Loading...
31B-249 (14) 9.3 Approvals A. After the successful completion of the Engineer's Inspection and Testing, the installing Contractor shall submit an NFPA 72 Test Certificate. The test certificate shall be added into the Close-Out Package to be submitted to the Northampton Fire Department. The test certificate shall also be submitted to the Local Building Inspector. B. The Installer shall submit a signed affidavit stating that the system has been installed in accordance with the plans and specifications and in accordance with the applicable codes and standards. C. The Design Engineer or the Engineer of Record shall submit a signed affidavit stating to the Northampton Fire department and the Local Building Inspector that the systems have been visually inspected and tested and that the system was installed in accordance with the plans and specifications. *** End of Basis of Design Narrative *** L&S 2133 Page 13 MEMEMENNOW 3. New and modified conductors shall be tested for stray voltages between conductors and between conductors and ground, for ground faults, for short circuits, for loop resistance and for supervision. 4. New, relocated, or relabeled smoke detectors shall be tested using smoke or listed aerosol. 5. Existing Manual pull stations serving the area shall be tested by initiating an alarm in accordance with the manufacturer's published instructions. 6. Existing Tamper switches serving the area shall be tested to ensure that a supervisory signal is initiated within the first two revolutions. 7. Existing water flow devices including located at the main riser serving the space shall be tested by flowing water through an inspector's test connection. 8. Notification audible devices shall be tested by measuring sound pressure levels with sound level meter meeting ANSI SI.4a, Type 2 requirements. 9. Notification visual devices shall be tested by observing strobe operation and verifying field settable candela setting. 9.2 Testing Schedule A. Upon completion of the fire alarm system rough-in, the Contractor shall request a Fire department Rough-in inspection. B. Prior to the Engineer's test of the fire alarm system, the installing Contractor shall test the system to verify its operation and components. C. After the Installing Contractor successfully tests the fire alarm system, the Contractor shall schedule the Engineer's test. The Engineer's test shall include testing 100% of the devices and equipment modified under this project. Upon successful completion of the Engineer's Test,the NFPA Test Report shall be submitted along with appropriate affidavits as part of a close-out package to the Northampton Fire Department and the Local Building Inspector. D. After the Engineer's inspection and testing is complete and the close-out package is submitted to the Northampton Fire Department and the Local Building Inspector,the Contractor shall schedule the Fire Department Acceptance Test with the Northampton Fire Department and the Local Building Inspector. L&S 2133 Page 12 Table 5.1 Summary of Sprinkler System Inspection, Testing, and Maintenance Item Activity Frequency Reference Gauges(dry,preaction, and deluge Inspection Weekly/monthly 5.2.4.2, 5.2.4.3 systems) Control valves Inspection Weekly/monthly Table 12.1 Alarm devices Inspection Quarterly 5.2.6 Gauges(wet pipe systems) Inspection Monthly 5.2.4.1 Hydraulic nameplate Inspection Quarterly 5.2.7 Buildings Inspection Annually(prior to freezing weather) 5.2.5 Hanger/seismic bracing Inspection Annually 5.2.3 Pipe and fittings Inspection Annually 5.2.2 Sprinklers Inspection Annually 5.2.1 Spare sprinklers Inspection Annually 5.2.1.3 Fire department connections Inspection Quarterly Table 12.1 Valves(all types) Inspection Table 12.1 Alarm devices Test Quarterly/semiannually 5.3.3 Main drain Test Annually Table 12.1 Antifreeze solution Test Annually 5.3.4 Gauges Test 5 years 5.3.2 Sprinklers—extra-high temperature Test 5 years 5.3.1.1.1.3 Sprinklers—fast response Test At 20 years and every 10 years thereafter 5.3.1.1.1.2 Sprinklers Test At 50 years and every 10 years thereafter 5.3.1.1.1 Valves(all types) Maintenance Annually or as needed Table 12.1 Obstruction investigation Maintenance 5 years or as needed 13.2.1, 13.2.2 Low point drains(dry pipe system) Maintenance _Annually prior to freezing and as needed _12.4.4.3.3 C. All features, devices, components, and modes of operation of the fire alarm system shall be tested for acceptance in accordance with NFPA 72. D. Testing personnel for the fire alarm system shall be qualified and experienced in the arrangement and operation of interface equipment and fire safety functions. E. Before to proceeding with testing, all persons and facilities receiving alarm, supervisory or trouble signals and all occupants shall be notified of the testing to prevent unnecessary response. The same shall be notified when the testing is complete. F. Prior to Fire Department Testing, the fire alarm system shall undergo a complete engineer's test to ensure proper operation. The Engineer's test shall include the following: 1. Prior to operational testing, the system components and devices shall be visually inspected. 2. The fire alarm control panel and remote annunciator LCD display and LED indicators shall be tested to verify that the alarm, trouble and supervisory signals from the relocated or new devices are properly displayed. L&S 2133 Page 11 of events shall be activated automatically via smoke detector, heat detector, or flow switch. C. Initiation of the fire alarm sequence of events will immediately and simultaneously activate all horns and visual units throughout the building to notify occupants, and perform all activities as programmed. The Fire Alarm control panel shall send an alarm signal to the Campus Police Master Fire Control Panel, personnel of which will then notify the Northampton Fire Department, as well as display alarm condition at the fire alarm control panel. D. The Fire Alarm System reset button returns the system to its normal state after all alarm conditions have been cleared. Display messages shall provide operator assurance of the sequential steps as they occur. The Fire Alarm Control Panel is equipped with battery back up capable of 24-hours of standby and 15 minutes of alarm. The Fire Alarm Control Panel is equipped with visible and audible signals to indicate alarm and trouble conditions. E. Activation of any tamper switch shall initiate a local supervisory signal at the fire alarm control panel and shall send the appropriate supervisory signal via the Fire Alarm Control Panel to the Campus Police Master Fire Control Panel, personnel of which will then notify the Northampton Fire Department. Campus personnel shall respond in accordance with policy to a tamper switch supervisory signal, as well as carbon monoxide condition. SECTION 9—TESTING CRITERIA AND METHODS 9.1 Testing Methods A. All sprinkler and standpipe systems shall be tested in accordance with the requirements of NFPA 25 (2007 Edition). Complete system flow test will be conducted utilizing the combination test & drain connection on the riser-check and a test certificate shall be issued by the sprinkler contractor to the Springfield Fire Department and the Local Building Inspector. B Testing and maintenance program in accordance with the requirements of NFPA 25 shall be adhered to by the building owner and a Massachusetts Licensed Sprinkler contractor. (See copy of Table 5.1 below for testing criteria) L&S 2133 Page 10 Existing Fire Protection Service is located along the exterior wall of the building nearest Chapin Way, on the lower level, This is a dedicated mechanical space in the lower level, and not accessible to the public. The Main Fire Alarm Control Panel is located on the main floor, adjacent the electrical room. SECTION 6 - DESIGN METHODOLOGY The sprinkler system is designed for light hazard occupancy, with ordinary hazard coverage in the storage areas, in accordance with NFPA 13 requirements. The light hazard areas shall be designed to a density of.10/1500 square feet with a 100 gpm hose allowance. Areas throughout the building that are ordinary hazard, such as storage spaces, the system will be designed to ordinary hazard group density with 250 gpm added for hose stream The existing fire alarm system shall remain. Within the renovated spaces, notification coverage shall be expanded as required to provide proper coverage to the renovated space, in accordance with NFPA 72. The existing fire alarm control panel programmed sequence of operation shall remain and be modified to include the new address labels where required. The existing sequence of operation associated with the sprinkler system monitors shall remain as well. The new visual and audible notification appliances shall be supplied by an expansion of the existing notification circuit loop. SECTION 7 - SPECIAL CONSIDERATIONS This scope of work is limited to a Level 1 Alteration, thus the space modifications are minor in scope. Only modifications to the existing systems serving the work areas are considered. SECTION 8 - SEQUENCE OF OPERATIONS 8.1 Fire Alarm System Sequence of Operation: A. This fire alarm system is designed to detect fires normally associated with this type of facility. The activation of a fire alarm initiating device will send a signal via the FACP and Campus loop system to the Campus Police Master Fire Control Panel, which will then be relayed to notify the Northampton Fire Department. B. The system fire alarm sequence of event can be activated manually through the use of manual pull stations. The system fire alarm sequence L&S 2133 Page 9 utilizing addressable control relays interconnected to the fire alarm control panel. The Fire Alarm Control Panel shall indicate a Supervisory condition and relay of the Carbon monoxide supervisory signaling shall be as directed by the fire department. F. Remote Alarm Reporting. The existing Fire Alarm Control Panel is connected to the Campus Fire Alarm Loop. This is be used to provide notification to the Campus Police station Master Fire Alarm Control Panel. The Campus monitoring personnel shall relay the alarm information to appropriate responders, including the Northampton Fire Department, as required by code, in the event of an alarm or other condition. G. There is no fire department Knox (key) box located at the Fire Department Primary response point. This area is outside the scope of work. 5.8 Emergency Alarm Systems - Section 908 Not Applicable 5.9 Smoke Control Systems - Section 909 Not Applicable 5.10 Smoke and Heat Vents - Section 910 Not Applicable 5.11 Fire Command Center - Section 911 Not Applicable 5.12 Fire Department Connections - Section 912 The pumper connection is an existing 3 x 2 1/2" Siamese type connection located on the Federal Street side of the building. Two Additional pumper connections serving other areas of the building are located at both the front and rear of the building. The Fire Hydrant nearest the pumper connection is located on Federal Street, at the corner of Mary Keller Bennett Way. 5.13 Fire Pumps - Section 913 Not Applicable. 5.14 Fire protection Systems Equipment Room Identification - Section 914.2 L&S 2133 Page 8 3. Elevator recall system smoke detection is existing at the building for code compliance interaction with the elevator(s). C. A fire protective signaling system will be installed in the areas of work in accordance with 780 CMR and NFPA 72. Fire protection signaling and detection devices in this building will include the following features: 1. Audio notification devices are wall mount speaker/strobe appliances, both existing and to be installed/relocated as shown on plans. It is the intent of this design that audible notification devices achieve sound pressure levels of 15dB above ambient sound levels for the business occupancy, or 5dB above maximum sound pressure levels having a continued duration of at least one minute. 2. Visual notification devices are both existing and to be installed/relocated as shown on the plans. It is the intent of this design that the area of work has proper strobe coverage throughout all areas. Visual notification devices shall be synchronized throughout the area. 3. There is an exterior strobe located outside the fire department main response point. This area is outside the scope of work. 4. New visual and audible notification devices that may be required for adequate coverage of the renovated spaces, shall be supplied from the existing signaling circuit serving the respective floor. D. Tamper and Flow switches are existing and installed where required on the sprinkler service equipment. The tamper and flow switches are located in the lower level at the water entry location. 1. The tamper switches are monitored by the fire alarm system using addressable interface modules. Activation of a tamper switch shall initiate a supervisory signal sequence of events. 2. The flow switches are monitored by the fire alarm system using addressable interface modules. Activation of a flow switch shall initiate the fire alarm system sequence of events. Additionally, flow switch activation shall engage the exterior blue strobe light. E. Carbon monoxide detection devices are required to be installed as part of this project. The devices will be interconnected and monitored by the fire alarm control panel serving the building. Two C/O detection devices shall be located in the proximity of each of the exhaust hoods installed in the kitchen area. In the event of the Carbon monoxide detector entering alarm, The fire alarm system shall send a signal to the gas soloniod valve interface module, to disengage the gas supply to the kitchen. Control of the solenoid valve shall be accomplished L&S 2133 Page 7 5.5 Standpipe System - Section 905 An existing 6" fire service enters the First Floor of this facility and feeds the sprinkler and standpipe riser station serving the entire area covered under this work scope. The standpipe feed runs through the first floor of the building and feeds 4" standpipe risers serving the 2nd and 3rd floor library level. 5.6 Portable Fire Extinguishers - Section 906 A. Hazard Class: Ordinary Hazard B. Size and Type of Extinguishers: 20 LB, Suitable for A/B/C C. Extinguishers are existing to remain where installed. This includes equipment located in the Cafe & adjoining receiving area subject to modifications in this project. 5.7 Fire Alarm and Detection - Section 907 A. The existing Fire Alarm Control Panel has full featured analog/addressable detection loop(s) and shall include the following: 1. The fire alarm system features an addressable, system integrated Fire Alarm Control Panel, with voice evacuation features. The Fire Alarm Control Panel is located in the rear entry vestibule, at the fire department primary response point. 2. Emergency power supply for the fire alarm panel is supplied by battery packs located at the FACP. B. System Initiation Devices are existing and meets the minimum requirements of the code in the areas of renovation and shall include the following: I. All existing manual pull stations shall remain. Renovations are limited to Cafe & dining spaces. No additional manual pull stations are required in the renovated spaces. Manual pull stations within 5 feet of each exit door and at all entry points leading to an egress stairway in the work scope area. All pull stations are dual action. Existing installation meets requirements for this building space (per 780CMR 907.2.2) 2. System connected smoke detectors are existing in the renovated areas of the building. Existing devices shall be removed and reinstalled as required to provide adequate coverage for the space. They shall be installed as as detailed on the plans. Activation of any system smoke detector will initiate the fire alarm system sequence of events for the building. L&S 2133 Page 6 An existing 6" fire service enters the Second Floor of this facility nearby Chapin Way, and feeds the sprinkler and standpipe riser station. The standpipe feed runs throughout the first floor of the building and feeds standpipe risers located adjacent the stairwells.. Under this contract, the Cafe space being renovated shall have the existing sprinkler system reworked to properly provide full automatic sprinkler protection, in compliance with code. The pumper connection serving the area subject to renovation is an existing 3 x 2 1/z" Siamese type connection located on the Chapin Way side of the building. This fire pumper location is one of three located on the building. A. Installation 1. The fire sprinkler system is designed in accordance with NFPA 13. 2. The existing branch sprinkler line installation shall generally remain where installed. Minimal additional work is required as part of this contract. 3. Rework existing local branch lines as required. and install heads on existing and reworked branch lines, to facilitate new construction as required to meet criteria ofNFPA 13. 4. Install dry head on existing branch line to protect cold storage rooms. B. Equipment 1. Interior piping is to be ASTM A53, A106, A120, or A135, with threaded, flanged, or grooved couplings and fittings: Schedule 10 seamless ERW ASTM A135 with rolled grooves for 2" and larger, Schedule 40 black steel with screwed fittings for 1-1/2" and smaller. C. Design Criteria 1. The system is designed for light hazard occupancy, with ordinary hazard coverage in the storage areas. The light hazard areas shall be designed to a density of.10/1500 square feet with a 100 gpm hose allowance. 2. For areas throughout the building that are ordinary hazard, such as storage spaces, the system will be designed to ordinary hazard group density with 250 gpm added for hose stream. 5.4 Alternative Automatic Fire Extinguishing System - Section 904 Not Applicable L&S 2133 Page 5 SECTION 4 - DESIGN RESPONSIBILITY The designs for both the renovations to the existing fire protection sprinkler system and fire detection and alarm systems were prepared by: Lindgren & Sharples, P.C. 435 Cottage Street Springfield, MA 01104-4005 413-732-4336 SECTION 5 - FIRE PROTECTION SYSTEMS TO BE INSTALLED PER CHAPTER 9 5.1 Fire protection Systems Equipment Identification and Operation Signs There is an existing Fire Protection System installed to serve portions of the existing building. The area of work for this project is currently protected by the existing system. The existing Sprinkler Service is identified with a permanently marked weatherproof metal or rigid plastic sign secured with corrosion-resistant wire. Signage is in place at the main riser location in the lower level. Additional Signage/ tags are available and include the following information: Location of the design area or areas, Discharge densities over the design area or areas, Required flow and residual pressure demand at the base of the riser, Occupancy classification or commodity classification and maximum permitted storage height and configuration. Hose stream demand included in addition to the sprinkler demand. 5.2 Carbon Monoxide Detection Carbon monoxide detection devices are required to be installed as part of this project. The devices will be interconnected and monitored by the fire alarm control panel serving the building. Two C/O detection devices shall be located in the proximity of each of the exhaust hoods installed in the kitchen area. In the event of the Carbon monoxide detector entering alarm, The fire alarm system shall send a signal to the gas soloniod valve interface module, to disengage the gas supply to the kitchen. The Fire Alarm Control Panel shall indicate a Supervisory condition and relay of the Carbon monoxide supervisory signaling shall be as directed by the fire department. 5.3 Automatic Sprinkler System - Section 903 The area of work is served by the building's sprinkler system. Under this contract all spaces in the area of work, as required by code shall be fitted with a full automatic sprinkler system to facilitate the new construction plan. The fire protection subcontractor shall perform a flow test and design a hydraulically calculated system in accordance with NFPA 13, with drawings submitted to Lindgren & Sharples and to the City of Northampton for approval prior to installation. L&S 2133 Page 4 the first and second floor of the building have grade access with one story located above the second level grade access. SECTION 2—BUILDING AND SITE ACCESS The building is located on the Smith College Campus, located at 100 Elm Street in Northampton Massachusetts. The Fire Department personnel and rescue vehicles can access the front of the building using Elm Street. The rear of the building may be accessed via Chapin Way, which is part of the campus roadway system. The Fire Department Primary Response Point and location of the fire alarm system control panel and is located on the second (main) level, accessible from the Chapin Way campus road, accessible from Elm Street. The fire department secondary response point is the Main level Front building entry, and is accessible from Elm Street. The sprinkler system pumper connection is an existing 3 x 2 '/2" Siamese type connection located on the Chapin Way side of the building. SECTION 3 - APPLICABLE LAWS. REGULATIONS & STANDARDS The changes to the building meet the defmition of a Level 1 alteration, thus required renovations are minimal in scope. Systems were designed in compliance with the following: 1. 780 CMR: Massachusetts State building Code —8"' Edition, Chapter 9: Fire Protection Systems. 2. NFPA 10— Portable Fire Extinguishers. 3. NFPA 13 — 2007 Edition: Installation of Sprinkler Systems. 4. NFPA 14—2007 Edition: Installation of Standpipe Systems. 5. NFPA 24—2007 Edition: Fire Service Water Mains. 6. NFPA 25 — Latest adopted Edition 7. NFPA 45 — Latest adopted Edition: Standard for Fire Protection for Laboratories using chemicals 8. NFPA 54, chapter 10. 9. NFPA 72—2010 Edition: National Fire Alarm Code. 10. NFPA 720—2005 Edition. 11. MGL 26G: Sprinkler Systems. 12. 248 CMR: Gas Code. 13. 521 CMR: Massachusetts Architectural Access Board Regulations. 14. 527 CMR: Massachusetts Fire Prevention Regulations 15. 527 CMR 12.00: Massachusetts Electrical Code. 16. 527 CMR 14.00: Flammable Liquids, Solids & Gases. 17. 527 CMR 31.00: Carbon Monoxide Alarms. L&S 2133 Page 3 SMITH COLLEGE CAMPUS CENTER CAFE RENOVATIONS FIRE PROTECTION AND ALARM SYSTEM BASIS OF DESIGN NARRATIVE May 21s' 2014 Information required pursuant to the Massachusetts State Building Code 780 CMR, 903.0. Owner: Smith College Northampton, Massachusetts Designers of Record: Lindgren & Sharples, P.C. Consulting Engineers Date of Submittal: May 21, 2014 INTRODUCTION This project consists of renovations to approximately 3,500 square feet of the Cafe' located on the first floor level of the existing 3-story campus center building. The Building has a grade accessible lower level with limited access to the public, and contains no accessible attic rooms. The majority of the building is accessible to the student population for general campus functions, and student service offices. This includes study areas, lounge areas, mail distribution areas, ancillary classrooms, and offices. A minor reworking of the sprinkler system is required to accommodate the new cafe layout. Also, a minor reworking and expansion of the existing addressable fire alarm system will also take place to provide proper notification coverage in the areas in the scope of work, proper monitoring of the ansul system & interaction with the gas solenoid valves serving equipment in the space. The design shall bring the cafe into compliance with current codes and standards. SECTION 1 —BUILDING DESCRIPTION The area where work is to be performed is classified as a Use Group: Type B (Business). The building is classified as a mixed Use Group: Type A3 (Assembly), A2 (Assembly), Sl (Storage), and M (Merchantile). The Construction Type is II-B, Non combustible exterior walls with Protected Combustible interior elements, as defined by the Massachusetts State Building Code. The building footprint is approximately 20,000 square feet, and contains a total of three levels. The total building square footage is approximately 54,200 square feet. The area of the building subject to minor renovations constitutes approximately 3500 square feet of the lower level. Both L&S 2133 Page 2 NARRATIVE REPORT FOR FIRE PROTECTION & ALARM SYSTEMS AT SMITH COLLEGE CAMPUS CENTER CAFE RENOVATIONS 100 ELM ST. NORTHAMPTON, MA PREPARED BY: LINDGREN & SHARPLES, P.C. CONSULTING ENGINEERS 435 COTTAGE STREET, SUITE 1 SPRINGFIELD, MA 01104-4005 TEL. 413-732-4336 MAY 21St, 2014 Initial Construction Control Document To be submitted with the Y building permit application by a Registered � � d Design Professional for work per the 8t' edition of the Massachusetts State Building Code, 780 CMR, Section 107.6.2 Project Title: Smith College Campus Center Cafe Renovations Date: 5/20/14 Property Address: Smith College, Northampton, MA Project: Check(x) one or both as applicable: New construction Existing Construction X Project description: Renovations to the existing cafe and kitchen. I, Mark W. Felgate, MA Registration Number: 47531, Expiration date: June 30, 2014, am a registered design professional, and hereby certify to the best of my knowledge, information and belief,that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning': Entire Project Architectural Structural Mechanical Fire Protection (X) Electrical Other: for the above named project and that such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted engineering practices for the proposed project. I understand and agree that I (or my designee)shall perform the necessary professional services in accordance with the Professional Standard of Care,and be present on the construction site on a regular and periodic basis to: 1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the contractor in accordance with the requirements of the construction documents. Such review shall not diminish or relieve the Contractor of its submittal and other responsibilities. 2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine if the work is being performed in a manner consistent with the approved construction documents and this code. The contractor shall be responsible for performing the work in accordance with the contract documents and shall be exclusively responsible for its construction means, methods, sequences and procedures,and for construction safety. 4._ The performance of the services shall not require any_ssecial testing or inspections unless specifically lly stated in the Code. _ _ When required by the building official, I shall submit field/progress reports (see item 3.)together with pertinent comments, in a form acceptable to the building official. Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'. Enter in the space to the right a"wet"or ���,1 OF p � ., electronic signature and seal: " Phone number: (413)732-4336 Email: mfelgate @lindgrensharples.com R ISTF NAL Trial Version 10 09 2012 Initial Construction Control z Document To be submitted with the " building permit application by a Registered � � d Design Professional for work per the 8`" ve edition of the Massachusetts State Building Code, 780 CMR, Section 107.6.2 Project Title: Smith College Campus Center Cafe Renovations Date: 5/20/14 Property Address: Smith College,Northampton, MA Project: Check(x) one or both as applicable: New construction Existing Construction X Project description: Renovations to the existing cafe and kitchen. I, Charles P. Sharples, MA Registration Number: 28940, Expiration date: June 30, 2014, am a registered design professional, and hereby certify to the best of my knowledge, information and belief, that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning': Entire Project Architectural Structural (X)Mechanical Fire Protection Electrical Other: for the above named project and that such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR), and accepted engineering practices for the proposed project. I understand and agree that I (or my designee)shall perform the necessary professional services in accordance with the Professional Standard of Care, and be present on the construction site on a regular and periodic basis to: 1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the contractor in accordance with the requirements of the construction documents. Such review shall not diminish or relieve the Contractor of its submittal and other responsibilities. 2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine if the work is being performed in a manner consistent with the approved construction documents and this code. The contractor shall be responsible for performing the work in accordance with the contract documents and shall be exclusively responsible for its construction means, methods, sequences and procedures, and for construction safety. 4._ The performance of the services shall not require any testin inpections unless specifically stated in the Code. _ _ —_- When required by the building official, I shall submit field/progress reports (see item 3.)together with pertinent comments,in a form acceptable to the building official. Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'. Enter in the space to the right a"wet" or 0, AI electronic signature and seal: C!-�IRRLES G, 1( P. Phone number: (413)732-4336 Email: csharples@lindgrensharples.com I 5 SHARPLES 28940 Aga��or Fsu R Trial Version 10 09 2012 Initial Construction Control Document W To be submitted with the building permit application by a Registered Design Professional for work per the 81h edition of the Massachusetts State Building Code, 780 CMR, Section 107 Project Title: Structural Design of Smith College Campus Center Cafe Renovations Date: 20 May Property Address: Smith College, Northampton, MA Project: Check(x) one or both as applicable: New construction X Existing Construction Project description: Renovation of existing building for Campus Center Cafe, Smith College, Northampton, MA I Pedro J. Sifre MA Registration Number: 47204 Expiration date: 6/30/2014 , am a registered design professional, and I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning': Architectural X Structural Mechanical Tire Protection Electrical Other: for the above named project and that to the best of my knowledge, information, and belief such plans, computations and specifications meet the applicable provisions of the Massachusetts State. Building Code, (780 CMR), and accepted engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary professional services and be present on the construction site on a regular and periodic basis to: 1. Review, for conformance to this code and the design concept, shop drawings, samples and other submittals by the contractor in accordance with the requirements of the construction documents. 2. Perform the duties for registered design professionals in 780 CMR Chapter 17, as applicable. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine if the work is being performed in a manner consistent with the approved construction documents and this code. Nothing in this document relieves the contractor of its responsibility regarding the provisions of 780 CMR 107. When required by the building official,I shall submit field/progress reports (see item 3.) together with pertinent comments, in a form acceptable to the building official. Upon completion of the work, I shall submit to the building official a `Final Construction Control Document'. Enter in the space to the right a "wet" or electronic signature and seal: P R0 a SIFRE a STRUCTURAL cn Phone number: 781.907.9000 Email: pjsifre @sgh.com ,0 9 No.47204 0 Building Official Use Only Building Official Name: Permit No.: Date: Note 1.Indicate with an `x' project design plans,computations and specifications that you prepared or directly supervised. If`other' is chosen, provide a description. I:\BOS\Projects\2014\140267.00-CAFE\W P\001 PJSifre-affidavit-140267.00.cah.docx Version 06 112013 A N A L V,G U E S T U D I O ANALOGUE STUDIO. LLC 21 DRYDOCK AVENUE, 6" FLOOR BOSTON, MA 02210 TIF 617.440.7568 ANALOGUESTUDIO.COM Construction Control Affidavit PROJECT NAME/NUMBER: Smith College LOCATION: Northampton,MA SCOPE OF PROJECT: Campus Center Cafe Renovations DATE: 20 May 2014 I,Vince Pan MA Registration Number 20568 Expiration Date 08/31/2014,am a registered design professional, and hereby certify,to the best of my knowledge, information and belief,that I have prepared or directly supervised the preparation of all design plans,computations and specifications concerning: [ ] Entire Project [x]Architectural [ ]Structural [ ] Mechanical [ ] Fire Protection [ ] Electrical [ ]Other for the above named project and that such plans,computations and specifications meet the applicable provisions of the Massachusetts State Building Code, (780 CMR),and accepted engineering practices for the proposed project. I understand and agree that I (or my designee) shall perform the necessary professional services in accordance with the Professional Standard of Care,and be present on the construction site on a regular and periodic basis to: 1. Review,for conformance to this code and the design concept, shop drawings, samples and other submittals by the contractor in accordance with the requirements of the construction documents. Such review shall not diminish or relieve the Contractor of its submittal and other responsibilities. 2. Perform the duties for registered design professionals in 780 CMR Chapter 17,as applicable. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine if the work is being performed in a manner consistent with the approved construction documents and this code.The contractor shall be responsible for performing the work in accordance with the contract documents and shall be exclusively responsible for its construction means,methods, sequences and procedures, and for construction safety. 4. The performance of the services shall not require any special testing or inspections unless specifically stated in the Code. When required by the building official, I shall submit field/progress reports together with pertinent comments, in a form acceptable to the building official. Upon completion of the work, I shall submit to the building official a`Final Construction Control Document'. Then personally appeared the above named Vince Pan and made oath that the above statement by him is true. Before me, X �n a Notary Pu i -''lf z FELIPE NICOLAOU Pubic,CamnanwMNh at Maadwwm� OF My commission #)NO"MyCaraissimEgi►K,Wwg22.2021 The Commonwealth of Massachusetts Department of Industrial Accidents Office of Investigations 0 1 Congress Street, Suite 100 =W Boston,MA 02114-2017 www mass.gov/dia Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers Applicant Information Please Print Legibly Name (Business/Organization/Individual): Petra Construction Corporation Address:98 Rebeschi Drive City/State/Zip:North Haven, CT 06473 Phone #:203-865-6043 Are you an employer?Check the appropriate box: Type of project(required): 1.❑■ I am a employer with 85 4. ❑ I am a general contractor and I employees(full and/or part-time).* have hired the sub-contractors 6. ❑New construction 2.❑ I am a sole proprietor or partner- listed on the attached sheet. 7. ❑Remodeling ship and have no employees These sub-contractors have 8. ❑Demolition working or me in an capacity. employees and have workers' g y p �'• $ 9. E] Building addition [No workers' comp. insurance comp. insurance. required.] 5. ❑ We are a corporation and its 10.❑ Electrical repairs or additions 3.❑ I am a homeowner doing all work officers have exercised their 11.❑ Plumbing repairs or additions myself. [No workers' comp. right of exemption per MGL 12.❑ Roof repairs insurance required.] t c. 152, §1(4),and we have no Contractor employees. [No workers' 13.■ Other comp. insurance required.] *Any applicant that checks box#I must also fill out the section below showing their workers'compensation policy information. t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such. Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have employees. If the sub-contractors have employees,they must provide their workers'comp.policy number. I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site information. Insurance Company Name: North River Insurance Co. Policy#or Self-ins. Lic. #:4087062027 Expiration Date:July 1, 2014 Job Site Address: 126 West Street City/State/Zip: North Hampton, MA 01063 Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to$1,500.00 and/or one-year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do hereby certify u r the pains and penalties of perjury that the information provided above is true and correct. Signature: Date:May 20 2014 Phone#: 203-865-6043 Official use only. Do not write in this area,to be completed by city or town official. City or Town: Permit/License# Issuing Authority(circle one): 1.Board of Health 2.Building Department 3. City/Town Clerk 4. Electrical Inspector 5.Plumbing Inspector 6.Other Contact Person: Phone#: Versionl.7 Commercial Building Permit May 15,2000 SECTION 10-STRUCTURAL PEER REVIEW(780 CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes 0 No Q SECTION 11 -OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT Karla Youngblood _ as Owner of the subject property - - _. ------ w .Petra Construction Corporation lto hereby authorize act on my beh f, i ers relativ o work authorized by this building permit application. 05/21/2014 gnatu f er Date Guido L Petra _ as Owner/Authorized Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge and belief. Signed under the pains and Penalties of periury. .Guido L. Petra Print Name -- '05/21/2014 Signature of Owner/Agent Date SECTION 12-CONSTRUCTION SERVICES 10.1 Licensed Construction Supervisor. Not Applicable ❑ Name of License Holder:David Perry CF-055449 r License Number 9 Sawmill Ridge Rd. Haverhill,MA 01832 03/29/2016 '� Address Expiration Date (203) 627-5488^ gnature Telephone SECTION 13-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c.152,§25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes 0 No 0 Version 1.7 Commercial Building Permit May 15,2000 SECTION 9-PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES-FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116(CONTAINING MORE THAN 35,000 C.F.OF ENCLOSED SPACE) 9.1 Registered Architect: a. ... Not Applicable ❑ /�► �,� Stltc LL(- Name(Registrant): Registration Number 1(617)440-7568 ; Expiration Date Signature Telephone 9.2 Registered Professional Engineer(s): Name Area of Responsibility s Address Registration Number Signature Telephone Expiration Date j NName Area of Responsibility a n ._..v _ �. . � � 1 t Address Registration Number Signature Telephone Expiration Date i Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date a i Name Area of Responsibility Address Registration Number k Signature Telephone Expiration Date 9.3 General Contractor :Petra Construction Corporation Not Applicable ❑ �.. Company Name: ;Kelly O'Brien Responsible In Charge of Construction 98 Rebeschi Dr. North Haven, CT 06473 Addre s /� �C' , ��i�� (203) 865-6043 Sign ture Telephone Versionl.7 Commercial Building Permit May 15,2000 8. NORTHAMPTON:ZONING Existing Proposed Required by Zoning This column to be filled in by Building Department Lot SizeN/A v _, Frontage Setbacks Front Side L�— R.f L:'- R°. m Rear Building Height Bldg. Square Footage % � Open Space Footage _. % (Lot area minus bldg&paved x parking) #of Parking Spaces -- _ - Fill: volume&Location) ---a.- A. Has a Special Permit/Variance/Finding ever been issued for/on the site? NO 0 DON'T KNOW (F) YES IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO 0 DON'T KNOW YES 0 IF YES: enter Book ` Page, and/or Document# B. Does the site contain a brook, body of water or wetlands? NO 0 DON'T KNOW (F) YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained Obtained ® , Date Issued: C. Do any signs exist on the property? YES NO IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property? YES NO IF YES, describe size, type and location: E. Will the construction activity disturb(clearing,grading, excavation, or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES 0 NO IF YES,then a Northampton Storm Water Management Permit from the DPW is required. Version 1.7 Commercial Building Permit May 15,2000 SECTION 4-CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE Interior Alterations ❑✓ Existing Wall Signs ❑ Demolition❑✓ Repairs❑ Additions ❑ Accessory Building❑ Exterior Alteration ❑✓ Existing Ground Sign❑ New Signs❑ Roofing❑✓ Change of Use❑ Other❑ Brief Description The project consists of the renovation of the the existing Cafe.Work includes demolition of existing kitchen equipment and interior finishes,modifications to the existing floor plan and associated MEP work,installation of new kitchen equipment and Of Proposed Work: interior finishes. SECTION 6-USE GROUP AND CONSTRUCTION TYPE USE GROUP(Check as applicable) CONSTRUCTION TYPE A Assembly ❑ A-1 ❑ A-2 ❑ A-3 ❑ 1A ❑ A-4 ❑ A-5 ❑ 1B ❑ B Business ❑ 2A ❑ E Educational ❑ 2B ❑✓ F Factory ❑ F-1 ❑ F-2 ❑ 2C ❑ H Hi h Hazard ❑ 3A ❑ I Institutional ❑ 1-1 ❑ 1-2 ❑ 1-3 ❑ 3B ❑ M Mercantile 4 ❑ R Residential ❑ R-1 ❑ R-2 ❑ R-3 ❑ 5A ❑ S Storage ❑✓ S-1 ❑ S-2 ❑ 5B ❑ U Utility ❑ Specify: { t M Mixed Use ❑ Specify: S Special Use ❑ Specify: ` COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS,ADDITIONS AND/OR CHANGE IN USE Existing Use Group: iA-2 Dining Facility _ Proposed Use Group. ;A-2 Dining Facility Existing Hazard Index 780 CMR 34). Proposed Hazard Index 780 CMR 34). 5, n _. ..W., . . SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY Floor Area per Floor(sf) _ 1 St 151 ; gy20,231 ��... 2nd; 20,094 2nd 3rd 3rd 13,952 _. 4th 4th Total Area(sf) i 54,27 7 Total Proposed New.Construction(sf) Total Height(ft) Total Height ft 7.Water Supply(M.G.L.c.40,§54) 7.1 Flood Zone Information: 7.3 Sewage Disposal System: Public 0 Private ❑ I Zone Outside Flood Zone E] Municipal ❑ On site disposal system❑ Versionl.7 Commercial Building Permit May 15,2000 -�_.�. Depart tent use or City of Northampton Statusf Peres Y Z $ Za�� ! Building Departmentr�ittlneway Petrrstt _° �� 1, t re e P;id yes 212 Main Street Selmer/fie "tt/�+ .. � Y Ayaltab�tty ! k i � I �� gF Room 100 WM6e/W 1[AvallabtHty lectric PlUmbin-,t&G8 , M� ,;tceo Northampton, MA 01060 Trri Sets'bf Structural s phone 413-587-1240 Fax 413-587-1272 PlptfSitePians . O#h�r:Spec � � r fix f APPLICATION TO CONSTRUCT, REPAIR, RENOVATE,CHANGE THE USE OR OCCUPANCY OF,OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 SITE INFORMATION 1.1 Property Address: This section to be completed by office 100 Elm Street Map Lot Unit ;Northampton, MA 01063 Zone Overlay District Elm St.District CB District SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: Smith College 126 West Street Northampton, MA 01063 Name(Print) Current Mailing Address: (413) 584-2700 Signature Telephone 2.2 Authori d Agent: ido . w 9.8. R.ea be..schi Drive L P_etra, _ . .. - Name(Print) Current Mailing Address: (203) 865-6043 � Signature Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only com feted by ermit applicant 1. Building (a)Building Permit Fee $547,674.00.` 2. Electrical (b)Estimated Total Cost of $42,341.00 Construction from 6 3. Plumbing $82,556.00 Building Permit Fee , 4. Mechanical(HVAC) 5. Fire Protection $73,009.00 6. Total=(1 +2+3+4+5) Check Number This Section For Official Use Only Building Permit Number Date Issued Signature: Building Commissioner/Inspector of Buildings Date File#BP-2014-1264 APPLICANT/CONTACT PERSON PETRA CONSTRUCTION CORP ADDRESS/PHONE 98 REBESCHI DR NORTH HAVEN (203)865-6043 PROPERTY LOCATION 100 ELM ST-CAMPUS CENTER MAP-3 I B PARCEL 249 001 ZONE EU(100)/URC(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out Fee Paid Tyneof Construction: RENOVATE CAFE New Construction Non Structural interior renovations Addition to Existing Accessory Structure Buildinizz Plans Included: Owner/Statement or License 055449 3 sets of Plans/Plot Plan THE Fp LLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON IN PRMATION PRESENTED: L/Approved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received&Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay 1 3k Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning&Development for more information. 100 ELM ST-CAMPUS CENTER BP-2014-1264 GIs#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 3 1 B-249 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: renovation BUILDING PERMIT Permit# BP-2014-1264 Project# JS-2014-002127 Est. Cost: $745580.00 Fee: $4473.00 PERMISSION IS HEREBY GRANTED TO: Const.Class: Contractor: License: Use Group: PETRA CONSTRUCTION CORP 055449 Lot Size(sq. ft.): 15855.84 Owner: SMITH COLLEGE OFFICE OF TREASURER Zoning-: EU(100)/URC(100)/ Applicant. PETRA CONSTRUCTION CORP AT. 100 ELM ST - CAMPUS CENTER Applicant Address: Phone: Insurance: 98 REBESCHI DR (203) 865-6043 WC NORTH HAVENCT06473 ISSUED ON.61512014 0:00:00 TO PERFORM THE FOLLOWING WORK:RENOVATE CAFE POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 6/5/2014 0:00:00 $4473.00 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck—Building Commissioner