38A-103 (14) Fire Sprinkler portion of Narrative Report For VCA 209 Earle Street Nothampton, Ma. 01086 BY Warehouse Mechanical Contractors, Inc. 342 Britton Street Chicopee, Ma 01020 Ma Sprinkler Contractor License SC 2254 Phone 413-536-9222 Fax 413-535-2486 January 24, 2008 E W r JAN 3 0 2,0108 yyk DEN Of EiJ1.501G INS,100"s FIRE PROTECTION SYSTEMS NARRATIVE REPORTS 903.1. 1 (La) BASIS (METHODOLOGY) OF DESIGN Section 1-Building Description a. Building "USE" Group: F-1 moderate hazard factory. b. Type (s) of occupancies (hazards within building): Factory and limited storage. c. Storage of commodities within the building: Class I through 3 commodities. cartooned and exposed. d. One story above grade high point of building roof 25-21/4. e. Zero stories below grade. f New 20,3 10 square feet. g. Storage limited to 12'-0" high. Project consists of a new building used for manufacturing of wood furniture. Wet sprinklers are provided throughout. The large outside canopy is provided with a non toxic freeze solution loop. The plant is designed for ordinary hazard group two .20 over the most remote 1500 square feet, the office light hazard .10 over the most remote 900 square feet and the paint room containing two spray booths is designed for extra hazard .30 over the entire room. Sprinklers will be provided in the paint spray booths under separate contract. Section 2- Applicable laws, regulations and standards a. 780 CMR code sections "Fire Protection System Requirements" 904.0 fire suppression systems, 906.5 requires audio visual alarm devices, 923.1 requires UL Central station for sprinkler system monitoring. b. NFPA Standards and Edition used for design of each specific fire protection system NFPA 13, 2002 NFPA 72, 2002 NFPA 24, 2002. Section 3 —Design Responsibility for Fire Protection Systems Warehouse Mechanical the installing contractor completely designs and specifies (develops a full system layout, design criteria and calculations), installs the system and certifies system installation for code compliance at completion. Exempt from requirement for seal of Massachusetts Registered Professional Engineer in accordance with MGLC 112 section 81r. Section 4-fire Protection systems to be installed. a. Water supply six-inch fire main supplied from twelve inch main in Earle Street. b. Automatic sprinkler systems and components. c. Fire alarm systems and components-audio and visual appliances installed throughout in accordance with NFPA 72. d. Manual suppression systems-small hose stations aren't required in accordance with NFPA 13, standpipe isn't required. e. Seismic provided in accordance with NFPA 13, 9.3. f. New storz connection provided on the front of the building. All of the above items are required by regulations. (780 CMR) all systems are new. 903.1.1 (1.13) Sequence of operation Section 1 Wet sprinkler system System operates automatically upon the fusing of a single fire sprinkler. Operational Sequence: 1. Wet system on fusing of one sprinkler head water flows. Water flow will close contacts of a flow switch. Closed Contacts on the flow switch will activate fire alarm panel. 903.1.l (1.C) Testing Criteria Section 1-Testing Criteria. Underground piping: Existing. System piping: 1. Hydrostatically test at a pressure of 200 psi. For two hours without a loss of pressure. 2. Conduct forward flow test of backflow preventer at 439.1 g.p.m. 3. 2" main drain test shall be conducted Record Static and residual pressures on test certificate. 4. Conduct system operational test from inspectors test connection. Local alarm must sound within 1 minute. 5. Central station must receive alarm and trouble signals. Warehouse Mechanical is in charge of setting up and coordinating testing. Warehouse Mechanical will provide test certificates. Section 2-Equipment and Tools a. Manufacturer's instructions b. Approved Narrative Report, sequence of operation section. c. Flow measuring devices-pitot tube for backflow preventer flushing. d. Gauges-main riser for 2" drain and hydrostatic testing. e. Fire hose is required to direct backflow preventer flushing discharge. Section 3-approval Requirements a. Certification from the legally recognized professional responsible for the design Stating that the fire protection sprinkler system has been installed in accordance with the approved fire protection construction documents and that he has reviewed the shop drawings for conformance to 780 CMR 903.3 and has identified deviations if any, from the approved fire protection construction documents. b. Confirmation by the building owner/developer or authorized representative that they-have received the as-built sprinkler system shop drawings from the installing contractor and that the legally recognized professional has certified their Accuracy. c. Material, Test, performance and Completion Certificates, properly executed by the installing contractor and that the legally recognized professional has certified their Accuracy. d. Satisfactory functional test of all fire protection systems witnessed by the Building official and the head of the fire department or their deignees. Industrial Residential Security Co. 396 Main Street Easthampton, MA 01027 413-527-3353 Fire Alarm Narrative: 01-05-2008 Location: VCA, Inc. Earle Street Northampton MA 01060 Building: Usage Group B, one story Commercial building. Installing Company: Industrial Residential Security Co. 396 main street Easthampton MA 01027 Fire Alarm System: The Fire Alarm System is a Silent Knight 5208 20 zone analog control. With 4 class B notifier zones, 2 class A zones and 18 class B zones. The Silent Knight Annuciator is LCD with all functions enabled (Key in Knox box to enable - operation). The procedure to reset and or silence the alarm, is to push the silence and or reset button then push in the code (1111). Fire Alarm Monitoring: The Fire Alarm System will be monitored at C.O.P.S. Monitoring in N.J. Irsco shall program all alarms, troubles and supervisory. It shall dial thru the built in digital dialer to the central station. Proper notifications to the Fire Dept. and responsible parties shall be made upon receiving the signals. Fire Alarm Equipment: 1 — Silent Knight 5208 control ( electrical room) 1 —Silent Knight 5235 LCD Annuciator ( Main entrance) 10 —Silent Knight Smoke detectors with bases 5 — Silent Knight Pull Stations 4 — Heat detectors 9— System Sensor horn Strobes 3 — System Sensor Strobe only 1 — Water flow zone 2 — Tamper zones 1 — Knox box 1 — Outdoor red strobe JCA' Drawing Date:01/22/07 1/22/08 8: 46 HYDRAULIC DESIGN INFORMATION SHEET Job Name: VCA Location: 209 Earle Street Northampton, MA Drawing Date: 01/22/07 Remote Area Number: 1 Contractor: WAREHOUSE MECHANICAL CONTRACTORS INC. Telephone: 413-536-9222 342 BRITTON STREET CHICOPEE, MA 01020 Designer: DAVID P. KRAUSE Calculated By: SprinkCAD www.sprinkcad. com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: METAL PURLINS Occupancy: Furniture Finishing Reviewing Authorities:CITY SYSTEM DESIGN Code:NFPA 13 Hazard:EC GR I System Type:WET Area of Sprinkler Oper. sq ftj Sprinkler or Nozzle Density (gpm/sq ft) 0. 300 1 Make: VIKING Area per Sprinkler 84 . 0 sq ftj Model: VK200 Hose Allowance Inside 0 gpm K-Factor: 8 . 00 Hose Allowance Outside 500 gpm Temperature Rating: 286 CALCULATION SUMMARY 14 Flowing Outlets gpm Required: 876.1 psi Required: 37.7 @ Source WATER SUPPLY Water Flow Test Pump Data Date of Test 6/20/02 Rated Capacity 0 gpm Static Pressure 115 . 0 psi Rated Pressure 0 . 0 psi Residual Pres 80. 0 psi Elevation 0 At a Flow of 620 gpm Make: Elevation 0" Model: Location: Earl street at Smith College sta Source of Information: WMC SYSTEM VOLUME 360 Gallons Notes: ' VCA' Drawing Date:01122107 1/22/08 8: 46 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 1 376 29.0 psi 1 4" Grvd Back Flow Valve WILKENS 1137 CHART LOSS 376 7 . 4 1 6" x 4" Fingd 90 Ell 14 ' 120 6. 065 376 0 . 1 1 Pipe 6" DIx18 Cl 350 350 ' 140 6.338 376 1 . 2 Fixed Flow Flow Loss 500 gpm Hydr Ref R1 Required at Source 876 37.7 psi Water Source115 . 0 psi static, 80 . 0 psi residual @ 620 gpm 876 gpm 48. 6 psi SAFETY PRESSURE 10. 9 psi Available Pressure of 48. 6 psi Exceeds Required Pressure of 37. 7 psi This is a safety margin of 10. 9 psi or 22 % of Supply Maximum Water Velocity is 16. 8 fps VCA` Drawing Date:01122107 1/22/08 8: 46 Page 3 FITTING NAME TABLE ABBREV. NAME Y�Gi%..$j$./xfi'C*4Y{Y{v+i�1i:�{t�'.ri{ii:{.r i:U:f ii$:=ilYl:�':+$$1`.i!ri:i.Ni)G:x"::iiSk'ti'• $k•'.1.f:?t:'f.4/J.'.'i.$.:ii.'•%Y:$$3'/.•i��,i.'•'i.{'•.'•::'�{.:•Yi,'{>,':'i:!}. C Coupling E 90 ' Standard Elbow F 45 ' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee V Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings . See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0 . 433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4 . 52 x (Q/C) ^1 . 85 / ID^4 . 87 Pv Velocity pressure (psi) where Pv = 0 . 001123 x Q^2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0 . 01 psi. Pressures are listed to 0.1 psi. Addition may vary by 0 . 1 psi due to accumulation of round off. - Calculations conform to NFPA 13 . - Velocity Pressures are not considered in these Calculations VCA Drawing Date:011'22107 1/22/08 8: 46 Page 4 G'1H.95fCG:;Y,3GtdG3Gt/JJJ��!/.`.J!/.{l:�vY/XC,t!iJ/J.V.h•�A'G'.{i.+/.<tL.'LY.G'fiGdC4Y!!!!,'YI.�:�GYH/////.VJ1.ii;•YJJNJ,C�//J.Hf'}�YN/f; 9.,"w:CfH////.!d'/.•;/.,;/.•.'?,:cYl.'!.+//,'�J.!+/J///.',G�%H!.{�N.�H/+1.�,',d',J/1.4///1,fY/fflYJ/JJi NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^',�) ) (PSI) (GPM) (GPM) (GPM/SQ. FT) nsssctstt .. .��.�r,. :..<xs«;�;;t:<srsr.-r.•sm>...r....:::x:st�sssnsns:sf;�:3.s>s :.s..�.ss,..Ecr«�.sr.•t;s, .:r�:�rrs�,sasssv.•x4s�;�s�ssy<.:::.:rwis.:•rr.•.�.,�s,�sv�„s�s3sz°. 1 18 .33 8 . 00 9. 9 25 .2 25 .2 0 . 30 2 18 .33 8 . 00 10.3 25 .7 25 . 2 0.31 3 18 .33 8 . 00 10. 9 26. 4 25 . 2 0. 31 4 18 .33 8 . 00 12 .3 28 . 1 25 . 2 0.33 5 18 .33 8 . 00 14 . 8 30 . 7 25 . 2 0.37 6 18 . 33 8 . 00 9. 9 25 . 2 25 . 2 0. 30 7 18 . 33 8 . 00 10. 3 25 . 7 25 . 2 0. 31 8 18 .33 8 . 00 11 . 0 26. 5 25 . 2 0. 32 9 18 . 33 8 . 00 12 .3 28 . 1 25 . 2 0. 33 10 18 . 33 8 . 00 14 . 8 30. 8 25 . 2 0.37 11 18 .33 8 . 00 9. 4 24 . 6 23 . 1 0 .32 12 18 . 33 8 . 00 9. 9 25 . 1 23 . 1 0 . 33 13 18 .33 8 . 00 10. 6 26. 1 23. 1 0 .34 14 18. 33 8 . 00 12 .3 28 . 0 23 . 1 0. 36 69 18 .33 20. 4 70 18 .33 20. 4 71 18 .33 21 . 5 72 18 .33 18 . 9 A5 16. 00 28 . 8 B1 16. 00 23 . 4 B2 16. 00 23.5 B3 16. 00 23. 7 B4 16. 00 27 . 0 W 16. 00 29. 0 Max velocity of 16. 79 occurs in the pipe from 10 TO 9 VCA Drawing Date: 01/22/07 1/22/08 8:46 Tyco Fire Products Page 5 3A?'{�6cJ,ft26&d/,c"NJY/.�d�EC'GS'iitdo�YG.'tE:Yetii$F/:S',63,v,'1+r3'.i.+•.+•'/.+S'/1,�,4J.�%t{..'•:r:^'4t+r;:?}{i::/x:{'ii:;::.t'i:i:iiii'tii{';J•.Jf�':$Y,3;?+h'+is4{%`•:•:C•;Fa."✓!'•.l�:J.N•,':Y,.:%/..�rJT1.ri5�%:-0`�+FI,:G::•',•.>,•:•;l/r,'i: :iG'J.::2:>+::i'/.•'.'•'I%•}+:`iJ3JJiS%%J fiJ%%+:J7�53Y/Ji:{+i'i77'y"JYHh'3�1lJ • HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn .'•SiY.$7//r197Y,"nHA9.tiJiCd'9Sf/fiYlY/,"i3}•gy�<i+`%�Y1+tY:Y�Y91,3;:,iG.Hl.'l:i7J!/lifi'/.C'/.HY,:'i,.:%i'//J;Yi'.;++3JYiif�Sv.'•+/:{+;;}'i$:%-0G Y:r:S£2Yt'I.•,;rs:.':aYicsi:'<;:;::::,:;:sc't."x.:;ry;�!!f!/:Yc�ift+ftJf�li s3f3;'.�`.•,ii'/i.'•1.Ji1i;`I1.9f+:,X•3::�/fl�1,Y�/.N!lI;CG//!!flllJili PATH 1 FROM HYDRAULIC REFERENCE 11 TO W (PRIMARY PATH) 24 . 56 1 .380 8 . 67 9. 4 9. 4 K = 8 . 00 11 C=120 0. 00 0. 0 0 . 0 24 . 56 0 . 050 8 . 67 0. 4 9. 4 Vel = 5 .32 25 . 12 1 . 610 8 . 67 9. 9 9. 9 K = 8 . 00 12 C=120 0. 00 0 . 0 0 . 0 49. 68 0. 087 8 . 67 0 . 8 9. 9 Vel = 7 . 91 26. 06 1 . 610 8 . 67 10. 6 10 . 6 K = 8 . 00 13 C=120 0. 00 0. 0 0. 0 75 . 75 0. 190 8 . 67 1. 6 10. 6 Vel = 12 . 05 28 . 01 1. 610 2E 11. 66 12 . 3 12 . 3 K = 8 . 00 14 C=120 8 . 00 0 . 0 0 . 0 103 . 76 0 . 340 19. 66 6.7 12 . 3 Vel = 16. 51 2 . 067 1T 15 . 00 18 . 9 18 . 9 72 C=120 10. 00 0 . 0 0. 0 103. 76 0. 101 25 . 00 2 . 5 18 . 9 Vel = 10. 02 2 . 067 1T 2 .33 21 . 5 21 . 5 71 C=120 10. 00 1 . 0 0 . 0 103.76 0. 101 12 .33 1.2 21. 5 Vel = 10. 02 272 . 37 4 . 260 1T 75 . 83 23 .7 23 .7 B3 C=120 26.33 0 . 0 0 . 0 See PATH 2 376. 13 0 . 032 102 . 17 3 . 3 23 .7 Vel = 8 .55 4 . 260 56. 81 27 . 0 27 . 0 B4 C=120 0 . 00 0 . 0 0. 0 376. 13 0. 032 56. 81 1. 8 27 . 0 Vel = 8 . 55 4 . 260 5 . 00 28 . 8 28 . 8 A5 C=120 0. 00 0. 0 0. 0 376. 13 0. 032 5 . 00 0. 2 28 . 8 Vel = 8 . 55 W 376. 13 29. 0 K = 69. 86 � YS�ii. �::5''i.+YWYri'`JJI/.lX�irJ.+I1.3i+iJ�ill�S.rJ.§'�J��i'il�r l:iY�l;Si+:.:yvl+.4s.'iSil,Cdiilf:vvi�i3�+S+ii/:J�i+iSi Y:%JiJl,•i::YL'Jiiiii::•'}/1 ii Yn iii.»�lvri i:v::iiY��iri+i�ii�����i.ii�I�$'Y�ti{�i�:/�JiJ llls'i3i� PATH 2 FROM HYDRAULIC REFERENCE 1 TO B3 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date: 01/22/07 1/22/08 8:46 Tyco Fire Products Page 6 ' +�J +G3+•'CLQ+dR/,d7+JJAJ/J.Lf9JJJJHJIJJJ:Gdf',3J„tS�JJ,!jJ.S;;'JJ/,:di;5'„7J.!-0JJ.0�rNNNfJ�S+»y,W,yJ,{{{.�„+,{�JJ.{•:{,',g,�5£+/.ClJyJJ,6CJJJ:t01.'�JJ.3:i'JJ.:(.•Y.��•r.;591.yJJ,.'dK{G%JJhJyJJJHJ.GJJHJJHJJd`,37.+Y. 975L2f0J,L�c HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn :mit:z.•,r.:;rearca�:::,:x.�.:rf �:�J�.�.ca:��rJ,cr.�>rrJ.�cz�x�:�J��,,•.:�xY,Jin..-���.war.��rxx�.,:::spam.�sy:�Jvsstcxh�s��:stJ�.� JJ..•,,; ;;.x:ws • PATH 2 FROM HYDRAULIC REFERENCE 1 TO B3 CONTINUED 25 .20 1 . 380 7 . 00 9. 9 9. 9 K = 8 . 00 1 C=120 0. 00 0 . 0 0 . 0 25 .20 0 . 052 7 . 00 0. 4 9. 9 Vel = 5 . 46 25 . 66 1. 610 7 . 00 10.3 10 . 3 K = 8 . 00 2 C=120 0. 00 0 . 0 0 . 0 50 . 86 0. 091 7 . 00 0. 6 10.3 Vel = 8 . 09 26. 44 1. 610 7 . 00 10. 9 10. 9 K = 8 . 00 3 C=120 0. 00 0 . 0 0 . 0 77 . 31 0. 197 7 . 00 1 . 4 10 . 9 Vel = 12 .30 28 . 06 1. 610 7 . 00 12 .3 12 .3 K = 8 . 00 4 C=120 0. 00 0 . 0 0 . 0 105 . 37 0 . 349 7 . 00 2 . 4 12 . 3 Vel = 16. 77 30.73 2. 067 1T 23 . 83 14 . 8 14 . 8 K = 8 . 00 5 C=120 10. 00 0. 0 0. 0 136. 09 0. 166 33. 83 5 . 6 14 . 8 Vel = 13. 14 2 . 067 1T 2 .33 20. 4 20. 4 69 C=120 10. 00 1 . 0 0. 0 136. 09 0. 166 12 . 33 2 . 0 20 . 4 Vel = 13. 14 4 . 260 12 . 00 23. 4 23. 4 B1 C=120 0. 00 0. 0 0. 0 136. 09 0. 005 12 . 00 0 . 1 23 . 4 Vel = 3. 09 136. 28 4 . 260 12 . 00 23. 5 23 . 5 B2 C=120 0. 00 0 . 0 0 . 0 See PATH 3 272 . 37 0. 018 12 . 00 0.2 23 . 5 Vel = 6. 19 B3 272 . 37 23.7 K = 55 . 94 }}Jld�k"IJJJ/.i9�'Jd9,d3'JJ1JJ}}JJ�1}J}JsiYJ11}}Yr.6/JJ•,'&'97JJJ/.fiS+PJJJJJ%}i7uY'iJ}/,%}}}}J}i%%l�Y%'1},G•.'•;;+J/}�}i➢.'}J.ri./,ddd'fi}}}}/.•'}}i.:lJnY}�},',�}}1J/.•9}„','/.YY}JJ.L,i,'�J}..'J�33�JJJl3.';%J�JJJJ.�4JJJ}l.✓},'J.J},G�'J}Jl1J/Jit}�+/.'},✓J.trrY}}}llJ.'.%�Y1iMic PATH 3 FROM HYDRAULIC REFERENCE 6 TO B2 25 .23 1 .380 7 . 00 9. 9 9. 9 K = 8 . 00 6 C=120 0. 00 0. 0 0. 0 25 .23 0. 053 7 . 00 0. 4 9. 9 Vel = 5 . 47 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date:01/22/07 1/22/08 8:46 Tyco Fire Products Page 7 tswv� raxc�rrrrrrn�tfnrrrrr�srw• .�a?5?ynsrs�rrsfrrrres::<,r.•.r�vi• ...-,.tr.�<�>:�:rrYr3.�.:,�rrrrr.•mc�rnt»rr.•zr�•�.v.�;�r..:�trc-rssswvsst�c:.r�.ry:,r,•,ss�.;;�rrrr,�r,�tzK:sramx�s�ty HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn rt3rrN+r' ... r/.3�Yr.-0fG9rrrrrr,35'J.fGt/.N.},}frr.{{fld+r.4.�S:r�.`.+SSi�... ; 59t! .., 2�b. :Y.�+.ur.Y1.+Yr,,:yr,'r.'rJ.?rt,-fr1.3X,f�i:4'.if�1".S3.i^%rrY:r/.rr.{r/r/.{frJ.rrrlrJ.rrrrrrrr.LClUr.,93X35:rrrrrrrrr.Mn/.rrrJ.•Y//r PATH 3 FROM HYDRAULIC REFERENCE 6 TO B2 CONTINUED 25 . 70 1. 610 7 . 00 10.3 10. 3 K = 8 . 00 7 C=120 0 . 00 0. 0 0. 0 50 . 93 0. 091 7 . 00 0. 6 10 . 3 Vel = 8 . 11 26. 48 1. 610 7 . 00 11 . 0 11 . 0 K = 8 . 00 8 C=120 0. 00 0 . 0 0. 0 77 . 41 0. 198 7 . 00 1. 4 11 . 0 Vel = 12 .32 28 . 10 1 . 610 7 . 00 12 . 3 12 . 3 K = 8 . 00 9 C=120 0. 00 0. 0 0. 0 105 . 51 0.350 7 . 00 2 . 5 12 . 3 Vel = 16.79 30.77 2 . 067 1T 23. 83 14 . 8 14 . 8 K = 8 . 00 10 C=120 10. 00 0. 0 0 . 0 136.28 0. 167 33. 83 5 . 6 14 . 8 Vel = 13 . 16 2. 067 1T 2 .33 20 . 4 20 . 4 70 C=120 10 . 00 1. 0 0. 0 136.28 0. 167 12 .33 2 . 1 20 . 4 Vel = 13. 16 B2 136. 28 23. 5 K = 28 . 12 ry r -rJb-t&54, b",,.'^;�5;�.Sri;;'i.�iafG4.;";wi:G3:d;;^S.YS".,r' r�i3r",i;�Y3dn.GiJ.4SS�,'r33G3;33.Y•;v,SsE:G:iS;ffLv33�3.�i.5�:? S4:aiwsfds�:iLa`.E�IJ//,ii',3f'3;avY..33G3GddC''9irJJS:iu1,�Xil. l' UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Job Water Required Hose Allowance VCA Static Pressure: 115.0 psi Pressure: 37.7 psi Inside: 0 gpm 209 Earle Street Residual Pressure: 80.0 psi System Flow: 376 gpm Outside: 500 gpm + se: m Northampton, MA Flow: 620 gpm System Ho 876 gp _ Remote Area: 1 Date: 6/20/02 Safety Pres: 10.9 psi Loc: Earl street at Smith Coll Head Elev Pres: 39.0 psi 140 120 100 Supply F 80 S I 60 40 500 gpm hose 20 I 200 300 400 500 600 700 800 900 10C Flow (gpm) VCA Drawing Date: 01/22/07 1/22/08 8:50 HYDRAULIC DESIGN INFORMATION SHEET Job Name: VCA Location: 209 Earle Street Northampton, MA Drawing Date: 01/22/07 Remote Area Number: 2 Contractor: WAREHOUSE MECHANICAL CONTRACTORS INC. Telephone: 413-536-9222 342 BRITTON STREET CHICOPEE, MA 01020 Designer: DAVID P. KRAUSE Calculated By: SprinkCAD www.sprinkcad. com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: METAL PURLINS Occupancy: Furniture Making Reviewing Authorities :CITY SYSTEM DESIGN Code:NFPA 13 Hazard:OR GR II System Type:WET Area of Sprinkler Oper. 1500 sq ftj Sprinkler or Nozzle Density (gpm/sq ft) 0. 200 1 Make: VIKING Area per Sprinkler 120. 0 sq ftj Model: VK200 Hose Allowance Inside 0 gpm I K-Factor: 8 . 00 Hose Allowance Outside 250 gpm I Temperature Rating: 200 CALCULATION SUMMARY 15 Flowing Outlets gpm Required: 689.1 psi Required: 56. 6 @ Source WATER SUPPLY Water Flow Test Pump Data Date of Test 6/20/02 Rated Capacity 0 gpm Static Pressure 115 . 0 psi Rated Pressure 0 . 0 psi Residual Pres 80. 0 psi Elevation 0 At a Flow of 620 gpm Make: Elevation 0" Model: Location: Earl street at Smith College sta Source of Information: WMC SYSTEM VOLUME 360 Gallons Notes : VCA' Drawing Date: 01/22/07 1/22/08 8:50 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 2 439 46.8 psi 1 4" Grvd Back Flow Valve WILKENS 1137 CHART LOSS 439 8 . 0 1 6" x 4" Fingd 90 Ell 141 120 6. 065 439 0 . 1 1 Pipe 6" DIx18 Cl 350 350 ' 140 6. 338 439 1. 6 Fixed Flow Flow Loss 250 gpm Hydr Ref R1 Required at Source 689 56. 6 psi Water Source115 . 0 psi static, 80 . 0 psi residual @ 620 gpm 689 gpm 72.4 psi SAFETY PRESSURE 15. 9 psi Available Pressure of 72.4 psi Exceeds Required Pressure of 56. 6 psi This is a safety margin of 15. 9 psi or 22 % of Supply Maximum Water Velocity is 25 . 4 fps VCA Drawing Date:01122107 1/22/08 8:50 Page 3 FITTING NAME TABLE ABBREV. NAME GG'G'H,fYidsYd9Sff�::C4�Y+/.+3YYi3.'+Jrf.{C'.Y,:;t%/.�JJJ.•:HJ,C,WrG3GY!..'91FdX 4R c'+,7.x�!GIJJJJJN,YYH.4JJA,'9Xtt','/,�;YJJJJ,:L"„':39X+:7i7J.. 'i C Coupling E 90 ' Standard Elbow F 45 ' Elbow S Straight Flow Thru Tee T 90 ' Flow Thru Tee V Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings . See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0. 433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4 .52 x (Q/C) ^1. 85 / ID^4 . 87 Pv Velocity pressure (psi) where Pv = 0 . 001123 x Q^2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0. 01 psi. Pressures are listed to 0 . 1 psi. Addition may vary by 0. 1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations VCA, Drawing Date:01122107 1/22/08 8:50 Page 4 cc���r��.�res�sr.�r,�, ic:;oys!s:�t.�.x�.s��.cryanmf�.,om��.m�f��.:u�w:.s:�r.���.r�..��ss�z.:z��...ass.;�.-���z�.��:s��.•�.,c.....�::���,u�.� ��.ssc. .auccaccces> NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^',�) ) (PSI) (GPM) (GPM) (GPM/SQ. FT) •. r�.c �.,.�rx�r�.�c��x,�wzv«:.,�,,.,.ys:.s�.���ss::•�.. r:mxK..,.cs�Y.:.,•.�a«;<::�-,�s«xrs<::<m��s;�rxr•��:�cwssy,.;..;:<.�•rys::�:•�:-•t �,�;,�,:,�w...�.,Y�. ss:,. r�:c:�:r�mrr�, 23 18 .33 8 . 00 7 . 0 21.2 21 .2 0.21 24 18 . 33 8 . 00 8 .2 22 . 9 21 . 2 0. 22 25 18 .33 8 . 00 9. 6 24 .7 21 . 2 0.24 26 18.33 8 . 00 11 . 0 26. 5 21.2 0.26 27 18 . 33 8 . 00 13 . 6 29. 5 24 . 0 0 . 25 28 18 . 33 8 . 00 18 . 4 34 . 3 24 . 0 0.29 29 18 .33 8 . 00 7 . 0 21.2 21.2 0. 21 30 18 . 33 8 . 00 8 .2 23 . 0 21 . 2 0 .23 31 18 . 33 8 . 00 9. 6 24 . 8 21 . 2 0.24 32 18 .33 8 . 00 11. 0 26. 6 21 . 2 0 .26 33 18 .33 8 . 00 13 . 6 29. 5 24 . 0 0 .25 34 18 .33 8 . 00 18 . 4 34 .3 24 . 0 0 .29 35 18 .33 8 . 00 26. 8 41 . 4 24 . 0 0 .35 36 18 .33 8 . 00 24 .7 39. 8 24 . 0 0. 33 37 18 .33 8 . 00 24 . 2 39. 4 21. 2 0.39 69 18 . 33 35 . 6 70 18 . 33 35 .7 71 18 .33 37 . 1 A5 16. 00 46. 6 B1 16. 00 39. 4 B2 16. 00 39.5 B3 16. 00 39. 8 B4 16. 00 44 . 1 W 16. 00 46. 8 Max velocity of 25. 36 occurs in the pipe from 34 TO 70 VCA Drawing Date:01/22/07 1/22/08 8:50 Tyco Fire Products Page 5 �7Drl7ll,.fJJJJII,9f915'/II+G9Y,GCAY.G:9.9FIII,'}H,6GYIII,G.f:sf;�I.4.Y,•X{}II}.Y.;3iS;39YHrY,S7IIfA}fi:6'XrA.0.,3Yf,9}}.{{,YIIII.{:`II.•J."L':��II+GII,Y}II1l!ii1Ga'Y.•'rf:','IrY},,,CII},.'d'r',.'•;'3;3'/.+Y,G;;'H.H,9;'l}I,G19I},%}}Il,Y1/}}},y�gl3Y�DP, HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn xx::crr.,ri»:z. stsuaaro�a��rs�o3aay .rtax��:>.Eaz�:cz�ixx :oxrcxxx:•:•,zrrc�zk!ss�:x�.:zcx�xw..xozzz¢•{{.,.:�. {rexxxx:cx>rs:�::x�:s:;�x�:x::{t•.x•,.:.w,r:<.rr::K..!as...:•wrexex::sw}roc.:arxx{{{{{r{xvctc�.•xY,:x;�zsrx •�,esa PATH 1 FROM HYDRAULIC REFERENCE 23 TO W (PRIMARY PATH) 21. 17 1. 049 8 .50 7 . 0 7 . 0 K = 8 . 00 23 C=120 0. 00 0. 0 0. 0 21. 17 0. 145 8 .50 1 . 2 7 . 0 Vel = 7 . 93 22 . 95 1 . 380 9. 00 8 .2 8 . 2 K = 8 . 00 24 C=120 0. 00 0 . 0 0. 0 44 . 11 0 . 148 9. 00 1. 3 8 . 2 Vel = 9. 56 24 . 73 1. 610 9. 00 9. 6 9. 6 K = 8 . 00 25 C=120 0 . 00 0. 0 0. 0 68 . 85 0. 159 9. 00 1. 4 9. 6 Vel = 10. 96 26. 52 1. 610 9. 00 11. 0 11. 0 K = 8 . 00 26 C=120 0. 00 0 . 0 0 . 0 95 . 37 0.291 9. 00 2 . 6 11 . 0 Vel = 15 . 18 29. 51 1. 610 10. 00 13. 6 13. 6 K = 8 . 00 27 C=120 0. 00 0. 0 0 . 0 124 . 88 0. 479 10. 00 4 . 8 13. 6 Vel = 19. 87 34 . 31 1 . 610 1T 15 . 00 18 . 4 18 . 4 K = 8 . 00 28 C=120 8 . 00 0. 0 0 . 0 159. 19 0. 750 23 . 00 17 . 2 18 . 4 Vel = 25 . 33 2 . 067 1T 2 .33 35 . 6 35 . 6 69 C=120 10. 00 1. 0 0. 0 159. 19 0. 222 12 .33 2 . 7 35 . 6 Vel = 15 .37 4 .260 12 . 00 39. 4 39. 4 B1 C=120 0. 00 0. 0 0. 0 159. 19 0. 007 12 . 00 0. 1 39. 4 Vel = 3. 62 159.36 4 .260 12 . 00 39.5 39.5 B2 C=120 0. 00 0. 0 0 . 0 See PATH 2 318 .55 0. 024 12 . 00 0. 3 39. 5 Vel = 7. 24 120.56 4 .260 1T 75 . 83 39. 8 39. 8 B3 C=120 26. 33 0. 0 0 . 0 See PATH 3 439. 11 0. 043 102 . 17 4 . 4 39. 8 Vel = 9. 98 4 . 260 56. 81 44 . 1 44 . 1 B4 C=120 0. 00 0 . 0 0 . 0 439. 11 0. 043 56. 81 2 . 4 44 . 1 Vel = 9. 98 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date:02122/07 1/22/08 8:50 Tyco Fire Products Page 6 7lJJ�Y,t�JIJ!lllflJ.4NJlJ„,#Y1yJ,WJIHYJJJJ�'JJNJJJNJJJlJJ1!!J!!/�YHJJJ.JJJJJf.,::�.�r,':;'+J.:'<'Ji;;SYS;'•'•3;%,:!!�!r/,%Jty1,WJlJ,3t�JJJ�YJri'JHJJJ1.3>'J!!!J!,•;.!!{+�'.•1J,11JllN,S„Y1..>'J!l1.�1!!!J!!lI.+JJf.JJJJ!!J!i i!!!}{q!J/,llJ.�JJ!!!J!!JlI.�JJJJJ!!!!!!lJIJJ!lHIJJJJIJJ,c HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn . .vvstcor..�u.•.•lxso;�.s»JJ..s ra��! r.�o�,.innx :�-�xexxza�ra�rJ.¢x�r�.:�rxzc:� .. PATH 1 FROM HYDRAULIC REFERENCE 23 TO W (PRIMARY PATH) 4 . 260 5 . 00 46. 6 46. 6 A5 C=120 0 . 00 0. 0 0. 0 439. 11 0. 043 5 . 00 0 .2 46. 6 Vel = 9. 98 W 439. 11 46. 8 K = 64 .20 '•• •• •• .'d's475'+.�L',.a� h+' '7.bJd/.ab83r�.'/.�'dru'tf:'rfG'av,Yrraa'..J.vY.•J.�;f/'�J,s.'.:L•icw;�"+IiG,'.ae.,?�JJ.v"J.•XJts'•,"•a.'•�.4,Cui3:!+/1.1�/J.r...:+�.;r�iiJ�Y/�+3.G,riu'kriiill+JleG+i�o �I�IJJi'�.�rXc%�:tu35,ifJ1J/�YsG;IIc'G.%J" PATH 2 FROM HYDRAULIC REFERENCE 29 TO B2 21. 19 1 . 049 8 .50 7 . 0 7 . 0 K = 8 . 00 29 C=120 0 . 00 0. 0 0. 0 21 . 19 0. 145 8 .50 1 . 2 7 . 0 Vel = 7 . 94 22 . 97 1 .380 9. 00 8 . 2 8 . 2 K = 8 . 00 30 C=120 0. 00 0. 0 0. 0 44 . 16 0. 148 9. 00 1.3 8 . 2 Vel = 9.57 24 . 76 1 . 610 9. 00 9. 6 9. 6 K = 8 . 00 31 C=120 0. 00 0 . 0 0 . 0 68 . 92 0. 159 9. 00 1 . 4 9. 6 Vel = 10. 97 26. 55 1. 610 9. 00 11. 0 11. 0 K = 8 . 00 32 C=120 0 . 00 0. 0 0 . 0 95 . 47 0.291 9. 00 2 . 6 11. 0 Vel = 15 . 19 29. 54 1. 610 10. 00 13. 6 13. 6 K = 8 . 00 33 C=120 0. 00 0. 0 0 . 0 125. 02 0. 480 10. 00 4 . 8 13. 6 Vel = 19. 89 34 . 34 1. 610 1T 15 . 00 18 . 4 18 . 4 K = 8 . 00 34 C=120 8 . 00 0. 0 0. 0 159. 36 0. 751 23. 00 17 .3 18 . 4 Vel = 25 .36 2 . 067 1T 2 . 33 35 .7 35 .7 70 C=120 10 . 00 1 . 0 0 . 0 159. 36 0. 223 12 . 33 2 . 7 35 . 7 Vel = 15 . 39 B2 159. 36 39. 5 K = 25 . 37 . JIfYJr%JJ"r$iIJJ/.`/.+7i.s7.iihf'.tyii9i.>i"1.//$ii"!/'i'//i?97$fYiir/�YiJlr?S1YH.��yrsl�l.Jri+ ��?.i!1.YlJ3.�i}�!}kYJJJ�Ir'Yri'Y.+iit�iN��'JJJ.•%!/.•�v"Ji'/Hr'^r�Y1SIFYJi9.'�.'+.yi5r'�43}yjJ�y!!!!!lJIJJ/ ; PATH 3 FROM HYDRAULIC REFERENCE 37 TO B3 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date: 01/22/07 1/22/08 8:50 Tyco Fire Products Page 7 /,9i 'i.55'i'fiS.`7;Y3m�i:s"�"m"ir`Yr:`v:""1,3.<fd5'..':59}kfY,:�'.)7Y%Vl9J.•5559Rb.dN+Y.+itv'Y,U9//.c>>.d."S9:f>7:>Ti'9R+J.�+X.¢..47)S',:�+^.5,'.:3'�l.G i:/.•:{C!.'+!//�l'x'r'riGic:'i+'W'SiR45i3WN/.K7.Y7K2Kf.Y:9F9Y.S„"r16SJ9i HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn r.:acomxserr�rnxrza:>::�::.�a.?t,.�:rrr„tc!!::r�r:�;zv�t?-ax��acarpeonac�'vsir;sty.ups. .�•r.•:;t:.ecc:wrc:s>m'v,:•,ccszx:�r�.w.isisv.Esq.,wcrwrrrirr�.rris�s.��..�'!f.�zsac•�:r. PATH 3 FROM HYDRAULIC REFERENCE 37 TO B3 CONTINUED 39. 37 1. 610 9. 00 24 . 2 24 .2 K = 8 . 00 37 C=120 0. 00 0 . 0 0 . 0 39. 37 0. 057 9. 00 0.5 24 . 2 Vel = 6.27 39. 78 1. 610 10. 00 24 . 7 24 .7 K = 8 . 00 36 C=120 0 . 00 0. 0 0 . 0 79. 15 0.206 10. 00 2 . 1 24 . 7 Vel = 12 . 60 41 . 41 1 . 610 1T 15 . 00 26. 8 26. 8 K = 8 . 00 35 C=120 8 . 00 0. 0 0. 0 120. 56 0. 448 23. 00 10. 3 26. 8 Vel = 19. 19 2 . 067 1T 2 .33 37 . 1 37 . 1 71 C=120 10. 00 1 . 0 0 . 0 120. 56 0 . 133 12 . 33 1. 6 37 . 1 Vel = 11. 64 B3 120. 56 39. 8 K = 19. 12 . .:.�' :,4;stbS`..`YiCzf+.S.N:�t`5..#%/.':.`.rv33'..d3Ls"usfGfiGiG:i:SL'LaS•i�v'u.�&3b`d3Lkis6.!.;'+;1dGS:1l/.''+.•,C`..,,+1�:3.t:3?.>::3C.£'i'3.'£:�,i�33?b�:�•}.yy"3.Y:•Y.'�6'Ilds :'Y.,�S UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Job Water Required Hose Allowance VCA Static Pressure: 115.0 psi Pressure: 56.6 psi Inside: 0 gpm 209 Earle Street Residual Pressure: 80.0 psi System Flow: 439 gpm Outside: 250 gpm Northampton, MA Flow: 620 gpm System+Hose: 689 gpm Remote Area: 2 Date: 6/20/02 Safety Pres: 15.9 psi Loc: Earl street at Smith Coll Head Elev Pres: 32.5 psi 140 120 100 Sup ly P 80 S I 60 250 gpm hose 40 32.5 psi 20 - 150 225 300 375 450 525 600 675 75( Flow (gpm) VCA, Drawing Date: 01/22/07 1/22/08 8:51 HYDRAULIC DESIGN INFORMATION SHEET Job Name: VCA Location: 209 Earle Street Northampton, MA Drawing Date: 01/22/07 Remote Area Number: 3 Contractor: WAREHOUSE MECHANICAL CONTRACTORS INC. Telephone: 413-536-9222 342 BRITTON STREET CHICOPEE, MA 01020 Designer: DAVID P. KRAUSE Calculated By:SprinkCAD www.sprinkcad.com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: METAL PURLINS Occupancy:OFFICE Reviewing Authorities:CITY SYSTEM DESIGN Code:NFPA 13 Hazard:OR GR II System Type:WET Area of Sprinkler Oper. sq ftj Sprinkler or Nozzle Density (gpm/sq ft) 0 . 200 1 Make: VIKING Area per Sprinkler 108 . 0 sq ftl Model: VK200 Hose Allowance Inside 0 gpm K-Factor: 8 . 00 Hose Allowance Outside 250 gpm Temperature Rating: 200 CALCULATION SUMMARY 8 Flowing Outlets gpm Required: 445.7 psi Required: 48.5 @ Source WATER SUPPLY Water Flow Test Pump Data Date of Test 6/20/02 Rated Capacity 0 gpm Static Pressure 115 . 0 psi Rated Pressure 0. 0 psi Residual Pres 80. 0 psi Elevation 0 At a Flow of 620 gpm Make: Elevation 0" Model: Location: Earl street at Smith College sta Source of Information: WMC SYSTEM VOLUME 360 Gallons Notes: VCA Drawing Date: 01/22/07 1/22/08 8:51 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 3 196 39.0 psi 1 4" Grvd Back Flow Valve WILKENS 1137 CHART LOSS 196 9. 1 1 6" x 4" Fingd 90 Ell 14 ' 120 6. 065 196 0 . 0 1 Pipe 6" DIx18 Cl 350 350' 140 6.338 196 0. 4 Fixed Flow Flow Loss 250 gpm Hydr Ref R1 Required at Source 446 48.5 psi Water Source115 . 0 psi static, 80 . 0 psi residual @ 620 gpm 446 gpm 96.0 psi SAFETY PRESSURE 47.5 psi Available Pressure of 96.0 psi Exceeds Required Pressure of 48.5 psi This is a safety margin of 47.5 psi or 50 % of Supply Maximum Water Velocity is 18 . 9 fps VCA Drawing Date: 01122107 1/22/08 8:51 Page 3 FITTING NAME TABLE ABBREV. NAME �Y'i.�'9.;9Y}}lI.A�Yi.A9.r.33:!/}/.,it/.•:3,`.'+,';rHH:Y3:'�}iJ:{{,G33gy}.9IG'}}}i91'Ai•9.'+/+.'�,5}}}!,'x"}1}}}}�iY�3'}'.:;9:553ii!L.c'}}.�Y1}}}} C Coupling E 90' Standard Elbow F 45 ' Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee V Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. _ K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNG'S Number of fittings . See table above. TOTAL Total length (PIPE + FTNG'S) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0. 433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4 .52 x (Q/C) ^1 . 85 / ID^4 . 87 Pv Velocity pressure (psi) where Pv = 0. 001123 x Q^2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0. 01 psi. Pressures are listed to 0. 1 psi. Addition may vary by 0. 1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations VCA Drawing Date: 01/22/07 1/22/08 8:51 Page 4 l//�59Y.67" , �+fP .•Y;CD�Y},33'H}}}}}}}}}},3'},33:6„w,{i},3N•i3Y.:if.533<IJ::Y4:4}.f�},3CStGYSLaNI.+l.+w?iY.C�}},,,:::nSY}.O.«Y}}.'}}}}}..�;ic•.3'•'J:91;;.G3%,G;}},L'/,'•Y}}}}}}1H}}}}N/}//.•+/,3.Y,.,a,:Y,W}.43Y}}.'!}.4'1,y,3Y//iYH,C49Y,'NN.3JY.✓}fY/,D}}� NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^',�) ) (PSI) (GPM) (GPM) (GPM/SQ. FT) -?3?c`}. /}{±i67Y //,C69Y.#}.H}}/.6Y:dd3%}�YF3.'{,}�cjY,'/!/.!6y}}.�}.,}}}}}}}}}.3'}.6t�}}.!6Y}},f4;62W�3'.6'}N}.6:6'}..W}}.6'f}!.�/}}}}/},.+�'}}}}1}}},.:+�`}{,r{,?HJf,'•::u,:r.',G9C17}}J},6r,%J/},;3;'G3Yl"J.•:'�}}}.739}�3Y}.UJ,%}},2�;'}J17}„'}/,3'A9i 38 14 .50 8 . 00 7 . 4 21 .7 21. 6 0. 20 39 14 .50 8 . 00 8 .7 23 . 6 21. 6 0. 22 40 14 .50 8 . 00 10 . 1 25 .5 21. 6 0.24 41 14 . 50 8 . 00 11. 6 27 .3 21. 6 0. 25 42 14 .50 8 . 00 7 . 3 21 . 6 21. 6 0. 20 43 14 .50 8 . 00 8 . 6 23 .5 21. 6 0. 22 44 14 .50 8 . 00 10. 0 25 .3 21 . 6 0. 23 45 14 . 50 8 . 00 11 . 5 27 . 2 21 . 6 0. 25 A5 16. 00 39. 0 B4 16. 00 38 . 4 C1 14 .50 13 . 3 C2 14 .50 14 . 4 D1 16 . 00 37 . 8 W 16. 00 39. 0 Max velocity of 18 . 89 occurs in the pipe from D1 TO C2 VGA Drawing Date:01/22/07 1/22/08 8:51 Tyco Fire Products Page 5 y,� ,�rrJirysrJJJ�rrrcrdrJ,i�rrrrrJ.rrJ,ts..rrrrr.�;c...srrrrrJ�rrr.�:vJ..cr �,svJ.xerr.,rrr..carx.?:r:+�:cYrr.,r�Jr�r�,JJJrrrJr.�xs.rs�s:�JJ,.wJ.,dJrfrrrrJJ,sr..r:�Jri,�,aiArr�,r�rrrJJ�JnrJ�rvJ.vn�J,oJrJrrorto HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn dY.G3Yf�'J1i.>XCG3v""JJJJ.•i�'iddrYC+.YYfi"JJA'JY+`YJ'�.Ct>/.GR"NY.ViJ%+rJlS:'SItGYr,G,t-'S'.3'ri'.Yrrrt'lr.Y.+.+JYi�Y♦i55�JN'.i3Y'i5�'r.'✓ii:GdS+/iv"JJ.d'r/.',�.'•'.:i',�'.11.•:3+iSYJAY,dii".3:'JHr."9i 57 'Ji5ii+6's PATH 1 FROM HYDRAULIC REFERENCE 42 TO W (PRIMARY PATH) 21. 60 1. 049 9. 00 7 . 3 7 . 3 K = 8 . 00 42 C=120 0. 00 0 . 0 0 . 0 21. 60 0 . 150 9. 00 1 . 4 7 . 3 Vel = 8 . 10 23. 52 1. 380 9. 00 8 . 6 8 . 6 K = 8 . 00 43 C=120 0 . 00 0 . 0 0 . 0 45 . 12 0 . 154 9. 00 1 . 4 8 . 6 Vel = 9.77 25 .33 1. 610 9. 00 10. 0 10. 0 K = 8 . 00 44 C=120 0. 00 0 . 0 0. 0 70. 45 0 . 166 9. 00 1. 5 10 . 0 Vel = 11 . 21 27 . 15 1. 610 1T 1 . 50 11.5 11.5 K = 8 . 00 45 C=120 8 . 00 0. 0 0. 0 97 . 60 0. 303 9. 50 2 . 9 11 .5 Vel = 15 .53 98 . 08 2 . 067 5E 38 . 84 14 . 4 14 . 4 C2 C=120 1T 35 . 00 -0 . 6 0 . 0 See PATH 2 195 . 68 0 . 325 73. 84 24 . 0 14 . 4 Vel = 18 . 89 4 .260 1T 40. 33 37 . 8 37 . 8 D1 C=120 26.33 0. 0 0. 0 195 . 68 0 . 010 66. 67 0. 6 37 . 8 Vel = 4 . 45 4 . 260 56. 81 38 . 4 38 . 4 B4 C=120 0 . 00 0 . 0 0 . 0 195 . 68 0. 010 56. 81 0 . 5 38 . 4 Vel = 4 . 45 4 . 260 5 . 00 39. 0 39. 0 A5 C=120 0 .00 0. 0 0. 0 195 . 68 0. 010 5 . 00 0. 0 39. 0 Vel = 4 . 45 W 195 . 68 39. 0 K = 31.33 •ld%/,f�J/rX ' .SG9.Gig.%A.isi1.c�,L.'/J.u'✓!//::.3:23;."�;.'•�:�i+�%'J/./..:��IY.G,'1J/!1/,•;;3.:.��%3rt'!l.•.'i//l!/,:i//�43/.•c'fY//Jl ii/.•,::!;vY.b.;;:.�f.•,1:'±Yi:91.t1.•.'G;isJJ�%i,+3�,�1//,t+�;5;'�%/Jai/,11J/JJ/.3Y,d'3.rrJb�:r31/i/lYi PATH 2 FROM HYDRAULIC REFERENCE 38 TO C2 21.71 1. 049 9. 00 7 . 4 7 . 4 K = 8 . 00 38 C=120 0. 00 0 . 0 0. 0 21 .71 0. 151 9. 00 1 . 4 7 . 4 Vel = 8 . 14 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date: 01/22/07 1/22/08 8:51 Tyco Fire Products Page 6 ..�. 'moi�v�+.Q��i �J.Yh.:YJ.C:t:�'i,I%%�:7�.•:;i,•.;,:Q:K l�;•'!.{I/'{/(�]Y3i.'s�.'1.>},: �n7,t.�{��•�{L+J.'•/.�.{J:LY.+.f1L,G,6.D,:Yl.X3f7}��i:3�v'�'.{,G;;•:ii�$:YI.`liv:!!•$.'•;;•::Y/�,:•.'iffJ.(+�:�.'r/i'Ji$�i�/Jl.�%/,+,'J/.>iJ,::v'}f$�Jf .rfi'JJJ.•i�{.:L:N.•:+.+1'JJ/.�'h HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn Y.Y,NSG'�19YJ1.!!J},q�+ddC,t+a:!,'J1.f}.:YJ.ti%}}}/.{4�.'G;3L'}/.{.'.'•.n�,;;'/.1JJYJ,.'•%JJ�JaY•'JJ},qya.GSJ}},dC�}J}}}iJ}/.f�!+J}}J.::: Job Water Required Hose Allowance VCA Static Pressure: 115.0 psi Pressure: 48.5 psi Inside: 0 gpm 209 Earle Street Residual Pressure: 80.0 psi System Flow: 196 gpm Outside: 250 gpm Northampton, MA Flow: 620 gpm System+Hose: 446 gpm Remote Area: 3 Date: 6/20/02 Safety Pres: 47.5 psi Loc: Earl street at Smith Coil Head Elev Pres: 46.8 psi 140 120 SU 100 -- PRI I 80 60 250 gpm hose 40 -- 20 100 150 200 250 300 350 400 450 50, Flow (gpm) YC-i Drawing Date:01122107 1122108 9: 3 HYDRAULIC DESIGN INFORMATION SHEET Job Name: VCA Location: 209 Earle Street Northampton, MA Drawing Date: 01/22/07 Remote Area Number: 4 Contractor: WAREHOUSE MECHANICAL CONTRACTORS INC. Telephone: 413-536-9222 342 BRITTON STREET CHICOPEE, MA 01020 Designer: DAVID P. KRAUSE Calculated By:SprinkCAD www.sprinkcad. com 451 N. Cannon Ave. Lansdale, PA 19446 Construction: METAL PURLINS Occupancy:OFFICE Reviewing Authorities:CITY SYSTEM DESIGN Code:NFPA 13 Hazard:LIGHT System Type:WET Area of Sprinkler Oper. 900 sq ftj Sprinkler or Nozzle Density (gpm/sq ft) 0.100 1 Make: VIKING Area per Sprinkler 186.0 sq ftj Model: VK302 Hose Allowance Inside 0 gpm K-Factor: 5 . 60 Hose Allowance Outside 100 gpm Temperature Rating: 155 CALCULATION SUMMARY 10 Flowing outlets gpm. Required: 327.3 psi Required: 41. 6 @ Source WATER SUPPLY Water Flow Test Pump Data Date of Test 6/20/02 Rated Capacity 0 gpm Static Pressure 115 . 0 psi Rated Pressure 0. 0 psi Residual Pres 80. 0 psi Elevation 0 At a Flow of 620 gpm Make: Elevation off Model: Location: Earl street at Smith College sta Source of Information: WMC SYSTEM VOLUME 360 Gallons Notes: VCA Drawing Date:01122107 1/22/08 9: 3 HYDRAULIC CALCULATION DETAILS HYDRAULIC FLOW LOSS QTY DESCRIPTION LENGTH C ID gpm psi TOTALS Hydr Ref W Required at Hyd Area 4 227 32.5 psi 1 4" Grvd Back Flow Valve WILKENS "37 CHART LOSS 227 8 . 6 1 6" x 4" Fingd 90 Ell 14 ' 120 6. 065 227 0. 0 1 Pipe 6" DIx18 Cl 350 350' 140 6. 338 227 0.5 Fixed Flow Flow Loss 100 gpm Hydr Ref R1 Required at Source 327 41. 6 psi Water Source115 . 0 psi static, 80. 0 psi residual @ 620 gpm 327 gpm 104 .3 psi SAFETY PRESSURE 62. 7 psi Available Pressure of 104.3 psi Exceeds Required Pressure of 41. 6 psi This is a safety margin of 62 . 7 psi or 60 % of Supply Maximum Water Velocity is 14 . 8 fps VCA Drawing Date: 01122107 1122108 9: 3 Page 3 FITTING NAME TABLE ABBREV. NAME C Coupling E 90' Standard Elbow F 451 Elbow S Straight Flow Thru Tee T 90' Flow Thru Tee V Valve LEGEND HYD REF Hydraulic reference. Refer to accompanying flow diagram. K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P Qa Flow added or subtracted Qt Total flow DIA Actual internal diameter of pipe C Hazen Williams pipe roughness factor Pf/ft Friction loss per foot of pipe PIPE Length of pipe FTNGIS Number of fittings. See table above. TOTAL Total length (PIPE + FTNGIS) Pt Total pressure (psi) at fitting Pe Pressure due to change in elevation where Pe = 0. 433 x change in elevation Pf Friction loss (psi) to fitting where Pf = 1 x 4 .52 x (Q/C) A1. 85 / ID^4 . 87 Pv Velocity pressure (psi) where Pv = 0. 001123 x Q"2/ID^4 Pn Normal pressure (psi) , where Pn = Pt - Pv NOTES: - Pressures are balanced to 0. 01 psi. Pressures are listed to 0.1 psi. Addition may vary by 0.1 psi due to accumulation of round off. - Calculations conform to NFPA 13. - Velocity Pressures are not considered in these Calculations VCA Drawing Date:01/22107 1/22/08 9: 3 Page 4 oY: `. r3t83G'.kt±r,S`r5f'r..'•l.4fisrr:'.'•h'.Y?:{a>=�"lA:tili5^:C;4{{r.•;S:frr:h<r:'r'ofiSR:%tC=w^#:t�::,ti{!�''r.<StS:F k`gf.?'r:2::'t�+.'raS:t:,t;ct:55.'{t`v.GS'rii::.'rstd;Si'r",i`x•<+i.gv�:'a.YyhW'»ri:S�9;YJi{.`L',3'•,�Si:�9Xrf53�!*'rSG3'.�, NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM ACTUAL NUMBER K-FACTOR FLOW FLOW DENSITY (FT) (GPM/ (PSI^-z) ) (PSI) (GPM) (GPM) (GPM/SQ. FT) IUrYll1.0+tt>:rll,YdG.{NAY,Gfr.✓rYX•:N,Yh°.'A.'di4sC3C{{{et:+.::'{y!/.{�Yr,•r,{.G'{{t>i.!':r,.c,�{{r!{r{,.,({rr..'d'••'{{ice{r,{{�;;{rrl..:r„r.,r m;�•;y,?:SfRY, mx:GS:{r,.Xti::<::;;,m,•:ry{m„�;9rY!!K•�t66'!rY/.!R;r•7'•X•::n„{{:'7.Y.{{L'Lt{{G:r!lrlbfffCt"F.';t{4+1.{L;G'!,:{,:{{{{/+59'.'{r.rll,W.ri'!!i 48 9.00 10. 9 48S 8 .00 5 . 60 11 .0 18 . 6 18 . 6 0 . 10 49 9.00 71.7 49S 8. 00 5. 60 11. 8 19.2 18. 6 0. 10 50 9. 00 13. 8 50S 8 . 00 5 . 60 13. 4 20 .5 14 . 8 0 . 16 51 9. 00 1.7 . 4 51S 8 .00 5 . 60 17 .3 23 . 3 14 . 8 0. 18 52 9.00 15 . 3 52S 8. 00 5. 60 1.5 .2 21. 9 18 . 6 0. 12 53 9. 00 16. 4 53S 8 . 00 5 . 60 16.3 22 . 6 18 . 6 0. 12 54 9. 00 21 .2 54S 8 . 00 5 . 60 21 . 0 25 .7 14 . 8 0 .20 55 9. 00 23 . 4 55S 8.00 5 . 60 23 .2 27 .0 14 . 8 0. 21 56 9.00 17 . 9 56S 8.00 5 . 60 17 .8 23.7 14 .8 0. 18 57 9. 00 20. 0 57S 8 . 00 5 . 60 19. 8 24 . 9 14 . 8 0. 19 60 9. 00 18 . 6 61 9.00 12 . 5 62 9.00 27 . 0 63 9. 00 25 . 0 64 9. 00 28.7 65 9. 00 21.7 66 9. 00 21. 4 67 9. 00 19.1 68 9.00 18 . 2 Al 9. 00 29.7 A2 9. 00 29. 9 A3 9. 00 30. 4 A4 9 . 00 35 .0 A5 16. 00 32 . 4 W 16. 00 32 . 5 Max velocity of 14. 81 occurs in the pipe from 65 TO 64 Nodes with "S" indicate a node at the top of a sprig or bottom of drop pendent. The node without an "S" is on the branch. VCA Drawing Date:01/22/07 1/22/08 9: 3 Tyco Fire Products Page 5 � , .,'C:✓J.V`.SnYfi;�2�,;lXuY::':i4�I;2F;:Ri+s2Yl,.a:.C,:S,�'$:tSr..�::YttisfiScr'3. .'19f?i5Y//rsi';.4�3>"�%}HIFc$ i3.4"/.•:+.t5'.r,$Y,iiFir//ai',5;$.`•'I,%I.`ii:4`.•Y,9r.•1.•i`A1,"i/I.ri`#!!Nf/.9{i�I.6/n;;�.'�+SYl3�P:9;'//f�iC+?9.P. HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn . ...Y.6;'fi.Y+;�Y.'�"3i.'Y,.`+U.�"/,`f.+1.S'9.Yft'c1.::•{•3.Y:13:?ii3Y,tH.':C+1/3Yl.OSY.+//+�X!'+.tY'Sb"i}31J.H.YyX+.2i:+i•X.?'{:5<,Kr+.:tn•X91!.•?.;;1,:'�i`H1.!fr�i'Y.+/lr,.;}Y/,Y/'.f,9N}�5'n'fiGuS'i i'fi�ii5.'!' fX+Y,//,i'lf�fiY/.,�'+/.y,YYfifi'/.C�+i�1+&'6i PATH 1 FROM HYDRAULIC REFERENCE 48 TO W (PRIMARY PATH) 18 . 60 1. 049 1E 1. 00 11 . 0 11 . 0 K = 5 . 60 48S C=120 2 . 00 -0. 4 0 . 0 18 . 60 0. 114 3. 00 0 . 3 11 . 0 Vel = 6. 97 1 . 049 14 . 00 10. 9 10. 9 EqK = 5 . 62 48 C=120 0 . 00 0. 0 0. 0 18 . 60 0. 114 14 . 00 1. 6 10 . 9 Vel = 6. 97 19. 20 1. 380 IE 8 . 48 12 . 5 12 . 5 61 C=120 3 . 00 0. 0 0. 0 See PATH 2 37. 80 0. 111 11 . 48 1.3 12 . 5 Vel = 8 . 19 20. 52 1.380 1E 16.50 13. 8 13 . 8 EqK = 5 .52 50 C=120 3. 00 0. 0 0. 0 58 . 32 0. 248 19.50 4 . 8 13 . 8 Vel = 12 . 63 23 . 32 1. 610 2E 34 .50 18 . 6 18 . 6 60 C=120 1T 16. 00 0. 0 0. 0 See PATH 5 81. 64 0 . 218 50. 50 11 . 0 18 . 6 Vel = 12 . 99 2 . 635 14 .35 29. 7 29. 7 Al C=120 0 . 00 0. 0 0. 0 81 . 64 0. 020 14 . 35 0.3 29. 7 Vel = 4 . 85 52 . 64 2 . 635 9. 98 29. 9 29. 9 A2 C=120 0 . 00 0. 0 0. 0 See PATH 8 134 . 28 0. 050 9. 98 0. 5 29. 9 Vel = 7 . 98 93. 04 2 . 635 2E 18 .52 30 . 4 30 . 4 A3 C=120 16. 47 0 . 0 0 . 0 See PATH 3 227.32 0. 132 35 . 00 4 . 6 30. 4 Vel = 13 . 51 4 .260 1T 7 . 00 35 . 0 35 . 0 A4 C=120 26.33 -3 . 0 0. 0 227.32 0 . 013 33.33 0. 4 35 . 0 Vel = 5 . 17 4 . 260 5 . 00 32 . 4 32 . 4 A5 C=120 0. 00 0 . 0 0 . 0 227 .32 0. 013 5 . 00 0 . 1 32 . 4 Vel = 5 . 17 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date: 01/22/07 1122108 9: 3 Tyco Fire Products Page 6 ��}�'��q�v�'.<59W.$YE4�,xCff,'Lr.Wa9.'{'%1.2'{`.::c.'CMk.�:fG'},.tuft{{{{c'cY+"dN.tt:t1,t5;53XG?f!'g'.C.:+;•,'>•.+:sgf'$.';oClfib.Cdr:rta:?6s3R?y�:cc;t:.:tw.'v�iY.tt::.'{+�:�'dr'i�':%J1.+3:a;;�F'..'+?;.? .?:;,rrr;�:,c�Yrri:::v:2re't�,��#l�:r/,!G3r�,tdt�{'v.'.3 'f,}iFf: ,�fsl/.97Y,r"i'ld: HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn %1.+'1A/.36Y✓A7/1.�+50AX A/A ','33.X'i"✓,$�ffr,�G!/.19195$:+i.'/,'!.6$f.///.$f✓i;/,�'///.:{: .q$'!,$$$$:'�;•fClt.$'.LdC?r/X+'.{GLG'l.+/JJd1.'+3'JJi k'+./1.'+%✓.+5�?r,,;.a,�:'4�."J.'!,$'l.C:/i:Y{,C�/:t,'+3f%!!.//'+/'/J.'?W'+f/�:'!;.'•'/::+1$!/!//,:ylllJ,','✓/.$'r/%1,%/Y:,$'!,$9,^3YJJJ.+S$'/,Y19L�Y//.{GdD W 227 .32 32 .5 K = 39. 88 XA�95s3?Y1.1"^YIr."3T)i?.+/�$19J3:9959;)'Ssr:;$$7.?:1>74��f1:Y.7i551r?i9?1919fi,9YffiYJS#r3ir,'$91$19th;9;ir;T?3591S39t"ct'r'r:S9;9t;�,7�959.+�71.N55:vfi59iF.ll."}s.',it9•ir"St}tf};9„97Y/3:�i/X519}S�?3;•d9Y7r�19.�i9f.'+Y,59?3#9F71r: 20 .52 1. 049 1T 1. 00 13. 4 13. 4 K = 5 . 60 50S C=120 5 . 00 -0 . 4 0. 0 20. 52 0. 136 6. 00 0. 8 13 . 4 Vel = 7 . 69 50 20.52 13. 8 K = 5 .52 PATH 2 FROM HYDRAULIC .REFERENCE 49 TO 61 19.20 1 . 049 1E 1 . 00 11. 8 11 . 8 K = 5 . 60 49S C=120 2.00 -0. 4 0. 0 19.20 0. 121 3.00 0. 4 11. 8 Vel = 7 .20 1. 049 1T 2 . 00 11. 7 11. 7 EqK = 5 . 62 49 C=120 5 . 00 0. 0 0. 0 19. 20 0. 121 7 . 00 0. 8 11.7 Vel = 7 .20 61 19.20 12 .5 K = 5 . 42 ... - v°,^w3.G''WiY�15e'.53/f:.L'.:'Xi.; 5X1..:.'.�3�+.5+}5l.'w'!::Cl,.'rd,tfb,'f///f,.44iYC.i'tt::'J/,rX1j.";li."+/?,..'+�./�k'ad'+:.'!s,C..!1,1�"txiH}.&5i'+11�.1.+.29r';!!!f{'+,5Y,f/.+.'+::Y./!�.'EaY;"!!,�»3/:t.3.3,'i/1J..',f+Y//�+1�//✓.d''t./i�rG�S;KSf.'&dJ� PATH 3 FROM HYDRAULIC REFERENCE 52 TO A3 21. 85 1. 049 1E 1.00 15 .2 15 . 2 K = 5 . 60 52S C=120 2.00 -0. 4 0. 0 21. 85 0. 153 3.00 0.5 15 .2 Vel = 8 . 19 1. 049 1E 17 . 19 15 .3 15 . 3 EqK = 5 . 60 52 C=120 2 . 00 0. 0 0 . 0 21. 85 0. 153 19.19 2 . 9 15 . 3 Vel = 8 . 19 22 . 62 1.380 6.15 18.2 18.2 68 C=120 0.00 0. 0 0. 0 See PATH 4 44 . 47 0. 150 6.15 0. 9 18 . 2 Vel = 9. 63 23. 65 1. 380 7 . 02 19. 1 19. 1 67 C=120 0. 00 0. 0 0. 0 See PATH 6 68 .12 0. 330 7 .02 2 . 3 19. 1 Vel = 14 .76 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) ' ' VCx Drawing Date:01/22/07 I/22/08 9: 3 Tyco Fire Products Page 7 HYD. Oa DZA, FITTING PIPE Pt Pt REF ncn TYPES FTNG,S Pe Pv ^+*++** NOTES POINT Qt Pf/ft TOTAL Pf Pn PATH 3 FROM HYDRAULIC REFERENCE 52 TO A3 CONTINUED I. 610 1. 98 21. 4 21. 4 66 C=I20 0. 00 0. 0 8, 0 68 , 12 0. I56 1 . 98 0'3 21. 4 `/eI ~ 10. 84 24 . 92 1 . 610 25 . 02 21 ,7 21.7 65 C=120 0. 010 0, 0 0. 0 See PATH 7 93,04 0.278 25.02 6.9 21.7 l7eI = 14 .8I 2 . 067 IT 11.17 28 .7 28 .7 64 C=I20 10. 00 0. 0 0. 0 93 , 04 0. 082 2I. 17 1 . 7 38 . 7 Vel = 8 , 98 A3 93 . 04 30. 4 K = 16,87 PATH 4 FROM HYDRAULIC REFERENCE 53 TO 68 22 . 62 1 , 049 lE 1.00 16.3 16. 3 K = 5 , 60 533 C=130 2 ' 00 -0, 4 0 . 0 22. 62 0.163 3. 00 0. 5 16, 3 Vel = 8 . 48 I. 049 IT 6. 19 16. 4 16. 4 Eg}I = 5 .59 53 C=I20 5 , 00 0. 0 0. 0 22. 62 0. I63 11 . 19 1. 8 I6- 4 Vel = 8 . 48 68 22. 62 18.2 E{ = 5 . 30 PATH 5 FROM HYDRAULIC REFERENCE 51 TO GO 23,32 1' 049 IE 1 . 00 17 . 3 17 . 3 K = 5 , 60 5I3 C=120 2 , 00 -0.4 0, 0 23'32 0, I73 3,00 0.5 17 .3 Vel = 8 ,74 1, 049 lT 2 ' 00 17 . 4 17 . 4 EgK = 5 ,59 51 C~I20 5 , 00 8, 0 0. 0 23, 32 0. I73 7 , 00 1 , 3 I7 ' 4 Vel = 8 .74 D0ZT3 - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PBZ) VCA Drawing Date:01122107 1/22/08 9: 3 Tyco Fire Products Page 8 . x'�''.fa,Y:v'7.",.'ff♦.•S:'final.C.',^.;'�g5:t.5'f�'f,:�,"+'+a?:NSk��,izri'wC<as}'v:.'•:�9.:w',dcS'.{H.'i:':','��G!+Co".-:;.'9'3�'•:+.;,�:J'>,+�::r?f.�f.'c 'rfYfi.",�.�3:�3F3.�3f1�:I.•:�kG:�vtW,R�'r,Y�3,.+3i:2'riF3Sit'�7aF✓�'tf..Y.;S;tr,'r9.R',s�r'�s f.{+J.Yfi' J.{aik+ HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn �:ta»sct�sssw.�»:sts.�sts�ss:.ts�'.s�-sssrfrasrx�s�csrotaro��fsrcr.t . . a��.�.a�ftsx}irns�ffasf�rasw�.a3s�fr�s�v�caat� 60 23.32 18 . 6 K = 5 . 40 �.tH .@141�R4:Ci4�k.�N: C4�k�',k.t�Sv'ScCC.'4kifi�:�:",.'C:�'+.:k�.urCt::"o-R�'ir.�:R�:::C'Y;oafk��St'th`�§?�.2cSt�r:�`.t�:�:•`.c?:.' .,�Vfi':��te.?t��f?S=zRcsY�S:cfkn.;{tt2t�f.::�.';:.v...>',::t;.;�.,rt35fasv?tt'ft;;:is3'.,c.J..+f?i�t�-'h.�N.:'•..:qhs:R'{i'tx�cZtd.SGc.'4'i�:tt'C'', PATH 6 FROM HYDRAULIC REFERENCE 56 TO 67 23. 65 1.049 1E 1 . 00 17 . 8 17 . 8 K = 5 . 60 56S C=120 2 . 00 -0. 4 0 . 0 23. 65 0. 177 3 . 00 0. 5 17 . 8 Vel = 8 . 87 1 . 049 1T 1. 65 17. 9 17 . 9 EqK = 5 . 58 56 C=120 5 . 00 0 . 0 0 . 0 23 . 65 0. 177 6. 65 1 . 2 17 . 9 Vel = 8.87 67 23. 65 19. 1 K = 5 . 41 �h89��'� YY%."ik"+^4Y1/.�UfrsS.'dt"c.�'C/�.5.�'[Y+.Ya4�Ei'!+#'itSS.LtF"�'GtGfr{2f19:J3;st.6PaSC'.!%5.:%vl./}✓ "a?b�if:�'fi+"Jc'+.+.xfrs<53."t' fJ.>.+SY_f1. .6?i�"fkla'+,s.':rr.5.5'a ,�E7tsiYtii .3'r:.3•+33Ylsr+�.+.1f.+1'S.k'flft'/.d',EY}�/�r� PATH 7 FROM HYDRAULIC REFERENCE 57 TO 65 24 . 92 1 . 049 1E 1 . 00 19. 8 19. 8 K = 5 . 60 57S C=120 2 .00 -0. 4 0. 0 24 . 92 0. 195 3. 00 0. 6 19. 8 Vel = 9. 34 1. 049 1T 4.15 20. 0 20. 0 EqK = 5 .58 57 C=120 5 . 00 0. 0 0 . 0 24 . 92 0. 195 9. 15 1. 8 20. 0 Vel = 9. 34 65 24. 92 21.7 K = 5 . 34 � .Cili'!:{+ii#s'''rv'fiYJ.r'fGi.`i+.�^X•r'::3'x'f:.:'N.{v":'L'f�}S%Yh`.•`.;ite+'f' "s^XfK4:t'91f�'%r:riCi6'i^.�i'Stv'FS?`raid?t'rH;;+:syrsY:�:v'F:Fitv9.�r.'•,'v$SS?$53:4'rf�.+:vGY.'�!Y'.'v",1Gi'�fifl.�i`.Yr'lS9i+')`93'J9.?�r',+ PATH 8 FROM HYDRAULIC REFERENCE 54 TO A2 25. 67 1. 049 lE 1 . 00 21 . 0 21 . 0 K = 5 . 60 54S C=120 2 . 00 -0. 4 0. 0 25 . 67 0.206 3. 00 0. 6 21. 0 Vel = 9. 62 1. 049 1E 16.52 21.2 21.2 EqK = 5 .58 54 C=120 2 . 00 0. 0 0. 0 25 . 67 0. 206 18 . 52 3. 8 21.2 Vel = 9. 62 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) VCA Drawing Date:01122107 1122108 9: 3 Tyco Fire Products Page 9 dam'19iitl'C7if6b':��' .. ,>:.,"+�.�✓�Y✓.L'��.3'�.'iiN✓.�'{:Y,Cw�'39.3'.Hi9.�Y.{+7Y+3`�✓✓✓.t:..YiC{�n'�9:�!✓at'✓.�9F.4Y1!✓✓i5'✓1fiY.{+Sr'Y✓✓�JY.�1lSak�3' iY..'✓�x�,�'✓✓i'✓U33'3C�{{�'+i✓Jt✓�i��t+.+r'?3'F,l.�iY�7r3.'LY�N3.�GGG HYD. Qa DIA. FITTING PIPE Pt Pt REF "C" TYPES FTNG'S Pe Pv ******* NOTES ******* POINT Qt Pf/ft TOTAL Pf Pn �. 3Y.t'>.'x'•kY+:Y9JSd839'+3t.Yv'.+sv:3'rikYd3:+.:33'i+:RCc3333:?v3C 3:airy'C<b:333::.33.,,:2;Y:>YS;3,r,:<5333R�:Cr{:,335aY,•+�iC:2:,+:"vY/.,cSs+.+.;33.+,:;+3C.3333'•'S3:{•3 3:tY.•33 33tY,33Y:�:33s.:k3;8,^.Y3'•33>.'.i..3333.'x,:333333333333333:r33Y,3Y.6:Y3;c333:<'x'33i d3336333f3f333Y.+1533339 PATH 8 FROM HYDRAULIC REFERENCE 54 TO A2 CONTINUED 26. 97 1.380 9. 48 25.0 25. 0 63 C=120 0. 00 0.0 0. 0 See PATH 9 52 . 64 0. 205 9. 48 1. 9 25 . 0 Vel = 11. 40 1. 610 1T 22 . 68 27 . 0 27 . 0 62 C=120 8 .00 0 . 0 0. 0 52 . 64 0.097 30. 68 3.0 27 . 0 Vel = 8 . 38 A2 52 . 64 29. 9 K = 9. 62 �r����, �.���sss��ss .,f�.y���,x��r✓.o�r���.�i:�;r�,3.�:�,cry�f;;�rr,>��.�s✓�iY.ti��✓✓✓���.s3,���n:z:�,�,3�:y .��y3�r.���rs�,�i.��,3r3m�Y.sss,.,�sr�,;.w✓.�s.�.�..3✓,���,�.3�.c..Y✓m.�✓�3Yr.:;���fr a+;.�-:�✓;��..ssr�.s�.�nr�� PATH 9 FROM HYDRAULIC REFERENCE 55 TO 63 26. 97 1. 049 1E 1. 00 23.2 23 .2 K = 5. 60 55S C=120 2 . 00 -0. 4 0. 0 26. 97 0. 226 3 . 00 0. 7 23 .2 Vel = 10. 11 1. 049 1T 2 . 02 23. 4 23. 4 EqK = 5 .57 55 C=120 5 . 00 0.0 0. 0 26. 97 0.226 7 . 02 1. 6 23. 4 Vel = 10. 11 63 26. 97 25 . 0 K = 5 .39 �✓✓HX,d3�Y✓✓l✓r�?+9P3P✓'IY.3Y�✓i;'%PYA✓i93✓/✓J✓.+P✓Jrlt,3.+,^✓✓✓✓,+.+iI✓✓,Y,59✓✓,if✓,Y✓AiY✓/✓b�.+Y✓✓✓�:3Y✓.+,:9;Y'Y�i✓✓✓✓✓✓lS3iYi:Y✓J9Y✓✓✓JY✓✓/G'✓�3fiY✓rYrY,Yr"r3`✓,`✓,3F✓✓.Yi 33Y✓d3Y✓r;YJ.33Y,Y✓''.Y✓H✓✓�;3:i"3.'�✓✓J,7.3Y,7%/✓.Y✓l✓✓:3'w'.'Y✓✓✓✓/.3Y✓/•Y✓H✓.Y•rYri53'✓A'�i.�A�ti�,c UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) Job Water Required Hose Allowance VCA Static Pressure: 115.0 psi Pressure: 41.6 psi Inside: 0 gpm 209 Earle Street Residual Pressure: 80.0 psi System Flow: 227 gpm Outside: 100 gpm Northampton, MA Flow: 620 gpm System+Hose: 327 gpm Remote Area: 4 Date: 6/20/02 Safety Pres: 62.7 psi Loc: Earl street at Smith Coll Head Elev Pres: 29.0 psi 140 ii 120 Su I — f 100 P 80 S I I 60 40 100 gpm hose 9.0 psi 20 - 100 150 200 250 300 350 400 450 50( Flow (gpm)