25A-185 (120) yP , 2-23-95 The Austin Company 48 Perimeter Center East Atlanta, Georgia 30346 Raul F. Trujillo; Raul , I have reviewed the Project Plans #7417 P-1 Dated 11-30-94- given to me on 2/9/95 at the afternoon meeting at the Coca Cola Plant Industrial Drive Northampton. The Blending Room and Mixing Room Hub Drains in my opinion are improperly wasted and vented as per our discussion. The eight plastic hub drain pipes without traps are a major concern. The air compressor room drains, boiler room drains, dock area drains that are piped in plastic are also a major concern. The Lab Special waste piping and Water treatment waste piping are also a concern. I need the notarized list of waste products that will be entering these drains. I also need Engs. Drawings of the waste,vent and water piping as per our conversation at the meeting on 2/9/95. My decision on these matters listed above is that you have a Plan review with the Mass. Board of Examiners. You indicated in our discussion at the meeting you would be seeking a Variance from the Board for the hub drains,air compressor room drains,boiler room drains and the dock area drains. It is my opinion that a Plan Review with the Board of Examiners will determine what means are needed to remedy the situation. At our meeting on 2/10/95 we discussed the option of using properly wasted and vented housetraps outside the building for the five hub drain lines that exit the building. I feel you should also bring this up to the Board at the time of your Plan Review for their decision. Respectfully; C ski Charles Maze Plumbing and Gas Inspector City of Northampton Rm 100, 212 Main Street. 413-586-6950 CC. Mass. Board of Examiners M.J. Moran Inc.