Loading...
17C-092 (6) 40. Closets beneath stair which have doors must be drywalled with%". 780 CMR R302.7 41. If there is mechanical equipment or a combustible roof, 30 sqft of space, and 30" measured from top of ceiling joist to bottom of rafters an attic access of minimum RO of 22"x 30" is required to be located in an accessible place. It must be insulated,gasketed, and secured in place. Relevant items must be submitted to the building department for approvals before inspections and or Certificates of Occupancy can be issued. Feel free to call if you have any questions. My telephone number is 587-1240 and office hours are Monday through Friday, 8:30 am to 4:30 pm, excepting we close for walk-ins at 12:00 noon on Wednesdays. My email address is: cmiller(a_northamptonma.gov Thank you for your cooperation on these matters. Chuck Miller City of Northampton Assistant Commissioner and Zoning Enforcement in joist are a maximum 1/3 the depth not closer than 2" from the top or bottom or to any other hole. Notches are different. 26. Drilling or notching of more than 50%of the wall plate width of an exterior wall or load bearing partition requires a 16 GA 1%" strap across the area and 6" beyond each side with 8- 10nd nails. 780 CMR R602.6.1 27. Dryer ducts must terminate outside of the building, have a backdraft damper, cannot include a screen, and require 3' clearance from windows. 780 CMR M1502.3 28. Dryer duct transition is limited to 8' of aluminum flex, must be exposed, and the proper UL listing.780 CMR M1502.4.3 29. Dryer duct maximum equivalent length is 25' less 5' per 900 elbow or per manufacturer's specs. 780 CMR M1502.4.4.1, no screwed connections. 30. Markup air is required for any exhaust hood of 400 CFM or more.780 CMR M1503.4 31. Fireplaces require all combustion air be provided from the exterior and below the firebox, duct work maintaining 1" clearance for 5'from the duct outlet for all fireplaces and airtight doors. 2009 IECC 402.4.3 32. Fire and draft stopping shall be completed before rough inspection.Typical locations,top (ceiling) and bottom (floor) plates,soffits, and every 10'within enclosed cavities.780 CMR R302. 33. Ignition barriers are required over all thermal plastics and must be in place before final. 780 CMR R316. 34. Dwelling/Garage fire separation.An attached garage (within 3' of main structure) is required to have%" drywall on the garage side of the separation wall and if there is a finished space above the garage all walls must have%" drywall and the ceiling 5/8" drywall. 780 CMR R302.6 35. Energy aspects shall comply with the stretch energy code.780 CMR Appendix 115AA or 2009 IECC. a. An initial HERS evaluation is required including insulation levels anticipated. b. A final HERS evaluation confirming code requirements have been met including duct testing. c. A signed copy of the Thermal Bypass Checklist. d. Energy information including mechanical equipment posted on the electric panel. e. Remodeling and Additions can be completed in accordance with IECC 2009 with Energy Star Windows and the Thermal Bypass Checklist. Duct blast testing when practicable. f. All band joist insulation must be enclosed within an air tight cavity, which you must create. 36. Vapor retarders.Although these are still in the code have exceptions, one must understand that there is a difference between a vapor retarder or barrier and an air barrier.An air barrier is intended to stop air flow (convection)a vapor retarder or barrier is intended to stop molecular moisture transfer(diffusion). A vapor retarder or barrier is effective even if there are some holes or gaps, however an air barrier has to be absolute and complete. If air can leak through an electrical device or through a crack it follows the path of least resistance and carries 99%of the moisture in a structure.This is evident every time one exposes fiberglass insulation and finds black insulation, which is dirt filter out of the air moving through the insulation.780 CMR R601.2 for vapor retarders and Table N1102.4.2 for air sealing requirements. 37. Unvented attic assemblies. Hot roofs are allowed, but have specific requirements 780 CMR R806.4. 38. Deck ledgers and post must be appropriately attached, bolts or lags. 780 CMR R502.2.2.1 Note:Thrul-oks are engineered for post attachment supporting a railing. Lateral attachment is required for each deck per section 502.2.2.3. 39. Smoke and CO detectors as required. 780 CMR R314 and R315. a. Smokes in each bedroom, within 10' of a bedroom door, and at the bottom of a stair leading to a finished floor above. b. CO within 10' of bedroom doors, at each level, for every 1500 sqft, (plumbing code in the mechanical room) Except if there are no fossil burning fuels. c. Heat detector in attached garage, and other large unfinished unconditioned spaces. 11. Steel straps over the ridge or 1x4 minimum collar ties are required 4' OC in the upper 1/3rd 780 CMR R802.3.1 12. Ridge boards must be the full depth of the cut. 780 CMR R802.3. 13. A complete window and header schedule is required. 780 CMR Table R502.5 for header sizing and number of jack studs required. 14. All framing materials which are not code prescriptive must have stamped engineering. a. LVLs b. 1-joist and or Floor Truss c. Roof truss 15. All I-Joist need to be protected from fire with% drywall or 5/8 wood structural panel. (R501.3) 16. A braced wall plan identifying appropriate braced wall areas where required (R301.1) and braced wall method being used. 780 CMR 602.10. a. Garage corners and large corner window/door layout may require special solutions. b. All corners must be appropriately attached to the foundation. c. When using PFH (R602.10.3.3) or PFG (R602.10.3.4)the nailing requirement is 4" and 3" respectively using 8d common nails or galvanized box nails. PNEUMATIC nails must be full headed with the temper and shank sizing meeting the strict code requirement. 17. When nailing sheathing make sure your pneumatic nailers' pressure is properly set. Nails set too deep perforate the sheathing weakening it and contribute to building damage in high wind events. 18. Ceiling heights minimum 7 for habitable spaces, 6'8" for bathrooms includes tub/shower area if a shower head is used, 6'8" for basements, 6'4" at beams/ducts.780 CMR R305.1. MA amended 19. Hazardous glazing locations, within 24 of a door, or within 60 of a stair, or across from hot tubs,spas, bathtubs within 60" if not 60" above the walking surface, and other locations. 780 CMR R308.4 20. Windows over 72" above grade with the opening less than 24 above the finished floor shall meet the 4" sphere rule. Order restrictors. 780 CMR R612.2 21. Egress and emergency escape requirements shall be strictly met. a. Basements, habitable attics, and all sleeping rooms require emergency escape.780 CMR R310 b. Windows within 44" of floor, DH 3.3 sqft min window size, Casement 20"x41" exception 5 sqft at 1St floor. Minimum clear opening 20"x24" or 24"x20". 780 CMR R310.1.1 c. Two doors remote as possible at the normal level of travel, opening measured from the face of the slab to the stop with door at 90 degrees, one 32" and one 28" minimum 78" high. 780 CMR R311.2 d. Landing at each door 36" out and the width of the door minimum 36", maximum step 7 %" from the top of the threshold and only in-swinging doors. 780 CMR R311.3 22. Stairs have critical standards, make sure you know the floor finishes when planning. Minimum tread 9", maximum riser 8%", maximum overall variance for the run is 3/8",4" sphere rule on risers except where the total rise is 30" or less 780 CMR R311.7.4.3 Exception,4 3/8"on balustrade, 6" in the triangle. Graspable rail 1%" minimum and 2" maximum rail, height minimum 34" maximum 38", required for 4 or more risers. Landing to landing constitutes a new run. Minimum 6'8" ceiling height from nosing. Rails must be continuous and returned to the wall if not to newel post. 780 CMR R311.7. 23. Guards 36" minimum height above walking surface, a bench is a walking surface, required for more than 30" above floor or grade within 36",4" sphere rule.780 CMR R312.1. 24. Floor joist systems that are not equal to 1%2" nominal dimension must be covered with%Z" drywall or 5/8"wood structural panel or equivalent with some exceptions.780 CMR R501.3 25. Educate the plumber and electrician about maximum notch and hole sizes,and placement. 780 CMR R502.8 and R602.6. In bearing studs holes not larger than 40%of a stud no closer than 5/8 to the edge, In interior non-bearing studs holes not larger than 60%of a stud no closer than 5/8 to the edge, or holes City of Northampton Massachusetts lri r DEPARTMENT OF BUILDING INSPECTIONS nom; 212 Main Street • Municipal Building 7 :f Northampton, MA 01060 INSPECTOR Wright Builders Inc. May 19, 2014 48 Bates Street Northampton, MA 01060 Subject Location: 122 Chestnut Street, Florence Map Block: 17C-092 Mr. Buzzell, Your building permit application dated 5-16-14 and plans dated 5-7-2014 have been approved as drawn and per this memo.All work must meet all applicable codes whether noted or not included within this memo. Please follow up on the following items: These items will need to be accomplished as the project moves forward and before rough inspections; 1. The proposed gas Parlor Stove must meet manufacturer's clearance requirements. Literature must be provided. 2. Appropriate blocking must be installed in the wall to support brackets for entry canopy 3. The header at the braced wall detail must be 2 x 12 minimum. Note August 16th 2013 begins the newest energy code 2012 IECC with MA amendments with a concurrency period until July 1, 2014 and an expectation of a new Stretch Code. As of August 4th 2011 the 8th Edition MA code is the 2009 IRC with MA amendments. In the following are some generic requirements which seem to be problematic. This is not intended to be comprehensive, nor is it a substitute for purchasing and reading the MA codes. Read only international codes are available on line at http•//publicecodes.cyberregs.com/icoL one must also consider the MA amendments to these codes which can be found at www.mass.gov/dps/­bbrs . The current relevant building codes are: 2009 IBC, 2009 IEBC, 2009 IMC, 2009 IRC, 2009 or 2012 IECC,AA115, MA amendments. 1. Structures shall conform to 780 CMR 8th Edition 1 and 2 family building codes with MA amendments. 2. Grading plan for structures being constructed required. 780 CMR R401.3 for drainage requirements. 3. A basement drainage system is required in all basements 780 CMR R405.2.3. except those in group I soils(table R405.1) 4. Foundations that retain earth and enclose interior space require damp proofing 780 CMR R406.1. 5. Through wall form ties must be removed from both faces and patched with hydraulic cement.780 CMR R406.2 of amendments. 6. Foundation anchor bolts must be%" and be embedded a minimum of 7" into the concrete. 10" bolts! 780 CMR R403.1.6 7. CMU foundations require 3/8" parging before damp proofing. 780 CMR R406.1 see exceptions. 8. Emergency escape is required out of every basement whether habitable or not. 780 CMR R310.1 9. Crawl spaces can be treated in three different ways,vented (poor idea), exhausted (similar to exhaust only systems),or treating the space with supply and return. See 780 CMR R408 10. Ceiling joist are intended to prevent spread, once raised above the wall plate they become rafters ties and may require up sizing of rafters and increased nailing for example with a 4" slope 8-16nd common are required at each connection. 780 CMR R802.3.1. When there is neither of these a structural ridge is required with a load path to the foundation. ENERGY CONSERVATION APPLICATION fOkAM F*OR LOW-RISE REISIDENTIAL NE\k' CONSTRUCTION and ADDITIONS 780 CMR Appendix J Applicant Names wpA< .01,L)OW Site AddrLss: r lay ftV-.(-1-jjU applicant Acldrlss: Citv,7okvn� Use' Group: __P! Date of application: Applicant Phone'. 12 f-D4 Applicant Signature: Compliance Path(check one): ❑ Prescriptive Package (Limited to I-or 2-farnilv wood frame buildings heated with fossil fuels only) Package (A through KK from Table J5.2.lb): I icatinf, Degree Days (TiDD,,'1 from Table J5.2.I a- (For items d.throe is i., fill in all val 1,11--t app!} fro.-11 Ta. 15.2 i b. a. Gross Wall Area -sq,ft f Wall R-value R- b. Glazing Area' g, Floor R--,aluc R- c. Glazm,g% (100xb-a)______'/'� h Basement wall R- d. Glazing TJ-value It- i, Slab Perimeter R- e. R- R-value Ceilin- Z_ J. Heating AFUE ❑ Component Performance: "Manual Trade-Off" (Limited to wood or metal framed buildings only) Climate Zone (frorn Figure J6.2.2) ❑ Zone 12 ❑ Zone 13 7 Zone 14 Attach D-ade-QffFf`orLvheel from Appendix J, [and if applicable] ❑ MAScheck Software Attach Compliance Report and Inspection Checklist printouts ❑ Home Enerlpy Rating System Evaluation Attach llorne Energy Rating Certificate (HERS rating score must be 83 or higher") ❑ Systems Analysis OR ❑ Renewable Energy Sources Attach Mass Registered Architect or Engineer Analysis ALTEP-NATIVE FOR ADDITIONS ONLY: a. Gross Wall + Ceiling Area015-5,-sq.ft. b, (ilizin:, Ar,-,i'a3?.Ig'sq.ft. c. Glaring%(io0xb-a) *% , 0 C N I R Table J1.1.2.3.1 b t-1 ow: r,tkDDlTlONN-,-6th Glazing % (c.) up to 40% may use 78 M A X 1 M1 1 N1 U-Value MIN1101 \1 R-Valises Fcnestration, I Ccilili! Wall Floor I Basement Wall Slab Perimeter.Depth 0,30' 1 R-31 I IZ-20 J R-30 1 R-10('011611LIOUS I R-10.2 ft I Glazing Area may be either Rough Opening or Unit dimensions Y unit,or to area-weighted units. 2 Based on NFRC listing. Applies either to every averag 4-e of all un 3 R-30 ceiling insulation rnay be used in place of R-3 7 if the insulation achieves the full R-value over the entire ceiling aica (i.e.-not compressed over exterior walls, xicl inclludiiig any access openings.) ❑ -SUNROONI" addition (greater than 40% glaring-to-wall and ceiling gross area) 1- *1 t, Attach"Consumer Information Form" from 780 CNIR Appendix B. Official's Name-. Oflfi";aYs si-(MatUr": ------ Application Approved ❑ Deriic] ❑ Date of'Appmval.'Denial: Reason(s) for Deniaj: (_provide addi icrlai dctnii a; ne t� l on back sid-.) a~ ► e — Eity 91' c+iit332III? : DEPARITM=:/T OF 3f:ILDLNG.INSP_C71CINS INSrE�OR 3I2 Main, Street - Manicipal Building Northampton, Mass. 01060 Scua_re Fcotace A-Mcunt Easi�ment @ Est _=ccr @ ,50 2nd =,cor @ •3o 1/2 Floors, Attic, Garage,34 Deck, Porches ,�0 . 4 Mar,; .-a o� - J ^Ap Lot t 00 SECTION 8-CONSTRUCTION SERVICES 8.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Holder Roo e.rju��e�l $�l asp License Number �� ess Expiration Date f 5-35-- SOD``- Signature Telephone 9.Replstnred Iloime IrnrovementlContr�etor: Not Applicable ❑ n Compan ame Registration Number Address Expiration Date Telephon& ��� SECTION 10-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c.152,§25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes....... No...... ❑ if .- Rome 0 ner Exemy0on The current exemption for"homeowners"was extended to include Owner-occupied Dwellings of one(1) or two(2)families and to allow such homeowner to engage an individual for hire who does not possess a license,provided that the owner acts as supervisor.CMR 780, Sixth Edition Section 108.3.5.1. Definition of Homeowner:Person(s)who own a parcel of land on which he/she resides or intends to reside,on which there is,or is intended to be,a one or two family dwelling,attached or detached structures accessory to such use and/or farm structures.A person who constructs more than one home in a two-year period shall not be considered a homeowner. Such"homeowner"shall submit to the Building Official,on a form acceptable to the Building Official,that he/she shall be responsible for all such work performed under the building permit. As acting Construction Supervisor your presence on the job site will be required from time to time,during and upon completion of the work for which this permit is issued. Also be advised that with reference to Chapter 152(Workers'Compensation) and Chapter 153(Liability of Employers to Employees for injuries not resulting in Death)of the Massachusetts General Laws Annotated,you may be liable for person(s) you hire to perform work for you under this permit. The undersigned"homeowner"certifies and assumes responsibility for compliance with the State Building Code,City of Northampton Ordinances,State and Local Zoning Laws and State of Massachusetts General Laws Annotated. Homeowner Signature SECTION 5-DESCRIPTION OF PROPOSED WORK(check all applicable) New House ❑ Addition Replacement Windows Alteration(s) Roofing ❑ Or Doors D Accessory Bldg. ❑ Demolition ❑ New Signs [O] Decks [p Siding[01 Other[0] Brief Desc�ggtion of Proposed Work: /VC0 y77 sg. al at h;M 40 le4r OZ� 6/u��i�G G✓��i��ga /'ODm C Demo e Get 7aarh /yXt$/ Ueo maxi`s fi�y Alteration of existing bedroom Yes X No Adding new bedroom Yes �C _No Attached Narrative Renovating unfinished basement Yes _ X No Plans Attached Roll /Sheet jai if New house and or adciitlon to existing housing, complete the following: a. Use of building : One Family�_ Two Family Other 0 // L b. Number of rooms in each family/unit: Adl'�iro.opqs Number of Bathrooms 410/1[ ?n Q4411Am4 c. Is there a garage attached? /� O d. Proposed Square footage of new construction. !T7 a Dimensions Y a t t ��f• I! �S t e. Number of stories? 01 f. Method of heating? Fireplaces or Woodstoves Number of each g. Energy Conservation Compliance. Masscheck Energy Compliance form attached? S h. Type of construction i. Is construction within 100 ft. of wetlands? Yes C No. Is construction within 100 yr. floodplain Yes X No j. Depth of basement or cellar floor below finished grade to g%6A2z — 1(10 r k k. Will building conform to the Building and Zoning regulations? Yes No.'� ! L, Zonq� I. Septic Tank City Sewer�_ Private well City water Supply SECTION 7a-OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT 4 I, Z44(11�t g . " lie—Irk a as Owner of the subject property t J hereby authorize 1 Jri aht — Bul 1 da-S to act on my behalf.in all matk&s relative to work authorized by this building permit application. i ature of Date I, INf1Q�7 — �IAIIdr-s In as Owner/ ;now nzed �e hereb eclare that the statements and information on the foregoing application are true and accurate,to the best of my fedge and belief. Signed under the pains and penalties of perjury. uz 1 Sign ture of Owner/Agent Date 5ee, #actin Za" Section 4. ZONING All Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information Existing Proposed Required by Zoning This column to be filledi y Building Departme Lot Size € €_---- Frontage Setbacks Front € ' mm Side L. ' R.=__.j L:! Rear _. .... Building Height Bldg.Square Footage _ % Open Space Footage _. % _.._., (Lot area minus bldg&paved ---- parking)#of Parking S ces • - ' m m ` -- Fi olume&Location) A. Has a Special Permit/Variance/Finding ever been issued for/on the site? NO 0 DONT KNOW YES 0 IF YES, date issued:' �� � ' IF YES: Was the permit recorded at the Registry of Deeds? NO Q DONT KNOW 0 YES 0 IF YES: enter Book , Page' and/or Document# B. Does the site contain a brook, body of water or wetlands? NO DONT KNOW Q YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained 0 Obtained 0 , Date Issued C. Do any signs exist on the property? YES Q NO IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property? YES 0 NO IF YES, describe size, type and location: c E. Will the construction activity disturb(clearing,grading,excavation,or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES Q NO IF YES,then a Northampton Storm Water Management Permit from the DPW is required. � �; ityof Northampton Statusof �,N �{ � 4 Department � a 212 Main Street 5ey;+erttc Avails ; MAY 19 2014 Room 100 No hampton, MA 01060 Two �y - g 13- 87-1240 Fax 413-587-1272 � 'lans Electric Plum �irc �(3 isp�tions sf APPLICATION TO CONSTRUCT,ALTER,REPAIR,RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING SECTION 1 -SITE INFORMATION 1.1 Property Address:: This section to be completed by office iaa cticsfnut �i�ryce� Map Lot Unit Flo reei c c,/Yl R Zone Overlay District Elm St.District J CS District SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: LQ1A-JCL St-Pter,r e [ 2-'Z7 Gies tnuA-5r• 4'cw-(nP l c.P- Name(Print Current Mailing Address: Al3 --S8(0• 6-(2(v Telephone Sign ure 2.2 Authorized Agent: Name(P' Current Mailing Address: (yr3 ) s& - s a s 7 Signature Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only completed b permit applicant 1. Building (a)Building Permit Fee lb6o, 5 x1 . 00 2. Electrical (b)Estimated Total Cost of 5771 - 00 Construction from 6 3. Plumbing ¢1; q 11 1. Ov Building Permit Fee 4. Mechanical(HVAC) -'7 q [� ©0 5. Fire Protection J ` '1 J 6. Total=(1 +2+3+4+5) 6 Y N Check Number This Section For Official Use Only` I Building Permit Number. stued: Signature: Building Commissioner/Inspector of Buildings` Date File#BP-2014-1210 APPLICANT/CONTACT PERSON WRIGHT BUILDERS ADDRESS/PHONE 48 Bates St NORTHAMPTON (413)586-8287(116) PROPERTY LOCATION 122 CHESTNUT ST MAP 17C PARCEL 092 001 ZONE URB(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Buildimz Permit Filled out Fee Paid -710 05129 9 Typeof Construction: CONSTRUCT ONE STORY ADDITION 11 X 15 DINING RM&14 X 18 GREAT ROOM &DEMO DECK New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/Statement or License 84280 fa 3 sets of Plans/Plot Plan IICC THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFO ATION PRESENTED: Approved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received& Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management lition Delay Si na B in acial Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A.Contact Office of Planning&Development for more information. 122 CHESTNUT ST BP-2014-1210 GIS#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 17C-092 CITY OF NORTHAMPTON Lot:-001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: ADDITION BUILDING PERMIT Permit# BP-2014-1210 Project# JS-2014-001783 Est.Cost: $64484.00 Fee: $227.00 PERMISSION IS HEREBY GRANTED TO: Const.Class: Contractor: License: Use Group: WRIGHT BUILDERS 84280 Lot Size(sa.ft.): 7013.16 Owner: RITT TOBIN C&LAURA A ST PIERRE Zoning:URB(l00)/ Applicant: WRIGHT BUILDERS AT. 122 CHESTNUT ST Applicant Address: Phone: Insurance: 48 Bates St (413) 586-8287 (116) Workers Compensation NORTHAMPTON MAO 1060 ISSUED ON.512012014 0:00:00 TO PERFORM THE FOLLOWING WORK.-CONSTRUCT ONE STORY ADDITION 11 X 15 DINING RM & 14 X 18 GREAT ROOM & DEMO DECK POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType• Date Paid: Amount: Building 5/20/2014 0:00:00 $227.00 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck—Building Commissioner