Loading...
approval letter January 28, 2011 DohertyFebruary 14, 2011 Wright Builders, Inc. 48 Bates Street Northampton, MA 01060 Subject Property: 119 North Maple Street Florence, MA 01062 Mr. Pichette The plans for the Doherty project dated 2-09-11 have been approved as noted; Structure conforms to 780 CMR 7th addition 1 and 2 family with 2009 IECC prescriptive requirements or RES Check 4.4.1 and mandatory requirements. Smoke and CO detectors per code and plan. A continuous air barrier is required behind tubs, spas, showers, fire places and electric boxes on exterior walls! Watch out or the tub comes out. Energy information and equipment must be posted on the electric panel upon completion. Each unit shall have a heat detector within the unit connected to a smoke detector in the stair hall. LVL shall have a minimum of 1 ½” bearing per manufacturers requirements. 5/8” drywall shall be installed over the disappearing stair cover panel. Shear panels or an equivalent system shall be installed in the garage. Charles Miller Assistant Commissioner of Buildings