Loading...
23B-074 (2) Engineer/License Holder Charles P Bonicker Trinity Heating&Air, MOUNTED TO ROOF Inc OBA Trinity Solar SOLAR MODULES MOUNTED TO ROOF ON 1 ARRAY UNDER SOLAR MODULE 2211 Allenwood Rd.Wall,NJ 07719 23 255W MODULES W/1 SOLAR EDGE P300 PER MODULE NEC 690.39 IBIS ADC MAX PER STRING - 1 STRING OF 11 MODULES N SERIES-350 1— 1STRNG OF.MODULESRNSERES RSa Vmax '251 RINGS TO BE TEE RMNATED IN PARALLEI INSIDE INVERTER S JUNCTION C• BOx BO% Issued/Revisions EXISTING 120/240V p UTILITY METER 240V To N0. DESCRIPTION DATE 200A MAIN BREAKER 200A BUSBAR Project Title: DOSTAL,STEPHEN ARMY CIRCUIT WIRING NOTES ))2p200A TRINIIYACCT R:7014-41439 PRODUCTION COMPLIES WITH 3011 NEC - METER 60A UNFUSED UTILITY DISCONNECT Project Address: 1.)LOWEST EXPECTED AMBIENT TEMPERATURE BASED ON _ INVERTER Y1 ASHRAE MINIMUM MEAN EXTREME DRY BULB - 240V 10 TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT - _—d+ 88 SOUTH MAIN STREET TEMP -I6'C 2p30A FLORENCE,MA 01062 2.)HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED a `- ON ASHRAE HIGHEST MONTH 2%DRY BULB y r __ ____ B ___ D n E a TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO L1 L2 N DfaWing Title: INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMP= - _ Z 33c � _� PROPOSED 5.865kW EXISTING MAIN BREAKER LOAD CENTER SQUARE D SOLAR SYSTEM 3.)2005 ASHRAE FUNDAMENTALS 2%DESIGN 2p3OA BACK FEED BREAKER PN D222RR _..._ _. -.. TEMPERATURES DO NOT EXCEED 47T IN THE UNITED NEC 690.64 STATES(PALM SPRINGS,CA IS 44.1-C). FOR LESS THAN -- Dfawin Information 9 CURRENI-CARRYING CONDUCTORS IN A R DOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5"ABOVE DRAWING DgiE. 1z/3/2014 ROOF AND'USING THE OUTDOOR DESIGN TEMPERATURE nRAWN Rr. Ic OF 47'C OR LESS(ALL OF UNITED STATES), RFVrsFD Rr. a_)PHOTOVOLTAIC POWER SYSTEMS SHALL RE PERMITTED TO OPERATE WED UNGROUNDED S tem Information: PHOTOVOL AIC SOURCE AND OUTPUT CIRCUIT AS PER ODUt 865kW NEC 690.35 M E 5R£.DTA COUNT 5.)ALL EDOORMEN INSTALLED OUTDOORS SHALL HAVE MnGL—LIN. CANADIAN SOLAR 255 A NEMA3 RATING. MODULE SPEC p. CS6P-255P v NAIL GRID CALCULATIONS FOR CURRENT CARRYING UTILITY ACC*rPN 3826660 ao1 CONDUCTORS uilurY METER n: 432430.0.9 REQUIRED CONDUCTOR AMPACITY PFR STRING [NEC690.6(6)(1)} (15.00.1.25)1 -18.75A nEAETYPC: AWG//10,DEBATED AMPACITY AMENT TEMP: 55'C,TEMP DERATNG FACTOR: 76 PV MODULE SPECIf1CABONS RBIACEWAY DERAIING=4 CCC: 0.80 (40176)0.80=24.32A CANADIAN SOLAR 255(CSIP-255P) Rev.ND. Sheet 24.32A'18.75A,THEREFORE WIRE S17E IS VALID Imp 8.43 Vmp 37.2 P 1 PV - 3 TOTAL AC REQUIRED CONDUCTOR AMPACITY TOM IN ps THn-2 GEC Tn EXISTING GROUND ROD 23.00A-1.25= 28.750. R 0 1"EMT W/3410THWN-2,1-a1DTHWN-2 GROUND AWG 0.10,DER ATED AMPACITY AMBIENT TEMP: 30'C,TEMP DER TING 1.0 INVERTER pI,SESOOOA-US 1"EMTW/4-p10THWN-2,148THWN 2GROUND RACEWAY DEBATING i 3 CCC'. N/A • 40A"1.0-40A DC AC L"EMT W/4410 THWN 2,1 I THWN 2GROUND 40A'28.75A THEREFORE AC WIRE SIZE IS VALID Imp 16.76 Pout 5000 E T'EMTW/3-a1DTHWN-2,1-R10THWN ROUND Vmp 350 lout 23 p p12RVWIREABI R RARE COPPER RONDTOMOOULEZgrvDRARZ SOLAR CALCULATION FOR PU O9ERCURRENT PROTECTION Voc 500 28.25 TO'AL INVERTER CURRENT: 2G CA 23.008.1.15=28./50. 240 -->30A QVERCURRENT PROTECTION IS VALID �AR 1—Rnad an-`9'-292e wall.N.v.Irtxy0T2t0 S'-2' NEW PV SOLAR MODULE,TYPICAL UNIRAC CLAMP U.O.I. (REFER TO EQUIPMENT SCHEDULE ­1 SPEC SHEET Vol OFTNLs Engineer l License Holder: FOR SPECS AND OUANTITIESI NEW MOUNTING FOOT/ATTACHMENT SOLAR MODULE SOLAR MODULE POINTS,TYPICAL (REFER TO E_ _ ___ ENGINEERING LETTER FOR SPACING AND DETMLSI L' UNIRAC SOLAR MOUNT BEAM _ P NEW UNIRAC RAIL,TYPICAL UNIRAC' fsEE SPEC SHEET FOe OETNLS (REFER TO THE UNIRAC IsEE PEC SHEET EDRDFOETAas OT PHALT SHINGLES ONE LAYER AS 4 CODE-COMPLIANT INSTALLATION S NMODO FLASHING lSEE ENDINEEes IETTEa FOe"CS c]A MANUAL FOR SPECS AND DETAILS) Is. JFORpETMLS APOC SEALANT ; �cl NEW END CLIP,TYPILAL PaP PSTAAS (REFER TO THE UNIRAC CODE-COMPLIANT INSTALLATION MANUAL 3.2.5 FOR SPECS AND -- -- --- ---- --- DETAILS) EXISTING RAFTER SOLAR MOD PEAK SHALL HEIGHT.OT NEW MID CLIP.TYPICAL 'HE'. 1—Rr.TR`—IICA-' (REFER TO THE UNIRAC CODE-COMPLIANT INSTALLATION MANUAL 3.2S FOR SPECS AND ATTACHMENT 8 CLIP DETAIL .—LER "Pu MODULE ATTACHMENT ON ASPHALT SHINGLE ROOF []HEIGHT FROM GROUND LEVEL TO PEAK OF ROOF scAIE:NOT TO SCALE SL LE NOT TO SCALE LJ sole NOT TO SCALE Issued I Revisions DC AC P D M EP NO. DESCRIPTION DATE Project Title: DOSTAL,STEPHEN TPINIry ACCT b:NUM-A 2639 Project Address: 1 - 88 SOUTH MAIN STREET Y f I i 'i FLORENCE,MA 01062 z C Drawing Title: �; 'I.I SOLAR SYSTEM j Drawing Information DRAWING DATE, 1t/3/EOI9 DRAWN 81 y .1. )C System Information: TOTAI SYSTEM SIZE: i 5.86SFW TOTAL MODULE COUNT:123 MODULES USED: 1 CANADIAN SOLAR 2SS DULL SPEC N: 6P-255P AT'L GRID UrIL11 All 1:NY 8]6660005 UTILITY METER 1: 9329159a NOTES: DEAL TYPE: I ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS. 2.)ALL OUTDOOR EQUIPMENT SHALL BE MIN TIGHT WITH MINIMUM NEMA 3R RATING. 3.)ALL LOCATIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION, 9.1 ALL EQUIPMENT INSTALLED OUTDOORS SHALL NAVE A NEMA J RATING Rev.No. Sheet 6J ROOFTOP SOLAR INSTALLATION ONLY PV ARRAY WILL NOT EXTEND BEYOND THE EXISTING PUILDING ENVELOPE �] ARRAY SCHEDULE SYMBOL LEGEND PLUMBING SCHEDULE EQUIPMENT SCHEDULE RI INDICATES ROOF DESIGNATION.REFER TO INDICATES NEW UTIL DISCONNECT TO BE NEW END CLIP,TYPICAL(REFER TO THE I INIRAC OTV SPECb Rt CODE-COMPLIANT INSTALLATION MANUAL ---- ANDULEPICH ORIENTATION-199.J' pRMYSCHEDULEFOR MORE INFORMATION INSTALLFOOUTSIDE ® SECTION 32.5 FOR SPECS AND DETAILS) 13 CANADIANSO]AR 255 tCS6P-25SPI MODULE PITCH .1' INDICATES NEW Pv Sol AR MODULE.HE.O MODULES NEW MID CLIP,TYPICAL(REFER TO THE UNIRAC 1 SE50p0A.U5 M INDICATES EXISTING METER LOCATION ,Iii INDICATE PANELS THA USE MICROR GUFRS. ® CODE-COMPLIANT INSTALLATION MANUAL `— REFER TO EQUIPMENT iCHEDULE FOR SPECS. SECTION J.2.5 FOR SPECS AND DETAILS) OTHER OBSTRUCTIONS INDICATES EXISTING ELECTRICAL PANEL INDICATES NEW PROD CTION METER TO BE NEW UNIRAC RAIL.TYPICAL ingy EB --- (REFER TO THE UNIRAC CODE—MPLIANT SOLAR LOCATION:IN BASEMENT INSTALLED IN BASEMEN ]MST ALLATION MANUAL FOR SPECS AND DETAILS) IN PLUMBING DESIGNATION.HEFEfl TO INDICATES NEW R E0.TO SE NEW MOUNTING FOOT)FOR POINTS, A PLUMBING SGHEWLE FOR DETAILS MSTALLED INBASEME N. TYPICAL (REFER TO ENGINEERING LETTER FOR bem.o dR.J BZJ 9)-i0>b REFER TO EQUIPMENT)CHEDULE FOR SPECS. SPACING AND DETAILS) W..R.N[\v In•cvBJ]19 �nv�vTHnirv-5olar.com Engineer/License Holder. INSTALLATION OF NEW ROOF MOUNTED SOUTH MAIN STREET. 5.865 kW PV SYSTEM 88 SOUTH MAIN STREET FLORENCE, MA 01062 Issued/Revisions VICINITY MAP SITE ND' mDESERIPTIpN DATE SCALE:NTS Project Title: DOSTAL,STEPHEN TRINITY ACCT 1:2014-424;9 Project Address: 88 SOUTH MAIN STREET FLORENCE,MA 01062 GENERAL NOTES GENERAL NOTES CONTINUED GENERAL NOTES CONTINUED ABBREVIATIONS CONTINUED SHEET INDEX B "IcTIONBox PV-1 COVER SHEET W/SITE INFO&NOTES Drawing rn_ THE INSTALLATION CONTRACTOR L P. THE DC VOLTAGE FROM THE PANELS IS 14. B CURRENT PREVAILING UTILITY kCMIL THOUSAND CIRCULAR MILS 1 ECU EM NI AN DR INSTA WING A ALL DISCONNECT ECT ENCLOSURE THE N STANDARDS COMPANY SPECIFICATIONS, EQUIPMENT AND INSTRUCTIONS TERMINAL$OF THE INVERTER THE OC ET F AND RED BEEN kVA KILOVOLT AMPERE PV'Z ROOF PLAN W/MODULE LOCATIONS PROPOSED 5.866kW CORINNE IN AND INSTRUCTIONS TERMINALS DOR$.INVERTER DURING 15 THISSETOFOR THE HAVE BEEN NW KILO-WATr SOLAR SYSTEM CONTAINED IN THE DRAWING PACKAGE AND DAYLIGHT HOURS.ALL PERSONS PREPARED FOR THE PURPOSE OF kWN KIL0.WATT HOUR PV-3 ELECTRICAL 3 LINE DIAGRAM INFORMATION RECEIVED FROM TRINITY, WORKING ON OR INVOLVED WITH THE MUNICIPAL AND AGENCY REVIEW AND L LINE 2.THE INSTALLATION CONTRACTOR IS PHOTOVOLTAIC SYSTEM ARE WARNED APPROVAL THIS SET OF FLANS SHALL NICE MAIN CIRCUIT BREAKER RESPONSIBLE FOR INSTALLING ALL THAT THE SOLAR rawin g In AR MODULES ARE NOT BE UTILIZED AS CONSTRUCTION MDP MAIN DISTRIBUTION PANEL formation EQUIPMENT AND FOLLOWING ALL ENERGIZED WHENEVER THEY ARE DRAWINGS UNTIL REVISED TO INDICATE MLO MAIN LUG ONLY DATF'. 12/3/2014 DIRECTIONS AN DINSTRUCTIONCONTAWED EXPOSED TO LIGHT. 'ISSUED FOR CONSTRUCTION', MID MOUNTED nRAWNBV'. IC INTHE CONPLETEMANUAL, 9. ALL PORTIONS OF THIS SOLAR 16 ALL INFORMATION SHOWN MUST BE MTG MOUNTIN B G FVISED BV: TH E INSTALLATION CONTRACTOR IS PROs DVOLTAIC SYSTEM SHALL BE CERTIFIED PRIOR TO USE FOR NEUTRAL RESPONSIBLE FOR READING AND MARK EDCLEARLYINACCORDANCEWITH CONSTRUCTION ACTMDIF1. NEC NATIONAL ELECTRICAL CODE UNDERSTANDING ALL DRAWINGS. THE NATIONAL ELECTRIC CODE ARTICLE NIC NOT IN CONTRACT COMPONENT AND INVERTER MANUALS 690. NON NUMBER System lnfomtation: PRIOR TO INSTALLATION.THE INSTALLATION 10. PRIOR TO THE INSTALLATION OF THIS ABBREVIATIONS NTS NOT TO SCALE TOTAL SVSiFM SIZE'. I E8 11,W CONTRACT OR IS ALSO REQUIRED TO HAVE PHOTOVOLTAIC SYSTEM,THE OCP OVERCURRENTPROTECTION iOiAt MOOUEECOUNi: I3 ALL COMPONENT SWITCHES IN THE OFF INSTALLATION CONTRACTOR SHALL AMP AMPERE P POLE USFO'. CANADIAN SOAR 255 POSITION AND FUSES REMOVED PRIOR TO ATTEND A PRE-INSTALLTION MEETING AC ALTERNATING CURRENT PB PULL BOX THE INSTALLATION OF ALL FUSES BEARING FOR THE REVIEW OF THE INSTALLATION AL ALUMINUM PH r PHASE WlF SPE[a: 6P-255P AF AMP.FRAME PVC POLY-VINYL CHLORIDE CONDUIT SYSTEM COMPONENTS. PROCEDURES,SCHEDULES,SAFETY AND MPA NATt I- 4.MO STHE PHOTOVOLTAIC MODULES ARE COORDINATION, AFF ABOVE FINISHED FLOOR PWR DOWER MOUNTED.THE INSTALLATION 11 PRIOR TO THE SYSTEM START UP THE A ABOVE FINISHED GRADE QTY -Al 11 AoCT p:NY 6660005 CONTRACTOR SHOULD HAVE A MINIMUM OF INSTALLATION CONTRACTOR SHALL AWG AMERICAN WIRF GAUGE RGS RIGIn GALVANIZED STEEL UTIUTY METED P. 43241EH ONE ELECTRICIAN WHO HAS ATTENDED A ASSIST IN PERFORMING ALL INITIAL C CONDUIT(GENERIC TERM OF SN SOLID NEUTRAL DFAI.TYPE. SO LARPHQTOVOLTAIC INSTALLATION HARDWARE CHECKS AND DC WIRING RACEWAY,PROVIDE AS JSWBDSWTTCHBOAflD COURSE ON SITE. CONDUCTIMT Y CHECKS. SPECIFIED) TYP TYPICAL 5.FOR SAFETY.IT IB RECOMMENDED BY THE 12. FOR THE PROPER MAINTENANCE AND CB COMBINER BOX U.O.I. UNLESS OTHERWISE INDICATED MANUFACTURE THAT THE INSTALLATION ISOLATION OF THE INVERTS REFER TO CKT CIRCUIT WP WEATHERPROOF CREW ALWAYS HAVE A MINIMUM OF TWO THE ISOLATION PROCEDURES F THE CT CURRENT TRANSFORMER %FMR TRANSFORMER CU COPPER ♦T2 RP.V,NO. Sheet PER50NS WORKING TOGETHER AND THAT OPERATION MAN UAL, DC DIRECT CURRENT MOUNT T2 INCHES TO BOTTOM EACH OF THE INSTALLATION CREW 13. THE LOCATION OF PROPOSED ELECTRIC DISC DISCONNECT RECTC CURRENT OF ABOVE FINISHED FLOOR OR MEMBERS BE TRAINED IN FIRST AID AND AND TELEPHONE UTILITIES ARE SUBJECT DWG DRAWING GRADE iHN. TO FINAL APPROVAL OF THE ELECTRICAL SYSTEM INSTALLER 6. IS SOLAR PHOTOVOLTAIC SYSTEM IS TO APPROPRIATE UTILITY COMPANNESAND EMT ELECTRICAL METALLIC TUBING BE INSTALLED FOLLOWING THE OWNERS. FS FUSIBLE SWITCH CONVENTIONS OF THE NATIONAL ELECTRIC 14. ALL MATERIALS.WORKMANSHIP AVID FU ELISE CODE.ANYLOCALCODEWHICHMAY CONSTRUCTION FOR THE WE G GROUND SUPERSEDE THE NEC SHALL GOVERN. IMPROVEMENTS SHOWN HEREIN SHALL GET GROUND FAULT INTERRUPTER 2,ALL SYSI EM COMPONENTS TO BE BE IN ACCORDANCE WITH'. HZ GROUND F V(CYCLES PER INSTALLED WITH THIS SYSTEM ARE TO BE N CURRENT PREVAILING MUNICIPAL SECOND} 'UL'LISTED,ALL EQUIPMENT WILL BE NEMA ANDOR COUNTY SPECIFICATIONS. 313 OUTDOOR RATED UNLESS INDOORS. STANDARDS AND REQUIREMENTS ni GENERAL NOTES SOLAR IF IS SUED DRAWING IS MARKED WITH A REVISION CHARACTER OTHER THAN'A',PLEASE BE ADVISED THAT FINAL EQUIPMENT ANDIOR SYSTEM CHARACTERISTICS ARE SUBJECT TO CHANGE DUE TO AVAILABLnY OF EQUIPMENT, 1111—nod I- 82?-292.2)26 W..II.N-1-11-19 www.Trinir2 Solar rom o� CanadianSolar Make The Difference ELECTRICAL DATA I STC MODULE ENGINEERING DRAWING Electrical Data CS613-250P C56P-2S5P CS6P-260P 'Rear View Nominal Maximum Power(Pmax) 250 W 255 W 260W Frame Cross Section Optimum Operating Voltage(Vmp) 30.1 V 30.2 V 30.4V I § Optimum operating Current(imp) 8.30A 8.43A 8.56A o Open Circuit Voltage(Voc) 37.2 V 37.4 V 37.SV ) Short Circuit Current(Isc) 8.87A 9.00A 9.12A Seti—,A-A Module Efficiency 15.54% 15.85% 16.16% j Operating Temperature -40°C-+85°C »1i Maximum System Voltage 1000V(IEC)/1000V(UL)/600V(UL) q Maximum Series Fuse Rating 15 A _-_-__ ! Application Classification Class A � i 0 Power Tolerance 0'°+S W v •Under Eta ndard Test conditions(STC)of irradiance of 1000W/m',spectrum AM 1.5 and cell temperature of 25°C. I ar 1 n ELECTRICAL DATA I NOCT 9 Electrical Data C56P-250P C56P-255P CS6P-260P i Nominal Maximum Power(Pmax) 181W 185 W 189W _ Optimum Operating Voltage(Vmp) 27.5 V 27.5 V 273V Optimum Operating Current(Imp) 6.60A 6.71 A 6.80A Open Circuit Voltage(Voc) 34.2 V 34.4 V 34.5V Short Circuit Current(Isc) 7.19A 7.29A 7.39A CS6P-255P I-V CURVES •Under Nominal Operating Cell To m pe rat u re(NOCT),irrad is nce of 800 W/m`,spectrum AM 1.5, - a m b i e nt tem pe ratu re 2OV,wind speed 1 m/s. 1e 10 MODULE I MECHANICAL DATA e e Specification Data 7 7 Cell Type Poly-crystalline,6inch 6 _s Cell Arrangement 60(6 x 10) g e Dimensions 1638x982 x40mm(64.5x38.7x1.57in) t5 t5 Weight 18.5kg(40.81bs) 0 4 4 Front Cover 3.2mm tempered glass 3 3 Frame Material Anodized aluminium alloy 1000w 1m2 111M Junction BOX IP67,3 diodes 2 800w/mz 2 ^—Cable 4mm'(IEC)/4mm'&12AWG1000V(UL100OV)/ 1 600W/m2 -12AWG(UL60OV),1000mm(650mm is optional) —aoo w/mz --o Connectors MC4orMC4comparable 0 5 10 15 20 25 30 35 40 o 5 10 15 20 se 40 45 Standard Packaging 24pcs,504kg(quantity and weight per pallet) Voltaga(V) Vaitaga(V) Module Pieces Per Container 672pcs(40'HQ) TEMPERATURE CHARACTERISTICS Specification Data Partner Section Temperature Coefficient(Pmax) -0.43%/aC Temperature Coefficient(Voc) -0.34%/°C Temperature Coefficient(Isc) 0.065%/°C Nominal Operating Cell Temperature 45+2°C PERFORMANCE AT LOW IRRADIANCE Industry leading performance at low irradiation, +96.5%module efficiency from an Irradiance of 1000W/m'to 20OW/m'(AM 1.5,25°C) As there are different certification requi ements rn different markets,please contact your sales representative forth c specific certificates applicable to your products.The specification and key features described in this Dotasheet may deviateslightly a,d,re,,t guaranteed.rDue too,-going thoo,ovah,research and product enhoncement,C,,adian Solorinc,r es the righttc make any adjustment to the information described herein atanyton without notice. Please always ab-,the most rerent vers,pn of the datasheet which.shall be tluly inrorporo red into the binding contract mad,by the parries governing a11 transactions related to the purchase and sale of the products described herein %okrCanadianSolar Make The Difference • • THE BEST IN CLASS Canadian Solar's modules are the best in class in terms of power output and long term reliability. Our meticulous product design and stringent quality control ensure our modules deliver an exceptionally high PV energy yield in live PV system as well as in PVsyst's system simulation.Our accredited in-house PV testing facilities guarantee all module component materials meet the highest quality standards possible. 'Blackframe product can be provided upon request. PRODUCT ( WARRANTY&INSURANCE PRODUCT i KEY FEATURES Power output 100% Added Value from Excellent module efficiency 97% m our limited up to 16.16% 9U% Industry Warranty Statement so% standard o% 5 10 15 20 25 High performance at low irradiance Years above 96.5% 25 Year Industry leading linear power output warranty 10 Year Product warranty on materials and workmanship Positive power tolerance up to 5w Canadian Solar provides 500%non-cancellable,immediate warranty insurance High PTC rating up to 91.96% PRODUCT&MANAGEMENT SYSTEM I CERTIFICATES* IEC 61215/IEC 61730:VDE/CE/MCS/JET/KEMCO/SI I/CEC AU/IN METRO/CQC/CGC UL 1703/IEC 61215 performance:CEC listed(US)/FSEC(US Florida) UL 1703:CSA I IEC 61701 ED2:VDE I IEC 62716:TUV I IEC60068-2-68:SGS Anti-glare module surface available PV CYCLE (EU) I UN19177 Reaction to Fire:Class 1 1509001:2008 1 Quality management system ISOTS16949:2009 I The automotive industry quality management system ISO14001:2004 I Standards for environmental management system IP67 junction box QC080000:2012 I The certificate for hazardous substances process management long-term weather endurance OHSAS18001:2007 I International standards for occupational health and safety d'E °_.$I C-R.,T c us( q � ;q Heavy snow load up to 5400pa *Please contactyour sales representativeforthe entire listof certificates applicable to your products CANADIAN SOLAR INC. Founded in 2001 in Canada,Canadian Solar Inc.,(NASDAQ:CSIQ)is the world's TOP 3 Salt mist,ammonia and blown sand solar power company.As a leading manufacturer of solar modules and PV project resistance,for seaside,farm and developer with about 6 GW of premium quality modules deployed around the world desert environment in the past 13 years,Canadian Solar is one of the most bankable solar companies in Europe, USA, Japan and China. Canadian Solar operates in six continents with customers in over 90 countries and regions. Canadian Solar is committed to providing high quality solar products, solar system solutions and services to customers around the world. o' o ti a mmmw Solar SolarEdge Power Optimizer Module Add-On for North America P300 / P350 P400 / P405 P300 P350 P400 P405 (for 60-cell modules) (for 72-cell module (for 96-cell modules) (for thin film modules) INPUT Rated Input DC Poweril) 300 350 400 405 W Absolute Maximum Input Voltage 48 60 80 (Voc at lowest temperature) 125 Vdc MPPT Operating Range i 8-48 8-60 8-80 12.5-105 1 Vdc 1 . ......... ....... Maximum Short Circuit Current(Isc) 10 Adc Maximum DC Input Current 12.5 Adc Maximum Efficiency 99.5 % ...... ... ... .................... ...... ... .... Weighted Efficiency 98.8 % 0 ve r volta ge Cate go or y -OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING INVERTER) Maximum Output Current 15 Adc Maximum O- utput Voltage 60 OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM INVERTER OR INVERTER OFF) Safety Output Voltage per Power Optimizer 1 Vdc STANDARD COMPLIANCE EMC FCC PartlS Class B,IEC61000-6-2,IEC61000-6-3 ........... ................... ...... Safety IE.C6.21.09.-,1.(.cI.ass,I1.s.afety.).,,IJ.L1.74'1.................... RoHS Yes IN-STALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc .......... ........ ....................... . . ... . .. .. ......... .. ...... ....... r—r....I Dimensions(W x L x H) 141 x 212 x 40.5 5.55 x 8.34 x 1.59 mm in Weight(Including lu din g cabI es) .......... ....... ........... 950/2.1 gr/lb Input Connector MC4 Amphenol .... ....... ........ MCA Output Wire Type/Connector Double Insulated;Amphenol Output ...........W i r e Length n gth 0.95/3.0 1 1.21 3 9 m/ft ,.Operating,Temperature Range ......401-.+8151-40.-+�18�5.. Protection Rating I P6 5 N EMA4 Relative Humidity 0 100 % I'�Rated STC power of the module.Module of up to+590 power tolerance allowed. PV SYSTEM DESIGN USING A SOLAREDGE INVERTER(2) SINGLE PHASE THREE PHASE 208V THREE PHASE 480V Minimum String Length 10 (Power Optimizers) 18 aximum ................. ...... ....... ...... ...... ..... . .. M String Length 25 (Power Optimizers) 25 50 Maximum Power per String 5250 6000 12750 W Parallel Strings of Different Lengths ci,r'Orientatiorls.. Yes It is not allowed to mix P405 with P300/P350/P400/P600/P700 in one string, rCE (Of 'C'Sciltt-Clge IMN1010gics,hic.All lights iesc�lcd.SOLARLUGL,kl�(?bf,�,,fLdgu loy _o,Dill�V�ZLD B)SULARLUGL tradcmaik�0­egi�lered tiadr,,,nd,ks of Sola,Ldgc loclmologjc�,hic.All(,thc.r liciew��w tradema,"of oArer_�,Uatc:01/2014 V.01.Suo'ect t') nmce. • solar=ee SolarEdge Power Optimizer Module Add-On For North America P300 / P350 / P400 / P405 • - � t s • s, i t PV power optimization at the module-level - Up to 25%more energy - Superior efficiency(99,5%) Mitigates all types of module mismatch losses,from manufacturing tolerance to partial shading — Flexible system design for maximum space utilization — Fast installation with a single bolt — Next generation maintenance with module-level monitoring — Module-level voltage shutdown for installer and firefighter safety USA - GERMANY - HALY FRANCE - JAPAN CHINA - ISRAEL - AUSTRALIA www.solaredge.us solar " • • Single Phase Inverters for North America SE3000A-US/SE3$OOA-US/SE500OA-US/SE600OA-US/ SE760OA-US/SE10000A-US/SE1140OA-US -- SE3000A_US SE3800A-US SE5000A US SE600DA US SE7600A US �SESOOOOA US SE11400A US OUTPUT ---------------- --�-5200 @ 208V 9980 @ 208V �- Nominal AC Power Output 3300 3840 6000 7680 Tl11520 VA 5520 @240V 1008' 0 @240V P f 1 .. 5600 @ 208V 10800 @ 208V Max.AC Power Output 3650 4150 0 @240V. 10950 @240V 6000 8350 12000 VA _.................................... ................� 600 . .._......... AC Output Voltage Min.-Nom.Max.* _... 183-208-229 Vac I .................. ........ ..............i............... ..........................,...................... ........✓ ...... AC Output Voltage Min.-Nom.-Max.* ✓ ✓ ✓ ✓ 211-240-264 Vac ................. .............. ......................... ..........I.................. . AC Frequency Min,Nom,-Max.* 59.3-60-60.5(with HI country settin 57-60-60.5 Hz 1.Max.Continuous Output Current 14 16 25 @ 208V I 25 32 I 48 @ 209V 48 A 23 @ 240V...!........... ...I...42 @ 240V.. . GFDI 1 A Utility Monitoring,Islanding Protection,Country Configurable — '—yes Thresholds ---INPUT ----- — - Recommended Max.DC Power** 6500 75 9600 i yvV (STC). 4100 4800 00 12400 14400 .. ..... ---��--- Transformer less,Ungrounded Yes,..T..­ .. I........................ .................................................................................................. ........... Max.Input Voltage 500 Vdc ............. ... .. .... .. ...., .. .. .. p g .... Nom.DC Input Voltage 325 @ 208V/350 @ 240V Vdc (. ....... .. .I..... ...... .. 17 @ 208V 33 @ 208V Max.Input Current*** 1 11 13 18 23.5 35 Adc ......... ...... .............. ...17 @ 240V... ...... 1..30.5 @ 240V..I...... ........... .... Max.Input Short Circuit Current 30 45 Adc Reverse.Polarity Protection . Yes Ground-Fault Isolation Detection 600ku Sensitivity ........... ....,. Maximum Inverter Efficiency 97.7 98.2 98.3 98 98 98 f .................. CEC Weighted Efficient 97 5 97.5 @ 208V 97 @ 208V i Y 98 97.5 97.5 97.5 % 1 I 98 240V 97.5 240V Nighttime Power Consumption — <2.5 <4 W ADDITIONAL FEATURES Supported Communication Interfaces— —_ RS485;RS232,Ethernet,ZigBee(optional) STANDARD COMPLIANCE _ Safety UL1741,UL1699B(Part numbers ending in",U"),UL1998,CSA 22.2 i........... Grid Connection Standards _.............. FCC artl5 class B-` ----- - -- ---- - — _.. ...... IEEE1547 ------- P Emissions __ _ _ ) I INSTALLATION SPECIFICATIONS ---- — ---- - — AC output conduit size f g AWG range T� 3 4"minimum 24-6 AWG 3/4"minimum 8-3 AWG................ ..........n ... /.......J..... ... ........-.................. ....... —�-- / T DC input AWG ane / / 3/4"minimum 1-2 strip g s/24-6 AWG 3/4"minimum/1-2 strings/14-6 AWG gonduit size #of strings. ..�.....-..................................................... ......�.................. ....... ....... ( ) 30.5 x12.5 x7/ 30.Sx12.5x7.5/ 30.5x12.Sx10.5/775x315x260 Weight c with ADC/DC Sa t Safety 775 x 315 x 172 77S x 315 x 141 mm Y ........... ..... .... ....... .......... .Y..... ........,51,2/23.....11................5­4.­/.2..4............. ............. ...,..88:4/40.1.1................_. .*/.kg... Cooling Natural Convection Fans user replaceable) Noise <25 <.50... ...... dBA Min:Max.Operating Temperature I Range -13 to+140/ 25 to+60(CAN version**** 40 to+60) 'F/'C ............. Protection Rating...... NEMA 3R i :For other regional settings please contact SolarEdge support "Limited to 125%for locations where the yearly average high temperature is above 77 9F/252C and to 135%for locations where it is below 77 9F/25 9C. For detailed information,refer to htto://www solaredae uslfiles lodfr(in prter do oversixina guide,DdIr A higher current source may be used,the inverter will limit its input current to the values stated. CAN P/Ns are eligible for the Ontario FIT and microFIT(mlcroFIT exc.SE1140OA-US-CANI ROHS solar=@@ • SolarEdge Single Phase Inverters For North America SE300OA-US/ SE380OA-US/ SE500OA-US / SE6000A-US/ SE760OA-US/ SE1000OA-US/ SE1140OA-US An 4� t G z a ._ .ZJ 9R a eats *, i t rx A ksw k . The best choice for SolarEdge enabled systems integrated arc fault protection(Type 1)for NEC 2011690.11 compliance(part numbers ending in Superior efficiency(98%) Small,lightweight and easy to install on provided bracket Built-in module-level monitoring Internet connection through Ethernet or Wireless Outdoor and indoor installation Fixed voltage inverter,DC/AC conversion only Pre-assembled AC/DC Safety Switch for faster installation USA - GERMANY - IIALY - FRANCE - JAPAN - CHINA ISRAEL AUSTRALIA www.solaredge.us NOW PAGE 51 A POWER DISTRIBUTION CU9AL BUG•BITES" 90'c Insulation Piercing onnectors Ul, ��_ g LISTED Eliminates need for conductor insulation stripping No taping required after installation For copper to copper, copper to aluminum, or aluminum to aluminum applications For use on insulated conductor only IPC SERIES NAED CATALOG WIRE RANGE TORQUE CTN EST.SHIPPING NUMBER NUMBER MAIN TAP VOLTS BOLTS FT-LBS QTY WEIGHT(lbs) UNIT 13110 IPC 1002 1/0-8 2-8 300 1 16 12 2.63 CTN 13107 'IPC 4006 4/0-4 6-14 600 1 13 12 1.90 CTN ±r 13108 'IPC 4020 410-2 2/0-6 600 1 25 12 4.08 CTN 13109 'IPC 2540 250-1 4/0-6 600 1 30 6 4.17 CTN rta 13113 IPC 3540 350-4/0 4/0-10 300 1 25 6 4.17 CTN 13114 IPC 3535 350-4/0 350-4/0 300 2 25 6 7.63 CTN h 13116 tIPC 5012 500-250 10-12 300 1 25 4 2.85 CTN 13104 "IPC 5025 500-250 250-4 600 1 55 4 4.06 CTN 13105 'IPC 5050 500-300 500-250 600 1 75 1 2.64 EA CAUTION 13106 'IPC 7550 750-500 500-350 600 1 75 1 2.62 EA Use Bug-Bites on `600 Volts,balance 300 Volts(for 480V grounded Y systems) insulated cable only! t Not CSA certified Do not install on bare cable. Dual-Rated GUTTER TAP CONNECTORS & H" 600V 90°V G 9000 High strength aluminum alloy 6061-T6,tin-plated LISTED Lay-in designed main conductor remains continuous Tap parallel or perpendicular to main GP SERIES NAED CATALOG CONDUCTOR RANGE APPROX.DIMENSIONS(IN) CTN EST.SHIPPING NUMBER NUMBER MAIN TAP H W L QTY WEIGHT(lbs) UNIT ri��fr(r 13117 GP 2' 2-12 4-12 SOL 7/8 5/8 125/5. 24 1.43 CTN 13118 GP 10 1/0-2 1/0-12 SOL 1 3/4 Vh 12 1.19 CTN 13119 GP 250 250-1/0 250-6 15/+6 1'/,s 29/32 12 2.54 CTN 13121 GP 350 350-4/0 350-6 1'/1s 1Y, 29/,s 6 2.75 CTN For copper-to-copper, 13122 GP 500 500-350 500-2 13/4 1'/a 31/e 6 3.10 CTN copper-to-aluminum, 13123 GP 750 750-500 500-2 2 11/2 33/a 3 2.5 CTN aluminum-to-aluminum 'GP2 has slotted screws. Oxide-inhibitor is recommended for added corrosion protection. 600V 90°C Snap-on insulating covers for use with GP connectors For indoor use only GPC SERIES NAED CATALOG FOR USE WITH APPROX.DIMENSIONS(IN) CTN EST.SHIPPING NS, NUMBER NUMBER CONNECTOR COLOR H W L QTY WEIGHT(lbs) UNIT \1 13137 GPC2 GP2 YELLOW 1'/6 129/32 1'/ 12 6 0.36 CTN 7r1`111(t, 13138 GPC 10 GP1/0 GRAY V/< 25/32 2% 13140 GPC 250 GP250 RED 1% 2'/a 3'h6 6 0.40 CTN 13141 GPC 350 GP350 YELLOW 13/4 3'/,s 3'/4 3 0.42 CTN 13142 GPC 500 GP500 BLUE 23/32 35hs 4% 3 0.46 CTN 13134 GPC 750 GP750 ORANGE 2"/32 3°/15 45h 3 0.65 CTN www.greaves-usa.com 11 Heritage Park,Clinton,CT 06413•Phone 860-664-4505•Fax 860-664-4546 TOLL FREE 1-800-243-1130(Outside CT) O"U N I RAC Ltnirac Code-Compliant Installation Manual SolarMount . Warranty Information See http://www.unirac.com for current warranty documents and information. ON t ann 1411 Broadway Boulevard NE paR an UNIRAC Albu uer ue NM 8 102-1 9 USA 26 9 7 545 SolarMount UniRac Code-Compliant Installation Manual VNARAc® [3.4] Installing SolarMount with grounding clips and lugs Clips and lugs are sold separately. UGC-I Top +r 1 mounting clamps L�rJ Module � 1 aim ME T-bolt Nib ,twrr I Figure 26.Slide UGC-1 grounding z",—L. UGC-1 gr€ clip into top mounting slot of rail. Torque modules to place on top of Cu S conforms to clip.Nibs will penetrate rail anod- UL standard 467 ization and create grounding path through rail(see Fig.3 reverse side). SolarMount®rail(any type) UGL r uGL Figure 27.Slide 1/,-inch hexhead bolt into top mouning slot of any SolarMount®rail(standard,Hb Serrations or light).Secure nut with 7/164rich crescent wrench with sufficient torque for tug serrations to penetrate anodized surface of rail SolarMount®rail(any type) Figure 28.Place grouding clips, lugs,and copper wire(6-10 AWG). Place a loop in the wire around splices to prevent tension.Be sure wiring between rails is not taut. KEY PV module SolarMount rail(any type) 0 Rail splice ' X Grounding lug Grounding clip Copper wire Single grounding Alternate wiring wire for entire array ` —�� for in-line splices pa, 25 EN U N I RAC Unirac Code-Compliant Installation Manual SolarMount [3.3.3] Attaching modules to the rails Lay the modules for a given panel face down on a surface that will not damage the module glass. Align the edges of the modules and snug them together (Fig.21,page 22). Trim the rails to the total width of the modules to be mounted. Place a rail adjacent to the outer mounting holes. Orient the footing bolt slot outward. Place a clip slot adjacent to the mounting holes,following the arrangement you selected earlier. Assemble the clips,mounting bolts,and flange nuts. Torque the flange nuts to 10 foot-pounds. [3.3.4] Installing the module-rail assembly Bring the module-rail assembly to the installation site. Keep rail slots free of debris that might cause bolts to bind in the Clip slots. slots Consider the weight of a fully assembled panel. Unirac recom- Mounti rg mends safety lines whenever lifting one to a roof. slots Align the panel with the previously installed L-feet. Slide 3/8 inch L-foot mounting bolts onto the rail and align them with Flange Footing �_\ut the L-feet mounting holes. Attach the panel to the L-feet and bolt slot 0 finger tighten the flange nuts. Rails may be attached to either of two mounting holes in the footings(Fig.25). • Mount in the lower hole for a low,more aethetically Figure 25.Leg-to-rail attachment pleasing installation. • Or mount in the upper hole to maximize a cooling airflow under the modules. This may enhance perfor- mance in hotter climates. Adjust the position of the panel as needed to fit the installa- tion area. Slide the remaining L-feet bolts onto the other rail, attach L-feet,and finger tighten with flange nuts. Align L-feet with mounting holes previously drilled into the roof. Install lag bolts into remaining L-feet as described in"Laying out and installing L-feet"above. Torque all footing flange nuts to 30 foot-pounds. Verify that all lag bolts are securely fastened. P.H, 24 SolarMount Chirac Code-Compliant Installation Manual C'U N I RAC¢ [3.3.2] Laying out the installing L-feet L-feet are used for installation through existing low profile roofing material,such as asphalt shingles or sheet metal. They are also used for most ground mount installations. To ensure that the L-feet will I I Install be easily accessible during flush installation: Second • Use the PV module mounting holes �` nearest the ends of the modules. ii i 1 SolarMouHt Rails 11 k • Situate the rails so that footing bolt slots face outward. The single slotted square side of the L-foot __ "" must always lie against the roof with the Instal First double-slotted side perpendicular to the roof. ——� Foot spacing(along the same rail)and rail Lower overhang depend on design wind loads. roof Rafters Install half the L-feet: eoge • If rails are perpendicular to rafters (Fig.23),install the feet closest to Figure 23.Layout with rails perpendicular to rafters. the lower edge of the roof. • If rails are parallel to rafters (Fig.24),install the feet for one of the rails,but not both. For the L-feet being installed now,drill pilot holes through the roofing into the center of Rafters�, �► Install L-Feet the rafter at each lag screw hole location. First Squirt sealant into the hole and onto the �...� � � shafts of the lag screws. Seal the underside of the L-feet with a sealant. Securely fasten the L-feet to the building structure with the lag screws. Ensure that the L-feet face as shown in Figure 23 or Figure 24. Hold the rest of the L-feet and fasteners aside until the panels are ready for the installation. -. Blocks Install L-Feet Second Figure 24.Layout with rails parallel to rafters. PaRc 23 h am U N I RAC unirac Code-Compliant Installation Manual SolarMount [3.3.1] Planning the installation area Distance between log bolt centers Decide on an arrangement for clips,rails,and L-feet(Fig.22). .zi-sr°a- �2=,,_2,•• Use Arrangement A if the full width of the rails contacts the Distance between--y module mounting holes module. Otherwise use Arrangement B. Caution:Ifyou choose Arrangement B,either PV module (1)use the upper mounting holes of the L feet or (2)be certain that the L feet and clip positions don't conflict. \Module bolt Clip- —� If rails must be parallel to the rafters,it is unlikely that they R°1`' can be spaced to match rafters. In that case,add structural -foot supports–either sleepers over the roof or mounting blocks -.—tog bolt beneath it. These additional members must meet code;if in doubt,consult a professional engineer. Distance between — ►� Never secure the footings to the roof decking alone. Such an y2_�/8'9 log bolt centers� '/2-7/811 arrangement will not meet code and leaves the installation Distance between and the roof itself vulnerable to severe damage from wind. module mounting holes 0 Leave enough room to safely move around the array during installation. The width of a rail-module assembly equals the length of one module. Note that L-feet may extend beyond the width of the assembly by as much as 2 inches on each side. The length of the assembly equals the total width of the modules. Figure 22.Clip Arrangements A and B Png 22 SolarMount Chirac Code-Compliant Installation Manual 1111'U N I RACm [3.3] Installing SolarMount with bottom mounting clips This section covers SolarMount rack assembly where the installer has elected to use bottom mounting clamps to secure modules to the rails. It details the procedure for flush mounting SolarMount systems to a pitched roof. FV modules(face down} e5 Soloi-Mol.nl rcaii •d �}l+ 1111 �s ih S H� [i of g'G Olt sot Bottom mounting clip Figure 21.SMR and CB components Table 14. Wrenches and torque Wrench Recommended Stainless steel hardware can seize up,a process size torque((t-lbs) called galling. To significantly reduce its likelihood, (1)apply lubricant to bolts,preferably '/," hardware %b" 10 an anti-seize lubricant,available at auto parts '/e"hardware �/l 6 30 stores, (2)shade hardware prior to installation, Note:Torque specifications do not appy to lag boh and(3)avoid spinning on nuts at high speed. connections. See Installation Supplement 910, Galling and Its Prevention,at www.unirac.com. Page 21 WHO .U N I RAC unirac Code-Compliant Installation Manual SolarMount [3.2.5] Installing the modules Pre-wiring Modules: If modules are the Plug and Play type, no pre-wiring is required,and you can proceed directly to - "Installing the First Module"below. a If modules have standard J-boxes,each module should be pre-wired with one end of the intermodule cable for ease of ,r installation. For safety reasons,module pre-wiring should not be . `b performed on the roof. Leave covers off J-boxes. They will be installed when the modules are installed on the rails. J boxes Installing the First Module:In high-profile installations,the best practice would be to install a safety bolt(1/4'-20 x 1/2")and Figure 17 flange nut(both installer provided)fastened to the module bolt slot at the aligned(lower)end of each rail. It will prevent the � � vle frame lower end clamps and clamping bolts from sliding out of the rail 1/2"minimum s slot during installation. If there is a return cable to the inverter,connect it to the first `'module bolt module. Close the J-box cover. Secure the first module with flange nut T bolts and end clamps at the aligned end of each rail. Allow — � half an inch between the rail ends and the end clamps(Fig.18). � _ Finger tighten flange nuts,center and align the module asF laic needed,and securely tighten the flange nuts(10 ft Ibs). End clamp X 4 , Installing the other Modules:Lay the second module face Figure 18 down(glass to glass)on the first module. Connect intermodule cable to the second module and close the J-box cover. Turn the second module face up (Fig.17). With T-bolts,mid-clamps and Module frames flange nuts,secure the adjacent sides of the first and second modules. Align the second module and securely tighten the "' flange nuts(Fig. 19). lrzd'"r>iodule bolt and-,,,,flange nut For a neat installation,fasten wire management devices to rails { with self-drilling screws. Repeat the pro edure until all modules are installed. Attach the ad R outside edge of the last module to the rail with end clamps. Trim off any excess rail,being careful not to cut into the roof. Allow half an inch between the end clamp and the end of the rail (Fig.18). Figure 19 High-lipped module Spacer Low lipped modae (cross section) 1 (cross section) SolarMount rail SolarMount rail Figure 20.Mid clamps and end clamps for lipped frame modules are identical. A spacer for the end clamps is necessary only if the lips are located high on the module frame. pa" 20 SolarMount Chirac Code-Compliant Installation Manual C U N I RAC [3.2.4] Installing SolarMount rails Keep rail slots free of roofing grit or other debris. Foreign matter will cause bolts to bind as they slide in the slots. Installing Splices:If your installation uses SolarMount splice bars,attach the rails together(Fig.13)before mounting the rails to the footings. Use splice bars only with flush installations or those that use low-profile tilt legs. Although structural,the joint is not as strong as the rail itself.A rail should always be supported by more than one footing on both sides of the splice,(Reference installation manual 908,Splices/Expansion Joints.) Figure 13.Splice bars slide into the footing bolt slots of SolarMount rail sections. Mounting Rails on Footings:Rails may be attached to either of two mounting holes in the L-feet(Fig.14). Mount in the lower hole for a low profile,more aesthetically pleasing installation. Mount in the upper hole for a higher profile,which will maximize airflow under the modules. This £, will cool them more and may enhance performance in hotter climates. Clamping �41 Slide the/e-inch mounting bolts into the footing bolt slots. Loosely attach bolt slot the rails to the footings with the flange nuts. f Ensure that the rails are oriented to the footings as shown in Figure 8,9, r �� Mounting 11,or 12,whichever is appropriate. �' slots t Footing 1 Aligning the Rail End:Align one pair of rail ends to the edge of the bolt slot installation area(Fig.15 or Fig.16). The opposite pair of rail ends will overhang the side of the installation area.Do not trim them off until the installation is complete. If the rails are perpendicular to the rafters(Fig.15),either end of the rails Figure 14.Foot-to-rail splice attachment can be aligned,but the first module must be installed at the aligned end. If the rails are parallel to the rafters(Fig.16),the aligned end of the rails must face the lower edge of the roof. Securely tighten all hardware after alignment is complete(20 ft lbs). Mount modules to the rails as soon as possible. Large temperature changes may bow the rails within a few hours if module placement is delayed. Edge of installation area Edge of installation area Figure 15.Rails perpendicular to the rafters. Figure 16.Rails parallel to the rafters. PsRe 19 OW W U N I RAC Unirac Code-Compliant Installation Manual SolarMount. [3.2.3] Laying out standoffs Standoffs(Figure 10) are used to increase the height of the array above the surface of the roof. Pair each standoff with a flashing to seal the lag bolt penetrations to the roof. Use Figure 11 or 12 to locate and mark the location of the standoff lag screw holes within the installation area. Remove the tile or shake underneath each standoff location, exposing the roofing underlayment. Ensure that the standoff Figure 10.Raised flange standoff(left) base lies flat on the underlayment,but remove no more mate- and,tlat top standoff used in conjunction rial than required for the flashings to be installed properly. with an L foot. The standoffs must be firmly attached to the building structure. If multiple high-profile rows are to be Overhang 33%L max I Foot spacing/�� installed adjacent to each other,it may not Rail an, L j be possible for each row to be centered above \' -- the rafters. Adjust as needed,following the — guidelines of Fig.12 as closely as possible. Installing standoffs: Lower roof edge Drill 3/16 inch pilot holes through the �— Rafters underlayment into the center of the rafters at (Building Structure) each standoff location. Securely fasten each standoff to the rafters with the two 5/16"lag Note:Modules must be centered symmetrically on the rails screws. (+/ 2"). Ensure that the standoffs face as shown in Figure 11. Layout with rails perpendicular to rafters.perpendicular to rafters. Figure 11 or 12. Unirac steel and aluminum two-piece standoffs(1-5/8"O.D.)are designed for collared flashings available from Unirac. Install and seal flashings and standoffs using standard building practices or as the jcompany providing roofing warranty directs. Foot spacing/ \ a Span "L" I I Lower roof edge Overhang 33%L,max L` '�—�— Rafters (Building Structure) Note:Modules must be centered symmetrically on the rails (+/2*). Figure 12.Layout with rails parallel to rafters. N: 18 • r SolarMount Unirac Code-Compliant Installation Manual UO U N I RACS [3.2.2] Laying out L-feet L-feet(Fig.7)can be used for attachment through existing roofing material,such as asphalt shingles,sheathing or sheet metal to the building structure. Use Figure 8 or 9 below to locate and mark the position of the L-feet lag screw holes within the installation area. ' J, If multiple rows are to be installed adjacent to one another,it is not likely that each row will be centered above the rafters. Figure 7 Adjust as needed,following the guidelines in Figure 9 as closely as possible. Overhang 33%L max Foot spacing/—~i Rail S an°L'� I 11 1 .\ II R I II II II .I I! II I' 1'h 13/4" ID la 1 \\ 1 Note:Modules must be Lower roof edge Rafters centered symmetrically on the (Building Structure) rails(+/ 2"). Figure 8.Layout with rails perpendicular to rafters. Installing L-feet: Drill pilot holes through the roof into the V/2-I'/4" center of the rafter at each L-foot lag screw , E` hole location. P/4_I3/4n Squirt sealant into the hole,and on the shafts of the lag screws. Seal the underside of the L- feet feet with a suitable sealant.Consult with the company providing the roofing warranty. Fdot spacin fff Securely fasten the L-feet to the roof with �, I == II ail Span,L the lag screws. Ensure that the L-feet face as t �` I 1! I shown in Figure 8 and 9. For greater ventila- tion,the preferred method is to place the single-slotted square side of the L-foot against the roof with the double-slotted side perpen Lower roof edge u u Overhang 33%L max dicular to the roof. If the installer chooses to a II mount the L-foot with the long leg against the roof,the bolt slot closest to the bend must be Note:Modules must be used. Rafters (Building Structure) centered symmetrically on the rails(+/-2„)• Figure 9.Layout with rails parallel to rafters. ra>;.: 17 U N I RAC unirac Code-Compliant Installation Manual SolarMount [3.2.11 Planning your SolarMount installations The installation can be laid out with rails parallel to the rafters The width of the installation area equals the length of one or perpendicular to the rafters. Note that SolarMount rails module. make excellent straight edges for doing layouts. The length of the installation area is equal to: Center the installation area over the structural members as • the total width of the modules, much as possible. Leave enough room to safely move around the array during plus 1 inch for each space between modules(for mid clamp), installation.Some building codes require minimum clearances around such installations,and the user should be directed to • plus 3 inches(11/z inches for each pair of end clamps). also check`The Code'. Peak a� w Low-profile High-profile mode "' mode Gutter Figure 6.Rails maybe placed parallel or perpendicular to rafters. N, 16 r SolarMount Chirac Code-Compliant Installation Manual W U N I RAC [3.2.] Installing SolarMount with top mounting clamps This section covers SolarMount rack assembly where the installer has elected to use top mounting clamps to secure modules to the rails. It details the procedure for flush mounting SolarMount systems to a pitched roof. s Mid Clamp b s End Clamp L-foot -� p SolarMount Rail SolgrMount Rail Figure 5.Exploded view of a flushmount installation mounted with L feet. Table 13.Wrenches and torque All top down clamps must be installed with anti- ' seize to prevent galling and provide uniformity Wrench Recommended ' in clamp load. UniRac Inc recommends Silver size torque(ft-lbs) Grade LocTite Anti-Seize Item numbers:38181, 80209,76732,76759,76764,80206,and 76775,or %,'"hardware '/b° 10 equivalent. 114"-20 hardware used in conjunction Ya" hardware '/16' 30 with top down clamps must be installed to 10 ft-lbs Torques are not designated for use with wood connectors of torque. When using UGC-1,UGC-2,WEEB 9.5 and WEEB 6.7, 114"-20 hardware must be installed to 10 ft-lbs of torque. Additionally,when used with a top down clamp,the module frame cross section must be boxed shaped as opposed to a single,I-shaped member.Please refer to installation supplement 910: Galling and Its Prevention for more information on galling and anti-seize and installation manual 225: Top Mounting Unirac Grounding Clips and WEEBLugs for more information on Grounding Clips." Page 15 uUm U N I RAC Chirac Code-Compliant Installation Manual SolarMount. Part III. Installing SolarMount The Unirac Code-Compliant Installation Instructions support applications for building permits for photovoltaic arrays using Unirac PV module mounting systems. This manual, SolarMount Planning and Assembly, governs installations using the SolarMount and SolarMount HD (Heavy Duty) systems. [3.1.] SolarMount rail components m s.�y .i r OFigure 4.SolarMount standard rail components. ORail —Supports PV modules. Use two per row of lock washer for attaching L-foot. Flashings:Use one per modules. Aluminum extrusion,anodized. standoff. Unirac offers appropriate flashings for both standoff types. © Rail splice—Joins and aligns rail sections into single Note:There is also a flange type standoff that does not length of rail. It can form either a rigid or thermal require an L-foot. expansion joint,8 inches long,predrilled. Aluminum Q Aluminum two-piece standoff(optional)(4"and 7') — extrusion,anodized. Use one per L-foot. Two-piece:Aluminum extrusion. Includes 3/8"x 3/4"serrated flange bolt with EPDM © Self-drilling screw—(No. 10 x 3/4") —Use 4 per rigid washer for attaching L-foot,and two 5/16"lag bolts. splice or 2 per expansion joint. Galvanized steel. OLag screw for L-foot(5/16")—Attaches standoff to OL-foot—Use to secure rails either through roofing rafter. material to building structure or standoffs. Refer to Top Mounting Clamps loading tables for spacing.Note:Please contact Unirac for use and specification of double L-foot. Top Mounting Grounding Clips and Lugs © L-foot bolt(3/8" x 3/4") —Use one per L-foot to secure rail to L-foot. Stainless steel. Installer supplied materials: OFlange nut(3/8")—Use one per L-foot to secure rail to Lag screw for L-foot—Attaches L-foot or standoff to L-foot. Stainless steel. rafter.Determine the length and diameter based on pull- out values. If lag screw head is exposed to elements,use stainless steel. Under flashings,zinc plated hardware is O Flattop standoff(optional) (3/8") —Use standoffs to adequate. increase the height of the array above the surface of the roof or to allow for the use of flashings. Use one per Waterproof roofing sealant—Use a sealant appropriate L-foot. One piece:Service Condition 4(very severe) zinc-plated-welded steel. Includes 3/8"x 3/4"bolt with to your roofing material.Consult with the company currently providing warranty of roofing. Pape 14 $olarMount Chirac Code-Compliant Installation Manual C; U N I RAC Step 6:Determine the Uplift Point Load,R(lbs),at each connection based on rail span You must also consider the Uplift Point Load,R(lbs),to determine the required lag bolt attachment to the roof (building)structure. Table 11.Uplift Point Load Calculation Total Design Load(uplift): P psf Step I Module length perpendicular to rails: B x ft Rail Span: L x ft Step 4 /2 Uplift Point Load: R lbs Table 12 Lag pull-out(withdrawal)capacities(lbs)in typical roof lumber(ASD) Use Table 12 to select a lag bolt size and embedment depth to Lag screw specifications satisfy your Uplift Point Load Force,R(lbs),requirements. Specific 5/6" shaft,* Divide the uplift pointload(from gravity per inch thread depth Table 11)by the withdrawal capacity in the 2nd column of Douglas Fir,Larch 0.50 266 Table 12. This results in inches of 5/16 lagbolt embedded thread Douglas Fir,South 0.46 235 depth needed to counteract the Engelmann Spruce,Lodgepole Pine uplift force.If other than lag (MSR 1650 f &higher) 0.46 235 bolt is used(as with a concrete or steel),consult fastener mfr Hem,Fir,Redwood(close grain) 0.43 212 documentation. Hem,Fir(North) 0.46 235 Thread It is the installer's responsibility Southern Pine 0.55 307 depth to verify that the substructure Spruce,Pine,Fir 0.42 205 and attachment method is strong enough to support the Spruce,Pine,Fir maximum point loads calculated (E of 2 million psi and higher according to Step 5 and Step 6. grades of MSR and MEL) 0.50 266 Sources:American Wood Council,NDS 2005,Tabie 11.2A,11.3.2A. Notes:(1)Thread must be embedded in the side grain of a rafter or other structural member integral with the building structure. (2)Lag bolts must be located in the middle third of the structural member. (3)These values are not valid for wet service. (4)This table does not include shear capacities. If necessary,contact a local engineer to specify lag bolt size with regard to shear forces. (5)Install lag bolts with head and washer flush to surface(no gap).Do not over-torque. (6)Withdrawal design values for lag screw connections shall be multiplied by applicable adjustment factors if necessary.See Table 10.3.1 in the American Wood Council NDS for Wood Construction. *Use flat washers with lag screws. Page 13 O U N I RAC' unirac Code-Compliant Installation Manual SolarMount Step 4: Select Rail Type Step 5: Determine the Downforce Point Load,R(Ibs), Selecting a span and rail type affects the price of your at each connection based on rail span installation. Longer spans produce fewer wall or roof When designing the Unirac Flush Mount Installation,you penetrations.However,longer spans create higher point load must consider the downforce Point Load,R(lbs)on the roof forces on the building structure. A point load force is the structure. amount of force transferred to the building structure at each The Downforce,Point Load,R(lbs),is determined by connection. multiplying the Total Design Load,P(psf)(Step 1)by the Rail It is the installer's responsibility to verify that the building Span,L(ft)(Step 3)and the Module Length Perpendicular to structure is strong enough to support the point load the Rails,B(ft)divided by two. forces. R(lbs)=PLB 12 R=Point Load(lbs) P= Total Design Load(psf) L=Rail Span(ft) B=Module Length Perpendicular to Rails(ft) It is the installer's responsibility to verify that the building structure is strong enough to support the maximum point loads calculated according to Step 5. Table 10.Downforce Point Load Calculation Total Design Load (downforce) (max of case 1,2 or 3): P psf Step I Module length perpendicular to rails: B x ft Rail Span: L x ft Step 4 /2 Downforce Point Load: R lbs P.R, 12 SolarMount Chirac Code-Compliant Installation Manual ;:'U N I RACE Table 7. ASCE 7 ASD Load Combinations Description Variable Down(orce Case I Down(orce Case 2 Dawniorce Case 3 uplift units Dead Load D 1.0 x 1.0 x 1.0 x 0.6 x psf Snow Load S 1.0 x + 0.75 x + psf Design Wind Load Pnet 1.0 x + 0.75 x + 1.0 x - psf Total Design Load P psf Note:Table to be filled out or attached for evaluation. Step 2:Determine the Distributed Load on the rail, Step 3:Determine Rail Span/L-Foot Spacing W(pID Using the distributed load,w,from Part II,Step 2,look up the Determine the Distributed Load,w(plf),by multiplying the allowable spans,L,for each Unirac rail type,SolarMount(SM) module length,B(ft),by the Total Design Load,P(psf)and and SolarMount Heavy Duty(HD). dividing by two.Use the maximum absolute value of the three downforce cases and the Uplift Case. We assume each module The L-Foot SolarMount Series Rail Span Table uses a single is supported by two rails. L-foot connection to the roof,wall or stand-off. Please refer to w=PB 12 the Part III for more installation information. w=Distributed Load(pounds per linearfoot,plf) B=Module Length Perpendicular to Rails(ft) P= Total Design Pressure(pounds per square foot,psf) Table 8.L-Foot SolarMount Series Rail Span SM-SolarMount HD-SolarMount Heavy Duty Span Distributed Load ounds/linear foot) (ft) 20 25 30 40 50 60 80 100 120 140 160 180 200 220 240 260 2 SM SM •SM.`„ .5M SM SM SM GSM sM �� 814' � SM, SM SM�, 2.5 SM .SMa SM SM sM SM" SM'�' SM 3 sM' . . sM� SM . SM SM sM sm SM � sM sm. SM y �_ a�� `_� , 3.5 $M $Mi SM SM S14— SM u {SM SM SM SM n 4 SM SM; SM SM SM sM ,sM, 5M :$I t 4.5 SM SM, sm sM sM SM GSM r 5 sM � SM�o� SM SM SM SM SM $M 5.5 SM shfi SM SM SM SM SM 2U- 6 SH1 sNl<.`' SM- SM SM .' sM SM 6.5 SM sM sM sM sM SM SM a y 7 sM SM I SM- SM SM sM° 7.5 SM,' SM sM. ' SM SM sM 8 SM' sM SM SM sM sM 8.5 sM . SM .SM SM - SM H "k 11-114r 9 sM SM SM sM � k � 9.5 SM SM sM I sM r E H xt 10 SM SM SM lift r s a 10.5 SM SM sM@ H I I SM 4 sM } Mr 1.5 SM z to 2 SM ap, 1 H' 1Dtl Pa 11 ::'U N I RAC Unirac Code-Compliant Installation Manual SolarMounx Part H. Procedure to Select Rail Span and Rail Type [2.1.] Using Standard Beam Calculations, Structural Engineering Methodology The procedure to determine the Unirac SolarMount series The Total Design Load,P(psf)is determined using ASCE 7-05 rail type and rail span uses standard beam calculations and 2.4.1 (ASD Method equations 3,5,6 and 7)by adding the Snow structural engineering methodology. The beam calculations Loadl,S (psf),Design Wind Load,pnet(psf)from Part I,Step 9 are based on a simply supported beam conservatively,ignoring and the Dead Load(psf).Both Uplift and Downforce Wind the reductions allowed for supports of continuous beams over Loads calculated in Step 9 of Part 1 must be investigated. Use multiple supports.Please refer to Part I for more information Table 7 to calculate the Total Design Load for the load cases. on beam calculations,equations and assumptions.If beams Use the maximum absolute value of the three downforce cases are installed perpendicular to the eaves on a roof steeper than and the uplift case for sizing the rail.Use the uplift case only a 4/12 pitch in an area with a ground snow load greater than for sizing lag bolts pull out capacities(Part II,Step 6).Use the 30psf,then additional analysis is required for side loading on following equations or Table 7. the roof attachment and beam. In using this document,obtaining correct results is P(psf)= 1.OD+I.OS1 (downforce case 1) dependent upon the following: 1.Obtain the Snow Load for your area from your local building P(psf)=LOD+1.0pnet(downforce case 2) official. 2.Obtain the Design Wind Load,pnet• See Part I(Procedure P(psf)=1.OD+0.7551 +0.7Spnet(downforce case 3) to Determine the Design Wind Load)for more information on P(psf)=0.6D+1.0pnet (uplift) calculating the Design Wind Load. 3.Please Note:The terms rail span and footing spacing D=Dead Load(psf) are interchangeable in this document. See Figure 3 for illustrations. S=Snow Load(psf) 4.To use Table 8 and Table 9 the Dead Load for your specific installation must be less than 5 psf,including modules and pnet=Design Wind Load(psf)(Positive for downforce,negative Unirac racking systems. If the Dead Load is greater than 5 for uplift) psf,see your Unirac distributor,a local structural engineer or contact Unirac. The maximum Dead Load D(Ps ) is 5 psf based on market research and internal data. The following procedure will guide you in selecting a Unirac 1 Snow Load Reduction- The snow load can be reduced according rail for a flush mount installation.It will also help determine to Chapter 7 ofASCE 7-05. The reduction is a function of the roof the design loading imposed by the Unirac PV Mounting slope,Exposure Factor,Importance Factor and Thermal Factor. Assembly that the building structure must be capable of Please refer to Chapter 7 ofASCE 7-05 for more information. supporting. Step 1:Determine the Total Design Load Figure 3.Rail span and footing spacing are interchangeable. y x w Brya� Ra��S od��e fan orP L ,'' Qe<Q ot o�aJs o spaco Note:Modules must be centered symmetrically on °ge the rails(+/-2*),as shown in Figure 3. 10 SolarMount Chirac Code-Compliant Installation Manual :F U N I RAC Table 6.Occupancy Category Importance Factor Non-Hurricane Prone Regions and Hurricane Prone Regions Hurricane Prone Re- with Basic Wind Speed,V= gions with Basic Wind Category Category Desicription Building Type Examples 85-100 mph,and Alaska Speed,V>I OOmph I Buildings and other Agricultural facilities 0.87 0.77 structures that Certain Temporary facilities represent a low Minor Storage facilities hazard to human life in the event of failure, including,but limited to: All buildings and other II structures except those listed in Occupancy Categories I,111,and IV. Buildings and other Buildings where more than 300 people congregate structures that Schools with a capacity more than 250 1.15 1.15 III represent a substantial Day Cares with a capacity more than 150 hazard to human life in Buildings for colleges with a capacity more than 500 the event of a failure, Health Care facilities with a capacity more than 50 or including,but not limited more resident patients to: Jails and Detention Facilities • Power Generating Stations • Water and Sewage Treatment Facilities • Telecommunication Centers • Buildings that manufacture or house hazardous materials Buildings and other Hospitals and other health care facilities having 1.15 1.15 structures designated surgery or emergency treatment IV as essential facilities, Fire,rescue,ambulance and police stations including,but not limited Designated earthquake,hurricane,or other to: emergency shelters • Designated emergency preparedness communication, and operation centers • Power generating stations and other public utility facilities required in an emergency • Ancillary structures required for operation of Occupancy Category IV structures • Aviation control towers,air traffic control centers,and emergency aircraft hangars • Water storage facilities and pump structures required to maintain water pressure for fire suppression • Buildings and other structures having critical national defense functions Source: IBC 2009,Table 1604.5,Occupancy Category of Buildings and other structures,p.281;ASCE/SEI 7-05, Minimum Design Loads for Buildings and Other Structures,Table 6-1, p.77 Ng' 9 WNW ::'U N I RAC unirac Code-Compliant Installation Manual SolarMount Step 7:Determine adjustmentfactorfor height and Table 4. Adjustment Factor (A) for Roof Height& exposure category,A Exposure Category Using the Exposure Category(Step 6)and the roof height, h look u the adjustment actor or height and exposure in Ezpasare (�)� P ) f f b' P Mean roof Table 4. height(ft) B C D 15 1.00 1.21 1.47 Step 8:Determine the Importance Factor,I 20 1.00 1.29 1.55 25 1.00 1.35 1.61 Determine if the installation is in a hurricane prone region. 30 1.00 1.40 1.66 Look up the Importance Factor,1,Table 6,page 9,using the 35 1.05 1.45 1.70 occupancy category description and the hurricane prone 40 1.09 1.49 1.74 region status. 45 1.12 1.53 1.78 50 1.16 1.56 1.81 55 1.19 1.59 1.84 Step 9:Calculate the Design Wind Load,Pnet(Psf) 60 1.22 1.62 1.87 Multiply the Net Design Wind Pressure,pnet30(psf)(Step 4)by Source: ASCE/SEI 7-05, Minimum Design Loads for Buildings and Other the adjustment factor for height and exposure,A (Step 7),the Structures,Chapter 6,Figure 6-3, p.44. Topographic Factor,Kzt(Step 5),and the Importance Factor,I (Step 8)using the following equation,or Table 5 Worksheet. pnet(Psf)=AKztl pnet30 pnet(Psf)=Design Wind Load(10 psf minimum) A=adjustment factor for height and exposure category(Step 7) Kzt= Topographic Factor at mean roof height,h(ft)(Step 5) I=Importance Factor(Step 8) pnet30(psf)=net design wind pressure for Exposure B,at height= 30,I=1 (Step 4) Use Table 5 below to calculate Design Wind Load. The Design Wind Load will be used in Part II to select the appropriate SolarMount Series rail,rail span and foot spacing. In Part Il,use both the positive(downforce)and the negative (uplift)results from this calculation. Table 5.Worksheet for Components and Cladding Wind Load Calculation:IBC 2009,ASCE 7-05 Variable Description Symbol Value unit Step Reference Building Height h ft Building,Least Horizontal Dimension ft Roof Pitch degrees Exposure Category 6 Basic Wind Speed V mph I, Figure 1 Effective Wind Area sf 2 Roof Zone Setback Length a ft 3 Table Roof Zone Location 3 Figure 2 Net Design Wind Pressure pnet30 psf 4 Table 2,3 Topographic Factor Kzt x 5 Adjustment factor for height and exposure category A x 7 Table 4' Importance Factor I x 8 Table 5 Total Design Wind Load pnet psf 9 P."' 8 SolarMount Chirac Code-Compliant Installation Manual 00'U N I RAC3 Table 3.p,,e,3o(psf Roof Overhang Effective 8osic Wind Speed,V(mph) Wind Area Zone (50 90 100 110 120 130 140 150 170 2 10 -21.0 -25.9 -31.4 -37.3 -43.8 -50.8 -58.3 -74.9 i 2 20 -20.6 -25.5 -30.8 -36.7 -43.0 -49.9 -57.3 -73.6 2 50 -20.1 -24.9 -30.1 -35.8 -42.0 -48.7 -55.9 -71.8 2 100 -19.8 -24.4 -29.5 -35.1 -41,2 -47.8 -54.9 -70.5 y 3 10 -34.6 -42.7 -51.6 -61.5 -72.1 -83.7 -96.0 -123.4 c 3 20 -27.1 -33.5 -40.5 -48.3 -56.6 -65.7 -75.4 -96.8 °0 3 5o -17.3 -21.4 -25.9 -30.8 -36.1 -41.9 -48.1 -61.8 3 100 -10.0 -12.2 -14,8 -17.6 -20.6 -23.9 -27.4 -35.2 2 10 27.2 -33.5 -40.6 -48.3 -56.7 -65.7 -75.5 -96.9 i 2 20 -27.2 -33.5 -40.6 -48.3 -56.7 -65.7 -75.5 -96.9 tko 2 50 -27.2 -33.5 -40.6 -48.3 -56.7 -65.7 -75,5 -96.9 N 2 100 -27.2 -33.5 -40.6 -48.3 -56.7 -65.7 -75.5 -96.9 a0+ 3 10 -45.7 -56.4 -68.3 -81.2 -95.3 -110.6 -126.9 -163.0 n 3 20 -41.2 -50.9 -61-.6 -73.3 -86.0 -99.8 -114.5 -147.1 0 3 50 -35.3 -43.6 -52.8 -62.8 -73.7 -85.5 -98.1 -126.1 f° 3 100 -30.9 -38.1 -46.1 -54.9 -64.4 -74.7 -85.8 -110.1 to 2 10 -24.7 -30.5 -36.9 -43.9 -51.5 -59.8 -68.6 -88.1 ao 2 20 -24.0 -29.6 -35.8 -42.6 -50.0 -58.0 -66.5 -85.5 N 2 50 -23.0 -28.4 -34.3 -40.8 -47.9 -55.6 -63.8 -82.0 �* 2 100 -22.2 -27.4 -33.2 -39.5 -46.4 -53.8 -61.7 -79.3 0 3 10 -24.7 -30.5 -36.9 -43.9 51.5 -59.8 -68.6 -88.1 A 3 20 -24.0 -29.6 -35.8 -42.6 -50.D -58.0 -66.5 -85.5 0 3 50 23.0 -28.4 -34.3 -40.8 -47.9 -55.6 -63.8 -82.0 0 3 100 -22.2 -27.4 -33.2 -39.5 -46.4 -53.8 -61.7 -79.3 Source: ASCEISEI 7-03, Minimum Design Loads for Buildings and Other Structures,Chapter 6, p.44. Step 5: Determine the Topographic Factor,Kzt For the purposes of this code compliance document,the SURFACE ROUGHNESS C: has open terrain with scat- Topographic Factor,Kt,is taken as equal to one(1),meaning, tered obstructions having heights generally less than the installation is surrounded by level ground(less than 10% 30 feet. This category includes flat open country, slope). If the installation is not surrounded by level ground, grasslands,and all water surfaces in hurricane prone please consult ASCE 7-05,Section 6.5.7 and the local building regions. authority to determine the Topographic Factor. SURFACE ROUGHNESS D:has flat,unobstructed areas and water surfaces outside hurricane prone regions. Step 6:Determine Exposure Category(B, C,D) This category includes smooth mud flats,salt flats,and unbroken ice. Determine the Exposure Category by using the following definitions for Surface Roughness Categories. Also see ASCE 7-05 pages 287-291 for further explanation and explanatory photographs,and confirm your selection with the The ASCE/SEI 7-05 defines wind surface roughness local building authority. categories as follows: SURFACE ROUGHNESS B: is urban and suburban areas, wooded areas,or other terrain with numerous closely spaced obstructions having the size of single family dwellings. Page 7 U N I RAC Chirac Code-Compliant Installation Manual SolarMount Table 2.pnet30(psf Roof and Wall Basic Wind Speed,V(mph) E(�ecti 90 100 110 120 130 140 150 170 ve Wind Area Zone (SO Downforce Uplift Downforce Uplift Downforce Uplift Downforce Uplift Downforce Uplift Downforce Uplift Downforce Uplift Downforce Uplift 1 10 5.9 -14.6 7.3 -18.0 8.9 -21.8 10.5 -25.9 12.4 -30,4 14.3 -35.3 16.5 -40.5 21.1 -52.0 1 20 5.6 -14.2 6.9 -17.5 8.3 -21.2 9.9 -25.2 11.6 -29.6 13.4 -34.4 15.4 -39.4 19.8 -50.7 1 50 5.1 -13.7 6.3 -16.9 7.6 -20.5 9.0 -24.4 10.6 -28.6 12.3 -33.2 14.1 -38.1 18.1 -48.9 1 100 4.7 -13.3 5.8 -16.5 7.0 -19.9 8.3 -23.7 9.8 -27.8 11.4 -32.3 13.0 -37.0 16.7 -47.6 d 2 10 5.9 -24.4 7.3 -30.2 8.9- -36.5 10.5 -43.5 12.4 51.0 14.3 -59.2 16.5 -67.9 21.1 -87.2 0 2 20 5.6 -21.8 6.9 -27.0 8.3 -32.6 9.9 -38.8 11.6 -45.6 13.4 -52.9 15,4 -60.7 19.8 -78.0 c 2 50 5.1 -18.4 6.3 -22.7 7.6 -27.5 9.0 -32.7 10.6 -38.4 12.3 -44.5 14.1 -51.1 18.1 -65.7 c 2 100 4.7 -15.8 5.8 -19.5 7.0' -23.6 8.3 -28.1 9.8 -33.0 11.4 -38.2 13.0 -43.9 16.7 56.4 0 3 10 5.9 -36.8 7.3 -45.4 8.9 -55.0 10.5 -65.4 12.4 -76.8 14.3 -89.0 16.5 --102.2 21.1 -131.3 3 20 5.6 -30.5 6.9 -37.6 8.3 -45.5 9.9 -54.2 11.6 63.6 13.4 -73.8 15`.4 -84.7 19.8 -108.7 3 50 5.1 -22.1 6.3 -27.3 7.6 -33.1 9.0 -39.3 10.6 46.2 12.3 -53.5 14.1 61.5 18.1 -78.9 3 100 4.7 " -15.8 5.8 -19.5 7.0 -23.6 8.3 -28.1 9.8 -33.0 11.4 -38.2 13.0 43.9 16.7 -56.4 1 10 8.4 -13.3 10.4 -16.5 12.5 -19.9 14.9 -23.7 17.5 -27.8 20.3 -32.3 233 -.37.0 30.0 -47.6 N I 20 7.7 -13.0 9.4 -16.0 11.4 -19,4 13.6 -23.0 16.0 -27.0 18.5 -31.4 21.3 -36.0 27.3 -46.3 y 1 50 6.7 -12.5 8.2 -15.4 10.0 -18.6 11.9 -22.2 13.9 -26.0 16.1 -30.2 18.5 -34.6< 23.8 -44.5 v 1 100 5.9 -12.1 7.3 -14.9 8.9 -18.1 10.5 -21.5 12,4 -25.2 14.3 -29.3 16.5 -33.6 21.1 -43.2 N 2 10 8.4 -23.2 10.4 -28.7 12.5 -34.7 ' 14.9 -41.3 17.5 -48.4 20.3 -56.2 23.3 -64.5 30.0 -82.8 0 2 20 7.7 -21.4 9.4 -26.4 11.4 -31.9 13.6 -38.0 16.0'- -44.6 18.5 -51.7 21.3 -59.3 27.3 -76.2 n 2 50 6.7 -18.9 8.2 -23.3 10.0 -28.2 11.9 -33.6 13.9 39.4 16.1 -45.7 18.5 -52.5 23.8 -67.4 A 2 100 5.9 -17.0 7.3 -21.0 8`.9 -25.5 10.5 -30.3 12.4` -35.6 14.3 -41.2 16.5 =47.3 21.1 60.8 w 0 0 3 10 8.4 -34.3 10.4 -42.4 12.5 -51.3 14.9 -61.0 17.5 -71.6 20.3 -83.1 23.3 -95.4 30.0 -122.5 3 20 7.7 -32.1 9.4 -39.6 11.4 -47.9 13.6 -57.1 16.0 -67.0 18.5 -77.7 21.3 -89.2 27.3 -114.5 3 50 6,7 -29.1 8.2 -36.0 10.0; -43.5 11.9 -51.8 13.9 -60.8 16.1 -70.5 18,5 81.0 23.8 -104.0 3 100 5.9 -26.9 7.3 -33.2 8.9 -40.2 10.5 -47.9 12.4 -56.2 14.3 -65.1 16.5 -74.8 21.1 -96.0 1 10 13.3 -14.6 16.5 -18.0 19.9 -21.8 23.7 -25.9 27.8 -30.4 32.3 -35.3 37.0 40.5 47.6 -52.0 1 20 13.0 -13.8 16.0 -17.1 19.4 -20.7 23.0 -24.6 27.0 -28.9 31.4 -33.5 36.0 ` -38.4 46.3 -49.3 N 1 50 12.5 -12.8 15.4 -15.9 18.6 -19.2 22.2 -22.8 26.0 -26.8 1 30.2 -31.1 34.6 -35.7 44.5 -45.8 1 100 12.1 -12.1 14.9 -14.9 18.1 -18.1 21.5 -21.5 25.2 -25.2 29.3 -29.3 33.6 .33.6- 43.2 -43.2 2 10 13.3 -17.0 16.5 -21.0 19.9 -25.5 ` 23.7 -30.3 27.8 -35.6 32.3 -41.2 37.0" -47.3 47.6 60.8 v 2 20 13.0 -16.3 16.0 -20.1 19.4 -24.3 23.0 -29.0 27.0 -34.0 31.4 -39.4 36.0 -45.3' 46.3 -58.1 2 50 12.5 -15.3 15.4 -18.9 18.6 -22.9 22.2 -27.2 26.0 =32.0 30.2 -37.1 34.6' -42.5' 44.5 -54.6 2 100 12.1 -14.6 14.9 -18.0 18.1 -21.8 21.5 -25.9 25.2 -30.4 29.3 -35.3 33.6 40.5 43.2 -52.0 0 3 10 13.3' -17.0 16.5 -21.0 19.9' -25.5 I> 23.7 -30.3 27.8 -35.6 32.3 -41.2 37.0 -47.3 47.6 -60.8 3 20 13.0 -16.3 16.0 -20.1 19.4 -24.3 23.0 -29.0 27.0 -34.0 31.4 -39.4 36.0 ; -45.3, 46.3 -58.1 3 50 12.5 -15.3 15.4 -18.9 18.6 -22.9 22.2 -27.2 26.0 -32.0 30.2 -37.1 34.6' -42.5' 44.5 -54.6 3 100 12.1 -14.6 14.9 -18.0 18.1' -21.8 21.5 -25.9 25.2 -30.4 29.3 -35.3 33.6 -40.5 43.2 -52.0 4 10 14.6 -15.8 18.0 -19.5 21.8 23.6 25.9 -28.1 30.4 -33.0 35.3 -38.2 40.5 -43.9: 52.0 -56.4 4 20 13.9 -15.1 17.2 -18.7 20.8` -22.6 24.7 -26.9 29.0 -31.6 33.7 -36.7 38.7' -42.1 49.6 -54.1 4 50 13.0 -14.3 16.1 -17.6 19.5 -21.3 23.2 -25.4 27.2 -29.8 31.6 -34.6 36.2 -39.7 46.6 -51.0 4 100 12.4 -13.6 15.3 -16.8 185 -20.4 rr 22.0 -24.2 25.9 -28.4 30.0 -33.0 34.4 -37.8 44.2 -48.6 4 500 10.9 -12.1 13.4 -14.9 16.2 -18.1 19.3 -21.5 22.7 -25.2 26.3 -29.3 30.2 -33.6 38.8 -43.2 5 10 14.6 -19.5 18.0 -24.1 21.8 -29.1 25.9 -34.7 30.4 -40.7 35.3 -47.2 40.5 -54.2 52.0 -69.6 5 20 13.9 -18.2 17.2 -22.5 20.8 -27.2 24.7 -32.4 29.0 38.0 - 33.7 -44.0 38.7 -50.5 49.6 -64.9 5 50 13.0 -16.5 16.1 -20.3 19.5 -24.6 23.2 -29.3 27.2 -34.3 31.6 -39.8 36.2 -45.7 46.6 -58.7 5 100 12.4 -15.1 15.3 -18.7 18.5 -22.6 22.0 -26.9 25.9 -31.6 30.0 -36.7 34.4 -42.1 44.2 -54.1 5 500 10.9 -12.1 13.4 -14.9 16.2 -18.1 19.3 -21.5 22.7 -25.2 26.3 -29.3 30.2 -33.6 38.8 -43.2 Source: ASCEISEI 7-05, Minimum Design Loads for Buildings and Other Structures,Chapter 6, Figure 6-3,p.42-43. Vag, 6 SolarMount Unirac Code-Compliant Installation Manual "IF U N I RAC Step 3: Determine Roof Zone(continued) Using Roof Zone Dimension Length,a,determine the roof zone locations according to your roof type,gable,hip or monoslope. Determine in which roof zone your pv system is located,Zone 1,2,or 3 according to Figure 2. Figure 2.Enclosed buildings,wall and roofs Flat Roof Hip Roof(7° < 9 <_ 27°) a. i h a, h �yQ a a= a ,a ar Gable Roof( 8 <_ 7°) Gable Roof(7° < 0 <_ 4S°) OM. h a- a." h a �a Interior Zones End Zones ® Corner Zones Roofs-Zone I/Walls-Zone 4 Roofs-Zone 2i'Walls-Zone 5 Roofs-Zone 3 Source: ASCE/SEI 7-05, Minimum Design Loads for Buildings and Other Structures,Chapter b, p.41. Step 4:Determine Net Design Wind pressure,pnet3o(ps.) Both downforce and uplift pressures must be considered Using the Effective Wind Area(Step 2),Roof Zone Location in overall design. Refer to Section II,Step 1 for applying (Step 3),and Basic Wind Speed(Step 1),look up the downforce and uplift pressures.Positive values are acting appropriate Net Design Wind Pressure in Table 2,page 6. Use toward the surface.Negative values are acting away from the the Effective Wind Area value in the table which is smaller than surface. the value calculated in Step 2.If the installation is located on a roof overhang,use Table 3,page 7. Page 5 8B U N I RAC Llnirac Code-Compliant Installation Manual SolarMount 90(40) k, 100(45) 85 mph ,. J38 m/s) k 110(49) v� 120(54) 40 mph (40 m/s} (40 m/s) " F 130(58) v� lr 140(63) Miles per hour 8 (meters per second) Figure 1.Basic Wind Speeds.Adapted and 130(58) applicable to ASCE 7-05.Values are nominal 140(63) 140(63) 140(63) design 3-second gust wind speeds at 33 feet 150(67) above ground forExposure Category C. gyp„ 150(67) X40) i €( Spe"Wind Region 1 (45] 130(58) 110(48)120(54) Step 3:Determine Roof/Wall Zone The Design Wind Load will vary based on where the installation is located on a roof. Arrays maybe located in more than one roof zone. Using Table 1,determine the Roof Zone Dimension Length,a (ft),according to the width and height of the building on which you are installing the pv system. Table I.Determine Roof/Wall Zone,dimension (a) according to building width and height a= 10 percent of the least horizontal dimension or 0.4h,whichever is smaller,but not less than either 4%of the least horizontal dimension or 3 ft of the building. Roof Least Horizontal Dimension(ft) Height(ft) 10 15 20 25 30 40 50 60 70 80 90 100 125 150 175 200 300 400 500 10 3 3 3 ; 3 3 4 4 4 4 4 4 4 5 6 7 8 12 16 20 15 3 3 3 3 3 4 5 6 6 6 6 6 6 6 7 8 12 16 20 20 3 3 3 3 3 4 5 , 6' 7 8 8, 8 8 8 8 8 12 16 20 25 3 3 3 3 3 4 5 6 7 8 9 10 10 10 10 10 12 16 20 30 3 3 3 ' 3 3 4' 5 6 7 8 9 10 _,12 12 12 12 12 16 20 35 3 3 3 3 3 4 5 6 7 8 9 10 12.5 14 14 14 14 16 20 40 3 3 3 3 3 '4 5 6 7 8 9 10 12.5 15 16 16 16 16 20 4S 3 3 3 3 3 4 5 6 7 8 9 10 12.5 15 17.5 18 18 18 20 s0 3 3 3 3 3 4 5 6 7 8 9 10 12.5 15 17.5 20 20 20 20 60 3 3 3 3 3 4 5 6 7 8 9 10 12.5 15 17.5 20 24 24 24 Source: ASCE/SEI 7-05, Minimum Design Loads for Buildings and Other Structures,Chapter 6,Figure 6-3, p.41. r.,x' 4 SolarMount Unirac Code-Compliant Installation Manual :F U N I RAC Part I. Procedure to Determine the Design Wind Load [1.1.] Using the Simplified Method - ASCE 7-05 The procedure to determine Design Wind Load is specified for more clarification on the use of Method I.Lower design by the American Society of Civil Engineers and referenced in wind loads may be obtained by applying Method II from ASCE the International Building Code 2009. For purposes of this 7-05.Consult with a licensed engineer if you want to use document,the values,equations and procedures used in this Method II procedures. document reference ASCE 7-05,Minimum Design Loads for The equation for determining the Design Wind Load for Buildings and Other Structures. Please refer to ASCE 7-05 if components and cladding is: you have any questions about the definitions or procedures presented in this manual.Unirac uses Method 1,the Simplified Method,for calculating the Design Wind Load for pnet(p s f)=AKZd pner3o pressures on components and cladding in this document. peer(psf)=Design Wind Load The method described in this document is valid for flush,no tilt,SolarMount Series applications on either roofs or walls. A=adjustment factor for building height and exposure category Flush is defined as panels parallel to the surface(or with no more than 3"difference between ends of assembly)with no Kt= Topographic Factor at mean roof height,h(ft) more than 10"space between the roof surface,and the bottom I=Importance Factor of the PV panels. This method is not approved for open structure calculations. pnet30(psf)=net design wind pressure forExposure B,at height= Applications of these procedures is subject to the following 30 feet,I=1.0 ASCE 7-05 limitations: 1.The building height must be less than 60 feet,h<60. See note for determining h in the next section. For installations You will also need to know the following information: on structures greater than 60 feet,contact your local Unirac Distributor. Basic Wind Speed= V(mph),the largest 3 second gust of wind in the last 50 years. 2.The building must be enclosed,not an open or partially enclosed structure,for example a carport. h(ft)=total roof height for flat roof buildings or mean roof height 3.The building is regular shaped with no unusual geometrical for pitched roof buildings irregularity in spatial form,for example a geodesic dome. Roof Pitch(degrees) 4.The building is not in an extreme geographic location such as a narrow canyon or steep cliff. This manual will help you determine: 5.The building has a flat or gable roof with a pitch less than 45 Effective Wind Area(sf)=minimum total continuous area of degrees or a hip roof with a pitch less than 27 degrees. modules being installed(Step 2) 6.If your installation does not conform to these requirements please contact your local Unirac distributor or a local Roof Zone=the area of the roof you are installing the pv system professional engineer. according to Step 3. If your installation is outside the United States or does not Roof Zone Dimension=a(ft)(Step 3) meet all of these limitations,consult a local professional engineer or your local building authority.Consult ASCE 7-05 Exposure Category(Step 6) [1.2.] Procedure to Calculate Total Design Wind The procedure for determining the Design Wind Load can be Step 2:Determining Effective Wind Area broken into steps that include looking up several values in Determine the smallest area of continuous modules you will different tables.Table 5 has been provided as a worksheet for be installing. This is the smallest area tributary(contributing the following 9 steps(page 8) load)to a support or to a simple-span of rail.That area is the Effective Wind Area,the total area of the fewest number of Step 1:Determine Basic Wind Speed, V(mph) modules on a run of rails.If the smallest area of continuous modules exceeds 100 sq ft,use 100 sq ft(See Table 2). If less, Determine the Basic Wind Speed, V(mph)by consulting your round down to values available in Table 2. local building department or locating your installation on the maps in Figure 1,page 4. raxr 3 ...U N I RAC unirac Code-Compliant Installation Manual SolarMount. L Installer's Responsibilities Please review this manual thoroughly before installing your SolarMount is much more than a product. SolarMount system. It's a system of engineered components that can be assembled This manual provides(1)supporting documentation for into a wide variety of PV mounting structures.With building permit applications relating to Unirac's SolarMount SolarMount you'll be able to solve virtually any PV module Universal PV Module Mounting system,and(2)planning and mounting challenge. assembly instructions for SolarMount It's also a system of technical support:complete installation SolarMount products,when installed in accordance with and code compliance documentation,an on-line SolarMount this bulletin,will be structurally adequate and will meet Estimator,person-to-person customer service,and design the structural requirements of the IBC 2009,ASCE 7-05 assistance to help you solve the toughest challenges. and California Building Code 2010(collectively referred to as"the Code").Unirac also provides a limited warranty on This is why SolarMount is PV s most widely used mounting SolarMount products(page 26). system. I _The installer is solely res onsible for: • Complying with all applicable local or national building codes, including any that may supersede this manual; • Ensuring that Unirac and other products are appropriate for the particular installation and the installation environment; • Ensuring that the roof, its rafters, connections, and other structural support members can support the array under all code level loading conditions (this total building assembly is referred to as the building structure); • Using only Unirac parts and installer-supplied parts as specified by Unirac (substitution of parts may void the warranty and invalidate the letters of certification in all Unirac publications); • Ensuring that lag screws have adequate pullout strength and shear capacities as installed; • Verifying the strength of any alternate mounting used in lieu of the lag screws; • Maintaining the waterproof integrity of the roof, including selection of appropriate flashing; • Ensuring safe installation of all electrical aspects of the PV array; • Ensuring correct and appropriate design parameters are used in determining the design loading used for design of the specific installation. Parameters, such as snow loading,wind speed, exposure and topographic factor should be confirmed with the local building official or a licensed professional engineer. P." 2 So RMO Code-Compliant Installation Manual 227.3 U.S.Des.Patent No.D496,248S,D496,249S. Other patents pending. r , • } z , mw • K� • • • Table of Contents LInstaller's Responsibilities........ ....... .... .............. . ...............................2 Part I.Procedure to Determine the Design Wind Load........................... . ...............3 Part II.Procedure to Select Rail Span and Rail Type.............................. ...............10 Part III.Installing SolarMount [3.1.] SolarMount rail components.......... ..... ............................ .....14 [3.2.]Installing SolarMount with top mounting clamps......... . ................ .....15 • [3.3.]Installing SolarMount with bottom mounting clips .............................21 [3.4.]Installing SolarMount with grounding clips and lugs.... ....... .................25 U N I RAC 0 A HIJI GROUP COMPANY Unirac welcomes input concerning the accuracy and user-friendliness of this publication.Please write to publications @unirac.com. J Customer Owned AWARNING Parallel Generation Service is energized from two sources. Safety Disconnect Solar system and utility grid Switch AC operating voltage: WARNING-ELECTRICAL SHOCK HAZARD. DO NOT TOUCH TERMINALS.TERMINALS Maximum solar AC current: ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION ELECTRICAL SHOCK HAZARD Do Not Touch Terminals Trinity Solar Terminals on Both the Line and Load Sides May Be Energized 2211 Allenwood Road In the Open Position. Wall, NJ 07719 732-780-3779 service@trinftysolarsystems.com PHOTOVOLTAIC SYSTEMS WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS Strings PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED Operating Current Operating Voltage WARNING ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED, Max. System Voltage NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED Short Circuit Current Grounding Connectors 90°C RATING (4866 LISTED) TYPE: LI Lay-In Connector CMC® LI-S ground connectors are manufactured from high strength 6061-T6 aluminum alloy to insure both maximum strength and conductivity. They are dual rated for both copper and aluminum conductors and are electro tin plated to provide low contact resistance and protection against corrosion. They are designed for use on conduit grounding bushings. The open-faced design allows the installer to quickly lay-in the grounding conductor as a jumper to multiple conduits with no break in the ground conductor. Eum Cond.Range Stud Size* Dimensions,Inches Fig. No. AWG H W L 1 4- 14 0.22 0.78 0.38 1.07 1/0- 14 0.27 1.17 0.6 1.5 2 3/0- 6 0.33 1.56 0.8 2 250 -6 0.33 1.79 0.8 2.2 Fig.I Fig.2 EXISTING SHEATHING AND ASPHALT SHINGLES SUNMODO Ez MOUNT "L" FOOT FOR SHINGLE ROOFS (TYP) (SEE DETAIL BELOW) EXISTING ROOF RAFTER SUNMODO Ez MOUNT "L" FOOT FOR SHINGLE ROOFS 5/16"x4" LAG BOLT INSTALLED INTO EXISTING ROOF RAFTER EXISTING ASPHALT SHINGLED ROOF ROOF PITCH syyz_„ ------------------ ------------- - 2211 ALLENWOOD RD. ROOF PENETRATIONS AND ROOF ATTACHMENT DETAIL WALL, NEW JERSEY FOOT SPACING AS PER VM SOLAR TEL: 732-780-3779 UNIRAC SPECS FAX: 732-780-6671 w�=r �411 �d. r� Serrated L Foot allows for 1lersat�ii aluminum base for Flashlrtg designed to redirect rail mounting on either multiple configurations., water flow. side. Optional'Standoff Kits Q available! 0 Eff lMlosrnt L-Foo►t Kit mor supoe*se. Kit# K10068-001 All kits come complete with the following parts: 1-Lag Bolt SS 5/16 x 4 1-AI Shoe Part#815015-002 Part#A20065-001 1-Ez L Foot Part#A20064-001 1-Flashing ` 1-Hex Cap 1-Bolt 3/8-16 x 3/4" Part#A20052-001 �J Part#A20066-001 1-Flange Nut 3/8" sUNmeArj 1915 E 5th St.,Ste. C Y Vancouver,WA 98661 Phone: 360-335-3037 www.sunmodo.com 1 ! y t Ez Mo nt L FootPatent Pending fior Shingle Refs WIN lil,,Illl - . k a, • All in One Roof Flashing & Mount • Mounts with all Standard Racking Systems • Stainless Steel Lag Bolts and • All Aluminum • Easy to install Ste. C SUNM*YCj Van ouver, WA�98661 Phone: 360-335-3037 www.sunmodo.com Engineer/License Holder: Charles P Bonicker ® Trinity Heating 8 Air, SO AN MODULES MOUNTED TO ROOF ON I ARRAY MOUNTED TO ROOF Inc DBA Trinity Solar z3 O A MODULES AAG MOLAR EDGE P3oo vER MODULE UNDER SOLAR MODULE I 2211 Allenwood Rd.Wall,NJ 07719 NEC 690.34 18.75 ADC MAX PER STRING 1 TR rv0 OF 11 moDOLES NSERLES-BSO Vma. B.e ETAL 1 TRING OF 12 MODUlE51N SERIES-350 Vmax F - JUMNCTION C �Vrvcr ory '2 STRINGS TO BE TERMINATED IN PARALLEL INSIDE INVERTEFI BOX BOX I 7 q 69 Issued I Revisions EXISTING t20/2AOV UTILITY METER NO. DESCRIPTION DATE 240V 10 200A MAIN BREAKER Project Title: 200A BUSBAR ---i _---- [ DOSTAL,STEPHEN ARRAY CIRCUIT WIRING NOTES ))2p20DA TRIN I1V ACCT p:2014d2439 PRODUCTION COMPLIES WITH 2011 NEC - METER 60A INFUSED UTILITY DISCONNECT Project Address: 1.)LOWEST EXPECTED AMBIENT TEMPERATURE BASED ON _ L 240V L. 'd�ER-$ ASHRAE MINIMUM MEAN EXTREME DRY BULB - F�� TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO d+� 88 SOUTH MAIN STREET INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT _- --- TEMP= -16'C P3 FLORENCE,MA 01062 p3 20A_ f� 2.)HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED a ai ON ASHRAE HIGHEST MONTH 2%DRY BULB L1 L2 N D i g Tlle'. TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO INSTALLATION LOCATION, HIGHEST CONTINUOUS TEMP= --- - ---- �- ---- --- -� --- ---_- 3TC 1 PROPOSED 5.865kW EXISTING MAIN BREAKER LOAD CENTER SQUARE D - SOLAR SYSTEM 3.)2005 ASHRAE FUNDAMENTALS 2%DESIGN 2p3OA BACK FEED BREAKER PN; D222RR TEMPERATURES 00 NOT EXCEED 47'C IN THE UNITED NEC 690.64 STATES(PALM SPRINGS,CA IS 44A C). FOR LESS THAN -'- DfeWing lnfOTRlallOn 9 CURRENT-CARRYING CONDUCTORS IN A ROOF-MOUNTED SUNLIT CONDUIT AT LEAST 0.5"ABOVE DRAW LNG DATE. 'C/3/zOt4 ROOF AND USING THE OUTDOOR DESIGN TEMPERATURE DRAWN er: OE 47-C OR LESS(ALL OF UNITED STATES). vISEO Br. 4.)PHOTOVOLTAIC POWER SYSTEMS SHALL BE System Information'. PERMITTED TO OPERATE WTH UNGROUNDED PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUIT AS PER TITAI SVSTE M 5I2. 5.965kW NEC 690.35 MODULE COUNT: 23 MODULES USFD. CANADIAN SOLAR 255 5.)ALL EQVIF'MENT INSTALLED OUTDOORS SHALL HAVE A MEMA3 RA TING. mODULf sPEt p. CS6P 255v iY COMPANY; GRID CALCULATIONS FOR CURRENT CARRYING uTIUTr ACCT': SIX 666-1 CONDUCTORS ILLIATI NU FER': 43241894 REQUIRED CONDUCTOR AMPACITY PER STRING DFALTYPE: 0. [NEC698(B)(1)]: (15.00`1.25)1= 18.75A AWG X10,UERAIED AMPACITY AMBIENT TEMP: 55'C,TEMP DEBATING FACTOR 76 PV MODULE SPECIFICATIONS RACEWAY DERATING=4 CCC: 0.80 Rev.No. Sheet (40'.76)0.80= 24.32A CANADIAN SOLAR 255IC56P 255PI -- WI Imp 8.43 24.32A?18.75A,THEREFORE RE SIZE IS VALID Vmp 302 p 6THWN�2 GEC TO EXISTING GROUND ROD TOTAL AC REQUIRED CONDUCTOR AMPACITY 23.00A'1.25= 28.75A 074 rw/I-a.10 rUwN-i.1-al0 rllwN AWG#10,DERATED AMPACITY AMBIENT TEMP: 30'C,TEMP DERAUNG: 1.0 [ I EmF W/4x10FNwN-21-a8FNwry 2GROUNn RACEWAY DEBATING`-3 CCC. N/A NVERTERa1 SE50—US 4OA`1.0=40A IK q[ i EMFW/4-p10THWNZ 1ARTHWN-z UND 40A'28.75A THEREFORE AC WIRE SIZE IS VALID IR'p 12.76 Pout 5000 VEMT W/3-NISTUWN-2,1—THWN-1 GROUND nitv Vmp 350 I.R 23 p12 PV WIRE W/pe PARE COP PER BONDTO MODULES AND RAILS CALCULATION FOR PV OVERCURRENT PROTECTION 29,75 SOLAR TOTAL INVERTER CURRENT: 23.00A 23.00A'1.25=28.7SA 13D JVr.1 1240 A11--1 a.1 --; 30A OVERCURRENT PROTECTION 13 VALID ., Wall NrwJ'�•�v0"tR wvwTreiury<DDr.QOm 1 2' NEW PV SOLAR MODULE,TYPICAL UNIRAC CLAMP U.V.I. ;REFER TO EQUIPMENT SCHEDULE IsEr sPECSREFTFOR.ETU1s Englneerl License Holder: FOR SPECS AND QUANTITIES) \ NEW MOUNTING To—ATTACHMENT(REFER TO SOLAR MODULE SOLAR MODULE POINTS,TYPICAL N ENGINEERING LETTER FOR SPACING AND DETAILS) UNIRAC SOLAR MOUNT BEAM s>EC SH'X"VP oFruLs NEW UNIRAC RAIL.TYPICAL UNIRAC"L"FOOT tsFF 4 REFER TO THE UNIRAC sE SPSC SneE FoR.FTNLS, ONE LAVER ASPHALT SHINGLES CO REFER TO HE 1INSTALLATION ISEE—EERS—TEN 1-SPECS .s SUNMODO FLASHING S MANUAL FOR SPECS AND DernlLS sFS SP< <r.ov ial AlLN APOC SEALANTN OSrnILe , -\ NEW ENGOLF TYPICAL REFER TO THE UNIRAC CODE-COMPLIANT INSTALLATION MANUAL 3.2.5 FOR SPECS AND SOLAR MODULES SHALL NOT -- �IREFERTOTHEUNIENC DETAILS) EXIST RAFTER EXCEED PEAK HEIGHT. NEW MID CLIP,TYPICAL Anal1 COOE-COMPLIANT INSTALLATION MANUAL 3.2.5 FOR SPECS AND 3ATTACHMEN7 8 CLIP DETAIL DETAILS) PV MODULE ATTACHMENT ON ASPHALT SHINGLE ROOF HEIGHT FROM GROUND LEVEL TO PEAK OF ROOF SEA LE.Nor To scALE SCALE'NoT To scALE scALE Nmr r,..GALE Issued/Revisions DC VACI P D M NO. DESCRIPTION DATE Project Title,'. DOSTAL,STEPHEN TRINITY ACCT d:2014-42639 Project Acidrem R1 88 SOUTH MAIN STREET F FLORENCE,MA 01062 U Z O m Drawing Title. PROPOSED 5.865kW SOLAR SYSTEM Drawin Information o.=DATE. 1z/3/zDl4 Ll RFV11[D By WN III System Information: LITAI 111111 OF 5 SS11I TOTAL ODUI.E COUNT. 23 MODULES USED. NAOIAN 1111111 MODULES...F. ISAR 2111 IT TLLpYCOMPANY: NATL BRID UTIUrY ACCT#. 382 E66...1 UTILITY METER 9, 43241884 DFALTYPE. NOTES'. 1.)ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 2.)ALL OUTDOOR EQUIPMENT SHALL BE RAIN TIGHT WITH MINIMUM NEMA 3R RATING. REV.NO Sheet 3U ALL LOCATIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION. 4.)ALL EOUIPMENT INSTALLED OUTDOORS SHALL HAVE A NEMA3 RATING 5.) ROOFTOP SOLAR INSTALLATION ONLY PV ARRAY WILL NOT EXTEND BEYOND THE EXISTING BUILDING ENVELOPE ARRAY SCHEDULE SYMBOL LEGEND PLUMBING SCHEDULE EQUIPMENT SCHEDULE Rl INDICATES ROOF DESIGNATION.REFER TO INDICATES NEW UTILITY DISCONNECT TO BE .NEW END CLIP.TYPICAL(REFER TO THE UNIRAC QTY SPECd ARRAY pRIENTAilON=144.!° E CODE-COMPLIANT INSTALLATION MANUAL CANADIAN SOIAR 255 CS6P-255P ARRAY SCHEDULE FOR MORE INFORMATION D INSTALLED OUTSIDE SECTION 32.5 FOR SPECS AND DETAILS) 2B I I MODULE 11TCH7 11 1' INDICATES NEW PV SOLAR MODULE RED MODULES NEW MID CUP.TYPICAL(REFER TO THE UNIRAC 1 SESODOA-US I IN I INDICATES EXISTING METER LOCATION INDICATE PANELS THAT USE MICRO INVERTERS. ® CODE-COMPLIANT INSTALLATION MANUAL I' REFER TO EQUIPMENT SCHEDULE FOR SPECS SECTION 12.5 FOR SPECS AND DETAILS) _ OTHER OBSTRUCTIONS ty INDIRATESE%IGTING ELECTRICAL PANEL INDICATES NEW PRODUCTION METER TO BE NEW UNIRAC RP1L TYPICAL EP LOC TION:IN BASEMENT I 1 IN STALLED IN BASEMENT. — (STALLA ITH MANUAL FOR SPECS ANDD SOLAR INSTALLATION MANUAL FOR SPECS AND DETAILS) /� INDICATES PLUMBING DESIGNATION REFER TO INDICATES NEW INVERTER TO BE NEW MOUNTING FOOTI ATTACHMENT POINTS, ??^1A��—d Pend 877,791207B /1 PLUMBING SCHEDULE FOR DETAILS INSTALLED IN BASEMENT. TYPICAL (REFER TOENGINEERINGLETTER FOR —11 N1.1-110"t9 ww 111-- I-11— REFER TO EQUIPMENT SCHEDULE FOR SPECS, SPACING AND DETAILS) Engineer I License Holtler: INSTALLATION OF NEW ROOF MOUNTED SOUTH MAIN STREET Is 5.865 kW PV SYSTEM 88 SOUTH MAIN STREET FLORENCE, MA 01062 Issued I Revisions VICINITY MAP SITE N0. DESCRI-ON DATE SCALE:NTS Project Title: DOSTAL,STEPHEN iBINITY ACCT p'JO14dJ439 Project Address: 88 SOUTH MAIN STREET FLORENCE,MA 01062 GENERAL NOTES GENERAL NOTES CONTINUED GENERAL NOTES CONTINUED ABBREVIATIONS CONTINUED SHEET INDEX PV-T COVER SHEET W/SITE INFO H NOTES Drawing Titte: 1.THEINSTALLATION CONTRACTORL 6. THE DC VOLTAGE FROM THE PANELS IS 16 B)CURRENT PREVAILING S,UTILITY JB JUNCTIONBO% - RESPONSIBLE FOR IN STALLING ALL ALWAYS PRESENT AT THE OC COMPANY SPECIFICATIONS, kCMIL THOUSAND CIRCULAR MILS EQUIPMENT AND FOLLOWING ALL 015CONNECT ENCLOSURE AND THE DC STANDARDS,AND REQUIREMENTS kVA KILO-VOLT AMPERE PV-2 ROOF PLAN W/MODULE LOCATIONS PROPOSED 5.86SkW DIRECTIONS AND INSTRUCTIONS TERMINALS OF THE INVERTER DURING 15 THIS SET OF PLANS HAVE BEEN kW KILO-WATT SOLAR SYSTEM CONTAINED IN THE DRAWING PACKAGE AND DAYLIGHT HOURS.ALL PERSONS PREPARED FOR THE PURPOSE OF kWH KILOWATT HOUR PV-3 ELECTRICAL 3 LINE DIAGRAM INFORMATIQNRECEIVEDFROMTRINIT VIE Y. WORKING ONORINVOLVED`MTHTHE MUNICIPAL AND AGENCY BEATEN AND L LINE 2.TH E.INSTALLATIONCONTRACTOR IS PHOTOVOLTAIC SYSTEM ARE WARNED APPROVAL.THIS SET OF PLANS SHALL MOB MAIN CIRCUIT BREAKER D(BWID InfOlRleIl00 RESPONSIBLE FOR INSTALLING ALL THAT THE SOLAR MODULES ARE NOT BE UTILIZED AS CONSTRUCTION MDR MAIN DISTRIBUTION PANEL EQUIPMENT AND FOLLOWING ALL ENERGIZED WHENEVER THEY ARE DRAWINGS UNTIL REVISED TO INDICATE SLID MAINLUG ONLY DRAWIxG DATE. 11/3/2014 DIRECTIONS AND INSTRUCTION CONTAINED EXPOSED TO LIGHT. ISSUED FOR CONSTRUCTION'. MTD MOUNTED U. A BV'. IN THE COMPLETE MANUAL. 9. ALL PORTIONS OF THIS SOLAR 16 ALL INFORMATION SHOWN MUST BE MTG MOUNTING FvIW RY. IT HC INSTALLATION CONTRACTOR IS PHOTOVOLTAIC SYSTEM SHALL BE CERTIFIED PRIOR TO USEFOR N NEUTRAL T RESPONSIBLE FOR READING AND MARK ED CLEARLY IN ACCORDANCE WITH CONSTRUCTION ACTIVITIES. NEC NATIONAL ELECTRICAL CODF UNDERSTANDING ALL DRAWINGS. THE NATIONAL ELECTRIC CODE ARTICLE LID NOT I NC ONTRACT COMPONENT AND INVERTER MANUALS S.. N04 NUMBER System lnfOl''bon: PRIOR TO INSTALLATION.THE INSTALLATION ID. PRIOR TO THE INSTALLATION OF THIS ABBREVIATIONS NTS NOT TO SCALE TM SYSTEM SIZE 5.S65kW CONIRACTOR IS ALSO REQUIRED TO HAVE PHOTOVOLTAIC SYSTEM,THE OCR OVER CURRENT PROTECTION ALL COMPONENT SWITCHES IN THE OFF INSTALLATION CONTRACTOR SHALL AMP AMPERE P POLE TOIIII N—I COUNT. 13 POSITION AND FUSES REMOVED PRIOR TO ATTEND A PRE4NSTALLTION MEETING AC ALTERNATING CURRENT PB PULL BOX MODULES USE D: CANADIAN SOLAR 155 THE INSTALLATION OF ALL FUSES BEARING FOR THE REVIEW OF THE INSTALLATION AL ALUMINUM PHI PHASE MCWLE 5AEC N: C56P-2554 SYSTEM COMPONENTS. PROCEDURES,3CHEUULEB.SAFETY AND AF AMP.FRAME PVC POLY-VINYL CHLORIDE CONDUIT NAT'L GRID 4.ONCE THE PHOTOVOLTAIC MODULES ARE COORDINATION, AFF ABOVE FINISHED FLOOR PWR POWER MOUNTED INSTALLATION 11 PRIOR TO THE SYSTEM START LIP THE 0.FG ABOVE FTRISHED GRADE QTY QUANTITY UTILITY ACCT..Y 3A166HT N)5 CONTRACTOR SHOULD HAVE A MINIMUM OF INSTALLATION CONTRACTOR SHALL AWG AMERICAN WIRE GAUGE RG RIGID GALVANIZED STEEL "I METER C. 43}41894 ONE ELECTRICIAN WHO HAS ATTENDED A ASSIST IN PERFORMING ALL INITIAL C CONDUIT(GENERIC TERM OF SNS SOLID NEUTRAL DTgI TYPE: SOLAR PHOTOVOLTAIC INSTALLATION HARDWARE CHECKS AND OC WIRING NACEWAY,PROVIDE AS JSWBOSWiTCHBOARD COURSE ON SITE. CONDUCTIVITY CHECKS. SPECIFIED TYP TYPICAL 5.FOR SAFETY.IT IS RECOMMENDED BY THE 12. FOR THE PROPER MAINTENANCE AND CB COMBINER BOX UCH UNLESS OTHERWISE INDICATED MANUFACTURE THAT THE INSTALLATION ISOLATION OF THE INVERTS REFER TO CKT CIRCUIT WP WEATHERPROOF CREW ALWAYS HAVE A MINIMUM OF TWO THE ISOLATION PROCEDURES IN THE CT CURRENT TRANSFORMER XFMR TRANSFORMER Rev.No. Sheet PERSONS WORKING TOGETHER AND THAT OPERATION MANUAL. CU COPPER tT2 MOUNT 72INCHES TO BOTTOM MEMBERS BE IINRAI ED IN F CREW AID AND iB AND TELEPHONE UTL(TIES ARE SUBJECT DISC DISCONNECURRENT SWITCH GRADE FINISHED FLOOR pR CPR_ TO FINAL APPROVALOFTHE DWG DRAWING 6.THIS SOLAR PHOTOVOLTAIC SYSTEM IS TO APPROPRIATE UTILITYCOMPANTES AND EC ELECTRICAL SYSTEM INSTALLER EMT ELECTRICAL METALLIC TUBING REINSTALLED FOLLOWING THE OWNERS. FS FUSIBLE SWITCH CONVENTIONS OF THE NATIONAL ELECTRIC 14. ALL MATERIALS.WORKMANSHIP AND FU FUSE CODE.ANYLOCAL CODE WHICH MAY CONSTRUCTK)N FOR THE SITE GND GROUND SUPERSEDE THE NEC SHALL GOVERN, IMPROVEMENTS SHOWN HEREIN SHALL GET GROUND FAULT INTERRUPTER ].ALL SYSTEM COMPONENTS TO BE BE IN ACCORDANCE WITH HZ FREQUENCY(CYCLES PER • IN ST ALLED M rH IN SYSTEM ARE TO BE N CURRENT PREVAILING MUNICIPAL SECOND) LISTED.ALL EQUIPMENT WILL BE NEMA ANDIOR COUNTY SPECIFICATIONS. 3R OUTDOOR RATED UNLESS INDOORS. STANDARDS AND REQUIREMENTS 4nni GENERAL NOTES SOLAR IF 195E0 DRAWING IS MARKED WITH REVISION CHARACTER OTHER THAN IV,PLEASE BE ADVISED THAT FINAL EQUIPMENT AND/OR SYSTEM CHARACTERISTICS ARE SUBJECT TO CHANGE DUE TO AVAILABLRY OF EQUIPMENT. wall,New n.nv OT>19 wwwT,In11y5olar nom Trinity Solar 20 Patterson Brook Road Wareham, MA 02571 508-291-0007 Date: 10/22/14 I, Stephen Dostal ,do hereby grant Trinity Solar the right to sign on (Homeowner's Nome) my behalf in all matters regarding the permit applications through the township of Florence, MA for the installation of solar panels and all other (Municipality) related work on my property at $8 South Maim St. Please accept this (Slre,t Address) document,with full signature,in place of all application signatures. Furthermore,should there be any issues or discrepancies with the paperwork,please contact Danielle DeVito at Trinity Solar, 732-780-3779 ext. 9044 or danielle.devito@trinitysolarsystems.com. Sincerely, 88 South Main St. Homeowners Signature Street Address Stephen Dostal Florence MA 01 062 Print name City,State,Zip Code 413-586-6289 Phone Number Optimize Engineering Co., LLC P.O. Box 2649Farmville•VA 23901 Ph: 434.574.6138.E-mail: grichardpe @aol.com Richard B. Gordon, P.E. President October 24, 2014 Florence Building Department Florence, MA Re: Solar Electric Panels Roof Structural Framing Support To Whom It May Concern: I hereby certify that I am a Licensed Professional Engineer in the State of Massachusetts. Please note the following conclusions regarding framing structure, roof loading, and photovoltaic system size and proposed site location of installation: 1. Existing roof framing: Conventional framing 2x8 at 24" o.c. and 12'-6" span (horizontal rafter projection). This existing structure is definitely capable to support all of the loads that are indicated below for this photovoltaic project after sister the rafters below solar array with a 2x8 using (2)10d nails 2' o.c. Use of(2)Guard DogTm FMGDO02 screws is approved, or equal shear strength of approx. 120 lb, 2' o.c.at areas where little space is available only with remainder of member secured with (2)10d nails 2' o.c. If do not sister,then install a 2x4 @ 24"o.c. knee wall over an interior bearing wall to limit span between supports to 10'-1". 2. Roof Loading • 4.33 psf dead load (modules plus all mounting hardware) • 35 psf snow live load (50 psf ground snow live load reference) • 4.5 psf roof materials (sheathing and shingles) • Exposure Category B, 115 mph wind uplift live load of 19.6 psf(wind resistance) 3. Address of proposed installation: Residence of Stephen Dostal, 88 South Main Street, Florence, MA 01062 This installation design will be in general conformance to the manufacturer's specifications, and is in compliance with all applicable laws, codes, and ordinances, and specifically, International Residential Code/IRC 2009, 2011 NEC, and 2012 ICC Energy Code. The spacing and fastening of the Unirac mounting brackets is to have a maximum of 64" o.c.span along the rail between mounting brackets and secured using 5/16" x 3%" length lag bolts. In order to evenly distribute the load across the roof rafters,there shall be a minimum of 2 mounting brackets per rafter& min. 2" penetration of lag bolt per bracket,which is adequate to resist all 115 mph wind live loads including wind shear. The mounting brackets shall alternate between adjacent rafters between rail rows for better distribution of roof load. Double quantity of anchors for modules mounted within 18" of ridge and edges of roof. Rails may be attached to either of two mounting holes in the L-feet. Mounting in the lower hole for a low profile, more aesthetically pleasing installation or mount in the upper hole for a higher profile to maximize airflow under the modules to cool them more. Slide the M-inch mounting bolts into the footing bolt slots.The rails will be attached to the footings with the flange nuts. Very truly yours, `ZH OP, Optimize Engineering Co., � ,� od, RICH S � ARD BRIM m 0 GOROON MECHgNICqL -� Richer r n, N0.49993 v' Massachus Li n e o.49993 c�SrER�G\ '�� TONAL EN CIVIL ELECTRICAL ENGINEERINGENGINEERING % The Conrnton ivealth of NMassach usetts X, Department of lndustrialAccidents Office of Irlvestigationt ��' 1 Congress Street, Suite IOU t�; t;1 Boston,MA 02114-2017 �r= � IVIVIV.rrrass.govldia Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers Applicant Information Please Print LelZibly C � Name(Easiness/OrganizationlIndividual): C y Y� t ti Address: C Ull, >1-- City/State/Zip: Phone#:Are you an employer? Check the a4ropriate box: Type of project(required_): 1. dam a employer with C 4• 1 am a general contractor and 3 6 New construction employees(full and/or par[-time).* have hired the sub-contractors 2. 1 am a sole proprietor or partner- listed on the attached sheet. %. Remodeling ship and have no employees These sub-contractors have g• Demolition working or me in an capacity. employees and have workers g y P �'• 9. Building addition [No workers' comp,insurance comp.insurance.t required.] 5. We are a corporation and its 10. Electrical repairs or additions 3. I am a homeowner doing all work officers have exercised their 11. Plumbing repairs or additions myself. [No workers'comp. right of exemption per MGL 12. Roof repairs insurance required.]t c. 152,§1(4),and we have no employees. [No workers' 13. Other comp.insurance required.] *Any applicant that checks box€t 1 must also fill out the section below showing their workers'compensation policy information. t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such. tContractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have employees. If the sub-contractors have employees,they must provide their workers'comp.policy number. I ant an employer that is providing workers'compensation hisurance for my employees. Below is the policy and job site information. Insurance Company Name: C- f^ Policy#or Self-ins.Lic.#: V V CI CJ 6j Expiration Sob Site Address: ��S y Ny� c:ten ST• City/State/Zip:fl 4P.✓Qt l hoA C j U&`� Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to$1,500.00 and/or one-year imprisonment,as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do lrerebv certify under the pants and penalties of perjury that flit irfortnatiorr provided above is true and correct. Si nature' _ __ ___. 1. e� _ Date; l 0 Phone# Official use ortly. Do not write in this area,to be completed by city or town official. City or Town: Permit/License 4 Issuing Authority(circle one): 1.Board of Health 2. Building Department 3. City/Town Cleric 4.Electrical Inspector 5. Plumbing Inspector 6.Other Contact Person: Phone M. SECTION 8-CONSTRUCTION SERVICES 8.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Holder: (` cPGS l�ti�c�SSc� /0'3L 31 l � , . n/ License Number X lj� &r/15- _ Address Expiration Date Signature Telephone 9.R is red H e 1 nt Contractor Not Applicable ❑ Company Name T Registration Number Address Expiratibn Dat Telephone,-'& %I-az'r SECTION 10-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c.152,§25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes....... 92 No...... ❑ 11. - Home Owner Exemption The current exemption for"homeowners"was extended to include Owner-occupied Dwellings of one(1) or two(2)families and to allow such homeowner to engage an individual for hire who does not possess a license,provided that the owner acts as supervisor.CMR 780, Sixth Edition Section 108.3.5.1. Definition of Homeowner:Person(s)who own a parcel of land on which he/she resides or intends to reside,on which there is,or is intended to be,a one or two family dwelling,attached or detached structures accessory to such use and/or farm structures.A person who constructs more than one home in a two-year period shall not be considered a homeowner. Such"homeowner"shall submit to the Building Official,on a form acceptable to the Building Official,that he/she shall be responsible for all such work performed under the buildine permit. As acting Construction Supervisor your presence on the job site will be required from time to time,during and upon completion of the work for which this permit is issued. Also be advised that with reference to Chapter 152(Workers' Compensation) and Chapter 153(Liability of Employers to Employees for injuries not resulting in Death)of the Massachusetts General Laws Annotated,you may be liable for person(s) you hire to perform work for you under this permit. The undersigned"homeowner"certifies and assumes responsibility for compliance with the State Building Code,City of Northampton Ordinances,State and Local Zoning Laws and State of Massachusetts General Laws Annotated. Homeowner Signature SECTION 5-DESCRIPTION OF PROPOSED WORK(check all applicable) New House ❑ Addition ❑ Replacement Windows Alteration(s) ❑ Roofing ❑ Or Doors D Accessory Bldg. ❑ Demolition ❑ New Signs [0] Decks [C7 Siding[0] Other[A st)Vc Brief Descripti n of Proposed ( �, (v(cl cc` Work:1,s lt�l Yl�� "_Xcet�c� ci f (tit ;��_ +c Alteration of existing bedroom Yes No Adding new bedroom Yes No Attached Narrative Renovating unfinished basement Yes _P No Plans Attached Roll -Sheet 6a. If New house and or addition to existing housing complete the following: a. Use of building: One Family Two Family Other b. Number of rooms in each family unit: Number of Bathrooms c. Is there a garage attached? d. Proposed Square footage of new construction. Dimensions e. Number of stories? f. Method of heating? Fireplaces or Woodstoves Number of each g. Energy Conservation Compliance. Masscheck Energy Compliance form attached? h. Type of construction i. Is construction within 100 ft. of wetlands? Yes No. Is construction within 100 yr. floodplain Yes No j. Depth of basement or cellar floor below finished grade k. Will building conform to the Building and Zoning regulations? Yes No. I. Septic Tank City Sewer Private well City water Supply SECTION 7a-OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT as Owner of the subject proper hereby authorize /i-Irl to act on my behalf, in all ma ers relative to work authorized by this building permit application. Id Signature of Owner Date as Owner/Authorized Agent hereby declare that the statements and intorrtiation on the foregoing application are true and accurate,to the best of my knowledge and belief. Signed under the pains and penalties of perjury. Print Name Signature of Owner/Agent Date . Vv Section 4. ZONING All Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information Existing Proposed Required by Zoning This column to be filled in by Building Department Lot Size Frontage Setbacks Front Side L: R: L: R: Rear Building Height Bldg.Square Footage % Open Space Footage % (Lot area minus bldg&paved parking) #of Parking Spaces Fill: volume&Location A. Has a Special Permit/Variance/Finding ever been issued for/on the site? NO ® DONT KNOW ® YES IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO ® DONT KNOW ® YES IF YES: enter Book Page and/or Document# B. Does the site contain a brook, body of water or wetlands? NO © DONT KNOW 0 YES IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained ® Obtained ® , Date Issued: C. Do any signs exist on the property? YES ® NO IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property? YES ® NO IF YES, describe size, type and location: E. Will the construction activity disturb(clearing,grading,excavation,or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES Q NO IF YES,then a Northampton Storm Water Management Permit from the DPW is required. Department use only City of Northampton Status of Permit: � Building Department Curb Cut/Driveway Permit I 212 Main Street Sewer/Septic Availability j 5 201 LJ) Room 100 Water/We(l Availability ___�_� Northampton, MA 01060 Two Sets of Structural Plans lectric, P;umana&Gas irk Fax 413-587-1272 Piot(Site Plans Northarnt�ion, I�IA C11 Other Specc ify APPLICATION TO CONSTRUCT,ALTER,REPAIR,RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING SECTION 1 -SITE INFORMATION 1.1 Prooerty Address. This section to be completed by office S� C \L^ `� �4 Map Lot Unit a Ial�a nCCen�� / v�n r Zone Overlay District t` Elm St District CB District SECTION 2-PROPERTY OWNERSHIPIAUTHORIZED AGENT 2.1 Owner of Record: c Name(Print) Current Mailing Address: �\fLn Sy eAk, Telephone Si nature 2.2 Authorized Agent: Name(Printj Current Mailing Address: Lr�S 7 Signature Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only completed by ermit applicant 1. Building 7co (a)Building Permit Fee J" 2. Electrical (b)Estimated Total Cost of Construction from 6 3. Plumbing Building Permit Fee 4. Mechanical(HVAC) 5. Fire Protection 6. Total=0 +2+3+4+5) T "71 Check Number This Section For Official Use Only Building Permit Number: Date Issued: Signature: Building Commissioner/Inspector of Buildings Date File 4•13P-2015-0659 APPLICANT/CONTACT PERSON TRINITY SOLAR ADDRESS/PHONE 20 PATTERSON BROOK RD UNIT 10 WEST WAREHAM (508)291-0007 PROPERTY LOCATION 88 SOUTH MAIN ST MAP 23B PARCEL 074 001 ZONE URB(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Buildiny,Permit Filled out ! ,Q Fee Paid X11,` Typeof Construction: INSTALL ROOF MOUNTED 5.865 KW SOLAR ARRAY New Construction Non Structural interior renovations Addition to Existing Accessory Structure Buildina Plans Included: Owner/Statement or License 103631 3 sets of Plans/Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFOIXMATION PRESENTED: Approved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received&Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Min Delay Si cial Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. *Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning&Development for more information. 88 SOUTH MAIN ST BP-2015-0659 GIS#: COMMONWEALTH OF MASSACHUSETTS Ma :Block: 23B-074 CITY OF NORTHAMPTON Lot:-001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: SOLAR PANELS BUILDING PERMIT Permit# BP-2015-0659 Project# JS-2015-001261 Est. Cost: $25219.00 Fee:$156.00 PERMISSION IS HEREBY GRANTED TO: Const.Class: Contractor: License: Use Group: TRINITY SOLAR 103631 Lot Size(sq.ft.): 18643.68 Owner: DOSTAL STEPHEN C&DIANE O Zoning: URB(100)/ Applicant: TRINITY SOLAR AT. 88 SOUTH MAIN ST Applicant Address: Phone: Insurance: 20 PATTERSON BROOK RD UNIT 10 (508)291-0007 WC WEST WAREHAMMA02576 ISSUED ON:1211512014 0:00:00 TO PERFORM THE FOLLOWING WORK:INSTALL ROOF MOUNTED 5.865 KW SOLAR ARRAY - rgh & final inspections required POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupant Signature: FeeType: Date Paid: Amount: Building 12/15/2014 0:00:00 $156.00 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck—Building Commissioner