Rough-In Duct Leakage Testing Report
Site Information
Date of Test Friday, September 16, 2016
Client Home Energy Solutions
Project Address 176 Prospect Ave, Northampton, MA 01060
Test completed by Miira Gates
Duct Leakage Test Results
Conditioned Area #1 672 sq ft
Duct System 1
Air Handler Installed? Yes
Duct Flow in CFM25 33
CFM25 per 100 sq ft 4.91
Pass or Fail IECC 2009? Pass
Notes:
Rough-In Duct Leakage Requirements
IECC 2009 - Air Handler Installed <6 CFM per 100 sq ft of conditioned floor area
IECC 2009 - NO Air Handler Installed <4 CFM per 100 sq ft of conditioned floor area
IECC 2012 - Air Handler Installed <4 CFM per 100 sq ft of conditioned floor area
IECC 2012 - NO Air Handler Installed <3 CFM per 100 sq ft of conditioned floor area