25A-190 (5) PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 1. All pressure gauges and test drain outlets are integral to the sprinkler/standpipe system; additional gauges are not required for testing. 2. Flow and pressure gauge assembly for the testing of direct acting reducing valves. C. SECTION 3 —Approval Requirements A. Certification in written form as agreed to by all parties from the Code Official that the systems as designed, installed and tested satisfy all operational and code compliance requirements. B. Documented method for remedial action if any system fails to operate to the satisfaction of the Code Official. C. Certification from the Registered Professional Engineers of record stating that the fire protection systems have been installed in accordance with the approved fire protection construction documents. The certification shall state that the engineer has reviewed the shop drawings for conformance to 780 CMR 901.7.1.1 and has identified deviations, if any, from the approved fire protection construction documents. D. Confirmation by the Building Owner that they have received the as-built fire protection system shop drawings from the installing contractor and that the Registered Professional Engineer has certified their reasonable accuracy. E. Listing of names, addresses and telephone numbers of service personnel for emergency notification. 12 • PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 g. Testing of each notification device and all notification circuits for proper sequence of operation and proper response at the Fire Alarm System Control Panel. h. Test audio visual devices with sound and light meters. Testing of the system for all specified functions according to the approved operation and maintenance manual and the system sequence of operation. j. Testing of primary and secondary power supplies including verification that the secondary power system is capable of operating the system for the period and in the manner specified. If any system fails to operate to the satisfaction of Building and/or Fire officials, the failed component or part of the system or function will be corrected immediately. Any reacceptance testing of fire alarm system devices and/or water supply system controls shall be performed in accordance with NFPA 72 (2007). Upon completion of successful performance of the fire protection systems the contractor shall submit "System Certification" stating that the systems installed are in compliance with the Fire Protection Construction Documents as well as all applicable Codes and Standards. B. SECTION 2 — Equipment and Tools A. Any equipment and/or tools required for testing will be provided by the respective subcontractor's as required by manufacturer's recommendations, field conditions and any other requirements. B. In general, the following items are required for the acceptance testing of the fire protection systems: 1. Manufacturer's Instructions 2. Fire Protection Systems Narrative 3. Communication Radios C. Fire Alarm System Testing 1. Heat source for testing of heat detectors. The heat source may be a hair dryer, heat lamp, etc. 2. Smoke source for testing of smoke detectors. Testing may be performed with canned smoke, smoke candles, smoke machine, etc. Testing with magnets is prohibited. 3. Volt/ohm meter for control unit testing. 4. ANSI 1.4a sound level meter for testing of notification appliances. D. Sprinkler/Standpipe System Testing 11 • PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 premises. Valve supervisory switches will be tested by actual operation of the valves. The sprinkler contractor shall provide the Owner with a Contractor's Material and Test Certificate for Aboveground Piping as required by NFPA 13 (2007). 7. Fire Alarm System a. Testing of the fire alarm system shall be performed in accordance with NFPA 72 and 780 CMR. Before this installation shall be considered complete and acceptable to Authorities, a complete test on the system shall be performed as follows: • Pretesting: After installation activate and adjust the system as needed and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Fire Protection Construction Documents. Correct deficiencies observed in pretesting. Replace any malfunctioning or damaged items with new and retest system as required until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results. After pretesting is complete, provide written confimration to the Owner certifying the installation is complete and fully operable, including the names and titles of the witnesses to the preliminary tests. • Final Test Notice: Provide a ten (10) day minimum notice in writing when that the Owner has received written confirmation that pretesting has been completed and that the system is ready for final acceptance testing. • Final System Testing and Acceptance: Testing of the fire alarm system shall be performed in accordance with NFPA 72 and 780 CMR. Minimum required testing shall include: b. Verification of the absence of unwanted voltages between circuit conductors and ground. c. Testing of all conductors for short circuits using an insulation-testing device. d. Short circuit testing at the far end of the circuit and measure the circuit resistance with an ohmmeter for each circuit pair. Circuit resistance of each circuit shall be recorded on the project Record Drawings. e. Verification that the Fire Alarm System Control Panel and all annunciators are in the normal condition as detailed in the manufacturer's operation and maintenance manual. f. Testing of each initiating device and all indicating circuits for proper sequence of operation and proper response at the Fire Alarm System Control Panel. Test smoke detectors with actual products of combustion 10 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 f. Upon receipt of any fire alarm system trouble or supervisory signal, the fire alarm system shall initiate the following: • Ring trouble bell and annunciate at the FACP and graphic annunciator • Record the event 901.2.1.1 (a.iii) - TESTING CRITERIA A. SECTION 1 —Testing Criteria 1. The General Contractor shall be responsible for setting up and coordinating all fire protection systems testing. The following documents must be submitted to the Building Official and the head of the City of Northampton Fire Department or their designees prior to the witnessing of the operational fire protection systems testing (780 CMR Section 901.7.4): 2. Certification from the Registered Professional Engineer responsible for design stating that the fire protection systems have been installed in accordance with the approved fire protection construction documents. It shall also state that the engineer has reviewed the shop drawings for conformance to 780 CMR 901.7.1.1 and has identified deviations, if any, from the approved fire protection construction documents. 3. Confirmation by the Building Owner that they have received the as-built fire protection system shop drawings from the installing contractor and that the Registered Professional Engineer has certified their reasonable accuracy. 4. Material, Test, Performance and Completion Certificates, properly executed by the installing contractor in accordance with the applicable NFPA Standards. 5. Listing of names, addresses and telephone numbers of system service personnel for emergency notification. Prior to any Fire Department acceptance testing, sprinkler test, egress lighting test and fire alarm system tests shall be performed per the Project Commissioning Plan. 6. Fire Sprinkler System a. Final system acceptance requirements for the fire sprinkler system will be as required by applicable sections of NFPA 13 (2007), NFPA 25 (2008) and 780 CMR. b. The fire sprinkler system will be hydrostatically tested in accordance with NFPA 13 at 200 psi for a period of two hours at the minimum. All valve supervisory switches and water flow indicators will be tested for proper operation and integration into the building fire alarm and fire alarm reporting system as required by NFPA 72. Water flow detecting devices including the associated alarm circuits will be flow tested through the inspectors test connection and will result in an audible alarm on the 9 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 • Alarm notification shall begin. • All of the visual signals (strobe lights) shall flash throughout the structure in a synchronized manner. • Identify alarm at the fire alarm control panel (FACP) and graphic annunciator panel. • Transmit an alarm signal to the remote alarm receiving station. • Transmit an alarm signal to the Northampton Fire Department central monitoring agency upon alarm. • Operate rotating beacon at exterior of the building. • Switch heating, ventilating, and air-conditioning equipment controls to fire alarm mode. • Shut down smoke dampers in air ducts of system interlocked with the unit in alarm only. • Record events in the system memory. d. Operation of any of the following devices shall initiate the fire alarm system supervisory signal: • Fire-protection system valve tamper • Low air pressure at dry pipe system e. Operation of any of the following devices, or occurrence of any of the following conditions shall initiate the fire alarm system trouble signal: • Open circuits, shorts and grounds of wiring for initiating device, signaling line, and notification-appliance circuits. • Opening, tampering, or removal of alarm-initiating and supervisory signal-initiating devices. • Loss of primary power at the FACP. • Ground or a single break in FACP internal circuits. • Abnormal ac voltage at the FACP. • A break in standby battery circuitry. • Failure of battery charging. • Abnormal position of any switch at the FACP or annunciator. 8 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 901.2.1.1 (a.ii) - SEQUENCE OF OPERATION a. The occurrence of fire or any another source of heat generated in a sufficient amount to fuse heat sensitive elements at individual fire sprinklers or a break at any point within the fire sprinkler system or any other situation that would create a water flow within the fire sprinkler piping system equal to the water flow from one fire sprinkler will cause the system water flow switch to activate. b. When electrical contacts within the system water flow switch activate, an alarm signal is sent to the existing Fire Alarm Control Panel. This will cause the Fire Alarm Control Panel to acknowledge an alarm condition and the Fire Alarm system will respond accordingly. 1. NARRATIVE DESCRIBING THE SEQUENCE OF OPERATION FOR THE FIRE ALARM AND DETECTION SYSTEM: a. One or more of the following devices shall initiate the fire alarm signal: • Manual pull stations. • Smoke detectors. • Verified automatic alarm operation of smoke detectors (see section b below). • Automatic sprinkler system water flow. • Fire standpipe system operation. b. The smoke alarm verification feature shall operate in the following manner: • Initiate audible and visible indication of an "alarm verification" signal at the FACP. • Activate a listed and approved "alarm verification" sequence at the FACP and the detector. • Record events. • Sound general alarm if the alarm is verified. • Cancel FACP indication and system reset if the alarm is not verified. c. The fire alarm system shall operate in the following manner upon receipt of an alarm signal: 7 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 F. SECTION 6— Special Consideration and Description 1. Application of "Performance-based design" in lieu of prescriptive code requirement: "Not Applicable." 2. Interpretation/clarification between designer and code officials: "Not Applicable." 3. Waiver or variance sought through the regulatory appeal process: "Not Applicable." 6 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 8. Emergency Power Equipment: a. All emergency power will be provided via battery backup. 9. Hazardous Material Monitoring Equipment: "Not Applicable." 10. Seismic Considerations: a. "Protection of piping from earthquakes (seismic activity) shall be in accordance with the eighth edition of 780 CRM, the Massachusetts State Building Code, NFPA 13 (2007) and any requirements of any applicable Codes and Standards for any systems installed." Drawings prepared for the fire protection systems shown are in accordance with all applicable Codes and Standards. The drawings provided satisfy the requirements of 780 CMR, section 901.2.1.1. E. SECTION 5— Features Used in the Design Methodology 1. Building occupant notification and evacuation procedures:: a. The building occupants shall be notified of an event/general alarm on the fire alarm system, including activation of a water flow switch, via existing and tone/strobe units. b. Building occupants will be notified of an alarm via the fire alarm tone/strobe units. 2. Emergency response personnel, site and systems features: a. The primary fire apparatus access will be maintained in its current location. 3. Safeguards, fire prevention and emergency procedures during new construction: "Construction shall proceed in accordance with NFPA 241, 527 CMR and City of Northampton Fire Department requirements. Specific guidelines and procedures shall be coordinated by the General Contractor." 4. Method for future testing and maintenance of systems and documentation: a. The sprinkler and other water-based fire suppression systems will be tested and maintained (in accordance with NFPA 25) by the Owner. The owner will maintain records of testing and maintenance. b. The fire alarm system will be tested and maintained (in accordance with NFPA 72) by the Owner. The Owner will maintain records of testing and maintenance. 5 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 D. SECTION 4— Fire Protection Systems to be Installed 1. Water Supply, Fire Mains and Hydrants: a. "The existing building system is supplied from a 6-inch fire protection service, which is connected to an existing 12-inch main on the site. There is an existing fire hydrant within one hundred feet of the building. The existing wet-type sprinkler system is monitored in accordance with NFPA 13 requirements and includes alarm valves, flow switches, alarm switches and tamper switches on isolation valves. 2. Automatic Sprinkler Systems and Components: "The new wet pipe fire sprinkler systems that will be installed to protect this building have been designed to meet the requirements of NFPA 13 (2007). The fire sprinkler system has been hydraulically calculated in accordance with NFPA 13 requirements for Occupancies as encountered in this building and will be supervised as required by CMR 780. 3. Fire Alarm Systems And Components: a. There is an existing addressable fire alarm control panel within the existing building which shall remain. The existing FACP is manufactured by Gamewell. b. The new building's fire alarm system shall be an extension of the existing addressable fire alarm control panel within the existing building. New notification appliance circuits and initiation loops shall be provided for new devices. c. New initiating devices (manual pull station, smoke detectors, etc.) and notification devices (horn/strobe, strobe only devices, etc.) will be added as required for the layout of the new space. d. At the completion of the project, the fire alarm system will be re- programmed, tested and re-certified. 4. Automatic Fire Extinguishing Systems: "Not Applicable." 5. Manual Suppression Systems: "Not Applicable." 6. Smoke Control/Management Systems: "Not Applicable." 7. Kitchen Cooking Equipment And Exhaust Systems: "Not Applicable." 4 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 • Electrical Engineer of Record: Michael D. Trickett, PE Electrical Engineer Robert W. Sullivan Engineering, Inc. Electrical License No. 41072 t*0 OF MA„ MICHAEL D. TRICKETT ELECTRIC.L kk,9... .:. 4,t, (f(''Y'j • Fire Protection Engineer of Record: Paul Sullivan, PE Fire Protection Engineer Robert W. Sullivan Engineering, Inc. Fire Protection License No. 40402 I,,S PAULO 0 t SUL,_IuA •n O FIRE PRATE, ',. l fir, x 0I 3 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 a. 521 CMR - Massachusetts State Architectural Access Board b. 527 CMR 12 - Massachusetts State Electric Code 7. Applicable Federal Laws: a. OHSA- Occupational Safety and Health Act b. ADA - Americans with Disabilities Act In addition to compliance with the requirements specified above, comply with pertinent regulations of all governmental agencies and authorities having jurisdiction (AHJ's) including local and state building, plumbing, mechanical, electrical, and fire codes and standards. C. SECTION 3— Design Responsibility for Fire Protection Systems 1. R.W. Sullivan Engineering has been retained by Westbn & Sampson as the Professional in Responsible Charge (the Engineer) to design the fire sprinkler, and fire alarm systems for this PVTA renovation. As the Professional in Responsible Charge, Robert W. Sullivan Engineering, Incorporated (the Engineer) has fully designed the fire sprinkler and fire alarm systems that will protect this portion of the building. The Fire Protection Construction Documents prepared for these systems are as required by CMR 780 (8th edition) and applicable NFPA Standards. 2. R.W. Sullivan Engineering has specified all the material and equipment that will be a part of these systems and will review all shop drawings, calculations, material data sheets, test reports and all other items required to be submitted to the Engineer for review. R.W. Sullivan Engineering will also conduct periodic construction administration site visits during the installation of this system to monitor compliance with the approved Fire Protection Construction Documents. At the completion of the project, R.W. Sullivan Engineering will issue documentation certifying that the system, as installed, complies with the approved Fire Protection Construction Documents. 2 PVTA Northampton, MA Date: 10/08/13 RWS Project No.11880.00 901.2.1.1 (a.i) - BASIS (METHODOLOGY) OF DESIGN A. SECTION 1 — Building Description 1. Building "Use" Group: Existing Building: B-1/S-1 & S-2 2. Total Square Foot of Facility: 24,034 SF 3. Building Height: 23'-6" 4. Number of Floors Above Grade: 1 5. Number of Floors Below Grade: 0 6. Square Footage of Renovation: 3,887 S.F. 7. Type(s) of Occupancies within the Building: Office/Motor vehicle repair garage 8. Type(s) of Construction: Type II B 9. Hazardous Material Usage and Storage: Not Applicable 10. High Storage of Commodities within a Building usually over 12 Feet: Not Applicable 11. Site Access Arrangement for Emergency Response Vehicles: Not Applicable B. SECTION 2 —Applicable Laws, Regulations and Standards Fire Protection and Electrical work shall comply with the noted editions of the following codes: 1. 780 CMR Massachusetts State Building Code (8th Edition): a. 780 CMR 901.2 - Required Systems b. 780 CMR 907.0 - Fire Alarm and Detection Systems c. 780 CMR 912.0 - Fire Department Connections 2. NFPA Standards used for design of each specific fire protection system: a. NFPA 13 (2007) - Installation of Sprinkler Systems b. NFPA 24 (2007) - Private Fire Service Mains and Their Appurtenances c. NFPA 25 (2008) - Inspection, Testing and Maintenance of Water Based Fire Protection Systems d. NFPA 70 (2008) - National Electric Code as amended by 527 CMR 12.00 e. NFPA 72 (2007) - National Fire Alarm Code as amended by 527 CMR 24 3. Massachusetts General Law, Chapter 148 - Fire Prevention 4. 527 CMR - Massachusetts State Board of Fire Prevention Regulations 5. Applicable Ordinances and Local By-Laws of the City of Northampton 6. Applicable Specialized Codes: 1 R Vil. PVTA Northampton 54 Industrial Drive Northampton, Massachusetts HVAC Electrical Plumbing Fire Protection FIRE PROTECTION SYSTEMS NARRATIVE Code IN ACCORDANCE WITH THE MASSACHUSETTS STATE BUILDING CODE, EIGHTH EDITION 780 CMR, SECTION 902.2.1 (1) PREPARED FOR: Northampton Fire Department Northampton Building Department OCTOBER 8, 2013 The Schrafft Center 529 Main Street Suite 203 Boston, MA 02129 617.523.8227 www.rwsullivan.com Page 2 2009 International Energy Code w/ 780 CMR Eight Edition Amendments, Appendix AA Stretch Energy Code 2011 NFPA—70 w/527 CMR Board of Fire Regulations 521 CMR Architectural Access Board USE GROUP B— Business: Administration /Operations (limit of work area) S-1 Storage: Vehicle Maintenance (outside area of work) S-2 Storage: Vehicle Parking (outside area of work) GENERAL BUILDING HEILGHT AND AREA LIMITS Use Group S-1 (most stringent) Allowable height per table 503: 2 stories Actual height: 1 story Allowable area for fully sprinkled building: 70,000 sf. Actual area: 10,278 sf. (including 1,930 sf. mezzanine) CONSTRUCTION TYPE II B: Non-combustible, Unprotected Fire resistance rating of structural elements: 0 hours MAXIMUM EXIT ACCESS TRAVEL DISTANCE — FULLY SPRINKLED BUILDING (Table 1016.1) Use Group B-1 (area of work) Maximum: 300 ft. Actual: 75 ft. Use Group S-1 (outside area of work) Maximum: 250 ft. Actual: 140 ft. Use Group S-2 (outside area of work) Maximum: 400 ft. Actual: 185 ft. WestonS Sampson to 85 Devonshire Street,3`d Floor Boston, MA 02109 tel:617-412-4480 fax:617-412-4255 www.westonandsampson.com (,)r r-'< ivr„c i r„ We StO to cR PVTA Northampton Vehicle Maintenance Facility Administration Reconfiguration and Addition SUMMARY BUILDING CODE REVIEW 8 October 2013 PROJECT OVERVIEW The project consists of reconfiguration of 1,500 sf. space with the facility that was previously used as a day care center, and reconfiguration of the adjacent existing 2,199 sf. administrative space, plus construction of a 188 sf. addition, all of which will be fitted out to provide a 3,887 sf. administrative/operations center. The scope of work includes: • Removal, reconfiguration and replacement of nearly all interior partitioning within the existing Northampton Operations Facility administration wing, and adjacent former day care center; • Construction of an 188 square foot addition to the administration wing; • Replacement of portion of existing exterior sidewalk and resetting of existing granite curbing; • Removal of existing wood-framed, exterior in-fill panels within precast concrete wall panels at the administration wing and adjacent former day care center; • Installation of sections of new tubular aluminum storefront system within precast concrete wall panels at the administration wing and adjacent former day care center; • Installation of sections of new hollow metal door/frame/window walls within the administration wing and adjacent former day care center; • Removal of existing and installation of new plumbing fixtures within the existing toilet rooms; • Installation of new finishes within all new and reconfigured spaces; • Replacement of existing boiler; • Replacement of existing roof top DX HVAC units on roof of administration wing, and patching/ re- flashing of the existing roof and roof membrane; • Installation of two new split AC systems, one within the reconfigured administration wing and one in an adjacent office; • Reuse of existing suspended ceiling lighting within the administration wing and adjacent former day care center; • Installation of new wired services from a central location to all new and reconfigured spaces. RELEVANT CODES 2009 Massachusetts State Building Code / 2009 IBC w/ 780 CMR Eight Edition Amendments 2009 International Mechanical Code 248 CMR Massachusetts State Plumbing Code Massachusetts Connecticut Rhode Island New Hampshire Maine Vermont New York Pennsylvania New Jersey South Carolina Florida When its essential...it's weston&Sampsowi, TA C. 1 *,,,wi ft Defeb40%44 4 Poit4 SAO/ "=: ; 044 A4 �, 1301 $ ., M, a 0210g-1615 NM 1)4 Kin)1 fox 1617) 727-5732 Construction Debris Disposal Affidavit (required for all demolition and renovation work) In accordance with the sixth edition of the State Building Code, 780 CMR section 111.5 Debris, and the provisions of MGL c 40, S 54; Building Permit# is issued with the condition that the debris resulting from this work shall be disposed of in a properly licensed waste disposal facility as defined by MGL c 111,S 150A. The debris will be transported by: (name of hauler) The debris will be disposed of in: I. 1ce -set) i - ,C Kati (name of facility) (address of facility) signature of permit applicant date debrisaff.doc ---_-_ ' , � City of Northampton Massachusetts DEPARTMENT OF BUILDING INSPECTIONS ` 212 Main Street • Municipal Building ` Northampton, MA 01060 �^!. ?«3v_�) ~ INSPECTOR Louis Hasbrouck Fax: 413-587-1272 Chuck Miller Building Commissioner Phone: 413-587-1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT (For professional Engineers/Architects responsible for a portion of a controlled project) 10 C5 Pn�e��TiUe� ��/��' -[��M�'~ ~� ` � ����L � / � '�,O • '', Date: �L) - c4- "%^�\'3 S >[ 1 \S,Io/off Project Location: 54 on� � .^ 0 -,-k- ,13C-o, f._/Kb thR-^Fa« 141 P Map: Parcel: Zone: Scope of Project: ZUkIct f-ec-o vi-CA 0ru,4, ~. . ' S/ 6.Ci � ; m In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: I, '~� %.L""nA A _ CCkr^et- ° (A Mass. Registration # 5 ~26L4. being a registered professional Engineer/Architect hereby CERTIFY that I have prepared or direc ly supervised the preparation of all design plans, computations and specifications concerning: [ ] Fire Protection [ 1 Architectural [ Structural [ ] Mechanical [ ] Electrical [ ] Other(specify) for the above named project and that to the best of my knmw|edgm, such p|ans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. , Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. Signature and Seal of Registered P ofessional i RICHARD A, rij,Ti ''~_ ~� �� CAMPBELL �� /� �`~_ \~__ �» �TMW�TUHAL �� � �----�- � N� c\ Oct-oOct- 2 F� �� ' - - ^ �� ` w6 \e —' ' - (seal) ,c‘ ` ' Yo City of Northampton _ 9"iHarw ,.\.,, 5�5,.......`..SAC. / '''g i~ Massachusetts �•t/ :' fce sof 1 '. F.i C�,, DEPARTMENT OF BUILDING INSPECTIONS ,x. U.11 ,� R s. 1\\,._______..4,0,' �1" 212 Main Street • Municipal Building Q,.. ,.,,,. i Northampton, MA 01060 44iY 3,.j'1C INSPECTOR Louis Hasbrouck Fax:413-587-1272 Chuck Miller Building Commissioner Phone:413-587-1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT 1 (For professional Engineers/Architects responsible for a portion of a controlled project) Project Title: PVTA Northampton ' Date: October 7, 2013 Project Location: 54 Industrial Drive, Northampton, MA 01060 Map: Parcel: Zone: Scope of Project: Renovation of existing building to convert to office space. In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: Paul D. Sullivan Mass. Registration# 42798 , being a registered professional Engineer/Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Fire Protection [ ]Architectural [ ]Structural Di Mechanical [ ] Electrical [ ]Other(specify) for the above named project and that to the best of my knowledge,such plans,computations and specifications meet the applicable provisions of the Massachusetts State Building Code,all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. r,. Signs -_-,r •,:-al of ` •-gistered Professional f�P�SH OF/114 9 AUL D. �y G o LLtVAN ,N 7th Day of October 2013 MECHANICAL y a No.42798 -P,, Pe, \�,c�, (seal) NAL E • _ City of Northampton / A ' �'��N. .-?c,;. SAS...r....,.ij.. (11'(. ,— Massachusetts ` 'c„,, C�-.� VI .t a `A I DEPARTMENT OF BUILDING INSPECTIONS 7j i ,; "4.\7W57, 212 Main Street • Municipal Building �y , a Northampton, MA 01060 hg` ..ai.�9. INSPECTOR Louis Hasbrouck Fax:413-587-1272 Chuck Miller Building Commissioner Phone:413-587-1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT 1 (For professional Engineers/Architects responsible for a portion of a controlled project) Project Title: PVTA Northampton ' Date: October 7,2013 Project Location: 54 Industrial Drive, Northampton, MA 01060 Map: Parcel: Zone: Scope of Project: Renovation of existing building to convert to office space. In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: Paul D. Sullivan Mass. Registration# 40402 , being a registered professional Engineer/Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [i Fire Protection [ ]Architectural [ ]Structural [ ] Mechanical [ ] Electrical [ ]Other(specify) for the above named project and that to the best of my knowledge,such plans,computations and specifications meet the applicable provisions of the Massachusetts State Building Code,all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. Signature and g red Professional °" t" ____„ , �c) PAUL D. tiG N 7th Day of October 2013 o(dJREPTioN) ) o.40402 (seal) °z'S`'IONr l .: City of Northampton � • F Massachusetts f - c.„.., ■r 6:..)i m 1M K.1 'l ' DEPARTMENT OF BUILDING INSPECTIONS : J 1 212 Main Street • Municipal Building ": I.° �rfk10;. J.. o• #"*".' Northampton, MA 01060 :Ili 3''.° INSPECTOR Louis Hasbrouck Fax: 413-587-1272 Chuck Miller Building Commissioner Phone:413-587-1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT t (For professional Engineers/Archltects responsible for a portion of a controlled project) Project Title: PVTA Northampton ' Date: October 7, 2013 Project Location: 54 Industrial Drive, Northampton, MA 01060 Map: Parcel: Zone: Scope of Project: Renovation of existing building to convert to office space. In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: Michael D. Trickett 4 Mass. Registration# 41072 being a registered professional Engineer/Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Fire Protection [ ]Architectural [ ]Structural [ ] Mechanical (xi Electrical [ ] Other(specify) for the above named project and that to the best of my knowledge, such plans,computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. �� N Of �q ;' ,'g rf f ` te, d Professional /4-'1. �TRIGKE - r Ir ` c- ELECTRICAL U'i j. � �AML. ,p No_41072 O 7th Davy of October 2q 13 \O,�F�©rsTE` `es�j` SrNA L t7-''< (Seal) City of Northampton 7. Massachusetts � - ' ;N DEPARTMENT OF BUILDING INSPECTIONS } „ ` 212 Main Street • Municipal Building Jt tea` \rs Northampton, MA 01060 ssf h „71\��' INSPECTOR Louis Hasbrouck Fax: 413-587-1272 Chuck Miller Building Commissioner Phone: 413-587-1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT (For professional Engineers/Architects responsible for a portion of a controlled project) 1�V TA tJ 0/TrtP p i o N M I N i peN► ctc" Project Title: Date: q- a c7'0.6.ei 2-6 0 Project Location: A- N b) ST Y1-(Ltz_ p(1 l�L" Map: Parcel: Zone: - - Scope of Project: (R(2..(43'-' kk) b` l)') - OP- /41- M IN, (�O� /I AJ d`p (`Prc(u T-7 In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: ViD (u `i e- tf7C-IcS Mass. Registration # - CO being a registered professional ineerfArchitect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Fire Protection siSrArchitectural [ ] Structural [ ] Mechanical [ ] Electrical [ ] Other(specify) for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. vy �5lrgnature = d Seal of '-gis -red Professional : • o-r� • I t>jc.595C) 10 T 4 Or BEt,tNT, of c 20± < mA85. 44',4 lee (seal) • The Commonwealth of Massachusetts Department of Industrial Accidents l_ Office of Investigations 1 Congress Street, Suite 100 t -'°�:�-a Boston,MA 02114-2017 ow,°°V° www.mass.gov/dia Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers Applicant Information Please Print Legibly _ �JJ��� Name (Business/Organization/Individual): i`C.J�)R.TZ p C.. Address: g' i 0 20vTLA 1.1., p—}-oN `2Q City/State/Zip:6.) es i f i L D, ,A 0/ 08\5" Phone #: y/3- S6 8'- oh 36 Are you an employer? Check the appropriate box: Type of project(required): 1.k. I am a employer with i l.I 4. ❑ I am a general contractor and 1 employees (full and/or part-time).* have hired the sub-contractors 6. 11 New construction listed on the attached sheet. 7. `t 'emodeling 2.❑ I am a sole proprietor or partner- ship and have no employees These sub-contractors have 8. ❑Demolition working for me in any capacity. employees and have workers' comp.insurance.$ 9. ❑Building addition [No workers' comp. insurance P required.] 5. ❑ We are a corporation and its 10.0 Electrical repairs or additions 3.❑ I am a homeowner doing all work officers have exercised their 11.0 Plumbing repairs or additions myself. [No workers' comp. right of exemption per MGL 12.❑Roof repairs insurance required.] t c. 152, §1(4),and we have no 13.0 Other employees. [No workers' comp. insurance required.] *My applicant that checks box#1 must also fill out the section below showing their workers'compensation policy information. t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such. Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have employees. If the sub-contractors have employees,they must provide their workers'comp.policy number. I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site information. �{— n Insurance Company Name: R¢aeLl A Ka-I-cc ° o ti �!. L) S. a p • _ Policy#or Self-ins. Lic.#: ©o s-i-i 3a c) / / a Expiration Date: Vole Li r 01404C)Job Site Address: ey TuAV.a Te.i Al.. De City/State/Zip:/6 6'�7H#4�Y Tof ' Attach a copy of the workers' compensation policy declaration page(showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to$1,500.00 and/or one-year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do hereby certify under the pains and penalties of perjury that the information provided above is true and correct. , Signature: - -° Date: /O///3 Phone#: (41 3 - 6L.8 - Official use only. Do not write in this area,to be completed by city or town official. City or Town: Permit/License# Issuing Authority(circle one): 1.Board of Health 2.Building Department 3.City/Town Clerk 4.Electrical Inspector 5.Plumbing Inspector 6.Other . Contact Person: Phone#: • Versionl.7 Commercial Building Permit May 15,2000 SECTION 10-STRUCTURAL PEER REVIEW(780 CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes ® No Pe SECTION 11 -OWNER AUTHORIZATION-TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT r �1 1 V , as Owner of the subject property hereby authorize G.2 t es 'S P.31.12 d ki) 1?■1. Z / 15'UC4 to act on my behalf, in all matters relative to work authorized by this building permit application. Signature of Owner I ate I C. LINO eiLS Sek-eb 9 , 1 -su RT L ZNQ, , as C›<r/Authorized Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge and belief. Signed under the pains and penalties of perjury. a A. 1 e s S Print Name Signature of Oer/Agent Date SECTION 12-CONSTRUCTION SERVICES 10.1 Licensed Construction Supervisor: �/ Not Applicable ❑ Name of License Holder: C '` J R-T Z S©s 1 License Number ii'/t -s©urr.inIP+DA) i WGs i t i4 Ml 0/ 68.0--** /Z/8//3 Address Expiration Date Signature Telephone Z4-.1.14"" /C SECTION 13-W RKERS'COMPE ATION INSURANCE AFFIDAVIT(M.G.L.c. 152,§25C(6)) Workers Compensation Insurance affi•avit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the •.riding permit. Signed Affidavit Attached Yes No I i Version1.7 Commercial Building Permit May 15,2000 SECTION 9-PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES-FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO MO CMR 116(CONTAINING MORE THAN 35,000 C.F.OF ENCLOSED SPACE) 9.1 Registered Architect . DAvto Amcm"-&-z_ o/c/L-5 J Not Applicable 0 ---1 Lefa,,,,Aorre-,2-7a,/PCA-- 1 Name(Registrant r-c-t- L 4. 3 ._a, (4)0Stit,-■;": CT' . 462?Ai P'24 0 i j i'Registralion Nwnber Address ..... 41111■ 1(617).412-4480i Ex"I'Dat:t ---- 3/7tzt-- I4A-it Signature Telephone 9.2 ", • – ii Profess , Engineer(s): r Michael D Trickett L 1 1Electrical Name Area of Responsibility ....._ 1529 Main Stree Suite 203, Boston, MA 02129 —1 41072 1 - - - ■11111/ ..rar , Registration Number iRve:iii--10 ir . ; se_ - al Alp, (617)523-8227 16'30-14 , , , 1 ....zags. -,•• •- Mtmaksikk -..nature Telephone Expkation Date ------Paul D Sullivan _____ [ I Fire Protection • Name Area of Responsbnity 1529 Mai fh_treet, Suite 203, Boston, MA 02129 J 140402 • RettiskatIon Number ---/fp- (617)523-8227 16-30-14 Telephone Expiration Date 1 Paul D Sullivan 1 'Plumbing Name Area of Responsibility 1529 Main : reet. Suite 203. Boston. MA ofig---------------- - 142798 L__ iff — Address Nip— Registration Number ,Atizir (617)523-8227 .6-30-14 ? ___ . signore if r Telephone Expiration Date Paul D Sullivan ____.1 1HVA.0 Name Area of Responsibility 529 Main Sifi et, Suite 203, Boston, MA 02129 1 42798 Address Regletnadon Number .asilm/or T 6 V ip (617)523-8227 ! -30-14 ___ ..._. Signature Telephone Expiration Date 9.3 General Contractor 1 .... I Not Applicable El Company Name: bene Kurtz 1 Responsible in Charge of Construction 1810 Southampton Road,Westfield,MA 01085 ..../i ,...— . Address. .........._............._.__ ........_.............._.._ 1(413)568-0636i _.. ...L. ..-■ Signature Telephone -- Versionl.7 Commercial Building Permit May 15,2000 8. NORTHAMPTON ZONING Existing Proposed Required by Zoning This column to be filled in by Building Department Lot Size a. a S". Z . z S� Frontage 3 6 ci 3 6 9 Setbacks Front Side L: ' R: a O L: 'b R: Z O Rear Building Height t Bldg.Square Footage 2 3/69 7 °°° �3 L?7 Open Space Footage (Lot area minus bldg&paved a Q•<l4 2 D, 0? parking) #of Parking Spaces Fill: (volume&Location) A. Has a Special Permit/Variance/Findin ever been issued for/on the site? NO ® DON'T KNOW YES C IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO Q DON'T KNOW ® YES 0 IF YES: enter Book Page and/or Document# B. Does the site contain a brook, body of water or wetlands? NO 4 DON'T KNOW 0 YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained 0 Obtained Q , Date Issued: C. Do any signs exist on the property? YES X40 NO 0 IF YES, describe size, type and location: N Al.) pi c.x p (P'Akk p c� D. Are there any proposed changes to or additions of signs intended for the property? YES 1141 NO Q IF YES, describe size, type and location: OA pp)ut it) �A�� N C E. Will the construction activity disturb(clearing, gradin. ex -vation, or filling)over 1 acre or is it part of a common plan that will disturb over 1 acre? YES () NO her IF YES,then a Northampton Storm Water Management Permit from the DPW is required. Version1.7 Commercial Building Permit May 15,2000 SECTION 4-CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE Interior Alterations%Existing Wall Signs ❑ Demolition❑ Repairs❑ Additions ❑ Accessory Building❑ Exterior Alteration f Existing Ground Sign❑ New Signs❑,Roofing 0 Change of Use❑ Other❑ 12C'.POUAT'OA c 6 Ck1.3T/.JG. s pAae /AueL bAfA) c. ELQ ..t. ..,c Brief Description - Of Proposed Work: N V A e.7 p L u)4 I u G f F J u. S.1 P p A.0.4 utivt, ANA A k.ii e T eaT at m._ SECTION 5-USE GROUP AND CONSTRUCTION TYPE USE GROUP(Check as applicable) CONSTRUCTION TYPE A Assembly A-1 ❑ A-2 ❑ A-3 ❑ 1A ❑ A-4 ❑ A-5 ❑ 1 B ❑ B Business Die 2A ❑ E Educational ❑ 2B I lEt, F Factory ❑ F-1 ❑ F-2 ❑ 2C ❑ H High Hazard ❑ 3A ❑ I Institutional ❑ I-1 ❑ 1-2 ❑ 1-3 ❑ 3B ❑ M Mercantile ❑ 4 ❑ R Residential ❑ R-1 ❑ R-2 ❑ R-3 ❑ 5A ❑ S Storage ❑ S-1 ❑ S-2 ❑ 5B [ ❑ U Utility ❑ Specify: M Mixed Use ❑ Specify: S Special Use ❑ Specify: COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS,ADDITIONS AND/OR CHANGE IN USE Existing Use Group: Q VS/Ness Proposed Use Group: ,80S/Ne..9.5 Existing Hazard Index 780 CMR 34): 2.. Proposed Hazard Index 780 CMR 34): L SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY Floor Area per Floor(sf) 1st a3, 6 /r7 l st �1 O� 3J 6 1 i 2nd 2nd 3rd 3rd 4th 4th Total Area(sf) a 3 , cf 7 Total Proposed New Construction(sf) l3, 64 ? Total Height(ft) /g 1 / Total Height ft 7.Water pply(M.G.L.c.40,§54) 7.1 Flood Zone Information: / 7.3 Sewa e isposal System: Public (RI Private ❑ Zone Outside Flood Zone 11St"'j� Municipal On site disposal system El r Versionl.7 Commercial Building_Permit May 15,2000 `' ',,.' Department use only s, ; ! City of Northampton Status of Permit: il, Gl,i X013 ,' i Building Department Curb Cut/Driveway Permit - .. i_____ 212 Main Street Sewer/Septic Availability ---- Room 100 Water/Well Availability Electric, Piumuing �4 fr, pection Northampton, 6,-010' ao;oso I orthampton, MA 01060 Two Sets of Structural Plans phone 413-587-1240 Fax 413-587-1272 Plot/Site Plans Other Specify APPLICATION TO CONSTRUCT,REPAIR,RENOVATE,CHANGE THE USE OR OCCUPANCY OF,OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 -SITE INFORMATION 1.1 Property Address: - This section to be completed by office 6. / _:"CA,O VS TL t Al. 10 Al d 8.. Map ?68- Lot 190 Unit IQ 0( 'T14 41'4 PT ON/ o sOlo O Zone Overlay District Elm St.District CB District SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: PVTA \I?J ,L.. �' -��.:--� L808 Maul St" Spz8441,F fa 1.4.3 µk 0 no7 Name(Print) Current Mailing Address: \!4\, k.(f�\ �„u1 , •- - k.f‘,.. .a 4 13- 7.3 a - 6 a lI r Signature Telephone 2.2 Authorized Agent: CL14€-s SelLet4 SVO SoLf, iI6PTo„) R.D. (A)CS7F/t .b A/4 Name(Print) Current Mailing Address: O/OFT- 14 I 3- s68- 0636 Signature Telephone SECTION 3-ESTIMATED CONSTRUCTION COSTS Item Estimated Cost(Dollars)to be Official Use Only completed by permit applicant 1. Building .ice S I ' •7 s b (a)Building Permit Fee 2. Electrical (b) Estimated Total Cost of t� t O J 3. () f S6J ? Construction from (6) 3. Plumbing 14 3 2 o Building Permit Fee 4. Mechanical(HVAC) ZII000 5. Fire Protection J 6. Total=(1 +2+3+4+5) i j 1 J of 3 3 4 Check Number 11 IA 4IQJ/Ig a - This Section For Official Use Only Building Permit Number Date Issued Signature: Building Commissioner/Inspector of Buildings Date File#BP-2014-0435 APPLICANT/CONTACT PERSON KURTZ INCORPORATED ADDRESS/PHONE P 0 BOX 1597 WESTFIELD (413) 568-0636 PROPERTY LOCATION 54 INDUSTRIAL DR MAP 25A PARCEL 190 001 ZONE GI(111)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out q, ,�� � Typeof Construction:_RENOVATE INTERIOR INCL ELEC,HVAC,PLBG,FIRE SUPPRESSION&ARCH New Construction Non Structural interior renovations Addition to Existing, Accessory Structure Building Plans Included: Owner/Statement or License 036505 3 sets of Plans/Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INF RMATION PRESENTED: 1/Approved Additional permits required(see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND/OR Special Permit With Site Plan Major Project: Site Plan AND/OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received&Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay /I/ 2-2./I3 Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health,Conservation Commission,Department of public works and other applicable permit granting authorities. *Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning&Development for more information. 54 INDUSTRIAL DR BP-2014-0435 GIS#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 25A- 190 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category:renovation BUILDING PERMIT Permit# BP-2014-0435 Project# JS-2014-000758 Est. Cost: $1110334.00 Fee: $6662.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: KURTZ INCORPORATED 036505 Lot Size(sq.ft.): 98010.00 Owner: PIONEER VALLEY TRANSIT AUTHORITY Zoning: GI(111)/ Applicant: KURTZ INCORPORATED AT: 54 INDUSTRIAL DR Applicant Address: Phone: Insurance: P 0 BOX 1597 (413) 568-0636 Workers Compensation WESTFIELDMA01086 ISSUED ON:11/22/2013 0:00:00 TO PERFORM THE FOLLOWING WORK:RENOVATE INTERIOR INCL ELEC,HVAC,PLBG,FIRE SUPPRESSION & ARCH POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 11/22/2013 0:00:00 $6662.00 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck—Building Commissioner