1" 1"
1"
1"
AIRFLOW
45°
SLOPE
1" IN 7"
1/4W,
4" MIN
W
AIRFLOW
45°
1/4W,
4" MIN W
AIRFLOW D1
D+D1
D
D
1-1/2W
W
AIRFLOW
LONG RADIUS TEE
SUPPLY DUCTS ONLY
LONG RADIUS TEE
RETURN DUCTS ONLY
TAKE-OFFS SUPPLY
DUCTS ONLY
TAKE-OFFS
RETURN DUCTS ONLY
TAKE-OFF SUPPLY
DUCTS ONLY
TYPICAL TURNING VANE
SUPPLY AND RETURN DUCTS
FULL RADIUS ELBOW
SUPPLY AND RETURN DUCTS
SQUARE ELBOW SUPPLY
AND RETURN DUCTS
NOT TO SCALE
DUCT DETAILS
0
0
0
0
0
0
0
00
D
D0 000 0
DUCT DETAILS
P
SHUTOFF VALVE (TYP)
FLEXIBLE CONNECTOR (TYP)
COMMON PRESSURE
GAUGE WITH
SHUTOFF VALVES
SUCTION DIFFUSER
WITH SUPPORT
FLOOR
SUPPORT BASE
18"
MIN
CHECK VALVE
REDUCER
BASE MOUNTED PUMP DETAIL - VFC CONTROLLED
NOT TO SCALE
HOSE END DRAIN VALVE
WITH GASKETED CAP
AND CHAIN
NOTE:
APPLIES TO END SUCTION AND HORIZONTAL SPLIT CASE.
-
METERING ORIFICE VALVE
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
NOT TO SCALE
8/16/2016 11:25:56 AMH-400
185-01-00
8/15/16
HVAC DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
FECELEVATORELEVATORELEVATOR
EXISTING
EMERG MGMT
STORAGE
G03
EXISTING ED STORAGE
G02
EXISTING OFFICE
G01A
EXISTING LOCKER ROOM
G01
STAIR
EXISTING ED LOCKER ROOM
G20
EXISTING ED DR ON CALL SLEEP
G19
EXISTING
VEST.
EXISTING EVS HSK
G18
EXISTING OFFICE
G17
SCOPE OF WORK
EXISTING OFFICE
G16
STORAGE
OFFICE
EXISTING ED CONF ROOM
G05
EXISTING ED MEN'S LOCKER
G15
EXISTING STORAGE
G14
EXISTING ED ADMIN CLINICAL
G13
EXTENT OF DEMO
EXTENT OF DEMOEXTENT OF DEMO
EXTENT OF FLOOR DEMO
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
SL-2
2
1
EXISTING
PANEL
3
3
3
REMOVE EXISTING ELECTRICAL
PULLBOX
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:31 AMED-101
185-01-00
8/15/16
GROUND FLOOR
ELECTRICAL DEMOLITION
PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DEMOLITION NOTES
EXISTING PANEL SHALL BE DISCONNECTED AND REMOVED, INCLUDING
FEEDERS BACK TO EXISTING SOURCE DISTRIBUTION PANEL IN
BASEMENT. CONFIRM LOCATION OF SOURCE PANEL WITH HOSPITAL
FACILITIES.
EXISTING PANEL ‘SL-2’ SHALL BE DISCONNECTED AND REMOVED,
INCLUDING FEEDERS BACK TO EXISTING SOURCE DISTRIBUTION PANEL
‘WWMP’ IN BASEMENT. ELECTRICAL CONTRACTOR SHALL ALLOCATE (6)
BRANCH CIRCUITS TO BE UTILIZED TO RE-FEED EXISTING LOADS
OUTSIDE OF THE PROPOSED SCOPE OR WORK TO THE PROPOSED
NEW PANEL. THE PHASING AND CONSTRUCTION INTENT FOR THIS IS TO
KEEP THE EXISTING PANELS ENERGIZED ON A TEMPORARY BASIS
DURING THE PERIOD OF DEMOLITION AND CONSTRUCTION SUCH THAT
THE AREAS OUTSIDE THE SCOPE OF WORK MAY REMAIN
OPERATIONAL. ONCE THE NEW PANELS ARE INSTALLED AND
ENERGIZED (SHOULD BE SCHEDULED TO BE CONSTRUCTED EARLY IN
THE PROCESS), EXISTING BRANCH CIRCUITS SERVING AREAS OUTSIDE
THE SCOPE OF WORK CAN BE EXTENDED OVER TO THE NEW PANELS.
EXISTING PANEL ‘SL-1’ (LOCATED IN EXISTING CORRIDOR
APPROXIMATELY 10’ PLAN NORTH OF NEW CORRIDOR DOORS) SHALL
BE DISCONNECTED AND REMOVED, INCLUDING FEEDERS BACK TO
EXISTING SOURCE DISTRIBUTION PANEL ‘WWMP’ IN BASEMENT.
ELECTRICAL CONTRACTOR SHALL ALLOCATE (16) BRANCH CIRCUITS TO
BE UTILIZED TO RE-FEED EXISTING LOADS OUTSIDE OF THE PROPOSED
SCOPE OR WORK. THERE ARE APPROXIMATELY (6) ROOMS THAT
REQUIRE EXISTING BRANCH CIRCUITS (LIGHTING AND POWER) TO BE
EXTENDED AND FED FROM NEW PANEL ‘SL-1’ OR 'SL-2'. EXISTING
CRITICAL BRANCH CIRCUITS SERVING SOME OF THE DEVICES IN THESE
ROOMS SHALL REMAIN. THE PHASING AND CONSTRUCTION INTENT FOR
THIS IS TO KEEP THE EXISTING PANELS ENERGIZED ON A TEMPORARY
BASIS DURING THE PERIOD OF DEMOLITION AND CONSTRUCTION SUCH
THAT THE AREAS OUTSIDE THE SCOPE OF WORK MAY REMAIN
OPERATIONAL. ONCE THE NEW PANELS ARE INSTALLED AND
ENERGIZED (SHOULD BE SCHEDULED TO BE CONSTRUCTED EARLY IN
THE PROCESS), EXISTING BRANCH CIRCUITS SERVING AREAS OUTSIDE
THE SCOPE OF WORK CAN BE EXTENDED OVER TO THE NEW PANELS.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR ELECTRICAL DEMOLITION PLAN
DEMOLITION NOTESGENERAL DEMOLITION NOTES
DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL EQUIPMENT WITHIN
DESIGNATED AREA FOR SCOPE OF WORK AND ON WALLS BEING REMOVED,
EXCEPT WHERE MARKED OTHERWISE. THIS WORK INCLUDES COMPLETE
DEMO AND IS NOT LIMITED TO THE EQUIPMENT SHOWN ON DEMO PLANS.
EXISTING PANELS ON WALLS TO REMAIN SHALL BE LEFT OUT.
DISCONNECT AND REMOVE EXISTING FIRE ALARM SYSTEM IN AREA
DESIGNATED INCLUDING BUT NOT LIMITED TO F.A. DEVICES, WIRING, CONDUIT,
BOXES, PANELS, ETC. COORDINATE REMOVAL WORK WITH INSTALLATION OF
NEW FIRE ALARM SYSTEM DEVICES SUCH THAT AN OPERATIONAL FIRE ALARM
SYSTEM IS MAINTAINED THROUGHOUT PERIODS OF BUILDING OCCUPATION.
COORDINATE ANY SERVICE SHUT-DOWN WITH LOCAL FIRE OFFICIAL AND
OWNER. PROVIDE FIRE WATCH AS REQUIRED. PROVIDE TEMPORARY SMOKE
DETECTORS IN AREAS WHERE SPRINKLER SYSTEM WORK IS CONDUCTED TO
MAINTAIN FIRE PROTECTION DURING CONSTRUCTION PERIOD.
DISCONNECT AND REMOVE EXISTING WIRING, CONDUIT, BOXES, ETC. SERVING
ALL EQUIPMENT BEING REMOVED BY MECHANICAL AND OTHER TRADES.
REFER TO PLUMBING, MECHANICAL AND ARCHITECTURAL DRAWINGS FOR
COORDINATION OF REQUIRED WORK. REMOVALS SHALL BE COMPLETE BACK
TO SOURCE PANEL.
EXISTING ELECTRICAL ITEMS THAT ARE BEING DISCONNECTED AND REMOVED
AND NOT BEING REUSED SHALL BE DISPOSED OF PROPERLY.
ALL ABANDONED ELECTRICAL WIRING AND DEVICES SHALL BE REMOVED.
IF CONTINUITY OF WIRING TO EXISTING ELECTRICAL ITEMS IS INTERRUPTED BY
REMOVAL OF DEVICES, CONTRACTOR SHALL INSTALL ALL NECESSARY WIRING
AND RACEWAY TO ENSURE THE CONTINUITY OF CIRCUITRY IN OTHER AREAS.
CONTRACTOR SHALL TRACE APPLICABLE BRANCH CIRCUITS AND MAINTAIN
POWER TO AREAS OUTSIDE OF DEMOLITION SCOPE OF WORK.
REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL RELATED WORK.
ALL EXISTING LIGHT FIXTURES BEING REMOVED BUT NOT BEING REUSED
SHALL BE TURNED OVER TO THE OWNER.
1
2
3
4
5
6
7
8
3
Issuance Schedule
Number Date Description
1 2016.07.08 ADDENDUM #1
A B C D E.1C.9
TRANS.
VAULT
STORAGE
ROOM
CORRIDOR
GENERATOR
ROOM
EQUIPMENT ROOM
EL. 217.9
SOILED
LINENCORRIDOR
T PUB
ENVIRO SERV
STORAGE
FD
FD
VFC VFC
B
A
DD
A B C D E F G H J K L M
5.2
4.5
E.1
5.1
C.9 I
AREAWAY
GENERAL
STORAGE
RAMP
UP
STOREROOM
GENERAL
STORAGE
EL. 217.9
LINEN STORAGE
MEDICAL RECORDS
RADIATION
PROTECTION
ROOM
TRANS.
VAULT
STORAGE
ROOM
CORRIDOR
SOILED LINEN
GENERATOR
ROOM
CORR.
ELEV.
STAIRS
EQUIPMENT ROOM
CORR.
EL. 217.9
SOILED
LINEN
X-RAY
ROOM
RAD
STOR
CORRIDORELECTRICAL ROOM
MECHANICAL ROOM
DECONTAMINATION
EQUIP. WASH
LOUNGE
HSKP.
OFFICE
PROCESSED STORES
SORTING & PACKING
STERILIZERS
STEAM
LKRS
FEMALE
LKRSMALE
TOIL
FEMALE
TOIL
MALE
SHWR
AREAWAY
AREAWAY
ACCESS AREAWAY
CENTRAL STERILE PROCESSING & STERILE STORES
SOILED WORKROOM
DISPATCH
CORRIDOR
ELEV. LOBBY
SERVICE ELEV.
LOBBY
CORRIDOR
CORR.
SOILED CART
STAGING AREA
STAIR
CONFERENCE ROOM B
LINEN EQUIP. STORAGE
HSKP.
SOILED
STAIR
CORRIDOR
STOR
COMMUNICATIONS
EMERGENCY ELECTRIC ROOM
PBDS STORAGE
BREAKOUT
TEL/COM. RM.
ELEV.ELEV.
LINEN
CONTROL
CATH
LAB
T PATCLN SPLY
SCRUB
T PUBT PUB
ENVIRO SERV
STORAGE
VIEWING/
FILM
EQUIP
PASS.PASS.
PASS.
T. STAFF
PREP/RECOV PREP/RECOVPREP/RECOV
WK
AREA
HSKPGSOIL
UTL
PASS.
VEST.
LKR
RM
LKR
RM
OFF
NOUR
MEDS
MAYO XFCSUPPLY CART
3STERI25 STERI25
STERP01
PASST01
WASHD08
STILL03
STILL03A/C
SHELM36
WASHD20
GUNST01COFFE15TUNNEL WASHER
STERP01
REF.FD
FD FD
FD
FD
FD
FD
FD
XFCXFCXFCFD
XFC
MGCVFDVCFDVCFDVCFD
FD
FD
MIN. DOOR SIZECU-S2
CU-S1
P-2P-1
REMOVE EXISTING HOT
WATER PUMPS P-1 AND
P-2 AND INSTALL NEW
PUMPS, P-1 & P-2, ON
EXISTING PAD
2
NEW CONDENSING UNITS MOUNTED ON
ROOF
NEW PANEL
'PNL'
1
EXISTING DISTRIBUTION
PANEL 'WWMP' TO REMAIN
APPROXIMATE LOCATION
OF PUMPS
P2000 MAIN ELECTRIC ROOM
(LOCATION OF PANEL 'EE-L5')
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
As indicated
8/16/2016 11:25:28 AME-100
185-01-00
8/15/16
BASEMENT ELECTRICAL
PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
SCALE: 1/4" = 1'-0"1 BASEMENT ELECTRICAL PLAN
DRAWING NOTES
FURNISH AND INSTALL A NEW 480/277V PANEL RATED FOR
100A WITH A 90A MAIN CIRCUIT BREAKER. COORDINATE
EXACT LOCATION FOR PANEL WITH HOSPITAL FACILITIES
PRIOR TO MOUNTING. PANEL SHALL BE A 30 POLE UNIT
WITH (1) 25A-3P BRANCH CIRCUIT BREAKER TO SERVE ‘CU-
S1’ AND (1) 20A-3P BRANCH CIRCUIT BREAKER TO SERVE
‘CU-S2’. THE NEW PANEL SHALL BE FED FROM AN EXISTING
480V, 90A RATED FEEDER THAT IS FED FROM EXISTING
DISTRIBUTION PANEL ‘N’. THE FEEDER IS CURRENTLY
TERMINATED IN A BOX NEAR THE EXISTING AREAWAY AND
SHALL BE CUT BACK AND UTILIZED TO SERVE THE NEW
PANEL. COORDINATE THE EXACT LOCATION OF FEEDER
WITH HOSPITAL FACILITIES.
DISCONNECT AND REMOVE EXISTING BRANCH CIRCUITS
SERVING EXISTING HOT WATER PUMPS ‘P-1’ AND ‘P-2’.
UNITS ARE SERVED FROM AN EXISTING 208V PANEL WITHIN
THE MECHANICAL ROOM. PROVIDE A NEW BRANCH CIRCUIT
FOR EACH NEW PROPOSED PUMP ‘P-1’ AND ‘P-2’ (TO BE
LOCATED IN SAME LOCATION). BRANCH CIRCUITS SHALL BE
480V; 3#10, 1#10G., IN 3/4” CONDUIT FROM A NEW 25A-3P
CIRCUIT BREAKER IN EXISTING PANEL ‘EE-L5’. THIS PANEL
IS LOCATED IN THE ESSENTIAL EMERGENCY SIDE OF THE
P2000 MAIN ELECTRIC ROOM.
1
2
GENERAL NOTES
COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES
SUCH AS LIGHTING, EXIT SIGNS, SWITCHES, RECEPTACLES,
DATA/TEL., FIRE ALARM DEVICES, ETC., WITH ALL DEVICES
WITHIN MECHANICAL AND ELECTRICAL ROOMS SHALL BE
COORDINATED WITH PANELS, DUCTWORK, PIPING, CONDUIT,
ETC. FOR FINAL LOCATIONS.
TYPICAL HOMERUN FOR EACH BRANCH CIRCUIT SHALL BE FED
BY 2#12,1#12G.,3/4" CONDUIT TO A 20A-1P CIRCUIT BREAKER IN
PANELBOARD AS DESIGNATED, UNLESS SHOWN OTHERWISE.
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS IN ABOVE CEILING SPACE TO PERMIT
THE PLACEMENT OF LIGHTS, DEVICES, AND SPRINKLER HEADS
IN THE EXACT LOCATION SHOWN ON THE ARCHITECTURAL
DRAWINGS.
TYPICAL WIRING AND INTENT FOR OPERATION OF ROOMS AND
CORRIDORS WITH EMERGENCY AND NORMAL LIGHTING POWER
INCLUDES: OCCUPANCY SENSOR AND EMERGENCY RELAY FOR
CONTROL OF BOTH NORMAL AND EMERGENCY LIGHTING
FIXTURES, PROVIDE BYPASS RELAY FOR ENERGIZING
EMERGENCY LIGHTING UPON LOSS OF NORMAL POWER WHEN
THE EMERGENCY FIXTURE(S) ARE OFF. FLOOR PLANS SHOW
NORMAL BRANCH CIRCUIT GRAPHICAL CLARIFICATION. REFER
TO SPECIFIC LIGHTING WIRING DIAGRAMS ON DETAIL
DRAWINGS FOR SCHEMATIC WIRING INTENT OF OPERATION.
ROOMS THAT ARE FED VIA MANUAL SWITCHES (IE:ELECTRIC &
TELCOM): PROVIDE EMERGENCY RELAY MODUAL FOR ROOM
PER DETAIL ON DRAWING #E200 TO PROVIDE CONTROL AND
ENSURE ACTIVATION OF EMERGENCY LIGHTING IN THE EVENT
OF LOSS OF NORMAL POWER.
1.
2.
3.
4.
DRAWING NOTES
GENERAL NOTES
5.
SCALE: 3/32" = 1'-0"2 BASEMENT ELECTRICAL PLAN
Issuance Schedule
Number Date Description
1 2016.07.12 ADDENDUM #2
FECDOC
OC
D
DDD
DD
D
OCDOCDD DVS VS
DDDD
OC
3 3D
OC
OC
DDD D DDDD
D
DD
VSVS
VS
OC
D
D
OC
OC
J
D3
D3
SD
DS
MDDSCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
A1
A1
B1B1
A1
B1
A3
A3 A3
A3
A2
A2
A2
A2
A2 A2
A2
A1A1
A1 A1
A1
A1 A1
A1 A1
B1
B1
A1
A1A4A2
A2
A4
A2
A2
A2
A2 A2
A2 A2
A2 A2
A2 A2
A1
A2
A2 A2
A2 A2
A3 A3
A3A3
A3 A3 A3 A3
A3A3
A3 A3
A2
A2
A2
A2
A2
A2
A2 A2A2
A2 A2 A2
W1
U1
U1
U1
W1
U1
U1
U1 U1
X2
U1
U1
X2X2 A1A1A1A1A1A1A1
A1
A1
A1
A1
A1
A1 A1
X1
X1
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
A1
A1
D1
D1
D1
D1
D1
D1
A1
NL NL
NL
NL
NL
SL-1 SL-2
SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
A4
A4
U1
1
NL
U1 U1
1 1
U11
U1U1 1U1
U1
U1 U1
1
W2 W2
U1
1
U1
1
U1
U1
U1
1
B1
B1
D1
D1W1
A1
A1 A1 A1
A1
1
A1
W1
C1
C1
U1
U1
1
C1
C1
C1
C1
C1
U1
U1 U1
2
A1
A1
A1
A1
EXISTING LIGHTING TO REMAIN (TYP.)
3
X1
U1
1
U1
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:35 AMEL-101
185-01-00
8/15/16
GROUND FLOOR
ELECTRICAL LIGHTING PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
WIRED TO LOCAL 120V BRANCH CIRCUIT. COORDINATE SWITCH
LOCATION WITH ARCHITECT.
TIED INTO LOCAL EXISTING NIGHT LIGHT CIRCUIT SERVING
CORRIDOR FROM EXISTING PANEL "LS3GA".
PROVIDE POWER FOR EXAM LIGHT. (FIXTURE FURNISHED BY
OWNER, INSTALLED BY CONTRACTOR). UNIT HAS INTEGRAL
ON/OFF SWITCH.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR ELECTRICAL LIGHTING PLAN
GENERAL NOTES
COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES
SUCH AS LIGHTING, EXIT SIGNS, SWITCHES, RECEPTACLES,
DATA/TEL., FIRE ALARM DEVICES, ETC., WITH ALL DEVICES
WITHIN MECHANICAL AND ELECTRICAL ROOMS SHALL BE
COORDINATED WITH PANELS, DUCTWORK, PIPING, CONDUIT,
ETC. FOR FINAL LOCATIONS.
TYPICAL HOMERUN FOR EACH BRANCH CIRCUIT SHALL BE FED
BY 2#12,1#12G.,3/4" CONDUIT TO A 20A-1P CIRCUIT BREAKER IN
PANELBOARD AS DESIGNATED, UNLESS SHOWN OTHERWISE.
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS IN ABOVE CEILING SPACE TO PERMIT
THE PLACEMENT OF LIGHTS, DEVICES, AND SPRINKLER HEADS
IN THE EXACT LOCATION SHOWN ON THE ARCHITECTURAL
DRAWINGS.
TYPICAL WIRING AND INTENT FOR OPERATION OF ROOMS AND
CORRIDORS WITH EMERGENCY AND NORMAL LIGHTING POWER
INCLUDES: OCCUPANCY SENSOR AND EMERGENCY RELAY FOR
CONTROL OF BOTH NORMAL AND EMERGENCY LIGHTING
FIXTURES, PROVIDE BYPASS RELAY FOR ENERGIZING
EMERGENCY LIGHTING UPON LOSS OF NORMAL POWER WHEN
THE EMERGENCY FIXTURE(S) ARE OFF. FLOOR PLANS SHOW
NORMAL BRANCH CIRCUIT GRAPHICAL CLARIFICATION. REFER
TO SPECIFIC LIGHTING WIRING DIAGRAMS ON DETAIL
DRAWINGS FOR SCHEMATIC WIRING INTENT OF OPERATION.
ROOMS THAT ARE FED VIA MANUAL SWITCHES (IE:ELECTRIC &
TELCOM): PROVIDE EMERGENCY RELAY MODUAL FOR ROOM
PER DETAIL ON DRAWING #E200 TO PROVIDE CONTROL AND
ENSURE ACTIVATION OF EMERGENCY LIGHTING IN THE EVENT
OF LOSS OF NORMAL POWER.
1.
2.
3.
4.
DRAWING NOTESGENERAL NOTES
3
5.
Issuance Schedule
Number Date Description
FECa
GF
a
GF
a
GF
TPTP
TP
aGFa
GF
a
GF
a
aGFaGFa
GF
a
GF
TP TPGFTPTPTPTP
a
GF aGFaGFGFa
GF
a
GF
GFa
GF
aGFaGFa
GF
a GFGFa
GFGF
aGFTP
TPTP TPTPTP
GF aGFa
GF
GF
SD
DS
M aa
GF TPTPa
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
SL-1 SL-2
SL-1
SL-1
SL-1
SL-1
SL-1
SL-2
SL-1
SL-1
SL-2
SL-2
SL-1 SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
SL-1
SL-2
SL-1
SL-1
SL-1
SL-1
5
5
X3
X3
SL-1
4
8
6
8
7
SL-2
X3
5
4
1
SL-2
SL-2
SL-2
7
8
SL-28
6 4
SL-2
SL-2
SL-2
3B
3A
3B
2
SL-1
TP
SL-1
ICE
SL-1
SL-1
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:39 AMEP-101
185-01-00
8/15/16
GROUND FLOOR
ELECTRICAL POWER PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
PROVIDE A 250V, 40A-2P ENCLOSED CIRCUIT BREAKER WITH SHUNT TRIP
ACCESSORY. UNIT SHALL BE WALL MOUNTED AS SHOWN. PROVIDE 3#8, 1#10G. IN
1” CONDUIT FROM A 40A-2P CIRCUIT BREAKER IN PANEL ‘SL-2’ TO SERVE THE
WALL MOUNT CIRCUIT BREAKER. THEN PROVIDE SAME FEEDER/CONDUIT FROM
WALL MOUNT CIRCUIT BREAKER TO THE WIREWAY AND RUN FEEDER IN POWER
SECTION OF WIREWAY TO FEED THE STEREO GENERATOR.
WIREWAY (10” WIDE X 3-1/2”D) WITH (2) SECTION BARRIER. VERTICAL RUN UNIT
DROP FROM CEILING. TIES INTO HORIZONTAL SECTION ABOVE ACCESSIBLE
CEILING AND TO HORIZONTAL SECTION RUN.
WIREWAY (10” WIDE X 3-1/2”D) WITH (2) SECTION BARRIER. HORIZONTAL RUN
UNIT ABOVE ACCESSIBLE CEILING. COORDINATE ROUTING WITH EXISTING
EQUIPMENT. WIREWAY (10” WIDE X 3-1/2”D) WITH (2) SECTION BARRIER.
HORIZONTAL RUN UNIT RUN ALONG WALL AT 12”AFF (TO BOTTOM OF UNIT)
CONNECTING VERTICAL RUN UNIT TO AREA BEHIND STEREO GENERATOR AND
CONNECTING INTO CONTROL ROOM BELOW COUNTER. PROVIDE GROMMETTED
CUT-OUT IN WIREWAY AT THE STEREO GENERATOR, CONTROL ROOM COUNTER
EQUIPMENT AND MONITOR STAND. REFER TO HOLOGIC PRE-INSTALLATION GUIDE
AND SITE REPRESENTATIVE FOR LOCATIONS AND REQUIREMENTS.
REMOTE MOUNTED EMERGENCY POWER-OFF SHUNT TRIP BUTTON (BY
CONTRACTOR). PROVIDE COVER FOR BUTTON.
XRAY WARNING LIGHT (BY CONTRACTOR). REFER TO HOLOGIC PRE-
INSTALLATION GUIDE AND SITE REPRESENTATIVE FOR LOCATIONS AND
REQUIREMENTS. LIGHT SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE.
PROVIDE A 250V, 40A-2P ENCLOSED CIRCUIT BREAKER WITH SHUNT TRIP
ACCESSORY. UNIT SHALL BE WALL MOUNTED AS SHOWN. PROVIDE 3#8, 1#10G. IN
1” CONDUIT FROM A 40A-2P CIRCUIT BREAKER IN PANEL ‘SL-2’ TO SERVE THE
WALL MOUNT CIRCUIT BREAKER.
WIREMOLD TYPE 4000 SERIES HORIZONTAL RACEWAY WITH (2) SECTION
BARRIER. MOUNT AT 12”AFF. REFER TO HOLOGIC PRE-INSTALLATION GUIDE AND
SITE REPRESENTATIVE FOR LOCATIONS AND REQUIREMENTS.
WIREMOLD TYPE 4000 SERIES VERTICAL RACEWAY WITH (2) SECTION BARRIER.
REFER TO HOLOGIC PRE-INSTALLATION GUIDE AND SITE REPRESENTATIVE FOR
LOCATIONS AND REQUIREMENTS.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR ELECTRICAL POWER PLAN
GENERAL NOTES
COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES SUCH AS
LIGHTING, EXIT SIGNS, SWITCHES, RECEPTACLES, DATA/TEL., FIRE
ALARM DEVICES, ETC., WITH ALL DEVICES WITHIN MECHANICAL
AND ELECTRICAL ROOMS SHALL BE COORDINATED WITH PANELS,
DUCTWORK, PIPING, CONDUIT, ETC. FOR FINAL LOCATIONS.
TYPICAL HOMERUN FOR EACH BRANCH CIRCUIT SHALL BE FED BY
2#12,1#12G.,3/4" CONDUIT TO A 20A-1P CIRCUIT BREAKER IN
PANELBOARD AS DESIGNATED, UNLESS SHOWN OTHERWISE.
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS IN ABOVE CEILING SPACE TO PERMIT THE
PLACEMENT OF LIGHTS, DEVICES, AND SPRINKLER HEADS IN THE
EXACT LOCATION SHOWN ON THE ARCHITECTURAL DRAWINGS.
1.
2.
3.
4.
DRAWING NOTESGENERAL NOTES
3
4
5
6
7
8
PROVIDE A NEW PANEL ‘SL1’ AS SHOWN ON DRAWINGS. REFER
TO PANEL SCHEDULE ON ‘MEP’ DRAWINGS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS. PROVIDE 4#2, 1#8G. IN 1-1/2”
CONDUIT FROM AN EXISTING 100A-3P CIRCUIT BREAKER (MADE
SPARE BY DEMOLITION) IN EXISTING MAIN DISTRIBUTION PANEL
‘WWMP’ LOCATED IN THE BASEMENT ELECTRIC ROOM BELOW.
REFER TO DEMOLITION/EXISTING DRAWING FOR LOCATION OF
EXISTING BASEMENT ELECTRIC ROOM.
PROVIDE A NEW PANEL ‘SL2’ AS SHOWN ON DRAWINGS. REFER
TO PANEL SCHEDULE ON ‘MEP’ DRAWINGS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS. PROVIDE 4#4/0, 1#4G. IN 2-
1/2” CONDUIT FROM A NEW 200A-3P CIRCUIT BREAKER IN
EXISTING MAIN DISTRIBUTION PANEL ‘WWMP’ LOCATED IN THE
BASEMENT ELECTRIC ROOM BELOW. (REMOVE EXISTING 100A-3P
CIRCUIT BREAKER MADE SPARE BY DEMOLITION AND REPLACE
WITH NEW CIRCUIT BREAKER AS REQUIRED). REFER TO
DEMOLITION/EXISTING DRAWING FOR LOCATION OF EXISTING
BASEMENT ELECTRIC ROOM.
ELECTRICAL CONTRACTOR SHALL PROVIDE A PULLBOX ABOVE
EXISTING PANEL ‘WWMP’ IN BASEMENT AND LEAVE FEEDERS
FROM NEW PANELS ‘SL-1’ AND ‘SL-2’ WITH 12’ OF EXTRA
CONDUCTOR LENGTH. THIS IS FOR HOSPITAL TO PERFORM ‘LIVE-
WORK’ TIE-IN TO EXISTING PANEL. PROVIDE NEW CIRCUIT
BREAKER, AS REQUIRED, AND LEAVE FOR FACILITIES WITHIN
ROOM. COORDINATE WORK AND TIMING WITH HOSPITAL
FACILITIES.
1.
2.
POWER DISTRIBUTION NOTES
3A
3B
3.
Issuance Schedule
Number Date Description
E
E NNS
F
NDNDNN
N
NA NA NDNDND
NNNN
E
E
NA
NSNSND
MNS ND
ES
S
S SSSS S S
S
S
S
S
S
CR CRPPPPPP CR
PP
J
J
S
SD
DS
M
NS NS
NAE
E
N
S
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
6 7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
SL-1 SL-2
EXISTING TECHNOLOGY
ROOM
1
3 (TYP.)
2
4 (TYP.)
4 (TYP.)
4 (TYP.)
4 (TYP.)
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:25:42 AMES-101
185-01-00
8/15/16
GROUND FLOOR
ELECTRICAL SPECIAL
SYSTEMS PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
TIE INTO LOCAL 120V RECEPTACLE EMERGENCY BRANCH CIRCUIT
SERVING SUB-WAITING AREA.
TIE INTO LOCAL 120V RECEPTACLE EMERGENCY BRANCH CIRCUIT
CORRIDOR.
NEW PAGING SPEAKERS. REFER TO SPECIFICATION SECTION FOR
ADDITIONAL INFORMATION. PROVIDE NEW WIRING FROM SPEAKERS
BACK TO EXISTING PAGING AMPLIFIER SYSTEM RACK LOCATED IN
THE BASEMENT ESSENTIAL SIDE OF THE P2000 MAIN ELECTRIC
ROOM. COORDINATE LOCATION WITH HOSPITAL FACILITIES.
PROVIDE NEW AMPLIFIER FOR THIS AREA. SEPARATE EXISTING
ROOMS THAT ARE JUST OUTSIDE THE AREA OF SCOPE THAT ARE
TIED TO THE ARE BEING RENOVATED AND MAINTAIN ON THEIR
EXISTING AMPLIFIER.
EXISTING SYSTEM IS NOTIFIER. REVIEW EXISTING CONDITIONS AND
COORDINATE DIRECTLY WITH NOTIFIER TECHNICIAN AND HOSPITAL
FACILITIES. THE EXISTING ADDRESSABLE LOOP SHALL BE TIED OFF
AND MAINTAINED AS IT SERVES THE UPPER FLOORS. INITIATION
LOOP FOR THE PROPOSED AREA WITHIN THE SCOPE OF WORK
COULD BE TIED INTO THE CANCER CENTER (ONCOLOGY LOOP)
RECENTLY COMPLETED. SPEAKERS CAN BE WIRED INTO THE FIRE
ALARM CONTROL PANEL LOCATED IN THE BASEMENT ESSENTIAL
SIDE OF THE P2000 MAIN ELECTRIC ROOM. PROVIDE AN
ALLOWANCE FOR FURNISHING AND INSTALLING A NEW ‘FCPS’ FOR
THE STROBE UNITS. THIS CAN BE LOCATED IN THE NEW ELECTRIC
CLOSET.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR ELECTRICAL SPECIAL SYSTEMS PLAN
DRAWING NOTESGENERAL NOTES
COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES SUCH AS
LIGHTING, EXIT SIGNS, SWITCHES, RECEPTACLES, DATA/TEL., FIRE
ALARM DEVICES, ETC., WITH ALL DEVICES WITHIN MECHANICAL
AND ELECTRICAL ROOMS SHALL BE COORDINATED WITH PANELS,
DUCTWORK, PIPING, CONDUIT, ETC. FOR FINAL LOCATIONS.
TYPICAL HOMERUN FOR EACH BRANCH CIRCUIT SHALL BE FED BY
2#12,1#12G.,3/4" CONDUIT TO A 20A-1P CIRCUIT BREAKER IN
PANELBOARD AS DESIGNATED, UNLESS SHOWN OTHERWISE.
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS IN ABOVE CEILING SPACE TO PERMIT THE
PLACEMENT OF LIGHTS, DEVICES, AND SPRINKLER HEADS IN THE
EXACT LOCATION SHOWN ON THE ARCHITECTURAL DRAWINGS.
1.
2.
3.
4.
GENERAL NOTES
3
4
Issuance Schedule
Number Date Description
E
TX
E
VISUAL UNIT WITH BUZZER
EMERGENCY CALL-FOR-AID.
MOUNTED 48" A.F.F. AT TOILET
LOCATION. CORD TO EXTEND TO
WITHIN 6" OF THE FLOOR
NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. UTILIZE (2) #18 IN RACEWAY FOR ALL WIRING, UNLESS OTHERWISE NOTED.
(2) #12 & (1) #12 GND. IN 3/4"C. TO LOCAL
120 VOLT LIGHTING CIRCUIT OR
RECEPTACLE CIRCUIT
FLOOR
CEILING
TRANSFORMER 120V/24V, REMOTE
MOUNTED ABOVE NEAREST
ACCESSIBLE CEILING IN NEMA1
ENCLOSURE
HANDICAPPED TOILET CALL FOR AID DETAIL
NOT TO SCALE
HANDICAPPED TOILET CALL FOR AID DETAIL
PANEL
DUPLEX POWER
RECEPTACLE
DETAIL NOTES:
1. ELECTRICAL DEVICE PLATE LABEL OR NAMEPLATE SHALL IDENTIFY THE SOURCE OF POWER TO THE
DEVICE. LABELS OR NAMEPLATES SHALL BE AN APPROVED PERMANENT TYPE.
LIGHT
SWITCH
NAMEPLATE
OR
LABEL
CIRCUIT
XXX-XX XXX-XX
TYPICAL DEVICE LABELING DETAIL
NOT TO SCALE
DETAIL NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL NAMEPLATE REQUIREMENTS.
2. NAMEPLATE TO BE 1/16" PLASTIC WITH 1/4" MINIMUM CENTER LETTER LAMINATION.
FACE TO BE BLACK WITH WHITE ENGRAVED LETTERS FOR NORMAL POWER; RED WITH
WHITE ENGRAVED LETTERS FOR ESSENTIAL POWER.
3. SECURE NAMEPLATE TO SURFACES 3M TAPE OR EQUAL.
"HVCB1-ED1"
277/480V., 3∅, 4W
FED FROM "DP-CB1-LAB/ED"
TYPICAL NAMEPLATE DETAIL
SCALE: NTS
PANEL NAME
PANEL CIRCUIT
SM-WING, EM PWR RM-100A
TYPICAL DEVICE LABELING DETAIL
TYPICAL NAMEPLATE DETAIL
TERMINATE RACEWAY WITH PLASTIC BUSHING
IN AN ACCESSIBLE LOCATION ABOVE CEILING
8" RADIUS
ELBOW
CEILING
(1) 1" CONDUIT WITH PULL
STRING
(2) GANG DEEP BACK BOX WITH
SINGLE GANG EXTENSION BOX 18"
AFF. VERIFY HEIGHT WITH
ARCHITECT
FLOOR
PROVIDE COVER PLATE.
FINISH AND COLOR
SELECTED BY ARCHITECT
UTILIZE THIS DETAIL WHEN ANY OF THE FOLLOWING
SYMBOLS ARE SHOWN ON PLAN:
NOT TO SCALE
TELEPHONE/DATA OUTLET DETAILTELEPHONE/DATA OUTLET DETAIL
MSM
MSM
LOW VOLTAGE
3 #14, 3/4"C.
SWITCH
3 WAY
LOW VOLTAGE
3 #14, 3/4"C.
STATIONSINGLE POLESWITCH ARRANGEMENT3/4"C., 120V
2 #12,+GRD.,ARRANGEMENT3-WAY SWITCHMASTER
CONTROL
STATION
3/4"C., 120V
2 #12,+GRD.,
MASTER
CONTROL
3 LAMP
BALLAST
3 LAMP
BALLAST
3 #12,+GRD.,
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
3/4"C.
SWITCH
3 WAY
2#12,+GRD.,
SWITCH
SINGLE POLE
3/4"C.
LIGHTING OCCUPANCY SENSOR NOTES:
COORDINATE FINAL WIRING REQUIREMENT OF SENSOR, POWER PACKS, CONTROLLERS WITH MANUFACTURER.
SENSOR(S) SHALL REPORT TO THE MASTER CONTROL STATION. PROVIDE LOW VOLTAGE PLENUM RATED WIRING
BETWEEN SENSOR AND MASTER STATION PER MANUFACTURER'S REQUIREMENTS.
MASTER CONTROL STATION SHALL BE MOUNTED ABOVE CEILING IN AREA BEING SERVED.
MASTER CONTROL STATION SHALL TURN ON THE LIGHTING CIRCUIT UPON ACTIVATION OF OCCUPANCY SENSOR.
CONTROL STATION SHALL TURN OFF THE LIGHTS WHEN SENSOR HAS DEACTIVATED AND AFTER A PREDETERMINED TIME
DELAY.
WALL SWITCH(ES), ONLY AS APPLICABLE TO PROJECT, SHALL BE WIRED TO BY-PASS THE SENSOR TURNING THE LIGHTS OFF.
COORDINATE SETTINGS FOR SENSORS WITH ARCHITECT AND OWNER. TIME-OUT DELAY SHALL BE SET TO MAXIMUM AS
INITIAL SETTING.
1.
2.
3.
4.
5.
6.
TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM
NOT TO SCALE
TYPICAL OCCUPANCY SENSOR WIRING DIAGRAM
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
As indicated
8/16/2016 11:25:29 AME-400
185-01-00
8/15/16
ELECTRICAL DETAILS
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
Issuance Schedule
Number Date Description
WAP
WAP
SD
DS
M
SCOPE OF WORK
RADIOLOGIST
WORKROOM
G-124
ULTRASOUND
EQUIPMENT
TASK
CHAIR
(EXISTING)
STRETCHER
STRETCHER
BIOPSY TABLE
SUCTION DEVICE
STERILE SUPPLY
CART
RED BOX BLACK BOX
GUEST
CHAIR
STEREO MONITOR
STAND
SOILED LINEN
HAMPER
SOILED LINEN
HAMPER
GUEST
CHAIR
SHARPS
EXAM TABLE
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
REFRIDGERATOR
SHARPS
SOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
SHARPS
GLOVES
AQUISITION
WORKSTATION
WHEELCHAIR
RED BOX
WALL MOUNTED
PADDLES
SET UP TRAY
SUCTION DEVICE
C-ARMSOILED LINEN
HAMPER
GUEST
CHAIR
GUEST
CHAIR
5 MP MONITOR STAND
FROM STEREOTATIC
LARGE
MAMMOGRAPHY
G-120
AQUISITION
WORKSTATION
WHEELCHAIR
SET UP TRAY
SUCTION DEVICE
C-ARM
CLEAN WORK AREA
G-126A
INTERVIEW 2
G-117
PATIENT CHANGING
ROOM 3
G-111C
TASK
CHAIR
TASK
CHAIRWALL MOUNTED
PADDLES
LARGE BIOPSY CHAIR
PATIENT CHANGING
ROOM 1
G-111D
PATIENT CHANGING
ROOM 2
G-111B
STAFF TOILET
G-130A
TASK
CHAIR
EXAM 2
G-107
EXAM TABLE
SOILED HOLDING
ROOM
G-112
CHANGING PATIENT
TOILET
G-111A
TASK
CHAIR
BONE DENSITY
G-113
GOWNED
SUB-WAITING
G-110
SOILED LINEN
HAMPER
TASK
CHAIR
GUEST
CHAIR
GUEST
CHAIR
TASK
CHAIR
PRINTER
FILM COPIER
PRINTER
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
WITHOUT
ARMS
TASK
CHAIR
(EXISTING)
BONE DENSITY TABLE
BONE DENSITY
WORKSTATION/CART
WHEELCHAIR
SCALE
SOILED LINEN
HAMPER
GUEST
CHAIR
TASK
CHAIR
(EXISTING)
STADIOMETER
GLOVES
PRINTER, SM
SOAP
PAPER
TOILET PAPER
SOAP
PAPER
TOILET PAPER
PAPER
SOAP SOILED LINEN BINTOILET PAPER
TOILET PAPER
COAT HOOKS
CODE CART
METRO RACK
TRAY RACK
5 MP MONITOR STAND
STEREO GENERATOR
MIRCROWAVE
KEURIG
PURELL
PURELL PURELL
PURELL
PURELL
PURELL
PURELLPURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
PURELL
RED BOX
SHARPS
SHARPS
TASK
CHAIR
(EXISTING)
PURELL
PURELL PURELLPURELL
TASK
CHAIR
TASK
CHAIR
WITHOUT
ARMS
BACKERBOARD
METRO RACK
WOW
TRASH
STANDING WATER
COOLER
RECYCLE
CONFIDENTIAL
RECYCLE
MOBILE
PED
MOBILE
PED
RADIOLOGIST
WORKSTATION
(EXISTING)
RADIOLOGIST
WORKSTATION
(EXISTING)
PHONE PHONE
SIDE
TABLE
-
SMALL
TASK
CHAIR
WITHOUT
ARMS
STRETCHER
ROUND
TABLE
WITH
4
CHAIRS
LOUNGE
CHAIR
SCANNER SCANNER
DESK DESK
LOUNGE
CHAIR
PURELL
INTERVIEW 1
G-118
ICE
PAPER
SOAP
TRASH
DEFIBRILLATOR
SOAP
PAPER
PRINTER, SM TASK
CHAIR
STAFF BREAK
ROOM
G-123
CORRIDOR
G-128
TECH WORKROOM
G-130
MANAGER'S OFFICE
G-130B
STRETCHER
WAITING
G-127
NURSE STATION
G-126
ELECTRICAL
CLOSET
G-125
WAITING ROOM
G-119
RECEPTION
G-114C
CORRIDOR
G-119B
WAITING ROOM
PATIENT TOILET
G-119A
MEN'S CHANGING &
WAITING
G-114
PATIENT TOILET
G-109
CORRIDOR
G-115D
CORRIDOR
G-115C
STEREOTACTIC
G-105
NAVIGATOR'S
OFFICE
G-116
ULTRASOUND
G-121MAMMOGRAPHY
G-122
EXAM 1
G-106
COPIER
RECYCLE
WASTEBASKET
PURELL
SIDE
TABLE
SETTEE
SIDE
TABLE LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
WHEELCHAIR
TRASH
SOAP
LOUNGE
CHAIR
LOUNGE
CHAIR
WATER
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
SETTEE
COFFEE
TABLE
SETTEE SIDE
TABLE
LOUNGE
CHAIR
LOUNGE
CHAIR
LOUNGE
CHAIR
SIDE
TABLE
MOBILE
PED
BLACK BOX
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
MOBILE
PED
TASK
CHAIR
WASTEBASKET
RECYCLE
TRASH
RECYCLE
WASTEBASKET
SOILED LINEN
HAMPER
TRASH
PAPER
SOAP
PAPER
TRASH
SOAP
TRASH
PHONE
PAPER
SOAP
COAT HOOKS
VIEW BOX
TRASH PAPER SOAP
PHONE
PURELL
PAPER SOAP
PHONE PHONE
WASTEBASKET
RECYCLE
SHARPS SHARPS
SHARPS
PHONE
PHONE
GLOVES
GLOVESGLOVES
PHONE
PURELL
SOAPPAPER
TRASH
WASTEBASKET
RECYCLE
SOAP
PAPER
PAPER SOAP
PAPERSOAP
TRASH
GLOVESGLOVES
SOAP
PAPER PAPER
PAPER SOAP
PHONE
TRASH TRASH
PHONE
COMPUTER
COMPUTER
PHONE
PHONESHARPS
SHARPS PHONE
COMPUTER COMPUTER
SOAP
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
MIRROR, TALL
PAPER
WATER
TRASH
TRASH
WASTEBASKET
PHONE
COMPUTER COMPUTER
PHONE
WASTEBASKET
COMPUTER
PHONE
PHONE
TRASH
WASTEBASKET
RECYCLE
RECYCLE RECYCLE
TRASH
TRASH
TRASH
COAT HOOKS
TRASH
UC FRIDGE
PHONE
COMPUTER
STABLERISE
STABLERISE
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
SCANNER
SCANNER
SCANNER
CPU
CPU
CPU
OFFICE
G-108
CPU
CPU
5
6 7 8
910
1112131415
18 19 20 21 22
16
17
25
26
27
28
1
1 1
11
1
1
1
EXISTING
TECHNOLOGY ROOM
2 TYP.
1 1
Scale: Date Issued:
Project Number:
Isgenuity LLC
321 Summer Street, Suite 401
Boston, MA 02210
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
NORTH
MEP/FP Engineer
BVH Integrated Services
50 Griffin Road South
Bloomfield, CT 06002
Tel 860 286 9171
Fax 860 242 0236
ISSUED FOR CONSTRUCTION
BVH: 21-15-085REFER TO MEP DRAWINGS FOR ADDITIONAL INFORMATION.
1/4" = 1'-0"8/16/2016 11:26:30 AMT-101
185-01-00
8/15/16
GROUND FLOOR
TECHNOLOGY PLAN
COOLEY DICKINSON
HOSPITAL
COMPREHENSIVE BREAST
CARE CENTER
DRAWING NOTES
DATA CABLING (TYPE 6A) AND VOICE CABLING (TYPE 5E) SHALL
BE RUN BY THE HOSPITAL VENDOR. CONTRACTOR SHALL
PROVIDE A CONDUIT WITH PULLWIRE FROM BOX TO ABOVE
ACCESSIBLE CEILING. VOICE JUNCTION BOX IN THIS LOCATION
SHALL BE AT 45” AFF. DATA CABLING IN THIS LOCATION SHALL BE
RUN DOWN TO 18” AFF. REFER TO TYPICAL DETAIL ON
ELECTRICAL DRAWINGS.
DATA CABLING (TYPE 6A) AND VOICE CABLING (TYPE 5E) SHALL
BE RUN BY THE HOSPITAL VENDOR. CONTRACTOR SHALL
PROVIDE A CONDUIT WITH PULLWIRE FROM BOX TO ABOVE
ACCESSIBLE CEILING. DATA/VOICE JUNCTION BOX SHALL BE
MOUNTED AT 18” AFF. REFER TO TYPICAL DETAIL ON
ELECTRICAL DRAWINGS.
1
2
SCALE: 1/4" = 1'-0"1 GROUND FLOOR TECHNOLOGY PLAN
DRAWING NOTESGENERAL NOTES
COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES SUCH AS
LIGHTING, EXIT SIGNS, SWITCHES, RECEPTACLES, DATA/TEL., FIRE
ALARM DEVICES, ETC., WITH ALL DEVICES WITHIN MECHANICAL
AND ELECTRICAL ROOMS SHALL BE COORDINATED WITH PANELS,
DUCTWORK, PIPING, CONDUIT, ETC. FOR FINAL LOCATIONS.
TYPICAL HOMERUN FOR EACH BRANCH CIRCUIT SHALL BE FED BY
2#12,1#12G.,3/4" CONDUIT TO A 20A-1P CIRCUIT BREAKER IN
PANELBOARD AS DESIGNATED, UNLESS SHOWN OTHERWISE.
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS IN ABOVE CEILING SPACE TO PERMIT THE
PLACEMENT OF LIGHTS, DEVICES, AND SPRINKLER HEADS IN THE
EXACT LOCATION SHOWN ON THE ARCHITECTURAL DRAWINGS.
1.
2.
3.
4.
GENERAL NOTES
Issuance Schedule
Number Date Description