Certificate of Product Ratings
AHRI Certified Reference Number: 4217872 Date: 10/30/2013
Product:Variable Speed Mini-Split Heat Pump,with Remote Outdoor Unit Air-Source, Free Delivery
Outdoor Unit Model Number: MUZ-GE24NA
Indoor Unit Model Number: MSZ-GE24NA
Manufacturer: MITSUBISHI ELECTRIC AND ELECTRONICS USA, INC.
Trade/Brand name: MR.SLIM
Manufacturer responsible for the rating of this system combination is MITSUBISHI ELECTRIC AND
ELECTRONICS USA, INC.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 22400
EER Rating(Cooling): 12.50
SEER Rating (Cooling): 19.00 -
Heating Capacity(Btuh)@ 47 F: 27600
Region IV HSPF Rating (Heating): 10.00
Heating Capacity(Btuh)@ 17 F: 16000
CERTIFIED RATINGS FOR VARIABLE-SPEED,MINI-AND MULTI-SPLIT SYSTEMS ARE VALID FOR ALL COMBINATIONS OF INDOOR UNITS
(BASED ON COMBINATION TYPES)WITH THE SPECIFIC OUTDOOR UNIT LISTED ABOVE AND IN THE AHRI DIRECTORY OF CERTIFIED
EQUIPMENT.VISIT WWW.AHRIDIRECTORY.ORG TO VERIFY THAT THIS COMBINATION IS AN ACTIVE LISTING AND THE DATA LISTED ON
THIS CERTIFICATE IS ACCURATE.SEARCH ON THE AHRI REFERENCE#TO QUICKLY LOCATE THIS COMBINATION IN THE DIRECTORY.
Ratings followed by an asterisk(')indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed in the directory at www.ahridirectoryorg.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents of this Certificate may not,in whole or in part,be reproduced;copied;disseminated;entered into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at w,.vw.ahridirectoryorg, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on ad al dnd Refrigeration Institute
which the certificate was issued,which is listed above,and the Certificate No.,which is listed below.
02013 air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 130276288124834456
Duct System Summary Job:
Date: Oct 16,2013
Entire House By: Tom LeMay
A Plus HVAC, Inc.
26 Airport Drive,Westfield,MA 01085 Phone:4135620054 Fax:4135620064 Email:Thomas@aplushvacinc.com Web:wwwaplushvacinc.com License:103
Project
For Alex Konheim
26 Orchard St, Northampton, MA 01060
Phone: 646.736.8115
Email: ack92 @yahoo.com
Heating Cooling
External static pressure 0 in H2O 0 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0 in H2O 0 in H2O
Supply/return available pressure 0.000 10.000 in H2O 0.000/0.000 in H2O
Lowest friction rate 0 in/100ft 0 in/100ft
Actual air flow 958 cfm 958 cfm
Total effective length(TEL) 0 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln(ft) Trunk
Room1 c 3492 160 160 0 0 Ox 0 ShMt 0 0
Room1-A c 3491 160 160 0 0 Ox 0 ShMt 0 0
Room1-B c 3491 160 160 0 0 Ox 0 ShMt 0 0
Room1-C c 3491 160 160 0 0 Ox 0 ShMt 0 0
Room1-D c 3491 160 160 0 0 OX 0 ShMt 0 0
Room1-E c 3491 160 160 0 0 Ox 0 ShMt 0 0
Table Return Branch Detail
Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Mat[ Trunk
rb1 Ox 0 958 958 0 0 0 0 Ox 0 ShMt
W rl h tSOftk
2013-Nov-11 12:33:54 Pge
1. 9 Right-Sufte®Universal RSU02778 Page 1
...CWlex Konheim-26 Orchard St,Northampton.rup Calc=MJ8 Front Door faces: N
N \ evel 3
:�,
958 cfm
160 cfm
Room1
160 dM160 cfm 160 cbn160 c1ml 61 cfm
Job#: A Plus HVAC, Inc. Scale: 1 : 72
Performed by Tom LeMayfor: Page 1
Alex Konheim 26Ai rport Dd ve RightSuitee Universal 2013
26 Orchard St Westfield,MA01085 13.0.08 RSU02778
Northampton,MAO 1060 Phone:4135620054 Fax:4135620064 2013-Nov-11 123406
Phone:646.736.8115 www.aplush✓xitc.com Thomas @aplushvacinc.com
...-26 Orchard St,Northampton.rup
ack92 @yahoo.com
Load Short Form Job:
Date: Oct 16,2013
Entire House By: Tom LeMay
A Plus HVAC, Inc.
26 Airport Drive,Westfield,MA 01085 Phone:4135620054 Fax:4135620064 Email:Thomas@aplushvacinc.com Web:wwwaplushvacinc.com License:103
Project
For Alex Konheim
26 Orchard St, Northampton, MA 01060
Phone: 646.736.8115
Email: ack92 @yahoo.com
Des;ign Information
Htg Clg Infiltration
Outside db(°F) -4 88 Method Simplified
Inside db(°F) 70 75 Construction quality Average
Design TD (°F) 74 13 Fireplaces 0
Daily range - M
Inside humidity(%) 30 50
Moisture difference(gr/lb) 29 27
HEATING EQUIPMENT COOLING EQUIPMENT
Make Make
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 80 AFUE Efficiency 0 SEER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 °F Total cooling 0 Btuh
Actual air flow 958 cfm Actual air flow 958 cfm
Air flow factor 0.023 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.92
ROOM NAME Area Htg load CIg load Htg AVF Clg AVF
(ft2) (Btuh) (Btuh) (cfm) (cfm)
Room 1130 41760 20947 958 958
Entire House d 1130 41760 20947 958 958
Other equip loads 0 0
Equip. @ 0.93 RSM 19565
Latent cooling 1923
TOTALS 1130 41760 21488 958 958
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
ti Wri htSOft' Rig Universal 201313.0.08 RSU02778 2013-Nov-1112:33:54
Page 1
ACCA ...CWIexKonheim-26 Orchard St,Northampton.rup Calc=MJ8 Front Door faces:N
Project Summary Job:
1 y Date: Oct 16,2013
Entire House By: Tom LeMay
A Plus HVAC, Inc.
26 Airport Drive,Westfield,MA 01085 Phone:4135620054 Fax:4135620064 Email:Thomas@aplushvadnc.com Web:wwwaplushvacinc.com License:103
Project
For: Alex Konheim
26 Orchard St, Northampton, MA 01060
Phone: 646.736.8115
Email: ack92 @yahoo.com
Notes: 1)Customer wants ductless mini-split.
2)Does NOT want condensing unit installed on house.
Design Information
Weather: Hartford Bradley Intl AP, CT, US
Winter Design Conditions Summer Design Conditions
Outside db -4 OF Outside db 88 OF
Inside db 70 OF Inside db 75 OF
Design TD 74 OF Design TD 13 OF
Daily range M
Relative humidity 50 %
Moisture difference 27 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 41760 Btuh Structure 20947 Btuh
Ducts 0 Btuh Ducts 0 Btuh
Central vent (0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 41760 Btuh Use manufacturer's data n
Rate/swing multiplier 0.93
Infiltration Equipment sensible load 19565 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 1923 Btuh
Ducts 0 Btuh
Heating Cooling Central vent(0 cfm) 0 Btuh
Area(ft') 1130 1130 Equipment latent load 1923 Btuh
Volume(ft3) 12430 12430
Air changes/hour 0.58 0.30 Equipment total load 21488 Btuh
Equiv.AVF(cfm) 120 62 Req. total capacity at 0.70 SHR 2.3 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make
Trade Trade
Model Cond
AHRI ref Coil
AHRI ref
Efficiency 80 AFUE Efficiency 0 SEER
Heating input 0 Btuh Sensible cooling 0 Btuh
Heating output 0 Btuh Latent cooling 0 Btuh
Temperature rise 0 OF Total cooling 0 Btuh
Actual air flow 958 cfm Actual air flow 958 cfm
Air flow factor 0.023 cfm/Btuh Air flow factor 0.046 cfm/Btuh
Static pressure 0 in H2O Static pressure 0 in H2O
Space thermostat Load sensible heat ratio 0.92
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsoft' Right-Suite®Universa1201313.0.08 RSU02778 2013-Nov-11 12:33:54 Pagel
ACCA
...C1AIexKonheim-26 CaIc=MJ8 Front Door faces:N
INSURANCE COVERAGE:
I have a current liabilit insurance policy or its equivalent which meets the requirements of M.G.L.Ch. 112 YeSN No❑
If you have checked Yes,indicate the type of coverage by checking the appropriate box below:
A liability insurance policy Other type of indemnity ❑ Bond ❑
OWNER'S INSURANCE WAIVER:I am aware that the licensee rinp-z nn+have the insurance coverage required by Chapter 112 of the
Massachusetts General Laws,and that my signature on this permit application waive this requirement.
Check One Only
Owner �( Agent ❑
Signature of Owner or n 's Agent
By checking this box I hereby certify that all of the details and information I have submitted(or entered)regarding this application are true and
accurate to the best of my knowledge and that all sheet metal work and installations performed under the permit issued for this application will be
in compliance with all pertinent provision of the Massachusetts Building Code and Chapter 112 of the General Laws.
Duct inspection required prior to insulation installation: YES NO
PrnareQQ inenvrtionc
Date
Fiinal inenPrtinn
Dale comment&
Type of License:
By 11master
Title ❑ Master-Restricted T `Q
City/Town ❑Journeyperson
Signature of Ldsee
Permit#
❑Jou rneyperson-Restricted
License Number:
Fee$ ❑
Check at www mace gnv�I
Inspector Signature of Permit Approval
42o�a Commonwealth of Massachusetts
a City Of Northampton
p1�^p�cgoa M�o� ,
�t1cNo�ham
Date: hy Sheet Metal Permit Permit# 507'N-0 a,6
Estimated Job Cost: $ 00 Permit Fee: $ �b CX
Plans Submitted: YES NO Plans Reviewed: YES NO
Business License#`(��, Applicant License# 9�J
Business Information: Property Owner/Job Location(Information:
Nade. Name
Stree
City/Tow x1 ' �� V t 1?►� City/TowI � C� hl
Telephone:`1 �� �• � �'—�� TelephonerO��`���
Photo I.D. required/Copy of Photo I.D. attached: YES NO
Staff Initial
J-1/M-1-unrestricted license
J-2/M-2-restricted to dwellings 3-stories or less and commercial up to 10,000 sq. ft./2-stories or less
Residential: 1-2 family Multi-family Condo/Townhouses Other
Commercial: Office Retail Industrial Educational
Institutional Other
Square Footage: under 10,000 sq. ft.)Cl.. over 10,000 sq. ft. Number of Stories:
Sheet metal work to be completed: New Work: Renovation:
HVAC Metal Watershed Roofing Kitchen Exhaust System
Metal Chimney/Vents Air Balancing
Provide detailed description of work to be done:
Fees with Building Permit:$25.00 Residential,$50.00 Commercial.Fees for jobs without a Building Permit$6.00 per$1000
Minimum fees for jobs without Building Permit$50.00 Residential,$100.00 Commercial
File#SM-2014-0053
APPLICANT/CONTACT PERSON A PLUS HVAC INC
ADDRESS/PHONE 26 AIRPORT DR (413)562-0054
PROPERTY LOCATION 24-26 ORCHARD ST 3&V dC t t4
MAP 25C PARCEL 166 001 ZONE URB000V
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid
Building Permit Filled out
Fee Paid
Typeof Construction: INSTALL HEATING&AC SYSTEM
New Construction
Non Structural interior renovations
Addition to Existing
Accessoly Structure
Building Plans Included•
Owner/Statement or License 905
3 sets of Plans/Plot Plan
THE FO WING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
I F ATION PRESENTED:
Approved Additional permits required(see below)
PLANNING BOARD PERMIT REQUIRED UNDER: §
Intermediate Project: Site Plan AND/OR Special Permit with Site Plan
Major Project: Site Plan AND/OR Special Permit with Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received&Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
e m Elm Street Co ssion Permit DPW Storm Water Management
Sig e of ding ff is Date
Note:Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health,Conservation Commission,Department
of public works and other applicable permit granting authorities.
*Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact the Office of
Planning&Development for more information.
24 - 26 ORCHARD ST SM-2014-0053
COMMONWEALTH OF MASSACHUSETTS
_ CITY OF NORTHAMPTON
GIS#: 4542 -
IMaP -- - 25'C
Block:
Lot. Q01 01 SHEETMETAL PERMIT
�� ,�•�°
Permit: .SHEETMETAL_— _
Category SHEETMETAL_
Permit# SM-2014-0053 PERMISSION IS HEREBY GRANTED TO:
Project# JS-2013-001538
Est. Cost $5,900.00 Contractor: License: Expires:
___- --.—_....— --- -IA PLUS HVAC INC Sheetmetal-905 11/28/2015
Fee Charged.$50 00
B alance Due:$_00 — __j Owner: KONHEIM ALEXANDER CARL
#of Fixtures Applicant: A PLUS HVAC INC
_ l
DlgSafe# AT: 24-26 ORCHARD ST
UseGroup
�ConstClass
ISSUED ON: 24-Apr-2014 AMENDED ON: EXPIRES ON:
TO PERFORM THE FOLLOWING WORK:
INSTALL HEATING&AC SYSTEM -3RD LEVEL ONLY
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Signature:
Fee Type: Receipt No: Date Paid: Check No: Amount:
Sheetmetal REC-2014-005959 14-Apr-14 4920 $50.00
212 Main Street,Phone:(413)587-1240,Fax:(413)587-1272,Email:lhasbrouck @northamptonma.gov
GeoTMS®2014 Des Lauriers Municipal Solutions,Inc.