Loading...
175 Industrial Drive Saint Gobain FD ReviewNorthampton Fire Department Memorandum To: Louis Hasbrouck From: Duane Nichols Date: September 9, 2010 CC: Brian Duggan, Larry Therrien Re: 175 Industrial Drive , Saint Gobain Secondary to a review narrative submitted to me for review, I concur with the issuance of a building permit subject to the following conditions: Fire alarm work permits shall be obtained for the project. The C/O inspection fee needs to be paid prior to approval of any fire alarm plan. The Fire Alarm Control Panel and Fire Alarm Annunciator must be labeled with red engraved signage with one-inch white lettering “Fire Alarm Control Panel” and/or “Fire Alarm Annunciator”. Also engraved signage listing all fire alarm zone locations installed near panels. A graphic representation of the structure with the new changes must be installed at the Fire Alarm Control Panel (FACP) and/or Fire Alarm Annunciator and/or Communicator. Pull Stations shall be double action type. A Fire Department Emergency Access Key Box is required on the exterior of the structure near the entrance to control equipment; a red 120-candela strobe light that actuates upon an alarm condition is required above the Emergency Access Key Box. Engraved key tags are required for the keys in Emergency Access Key Box. 5 lb ABC Fire extinguishers are needed located at exits. This shall be in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should be located above.