38A-061 (15) Phvsical Plant Department
Smith College
Northampton,Massachusetts 01063
(413)5135-2400 FAX(413)585-2444
October 25, 1994 �5
1
LJ i G
Mr. Frank Sienkiewicz DEPT
Building Inspector �
City of Northampton
210 Main Street
Northampton, MA 01060
Dear Mr. Sienkiewicz:
Enclosed, please find the sprinkler test results for the Smith College Riding
Stables. The hydrostatic test was performed by Warehouse Mechanical
Contractors, Inc. The test was witnessed by David Bean, Warehouse Mechanical,
Ed Everett, City of Northampton Building Inspectors representative and Frank
Perman on October 24, 1994. The test encompassed the newly installed dry
sprinkler system in its entirety.
Hydrostatic Test Results
Start Time 11:00 am 205 PSI
Finish 1:00 pm 205 PSI
If you require more information regarding this test, please contact me.
Sincerely,
Frank C. Perman
Plumbing Supervisor
FCP/gh