Loading...
223300_ElectricDomesticWaterHeatersCOCA-COLA NORTH AMERICA JOB NO. 7588.20 ISSUED: 070910 LINE ADDITIONS NORTHAMPTON, MASSACHUSETTS ELECTRIC DOMESTIC WATER HEATERS 223300 - 1 of 3 SECTION 223300 ELECTRIC DOMESTIC WATER HEATERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The other Contract Documents complement this Section. B. Division 01 – General Requirements and Section 220000 govern all Work of Division 22. C. Other specification sections (Divisions 02-14, 21, and 23-26) may contain requirements related to Division 22. 1.02 SUMMARY A. This Section includes the following electric water heaters: 1. Light-commercial, storage electric water heaters. 2. Water heater accessories. 1.03 SUBMITTALS A. Refer to procedures for submittals in Section 013323, “Shop Drawings, Product Data, and Samples.” B. Action Submittals: 1. Submit product data for each water heater specified. Include dimensional information, rated capacities, operating characteristics, furnished specialties, accessories, and electrical characteristics. Clearly indicate, by highlighting or itemized lists, all differences to “Design Basis” product features. 1.04 QUALITY ASSURANCE A. Source Limitations: Obtain same type of electric water heaters through one source from a single manufacturer. B. ASME Compliance: Where indicated, fabricate and label commercial water heater storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. C. Comply with NSF 61, “Drinking Water System Components – Health Effects; Sections 1 through 9,” for all components that will be in contact with potable water. COCA-COLA NORTH AMERICA JOB NO. 7588.20 ISSUED: 070910 LINE ADDITIONS NORTHAMPTON, MASSACHUSETTS ELECTRIC DOMESTIC WATER HEATERS 223300 - 2 of 3 PART 2 - PRODUCTS 2.01 LIGHT-COMMERCIAL, STORAGE ELECTRIC WATER HEATERS A. Description: Comply with UL 174 or UL 1453 for storage electric water heaters and listed by manufacturer for commercial applications. Capacity not less than 6 gallons and not more than 40 gallons and input not more than 12 kW. 1. Manufacturer: Design basis manufacturer(s) and specific product(s) are indicated on the drawings. Additional product information and other requirements are specified herein. 2. Where it is proposed that a product of one of the following manufacturers is to be used in lieu of the “design basis” specified on the drawings, follow the procedures for Other Products in Division 01 Section 016100, “Products, Materials, and Equipment,” and provide full product data for each product and direct comparative evidence of full equivalency to the “design basis.” a. Bradford White Corporation. b. Smith, A. O. Water Products Company. 3. Storage-Tank Construction: Steel, vertical arrangement. a. Tappings: ASME B1.20.1 pipe thread. b. Pressure Rating: 150 psig. c. Interior Finish: Comply with NSF 61 barrier materials for potable-water tank linings, including extending lining material into tappings. 4. Factory-Installed Storage-Tank Appurtenances: a. Anode Rod: Replaceable magnesium. b. Dip Tube: Provide unless cold-water inlet is near bottom of tank. c. Drain Valve: ASSE 1005. d. Insulation: Comply with ASHRAE/IESNA 90.1 or ASHRAE 90.2. e. Jacket: Steel with enameled finish. f. Heat Trap Fittings: Inlet type in cold-water inlet and outlet type in hot- water outlet. g. Heating Elements: Electric, screw-in immersion type. h. Temperature Control: Adjustable thermostat for each element. i. Safety Control: High-temperature-limit cutoff device or system. j. Relief Valve: ASME rated and stamped and complying with ASME PTC 25.3 for combination temperature and pressure relief valves. Include relieving capacity at least as great as heat input, and include pressure setting less than water heater working-pressure rating. Select relief valve with sensing element that extends into storage tank. 2.02 WATER HEATER ACCESSORIES A. Drain Pans: Corrosion-resistant metal with raised edge. Include dimensions not less than base of water heater and include drain outlet not less than NPS 3/4. COCA-COLA NORTH AMERICA JOB NO. 7588.20 ISSUED: 070910 LINE ADDITIONS NORTHAMPTON, MASSACHUSETTS ELECTRIC DOMESTIC WATER HEATERS 223300 - 3 of 3 B. Piping-Type Heat Traps: Field-fabricated piping arrangement according to ASHRAE/IESNA 90.1 or ASHRAE 90.2. PART 3 - EXECUTION 3.01 WATER HEATER INSTALLATION A. Install water heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible. B. Install combination temperature and pressure relief valves in top portion of storage tanks. Use relief valves with sensing elements that extend into tanks. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain. C. Install water-heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose-end drain valves at low points in water piping for water heaters that do not have tank drains. Refer to Division 22 Section “Water Distribution Piping Specialties” for hose-end drain valves. D. Install thermometer on inlet and outlet piping of water heaters. E. Install piping-type heat traps on inlet and outlet piping of water heater storage tanks without integral or fitting-type heat traps. F. Fill water heaters with water. 3.02 CONNECTIONS A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to water heaters to allow service and maintenance. Arrange piping for easy removal of water heaters. END OF SECTION