17B-007 (4) } l
O.C. 'a 7J ".if
154 1
vo
rte• �U�a �L.���
'�....»...�...... �,,,,t'�-; •mow`...-»�'�-�� ,
�" 11� `. �'E.„E7�,,�I�: "'"~�w�'�"�'""�'£'��..,�v:t'��p Q-�'i'' '�''`�,;,,•. .�,w -�;,...,z.. , t
erg-ve:»+:•••' �. u,.•,...:-�+.rr.�+...:...-•»e-•w.•..�•�•••,..nN.....�,...,...,1�_�.,..,....+•..•�.w........�,•.-.........-. ._.. .. .. . ... .... ......»«- i � .....W.�:,:-..
---
+��= Date: 1/18115
Entire House By: Jeff
Project Information
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Design Conditions
Location: Indoor: Heating Cooling
Springfield Westover AFB, MA, US Indoor temperature (°F) 72 75
Elevation: 190 ft Design TD(°F) 72 12
Latitude: 42°N Relative humidity(%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 54.5 24.1
Dry bul b(°F) 0 87 Infiltration:
Dailyrange(°F) - 19 ( M )
Wet bu I b(°F) - 71
Wind speed(mph) 15.0 7.5
Front Door North Northeast East Southeast South Southwest West Northwest
Sensible Load(Btuh) 11810 12826 12709 12719 11689 12719 12709 12814
Latent Load (Btuh) 2132 2168 2166 2166 2131 2166 2166 2168
Total Load (Btuh) 13942 14994 14875 14885 13820 14885 14875 14982
Heating AVF(cfm) 635 690 684 684 628 684 684 689
Cooling AVF(cfm) 635 690 684 684 628 684 684 689
Building Orientation Coding Load
1
1
0
N NE E SE S SW W NW
Ckecbm Front Dom faces
Current Orientation: Front Door faces North
Highest Cooling Load: Front Door faces Northeast
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�a
2015-Jan-2019:58:21
`., wrightsoft Right-Suite®Universal2012 12.1.05 RSU18116
Page 1
x. ,. �...«.. ........ ...... Date: 1/18/15
Entire House By: Jeff
4
Project
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Design Information
Htg Cig Infiltration
Outside db (°F) 0 87 Method Simplified
Inside db(°F) 72 75 Construction quality Semi-tight
Design TD(°F) 72 12 Fireplaces 0
Daily range - M
Inside humidity(%) 50 50
Moisture difference(gr/lb) 55 24
HEATING EQUIPMENT COOLING EQUIPMENT
Make YORK Make YORK
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 95.5 AFUE Efficiency 13 SEER
Heating input 0 MBtuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 635 cfm Actual air flow 635 cfm
Air flow factor 0.028 cfm/Btuh Air flow factor 0.049 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.86
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ftz) (Btuh) (Btuh) (cfm) (cfm)
Master Bed&Bath 314 8426 4484 235 222
Kitchen-Dining 574 10126 6194 283 306
Laundry-Foyer 88 4170 2160 116 107
Entire House d 975 22722 12837 635 635
Other equip loads 0 0
Equip. @ 0.92 RSM 11810
Latent cooling 2132
TOTALS 975 22722 13942 I 635 I 635
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2015-Jan-20 19:58:21
wrightsoft Right-Suite 8Universal201212.1.05RSU18116 Pagel
Level 1
Master Bed Ba'
Kitchen-Dinii
Laundry-Foy
Job#: 7890 Scale: 1 : 87
Performed by Jeff for: Page 1
New Residence 448 Bridge Road Florence RightSuite®Universal 2012
12.1.05 RSU18116
Entire House v1wio
By: Jeff
1 Room name Kitchen-Dining Laundry-Foyer
2 Exposed wall 73.5 it 32.0 it
3 Room height 8.0 it heat/cool 8.0 it heat/cool
4 Room dimensions 20.5 x 28.0 ft 12.5 x 7.0 ft
5 Room area 574.0 ft' 87.5 ft2
T Construction t-value Or HTM Area ft' Load Area ft' Load
Y I ( ) I ( )
number (Btuhlft'-°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool
6 V 12E-0sw 0.068 n 4.90 1.01 164 110 539 111 100 85 416 86
4A4-20c 0.470 n 33.84 14.24 12 0 406 171 15 0 508 214
11 JO 0.600 n 43.20 1440 42 42 1814 605 0 0 0 0
12E-0sw 0.068 a 4.90 1.01 168 138 676 140 56 56 274 57
11 4A4-2oc 0.470 a 33.84 47.89 30 0 1015 1437 0 0 0 0
12E-Osw 0.068 s 4.90 1.01 164 140 685 142 100 64 313 65
4A4-2oc 0.470 s 33.84 25.18 24 0 812 604 15 0 508 378
11,10 0.600 s 43.20 14.40 0 0 0 0 21 21 907 302
Vr/ 12E-Osw 0.068 w 4.90 1.01 92 92 450 93 0 0 0 0
I_{; 4A4-2oc 0.470 w 33.84 47.89 0 0 0 0 0 0 0 0
C 16B-38ad 0.026 1.87 1.24 574 574 1075 709 0 0 0 0
C 168-38ad 0.026 1.87 1.24 0 0 0 0 88 88 164 108
F 19A-19cswp 0.049 2.76 0.46 0 0 0 0 88 88 242 40
F 19C-19bswp 0.049 1.22 0.20 574 574 702 117 0 0 0 0
61 c)AED excursion 1 -312 -21
Envelope loss/gain 1 8174 3817 1 1 3332 1229
12 a) Infiltration 1456 125 634 55
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 4 920 1 230
Appliancesiother 1200 600
Subtotal(lines 6 to 13) 9631 6062 3966 2114
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 9631 6062 3966 2114
15 Dud loads 5% 2% 495 132 5% 2% 204 46
ATotal room load
required(cfm) ( I I 102831 63061 I 1 4116 1 2107 1
Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed.
-nrt wriohtsoft _ 2015-Jan-2019:58:22
Entire House Ud1e; "101"
By: Jeff
1 Room name Entire House Master Bed&Bath
2 Exposed wall 160.0 ft 54.5 ft
3 Room height 8.0 ft d 8.0 ft heat/cool
4 Room dimensions 19.0 x 16.5 ft
5 Room area 975.0 ft2 313.5 ft'
Ty Construction U-value Or HTM Area (f t') Load Area (f t') Load
number (Btuh/f t'-°F) (Btuh/ft') I or perimeter (ft) I (Btuh) I or perimeter (ft) I (Btuh)
Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool
6 Y 12E-0sw 0.068 n 4.90 1.01 416 332 1625 336 152 137 671 139
4A4-2oc 0.470 n 33.84 14.24 42 0 1421 598 15 0 508 214
11 JO 0.600 n 43.20 14.40 42 42 1814 605 0 0 0 0
12E-0sw 0.068 a 4.90 1.01 224 194 950 197 0 0 0 0
11 4A4-2oc 0.470 a 33.64 47.89 30 0 1015 1437 0 0 0 0
12E-0sw 0.068 s 4.90 1.01 416 299 1464 303 152 95 465 96
4A4-2oc 0.470 s 33.64 25.16 54 0 1827 1360 15 0 508 378
11J0 0.600 s 43.20 14.40 63 63 2722 907 42 42 1814 605
Vj/ 12E-0sw 0.068 w 4.90 1.01 224 194 950 197 132 102 499 103
I--' 4A42oc 0.470 w 33.64 47.89 30 0 1015 1437 30 0 1015 1437
C 16B-38ad 0.026 1.87 1.24 574 574 1075 709 0 0 0 0
C 16B-38ad 0.026 1.67 1.24 401 401 751 495 314 314 587 387
F 19A-19cswp 0.049 2.76 0.46 401 401 1109 185 314 314 867 144
F 19C-19bswp 0.049 1.22 0.20 574 574 702 117 0 0 0 0
61 c)AED excursion 01 1 1 1 333
Envelope lossigain 1 18440 6882 1 1 6934 3835
12 a) Infiltration 3170 273 1080 93
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 7 1610 2 460
Appliances/other 1800 0
Subtotal(lines 6 to 13) 21610 12564 8013 4388
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 21610 12564 8013 4388
15 Duct loads 5% 2% 1112 273 5% 2% 412 95
Total room load 22722 12837 8426 4484
Air required(cfm) I 1 635 I I 1 235 1 222 1
Calculations approved by ACCA to meet all reauirements of Manual J 8th Ed.
�'1+ wriol,ttsolFt _ a.. __._ ._ __ _ ..._.._ 2015-Jan-20 19:58:22
�. v 0 vauz: vtwto
Entire House By: Jeff
Project Inf• •
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Design Conditions
Location: Indoor: Heating Cooling
Springfield Westover AFB, MA, US Indoor temperature(°F) 72 75
Elevation: 190 ft Design TD(°F) 72 12
Latitude: 42'N Relative humidity(%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 54.5 24.1
Dry bulb(T) 0 87 Infiltration:
Dailyrange (°F) - 19 ( M ) Method Simplified
Wet bulb(°F) - 71 Construction quality Semi-tight
Wind speed(mph) 15.0 7.5 Fireplaces 0
Heating
Component Btu h/112 Btuh %of load
Walls 4.9 4989 22.0
Glazing 33.8 5279 23.2
Doors 43.2 4536 20.0
Ceilings 1.9 1825 8.0
Floors 1.9 1811 8.0
Infiltration 2.5 3170 14.0
Ducts 1112 4.9
Piping 0 0
Humidification 0 0
Ventilation 0 0
Adjustments 0
Total 1 227221 100.0
Component Btu h/11? Btuh %of load
Walls 1.0 1032 8.0 Wal
Glazing 31.0 4831 37.6 nternal Gains
Doors 14.4 1512 11.8
Ceilings 1.2 1204 9.4
Floors 0.3 302 2.4
Infiltration 0.2 273 2.1
Ducts 273 2.1 Glaa uds
Ventilation 0 0 nfittration
Internal gains 3410 26.6 Floors
Blower 0 0
Adjustments 0 Ceilings
Total 1 1 128371 100.0 O0rs
Latent Cooling Load=2132 Btuh
Overall U-value=0.086 Btuh/ftz--°F
Data entries checked.
wri htsOft 2015-Jan-2019:58:22
9 Right-Suite®Universal 2012 12.1.05 RSU18116 Page 1
ettingsljeff.baird\My Documents\Wrightsoft HVAC\ROCKVALLEY.rup Calc=MJ8 Front Door faces:
+ :. . ...r--•-••- -- -- ------••- Date: 1/18/15
Entire House By: Jeff
Project Information
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Design Conditions
Location: Indoor: Heating Cooling
Springfield Westover AFB, MA, US Indoor temperature(°F) 72 75
Elevation: 190 ft Design TD(°F) 72 12
Latitude: 42°N Relative humidity (%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 54.5 24.1
Dry bulb(°F) 0 87 Infiltration:
Dailyrange(°F) - 19 ( M ) Method Simplified
Wetbulb(°F) - 71 Construction quality Semi-tight
Wind speed (mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuhrt2--°F T-°F/Btuh Btuh/W Btuh Btuh/W Btuh
Walls
12E-Osw:Firm wall,wd ext, 1/2"wood shth,r-19 cav ins, 1/2" n 332 0.068 19.0 4.90 1625 1.01 336
gypsum board int fnsh,2"x6"wood frm a 194 0.068 19.0 4.90 950 1.01 197
s 299 0.068 19.0 4.90 1464 1.01 303
w 194 0.068 19.0 4.90 950 1.01 197
all 1019 0.068 19.0 4.90 4989 1.01 1032
Partitions
(none)
Windows
4A4-2oc:2 glazing,clr outr,air gas,clad wd frm mat,clr low-e innr, n 42 0.470 0 33.8 1421 14.2 598
1/4"gap, 1/8"thk a 30 0.470 0 33.8 1015 47.9 1437
s 54 0.470 0 33.8 1827 25.2 1360
w 30 0.470 0 33.8 1015 47.9 1437
all 156 0.470 0 33.8 5279 31.0 4831
Doors
11X Door,mtl fbrgl type n 42 0.600 6.3 43.2 1814 14.4 605
s 63 0.600 6.3 43.2 2722 14.4 907
all 105 0.600 63 43.2 4536 14.4 1512
Ceilings
16B-38ad:Attic ceiling,asphalt shingles roof mat,r-38 ceil ins, 1/2" 574 0.026 38.0 1.87 1075 1.24 709
gypsum board int fnsh
16B-38ad:Att ic ceiling,asphalt shingles roof mat,r-38 ceil ins 401 0.026 38.0 1.87 751 1.24 495
Floors
19A-19cswp:Fir floor,frm fir, 12"thkns,hrd wd fir fnsh,r-19 cav 401 0.049 19.0 2.76 1109 0.46 185
ins,tight crwl ovr
19C-19bswp:Fir floor,frm fir,12"thkns,hrd wd fir fnsh,r-19 cav 574 0.049 30.0 1.22 702 0.20 117
ins,tight bsmt ovr,r-11 wall insul
a Wr1 ftt5l1ft 2015-Jan-2019:58:22
9 Right-Suite®Universal 2012 12.1.05 RSU18116 Page 1
ettingsljeff.baird\My Documents\Wrightsoft HVAC\ROCKVALLEY.rup Calc=MJ8 Front Door faces:
- --- - ------...—.__ Date: 1/18115
Entire House By: Jeff
Project Inf• •
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Design Conditions
Location: Indoor: Heating Cooling
Springfield Westover AFB, MA, US Indoor temperature (°F) 72 75
Elevation: 190 ft Design TD(°F) 72 12
Latitude: 42°N Relative humidity(%) 50 50
Outdoor: Heating Cooling Moisture difference(gr/lb) 54.5 24.1
Dry bul b(°F) 0 87 Infiltration:
Dailyrange(°F) - 19 ( M )
Wet bu I b(o F) - 71
Wind speed (mph) 15.0 7.5
Test for • - • Exposure Diversity
Hourly Glazing Load
7,
4,
Uw-Z
Z000-
1,
0
8 9 10 11 12 13 14 15 16 17 18 19 27
Hard
/Hourly /#Average /AED limit
Maximum hourly glazing load exceeds average by 23.4%.
House has adequate exposure diversity(AED), based on AED limit of 30%.
AED excursion: 0 Btuh
t WPI hltsoft 2015-Jan-2019:58:22
9 Right-Suite®Universal 2012 12.1.05 RSU18116 Page 1
ACCA eftings\jeff.baird\My Documents\Wrightsoft HVAC\ROCKVALLEY.rup Calc=MJ8 Front Door faces:
V , - —a——- --- -------- i uate: intsn5
Entire House By: Jeff
Project Information
For: New Residence 448 Bridge Road Florence, Rock Valley HVAC
Notes:
Design Information
Weather: Springfield Westover AFB, MA, US
Winter Design Conditions Summer Design Conditions
Outside db 0 °F Outside db 87 °F
Inside db 72 °F Inside db 75 °F
Design TD 72 °F Design TD 12 °F
Daily range M
Relative humidity 50 %
Moisture difference 24 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 21610 Btuh Structure 12564 Btuh
Ducts 1112 Btuh Ducts 273 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 22722 Btuh Use manufacturer's data n
Rate/swing multiplier 0.92
Infiltration Equipment sensible load 11810 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Semi-tight
Fireplaces 0 Structure 1739 Btuh
Ducts 393 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft� 975 975 Equipment latent load 2132 Btuh
Volume(ft� 7800 7800
Air changes/hour 0.31 0.16 Equipment total load 13942 Btuh
Equiv. AVF(cfm) 40 21 Req.total capacity at 0.70 SHR 1.4 ton
Heating Equipment Summary Cooling Equipment Summary
Make YORK Make YORK
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 95.5 AFUE Efficiency 13 SEER
Heating input 0 MBtuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 635 cfm Actual air flow 635 cfm
Air flow factor 0.028 cfm/Btuh Air flow factor 0.049 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.86
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
w. Wrl htsoft Rig 12.1.05 RSU18116 2015-Jan-2019:58:22
Paae 1
INSURANCE COVERAGE:
I have a current liability insurance policy or its equivalent which meets the requirements of M.G.L.Ch. 112 Yes❑ No❑
If you have checked Yes,indicate the a of coverage by checking the appropriate box below:
A liability insurance policy Other type of indemnity ❑ Bond ❑
OWNER'S INSURANCE WAIVER: 1 am aware that the licensee does not have the insurance coverage required by Chapter 112 of the
Massachusetts General Laws,and that my signature on this permit application waives this requirement.
Check One Only
Owner ❑ Agent ❑
Signature of Owner or Owner's Agent
By checking this box[],I hereby certify that all of the details and information I have submitted(or entered)regarding this application are true and
accurate to the best of my knowledge and that all sheet metal work and installations performed under the permit issued for this application will be
in compliance with all pertinent provision of the Massachusetts Building Code and Chapter 112 of the General Laws.
Duct inspection required prior to insulation installation:YES NO
Progress Inspections
Date Comments
Final Inspection
Date Comments
Type of License:
By ❑ Master
Title
❑ Master-Restricted
CitylTown
❑Journeyperson Signature of Licensee
Permit#
❑Journeyperson-Restricted License Number:
Fee$ ❑
Check at www.mass.gov/dpi
Inspector Signature of Permit Approval
t.ommonweann of inassacnusens
JAN 2 3 Sheet Metal Permit
/J
Electric P urr Permit# C�
Noriira ,p a�.F:F,
Estimated Job Cost: $ Permit Fee:
Plans Submitted: YES ENO Plans Reviewed: YES NO
Business License# ;2-6;Lk Applicant License #
Business Information: Property Owner/Job Location Information:
Name: (4- UG I I e 9 `- Name:
Street: 7 ?9e,--l-e wocA c kj Street:
City/Town: - i y ya City/Town:
Telephone: (gl 3 3- = �-g r `/ Telephone:
Photo I.D. required/Copy of Photo I.D. attached: YES b,-�&O
Staff Initial
J-1 unrestricted license
J-2 /M-2-restricted to dwellings 3-stories or less and commercial up to 10,000 sq. ft. /2-stories or less
Residential: 1-2 family Multi-family Condo/Townhouses Other
Commercial: Office Retail Industrial Educational
Institutional Other
Square Footage: under 10,000 sq. ft. 1-1-�over 10,000 sq. ft. Number of Stories:
Sheet metal work to be completed: New Work: Renovation:
HVAC Metal Watershed Roofing Kitchen Exhaust System
Metal Chimney/Vents Air Balancing
Provide detailed description of work to be done:
c_ %- t..l !J ., i 7 f r i+v►'e.-.C kr-lf-
File#SM-2015-0028
APPLICANT/CONTACT PERSON ROCK VALLEY HVAC
ADDRESS/PHONE 7 APPLEWOOD LN (413)535-7804
PROPERTY LOCATION 448 BRIDGE RD
MAP 17B PARCEL 007 001 ZONE RI(100)/RR(100)
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid
Building Permit Filled out
Fee Paid
Typeof Construction: DUCTWORK FOR ACCESSORY APARTMENT&LAUNDRY ROOM TO EXISTING
HOUSE
New Construction
Non Structural interior renovations
Addition to Existing
Accessory Structure
Buildiniz Plans Included:
Owner/Statement or License 2626
3 sets of Plans/Plot Plan
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INFOJWATION PRESENTED:
Approved Additional permits required(see below)
PLANNING BOARD PERMIT REQUIRED UNDER: §
Intermediate Project: Site Plan AND/OR Special Permit with Site Plan
Major Project: Site Plan AND/OR Special Permit with Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received&Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
lM Street Co ssion Permit DPW Storm Water Management
or 111,11,1111111111
Si a of Bui i ial Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health,Conservation Commission,Department
of public works and other applicable permit granting authorities.
*Variances are granted only to those applicants who meet the strict standards of MGL 40A.Contact the Office of
Planning&Development for more information.
448 BRIDGE RD SM-2015-0028
COMMONWEALTH OF MASSACHUSETTS
CITY OF NORTHAMPTON
GIS#: 1618
Map: 17B
Block: 0
Lot: 001 01 SHEETMETAL PERMIT
„�.,.
Permit: SHEETMETAL
Category: SHEETMETAL
Permit'# SM-2015-0028 PERMISSION IS HEREB Y GRANTED TO:
Project# JS-2015.000013
Est.Cost: Contractor: License: Expires:
Fee Charged:$25.00 ROCK VALLEY HVAC Sheetmetal-2626 04/28/2016
Balance Due:$.00 Owner: SPEIGHT MAUREEN M
#of Fixtures Applicant: ROCK VALLEY HVAC
DigSafe# __ AT. 448 BRIDGE RD
�UseGroup
ConstClass
ISSUED ON. 23-Jan-2015 AMENDED ON. EXPIRES ON.
TO PERFORM THE FOLLOWING WORK:
DUCTWORK FOR ACCESSORY APARTMENT&LAUNDRY ROOM TO EXISTING HOUSE
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Signature:
Fee Type: Receipt No: Date Paid: Check No: Amount:
Sheetmetal REC-2015-002926 23-Jan-15 558 $25.00
212 Main Street,Ph one:(413)587-1240,Fax:(413)587-1272,Email:lhasbrouck @northamptonma.gov
GeoTMSO 2015 Des Lauriers Municipal Solutions,Inc.