Loading...
31B-294 (23) SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 3 .02 FIELD QUALITY CONTROL A. Field inspection and testing will be performed under provisions of Section 01400. B. Test in accordance with NFPA 72H and local fire department requirements . 3 .03 MANUFACTURER' S FIELD SERVICES A. Prepare and start systems under provisions of Section 01400 . B. Include services of certified technician to supervise installation, adjustments, final connections, and system testing. 3 .04 DEMONSTRATION A. Provide systems demonstration under provisions of Section 01650 . B. Demonstrate normal and abnormal modes of operation, and required responses to each. END OF SECTION FIRE ALARM SYSTEMS 16700 - 6 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects C. Ceiling Mounted Smoke Detector: Model 2098-9201 with Model 2098-9211 base. D. Elevator Lobby Smoke Detector: Model 2098-9536 RA6 with auxiliary contacts with base. 2 .04 SIGNALING APPLIANCES A. Alarm Lights : Model 4904-9105. B. Alarm Horn: Model 2901-9838 . C. Remote Annunciator: Provide supervised remote annunciator including audible and visual indication of fire alarm by zone, and audible and visual indication of system trouble. Install in flush wall-mounted enclosure. 2 .05 AUXILIARY DEVICES A. Outside strobe light Model 4904-9105WP. 2 . 06 FIRE ALARM WIRE AND CABLE A. Fire Alarm Power Branch Circuits: Building wire in raceways as specified in Section 16150 and 16200. B. Initiating Device and Indicating Appliance Circuits: Building wire in raceways as specified in Section 16150 and 16200 . PART 3 EXECUTION 3 . 01 INSTALLATION A. Install products in accordance with manufacturer' s instructions. B. Install manual station with operating handle 4 feet 6 inches above floor. Install audible and visual signal devices 7 feet 6 inches above floor. C. Completely wire in accordance with manufacturer' s requirements . D. Mount end-of-line device box with last device or separate box adjacent to last device in circuit. E. Make conduit and wiring connections to sprinkler valve tamper switches . F. Automatic Detector Installation: Conform to NFPA 72E. FIRE ALARM SYSTEMS 16700 - 5 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects G. Auxiliary Relays : Provide sufficient SPDT auxiliary relay contacts for each detection zone to provide accessory functions specified. H. Provide TROUBLE ACKNOWLEDGE, DRILL, and ALARM SILENCE switch. I . Trouble Sequence of Operation: System or circuit trouble places system in trouble mode, which causes the following system operations: 1 . Visual and audible trouble alarm indicated by zone at fire alarm control panel. 2 . Visual and audible trouble alarm indicated at remote annunciator panel. 3 . Trouble signal transmitted to central station. 4 . Manual acknowledge function at fire alarm control panel silences audible trouble alarm; visual alarm is displayed until initiating failure or circuit trouble is cleared. J. Alarm Sequence of Operation: Actuation of initiating device places circuit in alarm mode, which causes the following system operations : 1 . Sound and display local fire alarm signaling devices with signal. 2 . Transmit non-coded signal to central station. 3 . Indicate location of alarm zone on fire alarm control panel and on remote annunciator panel. K. Alarm Reset: System remains in alarm mode until manually reset with key-accessible reset function; system resets only if initiating circuits are out of alarm mode. L. Lamp Test: Manual lamp test function causes alarm indication at each zone at fire alarm control panel and at annunciator panel. M. Drill Sequence of Operation: Manual drill function causes alarm mode operation as described above. N. zoning: As indicated. 2 . 03 INITIATING DEVICES A. Manual Station: Model 2099-9754. Provide manufacturer' s standard backbox. B. Spot Heat Detector: Model 2098-9442 . FIRE ALARM SYSTEMS 16700 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Furnish products listed and classified by UL and FM as suitable for purpose specified and indicated. 1 . 10 MAINTENANCE SERVICE A. Furnish service and maintenance of fire alarm system for one year from Date of Substantial Completion. 1 . 11 EXTRA MATERIALS A. Furnish under provisions of Section 01700. B. Provide three of each type of automatic smoke detector. PART 2 PRODUCTS 2 . 01 MANUFACTURER A. Simplex. B. Substitutions: None 2 . 02 FIRE ALARM AND SMOKE DETECTION CONTROL PANEL A. Control Panel: Modular construction with surface wall-mounted enclosure. B. Power supply: Adequate to serve control panel modules, remote detectors, remote annunciators, relays, and alarm signaling devices . Include battery-operated emergency power supply with capacity for operating system in standby mode for 60 hours followed by alarm mode for 10 minutes. C. System Supervision: Component or power supply failure places system in trouble mode. D. Initiating Device Circuits : Supervised zone module with alarm and trouble indication; occurrence of single ground or open condition places circuit in trouble mode. E. Indicating Applicance Circuits: Supervised signal module, sufficient for signal devices connected to system; occurrence of single ground or open condition places circuit in trouble mode. F. Remote Station Signal Transmitter: Electrically supervised digital alarm communicator transmitter, capable of transmitting alarm and trouble signals over telephone lines to central station receiver. FIRE ALARM SYSTEMS 16700 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects A. Submit under provisions of Section 16100. B. Shop Drawings : Provide annunciator layout and system wiring diagram showing each device and wiring connection required. C. Product Data: Provide electrical characteristics and connection requirements. D. Test Reports: Indicate satisfactory completion of required tests and inspections . E. Manufacturer' s Installation Instructions : Indicate application conditions and limitations of use stipulated by Product testing agency. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of products. 1 . 06 PROJECT RECORD DOCUMENTS A. Submit under provisions of Section 16100. B. Record actual locations of initiating devices, signaling appliances, and end-of-line devices. 1 .07 OPERATION AND MAINTENANCE DATA A. Submit under provisions of Section 16100. B. Operation Data: Operating instructions . C. Maintenance Data: Maintenance and repair procedures . 1 . 08 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing the products specified in this section with minimum three years documented experience, and with service facilities within 100 miles of Project. B. Installer: Company specializing in installing the products specified in this section with minimum three years documented experience, and certified by State of Massachusetts as fire alarm installer. 1 .09 REGULATORY REQUIREMENTS A. Conform to requirements of NFPA 70 and NFPA 101 . FIRE ALARM SYSTEMS 16700 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16700 FIRE ALARM SYSTEMS PART 1 GENERAL 1 . 01 SECTION INCLUDES A. Fire alarm control panels . B. Manual fire alarm stations . C. Automatic smoke and heat detectors . D. Fire alarm signaling appliances . E. Auxiliary fire alarm equipment. 1 . 02 RELATED SECTIONS A. Section 14240 : Elevators. B. Section 15325 - Sprinkler Systems . C. Section 16200 - Wires and Cables . D. Section 16150 - Electrical Raceway Systems . 1 .03 REFERENCES A. NFPA 70 - National Electrical Code. B. NFPA 72 - Installation, Maintenance, and Use of Protective Signaling Systems. C. NFPA 72E - Automatic Fire Detectors . D. NFPA 72G - Notification Appliances for Protective Signaling Systems. E. NFPA 72H - Guide for Test Procedures for Protective Signaling Systems . F. NFPA 101 - Life Safety Code. 1 .04 SYSTEM DESCRIPTION A. Fire Alarm System: NFPA 72, manual and automatic local fire alarm system with connections to muncipal system with connections to campus central station. 1 . 05 SUBMITTALS FIRE ALARM SYSTEMS 16700 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects end of the run. The long sweep bends may be mad up of one or more curved or straight sections and/or combinations thereof. Manufactured bends shall have a minimum radius of 36 in. where a larger radius cannot be used. D. Spare raceways shall be plugged and sealed watertight with neoprene plugs at all handholes, buildings, and structures. Raceways in use shall be sealed watertight at all manholes, handholes, buildings, and structures. All raceways, including existing raceways, to be used under this contract shall be swabbed clean before cable installation. E. Warning tape shall be installed over underground conduit runs except where conduits run under buildings or other structures. Tape shall be installed 12 in. below finished grade or surfaces . *** END OF SECTION *** UNDERGROUND SYSTEM 16500 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects A. Unless otherwise indicated on the Drawings, raceways shall be PVC conduit. Where specifically indicated on the Drawings, galvanized rigid steel conduit shall be used. Refer to SECTION 16150 for material specification. B. Hardware shall be galvanized steel . C. Concrete shall have a minimum compression strength of 3000 psi at 28 days. D. Ground rods and other grounding materials and methods shall be as specified under SECTION 16550 Grounding System. E. Warning tape shall be 6 in. wide, yellow polyethylene not less than 3 .5 mil. thick with a minimum strength of 1500 psi. and shall be as manufactured by W.H. Brady Co. , Seton Name Plate Corp. , or equal. Tape shall have black lettering on two lines as follows: CAUTION CAUTION CAUTION BURIED ELECTRIC LINE BELOW PART 3 : EXECUTION 3 . 01 INSTALLATION A. Raceways shall be installed to drain away from buildings . Raceways between handholes and buildings or structures shall drain toward the handholes . Raceway slopes shall not be less than 4 in. per 100 ft. B. Raceway lines shall be laid in trenches as indicated on the Drawings. C. Conduit runs shall follow the Drawings and shall run in straight lines as far as possible. Where deviation from a straight line becomes necessary, bends shall be of sufficient radius for the proper rodding and installation of cable. Changes in direction of runs exceeding a total of 10 degrees, either vertical or horizontal, shall be made by long sweep bends having a minimum radius or curvature of 25 ft. , except that manufactured bends may be used at ends of short runs of 100 ft. or less, and then only at ends of short runs of 100 ft. or less, and then only at or close to the UNDERGROUND SYSTEM 16500 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16500 UNDERGROUND SYSTEM PART 1 : GENERAL 1 . 01 SCOPE OF WORK A. The Contractor shall furnish and install a complete system of underground raceways, and handholes, as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 .02 SUBMITTALS A. Manufacturer' s data and descriptive literature shall be submitted for all material specified hereinafter. B. The Contractor shall furnish one set of marked copies of Contract Drawings, showing the exact routing and depths of all underground conduit. The Drawings shall be scaled plot plans, showing the principal outline of buildings and structures . The conduits, ducts, all bends deviating from a straight line, and pads and handholes shall be referenced dimensionally from fixed objects of structures. 1 .03 RELATED WORK SPECIFIED ELSEWHERE A. Excavation and backfilling is included in Division 2 . B. All concrete and reinforcing is included in Division 3 . PART 2 : PRODUCTS 2 .01 MATERIALS UNDERGROUND SYSTEM 16500 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16450 SELECTIVE REMOVAL PART 1 : GENERAL 1 .01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required for selective removal and disposal of all electrical materials and equipment to be removed, and for miscellaneous alterations all as indicated on the Drawings and hereinafter specified. B. The Contractor shall be solely responsible for making all necessary arrangements and for performing any necessary work involved in connection with the discontinuance or interruption of all electric power to existing equipment and systems . PART 2 : PRODUCTS (None this Section) Part 3 : EXECUTION 3. 01 REMOVAL A. Selectively remove electrical single phase overhead service equipment currently serving the building. Remove such materials and dispose of same off the site in accordance with all federal, state and local laws and regulations. B. Removal work shall be coordinated with the electric utility and shall extend only to the main disconnect device in the basement. All other electrical equipment will be removed by others. *** END OF SECTION *** SELECTIVE REMOVAL 16450 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 5. Provision shall be made in the main breaker compartment of each unit to lock breakers "ON" or "OFF" . 6 . Provide lightning protection for each main disconnect device consisting of surge protection and lightning arrestors equal to G.E. Model 9118BAB301 and 9L15BCC008 . 7 . In metering compartment provide three donut type metering class CT' s and an electronic digital type microprocessor based meter. Meter to provide direct reading metered valves for : • AC amperes Phase A, Phase B and Phase C • AC voltage for each line and each line to neutral • Power Demand (KW) • Kilowatt hours Meter to be door mounted and shall provide an RS232 output port. PART 3 : EXECUTION 3 .01 INSTALLATION A. Nameplates shall be permanently install don all distribution and control equipment. Nameplates shall identify the distribution equipment and indicate the load served by control equipment. B. Electrical equipment shall be supported in an acceptable manner. A safety factor of not less than two shall be applied to all equipment supports. *** END OF SECTION *** MISCELLANEOUS EQUIPMENT 16400 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 3 . NEMA Type 4 enclosures shall be cast metal. 4 . Manual motor starters shall be as manufactured by Allen Bradley Company. D. Nameplates shall be black and white laminated plastic having engraved letters extending through the black face into the white layer. E. Equipment Supports 1 . Support for mounting lighting fixtures, meter centers, panelboards, starters and other electrical distribution and control equipment shall be continuous slot channels with inturned clamping ridges . Channels and fittings shall be formed from low carbon steel strip, hot dipped galvanized and field painted. Nuts shall be case-hardened steel with serrated grooves . 2 . Support equipment shall be as manufactured by Unistrut Building Systems, Van Huffel Tube Corp. , or approved equal. Support sizes and arrangements shall be as required for the equipment being supported. F. Main Circuit Breaker with Current Transformer Compartment Unit 1 . The main disconnect device for the building shall each consist of a main circuit breaker compartment and a cold sequence utility current transformer compartment. Unit shall be suitable for use as service entrance equipment, listed by Underwriters ' Laboratories. 2 . Enclosure shall be code-gauge sheet steel, totally enclosed, fron accessible with gray baked enamel finish. 3. Circuit breaker compartment shall contain thermal magnetic, molded case circuit breaker rated as indicated on the Drawings . Minimum interrupting rating to be 22,000 amperes RMS symmetrical at 240 volts . 4. Provision shall be made on the metering compartments for seals . MISCELLANEOUS EQUIPMENT 16400 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Magnetic Motor Starters 1 . Motor starters shall be 2 or 3 pole, 1 or 3- phase as required, 60 Hz, 208 volt, magnetically operated, full voltage, non- reversing, except as shown on the Drawings . NEMA sizes shall be as required for the horsepowers of the motors actually furnished. 2 . Two speed starters shall be for single or two winding motors as required. 3 . Each motor starter shall have a 120 volt operating coil. Three phase starters shall have a 3 pole overload relay. Auxiliary contacts shall be provided as shown on the Drawings or as required. 4 . Overload relays shall be adjustable, ambient compensated with manual, externally operable reset. 5 . Built-in control stations and indicating lights shall be furnished where shown on the Drawings . 6 . Enclosure type shall be NEMA 1 unless otherwise indicated on the Drawings. Outdoor units shall have NEMA 4 enclosures . 7 . Starters shall be furnished with built-in, dry-type control power transformers with secondary fuse. 8 . Combination starters shall include an unfused disconnect switch, unless otherwise indicated on the Drawings. 9 . Magnetic motor starters shall be as manufactured by Allen Bradley Company. C. Manual Motor Starters 1 . Manual motor starters shall be furnished and installed for single-phase motors. Manual starters shall be non-reversing type, or as otherwise shown on the Drawings. Built-in control stations shall be furnished where shown on the Drawings. 2 . Enclosure type shall be NEMA 1 unless otherwise indicated on the Drawings . Outdoor units shall have NEMA Type 4 enclosures. MISCELLANEOUS EQUIPMENT 16400 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16400 MISCELLANEOUS EQUIPMENT PART 1 : GENERAL 1 . 01 SCOPE OF WORK A. Furnish and install all miscellaneous equipment as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 . 02 SUBMITTALS A. Manufacturer' s data and descriptive literature shall be submitted for all material specified hereinafter. B. Shop drawings complete with dimensional data, overall and component ratings, manufacturer' s descriptive literature, wiring diagrams, and circuit breaker characteristic curves, shall be submitted for the main circuit breaker with metering compartment. PART 2 : PRODUCTS 2 .01 MATERIALS A. Disconnect Switches 1 . Disconnect switches shall be general-duty, quick-make, quick-break, visible blades, 240 volt, with full cover interlock. Switches shall be three pole, thirty ampere unless otherwise shown on the Drawings. Disconnect switches shall be of the fused type where indicated on the Drawings . 2 . Enclosure type shall be NEMA 1 unless otherwise indicated on the Drawings . All outdoor switches shall have NEMA 4 enclosures . 3 . Switches shall be as manufactured by Square D Co. , General Electric Co. , Westinghouse Electric Corp. , or equal. MISCELLANEOUS EQUIPMENT 16400 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 3 . 03 CLEANING UP A. All fixtures shall be left in a clean condition, free of dirt and defects, before acceptance by the Authority. *** END OF SECTION *** LIGHTING SYSTEMS 16350 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 1 . Ballasts shall be as required for the fixtures indicated on the Lighting Fixture Schedule. J. Flexible fixture hangers shall be totally- enclosed, gasketed, cushion type. Hangers shall be rated not less than 150 percent of the complete fixture weight being supported. PART 3: EXECUTION 3 .01 INSTALLATION A. Each lighting fixture shall be a completely finished unit and furnished, with all components, mounting and/or hanging devices necessary, for the proper installation of the particular fixture in its designated location and shall be completely wired ready for connection to the branch circuit wires at the outlet. B. When fixtures are noted to be installed recessed, they shall be complete with the proper accessories for installing in the particular ceiling involved. All recess mounted fixtures shall be supported from the structure and shall not be dependent on the suspended ceilings for their support. C. Flexible fixture hangers shall be used for all pendant mounted fixtures. D. Furnish and install nameplates at all wall switches where their purpose is not otherwise readily obvious and at special use receptacles. E. Back-to-back outlets shall not be permitted. Provide lateral separation of at least one stud. Through-the-wall boxes shall be prohibited. 3 .02 REPLACEMENT A. Lamps used during the building construction, prior to two weeks from completion of the work, shall be removed and replaced with new lamps. All lighting fixtures shall be left completely and properly lamped. LIGHTING SYSTEMS 16350 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects high strength thermoplastic or nylon actuator. Switches shall be self-grounding type, single pole, double pole, three way or four way as shown on Drawings . Switches shall be indicating, toggle reaction, flush, quiet type. Switches shall be manufactured by Arrow-Hart. E. General purpose receptacles shall be Specification Grade rated 20 ampere, 125 volt, 2 pole, 3 wire, with nylon face grounding type with totally- enclosed molded body, binding screw terminals, grounding screw terminal, and bronze contacts . Ground fault circuit interrupters with "TEST" and "RESET" pushbuttons shall be provided where indicated on the Drawings. Receptacles shall be self-grounding type as manufactured by Arrow-Hart. F. Unless otherwise specified, device plates for switches and receptacles shall be of high-impact self-extinguishing, thermoplastic materials in color to match devices . Plates for surface mounted boxes shall be the same materials and finish as the box. Plates for weatherproof devices shall be gasketed with rocket arm or lever operators for switches and spring covers for receptacles . G. Dimmers shall be NOVA series, slide to OFF type, as manufactured by Lutron. Where dimmers are indicated on the Drawings to be ganged with single or multi pole switches, such ganged devices shall also be of the NOVA series with a single multi gange face plate for the entire assembly. H. Lighting fixture types shall be as shown on the "Lighting Fixture Schedule" on the Drawings. No substitutions allowed. I . Lamps 1 . Fluorescent lamps shall be medium bi-pin, recessed double contact, rapid start, 3000 R watt-miser type by General Electric Company. 2 . Incandescent lamps shall be 120 volt, inside frosted with medium base. 3. Other lamps shall be as indicated on the Lighting Fixture Schedule. I . Ballasts LIGHTING SYSTEMS 16350 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16350 LIGHTING SYSTEMS PART 1: GENERAL 1 .01 SCOPE OF WORK A. Furnish and install complete lighting systems including panelboards, lighting fixtures, receptacles, switches, etc. and all necessary accessories and appurtenances as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 .02 SUBMITTALS A. Manufacturer' s data and descriptive literature shall be submitted for all materials specified hereinafter. Data for lighting fixtures shall include photometric data and curves. 1 .03 STANDARDS A. All lighting fixtures shall be in accordance with the National Electrical Code and shall be constructed in accordance with the latest edition of Underwriters' Laboratories, Inc. Standards for Safety, Electric Lighting Fixtures" . All lighting fixtures shall be U.L. labeled. PART 2: PRODUCTS 2 .01 MATERIALS A. Panelboards shall be as specified under SECTION 16300. B. Conduit shall be as specified under SECTION 16150. C. Wire shall be as specified under SECTION 16200. D. Unless otherwise specified, wall switches shall be rated 20 ampere, 120/277 volt. Switches shall be of Specification Grade, color to be selected by the Architect and shall have binding screw terminals, grounding screw terminal and totally- enclosed molded body with LIGHTING SYSTEMS 16350 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Test dielectric liquid to ASTM D877, using 25,000 volts minimum breakdown voltage, after installation and before energizing from system. C. Test transformer to ANSI/IEEE C57 . 12 .90 . D. Test transformer to ANSI/IEEE C57 . 12 .91 . 3. 04 ADJUSTING A. Adjust work under provisions of Section 16100. B. Adjust primary taps so that secondary voltage is within 2 percent of rated voltage. END OF SECTION DISTRIBUTION TRANSFORMERS 16321 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects I. Accessories : ANSI C57 . 12.22 standard accessories and magnetic liquid level gage, and dial type thermometer. J. Cooling and Temperature Rise: ANSI/IEEE C57 . 12 .01; Class AA. 220 degree C insulation class with 150 degree C rise over 40 degree C ambient. K. Primary Terminations: Bushing wells to ANSI/IEEE 386; provide six for primary selective feed. Include bushings for insulated loadbreak connectors. L. Primary Switching: Internal oil-immersed gang-operated load break switch. Provide two, for primary selective switching. M. Primary Overcurrent Protection: Internally-mounted, oil- immersed, expulsion fuses. N. Secondary Terminations: Spade lugs . 0. Other Accessories: Primary lightning arrestors. PART 3 EXECUTION 3 .01 EXAMINATION A. Verify that pads are ready to receive work. B. Verify field measurements are as shown on Drawings. C. Verify that required utilities are available, in proper location and ready for use. D. Beginning of installation means installer accepts conditions. 3.02 INSTALLATION A. Install in accordance with manufacturer' s instructions. B. Install safety labels to NEMA 260. 3 .03 FIELD QUALITY CONTROL A. Field testing will be performed by the Owner after installation is complete. DISTRIBUTION TRANSFORMERS 16321 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects D. Submit product data indicating standard model design tests and options . E. Submit manufacturer' s installation instructions under provisions of Section 16100 . 1 .05 OPERATION AND MAINTENANCE DATA A. Submit operation and maintenance data under provisions of Section 16100. B. Include procedures for sampling and maintaining fluid, cleaning unit, and replacing components . 1.06 QUALITY ASSURANCE A. Manufacturer: General Electric Company. 1.07 DELIVERY, STORAGE, AND HANDLING A. Store and protect products under provisions of Section 16100. PART 2 PRODUCTS 2 .01 MANUFACTURERS - PAD MOUNTED TRANSFORMERS A. General Electric Company 2 .02 PAD MOUNTED TRANSFORMERS A. Liquid-filled Transformers: ANSI C57. 12 .22; three phase, pad mounted, self-cooled transformer unit. B. Capacity: 112 .5 kVA. C. Primary Voltage: 2 .4 kV, delta connected; provide standard primary taps, with externally-operated tap changer. D. Secondary Voltage: 120/208 volts, wye connected. E. Impedance: 4.5 percent. F. Basic Impulse Level: 95 W. G. Cooling and Temperature Rise; ANSI C57 . 12 .22; Class OA. 65 degrees C, self-cooled. H. Liquid: Oil. DISTRIBUTION TRANSFORMERS 16321 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16321 DISTRIBUTION TRANSFORMERS PART 1 GENERAL 1 .01 SECTION INCLUDES A. Liquid filled pad mounted distribution transformer. 1 .02 RELATED SECTIONS A. Section 03300 - Cast-In-Place Concrete: Pads for transformer support. 1 .03 REFERENCES A. ANSI C37 .47 - Specifications for Distribution Fuse Disconnecting Switches, Fuse Supports, and Current- Limiting Fuses. B. ANSI C57 . 12 .22 - Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase Distribution Transformers with High--Voltage Bushings; High Voltage, 34500 GrdY/19920 Volts and Below; 2500 WA and Smaller. C. ANSI/IEEE C57 . 12.90 - Test Code for Liquid-Immersed Distribution Power, and Regulating Transformers. D. ANSI/IEEE 386 - Separable Insulated Connector Systems for Power Distribution Systems Above 600 V. E. ASTM D877 - Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes. F. NEMA 260 - Safety Labels for Padmounted Switchgear and Transformers Sited in Public Areas. 1.04 SUBMITTALS A. Submit shop drawings under the provisions of Section 16100 . B. Submit shop drawings indicating outline dimensions, connection and support points, weight, specified ratings and materials . C. Submit product data under the provisions of Section 16100. DISTRIBUTION TRANSFORMERS 16321 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects G. Panelboards shall be Series A as manufactured by General Electric Company. H. Circuit breakers used for panel switching of lighting circuits shall be so rated. I. Circuit breakers used in conjunction with HVAC compressor circuits shall be HACR rated. J. GFI type circuit breakers shall be provided where indicated on the panelboard schedules. PART 3: EXECUTION 3 . 01 INSTALLATION A. Boxes for surface-mounted panelboards shall be installed with at least 1/2 in. air space between the box and the wall. B. Circuit directories shall be typed, indicating circuit numbers and circuit designations actually connected. . C. Furnish and install a nameplate on the front of each panelboard indicating the panelboard designation. *** END OF SECTION *** PANELBOARDS 16300 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects sufficient size to provide a minimum gutter space of 4-in. on all sides . 2 . Surface mounted boxes shall have an internal and external finish as hereinafter specified in Paragraph E4. Surface mounted boxes shall be field punched for conduit entrances . 3. At least 4 interior mounting studs shall be provided. E. Trim 1 . Hinged doors covering all circuit breaker handles shall be included in all panel trims . 2 . Doors shall have semi flush type cylinder lock and catch, except that doors over 48-in. in height shall have a vault handle and 3- point catch, complete with lock, arranged to fasten door at top, bottom and center. Door hinges shall be concealed. Two keys shall be supplied for each lock. All locks shall be keyed alike; directory frame and card having a transparent cover shall be furnished on each door. 3 . The trims shall be fabricated from code gauge sheet steel. Trims shall be fastened with quarter-turn clamps. 4. All exterior and interior steel surfaces of the panelboard shall be properly cleaned and finished with ANSI 255 . 1, No. 61 light gray paint over a rust-inhibiting phosphatized coating. F. Circuit Breakers 1. Panelboards shall be furnished with circuit breakers having frame sizes and trip settings as shown on the Drawings. 2 . Circuit breakers shall be thermal-magnetic, molded case type with interrupting capacities not less than 10,000 amperes, RMS symmetrical at rated voltage. 3 . - Circuit breakers installed in panelboards shall be plug-in type. PANELBOARDS 16300 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Interiors 1 . All interiors shall be complete with buses, dead-front shield, circuit breakers, wire connectors, etc. All wire connectors, except screw terminals, shall be of the anti-turn, solderless type and all shall be suitable for copper or aluminum wire of the sizes indicated. 2 . Interiors shall be so designed that circuit breakers can be replaced without disturbing adjacent breakers and without removing the main bus connectors and shall be so designed that circuits may be changed without machining, drilling or tapping. 3 . Branch circuits shall be arranged using double row construction except when narrow column panels are indicated. Branch circuits shall be numbered by the manufacturer. 4 . A nameplate shall be provided listing panel type, number of circuit breakers and ratings . C. Buses 1 . Bus bars, cross connectors and neutral bars shall be manufacturer' s standard. Full size neutral bars shall be included. Bus bar taps shall be arranged for sequence phasing of the branch circuit devices. Bussing shall be braced throughout to conform to industry standard practice governing short circuit stresses in panelboards. Phase bussing shall be full height without reduction in size. Cross connections shall be copper. 2 . Neutral bussing shall have a suitable lug for each outgoing feeder requiring a neutral connection. 3 . Spaces for future circuit breakers shall be bussed for the maximum device that can be fitted into them. D. Boxes 1. Boxes shall be galvanized, code gauge steel without knockouts. Boxes shall be of PANELBOARDS 16300 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16300 PANELBOARDS PART 1: GENERAL 1 .01 SCOPE OF WORK A. Furnish and install the panelboards, with all necessary incidentals, as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 .02 SUBMITTALS A. Shop drawings complete with dimensional data, overall and component ratings, manufacturer' s descriptive literature and circuit breaker characteristic curves shall be submitted for the panelboards. PART 2 : PRODUCTS 2 .01 RATING A. Panelboard ratings shall be as shown on the Drawings . All panelboards shall be rated for the intended service. All panelboards shall be rated 101000 RMS, symmetrical fault current. 2 .02 STANDARDS A. Panelboards shall be in accordance with the Underwriters' Laboratories, Inc. "Standard for Panelboards" and "Standard for Cabinets and Boxes" and shall be so labeled where procedures exist. Panelboards shall also comply with NEMA Standards for panelboards and the Massachusetts Electrical Code. 2 . 03 CONSTRUCTION A. Panelboards shall be factory assembled dead-front type. PANELBOARDS 16300 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Liquidtight flexible metal conduit, larger than 1- 1/4 inch shall be furnished with bonding jumpers. Jumpers shall be external to the conduit and connected to grounding fittings . Jumpers shall be run parallel with the conduit, not spiral wound, and held with plastic tie wraps . C. All enclosures containing equipment to which electrical connections are made, motor and transformer frames, metallic raceway systems, electrical equipment supports and exposed structural steel shall be grounded. D. Exposed ground connections shall be made with suitable ground clamps . Concealed or buried connections shall be made by exothermic welding. Exothermic welding shall be performed using clean, properly sized molds . E. Grounding electrode conductors shall be run in rigid metal conduits where required for protection and where shown on the Drawings. The protecting conduits shall be bonded to the grounding electrode conductors at both ends. F. Water pipe connections shall not be painted. G. Underground conductors shall be laid slack. 3.02 TESTS A. Test the resistance of the interconnected system. All test equipment shall be provided under this Section. Dry season resistance of the interconnected system shall not exceed five ohms. If such resistance cannot be obtained with the system as shown, provide additional grounding as directed by the Architect, without additional payment. *** END OF SECTION *** GROUNDING SYSTEM 16250 - 2 SMITH COLLEGE,OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16250 GROUNDING SYSTEM PART 1 : GENERAL 1 .01 SCOPE OF WORK A. Furnish, install and test the complete grounding system, including all equipment, materials and incidentals, in strict accordance with Article 250 of the Massachusetts Electrical Code, as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 .02 SUBMITTALS A. Manufacturer' s data and descriptive literature shall be submitted for all material specified hereinafter. PART 2: PRODUCTS 2 .01 MATERIALS A. Conduit shall be as specified under SECTION 16150 . B. Wire shall be as specified under SECTION 16200. C. Ground rods shall be copperclad steel, 3/4 inch diameter, 10 ft. long minimum. Ground rods shall be Copperweld approved equal product. PART 3 : EXECUTION 3 .01 INSTALLATION A. The grounding system shall be installed as indicated on the Drawings and as specified herein. Grounding conductors shall be run with feeders and branch circuit conductors where required and where shown on the Drawings . Isolated boxes, enclosures and metal conduit sections shall be bonded to the grounding conductors by means of ground lugs or grounding bushings. GROUNDING SYSTEM 16250 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects C. Wire and cable shall be installed in raceways except as permitted hereinafter. Type THWN, XHHW or THW wire shall be installed for all circuits where raceways are indicated on the Drawings and for all circuits where raceways are required. Conduit sizes on the Drawings are based on Type XHHW or Type THWN conductors as appropriate. If Type THW wire is installed, the Contractor shall provide larger conduit size, if required, in accordance with requirements of the Massachusetts Electric Code at no additional cost to the Owner. D. All wires and cables, except lighting and receptacle wiring, shall be uniquely identified with wire markers at each termination and splice. E. Type MC may be installed in concealed construction only for branch circuits where raceways are not specifically noted on the Drawings. The application of and installation of Type MC cable shall be in strict conformance with the requirements of the Massachusetts Electric Code. F. Pull wire used in PVC conduits shall be non- metallic. G. Except where shown on the Drawings or specified, 5KV cable shall not be spliced. Where splicing is permitted, splice details shall be submitted to the Engineer for approval. H. Owner will fireproof 5 RV cable in primary manhole and pad-mounted transformer after installation is complete. I. Fire alarm system and telephone system cable shall be installed in conduit where exposed. 3 .02 TESTS A. All 600-volt wire insulation shall be tested with a megohm meter after installation. These shall be made at not less than 500-V. Submit a written test report of the results to the Architect. *** END OF SECTION *** WIRES AND CABLES 16200 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 2 .04 5000 VOLT CABLE TERMINATIONS A. Outdoor terminations shall be hook-stick operated local break elbows as manufactured by Elastimold or equal. 2 .05 5000 VOLT CABLE SPLICES A. Splices shall be pre-molded, permanent, straight, tee, or wye. Splices shall be suitable for manhole or direct-burial installation, and shall be rated for the cable current carrying capacity. B. Splices shall be as manufactured by Elastimold, or equal. 2 .06 WIRE AND CABLE MARKERS A. Wire and cable markers shall be "Omni-Grip" as manufactured by the W.H. Brady Co. , Thomas & Betts Co. , 3M Co. , or equal. B. Wire and cables with diameters exceeding the capacity of the "Omni-Grip" shall be marked with pre-printed, self-adhesive vinyl tapes as manufactured by the W.H. Brady Co. , Panduit Corp. , or equal. 2.07 FIRE-PROOFING TAPE A. Fire-proofing tape shall be Scotch No. 77 with Scotch No. 27 binding or equal. 2 .08 WALL AND FLOOR SLAB OPENING SEALS A. Wall and floor slab openings shall be sealed with "FLAME-SAFE" as manufactured by the Thomas and Betts Corp. , or equal. PART 3: EXECUTION 3.01 INSTALLATION A. All conductors shall be carefully handled to avoid kinks or damage to insulation. B. Lubrications shall be used to facilitate wire pulling. Lubricants shall be U.L. listed for use with the insulation specified. WIRES AND CABLES 16200 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects AWG shall be used. Wire sizes shall be not less than required by the Massachusetts Electric Code. E. Type MC cable may be used for concealed branch circuit wiring when wiring in raceways is not specifically indicated on the Drawings, and provided that the installation is in full compliance with the Massachusetts Electric Code. F. 5KV cable shall be used for the primary feeders to the pad-mounted transformer as indicated on the Drawings . G. Cable for fire alarm system wiring shall be limited energy type, 4 conductor No. 16 AWG, with outer jacket. H. Cable for telephone system wiring shall be 4 pair No. 24 AWG telephone cable with outer jacket. PART 2: PRODUCTS 2 .01 MATERIALS A. Conductors shall be annealed, 98 percent conductivity, soft-drawn copper, unless otherwise specified. B. All conductors No. 8 AWG and larger shall be stranded. All conductors No. 10 and smaller shall be solid. 2 .02 600 VOLT WIRE A. Type THWN, XHHW and THW shall be manufactured by the Pirelli Cable Co. , Collyer Insulated Wire Co. , The Okonite Co. , or approved equal. B. Type MC cable shall be multi-conductor with ground wire. Insulation shall be Type THWN or XHHN. Armor shall be interlocked galvanized steel or aluminum. 2 .03 5000 VOLT CABLE A. Five thousand volt cable shall be single conductor,ethelene propylene rubber insulated, shielded, polyvinyl chloride jacketed. 5KV ungrounded neutral (insulation level 133%) as manufactured by Okonite Company, Kerite Company or approved equal. WIRES AND CABLES 16200 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16200 WIRES AND CABLES PART 1: GENERAL 1 .01 SCOPE OF WORK A. Furnish, install and test all wire, cable and appurtenances as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1.02 SUBMITTALS A. Samples of proposed wire shall be submitted for review. Each sample shall have the manufacturer' s name, UL label, size, type of insulation and voltage stenciled on the jacket. B. Acceptable samples will be sent to the project location for comparison by the Architect with the wire actually installed. C. Installed, unacceptable wire shall be removed and replaced at no additional cost to the Authority. D. Manufacturer' s data and descriptive literature shall be submitted for all wire, cable and appurtenances. 1.03 APPLICATIONS A. Wire and cable for lighting and power branch circuits shall be Type THWN, or XHHW, as specified hereinafter. Feeders and branch circuit wiring larger than No. 6 AWG shall be Type XHHW or Type THW. B. Wire for control, indicating and metering circuits shall be Type THWN, stranded. No. 14 AWG main. C. Ground wires shall be Type THWN or XHHW, green. D. Except for control, indication, metering and signal wiring, no conductor smaller than No. 12 WIRES AND CABLES 16200 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects where required to raise conduits from the surface. Multiple, horizontal runs shall be supported on trapese hangers with steel horizontal members and threaded rods not less than 3/8 in. diameter. Hangers shall be attached to structural steel by means of beam clamps . Spot type inserts shall be used in concrete. B. Conduit bends shall be carefully made to prevent distortion of the circular cross-section. No conduit run shall have more than the equivalent of three 90 deg. bends between pulling points . Changes in direction shall be made with bends, standard elbows and pull boxes. Bends in parallel runs shall be concentric. C. Conduit shall not be supported from piping, piping supports, ductwork, suspended ceiling supports or mechanical equipment subject to vibration or removal. D. The ends of all conduits shall be tightly plugged during building construction until wires are to be pulled. Spare conduits shall be furnished with threaded caps. E. Conduits shall be terminated at pressed steel boxes and ungasketed sheet metal enclosures with double locknuts and suitable bushings . Bushings installed on conduits containing ground wires shall be grounding type. Conduits shall be terminated at gasketed sheet metal enclosures and all weatherproof enclosures with conduit hubs . F. Rigid steel conduit connections shall be made with threaded fittings. G. Wire shall not be pulled until the conduit system is complete in all details. H. Where underground conduits penetrate walls or slabs on grade, conduits shall be appropriately sealed by the General Contractor. *** END OF SECTION *** ELECTRICAL RACEWAY SYSTEM 16150 - 5 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 5 . Conduit elbows shall be of the same material and construction as the conduits to which they are connected. 6 . Conduit hubs shall be as manufactured by Myers Electric Products, Inc. , Raco, Inc. , Appleton Electric Co. , or approved equal. 7 . Fittings used with liquidtight, flexible conduit shall be of the screw-in, compression type with sealing ring. Fittings larger than 1-1/2 in. shall be furnished with integral ground lugs. Fittings shall be as manufactured by Thomas and Betts Co. , Crouse- Hinds Co. , Appleton Electric Co. , or approved equal. 8 . Combination expansion-deflection fittings shall be Type XD as manufactured by the Crouse-Hinds Co. , Type DX as manufactured by O/Z Gedney Co. , or approved equal. G. Hangers, rods, backplates, beam clamps etc. shall be galvanized iron or steel. They shall be as manufactured by the Appleton Electric Co. , Thomas and Betts Co. , Unistrut Corp. , or approved equal . H. Wireways shall be a sheet steel wiring trough with covers fabricated from a minimum of 14 gauge steel with ANSI gray polyester coating over phosphatized surfaces, inside and outside. Wireway sizes will be as indicated on the Drawings. Wireways shall be furnished without knockouts. Covers for wireways shall have a continuous hinge and shall be furnished complete with oil resistant gasket and cover clamps which shall make the unit oiltight. All hardware, including cover clamps, shall be stainless steel. PART 3 : EXECUTION 3 .01 INSTALLATION A. Exposed conduits shall be run parallel to or at right angles to walls . Conduit runs shall be straight and true. Conduit shall be supported at not more than 8 ft. intervals. Single conduits shall be supported by means of one-hole pipe clamps . One-screw backplates shall be installed ELECTRICAL RACEWAY SYSTEM 16150 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects C. Flexible metal conduit shall be of the interlocked type as manufactured by Electri-flex or approved equal . D. PVC conduit shall be rigid poly vinyl chloride Schedule 40, as manufactured by Carlon, an Indian Head Co. , Phillips Petroleum Co. , Triangle Pipe and Tube Co. , or equal. E. Liquidtight, flexible metal conduit shall consist of a flexible, corrosion-resistant metal core with an extruded, watertight, synthetic jacket. Conduits smaller than 1-1/2 in. shall have a continuous ground conductor under the jacket. Conduit shall be Sealtite Type UA manufactured by Anaconda Metal Hose Div. , or as manufactured by American Flexible Conduit Co. , Inc. , Universal Metal Hose Co. , or approved equal. F. Boxes and Fittings 1 . Pressed steel switch and outlet boxes shall be hot-dipped galvanized as manufactured by Raco, Inc. , Adalet Co. , O.Z . Manufacturing Co. , or approved equal: 2 . Sheet metal boxes shall have continuously welded seams, ground smooth. Steel boxes shall be hot-dipped galvanized after welding. Box bodies shall be flanged and shall be without holes or knockouts. Bodies shall be not less than 14 gauge metal and covers shall be not less than 12 gauge metal. Covers shall be gasketed and fastened with stainless steel hardware. Boxes shall be as a manufactured by Hoffman Engineering co. , Superior Switchboard & Devices, Sun Metal Products Div. , or approved equal. 3. Cast or malleable iron boxes and fittings shall have cadmium-zinc finish with cast covers and stainless steel screws as manufactured by the Crouse-Hinds Co. , Appleton Electric Co. , L.E. Mason Co. , or approved equal. 4. Electrical metallic tubing fittings shall be of the steel raintight type as manufactured by the Appleton Electric Co. , Crouse-Hinds Co. , or approved equal. ELECTRICAL RACEWAY SYSTEM 16150 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects G. Except as otherwise shown on the Drawings, terminal, junction and pull boxes larger than 4 in. square shall be sheet steel. H. Combination expansion - deflection fittings shall be used where conduits cross structure expansion joints . I. Liquidtight, flexible metal conduit shall be used for all motor terminations and for connections to equipment subject to vibration. J. No conduit smaller than 3/4 in. electrical trade size shall be used, except as otherwise shown on the Drawings. Box sizes shall not be less than that required by the Massachusetts Electrical Code. PART 2 : PRODUCTS 2 .01 MATERIALS A. Rigid Metal Conduit 1. Rigid steel conduit shall be, heavy-gauge steel, not dipped galvanized inside and outside over the entire length including threads and shall have an additional factory- applied sealing finish inside and outside. Conduit shall be as manufactured by Youngstown Sheet and Tube Co. , Allied Tube and Conduit Corp. , Wheeling-Pittsburgh Steel Corp. , or approved equal. 2 . Rigid metal conduit shall be furnished with a coupling on one end and a thread protector on the other. B. Electrical Metallic Tubing 1. Electrical metallic tubing shall be hot- dipped galvanized steel as manufactured by the Youngstown Sheet and Tube Co. , Allied Tube and Conduit Corp. , Wheatland Tube Co. , or approved equal. EMT shall conform to all provisions of ANSI standard C80. 3, Federal Specification NWC-563, and U.L. standard 797 . ELECTRICAL RACEWAY SYSTEM 16150 - 2 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects SECTION 16150 ELECTRICAL RACEWAY SYSTEMS PART 1: GENERAL 1.01 SCOPE OF WORK A. Furnish and install the complete raceway systems, with all accessories, fittings, boxes, etc. , as shown on the Drawings and as specified hereinafter. B. The Contractor' s attention is directed to the requirements of SECTION 16100, ELECTRICAL WORK - GENERAL PROVISIONS. 1 . 02 SUBMITTALS A. Manufacturer' s data and descriptive literature shall be submitted for all materials specified hereinafter. 1 .03 APPLICATIONS A. All wiring shall be installed in rigid electrical metallic tubing, except as otherwise shown on the Drawings or specified hereinafter. See SECTION 16200 for use of Type MC cable. B. Rigid steel conduit shall be used in outdoor locations. C. Flexible metal conduit shall be used where indicated on the Drawings. D. PVC conduit shall be used underground; where encased in concrete walls and slabs; or where indicated on the Drawings. E. Fittings, exposed switch, outlet and control station boxes and other exposed boxes 4 in. square, and smaller, shall be cast or malleable iron where used with electrical metallic tubing or rigid steel conduit. F. Flush switch, outlet and control station boxes shall be pressed steel. ELECTRICAL RACEWAY SYSTEM 16150 - 1 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects D. Workmanship shall be in accordance with the best modern practice and of "first quality" . 3 . 05 GUARANTEE A. The Contractor shall be responsible for the successful operation of all electrical systems, equipment and materials installed under this Contract for a period of one year from the date of final acceptance. Defective installations, equipment or material shall be repaired or replaced at no expense to the Authority. *** END OF SECTION *** ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 10 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects does not impair the functional integrity of the equipment. 3 . 02 RECORD DRAWINGS A. As the work progresses, legibly record all field changes on a set of project contract drawings . These drawings shall be given to the Architect or Owner at the completion of the project. 3 . 03 TESTS AND ADJUSTMENTS A. Test all systems furnished under DIVISION 16 and repair or replace all defective work. Make all necessary adjustments to the systems and equipment and instruct the Owner' s personnel in the proper operation of the systems and equipment. B. The Contractor' s attention is directed to requirement of the various sections of DIVISION 16 for additional test specifications. C. At a time designated by the Architect, the Contractor shall conduct final operating tests, inspections and demonstrations of the electrical systems. This inspection shall be done in the presence of the Architect and shall assure that the installation conforms to the requirements of the Contract. 3 .04 PROJECT EXECUTION A. Site Examination: The Contractor shall familiarize himself with the site and other conditions affecting the Contract. B. Construction utilities: Provide construction power wiring and lighting as required. Electrical energy costs will be paid by others . Conform to all applicable code requirements for temporary facilities. Specific attention is drawn to Articles 210 and 305 of the Massachusetts Electrical Code and OSHA requirement. C. Clean-up: Maintain and leave the premises in a neat and clean condition. Electrical equipment shall be left clean and undamaged. The Contractor shall repair or replace damaged items at no expense to the Authority. ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 9 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects B. Materials and equipment used shall be Underwriters ' Laboratories, Inc. listed. C. Electrical equipment shall at all times during construction be adequately protected against mechanical injury or damage by water. Electrical equipment shall be stored in dry permanent shelters. If any apparatus has been damaged, such damage shall be repaired at no additional cost to the Owner. If any apparatus has been subject to possible injury by water, it shall be thoroughly dried out and put through such special tests as directed by the Architect, or shall be replaced at no additional cost to the Owner. D. The Contractor' s attention is directed to the requirements of the various sections of DIVISION 16 for additional product specifications. 2 . 02 MANUFACTURER' S NAMEPLATES A. All equipment shall have the manufacturer' s name, address, model or type designation, serial number and all applicable ratings clearly marked thereon in a location which can be feadily observed after installation. The required information may be die- stamped into the surface of the equipment or may be marked on durable nameplates permanently fastened to the equipment. PART 3: EXECUTION 3.01 INSTALLATION A. Provide and place all sleeves for conduit penetrations through floors, walls, partitions, etc. B. Investigate each space in the structure through which equipment must pass to reach its final location. If necessary, the manufacturer shall be required to ship his equipment in sections, sized to permit passage through such restricted areas. C. Equipment shall be kept upright at all times . When equipment has to be tilted for east of passage through restricted areas during transportation, the manufacturer shall be required to brace the equipment suitably, to insure that the tilting ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 8 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects C. The term "Architect" shall designate either Architect or Engineer. 1 . 11 SITE VISIT A. Prior to preparing his bid, each bidder or his representative shall visit all areas of the existing facilities in which work is to be undertaken for this project, in order to carefully inspect the existing installation. The Contractor shall note all locations and conditions affecting his work. Submission of a bid shall be taken as evidence that he has undertaken this site inspection and is accepting full responsibility for a complete knowledge of the factors affecting his work. 1 . 12 BID ALTERNATES A. Contractor shall note that various components of the work as noted on the Drawings and as listed in the Invitation to Bidders are to be bid as add alternates to the Base Bid: B. Alternate No. 1 shall comprise all electrical work associated with providing a source of power for the dehumidifier. C. Alternate No. 2 shall comprise all electrical work associated with providing the primary electrical service to the building, including primary cables and terminations, primary ductbank, transformer pad and associated grounding and pad-mounted transformer. PART 2: PRODUCTS 2 .01 MATERIALS A. The materials used in all systems shall be new, unused and as hereinafter specified. All materials, where not specified, shall be of the very best of their respective kinds. Samples of materials or manufacturer' s specifications shall be submitted for review as required by the Architect. ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 7 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects other trades is also included under the work of this Section. 1 . 07 ELECTRIC SERVICE A. The electric service for the building will be obtained from the existing 2,400 volt primary underground distribution system as indicated on the Drawings . B. The existing 120/240 volt, single phase, 3 wire, 60 Hz service to the building shall be removed by the Contractor under Selective Removal. New service entrance equipment will be provided under this contract as indicated on the Drawings as specified herein. The new seconday service will be 120/208 volt, 3 phase, 4 wire, 60 Hz. C. This Contractor shall coordinate his work fully with the Owner to prevent unscheduled shutdowns of the primary campus distribution system. The Contractor will be allowed a total of two shutdowns, one for each connection to the two primary feeders from which the new service is tapped. Time of shutdown to be as approved by the Owner. 1.08 EXTRA WORK A. The Contractor shall obtain prior written authorization (Change Order) from the Architect for all Contract Extras. The Contractor shall furnish to the Architect an estimate of the cost of such work. 1.09 IDENTIFICATION A. Nameplates shall be provided for all motor starters, disconnect switches, circuit breakers and panelboards . They shall be laminated plastic, black with 1/4" high white engraved letters. 1 . 10 DEFINITIONS A. Approved Equivalent: Materials, equipment or methods deemed satisfactory in writing by the Architect as a substitute for those specified. This approval does not remove the requirements for Shop Drawings. B. Provide shall mean "furnish and install" . ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 6 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 4 . Fire detection and alarm system C. The manufacturer' s name, product designation or catalog number, descriptive literature and data shall be submitted for the following material and equipment. 1 . Raceways 2 . Boxes and fittings 3 . Wires, cables and appurtenances 4 . Lighting fixtures and appurtenances 5 . Wiring devices and appurtenances 6 . Switches 7 . Motor starters 8 . Control devices and stations 9 . Grounding equipment D. Prior to submittal, all shop drawings shall be checked by the Contractor for accuracy and conformance to contract requirements. Shop drawings shall bear the date checked and shall be accompanied by a statement that the shop drawings have been examined by the Contractor for conformity to specifications and Drawings. This statement shall also list all discrepancies with the specifications and Drawings. Shop drawings not so checked and noted will be returned. E. The Architect' s review shall be only for conformance with the design concept of the project and compliance with the specifications and Drawings. The responsibility of, or the necessity of, furnishing materials and workmanship required by the specification and Drawings which may not be indicated on the shop drawings is included under the work of this Section. F. The responsibility for all dimensions to be confirmed and correlated at the job site and for coordination of this work with the work of all ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 5 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects compensation will be allowed for making these changes . F. The locations of equipment, fixtures, outlets, and similar devices shown on the Drawings are approximate only. Exact locations shall be as determined by the Architect during construction. Obtain in the field all information relevant to the placing of electrical work and in case of any interference with other work, proceed as directed by the Architect and furnish all labor and materials necessary to complete the work in an acceptable manner. G. Circuit layouts are not intended to show the number of fittings, or other installation details. Furnish all labor and materials necessary to install and place in satisfactory operation all power, lighting, and other electrical systems shown. Additional circuits shall be installed wherever needed to conform to the specific requirements of the equipment. H. All connections to equipment shall be made as required, and in accordance with the approved shop and setting drawings . I . The work shall include selective removal of the existing electrical service equipment, conduit and wire as specified and as required for the installation of the new work. Electrical selective removal and disposal shall be in accordance with the requirements of SECTION 16450. J. Cutting and patching for electrical work is included under SECTION 2A - CUTTING AND PATCHING. 1 .06 SHOP DRAWINGS A. As specified under GENERAL CONDITIONS AND GENERAL REQUIREMENTS, shop drawings shall be submitted for all materials, equipment and apparatus. B. Complete shop drawings shall be submitted for the following equipment: 1 . Service equipment 2 . Panelboards 3 . Pad-mounted transformer ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 4 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects 1 .04 CODES, STANDARDS, INSPECTIONS AND FEES A. All material and installations shall be in accordance with the latest edition of the Massachusetts Electrical Code and all applicable local codes and ordinances . B. Obtain all necessary permits and pay all fees for permits and inspections. C. All applicable standards of the following organizations form a part of this specification. Where the requirements of these specifications exceed the requirements of the standards, the specifications shall govern: 1 . National Fire Protection Association (NFPA) . 2 . Institute of Electrical & Electronic Engineers (IEEE) . 3 . National Electrical Manufacturers ' Association (NEMA) . 4 . Underwriters ' Laboratories, Inc. (UL) . 1.05 INTERPRETATION OF DRAWINGS A. The Drawings are not intended to show exact locations of conduit runs. B. Each three phase circuit shall be run in a separate conduit unless otherwise shown on the Drawings. C. Where circuits are shown as "home-runs" all necessary fittings and boxes shall be provided for a complete raceway installation. D. Verify with the Architect the exact locations and mounting heights of lighting fixtures, switches and receptacles prior to installation. E. Any work installed contrary to or without review by the Architect shall be subject to change as directed by the Architect, and no extra ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 3 SMITH COLLEGE, OFFICE OF ADMISSION 03/01/93 David P. Handlin and Associates, Architects F. The Contractor' s attention is directed to the GENERAL CONDITIONS and the GENERAL REQUIREMENTS. 1.02 RELATED WORK SPECIFIED ELSEWHERE A. Section 2A - Cutting and Patching B. TEMPORARY FACILITIES AND CONTROLS 1 . Temporary electricity C. DIVISION 2 - SITE WORK 1 . Excavation and backfill D. DIVISION 9 - FINISHES 1 . Final painting of all electrical equipment E. DIVISION 15 - MECHANICAL 1 . All temperature and ventilation control wiring not indicated on the electrical Drawings, including raceways, is included under SECTION 15600 . 1 .03 DELIVERY STORAGE AND HANDLING A. Refer to SECTION 0100 - Delivery, Storage, Handling and Installation Conditions. B. Deliver materials and equipment to the job site in sealed, undamaged cartons, containers, crates, or bundles . C. Each carton, container or crate shall be identified with manufacturer' s name and model number. D. Electrical equipment shall at all times during construction be adequately protected against mechanical injury or damage by water. Electrical equipment shall be stored in dry permanent shelters. If any apparatus has been damaged, such damage shall be repaired at no additional cost. If any apparatus has been subject to possible injury by water, it shall be thoroughly dried out and put through such special tests as directed by the Architect, or shall be replaced at no additional cost to the Owner. ELECTRICAL WORK - GENERAL PROVISIONS 16100 - 2 SMITH COLLEGE, OFFICE OF (ADMISSION 03/01/93 David, P. Handlin and Associates, Architects t; 1 St •n�'J A.� L:1� ,.. .�tr f w.- .ti .,i.�'r�...�ax . u � __ �-.0 =.°? i ��� ..i:�J. �i.k t David P. Handlin and Associates, Architects Memorandum: Subject: Smith College Office of Admissions,Electrical Drawings and Specifications To: Contractors From: David P.Handlin Date: February 22, 1993 The Electrical Drawings and Specifications will be issued as an addendum on March 1, 1993. David P.Handlin DPH:lc ?/22/93 104 Mount Auburn Street, Cambridge, Massachusetts 02138 617 • 576 • 1496/ 576 • 1346 FAX 1 l 4 low Wimp dw olp r 0 0 �- .r > 0 � o I r' ! 6 TOTRL P.01 MAR-05-1593 15:27 FROM D.P.H. & Associates TO 14135840011 David P. Handlin and Associates, Architects Smith College, Office of Admission: Addendum #4l ( March 5, 1 ) By FAX (as per addendum#4 Nov. 12, 1992) 15300,1 5400: 1.) Water supply lines: Domestic water supply and sprinkler water supply to be tapped by G.C. } into 16"water main on College Lane 67'(V.I.F.) from the foundation wall penetration(see enclosed sketch). There is no conflict with existing steam tunnel. Water main location to be verified and trenching permit obtained from the Town of Northampton. 2.) Rainwater downspouts and foundation drains Downspout on P.1 at northeast Comer to travel counter clockwise around building and tie in with other downspouts to existing storm drain line west of the building. Downspout at southeast corner to travel clockwise to same. The portion of the site on the east side of the foundation is to remain unexcavated. G.C. to provide manhole at junct'on. 3.) Manhole shown on P.1 and manhole for drains in item 2.)to be 4"0"dia. min. 5000 psi precast concrete. Watertight between sections with flexible boots to all pipes. 24"dia.min. cast iron solid cover to match existing manhole covers on Smith grounds. t x i 1 r04 Mount Auburn Street, Cambridge, 'Massachusetts c2738 617 • 576 • 1+96/ 576 . 1,146 FAX 1 Q i T'f� lob Q� Z � 2' 3 Z :rA � o t J / ,b'�' I i : —� 1 s J David P. Handlin and Associates, Architects Smith College, Office of Admission: Addendum #4 ( March 5, 1992) By FAX (as per addendum#4 Nov. 12, 1992) 15300,15400: 1.) Water supply lines: Domestic water supply and sprinkler water supply to be tapped by G.C. into 16"water main on College Lane 67'(V.I.F.) from the foundation wall penetration(see enclosed sketch). There is no conflict with existing steam tunnel. Water main location to be verified and trenching permit obtained from the Town of Northampton. 2.) Rainwater downspouts and foundation drains Downspout on P-1 at northeast corner to travel counter clockwise around building and tie in with other downspouts to existing storm drain line west of the building. Downspout at southeast corner to travel clockwise to same. The portion of the site on the east side of the foundation is to remain unexcavated. G.C. to provide manhole at junction. 3.) Manhole shown on P-1 and manhole for drains in item 2.)to be 4"0"dia. min. 5000 psi precast concrete. Watertight between sections with flexible boots to all pipes. 24"dia. min. cast iron solid cover to match existing manhole covers on Smith grounds. 104 Mount Auburn Street, Cambridge, Massachusetts 02138 617 - 576 - 1496/ 576 - 1346 FAX David P. Handlin and Associates, Architects Smith College, Office of Admission Addendum #3 (March 5, 1993) By Fax The following are three points of clarification about electrical work: 1). The purpose of"Alternate#2"is simply to break out for Smith College's accounting purposes the infrastructure cost, the cost of bringing the service to the building, from the electrical work within the building. 2). The panel boards should be General Electric"or equal." 3). On panel board MDP schedule on drawing E8, revise the trip setting for circuit#3 and#4 from 225 to 100. DPH:lc 3/5/ 1993 �V T r- 104 Mount Auburn Street, Cambridge, Massachusetts 02138 617 • S76 • 1496/ 576 • 1346 FAX David P. Handlin and Associates, Architects Smith College, Office of Admission: Adedendum #2 (March 1, 1993) By FAX 16100-- Electrical: Two sets of drawings; one set of specifications. Note: Please note in particular "Alternate No. 2", on p. 7 of the electrical specification. 07180--For interior dampproofing,use Acryl 60. Thoro Systems Products, or other products as specified in 2.2. ----- DPH:lc 3/1/93 104 Mount Auburn Street, Cambridge, Massachusetts 02138 617 . 576 • i496/ 576 • 1346 FAX Adderi6w"I By FA 1 • am SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects .., G. Submit certified test reports signed by Test and Balance Supervisor who performed TAB work. wo H. Include identification and types of instruments used, and their most recent calibration date with submission of final test report. 'w I. Use standardized format for recording and presenting data. J. Include in the TAB report for each item balanced the unit number or tag, location, size, manufacturer and model. Record applicable design and actual values for specific equipment as listed below. AIR INLETS AND OUTLETS Air flow rate. FANS Static pressure. Fan RPM. Motor HP, voltage, phase. Amperage for each phase leg. FAN COIL UNITS (data for each coil) Water flow rate. *� Air temperature rise/drop. Ent. & lvg. water temperature. WATER PUMPS Water flow rate. Suction & discharge pressures. Motor HP, volts, phase. Amperage for each phase leg. HEAT EXCHANGER .. Water flow rate. Water pressure drop. Ent. & lvg. water temperature. ++ END OF SECTION 15600 ++ HVAC 15600-44 „� SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects " 3. 18 INSTALLATION OF STEAM TO WATER HEAT EXCHANGERS A. Install heat exchangers in accordance with manufacturers written installation instructions. 4" B. Install heat exchanger on fabricated support stand as indicated on the drawings. C. Provide vacuum breaker on shell. D. Provide relief valve on water side sized for full capacity at rated pressure. E. Provide minimum 12" length from shell to trap inlet. F. Position unions or flanges to allow for tube removal. 3. 19 TESTING, ADJUSTING & BALANCING A. Provide the services of an independent certified Testing and Balancing Contractor to perform the work of this section. B. Do not proceed with testing, adjusting, and balancing work until work has been completed and is operable. Ensure that there is no latent residual work still to be completed. C. Examine installed work and conditions under which testing is to be done to ensure that work has been completed, cleaned and is operable. Do not proceed with TAB work until unsatisfactory conditions have been corrected in manner acceptable to Tester. D. Test, adjust and balance environmental systems and components, to within 5% of design values, as indicated, in accordance with procedures outlined in applicable standards. E. Mark equipment settings, including damper control positions, valve indicators, and similar controls and devices to show final settings at completion of TAB work. Provide markings with paint or other suitable permanent identification materials. F. Prepare independent test report of test results, including instrumentation calibration reports, in format recommended by applicable standards. HVAC 15600-43 .w SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. EQUIPMENT CONNECTIONS: Connect steam and condensate equipment to piping system in accordance to equipment manufacturer's instructions. 3. 15 INSTALLATION OF A/C CONDENSATE PIPING A. Install piping with 1/4" per foot downward slope in direction of flow. B. Connect piping to all equipment and terminals requiring A/C condensate removal. C. Provide elbow formed water seal traps at all connections to fan driven units. D. Provide sufficient clean-out to provide for full cleaning of piping system. 3. 16 INSTALLATION OF DUPLEX CONDENSATE PUMPS A. Install condensate return units in accordance with manufacturers written installation instructions. B. Install base mounted pumps on minimum 4" high concrete housekeeping pad. C. Support in-line pumps from piping system. D. Install accessories and devices furnished by manufacturer _ but not factory mounted. E. Provide a check valve, metal flex pipe connector, union and isolation valve on each pump discharge. F. Provide electrical installer with copies of wiring diagrams and electrical installation data. •• G. Coordinate housekeeping pad size and location with contractor responsible for it's installation. 3. 17 INSTALLATION OF IN-LINE EXHAUSTERS A. Install equipment in accordance with manufacturers installation instructions. B. Furnish roof jacks and roof discharges to installer or general contractor for installation. Instruct installer in any special requirements for mounting curbs to structure. Provide locations of penetrations to installer. C. Furnish remote fan speed switches where specified to electrical installer. .m HVAC 15600-42 am on SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 'we 3. Provide drain valves on each mechanical equipment item located to completely drain equipment; at base of each isolated riser and elsewhere as indicated or required to completely drain hydronic piping system. ' C. EQUIPMENT CONNECTIONS: Connect hydronic equipment to the hydronic piping system in accordance to equipment manufacturer's instructions. 3. 14 INSTALLATION OF STEAM AND CONDENSATE SYSTEMS 4ft A. GENERAL: Unless otherwise indicated install steam and condensate piping as follows: 1. Install steam and condensate piping with 1/4" per 10 on foot downward slope in the direction of flow. 2. Install branch piping and riser offsets with 1/8" per Am foot downward slope in the direction of condensate flow. 3. Install branch and run-outs at top of main, either in ' " the vertical or at 45 deg. from the vertical and perpendicular to main. w 4. Install run-out piping to terminals with 1/4" per foot downward slope in direction of condensate return. 5. Install eccentric reducers where pipe is reduced in size, with bottoms of both pipes and reducer flush. Locate reducers 18" min. distance from branch connection. B. VALVES: Unless otherwise indicated install valves as listed below and elsewhere as indicated. 1. Provide isolation valves at each steam terminal each �. piece of mechanical equipment and elsewhere as indicated. 2. Provide drain valves on each mechanical equipment item located to completely drain equipment; at base of each isolated riser and elsewhere as indicated or required to completely drain steam and condensate piping system. HVAC 15600-41 no SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects WM 3. 12 INSTALLATION OF DUCTWORK ACCESSORIES 4W A. Install accessories in accordance with manufacturers instructions and as indicated. B. Install fire dampers with required perimeter mounting '" angles, sleeves, and breakaway duct connections. C. Provide flexible connections immediately adjacent to .� equipment in ducts associated with fans and motorized equipment. Cover connections to medium and high pressure fans with leaded vinyl sheet, held in place with metal straps. D. Provide duct access doors for inspection and cleaning before and after filters, fans, automatic dampers, fire and or smoke dampers and elsewhere as indicated. Provide minimum 8 x 8 inch size for hand access, 18 x 18 inch size for shoulder access, and as indicated. 3. 13 INSTALLATION OF HYDRONIC PIPING SYSTEMS A. GENERAL: Unless otherwise indicated install hydronic piping as follows: 1. Install eccentric reducers where pipe is reduced in size in direction of flow, with tops of both pipes and reducer flush. 2. Install piping level with no pitch. 3. Connect upfeed branches or run-outs at top of mains, either in the vertical or 45 deg. from the vertical. 4 . Connect downfeed branches or run-outs at bottom of mains, either at bottom vertical or 45 deg. from downward vertical. B. VALVES: Unless otherwise indicated install valves as listed below and elsewhere as indicated. 1. Provide isolation valves at each hydronic terminal and each mechanical equipment item and elsewhere as �* indicated. 2 . Provide balance valves at each hydronic terminal and each mechanical equipment item and elsewhere as indicated. HVAC 15600-40 ON SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 7. Locate ducts with sufficient space around equipment to allow normal operating and maintenance activities. 8. Coordinate duct installation with installation of accessories, dampers, coils frames, equipment, controls and other associated work of the ductwork system. 9. During construction provide temporary closures of metal or taped polyethylene on open ductwork to prevent construction dust from entering ductwork. 10. After each duct system is completed, test for duct leakage in accordance with appropriate SMACNA standard. Repair leaks and retest until system passes +� test. B. LOW PRESSURE DUCTWORK 1. Assemble and install to achieve maximum leakage rate of 5 percent. 2. Seal ductwork, after installation, to seal class recommended, and method prescribed in SMACNA "Low Pressure Duct Standards" . 3. Support ductwork in manner complying with SMACNA "Low Pressure Duct Standards" , hanger and support section. 4 . Connect diffusers or troffers (where connection is concealed) to ducts with 5 foot maximum length of flexible or insulated flexible duct as required by the application. Hold in place with strap or clamp. C. CLEANING 1. Clean ductwork internally, unit by unit as it is installed, of dust and debris. Clean external surfaces of foreign substances. D. DUCTWORK APPLICATION SCHEDULE ? SYSTEM MATERIAL LOW PRESS. SUPP. STEEL RETURN and RELIEF STEEL GENERAL EXHAUST STEEL w HVAC 15600-39 MW SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects ow 6. Do not insulate over nameplates or ASME stamps. Bevel and seal insulation around such. .w 7. When equipment with insulation requires periodical opening for maintenance, repair, or cleaning, install insulation in such a manner that it can be easily """'k removed and replaced without damage. B. APPLICATION ow 1. Insulate heat exchangers with 2" thick Rigid Fiberglass equipment insulation. 2. Insulate chilled water pump bodies with 1" thick Rubber Sheet equipment insulation. ow 3. Insulate air separators with 2" thick Rigid Fiberglass equipment insulation. 4. Insulate steel steam condensate receiver tanks with 2" thick Rigid Fiberglass equipment insulation. 3. 11 INSTALLATION OF DUCTWORK A. GENERAL 1. Align ductwork accurately at connections, within 1/8 inch misalignment tolerance and internal surfaces smooth. 2 . Support ducts rigidly with suitable ties, braces, hangers and anchors of type which will hold ducts true to shape and to prevent buckling. 3. Limit clearance to 1/2 inch where furring is shown for enclosure or concealment of ducts, but allow for insulation thickness, if any. 4 . Locate insulated ductwork for 1 inch clearance outside of insulation. 5. Coordinate layout with suspended ceiling and lighting layouts and similar finish work. 6. Where ducts pass thru interior partitions and exterior walls, conceal space between construction opening and duct or duct plus insulation with sheet metal flanges of same gage as duct. Overlap opening on 4 sides by at least 1-1/2 inch. HVAC 15600-38 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2. RIGID FIBERGLASS: Secure insulation to ductwork using mechanical fasteners with pin spacing no greater than 12 inch on center. Seal vapor barrier penetrations by mechanical fasteners with vapor barrier tape. Tape joints and edges with 3 inch pressure sensitive vapor barrier tape to match jacket. Stop and point insulation around access doors and damper operators to allow operation without disturbing wrapping. C. APPLICATION 1. Insulate all exposed hot and/or cold supply air ducts with 1 inch thick Rigid Fiberglass ductwork insulation. 2 . Insulate all concealed hot and/or cold supply air ducts with 1-1/2 inch thick Flexible Fiberglass ductwork insulation. 4W 3. Insulate all exposed exhaust air, fresh air intake, and combustion air ductwork within 10 feet of exterior opening with 1 inch thick Rigid Fiberglass ductwork insulation. 4 . Insulate all concealed exhaust air, fresh air intake, ON and combustion air ductwork within 10 feet of exterior opening with 1 inch thick Flexible Fiberglass ductwork insulation. OR 3. 10 INSTALLATION OF EQUIPMENT INSULATION A. GENERAL 1. Install materials in accordance with manufacturer's instructions. 2 . Do not insulate factory insulated equipment. 3. Apply insulation as close as possible to equipment by grooving, scoring, bevelling insulation, if necessary. Secure insulation to equipment with studs, pins, clips, adhesive, wires, or bands. 4 . Fill joints, cracks, seams, and depressions with bedding compound to form smooth surface. On cold equipment, use vapor barrier cement. 5. Cover Rigid Fiberglass and Calcium Silicate insulation with metal mesh finish and finish with heavy coat of insulating cement. HVAC 15600-37 ON SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects No 3.09 INSTALLATION OF DUCTWORK INSULATION .. A. GENERAL 1. Install materials after ductwork has been tested and approved. '" 2 . Install materials in accordance with manufacturer's instructions. 40 3. Clean and dry ductwork prior to insulating. Butt insulation joints firmly together to ensure complete at, and tight fit over surfaces to be covered. 4 . Maintain integrity of vapor barrier and protect it to prevent puncture and other damage. 'm 5. Extend ductwork insulation without interruption through walls, floors and similar ductwork so penetrations, except where otherwise indicated. 6. Omit ductwork insulation from the following: am a. Lined ductwork. b. Ductwork located in return air plenums above *m ceilings. C. Fibrous ductwork. am B. INSTALLATION 1. FLEXIBLE FIBERGLASS: Seal jacket joints with vapor barrier tape to match jacket. Staple seams 6" O.C. with outward cinching staples, then seal with pressure sensitive tape matching jacket. Install an without sag on underside of ductwork. Use adhesive or mechanical fasteners where necessary to prevent sagging. Seal vapor barrier penetrations by .. mechanical fasteners with vapor barrier tape. Stop and point insulation around access doors and damper operators to allow operation without disturbing wrapping. •^ HVAC 15600-36 „ o SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects on 3. Plastic Pipe Markers: Install in accordance with .0 manufacturer's instructions. 4 . Plastic Tape Duct Markers: Install in accordance with manufacturer's instructions. 5. Underground Plastic Pipe Markers: Install 6 to 8 inches below finished grade, directly above buried pipe. 6. EQUIPMENT: Identify air handling units, fans, rooftop units, pumps, heat transfer equipment, tanks, and water treatment devices with plastic nameplates. Small devices such as in-line pumps may be identified with metal tags. .w 7. CONTROLS: Identify control panels and major control components outside panels with plastic nameplates. 8. PIPING: Identify piping, concealed or exposed, with plastic pipe markers. Identify service and flow direction. Install in clear view and align with axis of piping. Locate identification not to exceed 20 feet on straight runs including risers and drops, adjacent to each valve and "T" , at each side of penetration of structure or enclosure, and at each obstruction. 9. DUCTWORK: Identify ductwork with plastic tape duct markers. Identify as to air handling unit number. Locate at air handling unit, at each side of penetration of structure or enclosure, and at each *� obstruction. 10. VALVES: Identify valves, except valves within heating or cooling terminals, with metal tags. 11. VALVE CHART AND SCHEDULE: Provide valve chart and schedule in aluminum frame with clear plastic shield. Install at location as directed. HVAC 15600-35 No SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects no 10. Exterior Applications: Provide indicated jacket with seams located on the bottom of horizontal piping. Insulate fitting, joints, and valves with insulation of like material and thickness as adjoining pipe, and finish with glass mesh reinforced vapor barrier cement. 11. INSULATION OMITTED: Omit insulation on hot piping within radiation enclosures or unit cabinets; on cold ,. piping within unit cabinets providing piping is located over drain pan; on condensate piping between steam trap and union; and on unions, flanges, strainers flexible connections, and expansion joints. B. PIPE INSULATION APPLICATION 1. Insulate the following piping systems with the type and thickness of insulation indicated as follows: F.G.=FIBERGLASS R.T.=RUBBER TUBE C.S.=CALCIUM SILICATE RUNOUTS 1" 1-1/4" 2-1/2" 5" 8" INSUL. up to and to to to and PIPING SYSTEM TYPE 2" less 2" 4" 6" larger -------------------- ----- ------ ------ ----- ----- ------ ------ HOT/CH WATER SUP/RET R.T. 0.5 1.0 1.0 1.0 1.0 1.5 LP STEAM SUPPLY F.G. 1.0 1.0 1.5 1.0 1.0 1.5 MP STEAM SUPPLY F.G. 1.5 1.5 2.0 2.5 3.0 3.0 HP STEAM SUPPLY F.G. 1.5 1.5 2.0 2 .5 3.5 3.5 STEAM CONDENSATE F.G. 1.0 1.0 1.0 1.5 1.5 2.0 MAKEUP WATER F.G. 0.5 0.5 1.0 1.0 1.0 1.0 AIR COND. CONDENSATE R.T. 0.5 0.5 0.5 0.5 0.5 0.5 REFRIGERANT SUCTION R.T. 0.5 0.5 0.75 1.0 1.0 1.0 REFRIGERANT HOT GAS R.T. 0.5 0.5 0.75 1.0 1.0 1.0 3.08 INSTALLATION OF MECHANICAL IDENTIFICATION .. A. PREPARATION 1. Degrease and clean surfaces to receive adhesive for identification materials. B. INSTALLATION 1. Plastic Nameplates: Install with corrosive resistant mechanical fasteners, or adhesive. 2. Metal Tags: Install with corrosive resistant chains. HVAC 15600-34 ago on SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects an 3. Place hanger within 12 inches of each horizontal elbow. 4 . Support vertical piping at every floor. 5. Where several pipes can be installed in parallel and at same elevation, provide trapeze or multiple hangers. 3.07 INSTALLATION OF PIPE INSULATION A. GENERAL 1. Insulate all new and existing steam and condensate piping. 2 . Install materials after piping has been tested and approved. 3. Install materials in accordance with manufacturer's instructions. 4. Continue insulation with vapor barrier through penetrations. 5. On insulated piping systems with vapor barrier, insulate fittings, valves, unions, flanges, strainers, flexible connections and expansion joints. 6. On insulated piping systems without vapor barriers and piping conveying fluids 140 deg. F. or less, do not insulate flanges and unions at equipment, but bevel and seal ends of insulation at such locations. 7. Provide an insert, not less than 6 inches long, of same thickness and contour as adjoining insulation, between support shield and piping, but under the finish jacket, on piping 2 inch diameter and larger, to prevent insulation from sagging at support points. Inserts shall be cork or other heavy density insulating material suitable for the planned temperature range. Factory fabricated inserts may be used. 8. Apply rubber tube sheet insulation to hot/chilled water piping prior to installation of pipe. Pipe insulation to be continuous with being slit for installation on the piping. 9. Neatly finish insulation at supports, protrusions, and interruptions. HVAC 15600-33 ,o SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects go E. PIPE SLEEVES: Install of type indicated where piping passes thru walls, floors, ceilings, and roofs. Install sleeves accurately centered on pipe runs. Size sleeves so that piping and insulation (if any) will have free movement. Install length of sleeve equal to thickness of construction penetrated, and finish flush to surface; except for floor sleeves. Extend floor sleeves 1/4" above level finish floor or as indicated. 1. Install sheet metal sleeves at interior partitions and ceilings other than suspended ceilings. 2. Install steel pipe iron pipe sleeves at exterior penetrations; both above and below grade. 3. Install steel or plastic sleeves except as otherwise indicated. F. SLEEVES SEALS 1. Lead and Oakum: Fill and pack annular space between .� sleeve and pipe with oakum, calk with lead on both sides. 3.06 INSTALLATION OF HANGERS AND SUPPORTS A. INSERTS 1. Provide inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete beams. 2. Where concrete forms finished ceiling, provide inserts to be flush with slab surface. 3. Where inserts are omitted, drill thru from below and provide thru bolts with recessed steel plate and nut flush with slab. B. PIPE HANGERS AND SUPPORTS 1. Support horizontal piping as follows: PIPE SIZE MAX. SPACING ROD DIA. 1/2 to 1-1/4" 6 '-6" 3/8" 1-1/2 to 2" 10'-0" 3/8" 2-1/2 to 3" 10'-0" 1/2" 2. Install hangers to provide minimum 1/2 inch space between finished covering and adjacent work. HVAC 15600-32 00 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 4 7. Drain test water from systems after testing and 40 repair work has been completed. 3.04 INSTALLATION OF VALVES A. Locate valves so as to be accessible and so that separate support can be provided when necessary. B. Install valves with stems pointed up, in vertical position where possible, but in no case with stems pointed downward from horizontal plane unless unavoidable. Install valve drains with hose-end adapter for each valve that must be installed with stem below horizontal plane. C. Where insulation is indicated, install extended stem valves, arranged to receive insulation. D. Install swing check valves in horizontal position with hinge pin horizontally perpendicular to center line of pipe. E. Valve Adjustment: After piping systems have been tested and put into service, but before final testing, adjusting, and balancing, inspect each valve for possible leaks, replace valve if leak persists. F. Cleaning: Clean factory finished surfaces. Repair any marred or scratched surfaces with manufacturer's touch-up ' paint. 3.05 INSTALLATION OF PIPING SPECIALTIES A. PIPE ESCUTCHEONS: Install on each pipe penetration thru floors, walls partitions and ceilings where penetration is exposed to view. B. Y-TYPE STRAINERS: Install full size of pipe line, install pipe nipple and blow-down valve except for strainers 2" and smaller ahead of control valves feeding individual terminals. ► C. DIELECTRIC UNIONS: Install at each piping joint between ferrous and non-ferrous piping. D. MECHANICAL SLEEVE SEALS: Loosely assembly rubber links around pipe with bolts and pressure plates located under each bolt head and nut. Push into sleeve and center. Tighten bolts until links have expanded to form watertight seal. HVAC 15600-31 am SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 00 C. SOLDERED JOINTS: Solder copper tube and fitting joints where indicated, in accordance with recognized industry ." practice. Cut tube ends squarely, ream to full diameter, and clean outside of tube ends and inside of fittings. Apply solder flux to joint areas of both tubes and fittings. Insert tube full depth into fitting, and solder '" in manner which will draw solder full depth and circumference of joint. Wipe excess solder from joint before it hardens. o, D. FLANGED JOINTS: Match flanges within piping system, and at connections with valves and equipment. Clean flange faces and install gaskets. Tighten bolts to provide so uniform compression of gaskets. E. CLEANING, FLUSHING, INSPECTING .w 1. Clean exterior surfaces of installed piping systems of superfluous materials, and prepare for application an of specified coating (if any) . Flush out piping systems with clean water before proceeding with required tests. Inspect each run of each system for completion of joints, supports and accessory items. to F. PIPING TESTS 00 1. Test pressure piping in accordance with ASME B 31. Owner to be present during testing. 2 . Fill system with water. Provide temporary equipment .a for testing, including pump and gages. Test piping systems before insulation is installed and remove control devices before testing. Test each natural section of each piping system independently but do not use piping system valves to isolate sections where test pressure exceeds valve pressure rating. ., 3. Required test period is 2 hours. 4 . Test each piping system at 150% of operating pressure indicated, but not less than 25 psi test pressure. 5. Observe each test section for leakage at end of test period. Test fails if leakage is observed or if pressure drops exceeds 5% of test pressure. 6. Repair piping systems sections that fail required .� test, by disassembly and reinstallation, using new materials to the extent required to overcome leakage. Do not use chemicals, stop-leak compounds, mastics, or other temporary repair methods. HVAC 15600-30 ow SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 40 C. Wherever factory finishes of paint, lacquer, baked enamel, etc. , have been damaged or deteriorated during construction, use factory furnished painting materials and refinish or touch up the damage or deterioration, to the satisfaction of the Architect. Application shall be by skilled workers experienced in painting and finishing. 3.02 INSTALLATION OF EQUIPMENT-GENERAL A. Install all equipment and products furnished and make system connections to such equipment in accordance with the manufacturer's instructions. B. Provide adequate clearances around equipment to permit replacement, normal servicing and maintenance. 3.03 INSTALLATION OF PIPE AND PIPE FITTINGS A. GENERAL 1. Hold piping close to walls, overhead construction, columns and other structural and permanent enclosure elements of building. Limit clearance to 1/2" where furring is shown for enclosure or concealment of piping, but allow for insulation thickness, if any. Where possible, locate insulated piping for 1" clearance outside insulation. 2 . Install each run with minimum joints and couplings, but with adequate and accessible unions for disassembly and maintenance/replacement of valves and equipment. 3. Align piping accurately at connections, within 1/16" misalignment tolerance. B. THREADED JOINTS: Thread pipe in accordance with ANSI B2. 1; cut threads full and clean using sharp dies. Ream threaded ends to remove burrs and restore full inside diameter. Apply pipe joint compound, or pipe joint tape (Teflon) on male threads at each joint and tighten joint to leave not less than 3 threads exposed. HVAC 15600-29 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects G. GRILLE: Provide manufacturers standard face grille with screw attachment to housing. ". H. ACCESSORIES: Provide manufacturers standard accessories as scheduled or otherwise indicated. 2 .23 STEAM TO LIQUID - TUBE IN SHELL EXCHANGERS A. ACCEPTABLE MANUFACTURERS 1. Bell & Gossett. 2 . Taco. 3. Patterson & Kelly. B. TYPE: Shell and tube, U-bend removable tube bundle, steam in shell, water in tubes. .� C. MATERIALS: 1. Shell: Steel. 2 . Tubes: 3/4 O.D. copper. 3. Heads: Cast iron or steel. 4 . Tube sheets: Steel. 5. Baffles, Tie Rods, Spacers: Steel. D. CONSTRUCTION: The heat exchanger shall bear the ASME "U" ■* symbol and shall conform to the latest ASME code for Pressure vessels. 2 .24 AUTOMATIC TEMPERATURE CONTROLS A. Refer to DIVISION 1 - Section 01020 Allowances. .w PART 3 - EXECUTION 3.01 PROTECTION 'o A. Be responsible for the care and protection of all work included in this Section until it has been tested and `w accepted. B. After delivery and before, during and after installation, protect all equipment, materials and systems from injury or damage of all causes, as well as from theft. Such loss or damage shall be made good without expense to the .� Owner. HVAC 15600-28 +.e SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects D. Control Package Components and Characteristics: 1. Factory wired and tested receiver mounted NEMA cabinet. 2 . (2 ) combination magnetic starters (each with overload +*� relays on each leg) with circuit breaker and cover interlock. 3. Electrical alternator. a. Change operating sequence automatically after each cycle. b. Provide simultaneous operation during peak load conditions. C. Operate second pump automatically upon failure of active pump. 4 . "Auto-Off" selector switch for each pump. • 5. Momentary contact test switches for each pump. 6. Fusible transformer when motor voltage exceeds 130 VAC. 7. Each control circuit shall be independent of the other. 2 .22 INLINE EXHAUSTERS A. ACCEPTABLE MANUFACTURERS 1. Loren Cook Co. 2 . Jenn Industries Inc. 3. Penn Ventilator Co. , Inc. 4. Greenheck Fan Corp. B. HOUSING: Galvanized steel with acoustical insulation. Housing shall be have duct inlet and outlet connections, *■ removable access panel and an integral backdraft damper. C. FAN WHEEL: Centrifugal, mounted on motor shaft, removable 4W as unit for servicing. D. MOTORS: Permanent split capacitor,permanently lubricated, resilient mounted, with grounded cord and plug. E. ELECTRICAL: Provide junction box for electrical connection on housing, and receptacle for motor plug in. 1. Provide remote solid state variable fan speed control switch. HVAC NO 15600-27 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects R. ACCESSORIES: 1. Provide horizontal concealed units with intake plenum �. and filter frame. 2 . Provide floor mounted units with unit mounted fan speed selector switch. 3 Provide floor mounted units with unit mounted thermostat. 4. Provide ceiling or concealed models with remote mounting fan speed selector switch (for multi-speed motors) . L. ACCEPTABLE MANUFACTURERS: 1. International Environmental Corp. 2. McQuay, Inc. 3. York Division; Borg-Warner Corp. 4. The Trane Co. 2.21 DUPLEX CONDENSATE PUMP UNITS - CAST IRON A. Subject to specific project requirements, the following manufacturers are acceptable: 1. Weil B. Provide duplex condensate return units with the following characteristics or accessories: 1. Receiver: Close grained cast iron, size per drawings. 2. Float switches: (2) externally adjustable, 2 pole. 3. Pressure gauges: (1) for each pump. 4. Water level gauge. 5. Cast iron inlet strainer with bronze screen. 6. Pumps. 7. Operating Controls. C. Pump and Motor Characteristics: 1. Centrifugal, flange mounted to receiver. 2 . Vertical close coupled. 3. Bronze fitted with stainless steel shaft, enclosed bronze impeller, removable bronze case ring. ., 4 . Mechanical seals. 5. Vertical drip-proof motor, HP and electrical characteristics per drawings. HVAC 15600-26 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects B. CLASSES: 1. Class I Fan Coil Units: Blow thru, standard chassis depth less than 12 inch, ARI & UL listed. 2. Class II Fan Coil Units: Blow thru, chassis depth greater than 16 inches, specifically designed for ducted applications, UL listed. 3. Class III Fan Coil Units: Draw thru belt driven horizontal cabinet specifically designed for ducted applications. C. CHASSIS: Galvanized steel. D. COILS: Evenly spaced aluminum fins mechanically bonded to copper tubes, minimum 250 psig working pressure, 300 psig test pressure. Provide each coil with a manual air vent. E. FANS: Forward curve, double inlet, centrifugal; statically and dynamically balanced. Belt driven units shall be equipped with adjustable drives. ' F. INSULATION: One inch thick coated glass fiber meeting NFPA-90A. +� G. CABINETS: Minimum 18 gauge removable steel panels. Provide insulation over entire coil section. Factory standard bonderized finish unless otherwise indicated. H. DRAIN PANS: Galvanized steel insulated with polystyrene or polyurethane insulation. I. Motors: 1. Single Phase motors shall be provided with integral thermal overload protection and shall be of the multispeed permanent split capacitor type. 2 . Belt drive motors shall be 1,750 RPM bolted to adjustable base to permit belt adjustment. J. FILTERS: Provide one inch thick fiberglass filters of disposable type. HVAC 15600-25 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2 . ACCEPTABLE MANUFACTURERS a. Farris Co. b. Spirax Sarco. C. Watts Regulator Co. 2 . 18 A/C CONDENSATE PIPING A. PIPE AND FITTINGS 1. All Sizes: Copper tube, Type L, hard drawn temper; wrought copper fitting; tin-lead solder (50/50) joints. 2 . 19 AIR OUTLET AND INLETS A. GENERAL 1. Provide manufacturers standard air outlets and inlets .. of type, size, materials and with accessories and options indicated. B. ACCEPTABLE MANUFACTURERS 1. Krueger Mfg. Co. 2. Titus Products Div. ; Philips Industries, Inc. *� 3. Tuttle & Bailey; Div. of Interpace Corp. C. REGISTERS AND GRILLES 1. Registers: Rectangular; streamlined blades; fabricated of materials and with finish indicated; opposed blade damper; mounting frame, face type and with accessories indicated. 2 . Grilles: Rectangular; streamlined blades; fabricated of materials and with finish indicated; mounting frame, face type and with accessories indicated. ow 2 .20 FAN COIL UNITS A GENERAL: Provide fan coil units of the class, type, "r size, capacities, having accessories and in the locations indicated. 1. Include in basic unit chassis, coils, fanboard, fan, drain pan assembly, housing, motor, filter and insulation. HVAC 15600-24 MW SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects w C. FLOAT AND THERMOSTATIC TRAPS: Cast iron or semi-steel body; diaphragm or bellows type thermostatic element with stainless steel valve cone and valve seat; stainless steel or copper float, with positive snap-action valve mechanism, stainless steel valve and renewable seat. 1. ACCEPTABLE MANUFACTURERS a. Armstrong Machine Works. b. Barnes & Jones, Inc. c. Spirax Sarco. D. INVERTED BUCKET TRAPS: Cast iron or semi-steel body and cover; 250 psi; brass or stainless steel bucket; stainless steel lever mechanism; stainless steel " removable seats; integral strainer and bimetal air vent. 1. ACCEPTABLE MANUFACTURERS a. Armstrong Machine Works. b. Barnes & Jones, Inc. c. Spirax Sarco. E. STEAM VENTS: Automatic; thermostatic balanced pressure type; brass or semi-steel bodies; renewable stainless steel head and seat; phosphor bronze thermostatic bellows, liquid filled. F. PRESSURE REDUCING VALVES: Pilot actuated, diaphragm type; cast semi-steel bodies with stainless steel trim; replaceable valve head and seat; main head stem guide fitted with flushing and pressure arresting device. wr 1. ACCEPTABLE MANUFACTURERS a. Spence Engineering co. , Inc. G. STEAM SAFETY VALVES: ASME Standard; Bronze body; forged copper alloy disc and nozzle; lap seats to optical flatness; Set valve to relieve 10 psi above operating pressure. 1. Provide drip pan elbows on steam safety valves; cast iron construction with bottom drain and pan drain connections. HVAC 15600-23 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects H. VALVES: Unless otherwise indicated provide valves as listed below. Refer to "VALVES" paragraph for valve type specifications. 1. LOW PRESSURE SERVICE VALVES Gate Valves (2" & Less) : Type GV3. Globe Valves (2" & Less) : Type GLV2. , Ball Valves (2" & Less) : Type BLV2. Check Valves (2" & Less) : Type SCV2. Drain Valves: Type DV1. 2 . MEDIUM PRESSURE SERVICE VALVES Gate Valves (2" & Less) : Type GV3. Globe Valves (2" & Less) : Type GLV2. Check Valves (2" & Less) : Type SCV2. Drain Valves: Type DV1. 3. HIGH PRESSURE SERVICE VALVES Gate Valves (2" & Less) : Type GV6. �Globe Valves (2" & Less) : Type GLVS. Check Valves (2" & Less) : Type SCV2. Drain Valves: Type DV1. 2 . 17 STEAM AND CONDENSATE SPECIALTIES A. GENERAL: Provide steam and condensate specialties of design pressures equal or greater than that of the piping " system to which they are connected. B. THERMOSTATIC TRAPS: Brass body; straight or angle pattern �- as required; screw-in top; union joint; diaphragm or bellows type thermostatic element with stainless steel valve cone; renewable stainless steel seat. ,W 1. ACCEPTABLE MANUFACTURERS a. Armstrong Machine Works. 4W b. Barnes & Jones, Inc. C. Spirax Sarco. ow HVAC 15600-22 «w SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 3. ACCEPTABLE MANUFACTURERS a. Watts Regulator Co. F. SHOT FEEDERS 1. 5 Gallon capacity or as otherwise indicated; cast iron or steel construction; 125 psi; funnel valve on top for loading; drain valve in bottom; recirculating valves on side. 2 . 16 STEAM AND CONDENSATE PIPING SYSTEMS A. DEFINITIONS 1. LOW PRESSURE: 0 to 15 psig. 2 . MEDIUM PRESSURE: Greater than 15; less than 100 psig. 3. HIGH PRESSURE: 100 psig and above. B. LP STEAM PIPE AND FITTINGS 4er 1. Size 2" and Less: SCH. 40 black steel pipe; 125 psi cast iron threaded fittings. C. LP CONDENSATE PIPE AND FITTINGS 1. Size 2" and Less: SCH. 80 black steel pipe; 125 psi cast iron threaded fittings. D. MP STEAM PIPE AND FITTINGS 1. Size 2" and Less: SCH. 80 black steel pipe; 125 psi cast iron threaded fittings. E. MP CONDENSATE PIPE AND FITTINGS 1. Size 2" and Less: SCH. 80 black steel pipe; 125 psi cast iron threaded fittings. F. HP STEAM PIPE AND FITTINGS 1. Size 2" and Less: SCH. 80 black steel pipe; 250 psi cast iron threaded fittings. G. HP CONDENSATE AND FITTINGS 1. Size 2" and Less: SCH. 80 black steel pipe; 250 psi cast iron threaded fittings. HVAC 15600-21 No SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects ow 2 . ACCEPTABLE MANUFACTURERS ow a. Tour-Anderson B. AIR VENTS .o 1 . Manual: Screwdriver or thumbscrew operated, 1/8 inch NPS connection. .,. 2 . ACCEPTABLE MANUFACTURERS a. Armstrong Machine Works. ,M b. B&G ITT; Fluid Handling Div. C. Spirax Sarco Co. d. Watts Regulator Co. no C. AIR SEPARATORS 1. Inline Type: 125 psi; cast iron for sizes 1-1/2 inch ow and smaller, steel for sizes 2 inch and larger; ASME Boiler and Pressure Vessel Code with "U" symbol. 2 . ACCEPTABLE MANUFACTURERS a. Spirotherm D. DIAPHRAGM-TYPE COMPRESSION TANKS 1. Steel construction; 125 psi; ASME Boiler and Pressure Vessel Code, stamped with "U" symbol; flexible diaphragm sealed into tank to permanently air from water; pressure gage and air charging fitting; drain fitting. 2 . ACCEPTABLE MANUFACTURERS a. Amtrol, Inc. b. Armstrong Pump, Inc. 3. Taco E. WATER RELIEF VALVES 1. ASME rated, direct spring loaded type, lever operated, nonadjustable factory set discharge pressure. 2. Select relief setting not to exceed 6 psig above maximum allowable working pressure for pressures up to and including 60 psig. HVAC 15600-20 w SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 4W 2 . Provide flush frames for uninsulated ductwork, 40 extended frames for insulated ductwork. 3. Provide one side hinged, other side with one latch type handle for doors 12" high and smaller, 2 handle " ` type latches for larger doors. 2 . 14 HYDRONIC PIPING SYSTEMS A. PIPE AND FITTINGS 1. Pipe Size 3" and Smaller: Copper tube, Type L, hard drawn temper; wrought copper fittings; tin-antimony solder (95/5) joints. 2. Pipe Run Within Concrete Construction: Copper tube; Type K, soft annealed temper; no joints or fittings allowed; sleeve tube with continuous length of 3/8" minimum thickness of rubber pipe insulation. B. VALVES: Unless otherwise indicated provide valves as listed below. Refer to "VALVES" and "HYDRONIC SPECIALTIES" paragraphs for valve type specifications. 1. BALL VALVES: 2" and Less; Type BLV1. 2. SWING CHECK VALVES 2" and Less; Type SCV1. 2-1/2" and Larger; SCV3. 3. DRAIN VALVES: Type DV1. 4. PLUG VALVES: Type PV1. 2 . 15 HYDRONIC SPECIALTIES A. BALANCE VALVES (CIRCUIT SETTER) 1. Threaded or Soldered Ends (as required) 2" and Smaller: Class 125, bronze body, globe type with memory stop, straight or angle pattern. HVAC 15600-19 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 6. Provide locking, indicating quadrant regulators on single and multi-blade dampers. 7 . On insulated ducts mount quadrant regulators on stand off mounting bracket, bases or adapters. B. TURNING VANES 1. Fabricated Type: Construct in accordance with SMACNA .• Duct Construction Standards. 2. Manufactured Type: 1-1/2" wide curved blades set at 3/4" O.C. , supported with bars perpendicular to blades set at 2" O.C. 3. Acoustical Type: Airfoil shaped aluminum extrusions with perforated faces and fiberglass fill. C. FIRE DAMPERS 1. Fabricate in accordance with NFPA 90A and UL 555; provide UL label for 1-1/2 hour rating unless otherwise indicated. 2 . Curtain type fire dampers; galvanized steel with interlocking blades; stainless steel closure spring and latches for horizontal installations. Blades out of air stream for medium and high pressure ducts. 3. Fusible links, UL 33, shall separate at 160 deg. F. D. FLEXIBLE DUCT CONNECTORS 1. Fabricate in accordance with SMACNA Duct Construction Standards. 2. UL listed fire retardant neoprene coated woven glass fiber fabric to NFPA 90A, minimum density 20 oz per sq yd, approximately 6 inches wide, crimped into metal edging strip. 3. Leaded vinyl sheet, minimum 0.55 inch thick, 0.87 lbs per sq ft, 10 db attenuation in 10 to 10,000 Hz range. E. DUCT ACCESS DOORS 1. Fabricate in accordance with SMACNA Duct Construction Standards. HVAC 15600-18 , , go SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. LOW PRESSURE DUCTWORK 1. Fabricate in accordance with SMACNA Low Pressure Duct Construction Standards. Provide duct gages, reinforcing, and sealing for applicable operating pressures. 2 . Construct T's, bends, and elbows with radius of not a.. less than 1-1/2 times width of duct on centerline. Where rectangular elbows are used, provide turning vanes. Where acoustical lining is indicated, provide �. turning vanes of perforated metal with glass fiber insulation. 3. Increase duct sizes gradually, not exceeding 15 deg. divergence wherever possible. Divergence upstream of equipment shall not exceed 30 deg. ; convergence downstream shall not exceed 45 deg. 4 . Connect fabric flexible duct to metal duct with draw bands. Connect metal flexible duct to rigid flexible duct with adhesives plus sheet metal screws. 2 . 13 DUCTWORK ACCESSORIES A. VOLUME DAMPERS 1. Fabricate in accordance with SMACNA Duct Construction Standards. 2. Fabricate splitter dampers of double thickness sheet metal to streamlined shape. Secure blades with continuous hinge or rod. Operate with min. 1/4 inch diameter rod in self aligning, universal joint action flanged bushing with set screw. 3. Fabricate single blade dampers for duct sizes to 12" x 30" . 4 . Fabricate opposed blade dampers with maximum blade sizes 12" x 72" . Assemble center and edge crimped blades in prime coated or galvanized frame with suitable hardware. 5. Except in round ductwork 12 inches and smaller, provide end bearings. On multiple blade dampers, provide oil-impregnated nylon or sintered bronze bearings. HVAC 15600-17 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 3. Connector: Brass with 1/4 inch male NPT. Provide protective siphon when used for steam service. 4 . Scale: White coated aluminum; permanently etched markings. 5. Range: a. Vacuum: 30" Hg - 15 psi. ,. b. Water: 0 - 100 psi. C. Steam: 0 - 100 psi. �. 6. Provide cocks between gages and piping; 1/4 inch female NPT; "T" handle brass plug. �. 2 . 12 DUCTWORK A. PRESSURE CLASSIFICATION CLASS S.P. ("WG) TYPE VEL. (FPM) HIGH 10 POS 2000 UP MINOR MEDIUM 6 POS 2000 UP MEDIUM 4 POS 2000 UP MEDIUM 3 POS/NEG 4000 DN LOW 2 POS/NEG 2500 DN LOW 1 POS/NEG 2500 DN LOW 1/2 POS/NEG 2500 DN B. MATERIALS 1. STEEL DUCTS: ASTM A525 galvanized steel sheet, lock forming quality, having zinc coating of 1.25 oz per sq ft for each side in conformance with ASTM A90. 2 . DUCT SEALANT: Non-hardening, non-migrating mastic or liquid elastic sealant as compounded and recommended by duct manufacturer specifically for sealing joints in ductwork. " 3. DUCTWORK SUPPORT MATERIALS: Hot dipped galvanized steel fasteners, anchors, rods, straps, trim and w angle support for ductwork. HVAC 15600-16 ew SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects B. MODEL NUMBERS: Model numbers indicated are based on Mason Industries (MD-###) and are meant only to indicate type and quality. C. HANGERS aw 1. Type H2 : Steel housing with neoprene in shear isolation element; double deflection. (MI-HD) . D. PADS 1. Type P1: Neoprene waffle pads, 30 durometer, minimum 1/2 inch thick, maximum loading 40 psi. (MI-WMW) . 2 . 11 THERMOMETERS AND GAGES A. GLASS THERMOMETERS 1. Case: Die cast aluminum, 9 inch long. 2. Adjustable joint; 180 deg. vertical; 360 deg. horizontal; locking device. 3. Mercury filled; 1% scale range accuracy, shock mounted. 4 . Scale: Satin faced; non-reflective; permanently etched markings. 5. Stem: Copper plated steel, or brass, for separable socket; length to suit installation. 6. Range: a. Hot Water: 30-240 deg. with 2 deg. F. divisions. b. Chilled Water: 30-180 deg. with 2 deg. F. divisions. 7. Provide thermometer wells constructed of brass or stainless steel, pressure rated to match piping system. Provide 2 inch extension for insulated *'! piping. B. PRESSURE GAGES 1. General use; 1% accuracy; phospher bronze bourdon type, bottom connection. 2 . Case: Steel; glass lens; 4-1/2 inch diameter. HVAC ,�, 15600-15 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. ACCESSORIES 1. Provide staples, bands, wires, tape, anchors, corner angles and similar accessories as recommended by insulation manufacturer for applications indicated. 2 . Provide cements, adhesives, coatings, sealers, protective finishes, and similar compounds as recommended by insulation manufacturer for �. applications indicated. 2 .09 EQUIPMENT INSULATION A. ACCEPTABLE MANUFACTURERS 1. CertainTeed Corp. ow 2. Knauf Fiber Glass 3. Owens Corning Fiberglas Corp. No B. EQUIPMENT INSULATION 1. RIGID FIBERGLASS: ANSI/ASTM C612, Class 1; 'k' value of 0.24 at 75 deg. F. mean temperature; 6.0 pcf minimum density; foil scrim kraft facing. 2 . RUBBER SHEET: Flexible unicellular equipment insulation; ASTM C534, TYPE II. C. ACCESSORIES 1. Provide staples, bands, wires, tape, anchors, corner angles and similar accessories as recommended by insulation manufacturer for applications indicated. 2 . Provide cements, adhesives, coatings, sealers, protective finishes, and similar compounds as recommended by insulation manufacturer for applications indicated. 3. Jacketing Material (Fiberglass & Calcium Silicate) : A Presized glass cloth jacketing material, not less than 7 .8 ounces per square yard. 2. 10 VIBRATION ISOLATION A. ACCEPTABLE MANUFACTURERS .. 1. Mason Industries Inc. 2 . Vibration Mountings and Controls, Inc. 3. Consolidated Kinetics Corp. HVAC 15600-14 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2 .07 ACCESS PANELS .ws A. ACCEPTABLE MANUFACTURERS 1. Milcor Div. ; Inryco Inc. 2 . Miami Carey 3. Way Loctor * B. GENERAL: Furnish for installation by others access panels for access to all concealed valves or equipment requiring accessibility for maintenance or proper operation, when such elements are located behind building surfaces or enclosures. C. Instruct appropriate panel installation contractor as to the proper location of all panels. Locate panels so that valve or element served can be easily reached. Size of panels shall be sufficient to serve intended purpose but in no case less than 9 inch by 9 inch. Panels located in corridors, lobbies or other habitable areas shall be reviewed by Architect as to location. D. Access panels shall be prime painted with flush screw driver operated cam locks and concealed hinges. *■ E. Type of panels shall be as follows: GYPSUM Board Surfaces "Milcor Type K" Masonry Construction "Milcor Type M" 2.08 DUCTWORK INSULATION A. ACCEPTABLE MANUFACTURERS 1. CertainTeed Corp. 2 . Knauf Fiber Glass 3. Owens Corning Fiberglas Corp. B. DUCTWORK INSULATION 1. FLEXIBLE FIBERGLASS INSULATION: ANSI/ASTM C553; commercial grade; 'k' value of 0.30 at 75 deg. F. mean temperature; 1.0 pcf density; foil scrim kraft facing. 2 . RIGID FIBERGLASS INSULATION: ANSI/ASTM C612, Class 1; 'k' value of 0.24 at 75 deg. F. mean temperature; 3.0 pcf minimum density; foil scrim kraft facing. HVAC „� 15600-13 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects E. ACCESSORIES 1. Insulating Cement: ASTM C195; hydraulic setting mineral wool. 2 . Adhesives, Sealers, and Protective Finishes: As recommended by insulation manufacturer for applications indicated. 3. Staples, Bands, Wires, and Cement: As recommended by insulation manufacturer for applications indicated. 2.06 MECHANICAL IDENTIFICATION A. ACCEPTABLE MANUFACTURERS 1. Allen Systems, Inc. 2. Brady (W.H. ) Co. ; Signmark Div. 3. Seton Name Plate Corp. B. MATERIALS 1. Unless specified otherwise, conform with ANSI/ASME A13. 1. 2 . Plastic Nameplates: Laminated three-layer plastic ** with engraved black letters on light contrasting background. 3. Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch diameter with smooth edges. 4. Plastic Pipe Markers: Factory fabricated, flexible, semirigid plastic, preformed to fit around pipe or pipe covering; minimum information indicating flow direction arrow and fluid being conveyed. 5. Plastic Tape Duct Markers: Flexible, vinyl film tape with pressure sensitive adhesive backing and printed markings. 6. Underground Plastic Pipe Markers: Bright colored continuously printed plastic ribbon tape of not less than 6 inch wide by 4 mil thick, manufactured for direct burial service. HVAC 15600-12 am SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects MR 5. Shields for Vertical Copper Pipe Risers: Sheet lead. 6. ACCEPTABLE MANUFACTURERS a. Carpenter and Patterson, Inc. b. Elcen Metal Products Co. C. ITT Grinnel Corp. t�wr B. HANGER RODS 1. Steel Hanger rods: Continuous threaded. C. INSERTS AND BUILDING ATTACHMENTS 1. Inserts: Malleable iron case of steel shell and *' expander plug for threaded connection with lateral adjustment, top slot for reinforcing rods, lugs for attaching to forms; size inserts to suit threaded hanger rods. 2. Provide: Provide steel beam clamps, C-clamps, and steel brackets as required to accept threaded rods. 2 .05 PIPING INSULATION +* A. ACCEPTABLE MANUFACTURERS 1. CertainTeed Corp. 2. Knauf Fiber Glass 3. Owens Corning Fiberglas Corp. B. INSULATION 1. FIBERGLASS PIPE INSULATION: Glass fiber pipe insulation; ASTM C547; Class 1; 'K' value of 0.24 at 75 deg. F. mean; noncombustible. Kraft reinforced foil vapor barrier jacket with self-sealing adhesive joints. 2 . RUBBER TUBE PIPE INSULATION: Flexible unicellular pipe insulation; ASTM C534; 'K' value of 0.255 at 75 deg. mean. C. FITTING JACKETS: PVC; one-piece; molded. D. EXTERIOR JACKETS 1. Aluminum: ASTM B209; 0.02 inch thick; smooth finish. HVAC 15600-11 .. SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects .. 4 . Type GLV5: Bronze, rising stem, renewable composition disc, screw-over bonnet, screwed ends, 250 psi. .. E. BALL VALVES 1. Acceptable Manufacturer: Watts Pressure Regulator. "' 2 . Type BLV1: Bronze body and retainer, reinforced Teflon seats and packing, chromium plated ball, soldered ends, 2" and less: Watts 6001 SS; 2-1/2" and up: Watts G4000. 3. Type BLV2: Bronze body and retainer, reinforced Teflon seats and packing, chromium plated ball, screwed ends, 2" and less: Watts 6000 SS; 2-1/2" and up: Watts G4000. * F. CHECK VALVES 1. Type SCV1: Swing check valve, bronze body, regrinding bronze disc, soldered ends, 300 psi, (Jenkins Fig. 122) . 2 . Type SCV2: Swing check valve, bronze body, regrinding bronze disc, screwed ends, Class 150, (Jenkins Fig. 92-A) . G. DRAIN VALVES 1. Type DV1: Ball or gate valve with hose end, bronze cap and chain. am H. PLUG VALVES 1. Type PV1: Semi-steel, bolt gland type, (Rockwell Fig. 142 or 143) . 2 .04 SUPPORTS AND ANCHORS A. PIPE HANGERS AND SUPPORTS 1. Hangers for Pipe Sizes 1/2 Inch to 1-1/2 Inch: Adjustable steel band hanger; MSS Type 7. 2 . Hangers for Pipe Sizes 2 Inch to 3 Inch : Carbon steel, adjustable, clevis; MSS Type 1. 3. Floor Support for Pipe Sizes to 4 Inch and All Cold Pipe Sizes: Cast iron adjustable pipe saddle, locknut nipple, floor flange, and concrete pier or steel support. 4 . Provide copper plated hangers and supports for copper piping systems. HVAC 15600-10 ON SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects no 2. Where a single acceptable manufacturer does not produce all valve types required, multiple manufacturers may be used, but in no case shall the same type valve be provided by different manufacturers. 3. Valve manufacturers and their valve numbers indicated herein are meant to describe type and quality only. 40 B. ACCEPTABLE MANUFACTURERS 1 . Jenkins Bros. 2 . Crane Co. 3. Powell (Wm. ) Co. 4. Conbraco Ind. Inc. , (Apollo) 5. Jamesbury Corp. 6. Mission Mfg. Co. 7. Rockwell Mfg. Co. 8. Watts Regulator Co. C. GATE VALVES 1. Type GV1: Bronze,non-rising stem, inside screw, solid wedge, solder ends, 200 psi water, (Jenkins Fig. 1240) . w 2. Type GV3: Bronze, traveling stem, inside screw, solid wedge, screwed ends, union bonnet, Class 150, (Jenkins Fig. 62-U) . 3. Type GV4: Iron body, bronze trim, OS&Y, solid wedge, rising stem,flanged ends, Class 125, (Jenkins Fig. 651-A) . 4. Type GV6: Bronze, non-rising stem, inside screw, solid wedge, screwed ends, screw-in bonnet,Class 300, (Jenkins Fig. 270) . D. GLOBE VALVES 1. Type GLV1: Bronze, rising stem, renewable composition disc, screw-in bonnet, solder ends, 300 psi water, (Jenkins Fig. 1200) . 2 . Type GLV2 : Bronze, rising stem, renewable composition disc, screw-over bonnet, screwed ends, Class 150, (Jenkins Fig. 106-A) . 3. Type GLV3: Iron body, bronze trim, OS&Y, renewable composition disc, rising stem, flanged ends, Class 125, (Jenkins Fig. 142) . HVAC 15600-9 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects F. FIRE BARRIER PENETRATION SEALS 1. Provide seals for any opening through fire rated .R walls, floors, or ceilings used as passage for mechanical components and piping. 2 . Cracks, Voids, or Holes UP to 4" Diameter: Use putty or calking, one piece intrumescent elastomer, non-corrosive to metal, compatible with synthetic ., cable jackets, and capable of expanding 10 times when exposed to flame or heat, UL listed. 3. Openings 4" or Greater: Use sealing system capable of passing 3-hour fire test in accordance with ASTM E-814, consisting of wall wrap or liner, partitions, and end caps capable of expanding when exposed to temperatures of 250 to 350 deg. F. , UL listed. 4. ACCEPTABLE MANUFACTURERS a. Electro Products Div./3M. b. Nelson; Unit of General Signal. G. FABRICATED PIPING SPECIALTIES 1. Pipe Sleeves: Provide pipe sleeves of one of the .� following: a. Sheet-Metal: Galvanized sheet steel. Fabricate of following gages: 3" and smaller, 20 gage, 4" to 6" , 16 gage, over 6", 14 gage. b. Steel-Pipe: Fabricate from schedule 40 galvanized steel pipe; remove burrs. C. Plastic-Pipe: Fabricate from Schedule 80 PVC plastic pipe; remove burrs. 2 . Sleeve Seals: Provide sleeve seals for sleeves located in foundation walls below grade, or in exterior walls. 2 .03 VALVES 4W A. GENERAL 1. Provide valves of same manufacturer throughout where possible. HVAC 15600-8 40 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects on 4 . ACCEPTABLE MANUFACTURERS 0. a. Armstrong Machine Works. b. Hoffman Specialty ITT; Fluid Handling Div. go C. Spirex Sarco. 40 C. HIGH PRESSURE Y-TYPE PIPELINE STRAINERS 1. General: Provide strainers full line size of 40 connecting piping, with ends matching piping systems materials. Select strainers for 250 psi working pressure, with Type 304 stainless steel screens, with 3/64" perforations @ 233 per sq. in. 2 . Threaded Ends - 2" and Smaller: Cast-iron body, screwed screen retainer with centered blowdown fitted ,., with pipe plug. 3. Flanged Ends - 2-1/2" and Larger: Cast-iron body, bolted screen retainer with off center blowdown fitted with pipe plug. 4 . ACCEPTABLE MANUFACTURERS w a. Armstrong Machine Works. b. Hoffman Specialty ITT; Fluid Handling Div. c. Spirex Sarco. D. DIELECTRIC UNIONS 1. General: Provide standard products for use in service • indicated, which effectively isolate ferrous from non-ferrous piping (electrical conductance) , prevent galvanic action, and stop corrosion. �. E. MECHANICAL SLEEVE SEALS 1. General: Modular mechanical type, consisting of interlocking synthetic rubber links shaped to continuously fill annular space between and sleeve, connected with bolts and pressure plates which cause rubber sealing elements to expand when tightened, providing watertight seal and electrical insulation. 2 . ACCEPTABLE MANUFACTURERS a. Thunderline Corp. HVAC 15600-7 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. UNIONS AND COUPLINGS 1. Pipe Size 2 inch and under: 150 psi malleable iron for threaded ferrous piping; bronze for copper or brass pipe soldered joints. D. MISCELLANEOUS PIPING MATERIALS/PRODUCTS 1. Tin-Lead Solder (95/5) : ASTM B 32, Grade 50 A. 2 . Silver-Lead Solder: ASTM B 32, Grade 96TS. 2 .02 PIPING SPECIALTIES A. PIPE ESCUTCHEONS 1 . General: Provide pipe escutcheons as specified herein with inside diameter closely fitting pipe or pipe insulation outside diameter. Select outside diameter .. of escutcheon to completely cover pipe penetration hole in floors, walls, or ceilings; and pipe sleeve extension, if any. Furnish pipe escutcheons with .. nickel or chrome finish for occupied areas, prime paint finish for unoccupied areas. 2 . Pipe Escutcheons for Moist Areas: For waterproof floors, and areas where water and condensation can be expected to accumulate, provide cast brass or sheet brass escutcheons, solid or split hinged. 3. Pipe Escutcheons for Dry Areas: Provide sheet steel escutcheons, solid or split hinged. B. LOW PRESSURE Y-TYPE PIPELINE STRAINERS 1. General: Provide strainers full line size of connecting piping, with ends matching piping systems materials. Select strainers for 125 psi working pressure, with Type 304 stainless steel screens, with 3/64" perforations @ 233 per sq. in. 2 . Threaded Ends - 2" and Smaller: Cast-iron body, screwed screen retainer with centered blowdown fitted with pipe plug. 3. Flanged Ends - 2-1/2" and Larger: Cast-iron body, bolted screen retainer with off center blowdown fitted with pipe plug. HVAC 15600-6 „ SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects ,w B. Provide extended period warranties and/or guaranties as required by this Section of the Specifications. C. Provide warranties of systems and equipment as required by the provisions of Section 01300 - Submittals and Section 01700 - Contract Closeout. 1. 14 SITE EXAMINATION A. Visit site prior to submitting bid to become familiar with the existing conditions which may affect the installation of systems or products provided as part of the work of this Section. B. Extra payment or compensation for work required by this *�* Section due to existing conditions that would have been observed during the site examination, will not be made. PART 2 - PRODUCTS 40 2.01 PIPE AND FITTINGS A. PIPE AND TUBE + • 1. Black Steel Pipe: ASTM A 53, A 106 or A 120; except comply with ASTM A 53 or A 106 where close coiling or bending is required 2. Copper Tube: ASTM B 88, seamless. 3. ACR Copper Tube: ASTM B 280. B. FITTINGS 1. Cast Iron Threaded Fittings: ANSI B 16.4. 2 . Malleable Iron Threaded Fittings: ANSI B 16.3; plain or galvanized as indicated. 3. Malleable Iron Threaded Unions: ANSI B 16.39; selected by installer for proper piping fabrication w and service requirements, including style, end connections, and metal to metal seats (iron, bronze or brass) ; plain or galvanized as indicated. m 4 . Wrought Copper Solder Joint Fittings: ANSI B 16.22 . m® AM HVAC ON 15600-5 ow SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 4W F. Submit separate product data of the following: 1. Chiller 2. Heat Exchanger 3. Fan Coil Units 4 . Insulation 5. Valves 6. Air Inlets and Outlets 7. Steam Specialties 8. Fans 9. Water Pumps 10. Hydronic Specialties 1.08 DELIVERY, STORAGE AND HANDLING A. Refer to Section 01600 - Materials and Equipment. B. Deliver materials and equipment to the job site in sealed, undamaged cartons, containers, crates or bundles. C. Each carton, container or crate shall be identified with manufacturer's name and model number. D. Protect all equipment and materials from damage, weather and construction activities. am 1.09 PERMITS A. Give all required notices, file all required plans and ,w Specifications relating to the work of this Section with the proper authorities and pay for any required permits. 1. 10 RECORD DRAWINGS A. Comply with the requirements of DIVISION 1 - GENERAL REQUIREMENTS. .� 1. 11 COORDINATION DRAWINGS A. Comply with the requirements of DIVISION 1 - GENERAL REQUIREMENTS. 1. 12 CORRECTIVE WORK A. Correct all defective or rejected work according to the provisions of the General Conditions of Contract. 1. 13 WARRANTIES A. Refer to General Conditions of Contract. HVAC 15600-4 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects B. MANUFACTURERS QUALIFICATIONS: Firms regularly engaged in the manufacture of any products they offer for the project of the types, materials and sizes required, whose products have been in service for at least 5 years. 40 1.06 REFERENCES A. STANDARDS: Except as modified by governing codes or this 40 specification, the following applicable standards (latest editions, unless otherwise stated) shall apply to materials, equipment and installation of components and am systems furnished and/or installed as part of this Section: 1. ASHRAE Standard 15-70: Safety Code for Mechanical `"" Refrigeration. 2 . NFPA 45: Laboratories Using Chemicals. am 3. NFPA 90A: Air Conditioning and Ventilation Systems. 4. NFPA 91: Blower and Exhaust Systems. 40 5. SMACNA Low Pressure Duct Construction Standards. 6. SMACNA High Velocity Duct Construction Standards. B. CODES and ORDINANCES: Conform with the provisions of the AM latest editions of the following: 1. Massachusetts State Building Code. "®' 2 . Town of Northampton, MA fire protection codes and/or ordinances. 00 3. BOCA Basic Mechanical Code. 1.07 SUBMITTALS A A. Make submissions in accordance with Section 01300 - Submittals. B. Within 30 days of receipt of bid, submit complete list of products proposed, with names of manufacturers, trade names and models. �. C. Submit independent testing and balancing reports. D. Submit operation and maintenance manuals with cut sheets of all equipment. E. Submit warranties. HVAC 15600-3 so SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects am C. DIVISION 7 - THERMAL AND MOISTURE PROTECTION 1. Installation of roof curbs and supports furnished by .o the HVAC Contractor. D. DIVISION 9 - FINISHES "' 1. Installation of access panels furnished under this Section of the Specifications. 4M 2. Final painting of HVAC elements. E. Section 15400 - Plumbing 1. Backflow preventors for water makeup. 2 . City water make up source. F. DIVISION 16 - ELECTRICAL 1. All power wiring. 2 . All motor starters not furnished as part of packaged HVAC equipment. 1.04 SYSTEMS DESCRIPTION .* A. New secondary chilled water piping system connected to the Campus chilled water distribution system. 4, B. New steam to hot water heat exchanger. Steam supplied via campus distribution system. .A C. New two pipe fan coil system. System consist of fan coil units, hot/chilled water pumps and piping. D. New A/C condensate drain piping system. E. New inline toilet exhaust fans and ductwork. F. ALTERNATE NO. 1: Install 25 ton split system chiller in lieu of connecting to the Campus chilled water distribution system. 1.05 QUALITY ASSURANCE ow A. INSTALLERS QUALIFICATIONS: Firms with at least 5 years of successful experience in the installation of systems of similar type as those included as part of this Section of the Specifications. MW .» HVAC 15600-2 am ON SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects SECTION 15600 HEATING, VENTILATION & AIR CONDITIONING PART 1 - GENERAL 1.01 GENERAL PROVISIONS A. Requirements of General Conditions of the Contract, Supplementary Conditions, and Division 1, General Requirements are hereby made a part of this Section as fully as if repeated herein. 1.02 WORK INCLUDED A. The work to be done under this Section, without limiting the generality thereof, shall include furnishing all labor, materials, equipment and services to construct and install the complete HVAC systems as shown on the plans and specified herein. This work shall include the following: 1. Heat transfer systems. 2 . Mechanical insulation 3. Heating hot water/chilled piping systems. 4 . Steam and steam condensate piping systems. 5. Air distribution systems (Ductwork) . 6. Heating and cooling terminals. 7 . Automatic temperature controls. B. Testing, balancing and adjusting. 1.03 RELATED WORK A. DIVISION 2 - SITEWORK 1. Excavation and backfill. B. DIVISION 3 - CONCRETE 1. Hold-down, traffic and house keeping pads for HVAC equipment and fuel storage tanks. HVAC 15600-1 PARR. TITLE PAGE 3.01 PROTECTION 15600-28 3.02 INSTALLATION OF EQUIPMENT-GENERAL 15600-29 3.03 INSTALLATION OF PIPE AND FITTINGS 15600-29 3.04 INSTALLATION OF VALVES 15600-31 3.05 INSTALLATION OF PIPING SPECIALTIES 15600-31 3.06 INSTALLATION OF HANGERS AND SUPPORTS 15600-32 3.07 INSTALLATION OF PIPE INSULATION 15600-33 3.08 INSTALLATION OF MECHANICAL IDENT. 15600-34 3.09 INSTALLATION OF DUCTWORK INSULATION 15600-36 *� 3. 10 INSTALLATION OF EQUIPMENT INSULATION 15600-37 3. 11 INSTALLATION OF DUCTWORK 15600-38 3. 12 INSTALLATION OF DUCTWORK ACCESSORIES 15600-40 3. 13 INSTALLATION OF HYDRONIC PIPING 15600-40 3. 14 INSTALLATION OF STEAM & COND. PIPING 15600-41 3. 15 INSTALLATION OF A/C COND. PIPING 15600-42 3. 16 INSTALLATION OF DUPLEX CONDENSATE PUMPS 15600-42 3. 17 INSTALLATION OF IN-LINE EXHAUSTERS 15600-42 3. 18 INSTALLATION OF STEAM TO WATER HEAT EXCH. 15600-43 3. 19 TESTING, ADJUSTING & BALANCING 15600-43 .. am SECTION 15600 HEATING, VENTILATION AND AIR CONDITIONING PARR. TITLE PAGE 1.01 GENERAL CONDITIONS 15600-01 1.02 WORK INCLUDED 15600-01 1.03 RELATED WORK 15600-01 1.04 SYSTEMS DESCRIPTION 15600-02 1.05 QUALITY ASSURANCE 15600-02 1.06 REFERENCES 15600-03 1.07 SUBMITTALS 15600-03 1.08 DELIVERY, STORAGE AND HANDLING 15600-04 1.09 PERMITS 15600-04 1. 10 RECORD DRAWINGS 15600-04 1. 11 COORDINATION DRAWINGS 15600-04 1. 12 CORRECTIVE WORK 15600-04 1. 13 WARRANTIES 15600-04 1. 14 SITE EXAMINATION 15600-05 2.01 PIPE AND FITTINGS 15600-05 2 .02 PIPING SPECIALTIES 15600-06 2 .03 VALVES 15600-08 2 .04 SUPPORTS AND ANCHORS 15600-10 2 .05 PIPING INSULATION 15600-11 2 .06 MECHANICAL IDENTIFICATION 15600-12 2.07 ACCESS PANELS 15600-13 2 .08 DUCTWORK INSULATION 15600-13 2.09 EQUIPMENT INSULATION 15600-14 2. 10 VIBRATION ISOLATION 15600-14 2. 11 THERMOMETERS AND GAGES 15600-15 2. 12 DUCTWORK 15600-16 2. 13 DUCTWORK ACCESSORIES 15600-17 2. 14 HYDRONIC PIPING SYSTEMS 15600-19 2. 15 HYDRONIC SPECIALTIES 15600-19 2 . 16 STEAM AND CONDENSATE PIPING SYSTEMS 15600-21 2 . 17 STEAM AND CONDENSATE SPECIALTIES 15600-22 2. 18 A/C CONDENSATE PIPING 15600-24 2 . 19 AIR INLETS AND OUTLETS 15600-24 2 .20 FAN COIL UNITS 15600-24 2.21 DUPLEX CONDENSATE UNITS - CAST IRON 15600-26 2.22 IN-LINE EXHAUSTERS 15600-27 2 .23 STEAM TO LIQUID-TUBE IN SHELL EXCHANGERS 15600-28 2 .24 AUTOMATIC TEMPERATURE CONTROLS 15600-28 as Im SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin S Associates, Architects 3.04 STERILIZATION A. The entire new potable hot and cold water distribution system for the building shall be thoroughly sterilized with a solution containing not less than 50 parts per million of available chlorine. The chlorinating materials shall be either liquid chlorine, calcium hypochlorite, or chlorinated lime. The sterilizing solution shall be allowed to remain in the system for a period of eight (8) hours, during which time all valves and faucets shall be opened and closed several times. After sterilization, the solution shall be flushed from the system with clean water until the residual chlorine content is not greater than 0.2 part per million, unless otherwise directed. 3.05 INSTRUCTIONS A. After a completion of assembly and installation of all systems and equipment and piping required under this Section of the Specifications, the Owner's supervisory and operating personnel and maintenance of the systems. The instructions shall be given by the Plumbing Subcontractor and other qualified personnel who are thoroughly familiar with all systems and shall be furnished for a time period as directed by the Architect. OF PART 3 ++ ++ END OF SECTION 15400 ++ PLUMBING M, 15400-21 Mo SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects ' D. Each new system shall be pressure tested at pressures described herein and in a manner as described herein. Test pressures for each system shall be maintained as long as required by the Architect to determine the tightness of the system and/or with painted soap solutions. Wherever testing indicates leaks, the leaks shall be repaired in a manner prescribed by the Architect and the test shall be reprocessed until the system is proven tight. E. New storm, soil, waste and vent piping shall have openings plugged and the system above filled with water to the top of vent pipes. Water shall be allowed to stand a minimum of 60 minutes, or as long thereafter as is required for the complete inspection. Each vertical stack with its branches may be tested separately. If the lines prove tight the water shall be drawn off and the fixtures connected. F. All water piping shall be tested to a hydrostatic pressure of one hundred twenty-five (125) pounds per square inch and proven tight at this pressure. Test pressures shall be held for at least 8 hours minimum, or as long thereafter as is required to make the complete - test. Water piping to be concealed by structural work or put in grade shall be tested to the above pressure and �. proven tight before pipes are concealed. G. Furnish and make temporary installations of all pumps, compressors and instruments for the testing. Test *► pressures shall be held for at least the minimum time periods noted above, or long enough thereafter to prove the system tight that is being tested. Any defects in any system shall be repaired or replaced as directed and the expense shall be borne by the Plumbing Subcontractor. H. All soap tested joints shall be washed clean after testing, and test water properly drawn off. 3.03 CLEANING AND ADJUSTING A. At the completion of the work, all fixtures, equipment apparatus and exposed trim for same included in this Section shall be cleaned, and where required polished ready for use. Faucet washers which have been damaged during construction shall be replaced. Drains and traps shall be thoroughly cleaned. PLUMBING """ 15400-20 SMITH COLLEGE - OFFICE OF ADMISSION .. David P. Handlin & Associates, Architects PART 3 - EXECUTION 3.01 PIPING INSTALLATION A. All above ground piping shall be installed as closely as possible to walls, ceilings, beams, columns, etc. , consistent with proper space allowance. B. The Plumbing Subcontractor shall note the invert elevations of existing and new sanitary and storm drains and shall run his piping to these inverts as evenly as possible. Branches on sanitary lines shall pitch a minimum of 1/8 inch to one foot wherever possible. C. All piping shall be run approximately as indicated on the Drawings and to avoid conflicts, rigidly supported and evenly spaced, aligned and/or graded and arranged without sags, pockets or low spots. Low ends of water lines shall be fitted with drain leg tees fitted with screwed plugs. D. Valves, special traps and accessories shall be installed *^°° so as to allow for proper operation and maintenance. E. Except where otherwise noted, all piping shall be concealed in walls, ceiling construction, access spaces and chases provided. F. In general, the sizes of drainage lines shall be as indicated on the Plans, but in no case shall fixture drains and wastes be less than those required by the Plumbing Code. • 3.02 PLUMBING SYSTEM TESTS A. All plumbing systems shall be tested by the Plumbing Subcontractor in the presence of the Owner, Architect or his representative and the Plumbing Inspector after completion of "ROUGHING IN" and before concealing any section from view. B. Furnish labor, tools and all materials and do all testing as described herein. C. No piping shall be insulated until it has been pressure , tested and proven tight. All new systems that can be isolated with valves shall be pressure tested and proven tight as described herein. PLUMBING 15400-19 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. Furnish and install stamped or embossed 1/2" diameter brass tags or plastic identification plates for each valve, control entity or piece of equipment. These identification plates shall be permanently attached to their identifying equipment or valves with brass hooks or brass link chain. Each drain valve or plug shall be tagged "DRAIN". D. Each brass valve tag shall be lettered for its appropriate service and numbered in consecutive order; "CW" for cold water and "HW" for hot water. E. Prepare in triplicate a complete listing of each valve, its number and describing its control function. These listings shall be framed and presented to the Architect at the completion of the job. 2. 11 ACCESS PANELS A. This Subcontractor shall furnish access panels for access „u„ to all concealed valves and cleanouts and to all other concealed parts of the plumbing system that require accessibility for the proper operation and maintenance of go the system. B. These panels will be installed by the appropriate Subcontractor concerned with that portion of the building «4 construction to which the access panel will be attached. C. All access panels shall be located and positioned so that on the valve or cleanout can be easily reached and the size shall be sufficient for this purpose (min. size 9"x 9" ) . When access panels are required in corridors, lobby or other habitable areas, they will be located as directed go by the Architect. D. Access panels shall be prime painted with cylinder lock so and two keys as manufactured by Inland Steel Products Company, "Milcor", Miami Carey or Walsh-Hannon-Gladwin, Inc. , "Way Loctor", or equal. no E. Type shall be as follows: Gypsum Board Surfaces "Milcor Type DW" go ++ END OF PART 2 ++ on PLUMBING 15400-18 SMITH COLLEGE - OFFICE OF ADMISSION �* David P. Handlin & Associates, Architects P-4 MOP BASIN Fiat MSB-2424 24" x 24" molded stone basin with integral drain body and dome strainer. Chicago 897 faucet with vacuum breaker, integral stops and wall brace. .. 832-AA hose and hose bracket. E-77-AA vinyl bumper guard. 3" C.I. P-trap. P-5 DRINKING FOUNTAIN, H.C. Oasis OEP8WM-AE wall mount electric fountain, complete with mounting brackets. 3/8" supply with stop and 1-1/2" P-trap to suit. Smith floor support hanger to suit. 2.09 WATER HEATER A. Furnish and install one (1) electric water heater where indicated. Heater shall have a capacity of 40 gallons and a recovery rate of 18 GPH at 100 deg. F. temperature rise with (2) 4.5 KW, 208V, 3 phase electric input. Heater shall be Sepco S40. 2. 10 VALVE TAGS, CHARTS AND PIPE MARKINGS A. Furnish and install pipe identification markers on all exposed piping installed under this part of the Specification. Piping above removable suspended ceilings shall be considered exposed as well as piping located in mechanical equipment room or spaces. B. Pipe identification markers shall consist of labels of black letters, imprinted on color coded background and 1-1/2" color bands. Labels and bands shall indicate the pipe fill and the direction of flow. Pipe identification �. labels shall be the coiled snap-on type, letters to be 2" high on all pipes 3" diameter and over, letters to be 3/4" high on all pipes under 3" diameter. Pipe identification markers shall be applied to the pipe or the insulation in the case of insulated pipes, on 15, centers and at each valve, whichever is closer. Color coding for pipe identification shall be as follows: ** Legend Background Cold Water Green Dom. Hot Water Supply Yellow Pipe identification markers shall be W.H. Brady & Co. , or approved equal. PLUMBING 15400-17 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin 6 Associates, Architects H. The Plumbing Subcontractor shall furnish all supports, brackets, brass bolt, etc. , for proper installation of any fixtures requiring support. They shall be in accordance with the manufacturer's recommendations and, if necessary, shall be built into place as the building progresses. This subcontractor shall be held responsible for the stability of and proper support of all plumbing fixtures. I. Unless otherwise specified, all fixtures shall be set flush and square to walls and floors and shall be taken up as close as possible without springing. Should there be a separation between fixture and wall and/or floor due to wall and/or floor variations, space shall be packed with oakum and sealed with a smooth bead of white silicone sealer. P-1 WATER CLOSET, HC 3043.102 'Cadet' siphon jet, floor mount, 1-1/2" top spud, 18" high rim, 1.5 GPF. (2) 481310-100 bolt caps. +*• 5320.536 white seat with open front and check hinge. Sloan 111 'Royal' flush valve complete. Closet flange with sealing ring to suit. P-2 LAVATORY. H.C. 0195.289 'Roxylyn' 24" x 20" vitreous china, wall hung, 4" centers. 2103.620 supply fitting with aerator and 4" wrist blade handles. 7723.018 offset drain with grid strainer and tailpiece. (2) 7536.014 3/8" close pattern supplies with loose key stops. 4402.061 1-1/4" x 1-1/2" C.P. P-trap with extension to wall. Smith floor support arm carrier with 2" escutcheon spacers to suit. P-3 WORK SINK Elkay LR-1918 19" x 18", 18 gauge stainless steel, single bowl, counter insert, self-rim, 3-hole punch. LK-4100 single lever faucet with swing spout. LK-35 drain with strainer and tailpiece. (2) 3/8" supplies with stops and escutcheons. 1-1/2" rough brass P-trap with cleanout and extension to wall with escutcheon. PLUMBING 15400-16 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2.07 CLEANOUTS A. Cleanouts shall be iron body with heavy brass plug and raised nut, same size as pipe for piping up to 4 inches in size and no less than 4 inches for piping larger than '* 4 inches in size and closed gas tight. Cleanouts occurring under finish floors on buried piping shall be brought flush with finish floor and shall have deck Owl plate, type as directed by the Architect, but be similar to Smith 4810 or approved equal, brass access cover with polished brass top. ow 2.08 PLUMBING FIXTURES A. The Plumbing Subcontractor shall furnish and install all "* fixtures shown on Plumbing Drawings and hereinafter specified, except as otherwise noted. on B. The number arrangement of the plumbing fixtures are as shown on the Drawings. The plate numbers and manufacturer's name given are American Standard and shall be used for the purpose of establishing size, grade and trim of fixtures. Kohler is also acceptable. C. The Plumbing Subcontractor must obtain written approval of the list of fixtures before placing orders for same. D. All exposed fixture brass goods shall be heavy , chromium-plated, and as manufactured by the manufacturer of the plumbing fixtures, unless otherwise specified. All exposed water and waste piping and fittings at any fixture, not required to be insulated shall be chromium-plated. E. All fixtures shall be fitted with a stop valve on each .. supply line. F. All fixtures shall be best quality, free from any defects. G. Supplies to individual fixtures shall be equipped with an air chamber at least 20 pipe diameters long and as large •* as the pipe it serves. Supplies to a group or battery of fixtures shall each be furnished with a water hammer arrestor similar to PPP, Inc. , 3/4" , or equal. PLUMBING 15400-15 WN SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects No D. Hot water supplies and drains under handicap lavatories and sinks shall be insulated in the same manner as for hot and cold water. "' E. All insulation installed shall pass through all walls, ceilings and floors continuously and shall not be applied to any piping system until that system has been tested, proven tight and furnished with a sheet metal shield to support the insulation. F. Fire Safety: Insulating materials as described above or approved equal materials shall meet Fire and Smoke Hazard Classification ratings on a COMPOSITE basis in accordance with NFPA 255 and UL723. These products shall not exceed a flame spread and developed smoke rating minimum. Fitting covers shall not exceed maximum toxicity ratings. 2.05 FLOOR DRAINS AND DECK DRAINS A. Floor and deck drains shall be furnished and installed by this Subcontractor and flashing installed by the Flashing SubContractor. These drains shall be as manufactured by J.R. Smith, Zurn, Josam, or approved equal and shall be as scheduled on the Drawings. Sizes of drains shall be aw the same size as the piping it serves. This Subcontractor shall be responsible for correctly setting all drains at proper grades for proper drainage. 2.06 WALL HYDRANTS A. Furnish and install wall hydrants, where indicated. Hydrants shall be set approximately 18 inches above finish grade. Wall hydrants shall be as manufactured by J.R. Smith, Josam Mfg. Co. , Zurn Mfg. Co. , or approved equal, and shall be similar to Smith 5609, non-freeze type with brass face, key handle, integral vacuum breaker and nozzle for 3/4 inch hose connections. They shall be of sufficient length to go through wall, placing the shut-off valve inside the building. Stem and washer shall be movable from the front of the hydrant, and shall have heavy brass coupling and union elbow for 3/4 inch pipe. The outer casing shall be galvanized steel, and the inside operating rods shall be brass. ®w PLUMBING 15400-14 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2. Fabrication: Piping and fittings shall be thoroughly cleaned over the full areas of the mating parts, after which solder shall be applied so as to flow over and offer complete bond to the full areas of the mating parts. Excess solder shall be removed. Each joint shall be held rigid and still until completely cooled after being made-up and soldered. solder shall be 95% tin and 5% antimony, Mueller Brass, Dutch Boy or Gem. 2.03 VALVES .� A. Furnish and install valves where indicated on the Drawings or specified so located that they may be operated, repaired or replaced with a minimum effort and repacked under pressure. B. The following list of valves is intended as a guide for type and quality for this Contract. C. Cold Water and Hot Water 1. 2-inch and smaller - ball valve, bronze body and trim, stainless steel ball, 200 psig, solder end, 3-piece, Watts 6800 series. D. All valves shall be of the same manufacturer and shall be manufactured by Watts. 2.04 PIPE INSULATION A. Furnish and install the following type pipe covering and insulation on all cold water, hot water and horizontal conductor piping throughout the addition and renovated areas, except stub-out supply piping immediately at AM fixtures and except as noted herein. No pipe covering shall be installed on piping designated as chromium-plated brass pipe. am B. Cold water and hot water piping insulation shall be 1/2" thick, with factory applied fiberglass cloth jacket with integral vapor barrier and self-sealing lap. Fittings and valves shall be fitted with molded PVC covers and shall be secured with glass fabric tape with mastic. Insulation shall be Fiberglass 25 ASJ or equal, and shall be installed as per manufacturer's recommendations to conform to the AUL non-combustible rating. C. Interior horizontal storm piping including fittings into the vertical and roof drain sumps shall be 1 inch thick and the same type as specified for hot and cold water. PLUMBING 15400-13 ! " SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2.02 PIPE. FITTINGS AND FABRICATION A. SANITARY, VENT AND STORM PIPING BELOW GROUND 1. Material: Service weight cast iron, bell and plain end soil pipe and fittings, coated, conforming to latest standards. 2 . Fabrication: Piping shall have all connections made with "Dupont-Neoprene" compression gasket fittings "TY-SEAL" as manufactured by the Tyler Pipe and Foundry Co. , or approved equal. The gaskets shall be furnished by the pipe manufacturer and installed in strict accordance with manufacturer's instructions. B. SANITARY, VENT AND STORM PIPING ABOVE GROUND 1. Material: Service weight cast iron, hubless soil pipe and fittings conforming to latest standards. �. Waste and vent piping 2 inches and smaller may be type L copper tubing with copper or cast brass solder type drainage pattern fittings. 2. Fabrication: Cast iron piping shall be joined with neoprene gaskets and stainless steel clamps as manufactured by Clamp-All and installed in strict accordance with manufacturer's recommendations. Copper DWV tubing and fittings shall be soldered using 50-50 type solder. C. WATER PIPING BELOW GROUND 1. Material: Type "R" hard temper copper tubing, with solder type copper fittings. 2. Fabrication: Piping and fittings shall be thoroughly cleaned over the full areas of the mating parts after which solder shall be applied so as to flow over and offer complete bond to the full areas of the mating parts. Excess solder shall be removed. Each joint shall be held rigid and still until completely cooled after being made-up and soldered. Soft solder shall be 95% tin 5% antimony, Mueller Brass, Dutch Boy, or Gem. D. WATER PIPING ABOVE GROUND 1. Material: Type "L" copper tubing, hard drawn with solder type copper fittings. PLUMBING 15400-12 SMITH COLLEGE — OFFICE OF ADMISSION on David P. Handlin & Associates, Architects E. Hangers for piping of sizes 4 inches and smaller shall be Carpenter Patterson Type No. 1A Band, or approved equal, am black steel and hanger rods with machine threads; for piping of sizes larger than 4, hangers shall be the adjustable clevis hanger type, malleable iron, with 4W extension rod to structure. Hanger rods shall be secured to the building structure by means of approved type inserts in concrete floor construction. F. Common runs of supply piping shall be supported on a single cross hanger consisting or prefabricated channel with rod support fittings and pipe guides. Guides for uninsulated copper pipe shall be copper coated. The Plumbing Subcontractor may share his hangers or share the hangers of other Subcontractors for the support of piping where permissible. G. In addition to normal beam clamps, etc. , the Plumbing Subcontractor shall furnish and install steel angle hanger supports to meet special conditions where hangers are required under ductwork. PIPING SHALL NOT BE SUPPORTED FROM DUCTWORK. H. Inserts: Inserts for concrete installation shall be cast iron or steel of a type to receive a machine bolt head - and nut after installation. I. Vertical risers shall be supported at each floor with long leg, bolted pipe clamps. In addition each riser shall be supported-with a pipe hanger at the top and at offset locations. J. On insulated piping, each hanger shall be equipped with a 18 gauge steel shield provided by the Insulating Subcontractor to support the insulation and prevent the .. hanger from deforming the insulation. Each hanger shall be oversized so that the hanger will allow the insulation to pass through undisturbed and uncut. K. Fixture Supports: All fixtures and equipment shall be supported and fastened in a satisfactory manner. Where wall hung fixtures are backed up to light wall 4" construction, they shall be supported with floor mounted fixture carriers. Floor mounted arm carriers for lavatories shall be securely fastened to the floor and be 4ft similar to Smith #700 or approved equal. 4W PLUMBING 15400-11 so SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects H. Common runs of supply piping shall be supported on a single cross hanger consisting or prefabricated channel with rod support fittings and pipe guides. Guides for uninsulated copper pipe shall be copper coated. The 40 Fire Protection Subcontractor may share his hangers or share the hangers of other Subcontractors for the support of piping where permissible. v I. In addition to normal beam clamps, etc. , the Fire Protection Subcontractor shall furnish and install steel angle hanger supports to meet special conditions where hangers are required under ductwork. PIPING SHALL NOT BE SUPPORTED FROM DUCTWORK. J. Vertical risers shall be supported at each floor level with long leg, bolted pipe clamps. In addition each riser shall be supported with a pipe hanger at the top and at offset locations. R. Inserts: Inserts for concrete installation shall be cast iron or steel of a type to receive a machine bolt head and nut after installation. L. Equipment Supports: All equipment and accessories shall be supported and secured in a satisfactory manner as recommended by the manufacturer or the Architect. 2.02 PIPE, FITTINGS AND FABRICATION A. Piping Below Ground 1. Material: Ductile iron water pipe, bell and spigot, cement lined, Class 50, conforming to latest standards, with neoprene gasket compression joints. 2. Fabrication: Pressure joints shall be push-on gasket type with neoprene gaskets, all assembled in accordance with manufacturer's instructions and code requirements. B. Piping Above Ground 1. Material: Fire Protection piping shall be Schedule 40 black steel with working pressure of not less than 175 PSI. Fittings, couplings, unions, reducers and bushings shall be of a type specifically approved for use in fire protection systems. FIRE PROTECTION 15500-10 SMITH COLLEGE - OFFICE OF ADMISSION so David P. Handlin & Associates, Architects PART 2 - PRODUCTS ". 2.01 SLEEVES, HANGERS, INSERTS AND FIXTURE SUPPORTS A. Pipe sleeves, pipe hangers and fixture supports for plumbing piping and fixtures shall be furnished and set by the Plumbing Subcontractor and this Contractor shall be responsible for their proper and permanent location. B. Sleeves: Cast iron or steel pipe sleeves shall be furnished and set in new walls, floors and roof where pipes are to pass through. Sleeves shall be two (2) nominal sizes larger than pipe and large enough to provide approximately 1/4" clearance around insulation on insulated systems, shall finish flush with wall surfaces • and extend a minimum of 1" above finished floors. C. All pipe openings through floors, interior and exterior building walls or partitions SHALL BE SEALED. Materials and systems shall be as specified herein. 1. Masonry walls shall have openings sealed by packing around the pipe with glass fiber rope and sealing each side with 1" fire resistant caulking. Other wall sleeve openings shall be sealed with glass fiber rope only. Seal floor sleeve openings with glass fiber rope and fire resistant caulking as required to make watertight. This shall be strictly enforced. A, 2. All sleeves through exterior building walls shall be properly sealed watertight and shall be flexible. D. Hangers: All piping shall be rigidly supported from the building structure by means of approved hangers and supports. Pipes shall be supported to maintain required grading and pitching of lines, to prevent vibration and to secure piping in place and shall be arranged so as to provide for proper expansion and contraction of pipe. All horizontal piping shall be supported by approved adjustable, steel pipe hangers, unless otherwise specified and spaced according to code requirements or manufacturer's recommendations for each type and size of piping. PLUMBING 15400-10 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects B. After delivery and before, during and after installation, the Plumbing Subcontractor shall protect all equipment and materials from injury or damage of all causes, as well as from theft. Such loss or damage shall be made good without expense to the Owner. 1.14 FLASHINGS A. All roof drains and vents thru roof shall be set by the Plumbing Subcontractor and shall be flashed by the work of the SECTION 01120, ALTERATIONS. 1.15 PAINTING A. Wherever factory finishes of paint, lacquer, baked enamel, etc. , have been damaged or deteriorated during construction, use factory furnished painting materials and refinish or touch-up the damage or deterioration applied by skilled workmen experienced in painting and finishing, to the satisfaction of the Architect. 1.16 EXCAVATION AND BACRFILL A. Excavation and backfill for plumbing work will be done by the work of SECTION 02200. It will be the responsibility of the Plumbing Subcontractor to coordinate his work in all areas requiring excavation and backfill with the Excavation Contractor so as to implement the job schedule and the orderly progress of the work of all trades. 1. 17 CORE DRILLING A. The Plumbing Subcontractor shall core drill openings through floors, walls and roofs as required to accommodate new plumbing work. B. Cut all masonary and concrete with an approved diamond •+� blade concrete saw in a neat straight direction, perpendicular to the plane of the wall or floor. C. Use a core drilling process which produces clean, sharp edges and the minimum hole size which will accommodate with insulation, where applicable. D. Any spalling or cracking of adjacent concrete or masonry shall be patched to by the Plumbing Subcontractor to the satisfaction of the Owner. E. Prior to any drilling, obtain permission from the General Contractor for each exact coring location. ++ END OF PART 1 ++ PLUMBING 15400-9 SMITH COLLEGE - OFFICE OF ADMISSION �* David P. Handlin 6 Associates, Architects F. When this procedure has been accomplished to the satisfaction of the Plumbing Engineer and the Architect, the Plumbing Subcontractor shall furnish to the Architect the following: 1. The marked up job record blackline prints. 2. The reproducible revised transparencies entitled "Record Drawings". 3. Three complete sets of blackline prints of the "Record Drawings". G. Distribution by the Architect shall be: 1. The reproducibles and one set blackline prints to the Owner. 2. One set blackline prints to the Plumbing Engineer. 3. One set blackline prints retained by the Architect. 1.11 JURISDICTIONAL DISPUTES A. In order to avoid any jurisdictional disputes and work - stoppages that could arise during the installation of the work shown on the Drawings or as specified herein, the Plumbing Subcontractor shall be held responsible to do any sub-letting work that might be required to furnish and install the work shown or specified herein. 1.12 CARTING, HANDLING AND CLEAN-UP A. The Plumbing Subcontractor shall do all carting, handling, hoisting, etc., for his material and equipment AM at his expense in a safe and satisfactory manner. Any damage resulting therefrom shall be repaired or paid for by this Subcontractor to the satisfaction of the Architect. B. Clean-up requirements as specified under Section 01700, PROJECT CLOSEOUT and shall be strictly enforced. 1.13 PROTECTION OF WORK AND PROPERTY A. The Plumbing Subcontractor shall be responsible for the care and protection of all work included in this Section of the Specifications and Drawings until it has been tested and accepted. PLUMBING 15400-8 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects .10 RECORD DRAWINGS A. The Plumbing Subcontractor shall maintain at the job at all times a complete and separate set of blackline prints of the Plumbing Drawings of this trade, on which he shall mark clearly, neatly, accurately and promptly as the work progresses: 1. Changes to be made, whether resulting from formal change orders or other instructions issued by the Architect. 2. His daily progress, by coloring in the various piping, apparatus, and associated appurtenances exactly as they are erected. This process shall incorporate both the changes noted above and all other deviations from the original drawings, whether resulting from job conditions or from any other cause. Principal dimensions of concealed work shall be recorded. B. These marked-up and colored-in-prints will be used as guides for determining the progress of the work installed. They will be inspected monthly by the Plumbing Engineer and they shall be corrected immediately if found either inaccurate or incomplete. C. This procedure is mandatory; as stipulated in DIVISION C, the Architect will not approve any requisition for payment submitted by this Subcontractor until the Plumbing Engineer and the Architect are satisfied that " this complete procedure has been complied with and is up to date. D. At the completion of the job, these prints shall be submitted to the Plumbing Engineer, through the Architect for final inspection and comment. E. The prints will be returned to the Plumbing Subcontractor with appropriate comments and recommendations, and then this Subcontractor shall at his own expense arrange to have an Engineer acceptable to the Plumbing Engineer, make the revisions, in a manner approved by the Plumbing Engineer, on wash-off mylar transparencies of the original contract drawings. PLUMBING ,, 15400-7 SMITH COLLEGE - OFFICE OF ADMISSION am David P. Handlin & Associates, Architects B. The Plumbing Subcontractor shall use only new materials No free from defects and of good quality. He shall see that all his materials, including fixtures, are delivered at the building when required so as to carry on the work in the most effective manner. C. Where "OR EQUAL" is used, it shall be interpreted to mean equal in the opinion of the Architect and subject to their written approval. D. Substitute materials will be considered on the basis of quality function and cost to the Owner. In all cases where approved substitute materials are furnished, the Plumbing Subcontractor shall pay for any additional work or changes required by him or by other Subcontractors on the job. E. All plumbing systems shall be delivered to the Owner complete and in perfect working order, tested and balanced in full accordance with the Plans and Specifications. 1.09 SHOP DRAWINGS A. Submit complete Shop Drawings in accordance with the provisions of Section 01301, SUBMITTALS B. Shop Drawings shall include enough information to prove that the requirements of the Specifications and Drawings are complied with and include installation instructions and wiring diagrams. Shop Drawings submittals shall include but not be limited to the following: 1. Fixtures, trim and accessories. AM 2. Valves. 3. Pipe Hangers. . . 4 . Fixture Supports. 5. Floor Drains. 6. Pipe Insulation. 7. Water Heater. 8. Backflow Preventor. • PLUMBING 15400-6 -• SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 1.06 CODES, PERMITS AND FEES A. All plumbing work shall be installed in accordance with the Massachusetts Plumbing and Gas Code and any applicable regulations of the Town of Northampton and the State of Massachusetts as they apply to the installation. Such laws and ordinances are to be considered a part of this Specification. B. The above Plumbing Ordinances and Building Laws shall be considered as minimum requirements for the plumbing installation. Where specifications call for work to be done in excess of the above requirements, the Specifications shall be followed. C. The Plumbing Subcontractor shall file all required notices and plans and shall secure and pay for all necessary permits and backcharges for his work. D. If any portion of the Plumbing Plans or Specifications conflict with any rules and regulations with regard to type of materials, equipment, or fixtures to be used, the Plumbing Subcontractor shall bring it to the Architect's attention. Otherwise, the cost of all work necessary to make the installation comply with the above rules and regulations shall be paid for by the Plumbing Subcontractor without additional expense to the Owner. 1.07 GUARANTEE A. Furnish to Owner a written guarantee of the General Contractor and this Subcontractor, jointly and severally, against any defects in materials and workmanship in work of this Section for a period of one year from date of substantial completion of the project. Guarantee shall state that defective work shall be remedied without cost to Owner during the guarantee period promptly after written notice of such defects by the Owner, and shall be binding upon both the General Contractor and this Subcontractor. 1.08 WORKMANSHIP. MATERIALS AND DELIVERY A. All work of a special nature shall be performed by r� skilled and qualified workmen who can present credentials showing experience in said trade. PLUMBING 15400-5 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects B. Due to the small scale of the Drawings, it is not possible to indicate all offsets, fittings, valves, etc. , which may be required to complete the work. The Plumbing Subcontractor shall study the drawings showing the structural and finished design of the buildings and shall • furnish and install all fittings, etc. , to fully complete the Plumbing Work. C. Before submitting prices, thoroughly examine all the Contract Documents and the site with special emphasis on all the adjoining work upon which this work depends. D. If for any reason the Plumbing Subcontractor finds that the work cannot be done in any area in accordance with the Plans and Specifications he must immediately notify �. the Architect in writing of his findings. If for any reason the Plumbing Subcontractor fails to do this it shall become his responsibility and he shall bear any and all costs for any work involved, at no extra cost to the Owner. 1.05 INFORMATION A. The Plumbing Subcontractor shall obtain detailed information from the manufacturers of apparatus which he is to furnish and/or install as to the proper method of installation and connections. He shall obtain all information from all other Subcontractors which may be necessary to facilitate his work and the completion of the project. B. He shall keep himself fully informed as to the shape, .. size and position of all openings required for his apparatus and shall give full information to the General Contractor and other Subcontractors as required sufficiently in advance of the work so that all openings may be built on schedule. The Plumbing Subcontractor shall also furnish all sleeves and supports hereinafter specified, shown or implied and shall set same in place. C. In the case of failure on the part of the Plumbing Subcontractor to give proper information as noted above, """ he will be required to do his own cutting and patching to the satisfaction of the General Contractor and without additional expense to the Owner. PLUMBING 15400-4 on SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects .. 10. Shutdown and draining of existing plumbing systems as required to install new work. C. Items to be Furnished Only: Furnish the following items for installation by the designated Sections: 1. Access Panels---Section-,09250. D. Items to be Installed Only: Installation of surface mounted toilet accessories and grab bars furnished by other Sections. 1.03 RELATED WORK IN OTHER SECTIONS A. The following is not included in this Section of the Specification and is work to be performed under other Sections at no expense to the Plumbing Subcontractor. 1. Cutting and Patching (except core drilling for plumbing work) . ■" 2. Excavation and Backfilling. 3. Painting. 4. Furnishing of all toilet accessories and grab bars. 5. Placing of casework. 6. All electrical- connections to plumbing equipment. 7. All required concrete work. 1.04 INTENT A. It is the intention of the Drawings and this Specification to show and specify complete systems of plumbing. Anything that is not shown on the Drawings but is mentioned in the Specifications, or vice-versa or anything not expressly set forth in either, but which is reasonably implied, shall be furnished and performed as though specifically shown and mentioned in both. e PLUMBING 15400-3 SMITH COLLEGE - OFFICE OF ADMISSION .. David P. Handlin S Associates, Architects 2. Complete hot water and cold water systems throughout the addition and renovated areas, connecting to all fixtures and equipment requiring hot and/or cold water. The cold water system work shall extend and connect to the existing cold water system as indicated. The existing water service for the Lower School shall be replaced with a new service, as indicated. The hot water system work shall extend and connect to the existing hot water system in the renovated areas. In the new addition, provide a new electric water heater as indicated. 3. A complete storm drainage system within the renovated areas, connecting to all storm water drains. The work shall extend and connect to the existing storm water system as indicated. 4. All plumbing fixtures, trim and accessories, complete with all necessary piping connections as specified. 5. Furnishing and setting of all pipe sleeves in new construction. 6. All core drilling of new or existing construction as required to install new plumbing work. 7. Furnishing and installation of all pipe insulation for the systems specified to be insulated. • S. Connection to equipment, piping or structures furnished by others: Items of special equipment will be furnished and set in place by the Owner and/or other Subcontractors. Make all final connections to this equipment in such a manner to insure proper operation. Equipment shall be located as indicated on the Drawings or as established in the field at the time of construction. Equipment roughing drawings will be furnished to the Plumbing Subcontractor prior .00 to his installation of finished roughing. 9. Disconnection of existing plumbing fixtures and equipment and removal of all related piping, as indicated. Fixtures and equipment shall be disposed of as directed by the Owner. PLUMBING 15400-2 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects SECTION 15400 PLUMING PART 1 - GENERAL 1.01 REFERENCE A. Requirements of General Conditions of the Contract, Supplementary Conditions and Division 1, General Requirements are hereby made a part of this Section as fully as if repeated herein. 4W B. Refer to the Drawings for further definition of location, extent and details of the work described herein. •ft C. Cooperate and coordinate with all other trades in executing the work described in this Section. D. Where referred to, Standard Specifications of technical "" societies, manufacturer's associations and Federal Agencies shall include all amendments current as of the date of issue of these Specifications. 1.02 SCOPE OF WORK A. The scope of the work under this Section, without limiting the generality thereof, consists of furnishing all labor, material, equipment, scaffolding, power, tools and rigging, except as otherwise specified and performing all work as necessary to fully complete the Plumbing Work shown on the drawings and as specified herein. * B. Work Included: The Plumbing Work will include but not be limited to the following: 1. A complete sanitary drainage and vent system throughout the addition and renovated areas, connecting to all fixtures and pieces of equipment requiring drainage whether furnished under this Section of these specifications or under other Sections. The work shall extend and connect to existing sanitary system as indicated. �lIN PLUMING „�, 15400-1 SECTION 15400 ow PLUMBING PARA. TITLE PAGE 1.01 REFERENCE 15400-01 1.02 _ SCOPE OF WORK 15400-01 1.03 RELATED WORK IN OTHER SECTIONS 15400-03 1.04 INTENT 15400-03 1.05 INFORMATION 15400-04 1.06 CODES, PERMITS AND FEES 15400-05 1.07 GUARANTEE 15400-05 1.08 WORKMANSHIP, MATERIALS AND DELIVERY 15400-05 1.09 SHOP DRAWINGS 15400-06 1. 10 RECORD DRAWINGS 15400-07 1. 11 JURISDICTIONAL DISPUTES 15400-08 1. 12 CARTING, HANDLING AND CLEAN-UP 15400-08 *" 1. 13 PROTECTION OF WORK AND PROPERTY 15400-08 1. 14 FLASHINGS 15400-09 1. 15 PAINTING 15400-09 go 1. 16 EXCAVATION AND BACKFILL 15400-09 1. 17 CORE DRILLING 15400-09 no 2.01 SLEEVES, HANGERS AND FIXTURE SUPPORTS 15400-10 2.02 PIPE, FITTINGS AND FABRICATION 15400-12 2.03 VALVES 15400-13 "w 2.04 PIPE INSULATION 15400-13 2.05 FLOOR DRAINS AND DECK DRAINS 15400-14 2.06 WALL HYDRANTS 15400-14 go 2.07 CLEANOUTS 15400-15 2.08 PLUMBING FIXTURES 15400-15 2.09 WATER HEATER 15400-17 04 2. 10 VALVE TAGS, CHARTS AND PIPE MARKINGS 15400-17 2.11 ACCESS PANELS 15400-18 3.01 PIPING INSTALLATION 15400-19 3.02 PLUMBING SYSTEMS TESTS 15400-19 3.03 CLEANING AND ADJUSTING 15400-20 3.04 STERILIZATION 15400-21 3.05 INSTRUCTIONS 15400-21 w. SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects D. Furnish and make temporary installation of all pumps, compressors and instruments for the testing. Test pressure shall be held for at least the minimum time periods noted above, or long enough thereafter to prove the system tight that is being tested. Any defects shall be repaired or replaced as directed and the expense shall be paid by the Fire Protection Subcontractor. All soap tested joints shall be washed clean after testing, and all tests water properly drawn off. 3.03 CLEANING AND ADJUSTING A. At the completion of the work, all equipment apparatus and exposed trim for same included in this Section shall be cleaned, and where required, polished ready for use. B. At the completion of the work, all valves and automatic ei control devices shall be adjusted for proper and quiet operation. 3.04 INSTRUCTIONS A. After completion of assembly and installation of all systems and equipment and piping required under this Section of the Specifications, the Owner's supervisory and operating personnel shall be instructed regarding the operation and maintenance of the systems. The instructions shall be given by the Fire Protection Subcontractor and other qualified personnel who are thoroughly familiar with all systems and shall be furnished for a time period as directed by the Architect. ++ END OF PART 3 ++ ++ END OF SECTION 15500 ++ FIRE PROTECTION 15500-16 SMITH COLLEGE - OFFICE OF ADMISSION "' David P. Handlin & Associates, Architects PART 3 - EXECUTION ow 3.01 PIPING INSTALLATION A. All above ground piping shall be installed as closely, as we possible to walls, ceilings, beams, columns, etc. , consistent with proper space allowance for covering and removal of pipes. op B. All piping shall be run approximately as indicated on the Drawings and to avoid conflicts, rigidly supported, 60 aligned and/or graded and arranged without sags, pockets or low spots. Low ends of lines shall be fitted with drain leg tees fitted with drain valves. C. All piping connections to equipment shall be made with flanges or couplings and shall be suitable for the type of system it serves. D. Except where otherwise noted, all piping shall be concealed in walls, ceiling construction, access spaces and chases provided. 3.02 FIRE PROTECTION SYSTEM TESTS A. The Fire Protection system shall be tested by the Fire Protection Subcontractor in the presence of the Owner, Architect or his representative and the Fire Protection MAI Inspector after completion and before concealing any section from view. B. Furnish labor, tools and all materials and do all testing as described herein. C. Each new system shall be pressure tested at pressure Am described herein and in a manner as described herein. Test pressures for each system shall be maintained as long as required by the Architect to determine the ., tightness of the system and/or as long as required to inspect the joints visually or with painted soap solutions. Wherever testing indicates leaks, the leaks shall be repaired in a manner prescribed by the Architect and the test shall be reprocessed until the system is proven tight. 1 . All portions of the fire protection system shall be tested in accordance with N.F.P.A. regulations governing that particular portion of the system. .. FIRE PROTECTION 15500-15 „ SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects �w E. The Fire Protection Subcontractor shall prepare in triplicate a complete listing of each valve, its number and describing its control function. These listings shall be presented to the Architect at the completion of the job. 2. 11 ACCESS PANELS A. This Subcontractor shall furnish access panels for access to all concealed valves and equipment and to all other concealed parts of the sprinkler system that require accessibility for the proper operation and maintenance of the system. B. These panels will be installed by the appropriate Subcontractor concerned with that portion of the building construction to which the access panel will be attached. C. All access panels shall be located and positioned so that the valve or cleanout can be easily reached and the size shall be sufficient for this purpose (min. size 9"x 9") . When access panels are required in corridors, lobby or other habitable areas, they will be located as directed by the Engineer. D. Access panels shall be prime painted with cylinder lock and two keys as manufactured by Inland Steel Products Company, "Milcor", Miami Carey or Walsh-Hannon-Gladwin, Inc. , "Way Loctor", or equal. E. Type shall be as follows: Gypsum Board Surfaces "Milcor Type DW" Masonry Construction "Milcor Type M" ++ END OF PART 2 ++ FIRE PROTECTION 15500-14 SMITH COLLEGE - OFFICE OF ADMISSION so David P. Handlin & Associates, Architects .09 FIRE PROTECTION SYSTEM ACCESSORIES ." A. The Fire Protection Subcontractor shall furnish and install all accessories necessary to fully complete the fire protection system, as specified or implied, which am shall include but not be limited to the following: 1. Supervisory switches, where indicated on the Drawings, type that attaches directly to O.S.& Y. gate valves or butterfly valves. 2. Inspectors test connection. 2. 10 VALVE TAGS, CHARTS AND PIPE MARKINGS A. Furnish and install pipe identification markers on all exposed piping installed under this part of the Specification. Piping above removable suspended ceilings shall be considered exposed as well as piping located in mechanical equipment rooms or spaces. B. Pipe identification markers shall consist of labels or black letters imprinted on color coded background and 1-1/2" color bands. Labels and bands shall indicate the pipe fill and the direction of flow. Pipe identification labels shall be the coiled snap-on type, letters to be 2" high on all pipes 3" diameter and over, letters to be 3/4" high on all pipes under 3" diameter. Pipe „ identification markers shall be applied to the pipe on 15 ' centers and at- each valve, whichever is closer. Color coding for pipe identification markers shall be as follows: LEGEND BACKGROUND Fire Protection Red Pipe identification markers shall be W. H. Brady Co., Seton Co. , or Bell Co. C. Furnish and install stamped or embossed 1-1/2" diameter brass tags or plastic identification plates for each valve, control entity or piece of equipment. These identification plates shall be permanently attached to their identifying equipment or valves with brass hooks or brass link chain. Each chain valve or plug shall be tagged "DRAIN". D. Each brass valve tag shall be lettered for its appropriate service and numbered in consecutive order "SP" for SPRINKLER. FIRE PROTECTION 15500-13 Wo SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin 6 Associates, Architects .05 AIR COMPRESSOR A. Furnish and install one (1) air compressor similar to Reliable Model A, 1-1/2 HP, 115 Volts, 1 Phase, with a capacity of 7.9 cubic feet of free air at 40 PSI. Also include Model B-1 automatic air maintenance device and electric alarm bell. Release valve set to cut in at 25 - PSI and cut out at 35 PSI, dashpot check valve. Viking or Automatic Sprinkler Corp. also acceptable. 2.06 FIRE DEPARTMENT SIAMESE CONNECTION A. Siamese unit shall be similar to Elkhart or Seco. Similar to Elkhart Model No. 166 flush mounted, polished chromium-plated. Unit shall be cast brass with 90 degree inverted angle body, independent drop clappers complete with caps and chains. Plate lettered "AUTO-SPRINKLER", 2-1/2" x 2-1/2" x 4" connections which shall match local fire department standards. .07 SPRINKLER HEADS A. Sprinkler heads generally shall be of the wet automatic closed type and of temperature rating to satisfy ,s. immediate conditions. .B. Heads located below finished ceilings, except where noted W otherwise shall be ornamental pendant type, semi-recessed, factory chromium-plated escutcheons. Grinnell or approved equal. All heads installed in 2' x 2 ' ceiling tiles shall be placed in the center of the tile. Use swing joints if necessary to insure center of the installation. C. Heads on exposed piping or in concealed spaces may be upright or pendant type with rough brass finish. D. Sidewall heads shall be of the extended coverage type, chromium-plated with chromium-plated escutcheons and have U.L. approval for extended coverage. Gem or approved equal. 2.08 SPARE HEADS A. Spare heads shall be furnished in a quantity as required by Underwriters or as otherwise directed. Heads shall be packed in a suitable container and shall be representative of, and in proportion to, the number of each type and temperature rating heads installed, in addition, one sprinkler-head wrench shall be provided for each type of head. FIRE PROTECTION 15500-12 SMITH COLLEGE - OFFICE OF ADMISSION -o David P. Handlin & Associates, Architects Piping shall have threaded joints. Piping between sm siamese connections and related check valves and drain and test piping subject to alternate wetting and drying, shall be galvanized steel. Im 2. Fabrication: Threaded fittings shall have an approved compound applied to male threads only and jointed watertight. .. 2.03 VALVES A. Gate valves 2" and smaller shall be all bronze with rising stem and threaded ends, similar to Jenkins 275-U. B. Gate valves larger than 2" shall be iron body, bronze mounted, outside screw and yoke type, threaded or flanged end type, similar to Jenkins 824A, 825A. C. Where permissible, valves 3" and larger may be butterfly ." type, iron body, wafer closure with crank handle, indicator and supervisory switch, similar to Grinnell 12427-151. .. D. Check valves 2" and smaller shall be all bronze with threaded ends, swing check type. E. Check valves larger than 2" shall be iron body, bronze mounted, swing check type, threaded or flanged end type similar to Jenkins 629. F. Install automatic ball drip connections to check valve on branch to siamese connection. G. All valves shall be of the same manufacturer and be UL approved, Jenkins, Kennedy or Grinnell. .► 2.04 DRY PIPE VALVE A. Furnish dry pipe valve, 4" size shall be approved type for a dry system, complete with accelerator, water operating gong, alarm switch, electric bell, drain valve, pressure gauges and other required trimmings and test connections. Water gong shall be located on outside of building, with head and identification tag, supply pipe from gong into building shall be I.P.S. brass or copper. Manufacturer's: Reliable, Viking, or Automatic Fire Protection Corp. FIRE PROTECTION 15500-11 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects PART 2 - PRODUCTS 2.01 SLEEVES, HANGERS, INSERTS AND EQUIPMENT SUPPORTS A. Pipe sleeves, pipe hangers and equipment supports for all piping shall be furnished and set by the Fire Protection Subcontractor and this Subcontractor shall be responsible for their proper and permanent location. B. Pipe Sleeves shall be cast iron or steel and shall be installed and properly secured at all points where pipes are to pass through building walls and floors. Sleeves shall be of sufficient diameter to provide approximately 1/4" clearance around pipe. C. All pipe openings through floors and walls shall be sealed. Sleeves shall be packed tight around piping with glass fiber rope and sealed with 1" of fire resistant caulking. Sleeves in floors shall extend 1/2" above floor and made watertight. Where popes pass through walls, the sleeves shall be full length through the wall and cut flush with finished surfaces on both sides. Provide chromium plated escutcheons held in place with set screws around all sleeves through floors and wall where sleeves Or are exposed. D. All sleeves through exterior building walls shall be properly sealed watertight and shall be flexible. E. Hangers: All piping shall be rigidly supported from the building structure by means of approved hangers, inserts, and supports. Pipes shall be supported to maintain required grading and pitching of lines to prevent vibration and to secure piping in place. F. All horizontal piping shall be hung with approved adjustable, malleable iron pipe hangers, unless otherwise specified and spaced according to code requirements and manufacturer's recommendations for each type and size of piping. G. Hangers for piping of sizes 4 inches and smaller shall be Carpenter Patterson Type No. lA Band, or approved equal, black steel and hanger rods with machine threads; for piping of sizes larger than 4 inches shall be the adjustable clevis hanger type, malleable iron, with extension rod to structure. Hanger rods shall be secured to concrete floor slabs by means of approved type inserts wherever possible. FIRE PROTECTION 15500-9 SMITH COLLEGE - OFFICE OF ADMISSION -r David P. Handlin i Associates, Architects . 15 CORE DRILLING A. The Fire Protection Subcontractor shall core drill openings through floors, walls and roofs as required to accommodate new fire protection work. B. Cut all masonary and concrete with an approved diamond blade concrete saw in a neat straight direction, perpendicular to the plane of the wall or floor. C. Use a core drilling process which produces clean, sharp edges and the minimum hole size which will accommodate pipe with insulation, where applicable. D. Any spalling or cracking of adjacent concrete or masonry shall be patched to by the Fire Protection Subcontractor to the satisfaction of the Owner. E. Prior to any drilling, obtain permission from the General Contractor for each exact coring location. ++ END OF PART 1 ++ FIRE PROTECTION 15500-8 r,, SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects ! 2. One set blackline prints to the Fire Protection Engineer. 3. One set blackline prints retained by the Architect. 1. 11 JURISDICTIONAL DISPUTES A. In order to avoid any jurisdictional disputes and work stoppages that could arise during the installation of the work shown on the Drawings or as specified herein, the ON Fire Protection Subcontractor shall be held responsible to do any sub-letting work that might be required to furnish and install the work shown or specified herein. r 1.12 CARTING, HANDLING AND CLEAN-UP A. The Fire Protection Subcontractor shall do all carting, handling, hoisting, etc. , for his material and equipment at his expense in a safe and satisfactory manner. Any damage resulting therefrom shall be repaired or paid for by this Subcontractor to the satisfaction of the General Contractor. B. Clean-up requirements as specified under SECTION 017000*- PROJECT CLOSEOUT will be strictly enforced. 1.13 PROTECTION OF WORK AND PROPERTY �w A. The Fire Protection Subcontractor shall be responsible for the care and protection of all work included in this Section of the Specifications and Drawings until it has been tested and accepted. B. After delivery and before, during and after installation, the Fire Protection Subcontractor shall protect all equipment and materials from injury or damage of all causes, as well as from theft. Such loss or damage shall be made good without expense to the Owner. 1.14 PAINTING A. Wherever factory finishes of paint, lacquer, baked enamel, etc. , have been damaged or deteriorated during construction, use factory furnished painting materials and refinish or touch-up the damage or deterioration applied by skilled workmen experienced in painting and finishing, to the satisfaction of the Architect. FIRE PROTECTION 15500-7 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin S Associates, Architects 2. His daily progress, by coloring in the various piping, apparatus, and associated appurtenances exactly as they are erected. This process shall incorporate both the changes noted above and all other deviations from the original drawings, whether resulting from job conditions or from any other cause. Principal dimensions of concealed work shall be recorded. B. These marked-up and colored-in-prints will be used as guides for determining the progress of the work installed. They will be inspected monthly by the Fire Protection Engineer and they shall be corrected immediately if found either inaccurate or incomplete. C. This procedure is mandatory; as stipulated in DIVISION C, the Architect will not approve any requisition for payment submitted by this Subcontractor until the Fire • Protection Engineer and the Architect are satisfied that this complete procedure has been complied with and is up to date. D. At the completion of the job, these prints shall be submitted to the Fire Protection Engineer, through the Architect for final inspection and comment. "•' E. The prints will be returned to the Fire Protection Subcontractor with appropriate comments and recommendations, and then this Subcontractor shall at his own expense arrange to have an Engineer acceptable to the Fire Protection Engineer, make the revisions, in a manner approved by the Fire Protection Engineer, on wash-off mylar transparencies of the original contract drawings. F. When this procedure has been accomplished to the satisfaction of the Fire Protection Engineer and the Architect, the Plumbing Subcontractor shall furnish to the Architect the following: 1. The marked up job record blackline prints. 2 . The reproducible revised transparencies entitled "Record Drawings% 3. Three complete sets of blackline prints of the *" "Record Drawings". G. Distribution by the Architect shall be: .. 1. The reproducibles and one set blackline prints to the Owner. FIRE PROTECTION 15500-6 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects C. The Fire Protection System shall be delivered to the Owner complete and in perfect working order; tested in full accordance with the Plans and Specifications. ,.. 1.09 SHOP DRAWINGS A. Submit complete Shop Drawings in accordance with the .s. provisions of SECTION 01300, SUBMITTALS B. Shop Drawings shall include information to prove that the requirements of the Specifications and Drawings are complied with and include installation instructions and wiring diagrams. Shop Drawings submittals shall include but not be limited to the following: 1. Valves. 2. Pipe Hangers. 3. Sprinkler Heads. 4. Piping, Fittings and Couplings. 5. Tamper Switches. 6. Dry Pipe Valve and Air Compressor. 7. Fire Department Siamese Connection. 8. Fire protection working drawings, stamped by the Owners insurer and the local Fire Department. 1. 10 RECORD DRAWINGS A. The Fire Protection Subcontractor shall maintain at the job at all times a complete and separate set of blackline prints of the Plumbing Drawings of this trade, on which he shall mark clearly, neatly, accurately and promptly as on the work progresses: 1. Changes to be made, whether resulting from formal MW change orders or other instructions issued by the Architect. FIRE PROTECTION 15500-5 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects .06 CODES. PERMITS AND FEES am A. All fire protection work shall be installed in accordance with the NFPA Code, the Owner's Insurance Company, and any applicable regulations of the Town of Northampton, No MA. as they apply to the installation. Such laws and ordinances are to be considered a part of this Specification. on B. The above Fire Protection Ordinances and Building Laws shall be considered as minimum requirements for the fire .R protection installation. Where specifications call for work to be done in excess of the above requirements, the Specifications shall be followed. .o C. The Fire Protection Subcontractor shall file all required notices and plans and shall secure and pay for all necessary permits for his work. „m, D. If any portion of the Fire Protection Plans or Specifications conflict with any rules and regulations with regard to type of materials, equipment, or fixtures to be used, the Fire Protection Subcontractor shall bring it to the Architect's attention. Otherwise, the cost of all work necessary to make the installation comply with the above rules and regulations shall be paid for by the Fire Protection Subcontractor without additional expense to the Owner. 1.07 GUARANTEE A. Furnish to Owner a written guarantee of the General Contractor and this Subcontractor, jointly and severally, against any defects in materials and workmanship in work of this Section for a period of one year from date of �. substantial completion of the project. Guarantee shall state that defective work shall be remedied without cost to Owner during the guarantee period promptly after written notice of such defects by the Owner, and shall be binding upon both the General Contractor and this Subcontractor. 1.08 WORKMANSHIP, MATERIALS AND DELIVERY A. All work of a special nature shall be performed by skilled and qualified workmen who can present credentials showing experience in said trade. B. The Fire Protection Subcontractor shall use only new �. materials free from defects and of good quality. He shall see that all his materials are delivered at the building when required so as to carry on the work in the most effective manner. FIRE PROTECTION 15500-4 on SMITH COLLEGE — OFFICE OF ADMISSION David P. Handlin & Associates, Architects 40 B. Due to the small scale of the Drawings, it is not possible to indicate all offsets, fitting, valves, etc. , which may be required to complete the work. The Fire Protection Subcontractor shall study the drawings showing the structural and finished design of the buildings and shall furnish and install all fittings, etc. , to fully complete the Fire Protection Work. C. Before submitting prices, thoroughly examine all the Contract Documents and the site with special emphasis on .� all the adjoining work upon which this work depends. D. If for any reason the Fire Protection Subcontractor finds that the work cannot be done in any area in accordance with the Plans and Specifications he must immediately notify the Architect in writing of his findings. If for any reason the Fire Protection Subcontractor fails to do this it shall become his responsibility and he shall bear any and all costs for any work involved, at no extra cost to the Owner. .05 INFORMATION A. The Fire Protection Subcontractor shall obtain detailed information from the manufacturers of apparatus which he is to furnish and/or install as to the proper method of installation and connections. He shall obtain all ,., information from the General Contractor and the other contractors which may be necessary to facilitate his work and the completion'of the project. B. He shall keep himself fully informed as to the shape, size and position of all openings required for his apparatus and shall give full information to other contractors as required sufficiently in advance of the work so that all openings may be built on schedule. The Fire Protection Subcontractor shall also furnish all sleeves and supports hereinafter specified, shown or implied and shall set same in place. C. In the case of failure on the part of the Fire Protection Subcontractor to give proper information as noted above, he will be required to do his own cutting and patching to the satisfaction of the General Contractor and without additional expense to the Owner. FIRE PROTECTION 15500-3 SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects 2. Furnishing and setting of all pipe sleeves in new construction. 3. Provide working drawings showing all sprinklers and piping, with drawings stamped and approved by the Owner's insurer and the local fire department. 4 . All core drilling of existing or new construction as ..� required to install new fire protection work. C. Items to be furnished only: Furnish the following items for installation by the designated Sections: 1. Access Panels - Section 09250. ®. 1.03 RELATED WORK IN OTHER SECTIONS A. The following is not included in this Section of the a Specification and is work to be performed under other Sections at no expense to the Fire Protection Subcontractor. 1. SECTION 01120, ALTERATIONS 2. Cutting and Patching (except core drilling for fire protection work) . 3. Painting. .� 4. All required concrete work. 5. All electrical connections to fire protection equipment. 1.04 INTENT A. It is the intention of the Drawings and this Specification to show and specify a complete fire protection system. Anything that is not shown on the Drawings but is mentioned in the Specifications, or vice-versa or anything not expressly set forth in either, but which is reasonably implied, shall be furnished and performed as though specifically shown and mentioned in both. FIRE PROTECTION 15500-2 no SMITH COLLEGE - OFFICE OF ADMISSION David P. Handlin & Associates, Architects SECTION 15300 FIRE PROTECTION PART 1 - GENERAL 1.01 REFERENCE +.A A. Requirements of General Conditions of the Contract, Supplementary Conditions and Division 1, General Requirements are hereby made a part of this Section as fully as if repeated herein. B. Refer to the Drawings for further definition of location, ^' extent and details of the work described herein. C. Cooperate and coordinate with all other trades in executing the work described in this Section. D. Where referred to, Standard Specifications of technical societies, manufacturer's associations and Federal Agencies shall include all amendments current as of the date of issue of these Specifications. 1.02 SCOPE OF WORK A. The scope of the work under this Section, without limiting the generality thereof, consists of furnishing all labor, material, equipment, scaffolding, power, tools and rigging, except as otherwise specified and performing all work as necessary to fully complete the Fire Protection Work shown on the drawings and as specified herein. B. Work Included: The Fire Protection Work will include but not be limited to the following: 1. A complete dry type sprinkler fire protection system throughout the renovated areas and addition connecting to all equipment making up the fire protection system. The fire protection work shall extend and connect to the exterior fire protection service as indicated. FIRE PROTECTION 15500-1 pill SECTION 15500 FIRE PROTECTION PARA. TITLE PAGE 1.01 REFERENCE 15500-01 1.02 SCOPE OF WORK 15500-01 1.03 RELATED WORK IN OTHER SECTIONS 15500-02 1.04 INTENT 15500-02 1.05 INFORMATION 15500-03 1.06 CODES PERMITS AND FEES 15500-04 1.07 GUARANTEE 15500-04 1.08 WORKMANSHIP, MATERIALS AND DELIVERY 15500-04 1.09 SHOP DRAWINGS 15500-05 1. 10 RECORD DRAWINGS 15500-05 1. 11 JURISDICTIONAL DISPUTES 15500-07 1. 12 CARTING, HANDLING AND CLEAN-UP 15500-07 . 1.13 PROTECTION OF WORK AND PROPERTY 15500-07 1.14 PAINTING 15500-07 1.15 CORE DRILLING 15500-08 2.01 SLEEVES, HANGERS, INSERTS & EQUIP. SUPPORTS 15500-09 2.02 PIPE, FITTINGS AND FABRICATION 15500-10 2.03 VALVES 15500-11 2.04 DRY PIPE VALVE 15500-11 2.05 AIR COMPRESSOR 15500-12 2.06 FIRE DEPARTMENT SIAMESE CONNECTION 15500-12 2.07 SPRINKLER HEADS 15500-12 2.08 SPARE HEADS 15500-12 2.09 FIRE PROTECTION SYSTEM ACCESSORIES 15500-13 w 2.10 VALVE TAGS, CHARTS AND PIPE MARKINGS 15500-13 2.11 ACCESS PANELS 15500-14 3.01 PIPING INSTALLATION 15500-15 3.02 FIRE PROTECTION SYSTEM TESTS 15500-15 3.03 CLEANING AND ADJUSTING 15500-16 3.04 INSTRUCTIONS 15500-16 ,w. ®w SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 .m David P. Handlin and Associates,Architects plumb and accurately located in hoistway. Anchor securely. Make welded connections wherever am Possible for connections which do not need future adjustment, replacement or routine maintenance. A. Coordination: Coordinate with other work to avoid project delays,to ensure dimensional coordination ow of the work,to ensure proper power characteristics, and to properly prepare for elevator cab communications. B. Hydraulic Jack: Install hydraulic jack casing with waterproof seals at pit floor. Install plunger/cylinder 4W unit plumb and accurately located in hoistway;anchor securely to prevent displacement. C. Isolation: Mount all equipment with sound and vibration isolating mounts to prevent transmission of .w noise to structure and cab. Provide isolation fittings in hydraulic lines. D. Hoistway Entrances: Place hoistway entrances prior to hoistway front wall to the greatest extent AM possible. Accurately align hoistway entrances with elevator guide rails and reduce clearances to minimum, safe,workable dimensions. E. Sills: Anchor and grout sills with non-staining, ran-shrink grout. Set sills accurately aligned and .A slightly above finished floors. F. Adjust operating parts to work easily, smoothly,and correctly. ow END OF SECTION No 4W W 4W no 1W aR 14240-2 ow No SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects me SECTION 14240 go HYDRAULIC ELEVATOR PART 1 -GENERAL am 1.1 DESCRIPTION OF WORK: This section includes,without limitation, a complete,fully functional,code complying, barrier-free passenger elevator system. No 1.2 RELATED WORK: Without limitation, related work includes: A. 05500-Miscellaneous Metals; elevator pit ladders, elevator sill sub-angles. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop drawings. C. Samples,fully finished and at least 6 inches square showing complete range of finish. PART 2-PRODUCTS 2.1 ELEVATOR: Provide complete,fully functional,code complying,barrier-free passenger elevator system having the following features and characteristics. Provide U.S. Elevator"Presidential 3000" Dover"Oildraulic 3000",or Architect approved equal. A. Hal lantern face plate #4 satin stainless steel. B. Hall call buttons face plate #4 satin stainless steel. C. Hall car position indicators Not required. D. Hoistway entrance doors Baked enamel with custom color. E. Hoistway entrance frames Baked enamel with custom color. F. Car front wall Plastic laminate to match Architect's sample. G. Car entrance doors and frames Baked enamel with custom color. • H. Car base #4 satin stainless steel. 1. Car handrail Wood with#4 satin stainless steel brackets. J. Car control panels #4 satin stainless steel. K. Carwak Plastic laminate to match Architect's sample. L. Car floor Prepare subfloor to receive carpet. M. Car ceiling Suspended aluminum eggcrate baffle. N. Car lighting Warm white fluorescent strips. ! ' O. Capacity: 3,000 pounds minimum. P. Speed: 100 fpm up and down minimum. Q. Height Under Finished Car Ceiling: T-4". R. Type of Entrances: Side opening, two speed. S. Hoistway and Car Entrance Size: T-6"wide x T-0"high. T. Car Operating Panels: One at front. U. Location of Entrances: Front V. Stops: 3. W. Approximate Travel Distance: 19 feet. X. Operation and Control: Selective Collective. * Y. Protective Blankets: Provide for all cab wall surfaces complete with stainless steel mounting hooks and blanket grommets. PART 3-EXECUTION 3.1 INSTALLATION:Strictly comply with manufacturer's instructions and recommendations. Install work 14240- 1 «w SMITH COLLEGE,OFFICE OF ADMISSION 02/22193 David P. Handlin and Associates,Architects 4W SECTION 12690 ENTRANCE MATS PART 1 -GENERAL 40 1.1 DESCRIPTION OF WORK: This section includes,without limitation: on A. Synthetic fiber entrance mats with recessed metal frames. 1.2 RELATED WORK: Without limitation, related work includes: A. 03300 - Concrete B. 06100- Rough Carpentry 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. B. Shop drawings. C. Samples,fully finished and at least 6 inches square showing complete range of finish. PART 2-PRODUCTS 2.1 POLYPROPYLENE"BERBER" ENTRANCE MAT: Provide 100%solution dyed polypropylene synthetic cocoa fiber permanently bonded to non-slip polyvinyl chloride backing for dimensional stability and improved shedding resistance. Provide color as selected by Architect from manufacturer's complete range of options. Provide one of the following: A. Pawling Corporation, Pawling, NY, "Coral Plus". B. Parkwood New England, Medford, MA, "Parkwood Entry Carpet, Berber Design". C. Mats, Inc., Braintree, MA.,"Berber Mat". 2.2 RECESSED FRAME: Extruded stainless steel angle. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Coordinate frame installation with concrete work. Coordinate top of entrance mat elevation with frame and floor elevations to provide proper foot cleaning,to ensure that mat is slightly higher than frame, and to '® avoid all possibility of tripping hazard. A. Do rat i nstail entrance mat until immediately before Owners final acceptance of the Project. Place entrance mat with"grain"perpendicular to main traff ic for best foot cleaning. Clean and prepare subfloors as needed to ensure good bond and proper installation. Apply adhesive with notched trowel in compliance with coverage rates printed on container. Provide seams between strips or tiles to match seams within strips or tile so that individual strips or tiles are invisible. END OF SECTION 12690- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 12390 PREMANUFACTURED CABINETS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Premanufactured plastic laminate casework at kitchenette. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry; concealed wood blocking. B. 06400-Custom Casework 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop drawings. C. Samples at least 6 inches square and fully finished showing complete range of finish. 1.4 REFERENCE STANDARDS: Comply with Architectural Woodwork Institute"Architectural Woodwork Quality Standards". PART 2-PRODUCTS 2.1 CASEWORK: Provide Imperia or Lewis Les-Care cabinets with flush doors and drawers with matching laminate edges. Provide white plastic laminate exteriors and white melamine interiors. Provide barrier-free wire loop pulls. Match elevations and layout shown. Provide matching filler and scribe strips. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with AWI Premium Grade standards. Provide work to sizes,shapes, and profiles indicated. A. Casework installation: Find high and low points of ceilings and floors and layout truly plumb and level guide lines before beginning work. Securely anchor cabinets plumb, level, and straight. Anchor cabinets to concealed wood blocking and framing with at least 3"long Phillips head screws. Connect adjacent cabinets to each other with connector bolts. 1. Leveling: Shim and level as necessary to ensure that doors swing freely and drawers slide • correctly. Align sight lines at doors and drawers to within a tolerance of±1/32 inch. 2. Filter Strips: Provide matching wood filter strips as necessary to make a complete installation without gaps between cabinets and adjacent construction. Scribe matching trim moldings to fit precisely. 3. Hardware: Complete hardware installation to the extent not completed in shop and adjust all hardware to work perfectly. END OF SECTION *■ 12390- 1 W SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects an SECTION 11450 am APPLIANCES PART 1 -GENERAL ON 1.1 DESCRIPTION OF WORK: This section includes,without limitation: no A. Providing appliances as scheduled. 1.2 RELATED WORK: Without limitation, related work includes: A. Division 15-Mechanical; plumbing and venting for appliances. B. Division 16-Electrical; power and wiring for appliances. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. 1.4 WARRANTY: Provide manufacturer's written warranty covering defects in materials or workmanship for one year from Date of Substantial Completion. PART 2-PRODUCTS 2.1 APPLIANCES: Provide as scheduled: A. Undercounter Refrigerator: General Electric TA6SL with face trim kit. w 2.2 CUSTOM FACE SHEET: Provide extruded aluminum or stainless steel edge trim at entire perimeter of appliance front to accommodate plastic laminate or veneer face insert so that front of appliance matches adjacent casework. Provide trim with hairline tight miter joints at corners. Make one edge of trim easily removable and replaceable to permit insertion of face sheet. PART 3-EXECUTION 3.1 INSTALLATION:Strictly comply with manufacturer's instructions and recommendations. A. Built-In Appliances: Securely anchor built-in appliances to cabinets and countertops with concealed fasteners. Take special care to ensure that manufacturer's recommended clearances are maintained and that all rough openings and unfinished edges are concealed. B. Freestanding Appliances: Place units after adjacent finish work is complete and accepted. Maintain manufacturer's recommended clearances. C. Mechanical and Electrical Connections: Refer to Divisions 15 and 16 for plumbing,venting and electrical requirements. Coordinate connection of appliances to water supply piping,drain lines, power supplies,vent ducts and all other mechanical and electrical work. END OF SECTION "" 11450-1 40 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 00 SECTION 10800 "m TOILET ACCESSORIES PART 1 -GENERAL 40 1.1 DESCRIPTION OF WORK: This section includes,without limitation: as A. Providing commercial quality toilet accessories as scheduled. B. Unloading, handling, storing, and installing accessories furnished by Owner. 1.2 RELATED WORK: Without limitation, related work includes: Jft A. 06100 - Rough Carpentry; blocking. mw 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. we B. Installation diagrams showing locations of concealed blocking. PART 2-PRODUCTS 2.1 TOILET ACCESSORIES: Provide#4 satin stainless steel accessories as scheduled: Item Model Item ma& Number Descrill6op TDWR Bobrick B-3904 Towel Dispenser/Waste Receptacle SNV Bobrick B-3500 Sanitary Napkin Vendor SNDR Bobrick B-354 Sanitary Napkin Disposal, Recessed TTDS Bobrick B-2740.60 Toilet Tissue Dispenser,Surface GB Bobrick B-5507.99 Grab Bars with configuration shown SDW Bobrick B-40 Liquid Soap Dispenser,Wall JUL) Bobrick B-224 30 Inch Janitor's Utility Unit FM Bobrick B-290 Framed Mirror[sizes as shown] PART 3-EXECUTION 3.1 INSTALLATION: Install truly plumb and level at heights and locations indicated,or if not indicated, at heights and locations approved by Architect. Adjust operating parts to work easily, smoothly, and correctly. A. Barrier Free Requirements: Where indicated to be handicapped accessible, install toilet accessories at locations and heights required by authorities having jurisdiction for barrier-free accessibility as approved by Architect. Install grab bars to support at least a 250 pound load acting in any direction and in a manner to cause greatest stress without damage or noticeable deflection. END OF SECTION • 10800- 1 ow on SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects ear SECTION 10520 FIRE EXTINGUISHERS AND CABINETS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Fully filled and tagged fire extinguishers. B. Fire extinguisher cabinets. 1.2 RELATED WORK: Without limitation, related work includes: A. 06700-Finish Hardware; building standard hardware finish. B. 09900- Painting; field painting cabinet exteriors. « C. Division 15-Mechanical; fixed fire protection systems,standpipes,valves and hose cabinets. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. PART 2-PRODUCTS 2.1 FIRE EXTINGUISHERS: Provide filled and tagged, 10 pound capacity mufti-purpose dry chemical, UL rated 4-A,60-BC, in red enameled steel cylinders. 2.2 FIRE EXTINGUISHER CABINETS: Provide one of the following with factory applied white primer suitable for field painting to match adjacent walls: A. J.L. Industries, Embassy Series. B. Larsen Manufacturing Co.,Occult Series. C. Muckel Manufacturing Co., 100 Series. ,w PART 3-EXECUTION �. 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Securely anchor cabinets and brackets truly plumb and level at heights indicated or, if not indicated, at heights acceptable to authorities having jurisdiction and the Architect. 9 exact locations are not indicated, locate where field directed by Architect. Place extinguishers in cabinets and brackets ready for immediate use. END OF SECTION �e 10520- 1 0 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects o SECTION 10440 am SIGNAGE PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Exterior sign at main entrance. B. Toilet room door signs. C. Elevator call button signs. 1.2 RELATED WORK: Without limitation, related work includes: A. Division 16-Electrical; exit signs. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop drawings for all signage. PART 2-PRODUCTS 2.1 BARRIER-FREE INTERIOR PANEL SIGNS: Provide Andco"Acrylic Plaque Raised Acrylic Letter" series with square comers,center copy position,adhesive tape mounting,8 inch by 8 inch size, and colors selcted by Architect. A. Toilet Rooms: Provide graphic image of"men", "women"and"wheelchair". 2.2 ELEVATOR CALL BUTTON SIGN: Engrave call button face plate with code required wording prohibiting use of elevators in case of fire. 2.3 EXTERIOR ENTRANCE SIGN: Provide 12 inch by 18 inch, minimum 1/8 inch thick,engraved brass plaque with forest green paint in lettering. Copy shall read"Smith College Office of Admission"on two Ines in Times Roman initial capitals. PART 3-EXECUTION 3.1 INSTALLATION: A. Adhere toilet room signs to toilet room doors at centerline and at height to comply with ADA barrier- free requirements. B. Screw engraved elevator call button face plates over fixture box. C. Mechanically mount entrance sign with pan head brass screw each comer. Place sign at location approved by Architect on wall at strike edge of door. END OF SECTION 10440- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handiin and Associates,Architects D. PAINT SYSTEM 4: INTERIOR FERROUS METAL (Satin Alkyd System) Coat 1: Moore's Ironclad Retardo Inhibitive Primer Coat 2: Moore's Satin Impervo Enamel �. Coat 3: Same as coat 2. E. PAINT SYSTEM 5: EXTERIOR FERROUS METAL (Acrylic Urethane System) Coat 1: Tnemec 90-97 Zinc-Rich Primer at 3.0 mils DFT Coat 2: Tnemec Series 69 High Build Epoxoline II at 3.0 mils DFT Coat 3: Tnemec Series Series 75 Endura-Shield at 3.0 mils DFT F. PAINT SYSTEM 7: EXTERIOR WOOD SIDING-PAINTED(Eggshell Alkyd System) Coat 1: Moorwhite Primer Coat 2: Moore's Eggshell Finish House Paint Coat 3: Same as coat 2. G. PAINT SYSTEM 6: EXTERIOR WOOD DOORS,WINDOWS,SHUTTERS,AND TRIM-PAINTED �^ (Gloss Alkyd Enamel System) Coat 1: Moorwhite Primer Coat 2: Moore's Impervo High Gloss Enamel Coat 3: Same as coat 2. 2.2 COLORS: Custom ma colors as directed by Architect. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations for both application of paint and preparation of surfaces before paining. Provide uniform final finishes,free from runs,color variation, and other imperfections. A. Remove hardware,fixtures,accessories, and other work or provide effective protection to insure that such work is not painted or splattered. Reinstall removed items when painting is complete. B. Apply paint with brushes or rollers. Spray painting is not acceptable, except for variegated paint. C. Apply at least the number of coats specified and apply additional coats as necessary to eliminate show-through and bleed-through,and to provide uniform final appearance approved by Architect. .» D. Finish behind all removable items. Finish inside duds and grilles when these areas are visible. Paint diffusers and grilles to match adjacent surfaces. E. When repainting existing surfaces,thoroughly prepare substrates. Remove all loose existing coatings. Wash, and clean substrates in compliance with paint manufacturer's recommendations. Ensure excellent bond and uniform final finish. END OF SECTION 09900-2 """ ON SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 4 SECTION 09900 PAINTING PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation, painting and finishing all visible surfaces within the work limits,both new and existing, except the following: A. Finished ornamental metal surfaces and hardware. B. Surfaces concealed from view, except for wood backpriming which is required. C. Finished floors and base. D. Sprinkler heads. E. Electrical outlets, switches, and cover plates. F. Light fixtures and bulbs. 1.2 SPECIAL ITEMS TO BE PAINTED: This list shall not be interpreted to limit the scope of painting work. The intent is to emphasize certain painting work. A. Paint all HVAC diffusers and grilles located in painted surfaces. B. Back prime millwork and woodwork before installation. C. Paint all electrical panels and cabinets, except those located in dedicated mechanical rooms. D. Repaint all existing painted surfaces. 1.3 RELATED WORK: The extent of painting work cannot be understood without a thorough review of all specification sections and Contract drawings. Some work of the Contract is specified to be shop primed and some work is specified to be fully factory finished. 1.4 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Precise, reproducible color formulas for all colors used. PART 2-PRODUCTS 40 2.1 PAINT PRODUCTS: Provide paint systems and products as scheduled or as otherwise approved by Architect. Provide products of Benjamin Moore or Architect approved equal. ow A. PAINT SYSTEM 1: INTERIOR WOOD-PAINTED (Satin Alkyd System) Coat 1: Moore's Pigmented Sanding Sealer Coat 2: Moore's Satin Impervo Enamel Coat 3: Same as coat 2. oft Note: Sand between every coat with successively finer sand paper ending with 320 grit. B. PAINT SYSTEM 2: INTERIOR DRYWALL (Pearl Sheen Latex System) 4 Coat 1: Moore's Latex Quick Dry Prime Seal or Latex Enamel Underbody Coat 2: Moore's Regal AquaPearl Coat 3: Same as coat 2. Note: Provide Moore's latex flat finish on ceilings. C. PAINT SYSTEM 3: INTERIOR DRYWALL IN TOILET ROOMS (Semi-gloss Latex System) Coat 1: Moore's Latex Quick Dry Prime Seal or Latex Enamel Underbody Coat 2: Moore's Regal AquaGlo Coat 3: Same as coat 2. Note: Provide Moore's latex flat finish on ceilings. '" 09900- 1 MW SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects ow 1. Adhere Cushion to Subtloor: Fold back cushion and apply adhesive uniformly to achieve 100 percent coverage but,for indoor air quality,limit quantity of adhesive used to minimum quantity .W necessary for proper installation. Comply with cushion and adhesive manufacturer's recommended adhesive spreading rates. Use new or reconditioned trowels since trowel notches wear down. Allow adhesive to dry in compliance with adhesive manufacturer's instructions and recommendations. Lay down padding and adjust to fit correctly as trimmed. Ensure that cushion is flat and free of bumps and am wrinkles. Ensure that seams in cushion are flush and tightly butted. 2. Adhere Carpet To Cushion: Layout carpet perpendicular to cushion direction and cut to fit up space and obstructions. Cut seams along a single row of carpet tufting and ensure that seams fit properly. Fold back carpet and apply adhesive uniformly to achieve 100 percent coverage. Comply with carpet and adhesive manufacturer's recommended adhesive spreading rates. Use new or N, reconditioned trowels since trowel notches wear down. Unless otherwise recommended by adhesive manufacturer, lay down carpet into wet adhesive and adjust carpet to fit correctly as trimmed before adhesive sets. Ensure that carpet is fiat and free of bumps and wrinkles. 3. Seams: Precut seams as specified above before laying carpet into adhesive. Provide 3 inch wide seam tape at seams. Apply seam adhesive to seams and cut carpet edges. Make seams flush and tightly butted using knee kicker or other effective technique. Press seams down and ensure that seaming adhesive fills up the line so the upper surface of carpet is fully adhered. 4. Roiling: Roll entire carpet area slowly and thoroughly in both directions with a 150 pound roller to .. remove air pockets and to ensure good contact and bond. Roll entire area a second time in both directions to ensure elimination of air pockets and good contact an bond. B. Stairs: Mechanically fasten and adhere resilient nosings to stairs prior to carpet installation. Fully .� adhere carpet over all stair surfaces including treads and risers. To the greatest extent possible, anchor tread carpet with fully concealed supplementary fasteners[tacks or power set staples]. Eliminate all tripping and slipping hazards. END OF SECTION 09680-2 '" on SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 4 SECTION 09680 an CARPET PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Glued down carpet over cushion/pad. B. Resilient edge strip. C. Substrate preparation. 1.2 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Samples at least 18 inches by 27 inches for carpet and 12 inch long edge strips. 1.3 REFERENCE STANDARDS: Comply with Carpet and Rug Institute"Carpet Specifier's Handbook". PART 2-PRODUCTS 2.1 CARPET: Lees Commercial Carpet"East Pointe"as selected by Architect from manufacturer's complete range of colors. 2.2 CUSHION: Provide 30 ounces per square yard,Class I fire-rated"Long Life 11", No-Muv Corporation, Inc., Jacksonville, FL., 800-227-7237. 2.3 INSTALLATION MATERIALS: Provide hot melt seaming cement recommended by carpet manufacturer. Provide latex leveling filling compound that is compatible with adhesives used. Provide resilient edge strips with color and profile selected by Architect from industry available choices. A. Double Glued Carpet Over Cushion Applications: Provide releasable adhesive between cushion and subfloor to permit removal of carpet and cushion assembly. Provide permanent, non-releasable adhesive between carpet and cushion to help carpet and cushion to work together as a single unit 4W PART 3-EXECUTION 3.1 PREPARATION: Check substrates and ensure that moisture content is within limits recommended by ON manufacturers. Carefully check and adjust environmental conditions. Clean subfloors thoroughly to remove all dust,grease, excess alkalinity, and all other foreign substances immediately before installation of flooring. Repair minor holes,cracks and depressions using leveling compound. Sand ridges and high spots level. Precondition and acclimatize carpet in installation areas for at least 24 hours before installation. 3.2 INSTALLATION: Maintain uniform and consistent dye lot and color throughout the work for each color and type of carpet used. Install carpet tight against columns,walls,fixed closed base cabinets, and other fixed items. Trim mill edges to be seamed with very sharp tools. Seal all cut edges with seam sealer to prevent edge delamination and fiber loss. Provide edge guards at all exposed edges and bind all cut edges not protected by edge guards. A. Glued-Down installation Over Adhered Cushion: Fit cushion to spaces before applying adhesive. Roil out cushion perpendicular to carpet direction so cushion and carpet seams are at right angles. Use largest cushion pieces possible and minimize the use of small cushion pieces. Install cushion with correct side down as recommended by cushion manufacturer. +®+ 09680- 1 Am SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 1. Chemically Welded Seams: Cut,fit,and chemically weld all seams and'pints using chemicals, adhesives, and techniques recommended and approved by flooring manufacturer. Make hairline tight seams continuously and uniformly so seams and pints are inconspicuous and nearly invisible. B. Base: Adhere base to walls,oolumns,casework,and to all other fixed and permanent surfaces and fixtures. Run base behind all movable items. Tightly bond base to walls with 100%coverage of adhesive. Do not leave any gaps between wall and base and base and floor. Hand roll base over all base surfaces and make full contact and excellent adhesion. 1. Outside Comers: Groove back of base and field form sharp outside comers. Keep base seams and 'pints as far from outside comers as possible and never closer than 24"to comer. 2. Inside Comers: Cut and cope base at inside comers. Do not round inside comers with one piece of base. 3.3 CLEANING AND CURING: Clean and remove excess and spilled adhesive from base,walls,and floors as the work progresses. Prohibit traffic over newly installed flooring for at least 48 hours or longer as recommended by flooring and adhesive manufacturers to permit adhesive to set and cure. Do not damp mop or clean floors until adhesive is set and cured. END OF SECTION 09650-2 *+ wR SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 09650 RESILIENT FLOORING AND BASE PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Sheet vinyl flooring. B. Resilient edge strips. C. Surface preparation. 1.2 RELATED WORK: Without limitation, related work includes: A. 09680-Carpet; resilient edge strips for carpet. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Samples at least 12 inches square for each type and color of flooring required. C. Samples at least 6 inches long for each type and color of base required. PART 2-PRODUCTS 2.1 RESILIENT FLOORING: Provide Armstrong World Industries"Classic Corlon Seagate". A. Color: 86500 White. 2.2 RESILIENT WALL BASE: Provide 1/8"thick vinyl base complying with FS SS-W-40a,type 1. A. Height: As indicated on drawings. If not indicated, provide 4 inch high base. B. Style: Coved base at hard floors and straight base at carpet. » C. Colors: White to closely match flooring as approved by Architect. 2.3 MISCELLANEOUS MATERIALS: Provide latex subfloor leveling compound; concrete subfloor primers;non-flammable,waterproof adhesives;resilient edge strips with profile and colors approved by Architect;and wax and polish materials as recommended by flooring and base manufacturers. PART 3-EXECUTION 3.1 PREPARATION: Check substrate and underlayment tolerances and fill holes,depressions and cracks with latex leveling compound. Scrape,grind,or sand down ridges and protruding irregularities to create a level substrate in true plane. Thoroughly clean and vacuum substrates immediately before installation of work. �. 3.2 INSTALLATION: Maintain uniformity of color and pattern. Cut materials neatly around fixtures and obstructions. Provide securely bonded resilient edge strips and trim wherever edge of floor would otherwise be exposed. *� A. Sheet Flooring: Layout the work, make paper templates, and accurately cut and fit sheet flooring to spaces prior to application of adhesives. Install flooring with 100%coverage of adhesive observing the flooring and adhesive manufacturers' recommended trowel notching, spreading rates, and open or dwell times. Roll installed flooring with 150 pound roller in both directions at least twice. Make uniform, continuous contact and excellent bond between flooring and subfloor. 09650- 1 .. SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects least 4". Tape seams and perimeter air tight with 2"wide grey duct tape. WN B. Flooring Installation: Power nail wood strip flooring using at least one fastener for each wood strip at Wo each framing member. Blind nail using only screw type flooring nails in strict compliance with floor system manufacturers recommendations and referenced standards. Maintain proper spacing between adjacent strips and at butt joints as recommended by flooring system manufacturer. 1. Pattern: Install wood flooring system in linear strip pattern with direction as indicated or field directed by Architect. C. Expansion Space: Provide 1/4"expansion space at the entire perimeter of the installation and .� wherever flooring abuts an obstruction or an interruption. Cover spaces with bases,trims, saddles, and thresholds as approved by the Architect. 3.2 SANDING AND FINISHING: Acclimate installed flooring system to ambient conditions for at least 10 days before sanding and finishing. Protect floor from traffic to reduce staining and damage. Effectively protect adjacent floors,walls,base,and other surfaces from damage due to floor finishing *�* operations. A. Machine belt sand at least three times with successively finer sand paper. For the last sanding, sand with 220 sandpaper, 150 grit screen,or as recommended by finish manufacturer and approved by ..+ Architect. Do not create sanding machine marks which could be noticeable after finishing. After sanding, surfaces shall be"glass smooth"with the entire floor truly level without ridges and cups. Vacuum thoroughly and wipe with tack rag. Do not use treated dust mops or tack cloths which may interfere with finish application. Finish floor immediately after sanding and preparation. Do not walk directly on sanded floor. Protect sanded floor with heavy protection paper or other effective means. B. Filler: Fill open grained wood with paste filler tinted to match wood color. Apply filler with brush,then wipe across grain to work into pores and cracks. Sand again to remove ridges and other defects. C. Stain: Undomdy wipe stain and provide multiple applications of stain, if necessary,to provide an even color and appearance matching Architect approved samples. D. Sealer: Provide uniform coat of sealer to reduce grain raising and to keep finish on top of wood. Comply with sealer manufacturers coverage recommendations. E. Finish: Provide final finish to match approved samples. Provide three coats of finish in strict compliance with finish manufacturers instructions and recommendations. Lightly screen before the final coat to remove grain raise,but do not remove finish. For first two coats, provide high gloss finish. For last coat, provide matte sheen finish. END OF SECTION 09550-2 ON SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 40 SECTION 09550 40 WOOD FLOORING PART 1 -GENERAL 40 1.1 DESCRIPTION OF WORK: This section includes,without limitation: 40 A. Complete wood floor system including wood moldings, saddles and trim. B. Subfloor preparation including vapor barriers. C. Field finishing of wood floor system including stair treads. OR 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry; subfboring. 4ft B. 06205-Interior Finish Carpentry; wood stair treads. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. B. Samples,fully finished and at least 6 inches square showing complete range of finish. "! 1.4 REFERENCE STANDARDS: Comply with recommendations and standards of National Oak Flooring Manufacturer's Association and Wood and Synthetic Flooring Institute[WSFI]. PART 2-PRODUCTS 2.1 WOOD FLOORING: Provide wood strip flooring system complying with the National Oak Flooring Manufacturer's Association grading rules as follows: A. Species: White Oak. B. Grade: Clear,kiln dried. C. Cut: Quarter Sawn. D. Sizes: Strips nominal 2-1/2"wide with standard random lengths and not more than 300 less than 3'. E. Edges: Square at top surface,tongue and grooved and end matched all sides. F. Thickness: 25/32"minimum. 2.2 VAPOR BARRIER: Provide 6 mil carbonated polyethylene film with average perm rating of 0.1. 2.3 NAILS/SCREWS: Provide type and size recommended and approved by MFMA. 2.4 REDUCER STRIPS AND SADDLES: Provide wood,species and finish exactly matching wood flooring system. Provide minimum 4"wide reducers and saddles.Taper to provide smooth, barrier- free transition between wood athletic flooring and adjacent flooring finishes. .. 2.5 FINISH MATERIALS: Provide pigmented Devoe Paste Wood Filler, Devoe Wonder Woodstain with color as selected by Architect, and Devoe Mirrothane polyurethane finish. PART 3-EXECUTION 3.1 INSTALLATION:Strictly comply with manufacturer's instructions and recommendations,except where more restrictive requirements are specified in this section. Strictly comply with the recommendations of referenced Association Standards. A. Vapor Barrier: Provide one layer of vapor barrier over 100%of floor area with seams overlapped at 09550- 1 Mw SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects O SECTION 09510 'o ACOUSTICAL CEILINGS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Acoustical ceiling system including suspension system and ceiling tiles and panels. 1.2 RELATED WORK: Without limitation, related work includes: A. Division 15-Mechanical; sprinklers,diffusers,grilles located in ceilings and needing coordination. B. Division 16- Electrical; light fixtures,electrical devices located in ceilings and needing coordination. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Samples at least 6 inches square for each type of ceiling panel and 6 inch long suspension members. PART 2-PRODUCTS 2.1 ACOUSTICAL CEILING TILES AND PANELS: Provide Armstrong "2195 Minatone Cortega". 2.2 SUSPENSION SYSTEMS: Provide Armstrong"Silhouette 9/16 Inch Slot Grid". Provide ASTM C635 dM intermediate-duty suspension system including anchors, hangers, and framing. Provide color to match ceiling tiles and panels, unless otherwise indicated. PART 3-EXECUTION am 3.1 INSTALLATION: Coordinate installation with other work to ensure proper location of related work such as light fixtures,mechanical fixtures,fire protection systems,and other work. Layout work and avoid use of less than 1/2 size ceiling modules. Wear clean white gloves to avoid handprints. A. Suspension Installation: Erect suspension system to comply with ASTM C636 and support only from 40 building structure. Level main suspension members to within tolerance of 1/8"in 12'. Splay hangers where necessary to avoid obstructions and countersplay to balance resulting horizontal forces. Cross brace suspension system to prevent lateral sway and displacement. B. Edge Moldings and Trim: Provide edge moldings at entire perimeter of ceiling, at columns and penetrations, and wherever necessary to conceal edges of ceiling units. Miter comers of edge moldings accurately with hairline tight joints, and connect securely, but do not use exposed fasteners. C. Ceiling Panel Installation: Install ceiling panels in coordination with suspension system. Take care to avoid damaging comers and edges of ceiling panels. Scribe and cut panels to fit accurately. Lay panels with rain if an running in one direction throughout the project. Route and paint field cut Pa g I� Y] ng � 9 Pa edges to match factory edges. END OF SECTION 09510- 1 on SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects ON SECTION 09250 Am GYPSUM DRYWALL PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Gypsum drywall systems. B. Metal trims. C. Joint and fastener treatment. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry B. 07200-Insulation; acoustical insulation C. 09100-Interior Light Gage Metal Framing Systems D. 09900 - Painting 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. ■ PART 2-PRODUCTS 2.1 GYPSUM WALLBOARD: ASTM C36 Regular, except fire-resistant type X at fire-rated assemblies. Provide tapered edges. Provide 5/8 inch thick, unless otherwise indicated. 2.2 WATER RESISTANT GYPSUM BOARD: 5/8 inch thick,ASTM C630 Regular,except fire-resistant type X at fire-rated assemblies. Provide tapered edges. 2.3 TYPICAL METAL TRIMS: Provide galvanized steel U.S.G. No.800 comer bead, No.093 control pint,and No.801-A and 801-B edge trim. 2.4 JOINT COMPOUND AND TAPE: Provide ready mixed all purpose vinyl compound and perforated tape complying with ASTM C475. For water resistant gypsum board,provide U.S.G. Durabond 90 Joint Compound. PART 3-EXECUTION 3.1 INSTALLATION: Install gypsum board in strict compliance with ASTM C840 and Gypsum Association publication 216, Recommended Specifications for the Application and Finishing of Gypsum Board. A. Provide comer bead trim at all external comers. Provide pint reinforcing tape at all internal comers. Provide metal edge trim wherever edge of gypsum board is exposed, revealed,or sealant filled. B. Provide control pints where recommended by manufacturer and approved by Architect. C. Provide 3 coat joint compound treatment at all pints,flanges of trim accessories, penetrations, fastener heads and surface defects. Sand before and after second and third coats. D. To be acceptable,board joints, seams, and fasteners shall be invisible after painting. END OF SECTION 09250- 1 an SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 09100 INTERIOR LIGHT GAGE METAL FRAMING SYSTEMS PART 1 -GENERAL .w 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Interior metal framing for drywall partitions and ceilings. 1.2 CONTRACTOR'S OPTION: Contractor may use metal framing or wood framing for interior non- loadbearing partitions and ceilings. 1.3 RELATED WORK: Without limitation, related work includes: A. 09250-Gypsum Drywall 1.4 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Manufacturer's bad tables marked to show spans, bads, and deflection. PART 2-PRODUCTS 2.1 INTERIOR STEEL FRAMING: Minimum 20 gage, ASTM A446,A527,and C645;galvanized steel �w with ASTM A525, G60 coating. 2.2 INTERIOR CEILING FRAMING: Minimum 16 gage cold rolled steel channels with black asphaltum coating, minimum 10 gage steel wire hangers,and minimum 25 gage hat shaped furring channels. PART 3-EXECUTION 3.1 INTERIOR PARTITION FRAMING: Erect framing to comply with ASTM C754. If not indicated otherwise,provide framing to comply with published details and recommendations of U. S. Gypsum, Gypsum Construction Handbook. Limit deflection to L/360. Frame to meet tolerances specified and required for finish materials. Isolate partition framing system from building structural loading both horizontally and vertically. Provide slip or cushioned'pints at top of partitions to accommodate building structural deflection. Space framing members at 16 inches on center. Provide all framing needed to accommodate finishes. A. Blocking: Coordinate the installation of wood blocking specified in Section 06100- Rough Carpentry. 3.2 CEILING FRAMING: Provide continuous steel channels at 4 feet on center and suspend with steel hangers spaced at not more than 4 feet on center and within 12 inches of ends. Provide hat channels at 16 inches on center at right angles to main channels and within 4 inches of ceiling edges. Connect framing and cross-brace hangers to prevent lateral ceiling movement. END OF SECTION 09100- 1 W SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 00 SECTION 08800 `W GLASS AND GLAZING PART 1 -GENERAL ON 1.1 DESCRIPTION OF WORK: This section includes,without limitation,glass and glazing for: A. Interior windows, sidelights, borrow lights. 1.2 RELATED WORK: Without limitation, related work includes: A. 06205- Interior Finish Carpentry B. 10800-Toilet Accessories; framed mirrors. aft PART 2-PRODUCTS 2.1 GLASS: Provide highest commercial quality glass as indicated on drawings and as follows: 00 A. Tempered Glass: Provide fully tempered safety glass in all hazardous locations. Place roll wave distortion horizontally. «■ B. Wire Glass: Provide UL listed,fire-rated wire glass laminated to dear tempered glass to make a safety glass unit. �. C. Thicknesses: Provide as shown. If not shown,provide 1/4 inch thickness. PART 3-EXECUTION 3.1 INSTALLATION: Comply with FGMA"Glazing Manual"and"Sealant Manual". Inspect all glass before installation and do not install defective glass. Check glass for proper size,squareness,edge bite, and clearances and make necessary corrections. Protect glass from all damage including edge damage. Use roger blocks when handling glass. Replace all damaged or weakened glass. A. Center glass in opening and provide minimum 1/2"glass bite and 1/8"minimum edge clearances, unless otherwise indicated. Place setting blocks at quarter points and side blocks at upper half of each side. Securely set setting blocks and side blocks in position to prevent displacement. Prevent direct metal to glass contact. Place glass with uniform pattern,draw, bow,and similar visual characteristics. END OF SECTION 08800- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects ON 3.1 INSTALLATION: Strictly comply with manufacturers instructions and recommendations. Mount hardware at locations to comply with Door and Hardware Institute Recommended Locations for ow Builders Hardware for Standard Steel Doors and Frames and National Wood Window and Door Association ANSI/NWWDA Industry Standard 1.7. A. Set hardware plumb, level and in exact alignment and location. Conceal and countersink fasteners to 4W the greatest extent possible. Use only threaded-to-the-head screws for all hardware attached to wood doors and frames. Use#12 screws for hinges,closers,and other highly stressed hardware, unless otherwise recommended by hardware manufacturer. Do not use exposed through-bolts to Ak mount any hardware. Adjust all hardware to work easily, smoothly, and correctly. 3.2 PRELIMINARY HARDWARE SCHEDULES: Schedules indicated are preliminary schedules and indicate general design intent. It is the responsibility of the AHC employed by the Contractor to ensure that: 1] all necessary hardware is included on final schedules,21 all hardware is coordinated with doors,frames,conditions, and other hardware,and 3]all codes and requirements of authorities having jurisdiction are met. END OF SECTION 08700-2 .w 40 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 08700 FINISH HARDWARE PART 1 -GENERAL �r. 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Finish hardware for doors. B. Providing the services of an Accredited Hardware Consultant to prepare final schedules. 1.2 RELATED WORK: Without limitation, related work includes: A. 08200 -Wood Doors 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data for each item of hardware used. B. Hardware schedules. PART 2-PRODUCTS 2.1 HINGES: Stanley,5 knuckle, heavy weight,4-1/2 x 4-1/2 minimum size,flat tips. Provide ball bearings when used with closers. 2.2 LOCKSETS AND LATCHSETS: Corbin 9800 series with 977 lever trim, rose, and closed box strikes. Provide functions scheduled. 2.3 EXIT DEVICES: Von Duprin 88 series, mortise,with lever trim to match locksets and latchsets. Provide entrance function with dogging feature on all exit devices. 2.4 CLOSERS: LCN 4010/4110 series, mounted on least visible side of door. 2.5 STOPS: Ives 406,407 or 408 to suit wall construction. 2.6 DOOR PLATES: Solid metal, not plated. 10"high by 2" less than door width, except as shown. 2.7 SILENCERS: Provide 3 silencers for single doors and 2 for pair doors. Ives#20 or#21. r 2.8 STRIPPING: Pemko 45062 head and jamb stripping with 18125 bottom sweep. 2.9 THRESHOLDS: Solid Oak incorporated into door frame, except at barrier free entrance,provide Reese S282. 2.10 POCKET DOORS: Provide Grant 1230 set with Baldwin 0465 edge pull and Grante 426 flush pulls. 2.11 RAIN CAP: Pemko B344 for all doors swinging out into rain. 2.12 KEYING: Provide Corbin master ring with 59 keyway. Comply with Owner's instructions and integrate new work into existing college keying system. 2.13 FINISHES: Provide US 4 satin brass,except do not provide plated door plates. Provide plated metal closer covers. PART 3-EXECUTION war 08700- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects smooth operation and a weather tight closure. C. Trim: Provide windows to accommodate exterior wood casings and sills as detailed. Place exterior trim on top of window and not butted to window. Accurately cut and fit trim to precisely fit field conditions. Use only continuous,seamless trim pieces between comers. Securely anchor trim with concealed connections. Provide uniform, hairline tight, miter pints at comers and fill with exterior sealant complying with Joint Sealers and Fillers specification section. Allow a uniform 1/4"wide gap * between trim and surrounding construction for perimeter sealant pints. D. Clean glass surfaces promptly after installation of windows. Exercise care to avoid damage to protective coatings and finishes. Remove excess glazing and sealant compounds,dirt, and other substances. Lubricate hardware and other moving parts. END OF SECTION A goo No low .w A* no -• 08600-2 �"" a SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 08600 WOOD WINDOWS PART 1 -PRODUCTS 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Operable aluminum dad wood windows. B. Insect screens. 1.2 RELATED WORK: Without limitation, related work includes: A. 08200 -Wood Doors 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop drawings for custom work. 1.4 REFERENCE STANDARD: Comply with ANSVNWWDA Industry Standard 2-87 Grade 40. PART 2-PRODUCTS 2.1 WOOD WINDOWS: Provide aluminum clad wood Eagle Windows or Pellla Clad Windows with features as follows. Match elevations and details indicated. A. Muntins: False muntins"Modem Divided Lites". B. Glass and Glazing: Provide factory glazed windows with 5/8 inch thick insulated low E coated glass with argon filled cavity. C. Hardware: Satin brass, heavy duty. Provide cam locks at meeting rails,two sash lifts,and adjustable balances. Use vinyl jamb tracks. D. Weatherstripping: Provide fully weatherstripped windows to meet specified performance requirements. 2.2 INSECT SCREENS: Provide 18 x 16 mesh aluminum wire screen in fully shop painted roll formed aluminum frame. Provide springs and clips to hold screens into place. PART 3-EXECUTION 3.1 INSPECTION: Inspect openings before beginning installation. Verify that rough opening is correct and the sill plate is level. Verily that concealed blocking is correct. 3.2 INSTALLATION: Comply with manufacturers specifications and recommendations for installation of window units, hardware,operators,and other components of the work. Set window units plumb, level, and true to line,without warp or rack of frames or sash. Provide proper support and anchor *"* securely in place. A. Set sill members in a bed of sealant to provide weather tight construction. Coordinate installation with wall flashings and other components of the work. B. Adjust operating sash and hardware to provide a tight fit at contact points and at weatherstripping for 08600- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 08305 ACCESS DOORS AND PANELS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Access doors and panels to provide access to valves,controls,chases, and equipment. 1.2 UNIFORMITY AND COORDINATION REQUIRED: Although access doors and panels may be furnished by several subcontractors, it is a Contract requirement and the General Contractor's responsibility to ensure that all access doors and panels of each type are identical in appearance throughout the work. 1.3 RELATED WORK: Without limitation, related work includes: A. 09900- Painting; field painting visible access door and panel surfaces. " 1.4 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. PART 2-PRODUCTS 2.1 ACCESS DOORS AND PANELS: Provide primed painted steel doors and panels with appearance as scheduled. Provide sizes adequate to provide needed access. Provide cam locks, except provide keyed locks for access doors accessible to the public. Provide two latches or locks on doors over 12". Provide fire-rated doors and panels in fire-rated assemblies. A. When located in Walls: Milcor/Iruyco Style DW. B. When located in Ceilings: Milcor/Inryco Style ATR. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Coordinate " installation with related and adjacent work. Set frames accurately into position and securely fasten truly plumb and level and in proper alignment with adjacent finishes. Set doors so that frames are in full contact with surrounding construction on entire perimeter of frame and doors are in true plane with frame without twisting and binding. Adjust operating parts to work easily, smoothly, and correctly without binding. END OF SECTION + ► 08305- 1 ow- SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects A. Use only threaded-to-the-head wood screws for mounting hardware and hanging doors. Make doors swing freely without binding or scraping the frame and so that doors that are not self-closing remain .� motionless at any location when released. B. Through-Bolts: Do not use visible through-bolts to mount any hardware. C. Hinges: Provide one properly driven screw for each hole in the hinge. At top hinge,provide at least three 3" long threaded-to-the-head wood screws. D. Screws and Pilot Holes: Drill proper size pilot holes for all screws to reduce splitting. If rot otherwise �. recommended by door or hardware manufacturer, use 1-1/2" long#12 threaded-to-the-head wood screws. Where visible,provide screws finished to exactly match visible hardware on door. Where screw penetrates into particleboard core, inject polyester resin adhesive into the pilot hole before inserting screw to increase screw holding power. E. Clearances and Tolerances: For non-rated doors,provide uniform 1/8"clearances at head,jambs and meeting stiles(of pairs of doors). Provide uniform 1/2"clearance at bottom,except at thresholds provide uniform 1/4"clearance. END OF SECTION aw V* .W .f. " Im off 08200-2 '* !F SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects w SECTION 08200 WOOD DOORS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Stile and rail wood exterior doors including complete restoration of existing main entrance door. B. Stile and rail wood panel interior doors. C. Solid core flush,fire-rated doors with vision panel. 1.2 RELATED WORK: Without limitation, related work includes: A. 06200- Finish Carpentry and Millwork; wood frames,casings,sidelights, and trims. ,. B. 08700- Finish Hardware C. 09900 - Painting; field finishing wood doors. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including complete information on door assembly and construction. B. Shop drawings including dimensioned elevations. 1.4 REFERENCE STANDARDS: Comply with Architectural Woodwork Institute"Architectural Woodwork Quality Standards". 1.5 DOOR WARRANTY: Life of Installation for interior doors and 2 years for exterior doors. Include refitting, rehanging, and refinishing. PART 2-PRODUCTS 2.1 STILE AND RAIL PANEL INTERIOR DOORS: AWI Premium Grade,Clear Fir or Pine,2 panel doors to accomrnodate locks,latches, and hardware specified. Minimum 5.5 inch wide stiles required. 2.2 STILE AND RAIL GLAZED EXTERIOR DOOR 103: Buffelin#13-5515 with low E insulated clear tempered safety glass and true divided lights. Match elevation indicated. 2.3 STILE AND RAIL WOOD PANEL EXTERIOR DOORS: Buffelin#F-944 with low E insulated clear tempered safety glass and true divided lights. Match elevation indicated. 2.4 FIRE-RATED INTERIOR WOOD DOORS: Provide 60 minute Warnock Hersey labeled flush wood fire door with laminated wood stiles and blocking for hardware indicated on final hardware shop drawings, so that through-bolts are not required anywhere on the door. Provide Algoma"Superfire System" doors with"Superstiles" and"Superbiocking", or Architect approved equal. A. Frame: Provide fully welded, minimum 16 gage,shop primed,fire-rated steel frame to coordinate with fire doors. Provide custom wood cladding,casings,and trims to conceal steel frame from major public side of frame. PART 3-EXECUTION 3.1 INSTALLATION OF DOORS:Strictly comply with manufacturer's instructions and recommendations, and recommendations of AWI. Acclimatize doors to prevailing conditions for at least 5 days before installing. Fit and machine doors to the extent not done at factory. Trim edges equally on both sides to prevent unbalanced construction. Do not trim tops or bottoms more than 3/4". 08200- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 07900 JOINT SEALERS AND FILLERS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Preparation of pints. B. Sealing and filling of pints indicated and all pints,seams,and intersections between dissimilar materials. 1.2 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Samples for color selection. PART 2-PRODUCTS 2.1 COLORS: Provide colors as selected by Architect from manufacturer's standard colors. 2.2 NON-SAG POLYURETHANE-SEALANT TYPE 1: Provide Pecora Dynatrol II or Tremco Dymeric Plus. Provide non-sag polyurethane sealant for all exterior joints in masonry. 2.3 ACRYLIC LATEX -SEALANT TYPE 2: Provide Pecora AC-20,Tremoo Acrylic Latex,or Sonneborne Sonolac. Provide acrylic latex sealant for typical interior joints and exterior joints in wood. 2.4 MILDEW RESISTANT SILICONE RUBBER-SEALANT TYPE 3: Provide Pecora 863,Tremco Proglaze,or General Electric 1700. Provide silicone rubber sealant for all interior joints in wet areas at tile, wet countertops, and plumbing fixtures. PART 3-EXECUTION 3.1 INSTALLATION: Clean joint surfaces immediately before installation. Remove all substances which could interfere with bond. Etch or roughen joint surfaces to improve bond. Provide backer rods for all liquid sealants to the greatest extent possible. Prevent three sided adhesion by use of bond breaker tapes or backer rods. Force sealant into joints to provide uniform,dense, continuous ribbons free from gaps and air pockets. Dry tool sealants to form a smooth dense surface. Make joint depth equal joint width for joints up to 1/2"wide. For joints over 1/2"wide, make depth equal to one-half of the joint width. Cure sealants in strict compliance with manufacturers'instructions and recommendations to obtain highest quality surface and maximum adhesion. END OF SECTION +w 44 * 07900- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects C. Rain Drainage: Provide half round gutters matching SMACNA Plate 3,figure A. Allow for expansion in compliance with Plate 6 and 7. Hang gutters to match Plate 21,figure A. Locate downspouts where shown on elevations and match Plate 32 figure A, Plate 33 figure D, and Plate 35 figure D. VW Locate downspout hanger straps at same elevations throughout the work. D. Throughwall Flashing: Locate in masonry cavity walls at every obstruction to downward flow of water. Conceal from sunlight. Make minimum 4 inch high,three sided flashing pans and direct water to weeps. E. Soffit Vent: Install continuously where indicated. Make tight butt pints. ALign joints precisely. Set • vents in coordination with surrounding finishes. Do not expose fasteners. END OF SECTION MW No AM am .. 4R ow AW 07600-2 or an SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects RO SECTION 07600 FLASHING AND SHEET METAL PART 1 -GENERAL * 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Sheet metal flashings. B. Rain drainage including gutters and downspouts. C. Sheet metal roofing. D. Miscellaneous counterflashings at sheet waterproofing system. E. Membrane throughwall flashing at masonry veneer. F. Soff it strip vent. 1.2 RELATED WORK: Without limitation, related work includes: A. 07115-Sheet Waterproofing System B. 07315 - Shingle Roofing C. 07900-Joint Sealers and Fillers 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Shop drawings. 1.4 REFERENCE STANDARDS: Comply with Sheet Metal and Air Conditioning Contractors National on Association, Inc. "Architectural Sheet Metal Manual",fourth edition. PART 2-PRODUCTS "" 2.1 COPPER: ASTM 8370,alloy 110, 16 ounce. Provide 50/50 tin lead solder and neutralize flux after soldering. WA 2.2 MEMBRANE THROUGHWALL FLASHING: W. R.Grace"Permabarrier"system. 2.3 SOFFIT VENT: Provide Ampcor"SA-8W"strip vents,factory finished with color approved by Architect. PART 3-EXECUTION 3.1 INSTALLATION: Construct as indicated and match standard details of SMACNA manual as approved by Architect. Make work watertight. Allow for expansion and contraction with watertight moving pints. A. Shingle Roofing: Provide sheet metal valley and ridge flashings and caps as indicated on drawings and SMACNA Plate 61. Use ice dam protection instead of felt under flashings. B. Sheet Metal Roofing: Provide continuous ice dam protection, specified with slate roofing, under all sheet metal roofing. Provide slip sheet of rosin paper between waterproofing and sheet metal. Locate seams uniforrNy and symmetrically,and oriented truly horizontal and vertical. Allow for expansion and contraction. Form sheet metal boots and flashings for penetrations. Do not use visible PVC or membrane flashings. 1. Standing Seam Roofing: Plate 120, 121, 122; 1"high double locked vertical seams and flat locked and soldered horizontal seams. 07600- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects MW B. Provide continuous 3 foot strip of ice dam protection at all roof edges, centered over each ridge, and centered in each valley. Locate under exposed and concealed sheet metal flashings. C. Securely nail roofing felt over entire area of roof. Take special care to place layers to best shed water. .. Pay dose attention at comers and changes of plane. D. Blend shingles from different bundles and cartons to create a uniform appearance with no noticeable pattern and color variation, unless the pattern and color change is shown on the drawings. 1. Install shingles with continuous starter strip of inverted shingles. 2. Provide guide grid of chalk lines to help ensure accurate, straight coursing. 3. Cut and fit shingles accurately at comers, interruptions,obstructions,and plane changes. 4. Securely fasten shingles to structural deck in strict compliance with manufacturer's instructions and recommendations for number of fasteners and fastener locations. 5. Do not permit fastener heads to tear into or penetrate shingles. 6. Coordinate shingle installation with metal flashing,vent flashing,penetrations,and all other work to ensure watertightness. 7. Install shingles with patterns and layout approved by Architect. 8. Provide uniform shingle exposure. E. Valleys: Form open valleys exposing metal flashing below. Cut ends of shingles parallel to centerline of valley and make uniform straight lines. F. Eaves and Rakes: Continuously at eaves and rakes,cement shingles to deck and underlayment and ®` to each other for improved wind uplift performance. G. Hip and Ridge Shingles: Start with a triple layer of field cut or factory cut hip and ridge shingles. �* Securely anchor ridge shingles to ridge vent with double coverage and seal fastener heads with plastic cement. Do not expose plastic cement to view or sunlight. Start from ridge end opposite prevailing wind and be consistent in overlap direction throughout the project. Expose hip and ridge shingles the same as for field shingles. 1 H. Snow Guards: Provide snow wards at 24 inches on center in staggered rows 24 inches on center for at least 6 feet on each side of each exterior entrance. I. Ridge Vents: Securely anchor ridge vents continuously along all ridges. Accurately align ridge vents and create a suitable substrate for application of ridge shingles. END OF SECTION 07315-2 go SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 07315 SHINGLE ROOFING PART 1 -GENERAL *■ 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Asphalt fiberglass shingle roofing. 'B. Ice dam protection and sheet waterproofing. C. Snow guards. D. Ridge vents. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100 - Rough Carpentry; sheathing under slate. B. 07600- Flashing and Sheet Metal; sheet metal flashings and roofing. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: ' A. Product data including installation instructions. B. Samples showing complete range of finish. 1.4 EXTRA MATERIAL: Provide packaged, sealed, and labeled maintenance stock equal to 33 square feet of finished installation. PART 2-PRODUCTS 2.1 SHINGLES: Provide Manville Weatherseal. A. Color: Cambridge Gray. 2.2 UNDERLAYMENT: Provide No. 15 nonperforated organic felt complying with ASTM D226. 2.3 ICE DAM PROTECTION AND SHEET WATERPROOFING: W. R.Grace"Ice and Water Shield"or Achitect approved equal. 2.4 NAILS: Provide 11 gage, hot-dip galvanized steel roofing nails with 3/8" minimum diameter heads and barbed shanks of suff icient length to completely penetrate decking/sheathing by 3/4 inch. ""' ✓ 2.5 SNOW GUARDS: Solid copper, SMACNA 4th edition, Plate 159,figure C or E. 2.6 SHINGLE OVER RIDGE VENTS: Provide one of the following: A. "Shinglevent II",Air Vent, Inc., Certainteed Corporation,Valley Forge, PA. B. "Rovar", Alcoa Building Products, Inc. C. "VenturiVent Plus"Browning Metal Products, Inc. PART 3-EXECUTION 3.1 INSTALLATION: Comply with applicable requirements and recommendations of National Roofing Contractor's Association Steep Roofing Manual and manufacturers' recommendations. A. Ensure proper sequencing of work. Coordinate roof installation with flashing and sheet metal work to prevent leaks and to create a completely watertight assembly. w 07315- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 07270 FIRESTOPPING PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Firestopping all penetrations through fire-rated assemblies. B. Complying with building codes and requirements of authorities having jurisdiction. 1.2 RELATED WORK: Without limitation, related work includes: A. 07900-Joint Sealers and Fillers 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions and UL tested assemblies for each firestopping system used. 1.4 PERFORMANCE REQUIREMENT. Provide UL tested firestopping assemblies which are applicable to each condition encountered, or in the absence of tested assemblies, provide firestopping *® assemblies as recommended by the firestopping system manufacturer's staff engineers and as approved by authorities having jurisdiction. Meet requirements of Section 921 of the Commonwealth of Massachusetts, State Building Code,fifth edition. g. PART 2-PRODUCTS on 2.1 MINERAL FIBER FIRESAFING: U.S.G. 'Therrnafiber Safing Insulation"or equal. 2.2 FIRESTOPPING SEALANTS AND PUTTY: Provide the following or equal: MR A. 3M Fire-Barrier FS_195 Wrap, CP-25 Caulk and Moldable Putty. B. SOHIO Carborundum Fiberfrax Fyre Putty. C. Nelson Electric Company, FSP Firestop Putty, CLK Firestop Sealant, CMP Firestop Compound. ,p D. Dow Coming Corporation, Silicone R7V Foam. E. General Electric Company, Pensil 100 Sealant and 200 Foam. F. Hilti Construction Chemicals, Inc., CS 240 Firestop Sealant and CS 2420 Intumescent Wrap. G. International Protective Coatings Corporation, Flamesafe and KBS products. '"" H. Tremoo, Fyre-Shieldor Fyre-Sil. 2.3 ACCESSORIES: Provide anchorage accessories and other components and accessories as needed to provide complete, effective firestopping systems complying with UL tested assemblies. PART 3-EXECUTION 3.1 INSTALLATION: Provide firestopping materials and thickness as required to maintain.the fire-ratings of the assemblies into which the materials are instailed.1 Strictly match UL tested assemblies. install firestopping without gaps and voids of any kind. A. Inspect firestopping work and repair or replace work which has been damaged,disturbed,or removed before firestopping is concealed or enclosed. END OF SECTION 07270- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects .m D. Foundation Insulation: Provide continuous foam insulation vertically over all below grade foundation walls and horizontally for 2 feet under slabs on grade. E. Vapor Barriers: Install vapor barrier continuously in largest sheets to minimize seams. Overlap seams at least 6"and tape seams,perimeter, and tears securely to create an effective vapor tight barrier. Provide sheet vapor barrier over all exterior assemblies where no other vapor barrier is indicated or exists. END OF SECTION 07200-2 "'" SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 07200 INSULATION PART 1 -GENERAL +�w 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Building thermal insulation. B. Acoustical insulation. C. Vapor barriers. 1.2 RELATED WORK: Without limitation, related work includes: A. 03300-Concrete; vapor barriers under slabs on grade. B. Division 15-Mechanical; pipe and duct insulation. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. PART 2-PRODUCTS 2.1 FIBERGLASS BATTS: ASTM C665,unfaced, 0.32 k-value,widths to coordinate with framing for friction fit,thickness to fill available cavity. 2.2 FOAM BOARD INSULATION FOR EXTERIOR APPLICATIONS: Provide 2 inch thick extruded polystyrene, "Styrofoam", "Foamular",or"Amofoam". 2.3 FOAM BOARD INSULATION FOR INTERIOR APPLICATIONS: Provide 1-1/2 inch thick Class A_ polyisocyanurate insulation. V~ 2.4 VAPOR BARRIER: ASTM D4397,minimum 6 mil clear,virgin polyethylene sheeting having maximum perm rating of 0.13 when tested according to ASTM E96, method E. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Clean substrates and remove projections which could puncture vapor barriers. Extend insulation over entire area indicated to be insulated and over all accessible exterior uninsulated surfaces. Fit tightly around penetrations and obstructions. Fill all holes,gaps and voids. Do not over compress insulation. Provide insulation in one layer with tightly butted edges, unless indicated otherwise. A. Batt Insulation: Friction fit batt and blanket type insulations into spaces indicated to be insulated and in all cavities,voids,and spaces in exterior wall assemblies. Provide supplemental stick-clips and 10 gage wire ties as needed to hold insulation in cavities and prevent falling. B. Acoustical Insulation: Provide unfaced batt insulation in all partitions between offices and offices and corridor on second floor, and completely around toilet rooms and mechanical and machine rooms. C. Interior Furred Spaces with Foam Insulation: Tightly fit insulation into cavities to eliminate voids and gaps. Adhere insulation with ribbons of construction adhesive known to be compatible with insulation. Ensure that foam insulation is covered with at least 1/2 inch of gypsum wallboard or veneer plaster base. 07200- 1 w SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates, Architects an SECTION 07180 CEMENTITIOUS DAMPPROOFING PART 1 -PRODUCTS ** 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Dampproofing and decorative coating of exposed to view vertical concrete surfaces. B. Surface preparation. 1.2 RELATED WORK: Without limitation, related work includes: A. 03300 - Concrete PART 2-PRODUCTS 2.1 CEMENTITIOUS DAMPPROOFING: Provide one of the following with colors selected by Architect from manufacturer's complete range of options. A. "Thoroseal Plaster Mix",Thoro System Products, ICI Americas Inc., Miami, FL.,800-327-1570 B. "UMACO, U-Seal Foundation Coating", Universal Masonry Coating, Inc.,Woburn, MA., 617-938- 8881 C. "Easy Mix Seal Cote",Silpro Masonry Systems, Inc.,Tewksbury, MA., 617-851-6136 D. "Conpro-Plaster Mix", Conproco Coatings, Hookset, NH., 800-258-3500 E. "Tamms Stucco Finish",Tamms Industries Company, Itasca, IL.,312-773-2350 2.2 BONDING ACRYLIC ADMIXTURE: Provide material recommended by cementitlous dampproofing manufacturer. Provide one of the following: A. "Acryl 60",Thoro System Products, ICI Americas Inc. B. "UMACO Add Mix", Universal Masonry Coating, Inc. C. "C-21 Acrylic Latex",Silpro Masonry Systems, Inc. D. "k-88", Conproco Coatings E. "Akkro-7T", Tamms Industries Company 2.3 WATER: Clean, potable, and free from deleterious substances or effects. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Thoroughly dean substrates to remove all dirt,dust,grease,oil,form coatings,curing compounds, efflorescence, and foreign substances. Do not trap moisture under dampproofing. A. Patching: Cut-out,enlarge, patch,and fill all cracks,voids,and honeycombs larger than 1/4"in any direction with acrylic modified cement patching material approved by dampproofing manufacturer. B. Two Coats: Apply first coat at about 2 pounds per square yard and not less than 25 mils dry thickness. Provide texture to bond well with second coat. Apply second coat at about 1 pound per square yard and not less than 15 mils dry thickness. Provide float, sand textured finish to match Architect approved mock-ups and samples. C. Repair and Cleaning: Repair damage and reclean immediately before final acceptance. Repairs shall be inconspicuous and not readily apparent at a distance of 10 feet in strong sunlight. END OF SECTION !! 07180- 1 so SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects in SECTION 07160 on BITUMINOUS DAMPPROOFING PART 1 -PRODUCTS 1.1 DESCRIPTION OF WORK: This section includes,without limitation: .w A. Dampproofing of new below grade foundation walls, back-up walls behind brick veneer, and elsewhere indicated. B. Dampproofing of existing below grade foundation walls which are exposed at any time during the work. Coordinate dampproofing work with existing foundation masonry repointing work. C. Protection board. 1.2 RELATED WORK: Without limitation, related work incudes: A. 07200- Insulation and Vapor Barriers; rigid insulation used as protection board. PART 2-PRODUCTS 2.1 DAMPPROOFING: ASTM D1227,type IV, non-abestos,fibrated type liquid emulsion. 2.2 PROTECTION BOARD: Rigid foam insulation[specified in Section 07200]. PART 3-EXECUTION uw 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Clean substrates,fill voids, seal'pints,dampen, and prime substrates as recommended by dampproofing manufacturer. Install separate flashings,comer protection strips,and cants as recommended by manufacturer even if not shown on drawings. Protect adjacent work from spillage and migration. Do not clog pipes and conduits with dampproofing, but ensure that holes around penetrations are properly sealed and dampproofed. A. Trowel 1/8 inch minimum dry film thickness of dampproofing from 1 inch below finished grade to top of footing and across top of footing and over all back-up walls behind brick veneer. Provide 100 percent coverage on surfaces indicated and on surfaces which are subject to water damage. At depressions, holes, and cracks,a greater thickness of dampproofing will be required so that finished dampproofed surface is reasonably in one plane. B. Protection Board: Provide continuous rigid insulation protection board over completed and approved dampproofing. Fit protection boards tightly around obstructions and penetrations. Adhere protection board with additional dampproofing material. ■ C. Sunlight Protection: Cover installed dampproofing quickly to minimize exposure to sunlight. Comply with manufacturer's recommended exposure limitations. If bubbles or blisters form,cut and remove air pocket and reapply dampproofing to ensure 100 percent coverage without gaps or voids. END OF SECTION 07160 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 4M SECTION 07115 on SHEET WATERPROOFING PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Sheet waterproofing system for terraces over occupied space. B. Protection board. C. Substrate preparation. 1.2 RELATED WORK: Without limitation, related work includes: A. 07900-Joint Sealers and Fillers B. 09600 - Stonework 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. PART 2-PRODUCTS 2.1 SHEET WATERPROOFING SYSTEM: Provide complete,waterproof, W. R.Grace Company "Bituthene 4000" sheet waterproofing system including, without limitation, primers, sheet waterproofing membrane, sealants, liquid waterproofing, and"Bituthene Asphaltic Hardboard" protection board. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Clean and prepare substrates. Grind fins and protrusion level. Radius sharp comers. A. Prime substrates before application of sheet membrane. Provide one layer of sheet membrane with joints overlapped to factory printed guidelines and shingled to best shed water. Seal edges and terminations with sealant. Seal penetrations,obstructions, and awkward conditions with liquid waterproofing. Provide a complete,waterproof assembly. Extend waterproofing system for form a completely watertight bathtub not less than 8 inches high. Flash into drains and scuppers. Run waterproofing to meet and be continuous with adjacent dampproofing and flashings so there is no gap and a continuous water barrier is created. B. Protect waterproofing system from direct exposure to sunlight with 20 ounce copper / counterflashings and building veneer materials. Protect waterproofing system with b layers of protection board. END OF SECTION 07115-1 am SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects relationship with adjacent work. .. 1. Splashes: Adhere splashes to walls with waterproof mastic adhesive which is concealed from view. ow 2. Joints and Seams: Locate joints in splashes uniformly and symmetrically, and only where shown on approved shop drawings or where approved by Architect. ow END OF SECTION ow 06410-2 .. fm SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects a�. SECTION 06410 COUNTERTOPS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Plastic laminate countertop at first floor kitchenette. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry; concealed wood blocking. 1.3 REFERENCE STANDARDS: Comply with Architectural Woodwork Institute"Architectural Woodwork Quality Standards". PART 2-PRODUCTS 2.1 PLASTIC LAMINATE COUNTERTOPS: Provide AWI Premium Grade materials and workmanship. Provide plastic laminate fully laminated with waterproof phenolic resin adhesive to 3/4 inch thick waterproof high density fiberboard A. Plastic Laminate: Provide NEMA LD-3,GP50,0.050"thick general purpose laminate. 1. Provide colors,textures,patterns, and appearance to match Architect's samples. B. Countertop Construction: Provide minimum NEMA LD-3 BK20 0.020"backer sheets for all work to provide balanced construction to reduce warping. Cover all exposed to view surfaces including core with decorative face laminate. C. Splashes: Provide loose splashes with all six sides covered with laminate. Cover exposed surfaces with face laminate and concealed surfaces with backer laminate. Provide 3/4 inch thick and 4 inch high splashes, unless otherwise indicated. Provide splashes where indicated. 2.2 FABRICATION: Prepare countertops for all related work including,without limitation, appliances and sinks. Cut holes to exact templates of items to be used. Trim and finish all openings so that all visible surfaces are fully finished and exactly match countertop. A. Joinery: Fabricate countertops to have the fewest possible seams. Locate seams where shown on shop drawings as approved by the Architect. Do not use any exposed fasteners or connectors. Use concealed bolts to hold seams and joints hairline tight. B. Supports: Provide concealed rough wood framing and supports on underside of countertop. Locate to be concealed from normal view. Ensure that no rough surfaces are placed to catch or snag clothing of person sitting with legs under countertops. PART 3-EXECUTION ** 3.1 INSTALLATION: Strictly comply with referenced standards and install field work to comply with quality standards and tolerances specified for shop work. Provide work to sizes, shapes, and profiles indicated on approved shop drawings. A. Countertops: Mechanically fasten countertops and trim to supports. Use only non-corrosive fasteners concealed from view in the finished work. Shim and accurately level countertops in proper 06410- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects promote air circulation around sleepers. B. Decking and Visible Wood: Vertical grain,C and Better, Douglas Fir,kiln dried. an C. Felt Paper: 30 pound asphalt felt. D. Fasteners: Ring shank or spiral stainless steel decking nails. MW PART 3-EXECUTION 3.1 INSTALLATION: Set nails flush with wood surfaces but do not crush wood fibers or overdrive nails. A. Trim: Nail trim at not over 8"on center and stagger nailing from edge to edge. Install in longest practical lengths to minimize joints and seams. Provide long tapered scarf joints in running work. .K B. Wood Bevel Siding: Provide continuous nailer strip starter course. Install bevel siding truly level with exposure indicated. Nail with stainess steel ring shank nails sized to penetrate into framing at least 1- 1/4 inches. Nail each siding board into each framing member. Locate nails 1-1/8 inch above bottom siding edge, but high enough to clear board below to allow movement. Predrill holes for nails located at ends of boards to reduce splitting. Overlap siding to leave 41/2 inches exposed to avoid cupping and nailing through siding below. Install siding with smooth texture side exposed. C. Ornamental Columns and Posts: Set columns and posts on wood plinths and post bases. Place plinths and post bases on lead shims and setting blocks. Do not permit direct wood to ground,wood to wood,wood to masonry,or wood to concrete contact. Allow air to circulate through interior of hollow columns by way of ventilation holes drilled in plinth bases. Erect columns and posts truly vertically and securely anchor to prevent displacement. Anchor capitals in proper position and .R provide tight fitting solid wood bad bearing column plugs for bad bearing columns. Cover top of capitals with accurately fitted metal flashing uniformly and neatly terminated evenly 3/16"down sides of capital. D. Wood Decking: Staple resilient pads to underside of sleepers at not over 16 inches on center. Place sleepers not over 24 inches on center. Stagger joints in sleepers. Provide 6 inch wide strips of felt continuously over tops of sleepers and staple in place. Nail decking perpendicular to sleepers. Provide two nails per intersection of decking and sleeper. Make nails penetrate at least 1 inch into sleepers. Space decking with 1/8 inch gaps. Avoid joints in decking. Where unavoidable,stagger joints randomly to avoid noticeable pattern. Locate joints over sleepers. Make joints scarfed. •• END OF SECTION 06210-2 '" �w SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 06210 EXTERIOR FINISH CARPENTRY PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Exterior wood siding. B. Exterior wood trim. C. Exterior bead board porch ceiling, soffit,and panels under windows. D. Exterior wood shutters. E. Exterior wood columns,pilasters, half-round columns, and deck ballusters. F. Exterior wood decking assembly. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry; concealed wood framing and blocking. B. 09900- Painting; field finishing work not indicated to be shop finished. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Samples at least 6 inches square and fully finished showing complete range of finish. s, PART 2-PRODUCTS 2.1 WOOD SIDING: Provide kiln dried, 1/2 inch by 6 inch,Western Red Cedar,West Coast Lumber Bureau Grade"Clear Vertical Grain Heart",surfaced 1 side and 2 edges. 2.2 EXTERIOR WOOD TRIM: Provide C&Better,vertical grain,S4S, Douglas Fir or clear, select White Pine. A. Stock Moldings: Brosco 8180 and 923. 2.3 EXTERIOR BEAD BOARD CEILING,SOFFIT,AND PANELS: Provide nominal 5/8 inch[9/16 inch actual]by 4 inch,C 8 Better, mixed grain, Douglas Fir with tongue and groove beaded edge and beaded center molded 'pint. 2.4 WOOD SHUTTERS: Provide Brosco Primed Blinds. A. Shutter Hinges: Stanley SC1640. B. Shutter Hold-Backs: Stanley 1685 1/2. 2.5 EXTERIOR WOOD COLUMNS AND PILASTERS: Reuse salvaged columns from pond side porch. 2.6 EXTERIOR WOOD DECK ASSEMBLY Provide a complete wood deck assembly as follows: A. Sleepers: Provide#2 Southern Yellow Pine pressure treated with water borne preservatives complying with AWPB LP-2 and AWPA C2. Dry lumber to maximum moisture content of 19%after treatment. 1. Resilient Pads: Provide Mason Industries, Inc. 1/2 inch thick hollow neoprene pads stapled to underside of sleepers at not over 16 inches on center. Intent of resilient pads is to isolate sleepers from direct contact with substrate,to prevent sleepers from laying directly on wet substrate, and to 06210- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects piece for each tread. Provide smooth,Gear White Pine or Douglas Fir risers. Provide Brosco .. Coffman stair parts as follows: A. Wall Rail Brackets: Provide Stanley SP 7081 or Architect approved equal. B. Starting Newel Post: B-765B. C. Balusters: B-777. D. Rail: B-720 with B-719 series staring volute. Provide all needed easements, goosenecks, sweeps, and turns needed for complete rail assembly. E. Starting Tread: B-779V. 2.5 ATTIC STAIR: Provide Brosco"Imperial"with 8'-9"ceiling height. m PART 3-EXECUTION .. 3.1 INSTALLATION: Strictly comply with referenced standards and install field work to comply with quality standards and tolerances specified for shop work. Provide work to sizes, shapes, and profiles indicated on approved shop drawings. 04 A. Standing and Running Trim: Install in longest practical lengths to minimize pints and seams. Locate visible pints and seams only where approved by Architect. Scribe and fit work neatly and accurately so with hairline tight pints. Provide long tapered scarf pints in running work. Miter and cope inside comer joints and seams. Select and color match wood at pints and seams to minimize expression of joints and seams. Scribe and fit base to floor irregularities so that top of base is truly level throughout the work. Find high and low spots and layout the work before installing base. B. Anchors and Fasteners: Securely and safely anchor work to substrates, blocking and grounds with concealed fasteners and anchors. Use finishing nails and casing nails for trim work;do not use •b screws including finishing screws. Set nails slightly below finished surfaces and do not make hammer dimples in wood. Do not use nail guns. C. Shelves: Securely attach shelf system only to solid blocking or framing. Provide brackets and braces at not over 48 inches on center. Install work to safely support 25 pounds per linear foot live bad. D. Stairs: Provide finished wood risers and treads. Provide seamless wood members for entire stair width. Assemble rail components to create a complete,continuous rail which supports loads specified in Building Code for egress stairs. END OF SECTION 06205-2 . X4 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates, Architects g SECTION 06205 on INTERIOR FINISH CARPENTRY PART 1 -GENERAL oft 1.1 DESCRIPTION OF WORK: This section includes,without limitation: on A. Interior standing and running trim,wall base,and miscellaneous molding and trim. B. Wood door,window,interior glass partition, and sidelight frames,casings, and trims. C. Shelving,shelf hardware, and closet coat rods. D. Interior decorative wood columns. "" E. Wood stair components. F. Attic stair. 1.2 RELATED WORK: Without limitation, related work includes: A. 06100- Rough Carpentry; concealed wood blocking. B. 09900- Painting; field finishing work not indicated to be shop finished. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop drawings for custom millwork and moldings. C. Samples at least 6 inches square and fully finished showing complete range of finish. 1.4 REFERENCE STANDARDS: Comply with Architectural Woodwork Institute"Architectural Woodwork Quality Standards". PART 2-PRODUCTS 2.1 DOOR FRAMES,CASINGS,WALL BASE,MOLDINGS,AND TRIMS: Provide AWI Premium Grade • materials and workmanship. Provide sizes and profiles indicated. Shop fabricate frames with glued, splined, and screwed connections. A. Painted Work: Clear non-fingerjointed White Pine or Poplar, or Brosco 8180 or 8712. 2.2 SHELVING: Provide Closet Maid,Schulte,or Lee-Rowan white vinyl or epoxy coated wire closet 1. shelving complete with all fasteners, brackets, accessories, and components needed for complete, fully functional assemblies. A. Depth: Unless otherwise indicated, provide 16 inch deep shelves with clothes hanger rod on bottom. 2.3 INTERIOR ORNAMENTAL WOOD COLUMNS: Provide Dixie-Pacific Manufacturing Company or Architect approved equal columns having the following features and characteristics: A. Wood Species: Clear White Pine. B. Shop Finish: None;field prime and paint. C. Intended Final Finish: Painted. D. Column Style: Plain shaft with no entassis or taper. E. Capital: None. F. Base: None. 2.4 STAIR TREADS AND RISERS-STAIR NO.1: Provide solid clear Red Oak 1-1/16"treads with one 06205- 1 .. SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects D. Underlayment: Install underlayment just before installation of finish flooring. Glue and nail to am subflooring at right angles to subflooring. Fill and sand'pints of underlayment scheduled to receive resilient flooring,carpet,thinset tile, and other thin finishes. Nail underlayment to subflooring with am minimum 6d ring-shank nails spaced 3"on center at panel edges and 6"on center each way within panels. 3.5 AIR INFILTRATION BARRIER: Strictly comply with manufacturers printed installation literature. Begin ow installation at a building comer and unroll continuously around building keeping barrier taut against sheathing. Cover all openings in walls including doors and windows. Fasten into framing from top to bottom about 24"on center vertically and not more than 16"on center horizontally smoothing out .. wrindes as work progresses. Use wide staples or roofing nails long enough to obtain excellent hold. After the building is completely wrapped,X cut openings from comer to comer and pull infiltration barrier into openings and securely fasten. W A. Overlaps: Overlap soleplate about six inches. Make minimum 8"overlap at ends of roll and when finished. For multi-story construction, make minimum 12"overlap at horizontal seams. Provide minimum 12"overlaps for"patched"work. ,o B. Sealing: Continuously seal infiltration barrier to foundation wall below sole plate, around windows, doors, and other openings, and all vertical seams with sheathing tape. END OF SECTION Oka ws w am AW am 06100-4 .". q" SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects an stringers notched to leave at least 3-1/2"of effective depth. Make all risers equal to within t 1/16". Make all treads equal to within t 1/16 0. Provide plywood treads and risers with rounded smooth ON nosings for stairs indicated to receive carpet. G. Firestopping: Firestop furred spaces and wall cavities at each floor level and at ceiling line of top story with solid, continuous wood blocking. H. Sill Sealer: Provide continuous sill sealer beneath all sill plates to form an effective barrier against air infiltration. I. Roof Decking: Provide new board decking to replace all damaged and missing existing decking. Provide a smooth,uniform substrate for plywood roof sheathing. 3.3 BLOCKING INSTALLATION: Choose blocking to eliminate split,warped and twisted members. Securely anchor blocking to substrates and structure to support applied work and loads. Install blocking flush with framing. Countersink bolts and other fasteners flush with face of blocking. Coordinate with other work to ensure correct size and placement of blocking. A. Handrails/Guardrails: Provide minimum 1"x 6"wherever rail touches wall. B. Toilet Accessories: Provide minimum 1"x 6", except 2"x 6"for grab bars. C. Shelving Supported By Vertical Shelf Standards: Provide minimum 2"x 6"continuous horizontally at *� top,middle and bottom of vertical shelf standards and extending the entire length of the shelves. At Contractor's option,continuous concealed plywood sheathing may be provided under the wall finish; no offsets or"bumps"in the wall are permitted, install flush. D. Casework: Provide minimum 1"x 6"in at least two horizontal rows where casework touches wall. E. Wail Mounted Door Stops: Provide minimum 2"x 4"blocking to accept stop mounting and to transfer impact bad to framing and not wag finish. F. Other Items Needing Blocking: Provide minimum 2"x 4"or 1"x 6"securely anchored from stud to stud. 3.4 PLYWOOD: Comply with instructions and recommendations of APA, Design and Construction Guide -Residential and Commercial for types of panels used and applications indicated. Fasten panels as indicated below following fastener spacing specified in APA Guide. A. Mounting Boards: Screw panels to framing at not over 6 inches on center at edges and 8 inches on ow center within panel. Countersink fasteners flush with surface of plywood. Coordinate with other work to ensure correct size and placement of mounting boards. 40 B. Plywood Sheathing: Provide plywood sheathing with pints staggered and with panels at right angles to framing. Locate panel edges over framing to the greatest extent possible. Nail sheathing to framing with 6d common nails for 1/2"thickness or less and 8d common nail for over 1/2"thickness at 6"on center at panel edges and 12"on center within panels. 1. Extent: In addition to locations shown on drawings, provide continuous plywood sheathing over all new and existing roof areas. C. Subfboring: Provide plywood subflooring with pints staggered and with panels at right angles to framing. Securely glue and screw subflooring to framing with continuous beads of panel adhesive on each framing member and 1-1/2"#10 fiat head wood screws spaced 6"on center at panel edges and 10"on center within panels. ,, 06100-3 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 2.8 SILL SEALER: Provide Dow Chemical"Ethafoam". 2.9 FASTENERS: Provide size,type,and material appropriate for intended use in strict compliance with .o building code nailing schedule and referenced industry standards. For exterior use, provide fasteners with ASTM A153 hot-dip galvanized coating. A. Anchor Bolls for Wood Plates to Concrete Foundations: Provide ASTM A3071/2"diameter, 10" ow long stnictural steel anchor bolls with nuts and washers of proper size and with bent or hook end for embedding into fresh concrete. 2.10 CONSTRUCTION ADHESIVE: Provide HIM, Inc."CA 3400 Heavy Duty Subfloor Adhesive"or SW Architect approved equal meeting American Plywood Association "AFG-01"specification requirements. No 2.11 FRAMING CONNECTORS: Provide code accepted framing connectors of type suitable for each condition. Provide Simpson `Strong Tie"connectors or Architect approved equal. PART 3-EXECUTION 3.1 LEVEL EXISTING: Shore,shim, and level existing structure to eliminate warped floors,deformed members, bowed members, and other defects. Permanently level structure to within 1/4 inch of true level. 3.2 NEW FRAMING: Choose wood members carefully to eliminate split,warped and twisted members. Set work to required levels and lines with members plumb and true to line with joints neatly and tightly cut and butted. Securely anchor work in strict compliance with referenced standards and building code nailing schedule. Countersink bolts and other fasteners flush with face of wood and provide a proper substrate for later work. A. Wall Framing: Provide stud framing at 16"on center,unless indicated otherwise. Provide single sill plate and double top plates, except single top plate is acceptable for non-loadbearing partitions. Provide at least three studs at comers and partition intersections. Provide milers in true plane wherever necessary for installation of gypsum wallboard and other finish materials. B. Headers: Frame openings with multiple studs and headers equal to width of studs. Set headers on edge and support with jamb studs and jack studs or cripples. Provide double jamb studs at openings 6'wide and less and triple jamb studs at openings over 6'wide. Provide headers matching width of .u, wall and with depth shown or if not shown,provide headers in strict compliance with referenced standards and codes. C. Joists: Provide floor joists with crown edge up and with not less than 1-1/2"of bearing at each end. .P Attach with toe nailing or code accepted joist hangers. Do not permit holes larger than 314 inch diameter nor holes closer than 2"from edges without first obtaining Architect's approval. Do not permit holes in headers,beams and girders supporting more than one member. Provide blocking at ^' ends of joists and bridging as required by codes. Provide double joists under non-loadbearing bearing partitions and triple joists under unusually heavy partitions or fixtures. D. Furring and Strapping: Where indicated to support ceiling finish materials,provide 1 x 3 strapping at 16"on center perpendicular to span of joists, rafters and truss chords. Provide wood furring at 16"on center where shown. Provide strapping and furring thickness to accommodate insulation thickness indicated. �* E. Special Framing: Provide special framing and supports for eaves,overhangs, and similar conditions as detailed and as required to adequately support construction shown. •� F. Stair Framing: Unless indicated otherwise,frame stairs and steps with not less than 3-2 x 12 06100-2 •� SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 4 SECTION 06100 go ROUGH CARPENTRY PART 1 -GENERAL .,A 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Wood framing. B. Concealed wood blocking and nailers. C. Structural sheathing for walls and roofs. D. Subflooring and underlayment. °"'" E. Mounting boards for mechanical equipment, electrical panels, and telephone equipment. F. Air infiltration barrier. G. Shoring, shimming, and leveling existing structure. 1.2 RELATED WORK: Without limitation, related work includes: to A. 06205-Interior Finish Carpentry; work needing blocking. B. 06210- Exterior Finish Carpentry; exterior wood deck assembly. C. 06400-Custom Casework; work needing blocking. D. 08700-Finish Hardware; wall stops needing blocking as E. 10800-Toilet Accessories; work needing blocking. F. 12390- Premanufactured Cabinets PART 2-PRODUCTS 2.1 FRAMING AND BLOCKING: Provide#2 Hem-Fir,#2 Southern Yellow Pine,or other wood species #2 or better having minimum bending stress Fb of 1000 psi[1150 repetitive]and modulus of elasticity E not less than 1400 ksi and complying with Product Standard 20. A. Decay Treated: For wood in contact with masonry or concrete,provide wood pressure treated with water bome preservatives complying with AWPB LP-2 and AWPA C2. Dry lumber to maximum moisture content of 19%after treatment. 2.2 MICROLAMINATED BEAMS: Provide"Micro=Lam"beams as manufactured by Trus Joist Corporation. Provide sizes, depths,and thicknesses as indicated on drawings. 2.3 PLYWOOD WALL AND ROOF SHEATHING: Provide APA trademarked, Exterior grade, performance rated plywood sheathing. Particleboard and flakeboard are not acceptable. Provide thickness shown, but not less than thickness needed to achieve span rating for spans indicated. r 2.4 SUBFLOORING: Provide minimum 518 inch thick APA trademarked, Exposure 1 plywood performance rated plywood subflooring with tongue and groove edges. Particleboard and flakeboard are not acceptable. 2.5 UNDERLAYMENT: Provide minimum 1/4 inch thick APA trademarked,waterproof interior plywood Underlayment. 2.6 EQUIPMENT MOUNTING PANELS: Provide 5/8 inch thick, APA trademarked, UL labeled,Class A fire-retardant treated, C face, Exposure 2 panels complying with Product Standard 1. 2.7 AIR INFILTRATION BARRIER: Provide DuPont"Tyvek Housewrap"in 9'wide rolls and associated "Siiiwrap"and"Headerwrap". Provide tape to seal seams and edges of air infiltration barrier. 06100- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects .F PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Provide suitable anchors and fasteners to connect miscellaneous metal items to other construction. Provide .W setting templates and diagrams and coordinate with other work so that adequate anchor bolts, blocking and bracing is in place and accurately located. A. Set work accurately and truly plumb,level and aligned. Make field assembly and connections with the same level of quality as shop fabricated work. B. Maintain allowable variation from true plumb, level,and line of t 1/8"in 20'-0". C. Install and anchor all work to support all bads prescribed by codes. END OF SECTION 05500-2 an SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 05500 MISCELLANEOUS METALS PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Welded steel handrails and guardrails at interior and exterior. B. Elevator pit ladder. C. Elevator subsill angles. D. Custom fabricated rough hardware. E. Other miscellaneous metal work needed for the project. 1.2 RELATED WORK: Without limitation, related work includes: A. 03300 - Concrete B. 09900- Painting 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Shop drawings stamped,signed and sealed by a Massachusetts Professional Engineer. PART 2-PRODUCTS 2.1 INTERIOR PIPE RAILS: Fabricate from ASTM A53, Schedule 40 steel pipe to match appearance indicated. Meet building codes for fire stair rails. Return rail ends to walls. Close visible open ends. Space brackets for wall mounted rails not over 6 feet on center. 2.2 EXTERIOR RAILS: Fabricate from ASTM A500 or A501 rectangular steel tubes minimum 1/4 inch wall thickness. Provide fully welded construction. Provide rail assemblies to match appearance indicated. 2.3 LADDERS: Comply with ANSI A14.3. Provide 3/8"x 1-1/2"bar side rails spaced 18"apart with no.5 deformed steel rebar rungs at 12"on center vertically. Extend rails 42"above top rung. Anchor each ladder siderail with dip angles at top,bottom and intermediate points. Provide 7"clearance from walls to centerline of rungs but do not obstruct elevator[coordinate with elevator supplier]. 2.4 ELEVATOR SUBSILL ANGLES: Provide continuous,concealed support angle for elevator sill. Coordinate requirements for size, load and anchorage with Elevator Supplier. 2.5 ROUGH HARDWARE: Provide all custom fabricated bolts,anchors, hangers,dowels and other miscellaneous metal items as needed to complete the project. 2.6 FABRICATION: Fabricate work to be truly straight and plumb with sizes,shapes,and profiles indicated. Shop fabricate work to the greatest extent possible. Clearly label pieces in shop to facilitate field assembly. Perform welding in compliance with American Welding Society Code. Choose materials that are smooth and free of blemishes such as pits, roller marks,trade names,scale and roughness. Fabricate work with uniform, hairline tight joints. Weld joints and seams continuously and grind welds smooth to be inconspicuous after painting. 2.7 SHOP PAINTING: Prepare for shop priming in compliance with Steel Structures Painting Council SP- 6 Commercial Blast Cleaning. Shop prime paint all work with rust inhibitive primer specified in Section 09900- Painting at 1.0 to 1.5 mils dry film thickness. say 05500- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects Code and Specifications. A. Bracing: Provide and maintain temporary bracing to make work safe and stable until entire structural system is complete. Make all necessary provisions for temporary bracing and for completion of erection where structural members are temporarily left out for erection at a later date. B. Connections: As work is erected,securely connect work with sufficient bolts and welds to resist all construction,wind, and erection bads. Splice members and make connections only as indicated on approved shop drawings. Provide washers under the head or nut turned in tightening. C. Drift Pins: Drift pins may be used only to align the parts. Do not distort or damage metal. D. Base Plates: Set base plates on clean bearing surfaces using wedges or leveling nuts as needed. Solidly pack open spaces with non-shrink commercially package grout. E. Corrections: Do not field correct fabrication errors by use of gas torches, except with the acceptance of the Architect. Do rat cut or alter members in the field in any way without the written permission of the Architect. Consult Architect in all cases field correction. Torch cutting,when permitted, shall be done in compliance with Building Codes and requirements of authorities having jurisdiction. F. Anchors and Inserts: Furnish inserts and anchors to other trades for building into concrete and masonry construction. Except as indicated otherwise,secure surface mounted work to masonry or concrete with hot dip galvanized expansion anchors or powder driven fasteners, properly designed and engineered for each application. G. Tolerances: Plumb, level, and align members in accordance with the requirements of the AISC Code of Standard Practice for Steel Buildings and Bridges. + • END OF SECTION 05120-2 "" SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 05120 as STRUCTURAL STEEL PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: „ A. All structural steel framing and members including connections required for the project. 1.2 RELATED WORK: Without limitation, related work includes: A. 05500-Miscellaneous Metals B. 09900- Painting 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data. B. Shop and erection drawings showing materials;sizes and weights of members; location,types and details of connections;openings in members;welding sequences as required by Structural Welding Code;and cleaning and painting schedules. ** 1.4 REFERENCE STANDARDS: Comply with the following: A. AISC Code of Standard Practice for Steel Buildings and Bridges. B. AISC Specification for the Design, Fabrication and Erection of Structural Steel for Buildings. C. AWS Structural Welding Code. D. AISC Specification for Structural Joints Using ASTM A325 and A490 Bolts. E. Industrial Fasteners Institute Fastener Standards Book. F. Research Council on Riveted and Bolted Structural Joints Specifications for Structural Joints Using ASTM Hi-Strength Bolts,ASTM A 141 Rivets and ASTM A307 Unfinished Bolts. G. SSPC Steel Structures Painting Manual, Volume 2, Systems and Specifications. PART 2- PRODUCTS 2.1 STRUCTURAL STEEL AND STEEL PIPE COLUMNS: ASTM A36 and A53 Schedule 80, unless otherwise indicated. A. Primer: Shop prime with minimum 2.0 mils DFT rust inhibiting primer over SSPC SP-6 preparation. aw 2.2 BOLTS: ASTM A325 and A490, minimum 3/4"diameter. Exclude threads from shear planes. ,w. PART 3-EXECUTION 3.1 FABRICATION: Fabricate work to comply with AISC Specifications and approved shop drawings. Detail steel in strict compliance with AISC"Manual of Steel Construction". Fabricate members with properly designed and located holes to provide for connections and for other work as indicated and needed. Provide all necessary reinforcement in compliance with AISC standards. A. Use bolts for field connections and welding for shop connections, except as otherwise indicated. Make connections to develop the full capacity of the members connected. 3.2 ERECTION: Check the alignment and elevations of all supports and location of all anchor bolts with transit and level instruments before starting erection. Carefully inspect members before erection. Do not use steel members which are bent,twisted or otherwise damaged. Strictly comply with AISC 05120- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects E. Curing: Cure mortar in a damp condition for not less than 72 hours. F. Quality Control Program: Establish specific procedures to prevent damage to masonry edges during preparation of pints for repointing,and feathering of mortar during repointing. END OF SECTION 04520-2 ° No SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 04520 rr MASONRY REPOINTING PART 1 -GENERAL +w 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Repointing all exposed to weather portions of the existing masonry chimney to eliminate cracked masonry and deteriorated mortar joints. B. Repointing all existing masonry foundation walls exposed at any time during the work to eliminate cracked masonry and deteriorated mortar joints. 1.2 RELATED WORK: Without limitation, related work includes: A. 07900-Joint Sealers and Fillers 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions. B. Samples not less than 3 linear feet of joint showing quality of workmanship and finished appearance. o► PART 2-PRODUCTS 2.1 MORTAR MATERIALS: Comply with requirements of Section 04200. Provide ASTM C270, cement ,0, lime mortar,Type O,proportion specifications. A. Appearance: Match original work in good condition as approved by the Architect. Control cement color, aggregate color, and pigment to provide uniform,consistent appearance matches. PART 3-EXECUTION 3.1 INSTALLATION: At existing foundation walls,thoroughly clean and scrub surfaces to remove soil and foreign substances and to prepare masonry for repointing. Remove all substances which can inhibit bonding of new mortar. A. Joint Preparation: Rake and cut out joints to a depth of at least 314"and not less than that necessary to expose sound, unweathered mortar. Carefully remove mortar with hand tools only. Do not damage bricks in any way. Power tools may not be used, unless the Contractor can demonstrate that he can use power tools without damaging masonry and only if obtaining the Architect's prior written permission. Do not enlarge joint widths. Brush and hose joints with water to remove all loose material and dust. Joint surfaces shall be damp, but free of standing water at time of repointing. B. Mortar Mixing: Measure mortar materials, including pigments,carefully using known volume measures;do not batch by shovelful. Mix well together in a mechanical mixer in specified proportions. Mix in small batches that can be used within one hour of mixing. Use the minimum amount of water that produces a workable mix. C. Repointing: Point joints up to 1/2"deep at one time. Install pointing mortar in layers not over 1/2" deep for joints over 1/2"deep. Do not spread mortar over masonry faces and do not featheredge mortar. Do not make repointed mortar joints appear wider than original joints. D. Tooling: Tool joints to form dense,weathertight surfaces. Size,tooling and appearance of finished joints shall match adjacent original joints in good condition and shall match approved samples. + 04520- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 3.2 MAKING NEW OPENINGS IN EXISTING MASONRY' and brace existing work to prevent collapse. Needle walls above opening and support needles to permit cutting away wall below. Install new lintels furnished under Miscellaneous Metals or Structural Steel. Provide at least 8"of uniform solid bearing at each end of lintels and supports. Saw cut or hand cut existing masonry along mortar joint lines to remove masonry indicated to be removed. Tooth jambs of new opening and build back with masonry to dose and finish all jambs and to create finished masonry surfaces. Grout solidly under lintel supports and above lintel to masonry above. Remove needles after lintel is ready to accept load and patch holes at removed needles. 3.3 CLOSING OPENINGS IN EXISTING MASONRY. Clean existing contact surfaces to remove all paint and foreign substances. Anchor'new masonry into existing masonry at not over 16 inches on center. Build masonry into existing opening and maintain existing coursing and bond pattern to the greatest extent possible. Solidly grout all voids and gaps and make new work integral with and match existing work. .. 3.4 CLEANING: Clean masonry work daily to remove excess mortar using bucket and brush method without add. Upon completion of work,provide final cleaning without add and leave work with .� uniform,clean finish. END OF SECTION am .. Ap 04200-2 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 04200 UNIT MASONRY PART 1 -PRODUCTS 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Exterior brick masonry veneer. B. Cutting, patching, and rebuilding existing masonry to accommodate new work. 1.2 RELATED WORK: Without limitation, related work includes: A. 03300-Concrete; installation of dovetail anchor slots in concrete. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data for each type of product used. 1.4 REFERENCE STANDARD: Comply with Brick Institute of America"Technical Notes". PART 2-PRODUCTS 2.1 BRICK: Provide ASTM C216,grade SW,2-1/4"high x 3-5/8"deep x 7-5/8"long Stiles and Hart"Full Range Belgian"sand struck molded brick. 2.2 CONCRETE MASONRY: Hollow loadbearing,ASTM C90,type I,grade N. 2.3 MORTAR: ASTM C270, property specif!cations,Type M for work in contact with earth and Type N for all other work. Do not use masonry cement. A. Mortar Color: Provide Solomon Grind Chem Service, Inc. "SGC 45A". 2.4 TIES AND ANCHORS: Provide the following Hohmann and Bamard, Inc.products or Architect approved equals. Hot dip galvanize all ties and anchors, except stainless steel. A. Masonry to Concrete Anchors: #305 slots and#315"Flexible Dovetail Brick Tie". B. Miscellaneous Anchors: Minimum 12 gage or 3/16"diameter to suit configuration. PART 3-EXECUTION 3.1 INSTALLATION: Install masonry to comply with reference standards. Cut masonry units with motor- ,, driven saws to provide clean, sharp, unchipped edges. Cut units to provide continuous pattern and to fit adjoining construction. Use full size units without cutting where possible. Avoid the use of less- than-half-size units at comers,jambs, and where possible at other locations. A. Bond: Running bond, except as otherwise shown. B. Joint Width:3/8 inch. C. Joint Tooling: Match existing foundation and provide dense, compressed,watertight joint surfaces. ! D. Lay work with full mortar coverage on bed and head joints. E. Form open head weeps at not over 24 inches on center and at each flashing and obstruction to downward water flow. F. Securely anchor masonry at not over 16 inches on center horizontally and 24 inches on center vertically. Provide anchors within 8 inches of perimeter of masonry. 04200- 1 .f SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects No D. Where concrete is visible, remove fins and projections and fill and patch voids with fine concrete grout to create a fine textured,uniform"plaster-Ike"surface. Steel trowel horizontal surfaces to provide hand, slick,smooth, uniform planes,then finish with coarse broom texture where mud set .e stonework is the indicated final finish. END OF SECTION • AM aft we .■ 03300-2 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 03300 CONCRETE PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. All concrete worts needed for the project. B. Vapor barriers under slabs on grade. 1.2 RELATED WORK: Without limitation, related work includes: A. 02200-Site Clearing and Earthwork B. 02710 - Foundation Drainage C. 07180 - Cementitious Dampproofing 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Shop drawings for reinforcing steel. B. Samples at least 3 square feet showing each concrete finish for Architect's approval. 1.4 REFERENCE STANDARDS: Comply with American Concrete Institute:ACI 318,ACI 301,ACI 614, ACI 306, ACI 347,ACI 315,ACI 302, and Concrete Reinforcing Steel Institute"Manual of Standard Practice". PART 2-PRODUCTS 2.1 CONCRETE: ASTM C94. Proportion mixes in compliance with ACI 301. Provide concrete having minimum 3,500 psi compressive strength at 28 days,3"to 4"slump,and 4%to 6%entrained air. 2.2 REINFORCING: Provide ASTM A615,Grade 60,new,deformed reinforcing bars. Provide ASTM All 85, new, rectangular welded wire fabric with size and gage specified on drawings. 2.3 FORM WORK: Provide new formsk suitable to provide straight,flat, accurately aligned surfaces with exposed surface as specified. 2.4 VAPOR BARRIER: 6 mil, non-perforated polyethylene sheeting. ' PART 3-EXECUTION 3.1 INSTALLATION: Securely construct and brace form work to provide concrete members and structures of sizes, shapes, elevations, profiles, alignments, and positions indicated. Place and tie reinforcing in position and secure against displacement. A. Provide continuous vapor barrier under slabs on grade over granular fill. Provide in largest practical sheets to minimize seams. Overlap seams at least 6 inches and seal with continuous 2 inch wide duct tape. Ensure that vapor barrier is continuous and unbroken immediately before placing concrete. B. At locations indicated or approved by Architect, provide joints as needed to control cracking, placement, and settlement. Provide shear transfer dowels between new and existing work. 40 C. Place concrete continuously and in compliance with ACI. Consolidate concrete with electric/mechanical vibrating equipment to eliminate honeycombs and air pockets and to ensure full coverage of reinforcing steel. 40 03300- 1 am SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects obstructions, repair damage, and retest until acceptable. am END OF SECTION .m .. ow AM .. no $W aw AW OF Aw .W 02710-2 ,. SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 02710 FOUNDATION DRAINAGE PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation: A. Perimeter foundation drainage system. 1.2 RELATED WORK: Without limitation, related work includes: A. Section 02200-Site Clearing and Earthwork; soil materials,drainage fill. B. Storm drainage system shown on drawings. 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: yaw A. Shop drawings showing layout of complete system including clean outs. PART 2- PRODUCTS 2.1 PIPE AND FITTINGS: ASTM D2729 solid and perforated 4 inch diameter PVC pipe. Provide coordinated fittings for solvent welded joints. 2.2 FILTER FABRIC: Provide Mirafi 140N. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Excavate pipe trenches to provide at least 6"clearance on both sides of the pipe. Grade bottom of trench to correct slope to drain, and place compacted sand to form a solid bed for the entire length of the pipe including bells. A. Impervious Fill: Apply and compact a minimum 8"deep impervious bentonite clay fill layer adjacent to concrete footings in minimum 12"wide strips to help prevent erosion and undermining of footings. B. Drainage Fill: Provide at least 4"compacted depth of drainage fill over compacted subgrades and beneath pipes. After testing of drainage system,place and compact drainage fill over and around pipes in 6"loose lifts. Extend drainage fill to at least 8"from sides of pipe,to adjacent foundation walls, and to 12"above the drainage pipe. C. Filter Fabric: Place one layer of filter fabric al around drainage fill to isolate drainage fill from adjacent soil and to prevent siltation fo drainage fill. Overlap filter fabric edges at least 4". D. Pipe Installation: Place pipe with perforations down and 'pints tightly closed. Provide collars and couplings as recommended by pipe manufacturer. 1. Connection: Run and connect foundation drainage system to storm drainage system. E. Ceeanouts: Provide wide sweeps and cleanouts at all turns and comers of foundation drainage !► system. Extend cleanouts vertically to within 6 inches of final grades and cap cleanouts with removable threaded caps. Clearly indicate locations of cleanouts on final record drawings giving dimensions from building structure in two directions at right angles. F. Testing: Thoroughly test and check piping system before backfilling to assure free flow. Remove 02710- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 02510 ASPHALT CONCRETE PAVING PART 1 -PRODUCTS 1.1 SCOPE OF WORK: This section includes asphalt concrete walks. 1.2 RELATED WORK: Without limitation,related work includes: A. 02200-Site Clearing and Earthwork; compacted granular sub-base beneath asphalt paving. 1.3 SUBMITTALS: Submit certification of grade and quality of asphalt concrete provided. 1.4 REFERENCE STANDARDS: Comply with Massachusetts Department of Public Works"Standard Specifications for Highways and Bridges". PART 2-PRODUCTS 2.1 ASPHALT CONCRETE: Provide Class 1-1 asphalt aggregate concrete mixture in compliance with Section 460 of State Standard Specifications. Provide base course, binder course, and top course in compliance with Section M3.11.03 of State Standard Specifications. PART 3-EXECUTION 3.1 INSTALLATION PREPARATION: Set grades and review grades with Architect prior to beginning paving work. Proof-roll subbase and identify all unstable areas. Do not begin work until unstable areas are excavated,refilled, and recompacted properly. 3.2 INSTALLATION STANDARDS: Install asphalt concrete paving in strict compliance with Sections 460.6 through 460.68 of the State Standard Specif ications. 3.3 INSTALLATION THICKNESSES: Place asphalt concrete with minimum total thickness of 1.5 inches. 3.4 PAVING ACCEPTANCE TOLERANCES: No ponding is permitted. All work shall slope to drain at least 2%and shall comply with tolerances of the standard specifications. 3.5 PAVING PATCHING: Remove and patch all defective work and all work not meeting acceptance tolerances in strict compliance with Section 460.67 of State Standard Specif ications. END OF SECTION w 02510 - 1 40 The fine aggregate to be used in bituminous setting bed shall be clean, hard sand with durable particles and shall be free from adherent coating, lumps of clay, alkili salts, and organic matter. It shall be uniformly graded from "coarse" to "fine" and all passing the No. 4 sieve, and it shall meet the gradation requirements when tested in accordance with the standard method of test for sieve of screen analysis of fine and coarse aggregates ASTM Designation C-136-81. The dried fine aggregate shall be combined with hot asphalt cement, and the mix shall be heated to approximately 300 degrees F at an asphalt plant. The approximate proportion of materials shall be 7% asphalt cement and 93% fine aggregate. Each tone shall be apportioned by weight in the approximate ratio of 145 pounds asphalt to 1 ,855 pounds sand. The Contractor shall determine the exact proportions to produce the best possible mixture for construction of the bituminous setting bed to meet construction requirements. B. Neoprene modified asphalt adhesive under brick: MASTIC (asphalt adhesive) Solids (base) 75+ 1% Lbs/Gal 8-85 lb? Solvent Varsol (over 100 F Flash) +w BASE (2% Neoprene, 10% Asbestos-free fibers 88% Asphalt) Melting Point- ASTM D-36 200 F Min. Penetration - 77 F 100 Gram Load 5 Second (.1 mm) 23-27 Ductility - ASTM D-1 13-44 @ 25 C 5 cros/per minute 125cm Min. 3.4 Grade Stakes A. Install and maintain grade stakes, as directed. All subgrades must be approved before base course construction. 3.5 Finish Grades A. The words "finish grades" as used herein mean the required final grade elevations. END OF SECTION 02500-3 PAVING AM E. Concrete pavement placement, curing, testing, reinforcing and protection and form work shall be as specified in Section 901 of the Standard Specification and as directed by the Landscape Architect. Concrete shall have a medium broom finish of parallel marks. AM Brooming shall be at right angles to the axis of walk or as shown on the Drawings. No spray or curing compounds shall be used in construction of concrete base course. Concrete covering over wire mesh and reinforcing bars shall be as indicated on the Drawings. F. Wire mesh used for reinforcement shall be unrolled flat before placing in concrete. Mesh reinforcement shall be held firmly in place against vertical or transverse movement by means or devices satisfactory to the Landscape Architect. G. Expansion joints shall be placed where pavement meets structure, thirty feet (30') on ,. center and/or as indicated on the Drawings. Expansion joint shall be a minimum of one- half inch (1/2") wide with premolded filler recessed 1/2" from the walk surfaces. (See 3.02 C) H. Install expansion dowels and sleeves across all expansion joints in the concrete paving two feet (2') on center. AWO I. Remove no forms for 24 hours after placing concrete. Protect concrete walks from pedestrian traffic for a period of 3 days after placing. Damp cure as specified under City Specification, Type C1-1 . Aft 3.2 Brick Pavers A. Brick shall be selected by Landscape Architect but for cost estimating purposes assume aw bricks to be City Hall Pavers manufactured by Stiles and Hart or equivalent. Final approval to be made by Landscape Architect. am B. Grades: All grades in pavement shall be established and maintained to a tolerance of 1/4" in 10'-0". C. Brick shall be installed over concrete where specified. Bricks shall be butt jointed and swept with stone dust and cement. 3.3 Setting Bed for Bricks or Concrete A. Bituminous setting bed shall be rolled with a power roller to a nominal depth of 3/4" while still hot. The thickness shall be adjusted so that when the asphalt block or brick pavers are placed, the top surface of the pavers will be at the required finished grade. A coating of 2% neoprene-modified asphalt adhesive shall be applied by squeegeeing or troweling over the top surface of the bituminous setting bed so as to provide a bond under the pavers. If it is troweled, the trowel shall be serrated with serrations not to exceed 1/16". Asphalt cement to be used in the bituminous setting bed shall conform to STM Designation D-3381 , viscosity grade A.C.10 or A.C.20. 02500-2 PAVING 00 SECTION 02500 PAVING PART 1 - GENERAL 1.1 Work Included A. Provide all labor, equipment, implements and materials required to furnish, install, construct and perform all paving operations complete as shown on the Drawings and specified herein. B. To be included, but not limited to the following: 1. Concrete and brick. 1.02 Submittals A. Samples: Submit representative samples of products to be furnished under this Section to the Engineer for selection and approval, as follows. Delivered materials shall closely match approved samples. 1 . Brick Pavers B. Do not order materials or begin installation of work of this Section until Landscape Architect approval of submittals has been obtained. PART 2 - PRODUCTS (see Part 3) PART 3 - EXECUTION 3.01 Concrete Pavement For Sidewalks A. Cast-in-place concrete shall be Class D, air-entrained concrete conforming to the requirements and applicable provisions of Section 701 of the Standard Specifications. Minimum 28 day compressive strength 4,000 psi. Concrete shall be air-entrained 5% minimum with a one (1 ") to three (3") inch maximum slump. B. Wire mesh for reinforcement shall conform to AASHTO M55, latest requirements or Standard Specifications for Welded Steel Wire Fabric and Concrete Reinforcement ASTM-A 185. C. Preformed Joint Filler: This specification covers nonextruding and resilient preformed expansion joint fillers and shall conform to AASHTO M213 requirements for premolded rigid cane fiber board impregnated through with asphaltic compound. D. Make any corrections necessary to compacted gravel base furnished and installed under Section 2B Earthwork to bring gravel to the section and elevations shown on the Drawings. 02500-1 PAVING SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 02280 TERMITE AND INSECT CONTROL PART 1 -GENERAL ++ 1.1 DESCRIPTION OF WORK: This section includes,without limitation, soil treatment for termite and insect control. 1.2 RELATED WORK: Without limitation, related work includes: A. Section 02200-Site Clearing and Earthwork 1.3 SUBMITTALS: Submit the following in compliance with Divisions 0 and 1: A. Product data including installation instructions and use limitations and recommendations for each material used. 1.4 REFERENCE STANDARDS: Comply with National Pest Control Association standards and applicable Federal, State, and Local governing regulations. 1.5 WARRANTY: Provide written warranty signed by Contractor and termite and insect control subcontractor certifying that treatment will prevent infestation and that N infestation is discovered during warranty period,the warrantors shall retreat soil and pay all costs of repair or replacement of damaged building components at no cost to the Owner. A. Warranty Period For Termites: 10 years from date of Substantial Completion. B. Warranty Period For Carpenter Ants and Other Non-Termites: 1 year from date of Substantial Completion. PART 2- PRODUCTS 2.1 TREATMENT PESTICIDES: Provide an emulsive concentrate insecticide specially formulated for soil treatment to prevent infestation by termites, carpenter ants, powder post beetles, and other insects and pests harmful to wood building structure and other building components. Provide chemical solutions which have a proven history of effective use in the Smith College area,and which are acceptable to authorities having jurisdiction. Use only chemical solutions which are not injurious to landscaping and which are approved for use in occupied spaces when used inside buildings. Do not use fuel oil or any other solvent or hydrocarbon as dilutent or vehicle. PART 3-EXECUTION 3.1 INSTALLATION: Strictly comply with manufacturer's instructions and recommendations. Perform „ work only when existing and forecasted weather conditions are within the limits established by treatment product manufacturers. Do not apply treatment to frozen or excessively wet ground. Perform soil treatment work only after earthwork,filling,and grading is complete. Reapply soil r. treatment to areas disturbed by subsequent construction operations or as needed to meet test requirements. Apply chemical treatment solutions at concentrations and coverages recommended by chemical manufacturer, but not less than the following application rates: A. Foundation Walls: Apply 1 gallon per foot of wall height per 2.5 linear feet of wall length. Apply this quantity on each side of wall. B. Slabs on Grade: Apply 1 gallon per each 10 square feet of area. C. Interruptions, Cracks, and Joints: Apply 0.5 gallons per linear foot. END OF SECTION ' 02280- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects B. Shoring and Bracing: Slope excavations and provide shoring and bracing as necessary to comply with requirements of all authorities having jurisdiction and to ensure the safety of persons and property. Shore existing foundation walls to prevent settlement. Protect trees from damage. C. Dewatering and Drainage: Dewater to maintain dry excavations. Prevent surface and subsurface water from entering excavations. Prevent softening of subgrades, undercutting of footings and foundations and other detrimental conditions. Provide temporary water control ditches, pumps and systems as needed to control water. All fill materials shall be placed and compacted in the dry. D. Excavation: Excavate all miscellaneous fill soils to the limits and subgrades indicated. Create subgrade having bearing capacity of at least 2 tons per square foot. E. Placement and Compaction: Place granular fill in layers not exceeding 8"loose depth. Compact each layer with at least four passes of a vibratory roller to achieve at least 95%of maximum dry density MW as determined by ASTM D1557. F. Trenches: Excavate trenches to provide at least 6"clearance on each side of pipe or conduit. Excavate to depths needed, but in all cases provide sufficient depth to avoid freezing of pipes or damage from traffic above. Provide solid bearing for entire body of pipes and conduits;shape subgrade to accommodate bells and hubs. Backf ill as soon as possible but not before inspection, testing, and approval of utilities. Take special care to prevent displacement of pipes, conduits or structures by backfilling operations. Backfill trenches within 18"of footings and foundations with structural concrete complying with the requirements of Concrete specification section. G. Grading: Uniformly rough grade areas to prevent ponding of water and to slope away from structures. Create wide swales to effectively control and drain water to drainage areas. Rough grade to within t1" of indicated subgrade. H. Damage and Erosion: Protect graded areas from traffic and erosion. Repair and reestablish grades in damaged areas. Recompact as necessary. I. Settlement: Where settling is measurable or observable, remove surface improvement[I any], add fill material,compact properly,and replace surface improvement[if any]. Restore appearance to eliminate evidence of patching or repair. END OF SECTION am AM 02200-2 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 02200 SITE CLEARING AND EARTHWORK PART 1 -PRODUCTS 1.1 DESCRIPTION OF WORK: This section includes,without limitation, A. Temporary protection of adjacent public and private property. B. Disconnecting and capping existing utilities indicated to be abandoned, removed, or relocated. C. Clearing of areas for new construction, including removal of trees and stumps. D. Stockpiling existing topsoil for reuse and spreading and grading topsoil. E. Uncovering below grade structures, improvements, and utilities. F. Removal of existing fill and other unsuitable foundation materials. G. Preparation of subgrade for building slabs,walks, pavements, and foundations. H. Excavation and baddill of open excavations and trenches inside and outside of building. I. Excavation and backfill for all utilities. J. Dewatering of excavations and general water and erosion control. K. Engineering and providing shoring and bracing. L. Legal disposal of unsuitable or surplus excavated materials off site. M. Providing fill materials,fill compaction and control, and rough grading. N. Work of this section is unclassified and requires excavation and removal of all natural and man-made materials and obstructions. PART 2-PRODUCTS 2.1 STRUCTURAL FILL: Provide gravel,sandy gravel,or gravelly sand free from organic material, loam, trash, snow,ice,frozen soil,or other objectionable material and which is suitable for use as structural fill as approved by the Architect. ■ 2.2 COMMON FILL: Provide easily spread and compactable mineral soil substantially free from organic material, loam,trash,ice,or other objectionable material and graded so that a maximum of 50% passes the no.200 sieve and a maximum of 80%passes the No.40 sieve. Ordinary fill shall not contain stones over 6"in diameter, nor any broken concrete or masonry. Soil excavated from the structure area which meets the above requirements may be used as Common Fill. 2.3 DRAINAGE FILL: Provide washed gravel or washed crushed stone complying with ASTM C33 size number 67, 1/4"minimum to 3/4"maximum. PART 3-EXECUTION 3.1 CLEARING: Clear entire area of new construction and landscaping. Use methods within limitations of governing regulations. Clear and grub to remove all surface vegetation and below grade roots to a depth of at least 12", except where existing vegetation is indicated to remain and except at areas of new foundation construction, demolish below grade improvements and remove roots and stumps completely. Remove all debris from site and dispose of legally. Burning on site is not permitted. 1.2 EARTHWORK: Stockpile topsoil in locations acceptable to Owner. Do not remove topsoil in any quantity from site without the written permission of the Owner. �u A. Unauthorized Excavation Correction: The Contractor shall pay for all unauthorized excavations and necessary remedial work. Notify Architect immediately in all cases of unauthorized excavation. Remedial work necessary to correct unauthorized excavation shall consist of additional concrete or compacted structural fill to bring elevations up to required subgrades. '"" 02200- 1 3.3 Existing Pavement Removal A. Remove existing concrete and bituminous concrete pavement and all other site features as shown on the Drawings. B. Included under this Section will be all saw cutting of pavement. All sawn edges of paving shall be protected from damage until new paving is placed against it. Existing MW pavement which is damaged, disturbed or settled, shall be cut back by the same method and replaced as directed by the Landscape Architect at no additional cost to the Owner. am 3.4 Dust Control A. Wet down thoroughly all work during excavation to prevent spread of dust. Make all arrangements and pay for all water and necessary connections therefor. no 3.5 Clean-Up no A. Remove from the project site all materials and debris resulting from the work of excavation. Storage of such materials on the project site will not be permitted. The project site shall be safe, clean and holes filled and compacted with clean fill upon no completion of the excavation and site clearance work. END OF SECTION ow 02100-4 SITE PREPARATION AND CLEARING wr 3.2 Tree Work A. Existing trees designated to be protected, removed or transplanted are shown on the Drawings. B. The Contractor shall arrange to meet the Landscape Architect on the site to verify trees to be protected, transplanted or removed before he begins any work of this Contract. C. Tree Protection 1. Trees to be saved within limit of work shall be enclosed by twelve foot square fence made of 2 x 4 lumber, or as directed by the Landscape Architect. Layout and method of construction of protection fences must be approved by the we Landscape Architect before construction. The work of protection fence construction shall be completed before starting of the rest of the work of this Contract. 2. Damage no trees to remain by burning, by pumping of water, or by cutting of live roots or branches, or by any other means. If, in order to perform excavation work, it becomes necessary to cut roots of plants to be saved, such roots shall be neatly cut and painted with an approved tree paint after consulting the Landscape Architect. * 3. The Contractor shall establish and carry out a maintenance program throughout the time of construction for trees to be saved. The program shall be as specified in Section 02900 Planting. 4. Pruning shall be done in a manner which does not change the natural appearance of the plant. Broken or badly bruised branches shall be removed with a clean cut and treated with asphalt base tree paint prepared for three surgery. All pruning shall be done by skilled men in accordance with best horticulture practice, appropriate to the type of plant and to its special or individual requirements. The Contractor shall meet with the Landscape Architect before commencing the work of pruning. 5. Any existing tree scheduled to be protected that is injured or destroyed shall be OF replaced at the Contractor's expense, with tree of equal type and size. D. Tree Removal: All plants to be cleared shall become the property of the Contractor, and the satisfactory disposal of the wood in such trees at the Contractor's dumps shall become his responsibility. No burning of trees on or adjacent to the site will be allowed. These shall be felled in such a manner as not to injure standing trees, plants, or other objects which are to be preserved. 2. Stumps and major roots shall be completely removed to the satisfaction of the Landscape Architect. 02100-3 SITE PREPARATION AND CLEARING C. Furnish, erect and maintain all fences, planking, bracing, shoring, sheathing, lights, barricades, warning signs, and guards as necessary for the protection of streets, sidewalks, and adjoining property. D. Completely remove all protection when the work is completed or when ordered in writing to do so by the College. 1.4 Utilities A. Discontinuance or Interruption Before starting demolition, the Contractor shall be solely responsible for making all necessary arrangements and for performing any necessary work involved in connection with the discontinuance or interruption of all public and private utilities or services under the jurisdiction of the utility companies or corporations, Fire Department and Public Works Department such as gas, electricity, steam, refrigeration, low tension system, telephone, telegraph, police signal, fire alarm, water, sanitary sewer, storm drainage, and without limiting the generality of the foregoing, including any system or systems which will be affected by the work to be performed under this Contract. Before starting demolition securely seal, at the street line of all buildings or structures to be demolished, .� all sanitary sewer or storm drainage pipes leading from the building or structure to existing mains. The pipe or pipes shall be filled full with cement mortar consisting of one part of Portland Cement and two parts of sand. Demolition shall not be started until said sewer and storm drainage pipes have been inspected by the Official. B. Protection Preserve in operating condition all active utilities traversing the project site which are to remain. Should any damage occur to a utility which is to remain as a result, in the judgement of the Official, of this operation, the Contractor shall at his own expense, repair all damage to any such utility to the satisfaction of the College. PART 2 - NOT USED PART 3 - EXECUTION 3.1 Clearing and Grubbing A. Clearing shall consist of the cutting and removal of all trees, logs, stumps, brush, roots and other ojectionable material from within the Limit of Work Line unless otherwise shown on the plans or directed. B. Protection - Protect all areas to remain undeveloped outside the Contract limit lines. Should these areas be damaged, the Contractor shall restore them to the satisfaction of •. the Landscape Architect and Owner. This includes the repairing and replacement of all damaged conditions such as plant materials and similar items. C. Grubbing shall include the removal and disposal of all stumps and roots to a depth not .� less than eighteen (18) inches below subgrade. 02100-2 SITE PREPARATION AND CLEARING .� ae� SECTION 02100 SITE PREPARATION AND CLEARING PART 1 - GENERAL 1.1 General Requirements A. The Contractor shall, prior to any removal of rubbish or debris from the site, furnish on a form supplied by the College written evidence satisfactory to the College that he has an approved dumping location for debris and/or spoil from his demolition and excavation activities. B. Cleaning of materials for the purpose of salvage on the site shall not be permitted. C. The Contractor shall secure all necessary permits from the City of North Hampton before starting this project. 1.2 Work Included A. Provide all labor, equipment, implements and materials required to furnish, install, construct and perform all Site Preparation and Demolition work complete, as shown on the Drawings and as specified herein. B. To be included: 1. Clearing within the limits of work by cutting, grubbing and removing, together with proper disposal of, all trees, shrubs, stumps, roots and any other objectional materials shown to be removed except as otherwise provided herein. �w 2. Spoiled material not suitable for fill shall be removed from the site and disposed of. No burning on the site shall be permitted. 3. Protecting existing trees to remain as directed by the Landscape Architect. 4. Pruning of existing trees as directed by the Landscape Architect. 5. Demolition and removal to a minimum depth of one and a half feet below existing grade from the site of items including foundations, footings and other below grade structures shown on the Drawings and as specified herein to be removed. ' 6. Demolition and removal from site of bituminous concrete and concrete pavement. 1.3 Special Protection for Maintaining Streets and Public Ways A. Do not close or obstruct streets without a permit. Do not place or store material in streets or sidewalks. B. Conduct operations with minimum interferences to street. 02100-1 SITE PREPARATION ,� AND CLEARING SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects H. Wood Framed Floors: Remove existing floor finishes and construction down to bare,cleaned subfloors free of traces of adhesives and debris which could interfere with new work. Patch all holes and depressed areas. Shoring and leveling is specified under Rough Carpentry. I. Existing First Floor Concrete Slab on Grade: Break up and remove in its entirety. J. New Openings: Remove all existing structure and construction and create new openings as indicated and as needed to properly complete the work of the Contract. Protect openings to prevent injury to persons in compliance with authorities having jurisdiction. Cut work using methods least likely to damage adjoining work. Use tools designed for sawing or grinding, not hammering or chopping. Use saws or drills to ensure neat, accurately formed holes to sizes required with minimum disturbance to adjacent work. K. Existing Utilities and Systems: Completely remove all existing utilities, services, and systems including,without limitation, existing HVAC,plumbing, electrical, and communication systems, and building mounted antennae. Remove all pipes, conduits, ducts, radiators, equipment,fans,wires, and other elements of utility and service systems. L. Roof: Strip and remove all existing roof coverings,flashings, underlayments, felts, and other materials down to bare clean wood framing,decking, and sheathing. inspect all wood and remove all damaged and deteriorated wood. 3.2 SALVAGE: Carefully remove and disconnect items indicated to be salvaged, except where noted to be salvaged in place. Package and label all parts and components. Record non-obvious conditions and details to facilitate reassembly and reinstallation. Salvage the following items,unless otherwise indicated or directed. Items which are not wanted or rejected by the Owner shall become the property of the Contractor. ,p A. Fireplace mantle[protect in place]. B. Exterior entrance door. C. Exterior wood siding on exterior walls to remain[protect in place]. "' D. Pond side porch columns. E. Other items of value and suitable for reuse as maintenance stock for the College. 4W END OF SECTION 1W ow am 02071 -2 ,.. 00 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects g. SECTION 02071 go SELECTIVE DEMOLITION PART 1 -GENERAL 1.1 DESCRIPTION OF WORK: This section includes,without limitation,complete demolition and removal from the site of all existing construction, materials, and systems,except existing construction indicated to remain and existing construction indicated to be salvaged. 1.2 PROJECT CONDITIONS: Ensure the safe passage of persons near areas of work. Prevent injury to persons and damage to property. Control dust and noise to avoid creating a nuisance and comply with local ordinances and Owner requests. Comply with Division 0 and 1 conditions and general requirements. PART 2-PRODUCTS-Not Used PART 3-EXECUTION 3.1 DEMOLITION: Use demolition methods within limitations of governing regulations. Proceed with demolition systematically and orderly. Demolish in small sections. Do not overload structures. Prevent uncontrolled collapse. Provide temporary shoring and bracing to ensure safety and stability. • Temporarily cover openings and maintain building weather tight and secure from unauthorized entry. Ensure the safety of people and property at all times. Provide effective temporary guardrails at open wells and changes of floor plane. A. General Scope: Remove all existing construction and improvements indicated to be removed, and as necessary to perform the new construction indicated. Remove debris from site and dispose of legally. B. Interior Walls: As indicated on drawings and as needed to accommodate new work, remove interior walls and partitions completely and entirely. Where wall or partition removal results in holes in floors, walls,ceilings,or other surfaces,cut loose materials back to sound materials,and patch and fill holes to match durability and quality of adjacent unpatched work and to create substrates suitable for installation of new finishes and work. For interior walls indicated to remain with only certain finishes or layers removed, remove finishes as indicated and as needed to accommodate new work and remove all adhesives, residue,and traces of previous finishes which could interfere with new work. C. Interior of Exterior Walls: Remove interior constriction from the inside surface of exterior walls down to bare,clean framing. Remove all existing insulation. D. Exterior of Exterior Walls: Remove existing windows and doors in their entirety[see salvage requirements]. Remove exterior wood trims at doors and windows. Preserve and protect existing siding and trim to the greatest extent possible. E. Ceilings: Remove ceilings and ceiling mounted systems and equipment leaving only bare structure free from hangers,wires,and other items. Remove all existing insulation. F. Exterior Columns: Remove and discard, except remove and salvage columns on pond side porch for * reuse on new entry porch. G. Interior Brick Columns: Shore structure and prepare for installation of new steel pipe columns. After structure is properly shored and supported, demolish and remove existing brick columns in their entirety. ,�, 02071 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 0222/93 David P. Handlin and Associates,Architects SECTION 01020 ALLOWANCES PART 1 -GENERAL 1.1 DESCRIPTION OF SECTION CONTENTS: This section includes,without limitation: �► A. Allowance amounts for items of work indicated. 1.2 RELATED WORK: Without limitation, related work includes: A. Division 16-Electrical 1.3 SCHEDULE OF ALLOWANCES A. HVAC Control System Allowance: Allow the amount of$29,000.00for HVAC control system. The allowance amount includes control system components, saws um, shipping and handling, and �. installation of all control system components,except control valves and control components installed in the piping system. Control valves and control components installed in the piping system shall be furnished by the ATC subconractor and installed by HVAC subcontractor. The cost of installing control valves and control components in the piping system shall be included in the Contract *" Amount, but not in this Allowance. PART 2-PRODUCTS - Not Used PART 3-EXECUTION - Not Used END OF SECTION 01020- 1 w� SMITH COLLEGE, OFFICE OF ADMISSION 0222/93 David P. Handlin and Associates,Architects O SECTION 01030 !" ALTERNATES PART 1 -GENERAL 1.1 DESCRIPTION OF SECTION CONTENTS: This section includes,without limitation: A. Alternates for Owner's selection and decision. 1.2 ALTERNATES: Alternates are alternative products, materials, equipment, installations or systems, which may, at the Owner's option be selected and recorded in the Contract(Owner/Contractor Agreement)to either supplement or displace corresponding basic requirements of contract documents. Alternates may or may not substantially change scope and general character of the work. ,+ A. Alternate Requirements: A Schedule of Alternates is included below. Each alternate is defined by abbreviated language, recognizing that Contract Documents define the specific requirements. Coordination of related work is required to ensure that work affected by each selected alternate is complete and properly interfaced with work of accepted alternates. B. Alternate Proposals: The Contractor shall provide written proposals for each afternate for the Owner's consideration. Each proposal amount shall include the entire cost of the alternate portion of work including all overhead,profit,and all other costs including costs to coordinate and interface the afternate with related and adjacent work. C. Selection of Alternates: The Owner shall be the sole judge of which alternates are selected for inclusion in the Contract. 1.4 SCHEDULE OF ALTERNATES aww A. Alternate 1: Provide an alternate price proposal to provide a dehumidifyer in room 006 PART 2-PRODUCTS - Not Used PART 3-EXECUTION - Not Used END OF SECTION 01030- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects and procedures,general and routine maintenance instructions, and listing of original installers, suppliers, and distributors. List types of lubricants to be used for each item requiring lubrication. Provide detailed information on maintaining,cleaning, and refinishing finish materials such as floors, walls, and ceilings. 1.25 OWNER OCCUPANCY: Cooperate and permit the Owner to install its materials,furnishings,fixtures, and equipment during the progress of the work in accordance with a mutually agreeable schedule before completion of the work of the Contract. 1.26 NOISE: Strictly comply with noise pollution and control regulations and requirements of authorities having jurisdiction. Use properly muffled equipment. Use rubber tired equipment instead of metal track equipment to the greatest extent possible. Abide by local ordinances regarding work hours and limitation of noise. Do not play radios on the jobsite which can be heard outside the work limits. 1.27 TRAFFIC AND PARKING: Limit site traffic to one access/egress point approved by the Owner. Control traffic to minimize damage to surrounding areas and danger to the public. Park only in locations designated by Owner. Do not obstruct streets,public ways, sidewalks. Comply with local ordinances and requirements of authorities having jurisdiction. A. Tickets: Vehicles parked outside of Owner designated areas will be ticketed and possibly towed. Owner reserves the right to deduct the cost of tickets from the Contract Amount and final payment. 1.28 ADVERTISEMENT. No mention of or reference to the Owner's name or this Project shall be made in any advertising or articles in any publication,without the prior approval of the copy and written permission of the Owner. Whenever the Project is permitted to be published or advertised,the Architect's name shall be clearly stated. PART 2 - PRODUCTS [Not Used] PART 3 - EXECUTION [Not Used] END OF SECTION GENERAL REQUIREMENTS 01000 -4 "� r SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 40 manpower, as needed to protect the work and create a suitable work environment. Protect building from soot, smoke and fire damage. Do rat use heaters which would interfere with curing of mortar and grout or damage any materials. If any material is damaged by temporary heating,remove and replace the material at no additional cost to the Owner. A. Restriction: Do not use the Owner's central plant heating for temporary heating. 1.17 TEMPORARY ELECTRIC POWER AND WATER: The Contractor may obtain power and water from sources available in the building. The Owner will pay for water and power used. Do rat waste. 1.18 PROTECTION: Protect the work and all nearby people and property. Provide and maintain barricades,warning signs and lights,railings,walkways and the like. Immediately repair damaged property to its condition before being damaged. A. Fence: Enclose the entire construction site including,without limitation, material stockpile and staging areas with at least a 4 feet high chain link fence. Locate fence where approved by Smith 40 College. Providing and maintaining a high quality fence appearance is important and is required. 1.19 SIGNS: Except for necessary safety and warning signs, no jobsite signs are permitted. 1.20 FIRE PREVENTION AND PROTECTION: Take every possible precaution to prevent fire. Arrange for periodic inspections by the local fire department and insurance underwriters,and abide by their instructions and recommendations. Eliminate hazardous conditions. Provide fire extinguishers nearby when soldering work is in progress. 1.21 EROSION CONTROL AND WETLAND PROTECTION: Provide rows of staked hay bales and sift fencing and effectively control erosion and prevent siltation of wet areas downhill. 1.22 SUBMITTALS: Submit at least one reproducible and two additional copies of each paper submittal. Provide at least three sets of samples. Allow at least 10 working days for Architect's review and approval. A. Shop Drawings: Provide accurately prepared, large scale, and detailed shop drawings prepared specifically for this project on reproducible sheets. Show adjacent conditions and related work. Show accurate field dimensions and clearly note field conditions. Identify materials and products in the work shown. Note special coordination required. 1.23 SUBSTITUTIONS: Provide materials and products as specified. Substitutions are not permitted. Contractor's submittal and Architect's acceptance of shop drawings, samples,product data,or other submittal is not a valid request for, nor an approval of a substitution. 1.24 RECORD DOCUMENTS: Provide and maintain a complete dedicated set of Contract Documents to serve as field record documents. Mark up the record drawings to clearly show concealed locations and deviations from the Contract Drawings. Mark up the specifications to clearly indicate products and model numbers used. Upon completion of project and after receiving Architect's preliminary approval of field record documents,transfer field rates clearly and neatly to a new,clean copy of the Contract Document specifications and to wash off[rat sepia]mylar copies of the drawings. Obtain final approval from Architect and submit final Record Documents to Owner and obtain receipt before final payment. A. Record Maintenance Data: As the work progresses,compile two complete and identical binders of operating and maintenance data for the entire project. Include complete information about each Rem of mechanical,electrical,and operating equipment. Provide copies of all valve tagging schedules, schematic diagrams of systems and wiring,copies of electrical panelboard directories, emergency instructions, complete parts listings and sources, recommended inspection schedules GENERAL REQUIREMENTS 01000 -3 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects .. the Owner in writing before execution of the Change. A. Change Orders: A formal Change Order,signed by the Owner,Architect, and Contractor, is required .w prior to any change in the work which affects Contract Amount or Contract Time. B. Field Directives: The Architect may issue field directives and instructions to clarify the Contract Documents and to accommodate unexpected or concealed conditions. If the Contractor believes that any field directive issued by the Architect significantly affects the Contract Amount or Contract Time,the Contractor shall obtain a formal Change Order approved by the Owner before performing the work. C. Contractor Waives Claim for Additional Payment and Time Extention: Except for cases of immediate danger to life or property, if the Contractor executes any work due to a field directive issued by the Architect or executes any other change in the work without first obtaining a formal Change Order,it shall be understood by all parties that there was no significant change in Contract Amount or Contract Time, and the Contractor,by his action,shall have waived all claims for additional payment or additional time related to the change. 1.08 MATCHING: Where matching such as"match existing"is indicated,the Owner shall be the sole and final judge of what is an acceptable match. 1.09 CLEAN-UP: Clean-up all waste and debris, remove from site regularly,and legally dispose of off- site. Keep premises clean, neat,orderly,and safe at all times. Keep adjacent areas, neighboring properties,streets,public ways, and all areas free of construction debris and waste including wind blown debris. A. Food Waste: Clean up and remove food waste,lunch bags,and containers daily. Do not permit ,W trash and litter to blow onto Campus. Do not create any condition which attracts vermin, insects, rodents, or other pests. 1.10 SUPERINTENDENT: The Contractor shall employ an experienced Superintendent who shall be subject to the Owner's approval and who shall be present at the site during all work. The approved Superintendent shall not be reassigned or replaced during the entire duration of the Project without the Owner's written approval. 1.11 LAYOUT OF WORK:Employ a Registered Land Surveyor or Professional Engineer to layout the work and to establish and be responsible for all lines,elevations,and measurements of the building, grading, utilities, benchmarks, and other work executed under the Contract. 1.12 PERMITS AND FEES: Obtain and pay for all permits,fees, licenses, inspection fees,and charges related to this Project. 1.13 TEMPORARY ENCLOSURES: Provide temporary enclosures and weather protection to prevent weather damage and water damage to the building,and to secure the building from unauthorized access. 1.14 EQUIPMENT AND TOOLS: Provide and maintain all equipment including,but not limited to,hoists, lifts, scaffolding, staging, ladders,tools and the like, as needed for proper and safe execution of the work. Provide safe access to all parts of the work for review, inspection, and observation. 1.15 TEMPORARY TOILETS: Provide and maintain clean,well supplied portable toilet facilities in compliance with municipal ordinances and requirements of authorities having jurisdiction. Do not use permanent facilities within the building,unless permitted by Owner in writing. 1.16 TEMPORARY HEAT: Provide and maintain temporary heat, including equipment,fuel,and GENERAL REQUIREMENTS 01000 -2 '" �e SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 01000 GENERAL REQUIREMENTS PART 1 -GENERAL 1.01 RELATED DOCUMENTS: This section contains general information that applies to all work performed under the Contract and is inherently made a part of each specification section. i0 1.02 DESCRIPTION OF WORK: Project is the complete renovation of and addition to an existing wood framed residential style building into very high quality offices, reception and meeting rooms for Smith College. Since this building will serve as a primary location for Smith College to meet prospective students and is an important first impression for the College,very high quality is required. A. The work includes selective demolition, new framing, new windows, new wood siding and trim, new waterproofed terrace, new slate roofing,new flashing and sheet metal roofing, painting new and reworked existing wood, a barrier-free elevator,complete new mechanical and electrical systems, and other work indicated and specified. B. Work Not In Contract: The following work is not in the Contract: 1. Furnishings. 1.03 TAXES: The Owner is exempt from payment of sales taxes on materials and products permanently incorporated into the work. Provide Owner's tax exemption certificate number on all invoices for materials incorporated into the project and provide two copies of each invoice to the Owner for record. A. Certification Required: Upon project completion, provide a notarized certification to the Owner stating that all purchases made under the tax exemption certificate were legitimate and entitled to the exemption. B. Penalties: Pay all penalties assessed by authorities having jurisdiction for the Contractor's improper or illegal use of the Owner's tax exemption certificate number. 1.04 STANDARDS: Referenced standards are part of the Contract Documents and have the same force and effect as if bound with these specifications. Except where specifically indicated otherwise, comply with the current standard in effect as of the date of the Purchase Order. Where referenced standards conflict or appear to conflict with other referenced standards or with requirements of the Contract Documents or with requirements of authorities having jurisdiction,the most restrictive requirement is hereby required by the Contract Documents. Where the language in any of the referenced standards is in the form of a recommendation or suggestion,such recommendations or suggestions are mandatory and required under this Contract. 1.05 CODES: Strictly comply with all applicable codes,ordinances, regulations and requirements of all authorities having jurisdiction. Submit to the Owner copies of all permits, licenses,certifications, inspection reports, releases, notices,judgements, and communications from authorities having jurisdiction. 1.06 PAYMENT TERMS: Unless otherwise arranged with Owner,payment terms are net 30 days from date of Owner's approval of invoice. 1.07 CHANGES IN THE WORK: All Changes in the work shall be documented, and shall be approved by GENERAL REQUIREMENTS ,� 01000- 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 00840 INSURANCE REQUIREMENTS ]..41 GENERAL A This section specifies the Owner's insurance requirements and relates to the General Conditions of the Contract for Construction. B. Provisions of the General Conditions of the Contract for Construction and Supplementary General Conditions of the Contract for Construction which are not modified by the following Insurance Requirements remain in full effect. INSURANCE REQUIREMENTS A. The insurance required shall be written for not less than the limits of liability required by law or the following limits,whichever is greater: State and Federal Workmen's Compensation Statutory Employer's Liability[Each Accident] $ 100,000. Employer's Liability[Policy Limit for Disease] $ 500,000. Employer's Liability[Per Employee Limit for Disease] $ 100,000. Benefits required by union contract As required. +0 GENERAL LIABILITY' General Liability-Bodily Injury Each Occurrence $ 500,000. General Liability-Bodily Injury Aggregate $ 500,000. ow General Liability-Property Damage Each Occurrence $ 500,000. General Liability-Property Damage Aggregate $ 500,000. 'General Liability shall include coverage for the following: Comprehensive Form Premises/Operations Liability Explosion, Collapse and Underground[XCU]. Products/Completed Operations for two years after final payment +•• Contractual Independent Contractors Broad Form Property Damage MW Personal Injury Including Libel and Slander Coverage, employment exclusion deleted Broad Form Comprehensive General Liability Endorsement Contract Liability-Bodily Injury Each Occurrence $ 500,000. Contract Liability-Bodily Injury Aggregate $ 500,000. am Contract Liability- Property Damage Each Occurrence $ 500,000. Contract Liability-Property Damage Aggregate $ 500,000. AUTOMOBILE LIABILITY" Im Comp.Automobile Liability"-Bodily Injury Per Person $ 500,000. Comp.Automobile Liability"-Bodily Injury Per Accident $ 500,000. Comp.Automobile Liability"-Property Damage $ 500,000. Provide coverage for All Owned, Non-owned, and Hired vehicles. EXCESS LIABILITY[UMBRELLA COVERAGE] Bodily Injury and Property Damage Combined over primary insurance $ 5,000,000. *� B. Exclusions: The Owner's property insurance shall not cover tools, equipment, shoring, staging, forms,temporary buildings or other equipment owned or rented by the Contractor,its Subcontractors, or any worker. END OF INSURANCE REQUIREMENTS INSURANCE REQUIREMENTS 00840 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 00610 "` PERFORMANCE BOND & LABOR AND MATERIALS BOND FORM PART J - GENERAL 1+Q1 PERFORMANCE BOND& LABOR AND MATERIALS BOND FORM A. Provide completely filled out copies of AIA A311. 1. Refer to Instructions to Bidders for the requirements of these bonds. 2. Unless otherwise directed by Owner, Bonds shall be for the entire value of the Contract Amount. 3. Bonds shall be executed by a surety company that is licensed to do business in the Commonwealth of Massachusetts. 4. List cost of bonds separately on Proposal Form. 5. Owner will determine before Contract signing if Bonds are required. PART 2 - PRODUCTS [NOT USED] PART 3 - EXECUTION [NOT USED] .�. END OF SECTION w PERFORMANCE BOND&LABOR AND MATERIALS BOND FORM 00610 - 1 am SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects Signage and Graphics Fire Extinguishers and Cabinets Toilet Accessories Appliances Entrance Mats Elevator Fire Protection Plumbing Heating, Ventilating, and Air Conditioning Electrical[without light fixtures] Light Fixtures[not including fixtures covered by allowance] WORK NOT INCLUDED ABOVE [item¢e separately] SUB-TOTAL OVERHEAD AND PROFIT TOTAL[Must equal base bid.] END OF BID BREAKDOWN FORM k i E r e BID BREAKDOWN FORM 00301 -2 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SECTION 00301 w BID BREAKDOWN FORM 1. Wit: (Bidder: Fill in your complete name and address.) 2. Instructions: Completely fill-in all blanks in this form and attach this form to the Bidder's Proposal Form. Total at bottom must equal base bid proposal. Work to be included in each line Item shall generally follow the subdivision of work as indicated in the specifications. ITEM AMOU NT in dollars General Conditions&General Requirements Owner Directed Allowances[Section 01020] Selective Demolition Site Clearing and Earthwork Termite and Insect Control Site Utilities and Drainage Site Improvements and Landscaping Concrete Masonry Miscellaneous Metals Rough Carpentry Interior Finish Carpentry and Millwork I Exterior Finish Carpentry Sheet Waterproofing at Terrace Dampproofing Insulation and Vapor Barriers Shingle Roofing, Flashing and Sheet Metal Joint Sealers and Fillers Wood Doors[includes metal door frames] Access Doors Wood Windows Finish Hardware Interior Framing Systems Gypsum Drywall Resilient Flooring Acoustical Ceiling Wood Strip Flooring Carpeting Painting ' BID BREAKDOWN FORM 00301 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects percentages for overhead and profit shall include taxes, insurance, and salaries of all employees necessary to administer the work. 9. Bid Breakdown: A complete copy of the bid breakdown included with the bidding documents is attached to this bid. 10. Bidder's On-Site Supervisor: The undersigned certifies that the name and resume of the Bidder's full time on-site supervisor who will be in charge of the project if the Bidder is awarded the Contract is attached to this Proposal Form. [Submit with the bid separately on the Bidder's stationery.] 11. Bidder's Subcontractors: The undersigned certifies that the name and address of the Bidders subcontractors who win be employed on this project the Bidder is awarded the Contract is attached to this Proposal Form. [Submit with the bid separatey on the Bidder's stationery.] 12. By submitting this bid,the Bidder certifies that he has visited the project site, he is aware of existing conditions which may affect his work,he has received and reviewed the Instructions to Bidders and the Contract Documents,and that this bid shan remain in effect THIRTY days after submission. Signed and ,. sealed this day of 19 Bidders Name: By: [Signature] [CORPORATE SEAL HERE] Title: Address: City&State: Telephone: CERTIFICATE AS TO CORPORATE BIDDER l certify that I am the Secretary-Clerk of the corporation named as General Bidder in the attached Bid Form: that who signed said Bid Form on behalf of the bidder was then w. of said corporation;that I know his signature;that his signature thereto is genuine and that said Bid Form was duly signed, sealed and executed for and in behalf of said corporation by authority of its governing body. Secretary-Clerk [Corporate Seal Here] Date 19_ .. END OF PROPOSAL FORM PROPOSALFORM 00300 -2 SMITH COLLEGE,OFFICE OF ADMISSION 02%22/93 David P. Handlin and Associates,Architects SECTION 00300 PROPOSAL FORM 1. Instructions: Submit proposals in strict compliance with Instructions to Bidders. Fill in all blanks. The ON Owner reserves the right to reject incomplete proposal forms. This bidding document is not part of the Contract Documents, unless specifically referenced in the Owner/Contractor Agreement. 2. Bidder: (Bidder. Fill in your complete name and address.) 3. Base Bid: The Bidder proposes to perform all of the Work required by the Contract Documents[not including any performance bonds]for the amount of: (Bidder. Fill in amount in wads and numbers. In cases of conflict between words and numbers, the words shall control.) 4. Bonds: If the Bidder is required to furnish a performance and labor and material payment bond(AIA Form A311)for the entire value of the Work, add the following amount to the Base Bid amount: (Bidder. Fill in amount in words and numbers. In cases of conflict between words and numbers, the words shall control.) +� $ 5. Alternates: Aftemate No. 1: If Alternate No. 1 [ 006 j is selected by the Owner,the Bidder proposes to perform all of the Work required by the Contina Documents for this alternate by adjusting his base bid proposal amount as follows: (Bidder. Fill in amount in words and numbers. In cases of conflict + . between words and numbers, the words shall control.) [ADD] $ 6. Contract Time: (Bidder. Fill in complete dates.) The Bidder proposes to commence work and achieve Substantial Completion [subject to authorized adjustments]on the following dates: A. Proposed Starting Date: B. Proposed Date of Substantial Completion: 7. Addenda: The undersigned certifies that he has received and reviewed the following Addenda and that these Addenda are included in this bid: [List Addenda.] Addendum No. Date: Addendum No. Date: 8. Additional Work: The undersigned agrees to perform any additional work added to the Contract at actual cost plus the following percentage for overhead and profit percent [__O/°]. The undersigned's sub-bidders' maximum percentage for overhead and profit added to the actual cost of any additional work added to the Contract shall be percent[ %]. Such PROPOSALFORM IM 00300 -1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates, Architects SECTION 00230 00 EXISTING CONDITION INFORMATION PART 1 - GENERAL JM RELATED DOCUMENTS A. All of the Contract Documents, including General and Supplementary Conditions and Division 1 General Requirements, apply to this section. 1.02 EXISTING CONDITION INFORMATION A. Information on existing conditions, such as property surveys, existing building dimensions, existing building conditions,and similar information,which is bound with the Contract Documents or otherwise made available to the Contractor was obtained by the Owner for use by the Architect in the design of the project. 1. Not In Contract Documents: This information is not part of the Contract Documents and is made available to the Contractor for information only. 2. Accuracy and Completeness: The Owner and the Architect do not warrant or contend that this information is complete or accurate. The Contractor may use this information at his sole risk and judgment. 3. Concealed Conditions: No claim for extra cost or extension of time may be made because of the use of this information by the Contractor,except as provided in the Conditions of the Contract regarding Concealed Conditions. The Contractor may obtain additional information on existing conditions at his sole expense, if prior approval is obtained from the Owner in writing. PART 2 - PRODUCTS NOT USED PART 3 - EXECUTION NOT USED END OF SECTION 40 EXISTING CONDITION INFORMATION 00230 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects 1. Address Bids To: The Trustees of Smith College,Attention Mr. Robert Lesko 2. Deliver Bids To: Physical Plant Department, Smith College, 126 West Street 3. Bid Due Date: March 9, 1993 4. Bid Due Not Latter Than: 2:00 p.m. PERFORMANCE AND PAYMENT BONDS A. Performance and Payment Bonds: With the bid,fumish the Owner with evidence that the Bidder can obtain a Performance Bond and a Labor and Materials Payment Bond in the full amount of the Contract Price including added alternates. Bonds shall be issued by a surety company that is licensed to do business in the Commonwealth of Massachusetts, State Division of Insurance. Bond form shall be AIA A311 or other form approved by the Owner. B. Bond Cost: List bond costs separately on the bid form in the space provided. C. Additional Bond Documents Required: With each bond, provide certified power of attorney or other certificate of authority where bond is executed by an agent, officer,or other representative of contractor or surety. .06 OTHER REQUIREMENTS A. Contract Time: Time is of the essence in this Contract. The Owner expects the work to begin on or before March 15, 1993 and expects the work to be Substantially Complete by August 27, 1993. Contract time and dates incorporated into the Owner/Contractor Agreement shall supersede these Instructions to Bidders. B. Contractors On-Site Supgryjs: Submit with the bid separately on the Bidder's stationery the name and detailed resume of the Bidder full time on-site supervisor who will be in charge of the project I the Bidder is awarded the Contract. C. Contractor's Subcontractors: Submit with the bid separately on the Bidders stationery the name and address of the Bidders subcontractors who will be in employed on the project If the Bidder is awarded the Contract. D. Jam: The Owner is exempt from payment of Massachusetts Sales Tax. 1. Owners Sales Tax Exemption Numbers: Massachusetts EO 41843040. Federal 04-1843040. 2. Copies of Receiot�quired: In compliance with IRS regulations,the Contractor shall provide • the Owner with copies of all receipts for materials and products used for this Contract purchased using the Owners Tax Exemption Number. ]�QZ CONTRACT AWARD A. Bid Qpening and Disoo� Bids will be opened in private and bidders will not be present. The bids may not be withdrawn for 30 days after receipt of bids. B. Bids May Be Rejected: The Owner reserves the right: to waive informalities in any or all bids; to reject any or all bids; to revised the Contract Documents and rebid to meet its budget; to reject specific subcontractors, and to enter into negotiations with any bidder. END OF INSTRUCTIONS TO BIDDERS INSTRUCTIONS TO BIDDERS 00100 -3 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 �» David P. Handlin and Associates,Architects C. Form of Aare An example Form of Owner/Contractor Agreement is included in the bidding documents. D. Questions_Clarifications and --etat_ Biers shall promptly notify the Architect of sow questions,ambiguities, inconsistencies, errors,or omissions,which they may discover upon examination of the Contract Documents,the site, and local conditions. 1. Written Rea ie� st Rea aired: Submit written requests for clarification and interpretation to the mom Architect by mail or fax. 2. Time R Mired: Requests for clarifications and interpretations must be received by the .W Architect at least five working days prior to the date bids are due. 3. Architect's Response. Addenda: The Architect's response will be in the form of a written 4M Addendum which shall become part of the Contract Documents. Clarifications and interpretations offered by the Owner,the Architect,or any of the Architect's consultant's in any form other than a formal written Addenda shall be invalid and shall have no validity. am 4. Issuance of Addenda: Addenda will be issued by mail or fax to every bidder on record as having obtained bid documents. ow 5• Addenda Must Be Acknowledged: Bidders shall acknowledge Addenda in the spaces provided on the bid forms. Failure of a bidder to acknowledge Addenda in the spaces provided on the bid form may cause rejection of the bid. Failure of a bidder to receive arty addenda shall not am relieve it from any obligation under its bid as submitted. LOA PREPARATION ANp RMIS-SION OF BIDS A. Completion of Bid Forms: Use only the Bid Forms fumished with the bidding documents. Additional forms will not be mailed by the Architect. Complete Bid Forms with typewriter or hand printed in ink. , B. Alterations Not Permitted: Do rot alter bid forms. Do rat include any recapitulation of the work to be done. Do not provide any information not requested. Do not strike out, line out,white out,or erase any information. C. Amounts: Express amounts in both words and numbers where space for both is provided. In cases of conflict,written amounts shall control over numbers. D. Blanks: Complete all spaces provided. Do not leave any blanks. Print"N/A"in arty space not needed or used. E. Bid Withdrawal: Any bid may be withdrawn by mailed written request,faxed written request,or telegraphic request prior to date and time of receipt of bids. Withdrawn bids may be resubmitted -ft until date and time of receipt of bids. 1. Modifications: No written,oral,telephone,or telegraphic modifications to bids will be considered after the bid is received. F. Bid Deposit (Bid Security],: A Bid Deposit[Bid Security]is not required. G. Bid Submission: Submit bid forms and bid deposit, if required, in a sealed enve boldly identify envelope with: 1 name of the Clearly and l project; 2)the name of the Owner; 31 the name, business address, and business telephone number of the bidder; and 4] "BID ENCLOSED". Submit bids as follows: INSTRUCTIONS TO BIDDERS 00100 -2 �,, SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects MW SECTION 00100 00 INSTRUCTIONS TO BIDDERS PART 1 - GENERAL J= IDENTIFICATION A. Owner: The Trustees of Smith College, Physical Plant Department 1. Address: 126 West Street, Northampton, MA 01063 2. Telephone: 413-585-2400 3. Fax Number: 413-585-2444 4. Contact Person: Mr. Robert Lesko and Ms.Amy Holich B. Architect: David R Handlin and Associates,Architects 1. gees: 104 Mount Auburn Street, Cambridge, Massachusetts 02138 2. Telel2hone: [617] 576-1496 3. Fax Number: [617] 576-1346 4. Contact Person: David R Handlin,Architect J= BIDDING DOCUMENTS A. Instructions to Bidders: This"Instructions to Bidders"contains important information about bidding procedures and is intended to provide guidance and assistance to bidders. This"Instructions to Bidders"is not part of the Contract Documents,unless specifically referenced or itemized in the Owner/Contractor Agreement. B. To Obtain Bidding Documents: Contact Smith College. Documents will be available at Smith College after 2:00 p.m., February 22, 1993. C. Bid Documents: Bid documents consists of one set of of Contract Document Drawings and one copy of the Contract Document Project Manual. 1. Bidders may obtain two bid sets. 2. Bid sets will be issued only in complete sets. ]iQ BIDDING REQUIREMENTS A. Site Visit Required: Each bidder shall visit the site of the proposed work and become fully and completely aware of all existing conditions, existing facilities, and the character of the operations to be carried on under the proposed Contract. Each bidder shall make itself fully understand the facilities,physical conditions, and restrictions attending the work under the Contract. Failure to make such examinations will not relieve the bidder from any obligation under the bidder's bid as submitted,nor shall it serve as the basis for change orders or equitable adjustments. 1. To Arraoge Site Visit: Contact Smith College, Physical Plant Department. B. Document Examination: Each bidder shall thoroughly examine and become familiar with the Contract Documents and the Bidding Documents. Failure to make such examinations will not relieve the bidder from any obligation under the bidder's bid as submitted, nor shall it serve as the basis for change orders or equitable adjustments. INSTRUCTIONS TO BIDDERS go 00100 - 1 SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SPECIFICATION TABLE OF CONTENTS LATEST DOCUMENT DATE �. 08305-Access Doors and Panels 02/22/93 08600 -Wood Windows 02/22/93 08700-Finish Hardware 02/22/93 08800-Glass and Glazing 02/22/93 DIVISION 9-FINISHES 09100-Interior Light Gage Metal Framing Systems 02/22/93 09250-Gypsum Drywall 02/22/93 09510-Acoustical Ceilings 02/22/93 09550 -Wood Flooring 02/22/93 09650- Resilient Flooring and Base 02/22/93 09680-Carpet 02/22/93 "'° 09900 - Painting 02/22/93 DIVISION 10-SPECIALTIES TIES 10440 -Signage 02/22/93 .. 10520- Fire Extinguishers and Cabinets 02/22/93 10800-Toilet Accessories 02/22/93 DIVISION 11 -EQUIPMENT 11450-Appliances 02/22/93 DIVISION 12-FURNISHINGS .� 12390- Premanufactured Cabinets 02/22/93 12690- Entrance Mats 02/22/93 DIVISION 13-SP CIAI CONSTRI CT10N Not used DIVISION 14---CONVEYING SYSTEMS , 14240-Hydraulic Elevator 02/22/93 DIVISION 15-M CHANICAI 15300- Fire Protection 02/22/93 15400 - Plumbing 02/22/93 15500- Heating, Ventilating, and Air Conditioning 02/22/93 DIVISION 16- E ECTRIQAI 16100- Electrical 02/22/93 END OF TABLE OF CONTENTS TABLE OF CONTENTS-2 ., SMITH COLLEGE,OFFICE OF ADMISSION 02/22/93 David P. Handlin and Associates,Architects SPECIFICATION TABLE OF CONTENTS LATEST DOCUMENT DATE Title Page Copyright Notice Table of Contents BIDDING DOCUMENTS CONTRACT FORMS &CONDITIONS OF THE CONTRACT 00100- Instructions to Bidders 02/22/93 00230 - Existing Condition Information 02/22/93 00300- Proposal Form 02/22/93 00301 - Bid Breakdown Form 02/22/93 00500-Owner/Contractor Agreement [AIA A107] 1987 Edition 00610-Performance Bond&Labor and Materials Bond Form 02/22/93 00840 - Insurance Requirements 02/22/93 DIVISION 1 -GENERAL REQUIREMENTS 01000-General Requirements 02/22/93 01020 -Allowances 10/23/92 01030 - Alternates 10/23/92 DIVISION 2-SITEWORK 02071 - Selective Demolition 02/22/93 02100-Site Preparation and Clearing 02/22/93 02200-Site Clearing and Earthwork 02/22/93 02280-Termite and Insect Control 02/22/93 02500- Pavers 02/22/93 02510 -Asphalt Concrete Paving 02/22/93 02710- Foundation Drainage 02/22/93 DIVISION 3-CONCRETE ,.. 03300 - Concrete 02/22/93 DIVISION 4-MASONRY 04200- Unit Masonry 02/22/93 04520 - Masonry Repointing 02/22/93 DIVISION 5-METALS 05120 - Structural Steel 02/22/93 05500 - Miscellaneous Metals 02/22/93 DIVISION 6-WOOD AND PLASTICS 06100 - Rough Carpentry 02/22/93 06205- Interior Finish Carpentry 02/22/93 06210- Exterior Finish Carpentry 02/22/93 06410 - Countertops 02/22/93 DIVISION 7-THERMAL AND MOISTURE PROTECTION 07115 - Sheet Waterproofing 02/22/93 07160 - Bituminous Dampproofing 02/22/93 07180 -Cementitious Dampproofing 02/22/93 07200- Insulation 02/22/93 07270 - Firestopping 02/22/93 07315 - Shingle Roofing 02/22/93 07600- Flashing and Sheet Metal 02/22/93 07900-Joint Sealers and Fillers 02/22/93 DIVISION 8-DOORS AND WINDOWS 08200-Wood Doors[includes metal door frames for fire-rated doors] 02/22/93 TABLE OF CONTENTS- 1 ..w w *N{ Project Manual and Specifications for SMITH COLLEGE, OFFICE OF ADMISSION 01992 and 1993 Richard D. White, CCS [508] 222-SPEC All Rights Reserved Except for the limited license granted for use with this Project, no portion of these Specifications may be reprinted in whole or in part without first obtaining the written permission of the copyright owner. Project Manual for SMITH COLLEGE 0 FFICE OF ADMISSION David P. Handlin and Associates, Architects 104 Mount Auburn Street Cambridge, Massachusetts 02138 [617] 576-1496 [617] 576-1346 Fax gun ®R February 22, 1993