17A-050 (8) ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. THIS SYSTEM IS GRID-INTERTIED VIA A AC ALTERNATING CURRENT UL-LISTED POWER-CONDITIONING INVERTER. BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. CONC CONCRETE 3. A NATIONALLY-RECOGNIZED TESTING DC DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. CITY EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING CITY OF i'.!:_ : i HAMPTON EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, BUILDING ✓LPARTMENT FSB FIRE SET-BACK A SIGN WILL BE PROVIDED WARNING OF THE GALV GALVANIZED HAZARDS PER ART. 690.17. GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE GND GROUND MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY These plans have been reviewed HDG HOT DIPPED GALVANIZED PHASE AND SYSTEM PER ART. 210.5. I CURRENT 6. CIRCUITS OVER 250V TO GROUND SHALL And approved. • Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). !so SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER - - kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR Date /7— as - �� kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC LBW LOAD BEARING WALL DISCONNECTING MEANS PER ART. 690.31(E). MIN MINIMUM 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN (N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BYSignature /i - - ALEUT NEUTRAL UL LISTING. _ NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT NE OC ON CENTER UL-LISTED LOCATION PROVIDED BY THE PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING P01 POINT OF INTERCONNECTION HARDWARE. PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS. S STAINLESS STEEL STC STANDARD TESTING CONDITIONS TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER VICINITY MAP INDEX Vac VOLTAGE AT OPEN CIRCUIT W WATT I 3R NEMA 3R, RAINTIGHT PV1 COVER SHEET PV2 PROPERTY PLAN - 0 PV3 SITE PLAN EWS LICENSE GENERAL NOTES k c PV4 STRUCTURAL I GR fir. PV5 THREE LINE DIAGRAM 5 •,-. Cutsheets Attached 1. ALL WORK TO BE DONE TO THE 8TH EDITION �Ohy F �Ph <d'.nBCly �ij GEN #168572 OF THE MA STATE BUILDING CODE. M delle S . TOO) l�A/, CLEC 1136 MR 2. ALL ELECTRICAL WORK SHALL COMPLY WIN .'i.?` THE 2014 NATIONAL ELECTRIC CODE INCLUDING iBridge Rd MASSACHUSETTS AMENDMENTS. MODULE GROUNDING METHOD: ZEP SOLAR Rd 8r'd9e - . ' ) REV BY DATE COMMENTS AHJ: Northampton - • I ®®°ATl COMMENTS UTILITY: National Grid USA (Massachusetts Electric) '' —®_ Google al T1 . in� CONFIDENTIAL - ONE INFORMATION HEREIN 108 NUMBER JB-0102528 00 PAEMSE CMEk DESCRIPTION: DEW \\, CONTMNED SHALL NOT BE us0 FOR THE JASON HARDER JASON HARDER RESIDENCE Shuhao Bal �_T, NOR SH a ANYONE EXCEPT IN %HOLY INC., NORM IIM: 144 BRIDGE RD S0Ia1Ci Y. N SHALL IT BE MsaosED IN XNDEE OR IN CompMount Type C 5.72 KW PV ARRAY XPi% PART TO OTHERS OUTSIDE THE REoPIors ONCAMIZAfl .EXCEPT N CONNECTION MTH uroMes NORTHAMPTON, MA 01062 THE SALE MD USE or ME RCS EC1IW 22) REC p REC260PEZ 24 St North Orin,°tiding Z Unit II SOVAOTY EWIPAFNT, VAIHWT THE NRITRN xMRM: PACE NAV: SHEET REV: DAM VortT: (650)e] aou f(e50T 6b-1M9 P[I AISSIO Sq ARO1Y INC. Delta ; Solivia 5.2 TL 4132442287 3 2 4422 8 7 COVER SHEET PV 1 11/19/2016 (688)-Sa-OTY(7e5-2469) .n..menryam 144 Bridge Rd (E) DRIVEWAY I A \\\\ r_h . . , PROPERTY PLAN N -0' Scale:1' = 20' w elk p 20' 40' %I E S JB-0102528 00 PREMISE DYNER DESCRIPTION: DESIGN: CONFIDENTIAL S A THE TIBE USED F HEREIN .IDB MNBDi: 4}..t.. A's CONTAINED SHALL NOT eE usm Ppt YJASON HARDER JASON HARDER RESIDENCE Shuhao Rai BENEFIT OF.ANYONE EXCEPT minor(INC..NWHIM SMoIE �' " NOR SHALL N BE DISCLOSED IN MIIX£OR IN Comp Mount Type C 144 BRIDGE RD 5.72 KW PV ARRAY PART TO()PIERS OUTSIDE THE RECIPIENTS YEOLIES: NORTHAMPTON, MA 01062 ORGANIZATION.IlEXCEPT IN CDNNECPnI MTH 24 St. Ma1F DPM. kM 0g 2 Unit 11 THE SME AND USE Q TIN RESPECTIVE (22) REC N REC260PE2 PAGE NAME WET AEY: OAK: Yarborough,SA 01]s2 VM ARaTY EQUIPMENT, WITHOUT THE WRITTEN NVFRRR: T. (650)5]B-roue F (b H7 5.19-rozs PERMISSION a SOVRaIY INC. Delta q SOlivia 5.2 TL 4132442287 PROPERTY PLAN PV 2 11/19/2016 (Axe}wt-aTr(>ss-zles) ....aw,Scam 144 Bridge Rd ����GO� a S " -'A- M PITCH: 1 ARRAY PITH: 1 355 1MP2 AZIMUTH:355 ARRAY AZIMUTH: /// -16 MATERIAL: Comp Shingle STORY 2 Stories (E) DRIVEWAY - �4 tN OF at Y. at NG c CML 1 NO.52791 "' ( Digitally signed by Henry • Henry mu14 F0AS7EPF° DN:cn=zenry0nu, •\ � em ' email=nxnupsulxrdryaum, \ ou=ADOBE(r)-AATI,c-US, Z h u o=Solarcity Corporation - Dale:2016.11.19 21:04:44 B -0800' 1 1 LEGEND City of Northampton Building Department 0 (E) UTILITY METER & WARNING LABEL Plan Review 2 2 Main Street ® & WARNING INVERTER LINTEGRATEDTDC DISCO LABELS ®®�'■♦�Rd1\!� Northampton. MA 01060 ® DC DISCONNECT & WARNING LABELS MUM � pa AC DISCONNECT & WARNING LABELS /II lf2.TUM Ilea' DC JUNCTION/COMBINER BOX & LABELS _ ���, ® ® 0 DISTRIBUTION PANEL & LABELS 0 LOAD CENTER & WARNING LABELS ODEDICATED PV SYSTEM METER F.�.I I-- --- AC AC xv RAPID SHUTDOWN 1�1 ,-, STANDOFF LOCATIONS CONDUIT RUN ON EXTERIOR D ' © M— CONDUIT- GATE/FENCE N ON INTERIOR / 0 HEAT PRODUCING VENTS ARE RED L-2_1 Il INTERIOR EQUIPMENT IS DASHED SITE PLAN N Scale: 1/8" = 1' W 4111911 Front Of House o 1' B' 16' Ivry e s PREII OMER 0fSCRPIICI: DESIGN: CONTIXxnu - THE ITBEpUSED FOR MEREIN JOB NUMBER: JB-0102528 00 JASON HARDER JASON HARDER RESIDENCE Shuhao Boi NM eie SOhrCl}" CONTAINED W>11 NOT USED F ME Nei 1 1.y BENEFIT OF ANYONE EXCEPT SOLARO-TY INC., MNJNTNG s5RN: NCR SIHALL IT BE DISCLOSED IN MHaE OR IN Com Mount Type C 144 BRIDGE RD 5.72 KW PV ARRAY • in PMT TO OTHERS OUTSIDE INE RECPImES NOODLES: NORTHAMPTON, MA 01062 ORGANIZATION, EZCEPT IN CONNECTION YAM y THE 511E AND USE OF 1HE RESPECTIVE (22) REC R REC260PEZ 24 St Matin Drive,020Auld"2. IML II COI AROTY EQUIPMENT, MMOUT THE NRmEN murk - PACE NUL SHEET: REV DAIL MMWwg1,MA 01752 PERMISSION Of wH.wan INC. 4132442287 3 2442 2 8 7 PV 3 11 ti (650)635-1028 F: (Also)65e-1029 Delta # Solivia 5.2 TL SITE PLAN /19/2016 0610-sa-ary(ws-2619) ....wamlmorn PV MODULE Sl' 4 5/16' BOLT W4THINSTALLATION ORDER FENDER WASHERS L.: ----- LOCATE RAFTER, MARK HOLE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT -- ZEP ARRAY SKIRT (6) HOLE. -f`~ 4) (6) (2T SEAL PILOT HOLE WITH -_ Qj POLYURETHANE SEALANT. 1 �� __.-_ � j' 4Zv ((3) INSERT FL ZEP COMP MOUNT C �- 5 -7" • ZEP FLASHING C � ASHING. (E) COMP. SHINGLEIlle `" 14)1 PLACE MOUNT. LI SIDE VIEW OF MP2 NTS E) ROOF DECKING VII (2) G_ _ INSTALL LAC BOLT WITH 5/16" DIA STAINLESS .5 (5) (\) SEALING WASHER. STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES INSTALL LEVELING FOOT WITH MP2 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES WITH SEALING WASHER (6) BOLT & WASHERS. LANDSCAPE 64" 24" 39" Cl" STAGGERED (2-1/2" EMBED, MIN) --- PORTRAIT 32" 16° 65" 0" y (E) RAFTER STANDOFF RAFTER 2X1.0 @ ib" OC ROOF AZI 355 PITCH 11 STORIES: 2 � ARRAY AZI 355 PITCH 11 Scale: 1 1/2" = 1' 2x8 @19" OC Comp Shingle- Solid Sheathing / 3s, ►;h YA NQ G CIVIL r v a ! No.52791 • / x"�i, C+9TEP4'U / MM+...��`,�R7NRl� emu-NM " 1H€INPORMANDN HEREU m mAem: JB-0102528 00 PREMISE NNW DESORPTION: MOT: (('''' {. CA4MTOD s NOT ee USED FOR JASON HARDER RESIDENCE_ �sb ^'�i 4�ly ciNTANED ARNMINTSD FOR Nuc, MaxmC S'S' JASON HARDER RESIDENCE shuhoo Boi 1.7I 1 NOR SHALL R RE DISCLOSED IN NOTE OR IN CompMount Type_ C 144 BRIDGE RD —"" r"'' PART TO OTHERS OUTSIDE THE RECIPIENTS - 5.72 KW PV ARRAY �tA OROAMZATCN, EXCEPT II CORRECTOR MTH u�DUEEs - NORTHAMPTON, MA 01062 _ THE SALE AND USE OF NE RESPECIVt J22) REC # REC26OPEZ 24 St xmH mow, MA 01 2 uPN Ti SOURCITY EMINENT.WHOM THE IN EN mak "'- • PAGE NM: Mt RY DALE: Ma8-I A.MA%152 Pmius9ON a'SMARMY iNC. Delta Scdivia 5.2 TL 4132442287N 755-)5011-Tms v: (550)ete-50TH STRUCTURAL VIEWS PV 4 11/19/2016 (5Nq- -a {>�:,,y » MSM,. GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE • BOND (N) #8 GEC TO MO (N) GROUND Panel Number:LC120DC Inv 1: DC Ungrounded INV 1 -(1)DeIto B Solivia 5.2 TL LABEL: A (22 REC yy REC260PEZ CEN #168572 RODS AT PANEL WTH IRREVERSIBLE CRIMP Meter Number:82708544 Te-In: Supply Side Connection Inverter, 5200W, 240V, 97.5% Inverter; 5200W, 240V/208V, 97.5%, PLC, Zigbee, R PV Module; 260W, 236.6W PTC, MC4, 40mm, Black Frame, ZEP Enabled ELEC 1136 MR Overhead Service Entrance INV 2 Voc: 37.8 Vpmox: 30.7 INV 3 Ise AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER E 125A MAIN SERVICE PANEL E 100A/2P MAIN CIRCUIT BREAKER Oelto CUTLER-HAMMER Inverter 1 IND Disconnect CUTLER-HAMMER Q q� � - � Q 100A/2P 0 Disconnect 0 Delta / L,� MP 2: 1X11 Bolivia 5.2 7L I B 30A O rMayABm: i 1 , 1 i r- (E) LOADS ® - ■ ® - I_ ow _ @mI Pa I II I II 1 V __ EEC --T© ®II -1-r_.--.--- 2C MP 2: 1x11 CD-II MP° �___a I GND I __ wc_ I _ I �c V N I (I)Conduit Kit; 3/4 EMT 1 EGwEa ji 1 ac TO 120/240V SINGLE PHASE URLITY SERVICE I I 11 PHOTO VOLTAIC SYSTEM EQUIPPED PATH RAPID SHUTDOVM Voc = MAX VOC AT MIN TEMP POI—(2)% dNatl B —(DOURER—HAMx0V i 0G222NFu /I/'* A —(2)OSm /Selina r �I—(I)PWG/6, Solid Bora Copper D(� 5//ee 84' Disconnect; BOA, 24CVac, Fusible,NEMA 3R AC Ste, 9 R55 Ropitl Shutdown, 600V, 20A,NEMA 4%, MC4 r�lU l� —(2)0.ScOIPC 5/0-16 (I) Inmlation Piacng Connector Mon 4/0-4. Tap 6-14 C —(1)CURER-HAMMER i 00221UR6 • Disconnect; 30A, 240Vac, Nan-Fusible,NEMA 3R I,(N) ARRAY GROUND PER 690.47(D). NOTE: PER EXCEPTION NO. 2, ADDITIONAL SSC—SUPPLY SIDE CONNECRON. DISCONNEcnNC MEANS SHALL BE SUITABLE -(I)CURER-IlAMlm�(0m3tN8 'ELECTRODE MAY NOT BE REQUIRED DEPENDING ON LOCATION or (E) ELECTRODE AS SERVICE EQUIPMENT AND SHALL BE RATED PER NEC. Ground ire, d; 30k General Duty(DC) ©FT(1)AMC/9, THMN-2, sack (1)AMG i10, 1HYM-2, Black (2}Aw:i10 PV wre, 600V,Block Voc* =480.91VDC tsc =9.01 AX ET(R)AWG/10 PV won, 609V, Black VCR' =480.91 VT Ix =9.01 AUC knF(1)ANG 16. THMw-2, Red O L$1--(1)AWG/I0. 1HYM-2, Red O (I)AWG K. Sad Bore Copper OTC Vmp -337.7 VDC Imp-8.5 ADC 1 w(1)AWG#6,Solid fore Copper ECC Vmp =337.7 VT Imp=8.5 ADC (1)ANG/6, 1HM4-2, Mite tEU1RAL VmP -240 VAC Imp=21.5 MC (1)AWG i10. txwT-2 Mite NEUTRAL Vmp 240 VAC IMP,21.6 MC [��r(1 Condul Kt: 3/fEMi FI (1)Condut Kit; 3/4' EMT O` ' (1)Gmeli 6 Kit;IM Ba EMT (I)AWC/10, liwap 6Co Copper Black Vmp =337.71 VT Im =8.51 ADC (1)AWG/5, Sod Bae Caper GEC (1)Condvit Ki 3/4'EMT e(1)AWG/8, MNH-2,Owen ECL/CEC,—(I)CmMlt KiN.3/4"EMT (2 AWG/10 PV wre, 600V,Block Voc* =480.91 VDC Isc =9.01 ADC O ET(I)AWG/5,Solid Boreeck VmP =480,9 VDC lsc =8.5 ADC 3 4' 4 (I)Con It Bae Copper E Vmp 337.7 VOC Imp 8.5 AX FFFbIF. (1)CmduR Kit; 3/4' EMT PREYSE Ow1ER O[A]M80M DESIGN: CCNDDER ATR NOT BEUSEDFHERON IHE seNIMI1fR JB-0102528 00 JASON HARDER JASON HARDER RESIDENCE SnuhaoBal \`N SoiarCity. BENEFT SHALL ECT SI AR THE qtr NOBER SH W NYE1DNCLOSED VM WOOR INC., Mwx1NG SYSTEM: 144 BRIDGE RD -blr ♦ IO SHALL IT RE DISCLOSED IN WOOER OR IN comp Mount Type c 5.72 KW PV ARRAY 4 Penn TO OTHERS MUM THE ECRONREOPIENCS MORALS: NORTHAMPTON, MA 01062 ORGSALAnN D EXCUSE OF M E RESPE KN wTH24 St Main Din,WEPo x Unit 11 NE SALE AND USE T,THE UT HIE WG (22) REC (� REC26OPEZ 9 S AROTY EakPualr, w1HaT HIE 11R1101 Nglltk DACE NNE: SHEET: REV DATE T: (650)M38-1026,MA A(B50)638-1029 PERMISSION asCLARan INC. Delta y Solivia 5.21L 4132442287 32 4 42 287 THREE LINE DIAGRAM PV 5 11/19/2016 (866)-934-a1Y(765-2489) ....mar itg n WARNING.PHOTOVOLTAIC POWER SOURCE Label Location: Label Location: Label Location: (C)(CB) WARNING (AC)(POD WARNING (DC)(INV) Per Code: Per Code: Per Code: E 17. NEC 690.35F ELECTRIC SHOCK HAZARD ELECTRIC SHOCK HAZARD NEC 690.31.G.3 DO NOT TOUCH TERMINALS NEC 690. THE DC CONDUCTORS OF THIS 690.35(F) Label Location: TERMINALS ON BOTH LINE AND PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN PHOTOVOLTAIC DC DC) (INV) LOAD NTHE OPEN POSITIONIZED MNGROUNDED AND AY BE ENERGIZED INVERTER IS DISCONNECT Per Code: UNGROUNDED NEC 690.14.C.2 Label Location: Label Location: PHOTOVOLTAIC POINT OF (P01) INTERCONNECTION Per Code: POINT CURRENT(Imp) Per Code: MAXIMUM POWER-_I (DC))(INV) WARNING'. ELECTRIC SHOCK HAZARDDO NOT TOUCH NEC 690.17.4; NEC 690.54 . MAXIMUM POWER- POINT VOLTAGE(Vmp)_V NEC 690.53 TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDE MAXIMUM SYSTEM v MAY BE ENERGIZED IN THE OPEN VOLTAGE(Voo) POSITION. FOR SERVICE SHORT-CIRCUIT _ DE-ENERGIZE BOTH SOURCE CURRENT(Isc) A AND MAIN BREAKER. PV POWER SOURCE MAXIMUM AC _A OPERATING CURRENT MAXIMUM AC V Label Location: OPERATING VOLTAGE WARNING (DC) (INV) Per Code: ELECTRIC SHOCK HAZARD 5(C IF A GROUND FAULT IS INDICATED NEC 690.5(C) NORMALLY GROUNDED Label Location: CONDUCTORS MAY BE CAUTION (P01) UNGROUNDED AND ENERGIZED DUAL POWER SOURCE Per Code: SECOND SOURCE IS NEC 690.64.6.4 PHOTOVOLTAIC SYSTEM Label Location: WARNING (DC) (CB) ELECTRICAL SHOCK HAZARD Per Code: Label Location: DO NOT TOUCH TERMINALS NEC 690.17(4) CAUTION (D) (P01) TERMINALS ON BOTH LINE AND PHOTOVOLTAIC SYSTEM Per Code: LOAD SIDES MAY BE ENERGIZED NEC 690.64.6.4 IN THE OPEN POSITION CIRCUIT IS BACKFED DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT Label Location: WARNING (P01) Per Code: INVERTER OUTPUT NEC 690.64.B.7 Label Location: CONNECTION PHOTOVOLTAIC AC (AC)(P01) DO NOT RELOCATE (AC):AC Disconnect DISCONNECT Per Code: THIS ODEVICERRENr (C): Conduit NEC 690.14.C.2 (CB): Combiner Box (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit Label Location: (INV): Inverter With Integrated DC Disconnect MAXIMUM ACA (AC)(P01) (LC): Load Center OPERA rmG CURRENT Per Code: (M): Utility Meter MAXIMUM AC _ v NEC 690.54 (P01): Point of Interconnection OPERATING VOLTAGE CCNCOENTOL- NE MFOVMAMH HEREIN coNTNNED SHALL NOT BE USED FlM ille 3055 acarva+.Way THE 00011 OF ANYENE EXCEPT w MOW INC.,NCA SHALL IT K DISCLOSED SraMateo.CA 99903 �?p./`1� /� T':(650)63&1026 R(650)638-1029 IN MOLE OR IN PART TO OT ERS OUNCE ME RECIPIENTS ORGANIZATION, Label Set �M� SolarCity (eae NNW)TY 7653989)wwwsola02Mcum EXCEPT N CCNNECRON'MTI ME SALE AND USE of ME RENECTK M SpARaTY EWIPNENT, NT OUT THE WRITTEN PERMIS90N Of SttMOTY MC „,SOIarCitY Zep Solar Next-Level PV Mounting Technology - SdarCity ZepSolar Next-Levet PV Mounting Technology 1111 Zep System Components tar compwl0on shingle roofs , Uproot t _ Leveling Foot x awmrro a 111 PartNo.850-1172 yr,”, ' Leveling Fool „'i, EiLrislatl t0 U146/ Ira Ili 191 zen co ount.w wen. r o aorta era _its" Comp Mount t l1PartNo.8501382 l Listed la UL 2582 Mounting Black Listed to UL 22703 wryeo 44 Description a .f . • • PV mounting solution for compwitron shingle mos feral orgy • AutoWorks bonding all UL-listed Compatible Modules tallilli �"� AutoaLai UL 1703 Classare creates structural aed electrical bond • Zep Systemnhas r UL 1 ed0 Type Fire Rating when installed using modules from any manufacturer certified as"Type V or"Type 2 UL ustro Interlock Ground Zep V2 DC Wire Clip Specifications Pad No.8501388 Part No.850-1511 Part No.850-1448 Listed to UL 2703 Listed Ia UL 467 and UL 2703 Listed to UL 1565 Designed for pitched roofs Installs in portrait and landscape orientations Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703 WZeptunnelm reportn ingo ASCE7-05asAiUstandards _ Zep System grounding products are UL listeddtotoUL 03 and UL 467 illikZep System bondingan products 72 can UL nttetl r up 2703 ZepEngineered ire for men up to ucand cd to UL s to r Zep wire management listeproductsd t listed to UL 1565 for wire positioning devices Attachment method UL listed to UL 2582 for Wind Driven Rain Array Skirt,Grip,End Caps Pad Nos.8500113.850-1421. zepsolar.com zepsolar.corn 85Listed 6566561 5 '0 16 08 0.14 Stirs document does not create am express warranty by Zap SOlar or aboutits products or services Zep Solar&sole warrent'rs mnaneb in fire written preduct wet It'for This araurnent any express warrantybhz Solar p Solfee warranty product werranly i each product The land User doeumeniatron shipped with Zep Solar s products Aspartutes lire sole r pershcatrons each prOdur-1 The sod,se r y�uis solely drapes1 .dol responsible forverifying the cra01y of2p6 p ucts for _Specifications subjectb change withoul nota Patents App p res rums tie forerag1be nobY ofLp productsb eachuseSpecoee subpar change re Patents andpprpamm Document 4 800-10PO4/01 Rev A Me bat agnnat November 11,20152'.23 PM Document 4 S0u-1890.001 Rea A Date last exported November 13.2015223 PM :‘::rr III, if' ,j_ . . - ' - ' --- R C • .>.... , ,'- t.- '',-af.,`"•- • - , ,......*.,.... A'.AAAAA A.AA. A 'Ay'AA':41:444 ' .' kAYASP" A4AAA:A.-4:Y.` ikyAky"i4 1,,3. ;-..- . Prt ' '''.. ". ;1 2 AZAA:4 AY. . /*;$1kAk. ,,,,''''1121",€, ,-''',,,d",,, ,' ,, r.t. - ., ii4'.›,e „,. -,;'"*. t ',,,' '!' 01" ' /7/412 ..:12.::. 'd.,,. ' .( 4 '',-.:t. kAA akk., kk.,"),AkkAAAA 14 kk " f M.. lkk'rke 51. 3k At' k .< 111 ,i ,,g,+ tit , . . r,.'g *J.,..x-rirc-,-1/4.11, • -p,.• i--:44, '-,:1-4-1 ....: -i, --, II ig itttrsl'-=";$'-', -..' .,-3, •-t i „tC,`•it,...,',f,!' Ott t 1 ',„•.,,-;,,4,14- -kky-^..: ,.-•, -, ' ... . --"- -e t -• t,,,,;.,,,r etkit:t : ':t,:^‘,••••.x. -, = :-1- 13 \ =-,1°31,,,, tti,,,,‘,.•:-,,‘,-,3:44 ' RECNOE 1 ,' CIMW-'!;`Y-k-n 3 Aira33 3,3 ' 33' leed 14".It 11'. 3"3"33,t, i i ri":"t".3 IK loi-i. -454 ' ' ' .-.."- ..;',',:..,$:. 7. , . . . , mamt r,:r 1.tOpt e gi , , , -,;"*, 4-6:‘.,,,.."-',,,-,02.-W;-, ",t;ALW +=" ,._ • 1.• weiwit**.-14',44.-.'l ' 7, , i, -..;' -'' :lb; .• . -:, --,,,..$1.. , \ rikt -' dr, ' k.,,„s4-;•,.-, '.-..----r: `.. k.k.,,, ....,-A ti a.:.- ....a ..• -, . 'i \ rI1c/lr ..P".e....ii , '.;.:e —..-=-0(' , \ 4, ii ' \ , , \ , ` '- ''''c..',' "-,:.,;%;„;-, `A',4, \ I 1\ ' ' . \ . ..r'k ‘L''I I'I' RE( wrEgicopcm \ \ \ \ \ \ \ \IlL \ \ \\\ \ \ \ , \, ,\ \ \ \\ \ \ ‘ \ 1, \ Technical Data for Delta Smart Rapid Shutdown System RATINGS Max swam VON. 60W DC MAW MPRcnM1. 20A DC ROW Had cpAaIo NMga. 150 SSOV DC R.MSFMMc.Sga!Ft 0-20A DC NA Max%NONOf6•110tbdokudI 1 SW.pMrmMemake <4W GENERAL DATA Lx WXDHOW. 7 8x 591x 2.09 WHOM 0519s. CmF9 Natural Ca veclkn DC FIPKAWMM cMi01M AmpMd Helm H4 or MCA PV Cmmclor fIMM& Groove Adapter Bracket E�1d�mya�lms4N Moist Hum num OPTFNM dNN'AYa6 -40-159°F(A0-T0C) SMeyedailpmlue -40-fes%(40-d5°C) MUMxb . 0-100% Mm.gaRFC Stu. 2000m above sea Wel STANDARD COMPLIANCE EnclosupokFccaOIM NPMA4X %INN UL 1741 It 1741 CRD PVRSS.CSA 022.2 No.10.141 Rapid Slubkwl NEC 2014 Nide 690.12 EMC FCC Pail 15A WARRANTY SISM&d NLanly 10 yeas RpOMPAlAe DELTA SMART RAPID SHUTDOWN "'F `h,' r%.' c^ BOX ON ROOF WITHIN 10OF PV DfiF COMPIF •-I .-7. HIV I ammo :till AC ...T Orecontluit BREAKER GRID GRID 00%- for altwmne t_..i I AC Dela PMucis Catnn'allcn.m4. 40,0,Paamnl oma. Fi aaoul.CA 94518 Sales Ema I ASP acsadoaao FF Our Frna ASI.sapponAdo s° :,; =61° ° .d,SDm : 440 585 I p RELTAMo;ry an, Fad°y Inns 8 z,a to 5 Pm PST(apart In.Heidaysl le Delta Solar loverfes Datasheet nor SolarClty wauri Kr � 'Qtp r• SmIa2ftY �,. „o, .. Soia so eon ao. on ?, v wr.rto..a. �`'``^----___�� _ ouWTWI n w3v a�aWw pillow galVMD we.up% axa'.o:' ma o� °�Trwmma., nxm nne 6•mxw.,"°°mx°°v z„ .mm'vJ0 mm,. amwm 6nmaov '+®6'0' '""'?Ott' j 111:11 x+ wx. 6.mm "mmx" al k. i i III , zy One , ___ _ _ TM a One mM wes%m 73-Solar inverters 6r, :5„'.,,6,,, „ enters **<,6,. 60,.,,,wN I' les?It!S )(JkW 3ffFW wwa,nm r„r.Ma, :'AllttCoPP.umroa emu ,«eamn6) 52 klry fi>'kW lfikW +ucenmGewm..I t i "^m^aw xa-moer�o•,•"",mea g nr fie ' S:AV NAMMNW>WEOip4x 4a f Yln 1( t v@0.1uy1[n I l i mrtn y 9u I t �� ttanniu'nuc 160 1 f i• i]Tlr .. _ PL t AK IL Ino+ _ u�NrFkWtieuncsn rr9 y lu, i0li fi,! 6 n' ^' fat +eCasala ww.pPo _ mae �emr fM kWl r nrsawe µayNNM1 m»a „.„sz ir n Sart.? Cr pSw. IS n? auwiRas Com rxaM141g6r, a q haN SIE°°fix l£6erc.r IS' lrt, I N t +uan,y ID'S" a ne�rn tea`a ' M K„ �r, A AELT4 144 BRIDGE RD BP-2017-0713 GIS#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 17A-050 CITY OF NORTHAMPTON Lot:-001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: SOLAR ELECTRIC SYSTEM BUILDING PERMIT Permit# BP-2017-0713 Project# JS-2017-001177 Est.Cost: S25000.00 Fee: S75.00 PERMISSION IS HEREBY GRANTED TO: Const.Class: Contractor: License: use Grouo: SOLARCITY CORE' 108706 Lot Size(sq. ft.): 11935.44 Owner: HARDER JASON C Zoning:RI(100)/URA(l00)/ Applicant: SOLARCITY CORP AT: 144 BRIDGE RD Applicant Address: Phone: Insurance: 604 SILVER ST (978)215-2369 O Workers Compensation AGAWAMMA01001 ISSUED ON:11/22/2016 0:00:00 TO PERFORM THE FOLLOWING WORK:INSTALL SOALR ELECRIC PANELS TO ROOF - 22 PANELS, 5.72KW POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy signature: FeeTvpe: Date Paid: Amount: Building 11/22/20160:00:00 S75.00 212 Main Street, Phone(413)587-1240,Fax:(413)587-1272 Louis Hasbrouck-.Building Commissioner File#BP-2017-0713 APPLICANT/CONTACT PERSON SOLARCITY CORP ADDRESS/PHONE 604 SILVER ST AGAWAM (978)215-23690 PROPERTY LOCATION 144 BRIDGE RD MAP 17A PARCEL 050 001 ZONE RI(100)/URA(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid 1� Building Permit Filled out Fee Paid Typeof Construction: INSTA LR ELECRIC PANELS TO ROOF-22 PANELS,5.72KW New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/Statement or License 108706 3 sets of Plans/Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFOR N PRESENTED: proved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received&Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management De . ition De . Sign.aril7ng i icia Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A.Contact Office of Planning&Development for more information. V c _ Department use only. t ity of Northampton Status of Permit B 'ding Department Curb Cut/Diveway Penult <� % s 2 Main Street Sewetf epOPAvailability Room 100 W* iWeltAvakbirity , Northampton, MA 01060 Tao Sets*?Stnjtural Plans oE��O"�' phone 413-587-1240 Fax 413-587-1272 Plot/Sfte Plans Other Specify APPLICATION TO CONSTRUCT,ALTER, REPAIR,RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING SECTION 1 -SITE INFORMATION 1.1 Procell Atltlress. This section to be completed by office 144 Bridge Rd, Map Lot Unit Zone Overlay District Elm St District CB District SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: Jason Harder 144 Bridge Rd,Northampton MA 01062 Name(Print) Current Marling Address: ((413)586-9384 Telephone Signature 2.2 Authorized Agent: SolarCity Corp/James DiPadua 604 Silver St Agawam MA 01001 Nab¢(Poop / Current Mailing Address: 1 o I� 978-215-2367 Signa ure Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only completed by permit applicant 1. Building 7,000 (a)Building Permit Fee 2. Electrical 18,000 (b)Estimad Total s ConstructiontefroCom(6t)of 3. Plumbing Building Permit Fee 4. Mechanical(HVAC) 5. Fire Protection p 6. Total=(1 +2+3+4+5) 25,000 Check Number '7"I(id(u 'C76 This Section For Official Use Only Building Permit Number Date Issued Signature: Building Commissioner/Inspector of Buildings Date Section 4. ZONING AR Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information Existing Proposed Required by Zoning This cnl umn to he filled in by Building Department Lot Size Frontage Setbacks Front Side L: 2 I : R: Rear Building Height Bldg. Square Footage 11/0 Open Space Footage (Lot area minus bldg&paved parking) of Parking Spaces Fill: (volume&Location) A. Has a Special Permit/Variance/Finding ever been issued for/on the site? NO DONT KNOW YES IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO DONT KNOW YES IF YES: enter Book Page and/or Document N B. Does the site contain a brook, body of water or wetlands? NO DONT KNOW YES IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained Obtained , Date Issued: C. Do any signs exist on the property? YES NO IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property? YES NO IF YES, describe size, type and location: E. Will the construction activity disturb(clearing,grading, excavation,or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES NO IF YES,then a Northampton Storm Water Management Permit from the DPW is required. SECTION 5-DESCRIPTION OF PROPOSED WORK(check all applicable) New House Addition Replacement Windows Alteration(s) Roofing Or Doors Accessory Bldg. Demolition New Signs [ I Decks [ ] Siding[ ] Other n Brief Description of Proposed Work: Install solar electric panels to roof of existing home to be interconnected with home's electrical system. Alteration of existing bedroom Yes No Adding new bedroom Yes No Attached Narrative Renovating unfinished basement Yes No Plans Attached Roll -Sheet 6a. If New house and or addition to existing housing,complete the following: a. Use of building: One Family Two Family Other b. Number of rooms in each family unit: Number of Bathrooms c. Is there a garage attached? d. Proposed Square footage of new construction. Dimensions e. Number of stories? f. Method of heating? Fireplaces or Woodstoves Number of each g. Energy Conservation Compliance. Masscheck Energy Compliance form attached? h. Type of construction Is construction within 100 ft. of wetlands? Yes No. Is construction within 100 yr. floodplain Yes No j. Depth of basement or cellar floor below finished grade k. Will building conform to the Building and Zoning regulations? Yes No. I. Septic Tank City Sewer Private well City water Supply SECTION 7a-OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT 1 Jason Harder ,as Owner of the subject property hereby authorize SOLARCITY to act on my behalf, in all matters relative to work authorized by this building permit application. 11/17/16 Signature of Owner Date SOLARCITY CORP/James DiPadua , as Owner/Authorized Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge and belief. Signed under the pains and penalties of perjury. SOLARCITY CORP/James DiPadua Pri 11/17/16 Slgnetur of Owner/Agent Date SECTION 8-CONSTRUCTION SERVICES 8.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Hower_SOLARCITY/JEREMY GRAVES 108706 License Number 604 SILVER ST AGAWAM MA 01001 02/23/2019 Ad s Expiration Date astar--• 774-279-7650 Sign Telephone 9.Registered Home Improvement Contractor: Not Applicable ❑ SOLARCITY CORP/James DiPadua 168572 Company Name Registration Number 604 SILVER ST AGAWAM MA 01001 03/08/2017 Ar7 Expiration Date Telephone 978-215-2367 SECTION 10-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c. 152,§25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes. ❑ No ❑ 11. - Home Owner Exemption The current exemption for"homeowners"was extended to include Owner-occupied Dwellings of one(I) or two(2)families and to allow such homeowner to engage an individual for hire who does not possess a license,provided that the owner acts as supervisor.CMR 780, Sixth Edition Section 108.3.5.1. Definition of Homeowner: Person(s)who own a parcel of land on which he/she resides or intends to reside,on which there is,or is intended to be,a one or two family dwelling,attached or detached structures accessory to such use and/or farm structures.A person who constructs more than one home in a two-year period shall not be considered a homeowner. Such"homeowner"shall submit to the Building Official,on a form acceptable to the Building Official that he/she shall be responsible for all such work performed under the building permit. As acting Construction Supervisor your presence on the job site will be required from time to time,during and upon completion of the work for which this permit is issued. Also be advised that with reference to Chapter 152(Workers' Compensation) and Chapter 153(Liability of Employers to Employees for injuries not resulting in Death)of the Massachusetts General Laws Annotated,you may be liable for person(s) you hire to perform work for you under this permit. The undersigned"homeowner"certifies and assumes responsibility for compliance with the State Building Code,City of Northampton Ordinances,State and Local Zoning Laws and State of Massachusetts General Laws Annotated. Homeowner Signature _ iLk The Commonwealth of Ma.saehusens Department of industrial Accidents Office oflnvestigations 600 Washington Street • Boston,MA 0211 • 1 ✓'' Ivlvw.roangov/dla Workers' Compensation insurance Affidavit Builders/Contractors/Electricians/Plumbers AuoticantInformatiou Please_Prinf Legibly Name 93usima¢rOrga.h®thnm,divtdua): SOLARCITY CORP. Address: 3055 CLEARVIEW WAY city/slate/zip: SAN MATEO, CA 94402 phone#: 888-765-2489 Are you au employer?Cheep the appropriate bur: • Type of project (required): 1.0 am a employer wnh 5000 4. ❑ I am a general contractor and I 6. ❑New construction employees(MI and/or part-time).* have hired the subcontractors 2.❑ I am a sole proprietor or partner- listed on the attached sheet.I 3• ❑ Remodeling ship and have no employees These sub-contractors have 8. 0 Demolition working for me In any capacity. was'QIP.irtsulan= 9. ❑ Building addition No workers'comp.insurance 5. 0 We am a corporation and its required.) ofiicers have exercised their 10.0 Electrical replies or additions 3.❑ 1 am a homeowner doing all work right of exemption per MOL 11.0 Plumbing repairs or additions myself.[No workers'camp. c. 152,§I(4).and we have no 12.0 Roof repairs insurance required.) employees. [No workers' 13.0 Oda comp. required) — 'Aorm quem reg eines box III nun ate ml not are xenon below showing their workers'compensation policy infonnerin¢ I lomw'smera woo submit this aflltlwa inneraiog they ore doing Si wort ad then hire amsido contrm:lorsmrel submit a new amAova indioaina sock ICmarsima Mg check this box muss eurh l au additional sheaf showing the none of rho arbmamcwn old thea wmtvs'comp policy information. I am an employer that is pros dilmg workers'compensation insurance for my employer,. Beim Is the policy and job site information r nydiar_:�7U11(�1 f �I�PAI�1 t' .-nte _C . — Inrrnace p,h rNnv //II Polity or Sclf-itis.l.ic.A: W t.- 0 f g2 t21a - 01 Expiration Date: Oak 0i- P7 --- pp�� r.'NpTJs m w 11 Job Site Address: 1L\�� �\D6F tiv _City/State/Zip: IJ \obs _____ Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date). failure to secure coverage as required under Section 25A of MGI.c. 152 can lead to the imposition of crimiwdl penalties of a inc up to$1,500.00 and/or bne-year imprisonment,as well as civil penalties in the form of a STOP WORK ORDER and a fine t up to$250.008 day against the violator. Be advised that a ropy of this slmeinem may befonvarded to the Office of instigations of the DIA for Insurance coverage verification. do hereby county ander the pops and penabler afperjary dna the information provided above is true and rouget gum i'is'r .. '�' .._: _� './iE�-. Mie: \ -at - \b s as one 0:` Official as only. Do nor mile la this area, to be completed by city or town official • • t. ._.Tows ... . . ...Permit City or Town: ...... .... .._. .. ._.. . PermrdMcenac ft "suing Authority(circle one): . Board of Health 2. Buiidin?Department 3. City/Town Clerk 4.Rlectrteal Inspector S.Plumbing inspector Other unmet Person: Plume th - ,,, no—ant I—• CERTIFICATE OF O.JABIUTY INSURANCE PATE B THIS CERIIRCAIE 5 MOW AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER.THIS CERDRCATE DOES NOT AFFIRMATIVELY OR NEGATTVE.Y AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICES BELOW. THIS CERTIFICATE OF INSURANCE DOM NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUBIORILED REPRESENTATIVE OR PRODUCER AND DC CERTIFICATE HOLDER. IMPORTANT. I IE cerfihnale holder is an ADDDIONAL INSURED,The policy(res)must be endorsed N SUBROGITION IS WAIVED,subject b NEE terms end amN®oas of the policy,certain poroles nnw require an endorsement A statement on Ibis mamba does not seder rlghs to the caaab holder in Nee of each endure m t(s). MOW CiAnscr MAfSHMK MSLENCE SERVICES LF.teaet I PSCm- - ,MEET,(NC o DI ter H UCESE 941100.47169 SALORANCISCO,CA 94101 Am:Slabs 600 415'4S.834 Nara)AFF0ErapGcoVBRARE NMDA SIE9OMPIDCLLIREME .ISA:Welt leaim Wawa?C l m7 1855 INURED WA &WIN Cmp,rdlm ASYienl e:NW WS Oa.+gy.War. annnRlylcA WA WA San Nato,CA 9140E Damn;Ameba Dab Dana Company 1014E n9MER E. Iammr F. COVERAGES CERTIFICATE NUMBER: SEA-012013218113 REVISION NUMBER:6 TNS IS TO CERTIFY THAT THE POLICES OF INSURANCE LIMED BELOW HAVE BEEN ISSUED TO THE INSUIRE)MMAEO MOVE FOR 771E POLICY PRIV INDICATED, NOITVWiSTPHDNNG ANY REQUIREMENT,TESL OR COIIDFIION OF AMC CONTRACT OR OTHER DOC/WENT WITH RESPECT TO WITCH THIS CEn1 n-IGTE MAY SE ISSUED OR MAY PERTAIN.THE INSURANCE AFFORDED BY THE POLICIES DESCRIBE)KERMA IS SUBJECT TO ALL THE TERMS, ImM1I r acWSIONSAND CONDITIONS OF SUCH POLICIES WITS SHOWN MAY HAVE BEEN REDUCED BY MDD�CLLARIS. Arecause Ria TYPE OFaaNANL£ VAL MET WORM 5X, Ir�AponTl'1T Urn A X cOIlmmaLGENERAL D4SDTY GLOOI8M16RI MIME WIO1I2P1Y im- .. s 1,0E0001 LIAmSaACE C OCCUR - =L014.2 Pa rmw 1 1,13:13,30o X ERSEOA00 mowenroneoNmJ s 5000 ISA ADENARY $ 1m440 m+LAP3REGME�LWTAFIa Pec GENERAL/GC/0MME a =TM aPatiCJI LOC PRODUCTS-Cpm OP AGO I at= once 1 AaIODLAIDLLREOUTY 9APNE2117.01 mote 08014)1) Mr:MILE Lk r 1 IAR®O JAUTO B°c"1' I"(Pcpam'M ©.W PI z RS' pPMnO�py,Y�ryuer Rsae�gl 1 _.,_. ' ©AIUP1O %AWUS Try rlPsray ATAIIl� 1 11OitA/Jf106 ARRR e meRr, 1 EACH OCA9yENDE 1 MCBEE eau .ATS' PO2 AOGR6GAtE 1 _ — nEo I NEr-,a1. RmFeam-ofcc91. 0301/XE DISIDOIT A FnTu1E O+ s AND 9oPt OIEINTuaMMYA'91B2D1601 PAW m.G11A %O MR MR) ANY PROPRIETflECAITIVEN�N/A Ti F.AL1IMCJOt 1,000,0001 7,090,O CCNyu���EEseNa�Oe EENEIm1801(CM Ostro 16 0200117 EL DliENE-ESIPO1EE1 1.00INO >BgwlYY10F cPERAnos mw Limb NM ewes ofMKER-CA ELDENESE-ABBEY LENT 1,600& ipso.OF a9iATIMSL LOCATIONS IVBY6®LAIRD 9e1,AARaeml Mama SOI¢Lm,nayb attached Jr mom span Is,,Peon FICATE HOLDER CANOE L ATION Moran Comarnian sHoULO*HYDE TNE ABOVE CESCREED MUMS BS CANCELLED BEAM OM Camden Way TIB WdrATION DATE THEREOF, NOTICE WILL OE DELHERRED N an MS CA Ment A^"^IAANCE MN THE PCUCYPFCm9ONS. AIMNnn®R9u.n asrE i.i of mash Mac hwe®9rNs Stamina*Guaira' -e -d d.a4....• I ID 1986.2014 ACORD CORPORATION. All rights reserved 25(201451) The ACORD name and logo am regitored narks of ACORD rthieYY1l! /I(�//f✓1('r(/// (r/(h/%tirfJJ(tr/1(!J /( Office' of Consuiner Aflalrsiand Business Regulation 10 Park Plaza - Suite 5170 Boston, Massachusetts 02116 Home Improvement Contractor Registration Reffettabon: 108572 type Supplement Card Waken SOLAR CITY CORPORATION e40017 JEREMY GRAVES - 3055 CLEARVIEW WAY . . .. . - SAN MATEO,CA 94402 Plane Address and atom tank,Mart:memo far Snipe r o aares�i - '• Address '1 Renal , Eeployean Lest Cad ''' t..,,,,nr,..ru/ cemeorca.®e.A®is&Meets lacerate Loose or n6dn7den'115d for Maiidal aye any :I' before ekesryhaial toe. Wooed rears be �`- Wee ; mrorsoumrexrcoormonoR 15E572 VP= JOP&ofConer Mears and Rosmes Repaint IY Park Plan--r5ur7s 5178 tiDedfa5MC 3442017 Supph+poot Cafe Basler R4 02116 SOLAR CM'CORP uN.1'iCN JEREMY GMME5 24 BTJ RTINantto MD SUMO S x,19 raltl16CJtDIC41.dN 01108 mr.. p vaMsrikoW slRoecory .. I I `L7 fikesechtsdts.Department of Pualic Safety �- Board of Belding Reg Waimea and Standards Connreclkn Sapeniwr. { ''r`1 .. License:DS-100700 �i.,"5 I 2RYRIm'CRAM of Ci . • f79 .` ^A Marlborough Mt/01 ommeE _ " C " Expiration orrnddgana 02F43t2019 t." T/r' rri/i/iiPil( ref7/a o. (n/10I/).iNri/(iell.; gel; 3f; Office of Consumer Affairs/and Business Regulation 10 Park Plaza - Suite 5170 i971. Boston, Massachusetts 02116 • Home Improvement Contractor Registration Reg/station: 168572 • Type: Supplement Card SOLAR CITY CORPORATION Emi anent 3/8/2017 JAMES DIPADUA — 3055 CLEARVIEW WAY SAN MATEO, CA 94402 Update Address mid rears:card.Mart reason for change ,1 n 211.105,1I ] Address ❑ Reoewel ❑ Employment 9 Lost Card rOOheafermsmoerMaim&Basin @Auldles Lerma ert tram' idfor&aidd as only 7r" Were dm mindingmindingdam R fond Man ac,l CO101RAC70R Mee rfGonsamer*Mks nod datum Re:Mada eglearadorr team Tie 10 Park Naa-Sole 5170 _ 3.f Expire/88K. wa.2017 Siwemenl Gad Banat MA am SOLAR an CORPORA flUN KELLY SIWC LAND L///// 21 ST IMR11Nbpeazl OtD21M1 .+4.4--yeaze-b.. — / OeepItataDJIDLir✓ USM ma 0174 r ..evr ✓` V.rliteginmei Mormare • • • • DecoSgn Envelope ID:CEBEDCF7-7C12-482C-B7A5-C5A88846A4E9 SolarCity Purchase Customer Name ane Address Installation Location Date Jason Harder 144 Bridge Road 10/28/2016 144 Bridge Road Northampton,MA 01062 Northampton,MA 01062 Here are the terms of your Solar Home Improvement Agreement 5 . 72 kW DC 2Oyr System Size System Warranty The SolarCity Promise •We provide a money-back energy performance guarantee. DS •We warrant all of our roofing work. L •We warrant and repair the System. _ __ __ _._ __ initial here •We fix or pay for any damage we may cause to your property. •We provide 24/7 web-enabled monitoring at no additional cost. •The pricing in this Agreement is valid for 30 days after 10/24/2016. Your SolarCity Purchase Agreement Details Contract Price $24,482 Amount Due $20,363 Est.first year production 5,504 kWh 3055 Clearview Way,San Mateo,CA 94402 1888.765.2489 I solarcity.com 22/2221 Solar•ome improvement Agreement,version 368,October 5,2016 Contractors License MA HIC 168572/EL-1136MR Document generated on lok )0 47p6 0 Docur ed Sola L 2y201oration,All nets Reserved it DocuSign Envelope ID:CEBEOCE7-]C12-482C-B]A5-C5A88846A4E9 6. ADDITIONAL RIGHTS TO CANCEL. IN ADDITION TO ANY RIGHTS YOU MAY HAVE TO CANCEL THIS AGREEMENT UNDER SECTION 7 BELOW AND UNDER SECTION 1 OF THE GENERAL TERMS AND CONDITIONS,YOU MAY ALSO CANCEL THIS AGREEMENT AT NO COST AT ANY TIME PRIOR TO COMMENCEMENT OF CONSTRUCTION ON YOUR HOME. 7. NOTICE OF RIGHT TO CANCEL. YOU MAY CANCEL THIS AGREEMENT AT ANY TIME PRIOR TO MIDNIGHT OF THE THIRD BUSINESS DAY AFTER THE DATE YOU SIGN THIS AGREEMENT. SEE THE ATTACHED NOTICE OF CANCELLATION FORM ATTACHED AS EXHIBIT 1 FOR AN EXPLANATION OF THIS RIGHT. Customer's Name:Jason Harder oocusqned by: ,�oqq11 Signature: CaS� non 15CSEBC9BA79412. Date: inn x/2016 Customer's Name: Signature: Date: Solar Home Improvement Agreement SolarCity approved �•�.� Signature: Lyndon Rive, CEO Date: 10/24/2016 22l7r name Improvement Agreement,version 3.5 A,(kroner 5,20E6 El2272221 ' p 0 4.,v. S0 arCity. Version#64.1-TBD A'i. November 19,2016 T. r RE: CERTIFICATION LETTER I Project/Job#0102528 o NO.52791 Project Address: Harder Residence 194 Bridge Rd %MI/ Northampton, MA 01062 AHJ Northampton SC Office Springfield HenryDN - .h" enialfthi tOty Design Criteria; —,I u OL,PWcn CoDale 1016 11 pOt=aon6. -Applicable Codes = MA Res. Code,8th Edition,ASCE 7-05,and 2005 NDS n oea -Risk Category =II -Wind Speed = 90 mph, Exposure Category C, Partially/Fully Enclosed Method -Ground Snow Load = 40 psf -MP2: 2x10 @ 16"OC, Roof DL =9.5 psf,Roof LL/SL= 28 psf(Non-PV), Roof LL/SL=28 psf(PV) Note: Per IBC 1613.1; Seismic check is not required because Ss = 0.22424< 0.4g and Seismic Design Category(SDC) = B < D To Whom It May Concern, A jobsde survey of the existing framing system of the address indicated above was performed by a site survey team from SolarOty. Structural evaluation was based on site observations and the design criteria listed above. Based on this evaluation, I certify that the existing structure directly supporting the PV system is adequate to withstand all loading indicated in the design criteria above based on the requirements of the applicable existing building and/or new building provisions adopted/referenced above. Additionally, I certify that the PV module assembly including all standoffs supporting it have been reviewed to be in accordance with the manufacturer's specifications and to meet and/or exceed all requirements set forth by the referenced codes for loading. The PV assembly hardware specifications are contained in the plans/docs submitted for approval. O55 Clear a Mateo GQ14O o50-[JE-ICS :Rs ai SOL-0 1 +301o3R-10 y_a"n Version#64.1-TBD pe R`SolarCity. HARDWARE DESIGN AND STRUCTURAL ANALYSIS RESULTS SUMMARY TABLES Landscape Hardware-Landscape Modules'Standoff Specifications Hardware X-X Spacing I X-X Cantilever Y-Y Spacing V-V Cantilever Configuration Uplift DCR MP2 64" 24" 39" NA Staggered 34.9% Portrait Hardware-Portrait Modules'Standoff Specifications Hardware X-X Spacing X-X Cantilever Y-V Spacing V-Y Cantilever Configuration Uplift DCR MP2 32" 16" 66" NA Staggered 29.3% Structure Mounting Plane Framing Qualification Results Type Spacing Pitch Member Evaluation Results MP2 Stick Frame l6"O.C. IF Member Analysis OK Refer to the submitted drawings for details of information collected during a site survey. All member analysis and/or evaluation is based on framing information gathered on site.The existing gravity and lateral load orrying members were evaluated In accordance with the IBC and the IEBC. ]. Jlear.ia.. a�Matea i a4C a_F 1 P i.5Si` 'L ...r_, le la citr__m STRUCTURE ANALYSIS - LOADING SUMMARY AND MEMBER CHECK- MP2 Member Properties Summary MP2 Horizontal Member Spans Rafter Properties Overhang 0.32 ft Actual W 1.50" Roof System Properties Span 1 15.22 ft Actual D 9.25" Number of Spans(w/o Overhang) 1 Span2 Nominal Yes Roofing Material Comp Roof Span 3 A(MA 2) 13.88 Re-Roof No Span 4 Sx(in.A3) 21.39 Plywood Sheathing No Span 5 Ix(inA4) 98.93 Board Sheathing Solid-Sheathing Total Rake Span 15.83 ft TL Deft'n Limit 120 Vaulted Ceiling No PV 1 Start 1.67 ft Wood Species SPF Ceiling Finish 1/2"Gypsum Board PV 1 End 14.67 ft Wood Grade ; #2 Rafter Slope 11° PV 2 Start Fb(psi) 875 Rafter Spacing 16"O.C. PV 2 End Fv(psi) 135 Top tat Bracing Fug __PV 3 Start E(psi) 1,400,000 Bot tat Bracing At Supports PV 3 End E-min(psi) 510,000 Member Loading Summary Roof Pitch 3/12 Initial Pitch Adjust Non-PV Areas PV Areas Roof Dead Load DL 9.5 psf x 1.02 9.7 psf 9.7 psf PV Dead Load PV-DL 3.0 psf x 1.02 3.1 psf Roof Live Load RLL 20.0 psf x 1.00 20.0 psf Live/Snow Load LL/SLIa 40.0 psf x 0.7 I x 0.7 28.0 psf 28.0 psf Total Load(Governing LC) TL 37.7 psf 40.7 psf Notes: 1. ps=Csspf; Cs-roof,Cs-pv per ASCE 7[Rgure 7-2] 2. pf=0.7(CO(Cd(Is)Pa; 4=0.9,c=1.1,1,=1.0 Member Design Summary (per NDS) Governing Load Comb CD Cl.(+) CL(-) CF Cr D+S 1.15 1.00 0.34 1.1 1.15 Member Analyst Results Summary Cosentino Analysis Max Moment I 0 L0001011 Gpadty DCR Result (+)Bending Stress(psi) 880 7.9 ft 1,273 0.69 Pass CALCULATION OF DESIGN WIND LOADS- MP2 Mounting Plane Information i Roofing Material Comp Roof Roof Slope 110 Rafter Spacing I 16"O.C. Framing Type/Direction ' Y-Y Rafters PV System Type I SolarCity SleekMount'" Zep System Type ZS Comp Standoff(Attachment Hardware) Como Mount Tyne c Spanning Vents No Wind Design Criteria Wind Design Code IBC 2009 ASCE 7-05 Wind Design Method Partially/Fully Enclosed Method Basic Wind Speed V 90 mph Fig. 6-1 Exposure Category C Section 6.5.6.3 Roof Style Gable Roof Hg.6-118/c/D-146/6 Mean Roof Heioht h 25 ft Section 6.2 Wind Pressure Calculation Coefficients Wind Pressure Exposure K, 0.95 Table 6-3 Topographic Factor Kn 1.00 Section 6.5.7 Wind Directionality Factor Ica 0.85 Table 6-4 Importance Factor I 1.0 Table 6-1 Velocity Pressure qh • qh= 0.00256(1(z)(Kzt)(Kd)(VA 2)(I) Equation 6-15 • • 16.7 psf Wind Pressure Ext. Pressure Coefficient(Up) I GCp(Up) i -0.88 Fig.6-118/C/D-14A/B Ext.Pressure Coefficient(Down) GCp(Down) 0.45 Fig.6-118/C/D-14NB Design Wind Pressure p p=qh(GCp) Equation 6-22 Wind Pressure Up Pura -14.6 psf Wind Pressure Down Norma 10.0 psf ALLOWABLE STANDOFF SPACINGS X-Dhectlon Y-Direction Max Allowable Standoff Spacing Landscape 64" 39" Max Allowable Cantilever Landscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trib 17 sf PV Assembly Dead Load W-PV 3.0 psf Net Wind Uplift at Standoff T-actual -222 lbs Uplift Capacity of Standoff T-allow 637 lbs Standoff Demand/Capacity DCR 34.9% X-Direction I Y-Direction Max Allowable Standoff Spacing Portrait 32" 66" Max Allowable Cantilever Portrait 16" I NA Standoff Configuration Portrait i Staggered Max Standoff Tributary Area Trib 15 sf PV Assembly Dead Load W-PV 3.0 psf Net Wind Uplift at Standoff T-actual -187 lbs Uplift Capacity of Standoff T-albw 637 lbs Standoff Demand/Capacity DCR 29.3%