Loading...
18C-059 (3) H $c W CENTER FOR U EcoTechnology ^ �y we make green make sense- Rough-In Duct Leakage Testing Report Site Information Date of Test Friday, September 16, 2016 Client Home Energy Solutions Project Address 176 Prospect Ave, Northampton, MA 01060 Test completed by Miira Gates Duct Leakage Test Results Conditioned Area #1 672 sq ft Duct System 1 Air Handler Installed? Yes Duct Flow in CFM25 33 CFM25 per 100 sq ft 4.91 Pass or Fail IECC 2009? Pass Notes: Rough-In Duct Leakage Requirements IECC 2009 - Air Handler Installed <6 CFM per 100 sq ft of conditioned floor area IECC 2009 - NO Air Handler Installed <4 CFM per 100 sq ft of conditioned floor area IECC 2012 - Air Handler Installed <4 CFM per 100 sq ft of conditioned floor area IECC 2012 - NO Air Handler Installed <3 CFM per 100 sq ft of conditioned floor area