Loading...
HERS-110 96 Moser St air leakageAir Leakage Property Wordelman & Loehr 96 Moser St Northampton, MA 01060 Weather:Northampton, MA 96 Moser St HERS-110 96 Moser St registered.blg Organization Power House Energy Consulting 413-835-5162 Matt Turcotte Builder Pecoy Companies Whole House Infiltration ASHRAE 62.2 - 2010 Ventilation Requirements For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, a minimum of 52 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjusted accordingly. For example, a 103 cfm mechanical ventilation system would need to operate 12 hours per day, as long as the system operates to provide required average ventilation once each hour. REM/Rate - Residential Energy Analysis and Rating Software v14.2 This information does not constitute any warranty of energy cost or savings. © 1985-2013 Architectural Energy Corporation, Boulder, Colorado. HERS Confirmed 8/28/13 Rating No:HERS-110 Rater ID:1497133 Duct Leakage Ventilation Blower Door Test Heating Cooling Natural ACH 0.07 0.05 Leakage to Outside Units ducts Mechanical Balanced ACH @ 50 Pascals 1.08 1.08 CFM @ 25 Pascals 11 Sensible Recovery Eff. (%)67.0 CFM @ 25 Pascals 284 284 CFM25 / CFMfan 0.0088 Total Recovery Eff. (%)52.0 CFM @ 50 Pascals 446 446 CFM25 / CFA 0.0051 Rate (cfm)52 Eff. Leakage Area (sq.in)24.5 24.5 CFM per Std 152 N/A Hours/Day 24.0 Specific Leakage Area 0.00008 0.00008 CFM per Std 152 / CFA N/A Fan Watts 24.0 ELA/100 sf shell (sq.in)0.39 0.39 CFM @ 50 Pascals 17 Cooling Ventilation Natural Ventilation Eff. Leakage Area (sq.in)0.95 Thermal Efficiency N/A Total Duct Leakage Units CFM25/CFA Total Duct Leakage 0.1200