25C-166 (7) KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
4, A Boulder, CO 80301
' 07/19/13 Phone:303 443-2068
": � �' 07:09:17 EWPjobs @keymark.com
EWelEERINO,W 8 of 8
CS Beam4.605 Joey @ Bollard Lumber 6-17-1
kmBeamEngine 4.6026 49 Orchard ST 8:55am
Materials Database 1429 Northampton MA Seal:Massachusetts
Member Data
Description: Beam 3 Member Type: Girder Application: Floor
Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 10 PLF Deck Connection:Nailed Member Weight: 8.3 PLF
Filename: Beam 3.KYB
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Additional Uniform(PLF) Top 0' 0.00" 13' 0.00" 0 80 Live
Additional Uniform(PLF) Top 0' 0.00" 13' 0.00" 0 125 Snow
I I-
13 0 0
/0 0/
13 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.500" 1654# --
2 13' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.500" 1654# --
Maximum Load Case Reactions
Used for applying point bads(or line bads)to carrying members
Uve Dead
1 251# 1403#
2 251# 1403#
Design spans
12' 6.750"
Product: 2.0 RigidLam LVL 1-3/4 x 9-1/2 2 ply PASSES DESIGN CHECKS
Connect members with 2 rows of 16d common nails at 12.0"oc
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 5194.'# 13100.'# 39% 6.5' Total Load D+L
Shear 1445.# 6318.# 22% 0.23' Total Load D+L
Max.Reaction 1654.# 7962.# 20% 13' Total Load D+L
TL Deflection 0.2950" 0.6281" U510 6.5' Total Load D+L
LL Deflection 0.0448" 0.4187" L/999+ 6.5' Total Load L
Control: TL Deflection
DOLs: Live=100%a Snow=115% Roof=125% Wind=160%
ceare
(14 OF MgS
S�c.,
Z.40411 114 6 JEREMY MARTIN
m
a..- p GILSTRAP
All product names are trademarks of their respecave owners. U STRUCTURAL to j
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. NO 50090 1
Thos drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete
\,e, �^
without the accompanying General Notes.The Engineers Seal on this drawing indicates only that the floor Joist component shownon this
• � -
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet This design assumes product . TER
installation according to Memanufacturer's specifications. \
Keymark Engineering SS/�AL
07/19/2013
Key Beam® Calculation Keymark Engineering, Inc.
y 6707 Winchester Circle
I/ 07/19/13 Boulder, CO 80301
Phone:303-443-2068
i I, 07:09:17 EWPjobs @keymark.com
II ENONEERINO, 7of8
Control: TL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Design assumes a repetitive member use increase in bending stress: 4%
O�� y�N OF Mg SS 1,,
JEREMY MARTIN LA
k O GILSTRAP —I
All product names are trademarks of their respective owners. U STRUCTURAL o
Copyright(c)2012 by Simpson Strong-Tie Company,no ALL RIGHTS RESERVED. ` \ NO 50090 /
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete Q'/.'
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this %* ��• R
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product
installation according to themanufacturer's specifications G\
SS/CINAL-Eta
Keymark Engineering
07/19)2013
Key Beam® Calculation Keymark Engineering, Inc.
y 6707 Winchester Circle
I `�./. ' Boulder, CO 80301
07/19/13 Phone:303-443-2068
'
t 07:09:17 EWPjobs @keymark.com
1RNO.INC 6 of 8
N Beam4.605 Joey @,Bollard Lumber 6-17-I
lanBeamEngine 4.6026 49 Orchard ST 8:46am
Materials Database 1429 Northampton MA Seal:Massachusetts
Member Data
Description: Beam 2 Member Type: Beam Application: Floor
Top Lateral Bracing: Continuous
Bottom Lateral Bracing:Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 10 PLF Deck Connection: Nailed Member Weight: 15.6 PLF
Filename: Beam 2.KYB
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Replacement Uniform(PSF) Top 0' 0.00" 13' 0.00" 6' 0.00" 30 15 Live
Additional Uniform(PLF) Top 0' 0.00" 13' 0.00" 0 80 Live
Additional Uniform(PSF) Top 0' 0.00" 13' 0.00" 14' 0.00" 40 15 Snow
Additional Uniform(PSF) Top 0' 0.00" 13' 0.00" 2' 0.00" 10 10 Live
Additional Uniform(PSF) Top 0' 0.00" 13' 0.00" 2' 0.00" 40 15 Snow
13 0 0
13 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.998" 6819# --
2 13' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.998" 6819# --
Maximum Load Case Reactions
Used for applying point beds(or line bads)to carrying members
Live Snow Dead
1 1256# 4020# 2799#
2 1256# 4020# 2799#
Design spans
12' 6.750"
Product: 2.0 RigidLam LVL 1-3/4 x 11-7/8 3 ply PASSES DESIGN CHECKS
Connect members with 2 rows of 16d common nails at 12.0"oc
NOTE:Nails must be applied from both sides
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 21416.'# 35710.'# 59% 6.5' Total Load D+S
Shear 5745.# 13622.# 42% 12.15' Total Load D+S
Max.Reaction 6819.# 11944.# 57% 0' Total Load D+S
TL Deflection 0.4152" 0.6281" L/363 6.5' Total Load D+S
LL Deflection 0.2448" 0.4187" L/615 6.5' Total Load S
littfif" Z O��'P�tH OF MgSS9cyG
JEREMY MARTIN m
O GILSTRAP -t
All product names are trademarks of their respective owners. o STRUCTURAL to
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. NO.50090
This drawing is an integral part of a floor joist component document as defined in theetteched General Notes.This drawing is not complete n �6 Q-
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component showmen this ,r
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product R
installation according to themanufacturer's specifications. T ``
sn9/ONAt.Ea"
Keymark Engineenng
07/19/2013
Key Beam® Calculation Keymark Engineering, Inc.
/ y 6707 Winchester Circle
��.� Boulder, CO 80301
-
07/19/13 Phone: 303-443-2068
07:09:16 EWPjobs @keymark.com
ENONEERND,aK 5 of 8
Control: Max.Reaction
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Design assumes a repetitive member use increase in bending stress: 4%
L µOF Mg
.�*,P SS9cy
O G
JEREMY MARTIN U,41,K,R —
.„,,Z'
I GILSTRAP
All product names are trademarks of their respecoveowners. a 1 STRUCTURAL tn�
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. �, ` NO.50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete `\\ Q'
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this �• 'Q —'p.
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product 0 .41.1.0 R f
installation according to themanufacturers specifications. \' ��
Keymark Engineering / S`s/ANAL E�
r 07/19/2013
" KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
,y 4 Boulder, CO 80301
' 07/19/13
Phone:303-443-2068
0 " b 07:09:16 EWPjobs @keymark.com
ENGINEERING, 4 of 8
.:S Beam4.605 Joey L Bollard Lumber 6-17-1
GnBeamEngine 4.6026 49 Orchard ST 8:44am
Materials Database 1429 Northampton MA Seal:Massachusetts
Member Data
Description:Roof Beam Member Type: Beam Application: Floor
Top Lateral Bracing:Continuous
Bottom Lateral Bracing:Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 10 PLF Deck Connection: Nailed Member Weight: 31.5 PLF
Filename: Beam 1.KYB
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Replacement Uniform(PSF) Top 0' 0.00" 22' 0.00" 9' 0.00" 30 15 Live
Additional Uniform(PLF) Top 0' 0.00" 22' 0.00" 0 80 Live
Additional Uniform(PSF) Top 0' 0.00" 22' 0.00" 9' 0.00" 10 10 Live
Additional Uniform(PSF) Top 0' 0.00" 22' 0.00" 13' 0.00" 40 15 Snow
Additional Uniform(PSF) Top 0' 0.00" 22' 0.00" 2' 0.00" 40 15 Snow
2200
P a,
2200
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 5.500" 3.986" 13603# --
2 22' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 5.500" 3.986" 13603# --
Maximum Load Case Reactions
Used for applying point bads(or line bads)to carrying members
Live Snow Dead
1 3821# 6369# 5960#
2 3821# 6369# 5960#
Design spans
21' 2.750"
Product: 2.0 RigidLam LVL 1-3/4 x 24 3 ply PASSES DESIGN CHECKS
Connect members with 4 rows of 16d common nails at 12.0"oc
NOTE:Nails must be applied from both sides
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 72193.'# 133583.'# 54% 11' Total Load D+0.75(L+S)
Shear 11040.# 27531.# 40% 0.4' Total Load D+0.75(L+S)
Max.Reaction 13603.# 18769.# 72% 0' Total Load D+0.75(L+S)
TL Deflection 0.4842" 1.0615" U526 11' Total Load D+0.75(L+S)
LL Deflection 0.2720" 0.7076" L/936 11' Total Load 0.75 +
O�,14°' H OF MgSS.4O
yG
Z' JEREMY MARTIN m
O0 GILSTRAP
All product names are trademarks of their respective owners. o STRUCTURAL ca `
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. , NO.50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete
without the accompanying General Notes The Engineer's Seal on this drawing indicates only that the floor joist component shownon this • 'Q 4'°r°
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product 1.r' Vii?•TERM ,,
installation according to themanufacturer's specifications
/yy,,� r�
Keymark Engineering
07/19/2013
• Key Beam® Calculation Keymark Engineering, Inc.
Y 6707 Winchester Circle
:� Boulder, CO 80301
07/19/13 Phone:303-443-2068
"~ � f " ' �' 07:09:16 EWPjobs @keymark.com
^°•'NC 3of8
10. MULTI-PLY COMPONENTS
Multi-ply components shall be connected together in accordance with the manufacturer's recommendations
11. BEARING LENGTH
The"Input Brg. Length" listed on the individual floor joist, beam, or girder design drawing is the actual length of bearing at that location. The
"Minimum Brg. Length"on the individual floor joist, beam,or girder design drawing is the minimum required length of bearing at that location.
The length of the bearing is measured along the length of the member. The width of the bearing is measured perpendicular to the length of
the member. Each ply of the member shall be supported for the full member width,for the full required minimum length of the bearing.
12. POINT LOADS OVER A BEARING
Point loads applied over a bearing are assumed to be carried not by the I-joist, beam,or girder, but instead by rim board,squash blocks,or
some other means. Therefore the points loads over the bearings will be included in the bearings and reactions summary, but will not be
considered when evaluating the interior and end reactions and is indicated on the drawings by"Pass-thru"framing is required at point loads
over bearings.
13. PONDING WARNING
Where components are used in roof systems,these components have not been investigated for the effects of ponding. The Building
Designer shall ensure that adequate drainage has been provided, and that the roof system as a whole is not susceptible to ponding.
O���P`-�N OF Mg SS1OyG
JEREMY MARTIN m
� ,.w GILSTRAP
All product names are trademarks of their respective owners. V STRUCTURAL ti
Copright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. b NO 50090
This drawing Is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete 13—,
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product 1r'-�5-T 06- 4
installation according to themanufacturer's specifications. \e t C,
SS/ONAI.E�
Keymark Engineering
7-7 07/19/2013
w
• KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
f.. 07/19/13 Boulder, CO 80301
Phone:303-443-2068
s ► • 07:09:16 EWPjobs @keymark.com
Ef10fEERNO,NC. 2 of 8
Floor Joist, Beam, and Girder Component General Notes
1. FLOOR JOIST, BEAM, AND GIRDER COMPONENT DOCUMENT
A Member Component Document is defined herein as being composed of a cover letter,this set of general notes, individual floor joist,
beam,or girder design drawings. The cover letter lists the contents of the Member Component Document. Each sheet of this Member
Component Document is an integral part of the whole,and shall be used only for the specific job name listed on the cover letter. This
Member Component Document is the exclusive property of Keymark Engineering,and shall not be copied,transferred, or reproduced, in
whole or in part,without the written consent of Keymark Engineering, Inc.Copyright Keymark Engineering, Inc.,2010, all rights reserved.
2. COMPONENT DESIGN
This design is for an individual building member component and has been based on information provided by the client. The Member
Component Designer disclaims any responsibility for damages as a result of faulty or incorrect information,specifications,and/or designs
furnished to the Member Component Designer by the client and the correctness or accuracy of this information as it may relate to a specific
project. The Member Component Designer accepts no responsibility and exercises no control with regard to fabrication, handling,shipment,
and installation of member components. Each member component specified herein has been designed as an individual building
component. Each component shall be incorporated as part of the building design by a Building Designer(registered architect or
professional engineer,as applicable). The Building Designer shall review the design loading, member component geometry,and all other
aspects of each component design to ensure that the data shown are in agreement with the local building codes, local climatic records for
snow or wind loads, project specifications,or special applied loads.
3. FABRICATION NOTES
Prior to fabrication,the fabricator shall review this Member Component Document to verify that this Member Component Document is in
conformance with the fabricator's plans and to realize a continuing responsibility for such verification. Fabrication of member components
shall not proceed until the fabricator has certified drawings in hand.
4. PRECAUTIONARY NOTES
Refer to the manufacturer's recommendations for instructions on handling, bundling,and delivery of the member components specified
herein.
5. MODIFICATION OF COMPONENT MEMBERS
Refer to the manufacturer's recommendations for instructions on allowable modifications of the member components specified herein.
6. MEMBER COMPONENT TO MEMBER COMPONENT CONNECTION DESIGN
The design of any connections between member components and other member components is not provided with the component designs
specified herein. Web stiffener requirements at hangered connections depend on the connection style and are not included in this design.
Supported components attached to the side of this member with reactions greater than 400 lbs shall be attached in such a way to preclude
twisting of this member.
7. MEMBER COMPONENT TO STRUCTURE CONNECTION DESIGN
The design of any connections between the member component and other elements of the overall structure is not provided with the
component designs specified herein.
8. UPLIFT REACTIONS
Floor joists,beams or girders with multiple spans may generate uplift reactions due to gravity loads. The reactions shown in these
calculations assume that all of the bearings are infinitely stiff. The Building Designer shall review all reaction forces and ensure that the
structure can resist any uplift reactions appropriately.
9. LATERAL BRACING
All lateral bracing requirements apply along the entire length of the component member. The design of the individual component member
brace and the anchorage of the brace is the responsibility of the Building Designer. Design assumes that the component member is braced
top and bottom at all bearing locations.
O2 P'\. OF MgSST(.
Z' JEREMY MARTIN m
p GILSTRAP �i
All product names are trademarks of their reepeotue owners. U STRUCTURAL fn
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. , NO 50090
This drawing is an integral pan of a floor joist component document as defined in theattached General Notes.This drawing is not complete , Q.
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this i'� 'Q 7^-fj-
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet This design assumes product ■1 `•,. S.T.
installation according to themanufacturer's specifications. �. nom!.., E f_`
Keymark Engineering `S`S1ONAt- ``G
07/19/2013
KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
�!� A Boulder, CO 80301
07/19/13 Phone:303-443-2068
4 07:09:16 EWPjobs @keymark.com
EN1>"IEE '.IC 1 of 8
Cover Sheet
Job: 49Orchard
Confirmation#: 0719090911
Contact Person: Bill Ingham
Company Name: Roseburg Forest Products
PO Box 922
South Hadley, MA 01075
Phone/Fax: 4134273233/8772711080
Email: billi @rfpco.com;davea @rfpco.com
Ship-To Contact: Adam Tredo
Ship-To Company: Seven D
Ship-To Phone/Fax: 8008006894/
Ship-To Email: atredo @degol.com;plans @degol.com
Member Information
(1)-Beam 1.KYB (2)-Beam 2.KYB (3)-Beam 3.KYB
Comments
ION*
jN OF MS1/45'
JEREMY MARTIN m
�.M 0 GILSTRAP
All product names are trademarks of their respective owners. U STRUCTURAL co
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. , NO.5()090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete kill, n ..
without the accompanying General Notes.The Engineers Seal on this drawing indicates only that the floor joist component shownon this
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product ♦ E \ ,�
installation according to themanufacturer's specifications. ••( c �[-
Keymark Engineering SS1ONAL
07/19/2013
" 1t' -7 - I.
•
KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
<<,! .` .
07/31/13 Boulder, CO 80301
Phone:303-443-2068
1 V " ' �' 05:38:19 EWPjobs @keymark.com
Iia«EEfI40,tc 5 of 5
keyBeam®4.600d Joey @ Bollard Lumber 7-29-1S
lmtBeamEngine 4.6026 49 Orchard ST 9:36pm
Materials Database 1421 Northampton MA Seal:Massachusetts
Member Data
Description:Girder 2 Member Type: Girder Application: Floor
Top Lateral Bracing:Continuous
Bottom Lateral Bracing:Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 15 PLF Deck Connection: Nailed Member Weight: 8.3 PLF
Filename:Girder 2.KYB
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Point(LBS) Top 0'10.00" 5600 2800 Live
Additional Uniform(PLF) Top 0' 0.00" 12' 0.00" 0 125 Snow
. i j y ,g i A ik t"MO N fi *k ( ',
� r' ;� p?"J '". y� s is� } f,'t , :Mt . ,,
E T x�` �5�, °n k � �, ! re ,: ,f.,-, ar ti
w ,;a�ir,.�r.,,L . . �.�4?d ,a aw.ze,.lt."� ,,. .. ' ..,, .r ..: ...M..+a.x'-.c.. .. ..',, .:'
12 0 0
,0 0 ,
12 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 5.500" 4.010" 9122# --
2 12' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 5.500" 1.500" 1392# --
Maximum Load Case Reactions
Used for applying point bads(or line bads)to carrying members
Live Dead
1 5601# 3521#
2 448# 944#
Design spans
11' 2.750"
Product: 2.0 RigidLam LVL 1-3/4 x 9-1/2 2 ply PASSES DESIGN CHECKS
Connect members with 2 rows of 16d common nails at 12.0"oc
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 5146.'# 13100.'# 39% 4.32' Total Load D+L
Shear 5326.# 6318.# 84% 0.4' Total Load D+L
Max.Reaction 9122.# 12512.# 72% 0' Total Load D+L
TL Deflection 0.2376" 0.5615" L/567 5.44' Total Load D+L
LL Deflection 0.0980" 0.3743" U999+ 5.44' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
O���P\(///''''-i;OF�gSsle
C.
Z JEREMY MARTIN
m
r .,,,.
0 0
GIL STRAP
All product names are trademarks of their respective owners. 0 STRUCTURAL vi
Copyright(c)2012 by Simpson Strong-Tie Company.Inc.ALL RIGHTS RESERVED. , NO 50090 (J
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete ,� .p Q It/"
without the accompanying General Notes The Engineer's Seal on this drawing indicates only that the floor joist component shownon this y F _
drawing meets applicable design criteria for Loads.Loading Conditions,and Spanslisted on this sheet This design assumes product CI*.,,T ,
installation according to Nemanufacturer's specifications \ w
Keymark Engineenng ,
07/31/2013
5-
KeyBeam® Calculation Keymark Engineering, Inc.
A•• 6707 Winchester Circle
07/31/13 Boulder, CO 80301
. ',,- ` •
Phone:303443-2068
05:38:19 EWPjobs @keymark.com
.NYC 4of5
KeyBeam®4.600d Joey @ Bollard Lumber 7-29-13
kmBeamEngine 4.6026 49 Orchard ST 9:34pm
Materials Database 1421 Northampton MA Seal:Massachusetts
Member Data
Description:Girder 1 Member Type: Girder Application: Floor
Top Lateral Bracing: Continuous
Bottom Lateral Bracing:Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 15 PLF Deck Connection: Nailed Member Weight: 16.6 PLF
Filename:Girder 1.KYB
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Point(LBS) Top 0'10.00" 10190 5960 Live
Additional Uniform(PLF) Top 0' 0.00" 15' 0.00" 0 125 Snow
15 0 0
15 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 5.500" 3.750" 17063# --
2 15' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.500" 1918# --
Maximum Load Case Reactions
Used for applying point bads(or line bads)to carrying members
Uve Dead
1 10161# 6902#
2 605# 1313#
Design spans
14' 4.750"
Product: 2.0 RigidLam LVL 1-3/4 x 9-1/2 4 ply PASSES DESIGN CHECKS
Connect members with 2 rows of 112"diameter bolts at 24.0"oc
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 9342.'# 27247.'# 34% 4.7' Total Load D+L
Shear 9894.# 12635.# 78% 0.4' Total Load D+L
Max.Reaction 17063.# 25025.# 68% 0' Total Load D+L
TL Deflection 0.3530" 0.7198" U489 6.86' Total Load D+L
LL Deflection 0.1425" 0.4799" L/999+ 6.86' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Design assumes a repetitive member use increase in bending stress: 4%
o2 l'\-µOF yq SS1cyG
JEREMY MARTIN m
140#10614
U GIL5TRAP -i
All product names are trademarks of their respective owners. U STRUCTURAL to
Copyright(e)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. NO 50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete ,,� Q �e-
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this , 'Pc,' e T _ '
drawing meets applicable design criteria for Loads,Loading Conditions,and Spansltsted on this sheet.This design assumes product t
installation according to themanufacturer's specifications. II
Keymark Engineering
07/31/2013
KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
07/31/13 Boulder, CO 80301
Phone:303-443-2068
1 ► ' 05:38:19 EWPjobs @keymark.com
EOMERINO,NC 3 of 5
10. MULTI-PLY COMPONENTS
Multi-ply components shall be connected together in accordance with the manufacturer's recommendations
11. BEARING LENGTH
The"Input Brg. Length"listed on the individual floor joist, beam, or girder design drawing is the actual length of bearing at that location. The
"Minimum Brg. Length"on the individual floor joist, beam,or girder design drawing is the minimum required length of bearing at that location,
The length of the bearing is measured along the length of the member. The width of the bearing is measured perpendicular to the length of
the member. Each ply of the member shall be supported for the full member width,for the full required minimum length of the bearing.
12. POINT LOADS OVER A BEARING
Point loads applied over a bearing are assumed to be carried not by the I-joist, beam,or girder, but instead by rim board,squash blocks,or
some other means. Therefore the points loads over the bearings will be included in the bearings and reactions summary, but will not be
considered when evaluating the interior and end reactions and is indicated on the drawings by"Pass-thru"framing is required at point loads
over bearings.
13. PONDING WARNING
Where components are used in roof systems,these components have not been investigated for the effects of ponding. The Building
Designer shall ensure that adequate drainage has been provided, and that the roof system as a whole is not susceptible to ponding.
Agog* 2�� ZN OF
Ssio
Mg
JEREMY MARTIN m
GILSTRAP
All product names are trademarks of their respective owners. 0 STRUCTURAL 0
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED NO.50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete ,'D ,1y Q ki
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this s tl +cG • -
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product GI CT
installation according to themanufacturer's specifications. ' �•�. ��
Keymark Engineering
07/31/2013
KeyBeam0 Calculation Keymark Engineering, Inc.
6707 Winchester Circle
Boulder, CO 80301
07/31/13 Phone:303-443-2068
05:38:19 EWPjobs @keymark.com
EflKiNEERINO,NC. 2 of 5
Floor Joist, Beam, and Girder Component General Notes
1. FLOOR JOIST, BEAM, AND GIRDER COMPONENT DOCUMENT
A Member Component Document is defined herein as being composed of a cover letter,this set of general notes, individual floor joist,
beam,or girder design drawings. The cover letter lists the contents of the Member Component Document. Each sheet of this Member
Component Document is an integral part of the whole,and shall be used only for the specific job name listed on the cover letter. This
Member Component Document is the exclusive property of Keymark Engineering,and shall not be copied,transferred,or reproduced, in
whole or in part,without the written consent of Keymark Engineering, Inc.Copyright Keymark Engineering, Inc.,2010, all rights reserved.
2. COMPONENT DESIGN
This design is for an individual building member component and has been based on information provided by the client. The Member
Component Designer disclaims any responsibility for damages as a result of faulty or incorrect information,specifications, and/or designs
furnished to the Member Component Designer by the client and the correctness or accuracy of this information as it may relate to a specific
project. The Member Component Designer accepts no responsibility and exercises no control with regard to fabrication, handling,shipment,
and installation of member components. Each member component specified herein has been designed as an individual building
component. Each component shall be incorporated as part of the building design by a Building Designer(registered architect or
professional engineer,as applicable). The Building Designer shall review the design loading, member component geometry,and all other
aspects of each component design to ensure that the data shown are in agreement with the local building codes, local climatic records for
snow or wind loads, project specifications,or special applied loads.
3. FABRICATION NOTES
Prior to fabrication,the fabricator shall review this Member Component Document to verify that this Member Component Document is in
conformance with the fabricator's plans and to realize a continuing responsibility for such verification. Fabrication of member components
shall not proceed until the fabricator has certified drawings in hand.
4. PRECAUTIONARY NOTES
Refer to the manufacturer's recommendations for instructions on handling,bundling, and delivery of the member components specified
herein.
5. MODIFICATION OF COMPONENT MEMBERS
Refer to the manufacturer's recommendations for instructions on allowable modifications of the member components specified herein.
6. MEMBER COMPONENT TO MEMBER COMPONENT CONNECTION DESIGN
The design of any connections between member components and other member components is not provided with the component designs
specified herein. Web stiffener requirements at hangered connections depend on the connection style and are not included in this design.
Supported components attached to the side of this member with reactions greater than 400 lbs shall be attached in such a way to preclude
twisting of this member.
7. MEMBER COMPONENT TO STRUCTURE CONNECTION DESIGN
The design of any connections between the member component and other elements of the overall structure is not provided with the
component designs specified herein.
8. UPLIFT REACTIONS
Floor joists,beams or girders with multiple spans may generate uplift reactions due to gravity loads. The reactions shown in these
calculations assume that all of the bearings are infinitely stiff. The Building Designer shall review all reaction forces and ensure that the
structure can resist any uplift reactions appropriately.
9. LATERAL BRACING
All lateral bracing requirements apply along the entire length of the component member. The design of the individual component member
brace and the anchorage of the brace is the responsibility of the Building Designer. Design assumes that the component member is braced
top and bottom at all bearing locations.
O��� �N Or MgsS-9c,
g JEREMY MARTIN m
A1110041111
,.,�,,,,,,,_ GILSTRAP
All product names are trademarks of their respective owners. o STRUCTURAL to
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. NO.50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete ,ea .Q • Q
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this y • F'
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet.This design assumes product G/CT f
installation according to themanufacturer's specifications. ' ` �
Keymark Engineering
07/31/2013
•
KeyBeam® Calculation Keymark Engineering, Inc.
6707 Winchester Circle
..,%:' 07/31/13 Boulder, CO 80301
l , .
Phone:303-443-2068
l'' 05:38:19
EWPjobs @keymark.com
ENGINEERING,NC 1 of 5
Cover Sheet
Job: 49OrchardSt2
Confirmation#: 0731073802
Contact Person: Bill Ingham
Company Name: Roseburg Forest Products
PO Box 922
South Hadley, MA 01075
Phone/Fax: 4134273233/8772711080
Email: billi @rfpco.com;davea @rfpco.com
Ship-To Contact: Adam Tredo
Ship-To Company: Seven D
Ship-To Phone/Fax: 8008006894/
Ship-To Email: atredo @degol.com;plans @degol.com
Member Information
(1)-Girder 1.KYB (2)-Girder 2.KYB
Comments
O���P�SN OF MgSS�cyG
Z JEREMY MARTIN m
r„e1�,„.,„ O GILSTRAP -i
All product names are trademarks of their respective owners. U STRUCT URAL Ch
Copyright(c)2012 by Simpson Strong-Tie Company,Inc.ALL RIGHTS RESERVED. NO 50090
This drawing is an integral part of a floor joist component document as defined in theattached General Notes.This drawing is not complete ,,a. ��
without the accompanying General Notes.The Engineer's Seal on this drawing indicates only that the floor joist component shownon this
drawing meets applicable design criteria for Loads,Loading Conditions,and Spanslisted on this sheet This design assumes product C'/C e T /,
installation according to themanufacturer•s specifications.
Keymark Engineering ��
07/31/2013
-- — —
Z-8-L L
o>} �'�, 8.8-0 3 =2 m
M a(* ab m ^ t C 0 m o 0 C
i v - 0 2) m
y ° 00h 8 EE a 8 v S
LI,0,Y B v Z N� t-8
_N m 2 Z< ET 5Z E
'E ° 8 p¢,"
qg 1 ' c0 ENc
m
o d
b 8o- § O; :VG �gc"$
2 g� a g0 act o ; °r L g)cv
H N p N E O O r U
I- O r O r O.,-
1p m,_ ° ' §9y Y n
-IM M ' n • H° z
N3N N W ° °p
c
f '0- 1-8 .0
2 a 3 g N `�g y c c�'o
Z NX "i811;c�c�— 4)(p7
m = tl .z0 FE:22.� y Ha U a
w a r - ng-� a � ¢ Qm
w 2 N ~ g".:.-.1g",-,-...._`10-1—.-a N 0)n
N m . p .....1-
a, a ac NAB a J
o _
0. C re j M � it E .. co:4
L
o pN$2 9
0 m W.§ 8
0.9NU) )
S - °m WN O�d�ii' 6 C
A A =9 9 5 a ��j
.A .I� ,1 ,I) 2 O
w, c' rnm(o U-{vae q 52 tr,,` " X L
r r C P°]N.0) f h fib N {0n fi
co 44° I ou �c9i �+�.2 o
aapq 6 Sill E 3
..._11—_,N §5�0i8 ; pU7E� .. CtE
a 7i� o,
// N II o >x a� mg' p $'E g
I ANEMONE. - I- N 4;i2 0 ,C N mom V
IV N W 4 N N-Ui -- J
�O o L �g pCm,
2
C a 8A-61-1:7).2, ,0 8
_ ,,§71.7-;�f�N N Y 8 . q
. q.0 r°a
a
$
r r c.,...,... LA m 8 °C m
wm V °r r coM o of rirn ° °m w x y M z E 0 l d E rnW 4 m
N 0) v w
V ' CG C � � w 2 2
7UUmg 033N0 0Q ^L NQ_
UI-ro3, m b
1N _ 8 O
m U 11111111° Im 7 W E g Q U L L t
\ O o-c:4056 bm N» * N N NUM etC,N
I- I 4 o` M M
I- 0
2 4
N Iw g
M N C
IN 4..„ a
E_ til
% t
rr e- e- 0b8 8 b
rr rr = a
tiff tir� 5 wd 8. °
N.. P- ti ti o E e0 8 N
U�JO U
N N 7 g
w ,- O' N 0 b a
r
co a 0" d d a N-C N N a)t ' ----- a d C'C U U U 0 0 I-
>. E E J J- J'"-i (
8
_ M N
C d N N O b ; N r ° on °
A )
II o aaa 2 a 6_6_
o N
k W (pp
c.c.)� al°^000 O)o V y m N� )(
C _ GO G T $ O)I OOO N NN N Rw_ € 2 m7 II v C C CO
m CO N c 3 Nn 0. o OotO cu cKt
M o, ; 10 v) WOO ZO O OII II II �-an a � u a WOcv
0 CO _99II' 0 Q� n_I_10 COa0�Va.609 0 I D C7 00 Ii
g C7 so.y m 0000C.)0 m000.-0.2, 007
d -AI--I-om JI-03 mHNnm R'N(OMN2N(OMNCD UI-N
m>-
--- ' 01,"I. __ _■
d
,6-9-O
(1!;., 11 Q ac ti o -2 -
} _ d " n
_ . a
o 0 .c
. m
w n N N A N
0n Ntz 2_
4,,_N Y- ° ( 2(2 oZQ �E,
g c 0 G L N X
E g.� 8 E°gyEgg2
yC m O �. N U) '}$IpNj
N' ' A L N 2 6()°aL,QC1�N 872 L�S
v'YA 3 N Q' `
H .,i r Cl.'- mq 2"1541 y
pN N _ [A N N t
01° L p rB/y� C ciL 6Z
N2 W .�Q Q C .QCNO
▪ IA 18.§81b-vw/vp
2 I8 6 j 2 c�� tcm
Z ii'h ~ Ly ypm m' ^p°y�:Q a'0 R w oiX
_• 2 a 2 d C {0 7 N G N§ C L� N
J �j C p� m-g x.1 N l0
W
▪ c °N :- ��.aRcag^ pia g3
m
y m a U) NUUUC)C°3� CV oun
O r t —
ce 0. II r
N 3
r o �` jNN-Z d� g 3 C.
N-
O
o-o-e Qxqd 6 r
0 C C d44-2 N°E g b 8 §o
a r r r t• -A A -94g N -gi
�i1 m N to to M �� � 4' $ R B us
✓ r N N C °r�L
� Y �Q y�j'fps d
y C O 1 2_ C N O O N
II d M 09L 4 2 mpm viro 6
CO\\ .....■ A N OW 0R L'Z ;L L
Q .a
O _W�� �' W NNO �? UC o; ,=§8 S
N V B 8.
T N N NN- . 0 4 U C-° V O
OMB 0 a m C �p,$O
,0- f ^
_ . U NN p wUA a b-
0 ~� qu N �
I N,--I,.< � yJOX� D
T.r1ty Or °• `� OiriiiIiii 1 ON N c0 Ih O - .= _m_ . 8.. . .
1
✓ �" o�.1 Yi 4 0o;m 0 3
Av 0r ri 4N°d 14 . s .sRsL
N-N N �O- r ^ n N Nth N m
00o x I�r�-ova-a-08 (p ^w 4�' Uw °r E o
m• m--- dice- (O vQ N. . N �Nq N y>
c01-03 ,- 02'-30N Rr NMQ W 0E-g `S of 67 n a.Q aL
p \\ `, a a n -1mOu a 1-58 E H .oHgH - g
K ; fad m A — O 4 o aQ n o.-.E_ 0` o,,,-.m.-. c
2 avAa0N M z.- a)_ N NUMw7c1° (Om
W
2
I? y M g
N
O m •
C
L I- 3
0 U)UU )N- Q
4',77P8 2R
a d d
w °NBA
Iry st vi7 21-
✓ r r r d 0 g 0 ? -
in in in m,E, 0 m n o
IC I,- P rs. N�J�-8 8 N co
N O N C X
N ,_ N i ,L
• O VF O U 3 aD c0 Q
✓ of a r6811.
e- a d O O 61-'7: RR e
L N'- " m C C U UU UU
p ^ iL fn• fD N M r4n
ON
E N _ r($ 4 r aD
V A z0 Z 0-0 v �0 r r n
\\ 8 U 0 U U Cp N 6 E
O� ■
V aR0.=—.=00^000 aNCONO m N.. 0
0 a On O >- V 0 0 X N X N X N i 2
C - r T X cyy. 13>1 N I-N m N 'pQ _
,- N Q 2 V ,3 N
CO N O GCC
coo ' Z
M _a _ °g o mO 0 00T,0= 0 N tt > N
F C I Z W 2 I 2 2 2 F n u a u a u m m H u w
n w "8=9=-0' O 8 JJJ mU 0 00.j0u U 2 0 U
o al N —_. N oo EOJ0 2a I- a H:2 x o:
• C7 — Eo-v oUUUU �o o w�aoo� m o
E-v-S (1 _,1--1-00m _.1-., m >m I-O)m� C'C(N (N UON,(ON LL
Y:
•
co,- oup
CO T 680, m 2
0
MX d y _
�o a m ° •3
A> H d
No. - y
o4) Q- o m
-Z . 2 to=m a a,
NL — N Z 'n 2�
41r- 6 in 12
a o Xgg
N o O N
D ;i. p
pN
-Do o a
C7 1 �', N
FO a-a.N- ri m72.6.- 93tg
rn
_� 0— a§a a) c xi S
N U
m = 0,c Z
NY�t „,.I h .. C W ,.Q N 3�
mSQ 4 Fo ; $�=Ta'-�� 'irj
w o, � ti v- N.
g� nv$a g��8'
Y C p=j p
2-m N`” ,Nm-O'N w
{7 G
~ 2 g
y a U h r ana 02
W m ZZ a ~ <m
o A mOuN w co m .- .- co.-
• 2
CZ - = g .m o N� �0 II - N t
a. i V
' i LZE-2 fi o R
S c 0-0-£ n n fn E o E
.NO E
M O O Uq ° Ul-r.: , z$
a
M B r N U
cl M
. ~ ~ `
ll1 ! tIifli ce)
ce) J JJ tD OUOg I E2 V O� U
F. n a E cQi_ R
p
_1-J 1- NN N n j -1(2),: m _
// di 'TIM n ,0 O r,c E $ 3 w
M m N 1M<{ .44)o N o m Iz. :2 O 0- 3?i
NN Nn N's EJC 8.2-2� q Z
N 4 J m N U p L > �.
0 — dc' 0m U_—U� lS'q,� qpa fn
r e- Or O Ob co S
r w°w t 09 Q
1 1 1 1 NA EL a�
MM MO 19 LO S �cod$ u yqy ', 15m E
I I d r L 8 = mp, y;,
or`z II m-= m= = N
N6 to O W4a @y,a,qyy9,j m
II Opppp II Q r0 =O Q m +' ++N y
AODO T -;17611-.209- 6-Ng aN N �cl 1� ym, yn'
K 0 0 0 Y O N 0 c N m m�=Q
o CD Moon m O�� 6 v¢ .„m r< m� -.4`4 Ea'.
N
CL 000H II HSZS 01-Y DI--,I- T~ 6Ta
U'D� U m�.-.8j
C -.1 A,hm N 8_ V NNUt7; a N(O z N I�
g• o A
2 U F
co I
nt 'it
met st Q LL77ww QA 8
1 1 1 d 8
in. O O �ti �b t 73 1 1
g i6
U00 (-) z b QN
QQ V �
m 8 o
S,[rr
_ a � N Nnj ma JaU d m II e
C 6 N m�
O M V 4 5 M h � �
1- H § Ro O MN
8 V a 0 C 0 O- F c�a c N N C
A
_Q m Q
O OQ
> d U SS U U I- m-
"
a,A Y ' , d� a , u
N N — O 0)C`
NN �^ Gbh
C M 0 d ❑Z "3 "@ th M ' , n N
d E Ion
O A . (ana O1 a in 0 -,N oo
o c00^000 0� m 7. N00 X N O
O, > p000 N N N ' (�6 q_
N. C OZ g �__-= @_'y IIII6IIaIIIINIIII W=AN
C W E•Y-Z - O,J JJJ mUUUU.gU [.1 U = D 0 UUN II
M .to
6.0-E ---
m <J �OJO 2al-�a �� QQ
o ~ E-Y5 - a OJ1-�i-mm ��mmi-cnm Wa'.-lom.-m.-u,m.-o WO_
pa IP>»ai Aew uopeionN, A4 P.O., s+ .o suosuawPlo uus a4 ION. I J9 P BaauBua ZO N • ;
D =...,,1. p P +W s you.ssauno/iau.x 8p. P Alas ,3 Nou wya essune n 72 I`
9suotivsaq 11 atl N
wl ssuaww p P p yauwa8'suosu N an IN ala sswtlsw AN oss 1 H sswwo/aux.8 of pal sse neap pue suetlo N011b d 31NIS a iaau eu3 ss III pi 4l Qi w 1II •j►
ssal 3 PseBw Issanbas uotln app..env)Z+astle4 d 9 W assnsl pooun paewuo,aseld le aW 31 W S 4 P F O4 ¢ p `
A s�' os AM uuawannbw pue suo ew 9 vss to as 4 9 atl P W n P B E a Kp r
ssneilwuaw� y Aqp Ieu no nywewuda ( uoN , 98_p n43o nuawainbasl I 3 P 4 ani a3 N 8 g it 2 II ,
Vs le V 1 9..1..1.1 sronsue'enua9 H Ilea P Pa 1 ei Asaoostl nun 9 i Z Z L
9, ob uo N91 p aes asnsua bw auk...as r 3 nuawwus nl Nsu P •
nn sns w mils,,o Ay.,,e.sang a41 nW 5.M w.N y sfNsv s IJ311 ua1 s w8u3 soul M P+ldnns a slassnglo ualew Iryap a sa quo s.Paitl s,�311oslaayea4l� € @ �,
ays 9u!N.u sal P aeltl lei ssnOS uou s44 O Q$ 1
1117 II'+ @@11VMJOdO
w
00-01.-CZ > z
z
w
I
I
CD
O e— O
oI
O
9
N
00-8 -Z
x I Ng
cp a //, ,
cI CO
o O
O
— o
co
i.
I c
X— co-
-_,_ ,. .;
_, , v
1 iba
it�'■
o r,
N °'
c
co
t c
CD
o '
r: iii O
acv
C i. • c Y
J
x O a�
•
O 2
1 (C)
O x v
1 N o
Oaic
O 1 c
CS)
c
O v,
N.
Z
N o
1.
V V =N mo
t ^
Eco
aQ
:o)6
v
0p • a w iri
W
€m CU
00-£0-ZZ ^ `_
?co >,
CONTRACTOR QUOTE PRINTED ON: 07/25/13 PAGE 1
, SS('‘‘
QUOTE # Q1307133
DATE QUOTED:07/12/13
EN .1
181 GOODWIN ST VALID UNTIL: 08/09/13
CORP• • 'T • PO BOX 51027
/ANFA�∎�•∎∎4 INDIAN ORCHARD, MA 01151 .lob: PROSPECT / KONHEIM
MANUFACTURERS OF ROOF & FLOOR TRUSSES 24-26 ORCHARD ST
Phone(413)543-1298 Fax(413)543-1847 Toll Free(800)456-0187 NORTHAMPTON, MA
Quote To:A. Boilard Sons, Inc. Requested By: JOEY
P.O. Box 51065 q y'
Indian Orchard, MA 01151 Quoted By: Adrian Santos
Attn:JOEY
Phone:(413)-543-4100
ROOF TRUSSES LOADING TCLL-TCDL-BCLL-BCDL STRESS INCR.
INFORMATION 40.0,10.0,0.0,10.0 ROOF TRUSS SPACING:24.0 IN.O.C.(TYP.) LAYOUTAS 07/25/13
1.15
PROFILE QTY) PITCH I TYPE BASE I 0/A LUMBER OVRHG/CANT I SHIPPING I UNIT I
PLY TOP BOT TRUSS ID SPAN SPAN TOP I BOT LEFT RIGHT HEIGHT WEIGHT
_,=,,_ Scissor Truss 00-08-00 00-0.8-00
8 3.50 1.73 Si 23-10-00 23-10-00 2 X 4 2 X 6 04-00-03 86
Common Truss 07-0.5-14 07-05-14
�//: `-`. 27 5.00 0.00 T1 07-03-03 07-03-03 2 X 2 X 6 05-04-03 109
;_ Special Truss 00-08-00 07-05-14
°? 3 3.50 1.73 T2 15-06-10 15-06-10 2 X 4 2 X 6 05-04-03 99
Truss Engineering Corporation(TEC)strictly adheres to the'Standard Responsibilities in the Design of Metal Plate
Connected Wood Trusses'as defined by TPI Chapter 2(available upon request)regardless of any job specific SUBTOTAL
specifications unless clearly defined otherwise in writing by TEC.
This product list is Truss Engineering Corporation's INTERPRETATION of plans and drawings as supplied to us. No
responsibility is taken or implied by TEC for the structural integrity of the structure below the trusses or the affects of
TEC's product on the structure as a whole. The building owner/owner's agent is solely responsible for verifying all
dimensions,geometry,loads and load requirements for accuracy and full compliance to construction documents and shall
be responsible for notifying TEC immediately of any discrepancies. Truss Engineering Corporation is NOT responsible for
field verification of dimensions or special conditions.
The building owner/owner's agent is responsible for coordinating all construction details between trades. The truss
installer shall follow all BCSI recommendations,construction document specifications as well as any site specific GRAND TOTAL
requirements to ensure safe and proper installation. No loading shall be applied to trusses until properly and fully
installed,including all sheathing,hangers,wall anchors,lateral web bracing(as shown on individual shop drawings),and
permanent bracing(as required by the construction documents). Installation contractor shall refer to the individual truss
shop drawings for all structural requirements of trusses,including but not limited to bearing locations and requirements,
ply to ply nailing,lateral web bracing,and truss spacing.
No trusses supplied by Truss Engineering Corporation may be cut,drilled,or altered in any way without first contacting
TEC and receiving engineering documents allowing such.
*** THESE DRAWINGS HAVE BEEN REVIEWED AND ARE APPROVED AS AN ORDER ***
Approved By: Approval Date:
PO#: Requested Delivery Date: