Loading...
23B-046 (157) 1 ']✓,�`! ,S?Y, " 'YTS_.. w - E SPW 1-11 Al bit . s . + ,.g N yy y _r ;'�E•"�4'�5'-:��ti LM1r�fi[h r^��r t k'0:';'Ay E'}T t I`l<�SrZ`r�V•t•'y'M 5%l f,fir, e•t a ,��. 1 1..-12 1 j a 1-79 I_i 1_81 2 7 1-125 -12 03 102 1`9JiQ6 -9 -91 1-99 1 101 1-93 -92 1-95 M. m 0& wr�� wo .w.r.r.lm.um n.mmum"M � LML`KS � 1-8 88 114 .. t ' .. M K 1-89 inM. a,., Z -HOUR EIRE BARRIER 'n f Y� � rob � •�. - F H G-176 � riHyad Y, r it .t G-178 G-177 l w 18 - J 1 t —180 G-17 � 1 1 T G 18 LG—16 17 t p. G--165 G-164 t k 1,cw G�159 �fiy lot .'fk r r#, t {s G-166. G-163 —1 G-161 G-160 G-158 t t �-�169 iM • oir riY� •'Iir Mr�rrYr w� • mm I m w w m �� im 1.. 4o..rr.�■ w �r� lift mm�r r m t - t P 4 �yp gry� 1 K '� tr EXISTING HEALTH CARE OCCUPANCIES 669 ii If Suite < 10,000 sq It X Distance: (930 sq m) Subdivision Walls X C Must Be < 50 ft Within Suite Need Not (15 m) Per 13-2.5.4 Comply With 13-3.6 But May C — E Must Be < 100 ft Be Of Nonfire-Rated, Non- (30 m) Per 13-2.6.2 Combustible, Or Limited- X — E Must Be < 150 ft Non-Slee m Suite, p' g 9 Combustible Partitions. (45 m) Per 13-2.6.2 0 Such As A Surgical r ; Suite If Suite > 10,000 sq ft (930 sq m) k; 13-2.5.1 Must Be Complied With. z if Note: C r E And X +E Only May Be+50 ft(15 m) If Building Is Sprinklered ying With C Corridor Walls Complying E With 13-3.6 And 13-2.3.3 i b ! i I'.Flf soms to an Existing # ''• P 13-2.5.2. The suites l , #a and c. Figure 13-10c. Suites Not Involving Patient Sleeping Rooms in an Existing 1 Health Care Occupancy. The requirements of 13-2.5.2, 13-2.5.4, and 13-2.6.2 for There is No More Than suites not involving patient sleeping rooms are illustrated. The suite must comply t One Intervening Room with Figures 13-10a and b or 13-10a and c. Between A Patient Treatment Area And A Corridor. In This Case 13-2.5.5* Every corridor shall provide access to at least two approved exits in The Aisle"a"Within accordance with Sections 5-4 and 5-5 without passing through any intervening rooms on t The Suite Is Considered spaces other than corridors or lobbies. An Intervening Room. p 4 Exception: Existing dead-end corridors may be continued in use if it is not practical and #;' Note That 13-2.6.2 � Requires That Distance: " feasible to alter them so that exits will be accessible in at least two different directions from all X — C Be < 100 ft(30 m) point) in aisles, passageways, and corridors. C — E Be < 100 ft (30 m) X — E Be <150 ft (45 m) A-13-2.5.5 Every exit or exit access should be so arranged, if practical and feasible, Note:C — E And X — E Only that no corridor, passageway, or aisle has a pocket or dead end exceeding 30 ft (9.1 m). May Be+50 ft (15 m) If Building (Also see Table A-5-6.1.) Is Sprinklered Exit access corridors, aisles, and passageways should preferably be arranged so that exits will be accessible in at least two different directions I from all points in the corridor, aisle, or passageway. However, in many i'y# inplying With buildings, dead-end corridors exist. The Code intends to allow dead-end ,.3 corridors of moderate length to remain without correction. In all instances, dead-end corridors up to 30 ft (9.1 m) may remain in = use without correction. For dead-end corridors in excess of 30 ft (9.1 m), � $ ,oms in an Existing considerable judgment must be exercised in determining what constitutes .5.4, and 13-2.6.2 are an excessive dead-end pocket. Where a dead-end corridor is judged 9�P r 13 wa and c. excessive, corrective action. should be taken either by provision of 668 LIFE SAFETY CODE HANDBOOK If Suite < 10,000 s(, If Suite Over 2500 sq It (930 sq m) Subdivis, (230 sq m) 2 Doors Are Within Suite Need r; Required And They Be 0 I Comply With 133.6 Must Be As Remote Nonfire-Rate(� From Each Other As Combustible, Or Lin, Practical.As A Guide,"d" Non-Sleeping Suite,Such As A Surgical Combustible Partitio, Should Be At Least'/� "D"(See Section 5-5) p Suite If Suite > io,000 sq, 13-2.5.1 Must Be Cc, With. d-------- -Corrid or Walls complying with T' 13-3.6 And 13-2.3.3 E Figure 13-10a. Suites Not Involving Patient Sleeping Rooms in an Existing Health Care Occupancy. This illustrates the provisions of 13-2.5.2. The suites must comply with Figures 13-10a and b or 13-10a and c. Figure 13-10c. S Health Care occtil, If Suite < 10,000 sq ft There Is No More Than suites not involving (9 30 sq m) Subdivision Walls One Intervening Room Within Suite Need Not a X Between A Patient Comply With 13-3.6 But May Treatment Area And A Be Of Nonfire-Rated, Non- Corridor. In This Case 13-2.5.5* Every cot Combustible, Or Limited- The Aisle"a"Within accordance with Sectio, Is Combustible Partitions. a The Suite Is Considered An Intervening Room. spaces other than coril,� If Suite > 10,000 sq It (930 sq m) Then Aisle Note That 13-2.6.2 Exception.- Exiving A, Requires That Distance: a"Would Be Required feasible to after 111e)n jo t/ To Meet All Corridor X - C Be �� 100 it(30 m) Pointf in aisles, pamageu Requirements(13-3.6 And C - E Be < 100 it (30 m) 13-2.3.3) X - E Be <150 It (45 m) A-13-2.5.5 Every exit a Note:C - E And X - E Only that no Corridor,passag, May Be+50 ft (15 m) If Buildii (Also jee Table A-5-6.1.' Is Sprinklered Exit access co, C arranged so that c E from all points ir VF-1 Corridor Walls Complying With buildings, dead-er 13-3.6 And 13-2.3.3 corridors of mod, FEIF-zEl In all instances, use without corre, considerable judg, Figure 13-10b. Suites Not Involving Patient Sleeping Rooms in an Existing Health Care Occupancy. The requirements of 13-2.5.2, 13-2.5.4,and 13-2.6.2 are an excessive dea, illustrated. The suite must comply with 13-10a and b or 13-10a and c. excessive, correct 6. 1 rd EXISTING HEALTH CARE OCCUPANCIES' 667 viously ct ct }` Max Of One Intervening and d Room (13-2.5.1). if Individual call not E Cubicals Became Enclosed fir. As A Room Then Egress Could Not Go through h This Room. r 't ing ii it nits ,ith for 122 �4 Tres If Suite < 5000 sq ft �{ (460 sq ft)And If Special Nursing Direct Constant Visual C Suite Supervision Is Provided ;(` By Nursing Staff, Suite May Be Subdivided (!) With Non-Rated, Non- Combustible, Or Limited-Combustible { { { uires That Dist Note That 13-2.6.2 Re \e: l fl Partitions. q it X — C < 100 It (30 m) C — E 5 100 It(30 m) X — E < 150 It(45 m) Note C — E And X —E Only May Be+50 ft(15 m) If Building Is Sprinklere(f �s Figure 13-96, Suites Involving Patient Sleeping Rooms in an Existing Health �s Care Occupancy. The requirements of 13-2.5.1, 13-2.5.2, 13-2.5.3, and 13-2.6.2 ,, for patient sleeping suites are illustrated.The suite must comply with Figures 13-9a r' tt, and 13-9b. Ek: 13-2.5.4 Any suite of rooms, other than patient sleeping rooms, that complies with the requirements previously set forth in this section may be subdivided with ' 1 non-fire-rated, noncombustible, or limited-combustible partitions. Such suites shall not exceed 10,000 sq ft (930 sq in) in area and either: ter i' (a) The maximum travel distance from any point in the suite to a corridor door shall 4i+ be limited to 50 ft (15 m), or i (b) There shall he unrestricted access from patient treatment areas to a corridor with a Il`+. maximum of one intervening room. i ra The requirements of 13-2.5,4 are illustrated in Figures 13-10a, 13-10b, and 13-10c. c: t { ii s, ,i By i(--" t It a rea'; 'j i I ? }.ti s 1.ffF� ._l bor a L F V 1-1 Ckf r j d corl, t11 1 ll(�i' h000mc- or J t !-"I,l I i-?,h c,r'i w t t 1 1 ow 1 aboi- i i r I i z )a 1: f t -i T'P d I r u I-i Old -n t a n o f cv); u,4 rn'l j is !()t a 11(4 1) 11 'i vo ry L.( o t-i d i i 1 1,v T f lo c.i r i 10 !n rI I H I A i i V APR 2 6 l9es -- Ail } a a HEALTHCARE ARCHITECTS INC. Mr. Anthony L. Patillo, Building Commissioner City of Northampton CORPORATE DIRECTORS Office of the Building Inspector goy S. &wwn.AI A. 212 Main Street $dward L Jendry.A.I.L Northampton, Massachusetts 01060 SE GOR PRINCIPALS C. J. Rhitham Re: Existing Hospital Laboratory PRINCIPAM Cooley Dickinson Hospital York T. nu,nAI Dan gainer Dear Tonv: Richard I£ Katsanos " A= Iawnnoe Rno: Fd°h"dp• WUk This letter is a follow-up to our previous telephone ENGINEERING ASSOCIATES conversation relative to the designation of the llmlam Y. Barry.P.S. Hospital ' s existing Laboratory areas as a suite as Ronald G. Stenlund.P.1ti. per N.F.P .A. (101) Life Safety Code, Chapter 13 . Chapter 13 , Paragraph 13-2. 5. 4 , of the Life Safety Code allows for suites of rooms in hospitals that are not designated for sleeping purposes to be designated as "suites" . This terminology allows the departmental area to be sub-divided by non-fire- rated, noncombustible partitions . Please see the attached copy of the Life Safety Code Handbook for your review. The Hospital would like to designate its existing Laboratory, which exists on two floors of the old Shepard Wing, as suite areas . The areas in question meet the requirements for a suite area, i .e . : 1 . Less than 10 , 000 square feet in area. 2 . ;Maximum travel distance of 50 feet from anywhere in the suite to a corridor door or exit . The Hospital would install new fire-rated doors , frames and hardware at the main Hospital corridor that services the Shepard Wing to fire-separate the area off as a suite on the Ground Floor level and the First Floor level . 1 of 2 64 GOTHIC MWW / NOMRAUMN. YA.49ACEMSMS 01060 (419) 586-1512