05-028 (9) J12/28/2004 23: 43 4135257023 EAV STATE SPRINKLER PAGE 02 6 BAY STATE SPRINKLER CO. I NC. 560 PARKER ST.—East Longmeadow, MA. 01028 —413-536-6261 —fax 413-525-7023 December 27, 2004 Hampshire Care Attn: Charlie 222 River Rd, Leeds, Ma. 01053 RE: Impaired Sprinkler System. Dear Charlie: Enclosed is a copy of the letter we received from Rybak Engineering, Inc. as to the status of your automatic sprinkler system. As suspected and discussed during our last quarterly inspection, it is now both Our and Rybak Engineering's opinion, the sprinkler system must be considered fully impaired and no.n operational until the water tank or water supply is restored to it's original condition. Steps should be taken, immediately to address this problem and a plan should be put into place in the interim. I spoke to Deputy Chief Nichols about this situation on 12/28/04 and have forwarded him a copy of this letter. Thank you for the opportunity to be of service to you, if you have any questions or we can be of any additional service please don't hesitate to call. Yours Truly, Bay State Sprinkler Co., Inc. ,Tart J_ Gwozdzik JJG/dmg Cc: Northampton.Fire Department (Attn: Deputy Chief Nichols ) 26 Carlon Dr. Northampton, MA. 01060 Fire Protection Contractor since 1977 112/28/2004 23:43 4135257023 BAY STATE SPRINKLER PAGE 03 From;Of11ee To;ion OwozMk Date:1212212004 Tlme;2:41:34 PM PAge 2 of 2 S Ls s� Rybak Engincering, Inc. Fire Prorectlon Cone+lranrs 132 Forest Avenue Warren,MA 01 083-0709 (413)436-5500• Fox 476-5,567 December 22,2004 Jan Gwozdzik 6aystate Sprinkler Company 27 Labrie Lane Holyoke, MA 01040 RE: Hampshire Care, 222 Rivers Road, Leeds, MA 01053 Pursuant to your conccm for the status of the sprinkler system at this address-I visited the site on 12/21/04 to obtain information regarding the water supply and the sprinkler system. It is my professional opinion that the sprinkler system must be considered fully impaired and not operational until the water tank/water supply is restored to it's original operating condition. This opinion is based on analysis of the following: a. Water tank on site is out of service b. Static pressure varies greatly with domestic demands(20 psi static pressure fluctuations) c_ Water hydrant flow as observed by Baystate Sprinkler d. Hazard classification of occupancy(includes kitchen/mechanical) e. Elevation of site and distance to alternate water supply f: Existing pipe sizing g. Existing standard response sprinklers. i understand that you intend to inform the owner and fire department of this condition. Sincerely, a'�� Carl C.Koslowski,P.E. Fire Protection Engineer 1 1 Page 1 of 1 hempshire c9re,doc