Loading...
38A-107 (7) Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA D. Preparation 1. At all fire rated assemblies, prepare all penetrations for pipes and perimeters. E. Application 1. Install approved fire safmg insulation of proper size leaving no voids. Compress and friction fit fire safing and use attachment clips where necessary. 2. Seal completely around all openings and over the fire safing insulation with sealing compound. 3.06 FINAL CLOSEOUT A. Identification: Apply signs to control, drain, test, and alarm valves identifying their purpose and function. Provide lettering size and style selected by Architect/Engineer from NFPA's suggested styles. B. Adjustments: Place the system in operation with controls functioning. Adjust controls and apparatus for proper operation. Test thermometers and gauges for accuracy over the entire range. Remove and replace items found defective. C. Provide all required system trip tests, flow tests, system flushing and pressure test as required by NFPA, and the Northampton Fire Department. At the conclusion of each test provide test certificate signed by the owner, General contractor, and the Fire protection contractor. 3.07 SERVICES A. Water Service 1. This contractor shall be responsible for providing a new 6" sprinkler service to from the municipal main in Larkspar Road to the building, including all site work, fire hydrants, piping, valves, etc. The fire protection subcontractor shall further test the entire new service as required by NFPA, and shall pay all fees and obtain all permits required to perform this work. END OF SECTION 15300 FIRE PROTECTION 15300- 23 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA work with other Divisions, shall be the responsibility of the Fire Protection Subcontractor failing to co- ordinate, who shall make the corrections at his own expense. B. Work shall include furnishing and locating sleeves or inserts required before the new walls are built, or be responsible for the cost of cutting and patching required for pipes where sleeves were not installed, or where incorrectly located. The Fire Protection Subcontractor shall do all drilling required for the installation of hangers. C. Patching of all holes after installation of piping or equipment shall be performed by the General Contractor or appropriate tradesmen. D. All piping, cutting, and threading shall be done in a location approved by the Architect/Engineer. E. No pipe cutting or threading shall be done in areas where completed concrete floor slab is to remain as fmished or be painted later. Should this area be necessary, the Fire Protection Subcontractor shall cover the entire working area with canvas tarpaulins in an approved manner. 3.03 FIRE SAFING A. Work Included: Provide labor, materials, and equipment necessary to complete the work including, but not limited to the following: 1. Fire safmg at all penetrations through fire barriers. 2. Fire safmg at all penetrations through smoke barriers. 3. Extent of fire and smoke barriers as indicated on the Architectural Drawings. 4. Fire safing at all penetrations through floors, shafts, corridor walls, stairway walls, mechanical rooms, electrical rooms, vaults, storage rooms, kitchen, machine rooms, outdoor storage rooms, and receiving rooms. B. Safmg Insulation 1. Fire safmg insulation shall be Thermafiber as manufactured by USG Interiors, Inc. or Architect- Engineer approved equal, 4" minimum thickness by the required full length and width, or as indicated on the Drawings. 2. Provide incidental galvanized steel clip anchors. C. Seal Compound: At "poke- through" openings, apply "Firecode" seal compound as manufactured by USG Interiors, Inc., or approved equal, over Thermafiber fire safmg. FIRE PROTECTION 15300- 22 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA jacket with lock for all valves. 14. Outside gate valve shall be equal to Kennedy Model 952 XP -GH complete with Figure 123 two -piece valve box and cover and figure 122 valve wrench and tamper switch. 15. Wet -pipe alarm check valve shall be equal to Reliable Model "E" with conventional trim kit, retarder, and excess pressure pump. 16. Alarm Test Modules: Furnish and install AGF Manufacturing, Inc.'s UL listed and FM approved "Test and Drain" for the alarm test loops, where indicated on the drawings, complete with combination sight glass /orifice. PART 3 - EXECUTION 3.01 CLEANING AND TESTING A. Prior to connecting sprinkler risers for flushing, flush water feed mains, lead -in connections and control portions of sprinkler piping. After fire sprinkler piping installation has been completed and before piping is placed in service, flush entire sprinkler system, as required to remove foreign substances, under pressure as specified in ANSI/NFPA 13. Continue flushing until water is clear, and check to ensure that debris has not clogged sprinklers. B. After flushing system, test fire sprinkler piping hydrostatically, for period of 2 hours, at not less than 200 psi or at 50 psi in excess of maximum static pressure when maximum static pressure is in excess of 150 psi. Check system for leakage of joints. Measure hydrostatic pressure at low point of each system of zone being tested. Test dry-pipe hydrostatically except, in freezing conditions, test with air at pressures not less than 50 psi, for period of 2 hours. Check system for leakage. Leave differential dry-valve clappers open during test, to prevent damage. C. Repair or replace piping system as required to eliminate leakage in accordance with ANSI/NFPA standards for "little or no leakage ", and retest as specified to demonstrate compliance. Do not use chemicals, stop -leak compounds, mastics, or other temporary repair methods. 3.02 CUTTING AND PATCHING A. Cutting and/or patching of holes 4 inch diameter and/or larger openings and holes, required for the installation of fire protection in the building, shall be performed by the General Contractor. All holes smaller than 4" diameter shall be by the Subcontractor. All work and materials shall be installed in such a manner and at such time to keep cutting and patching to a minimum. Location for openings shall be checked by the Fire Protection Subcontractor and error, due to failure to co- ordinate FIRE PROTECTION 15300- 21 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1. Upright sprinkler heads shall be Viking Sprinkler Corp., Model "M" standard upright sprinkler head, rough brass. Temperature rating 165 or as required by the insurance underwriter. Boiler Room heads to have 212 rating. 2. Pendent sprinkler heads shall be extended range polished chrome fmish. Viking Model "M" semi - recessed rated at 165 unless noted otherwise. Dry pendants shall be equal to Reliable Model G3FR with white finish. 3. Horizontal sidewall sprinkler heads shall be Viking extended range Model "M/ME" with chrome finish, temperature 165 unless noted otherwise. Dry sidewall heads shall be equal to Reliable Model G3FR with white fmish. 4. Concealed pendent sprinkler heads shall be Central Model "A" Royal Flush. 5. Tamper switches shall be equal to Potter Electrical Signal Company, Model OSYS -B, small case, and shall be installed on all control valves for the sprin- kler system. 6. Fire Department pumper connection shall be equal to Potter - Roemer, Inc. Stortz Type, cast brass identification base plate lettered to read "Automatic Sprinklers ", cast brass pin lug plugs and chains on each pin lug swivel spaced 9 inches on center. Threads shall conform with the local Fire Department standards. Furnish and install 4" check valve with automatic ball drip equal to Potter - Roemer Model 5982. 7. Automatic ball drips, as manufactured by Potter - Roemer shall be Fig. 5982, size 3/4 ", of straight design in case brass. Install in horizontal position only. 8. Swing Check valve shall be equal to Central, Model "80" with tapping for automatic ball drip, size as required. 9. Double check valve assembly as noted on plans, DEP approved for backflow prevention, Watts Model 709DDC with check meter. Provide test kits Model TK- 7 -BFP, and one repair kit. 10. Spare sprinklers shall be provided in one 12 -head cabinet equal to Reliable, Model A -1 cabinet. Each cabinet shall have an assortment of heads, as well as three (3) spare dry head and stems of various representative lengths, as used on the job, and also an approved type sprinkler head wrench; mount cabinet in alarm check valve area. Provide one cabinet at each riser located at riser. 11. Subject to compliance with requirements, provide fire protection specialties of the following Grinnell Fire Protection Systems, Co., Inc., Viking Corporation, or equal. 12. Alarm Test Modules: Furnish and install AGF Manufacturing, Inc.'s UL listed and FM approved "Test and Drain" for the alarm test loops, where indicated on the Drawings, complete with combination sight glass /orifice. 13. Valves with Built -in Tamper Switches: Furnish and install, and each flow control station, Milwaukee Valve Co.'s Model BB- VSCSO2 grooved ends, 175 psi, slow closing "Butterball" butterfly valves, complete with built -in tamper switch for 2 -1/2" pipe size; Model BB -SCSO2 for threaded pipe 2" and smaller. Valves shall be FM approved and UL listed. Provide PVC FIRE PROTECTION 15300- 20 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1. Threaded End, 2" and Smaller: FM, UL- listed, 175 psi, bronze body, solid wedge, outside screw and yoke, rising stem. Crane: 459 Fairbanks: 0222 Hammond: 1B681 Jenkins: 275U Stockham: B -133 Walworth: 904 2. Flanged End, 2 -1/2" and Larger: FM, UL- listed, 175 psi, iron body bronze mounted, solid wedge, outside screw and yoke, rising stem. Crane: 467 Fairbanks: 0412 Hammond: 1R1 154 Jenkins: 825 -A Stockham: G -634 Walworth: 8713 -F C. Check Valves 1. 2 -1/2" and Larger: FM, 175 psi, iron body bronze mounted, renewable composition disc and bronze seat ring, bolted cover, flanged ends. Fairbanks: 0711 Jenkins: 729 Stockham: G -940 Walworth: 8883 -LT D. Install valves where required for proper operation of piping and equipment, including valves in branch lines where necessary to isolate sections of piping. Locate valves so as to be accessible and so that separate support can be provided when necessary. E. Install valves with stems pointed up, in vertical position where possible, but in no case with stems pointed downward from horizontal plane unless unavoidable. 2.06 FIRE PROTECTION SPECIALTIES A. Provide fire protection specialties, UL listed, in accordance with the following listing. Provide sizes and types which mate and match piping and equipment connections. FIRE PROTECTION 15300- 19 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA support. Space attachments within maximum piping span length indicated on MSS SP -69. Install additional building attachments where support is required for additional concentrated loads, including valves, flanges, guides, strainers, expansion joints, and at changes in direction of piping. F. Install hangers, supports, clamps and attachments to support piping properly from building structure; comply with MSS SP -69. Arrange for grouping of parallel runs of horizontal piping to be supported together on trapeze type hangers where possible. Install supports with maximum spacings complying with MSS SP -69. Where piping of various sizes is to be supported together by trapeze hangers, space hangers for smallest pipe size or install intermediate supports for smaller diameter pipe. Do not use wire or perforated metal to support piping, and do not support piping from other piping. G. Support sprinkler piping independently of other piping. H. Install hangers and supports to allow controlled movement of piping systems and to permit freedom of movement between pipe anchors and to facilitate action of expan- sion joints, expansion loops, expansion bends and similar units. I. Pipe Slopes: Install hangers and supports to provide pipe slopes and so that maximum pipe deflections allowed to ANSI B31 Pressure Piping Codes are not exceeded. J. Hanger Adjustments: Adjust hangers so as to distribute loads equally on attachments. 2.05 VALVES A. Provide factory- fabricated valves recommended by manufacturer for use in service indicated. Provide valves of types and pressure ratings indicated; provide proper selection as determined by Installer to comply with installation requirements. Provide end connections which properly mate with pipe, tube, and equipment connections. Where more than one type is indicated, selection is Installer's option. 1. Unless otherwise indicated, provide valves of same size as upstream pipe size. 2. Provide handwheels, fastened to valve stem, for valves other than quarter - turn. 3. Provide lockable PVC covers on all valves with tamper switches. B. Gate Valves FIRE PROTECTION 15300- 18 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA A. Provide factory- fabricated piping hangers and supports complying with MSS SP -58, of one of the following MSS types listed, selected by Installer to suit piping systems, in accordance with MSS SP -69 and manufacturer's published product information. Use only one type by one manufacturer for each piping service. Select size of hangers and supports to exactly fit pipe size. 1. Adjustable Steel Clevis Hangers: MSS Type 1, for piping larger than 6 ". 2. Adjustable Steel Band Hangers: MSS Type 7, for piping 6" and less. 3. Two -Bolt Riser Clamps: MSS Type 8. B. Provide factory- fabricated hanger -rod attachments complying with MSS SP -58, of one of the following MSS types listed, selected by Installer to suit horizontal piping hangers and building attachments, in accordance with MSS SP -69 and manufacturer's published product information. Use only one type by one manufacturer for each piping service. Select size of hanger -rod attachments to suit hanger rods. 1. Steel Turnbuckles: MSS Type 13. 2. Swivel Turnbuckles: MSS Type 15. 3. Malleable Iron Sockets: MSS Type 16. 4. Steel Weldless Eye Nuts: MSS Type 17. C. Provide factory- fabricated building attachments complying with MSS SP -58, of one of the following types listed, selected by Installer to suit building substrate conditions, in accordance with MSS SP -69 and manufacturer's published product information. Select size of building attachments to suit hanger rods. 1. Top Beam C- Clamps: MSS Type 19. 2. Side Beam or Channel Clamps: MSS Type 20. 3. C- Clamps: MSS Type 23. 4. Side Beam Clamps: MSS Type 27. 5. Malleable Beam Clamps: MSS Type 30. D. Subject to compliance with requirements, provide hangers and supports of one of the following: B -Line Systems Inc. Carpenter and Patterson, Inc. Corner & Lada Co., Inc. Elcen Metal Products Co. Fee & Mason Mfg. Co. ITT Grinnell Corp. E. Install building attachments at required locations on structural steel for proper piping FIRE PROTECTION 15300 17 1 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1. Steel Pipe: Fabricate from schedule 40 galvanized steel pipe; remove burrs. 2. Sleeve Seals: Provide sleeve seals for sleeves located in foundation walls below grade, or in exterior walls, caulked between sleeve and pipe. 3. Install pipe sleeves of types indicated where piping passes through walls, floors, ceilings and roofs. Do not install sleeves through structural members of work, except as detailed on Drawings, or as reviewed by Architect. Install sleeves so that piping will have free movement in sleeve, including allowance for thermal expansion; but not less than 2 pipe sizes larger than piping run. Install length of sleeve equal to thickness of surface; except floor sleeves. Extend floor sleeves 1/4" above level floor finish, and 3/4" above floor finish sloped to drain. Provide temporary support of sleeves during placement of concrete and other work around sleeves, and provide temporary closure to prevent concrete and other materials from entering sleeves. 4. Sleeve Seals: Install in accordance with the following: a. Fill and pack annular space between sleeve and pipe with oakum, caulk with lead, on both sides. b. Note fire safmg specified in subsection 3.04. N. Provide pipe escutcheons as specified herein with inside diameter closely fitting pipe outside diameter, or outside of pipe insulation where pipe is insulated. Select outside diameter of escutcheon to completely cover pipe sleeve extension, if any. Furnish pipe escutcheons with nickel or chrome fmish for occupied areas; prime paint fmish for unoccupied areas. 1. Pipe Escutcheons for Dry Areas: Provide chrome plated sheet steel escutcheons, solid or split hinged. 2. Subject to compliance with requirements, provide pipe escutcheons of one of the following: Chicago Specialty Mfg. Co. Producers Specialty & Mfg. Co. Sanitary-Dash Mfg. Co. 3. Install pipe escutcheons on each pipe penetration through floors, walls, partitions, and ceilings where penetration is exposed to view; and on exterior of building. Secure escutcheon to pipe so escutcheon covers penetration hole, and is flush with adjoining surface. 2.04 SUPPORTS AND ANCHORS FIRE PROTECTION 15300- 16 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA E. Locate piping runs, except as otherwise indicated, vertically and horizontally (pitched to drain) and avoid diagonal runs wherever possible. Orient horizontal runs parallel with walls and column lines. Locate runs as shown or described by diagrams, details and notations or, if not otherwise indicated, run piping in shortest route which does not obstruct usable space or block access for servicing building and its equipment. Hold piping close to walls, overhead construction, columns and other structural and permanent- enclosure elements of building. Wherever possible in finished and occupied spaces, conceal piping from view, by locating in column enclosures, in hollow wall construction or above suspended ceilings; do not encase horizontal runs in solid partitions, except as indicated. F. Electrical Equipment Spaces: Do not run piping through transformer vaults, elevator machine rooms, and other electrical or electronic equipment spaces and enclosures unless approved by the Building Department. Install drip pan under piping that must be run through electrical spaces. Any piping intended to be run through electrical spaces shall be reviewed by the Architect prior to installation. G. Thread pipe in accordance with ANSI B2.1; cut threads full and clean using sharp dies. Ream threaded ends to remove burrs and restore full inside diameter. Apply pipe joint compound, or pipe joint tape (Teflon) where recommended by pipe /fitting manufacturer, on male threads at each joint and tighten joint to leave not more than 3 threads exposed. H. Flanged Joints: Match flanges within piping system, and at connections with valves and equipment. Clean flange faces and install gaskets. Tighten bolts to provide uniform compression of gaskets. I. Grooved Pipe Joints: Comply with fitting manufacturer's instructions for making grooves in pipe ends. Remove burrs and ream pipe ends. Assemble joints in accordance with manufacturer's instructions. J. Install ductile cast -iron water mains and appurtenances in accordance with AWWA C600. K. Clean exterior surfaces of installed piping systems of superfluous materials, and prepare for application of specified coatings (if any). L. Provide temporary equipment for testing, including pump and gages. Test each natural section of each piping system independently, but do not use piping system valves to isolate sections where test pressures exceed valve pressure rating. Fill each section with water and pressurize for indicated pressure and time. M. Pipe Sleeves: Provide pipe sleeves of one of the following: FIRE PROTECTION 15300- 15 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA Lightweight Steel: Roll grooved. j. Manufacturer: Subject to compliance with requirements, provide grooved piping products of the following: ITT Grinnell Corp. Victaulic Co. B. Exterior Piping 1. Ductile -Iron Pipe: ANSI A21.51; AWWA C141; thickness class 50, mechanical joint. 2. Cement - Mortar Lining for ductile -iron pipe and fittings: ANSI A21.4; AWWA C104. 3. Ductile -Iron Fittings: AWWA C110, ANSI A21.10, mechanical joint. 4. Valves: Clow Cat. No. F -5707 with No. F -2452 valve box and No. F -2493 cover. C. Piping above ground and within the building shall conform to all requirements of NFPA 13 and shall be as follows: 1. Piping and fittings run below grade shall be ductile iron, cement lined, as hereinafter specified. 2. All concealed sprinkler piping (above acoustical ceiling tiles and plaster ceilings; in pipe chases) and exposed sprinkle piping downstream of alarm check valves, shall be Schedule 10 seamless light wall, steel pipe with rolled grooved ends, for piping 2" and larger, complete with suitable couplings and fittings for rolled grooved end steel pipe. 3. All concealed piping and all exposed sprinkler piping 1 -1/2" and smaller, shall be Schedule 40 black steel pipe with screwed fittings. 5. All exposed sprinkler piping, 1 -1/2" and smaller shall be Schedule 40 black steel pipe with screwed fittings. 6. Schedule 40 seamless red brass pipe with brass screwed fittings suitable for 175 psi. working water pressure. 7. Type "L" seamless drawn hard copper tubing with solder joint pressure fittings, where noted on the Drawings. D. Install pipes and pipe fittings in accordance with recognized industry practices which will achieve permanently leakproof piping systems, capable of performing each indicated service without piping failure. Install each run with minimum joints and couplings, but with adequate and accessible unions for disassembly and maintenance /replacement of valves and equipment. Reduce sizes (where indicated) by use of reducing fittings. Align piping accurately at connections, within 1/16" misalignment tolerance. Comply with ANSI B31 Code for Pressure Piping. FIRE PROTECTION 15300- 14 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 2. Electric- Resistance- Welded Steel Pipe: ASTM A 135. a. Pipe Weight: Schedule 10 for 5" and smaller; 0.134" wall thickness for 6 ". b. Fittings: Mechanical grooved pipe couplings and fittings; roll -groove or mechanical locking type. 3. Grooved Piping Products (for use on pipes 2 -1/2" and larger) a. Coupling Housings: Malleable iron conforming to ASTM A 47. b. Coupling Housing: Ductile iron conforming to ASTM A 536. c. Coupling Housings Description: Grooved mechanical type, which engages grooved or shouldered pipe ends, encasing an elastomeric gasket which bridges pipe ends to create seal. Cast in two or more parts, secure together during assembly with nuts and bolts. Permit degree of contraction and expansion as specified in manufacturer's latest published literature. d. Gaskets: Mechanical grooved coupling design, pressure responsive so that internal pressure serves to increase seal's tightness, con- structed of elastomers having properties as designated by ASTM D 2000. e. Bolts and Nuts: Heat - treated carbon steel, ASTM A 183, minimum tensile 110,000 psi. f. Branch Stub -Ins: Upper housing with full locating collar for rigid positioning engaging machine -cut hole in pipe, encasing elastomeric gasket conforming to pipe outside diameter around hole, and lower housing with positioning lugs, secured together during assembly with nuts and bolts. g. Fittings: Grooved or shouldered end design to accept grooved mechanical couplings. Malleable Iron: ASTM A 47. Ductile Iron: ASTM A 536. h. Flanges: Conform to Class 125 cast iron and Class 150 steel bolt hole alignment. Malleable Iron: ASTM 47. Ductile Iron: ASTM A 536. i. Grooves: Conform to the following: Standard Steel: Square cut. FIRE PROTECTION 15300- 13 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1. Provide 1 -1/8" sq. white tags with black lettering. 2. Provide manufacturer's standard solid brass chain (wire link or beaded type), or solid brass S -hooks of the sizes required for proper attachment of tags to valves, and manufactured specifically for that purpose. 3. Submit valve schedule for piping system, typewritten and reproduced on 8 -1/2" x 11" bond paper. Tabulate valve number, piping system, system abbreviation (as shown on tag), location of valve (room or space), and variations for identification (if any). Mark valves which are intended for emergency shut -off and similar special uses, by special "flags ", in margin of schedule. In addition to mounted copies, furnish extra copies for Mainte- nance Manuals as specified in Division 1 and forward two (2) copies to the Northampton Fire Department. 4. For each page of valve schedule, provide glazed display frame, with screws for removable mounting on masonry walls. Provide frames of finished hardwood or extruded aluminum, with SSB -grade sheet glass. 5. Mount valve schedule frames and schedules in rooms where indicated or, if not otherwise indicated, where directed by Architect. 6. Furnish complete chart and flow diagram of entire system listing the valve number, fluid controlled, and zone reference location for all valves corre- sponding to the tag numbers. The chart shall be framed under glass and hung in the Mechanical Equipment Room where directed. Furnish two (2) extra copies of the chart to the Architect. 7. Furnish and install a laminated red phenolic plate with engraved white lettering for each zone control flow switch and valve. Nameplates shall be located adjacent to all exposed and concealed valves. Where flow control stations are installed above hung ceilings, nameplates shall be installed just below the ceiling. Provide a similar sign at the sprinkler entrance and fire alarm control panel. 2.03 PIPE, TUBE, AND FITTINGS A. Interior Piping 1. Black Steel Pipe: ASTM A 53, A 106 or A 120: except comply with ASTM A 53 or A 106 where close coiling or bending is required. All dry pipe system piping shall be galvanized steel pipe. a. Pipe Weight: Schedule 40. b. Fittings: Class 125, cast -iron threaded, ANSI B16.4, or flanged, ANSI B16.1. c. Fittings: Mechanical grooved pipe couplings and fittings; cut - groove type for piping 2 -1/2" and larger only. FIRE PROTECTION 15300- 12 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA A. Provide piping materials and factory- fabricated piping products of sizes, types, pressure ratings, temperature ratings, and capacities as indicated. Where not indicat- ed, provide proper selection as determined by Installer to comply with installation requirements. Provide sizes and types matching piping and equipment connections; provide fittings of materials which match pipe materials used in fire protection piping systems. Where more than one type of material or product is indicated, selection is Installer's option. 2.02 BASIC IDENTIFICATION A. Subject to compliance with requirements, provide mechanical identification materials of one of the following: Allen Systems, Inc. Brady (W. H.) Co., ; Signmark Div. Industrial Safety Supply Co., Inc. Seton Name Plate Corp. B. Provide manufacturer's standard pre - printed, semi -rigid, snap -on, color -coded pipe markers, complying with ANSI A13.1. 1. For external diameters less than 6 ", provide full -band pipe markers, extending 360 around pipe at each location, fastened as follows: Snap -on application of pre- tensioned, semi -rigid plastic pipe marker. 2. Lettering: Manufacturer's standard pre - printed nomenclature which best describes piping system in each instance, as selected by Architect. 3. Locate pipe markers as follows: a. Near each valve and control device. b. Spaced intermediately at maximum spacing of 50' along each piping run, except reduce spacing to 25' in congested areas of piping and equipment. c. Branch piping need not be marked. 4. For each feed main and cross main, install zone identification marks on 50' centers. C. Provide manufacturer's standard solid plastic valve tags with printed enamel lettering, with piping system abbreviation in approximately 3/16" high letters and sequenced valve numbers approximately 3/8" high, and with 5/32" hole for fastener. Provide tags on all valves and control devices. FIRE PROTECTION 15300- 11 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA B. The Fire Protection Subcontractor shall pay for repair of damage to the building caused by defects in his work and for repair to plaster, wood, and other materials or equipment caused by replacement or repairs to the entire satisfaction of the Architect. C. Any part of the work installed under this Contract requiring excessive maintenance shall be considered as being defective. 1.17 RECORD DRAWINGS A. Provide a complete set of record drawings. B. Record Drawings shall reflect all changes from the Contract Drawings whether by change order or by field conditions. Principal dimensions shall be indicated of concealed work, fire protection lines, valves, and zone flow switches. All changes must be clearly marked with a bubble drawn around the area of work affected by the change. 1.18 CO- ORDINATION OF TRADES A. The Fire Protection Subcontractor shall give full co- operation to the Subcontractors of other trades, and shall furnish any information necessary to permit the work of all trades to be installed satisfactorily and with least possible interference or delay. The Fire Protection Subcontractor shall co- operate with the other sub trades in preparing a complete set of co- ordination drawings. The coordination drawings for the fire protection shall be prepared by this contractor on backgrounds provided by the HVAC subcontractor and this contractor shall draw all piping, valves, and equipment on this set of drawings B. In areas where conflicts may occur, if so directed by the Architect, this Subcontractor shall prepare composite sketches at a suitable scale, not less than 1/4" = 1 ' -0 ", clearly showing how his work is to be installed in relation to the work of other trades. C. Piping and other equipment shall not be installed in congested and possible problem areas by this Subcontractor without first co- ordinating the installation of same with PART 2 - PRODUCTS 2.01 FIRE PROTECTION PIPING MATERIALS AND PRODUCTS FIRE PROTECTION 15300- 10 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA B. Piping containing water shall not be installed concealed in walls having an exterior exposure above grade. 1.15 OPERATING AND MAINTENANCE MANUALS A. After all final tests and adjustments have been completed, fully instruct the proper Owner's representative in all details of operation of equipment installed. Supply qualified personnel to operate equipment for sufficient length of time to assure that Owner's representative is properly qualified to take over operation and maintenance procedures. This Subcontractor shall video tape the instruction procedures and deliver two (2) copies of the tape with the Operation and Maintenance Manuals. B. Furnish the Architect, for his approval, three (3) copies of an Operation and Maintenance Manual. Inscribe the following identification on the cover: the words, "Operation and Maintenance Manual ", the name and location of the equipment or the building, the name of the Subcontractor, and the Contract number. The manual shall have a Table of Contents with tab sheets placed before each section. The instructions shall be legible and easily read, with large sheets of Drawings folded in. The manuals shall be bound in hard binders or an approved equivalent. C. The Manual shall include the following information: 1. Description of systems. 2. Description of start-up, operation, and shutdown. 3. Schedule of adjustment, care, and routine maintenance for each item of equipment. 4. Lubrication chart. 5. Wiring and control diagrams with data to explain detailed operation and control of each item of equipment. 6. Valve chart. 7. List of recommended spare parts. 8. Copies of all service contracts. 9. Performance curves for pumps, etc. 10. List of all names, addresses, and phone numbers of all Subcontractors as well as the local representative for each item of equipment. 1.16 GUARANTEE A. The Fire Protection Subcontractor shall guarantee the satisfactory operation of his work in all parts for a period of one (1) year after the date of final acceptance, and shall agree to promptly repair or replace any items of his work which are found to be defective during this period. FIRE PROTECTION 15300- 9 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA considered a part of the Contract requirements. B. The Specifications and Plans are complementary and anything called for, or reasonably implied, in the Plans and not in the Specifications, or vice versa, shall be considered as called for or reasonably implied in both. C. The Fire Protection Subcontractor shall not scale the Drawings. D. Because of the small scale of the Drawings, it is not possible to indicate all offsets, fittings and accessories that may be required. The Fire Protection Subcontractor shall carefully investigate the structural and finish conditions affecting all his work and shall arrange such work accordingly, furnishing such fittings, traps, offsets, valves, and accessories as may be required to meet such conditions, at no additional cost. 1.12 PRODUCT HANDLING A. The Fire Protection Subcontractor shall provide for the delivery of all his materials and fixtures to the building site when required, so as to carry on his work efficiently and to avoid delaying his work and that of other trades. 1.13 ENVIRONMENTAL CONDITIONS A. All necessary tools machinery, scaffolding, and transportation for completion of his Contract shall be provided by the Fire Protection Subcontractor. B. The Fire Protection Subcontractor shall provide his own portable extension lines and obtain 120 volt, 60 cycle, single phase electric energy from the General Contractor to drive his machines and light his work. He shall provide his own light bulbs, plugs, sockets, etc. C. All broken or waste material, rags, packing, etc., resulting from his work shall be removed by the individual Subcontractor. 1.14 WORK CONCEALED A. All piping shall be installed concealed in all areas except storage rooms, closets, and mechanical or electrical equipment rooms, except that in rooms without ceilings, horizontal runs only may be exposed and spaces where existing applied acoustic ceilings are to remain, exposed piping will be allowed. FIRE PROTECTION 15300- 8 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. The Fire Protection Subcontractor shall check the Shop Drawings thoroughly for compliance with the Plans and Specifications before submitting them to the Architect for review, making any and all changes which may be required. D. The review of Shop Drawings by the Architect shall not relieve the Fire Protection Subcontractor from any obligation to perform the work strictly in accordance with the Contract Drawings and Specifications. The responsibility for errors in Shop Drawings shall remain with the individual Subcontractor. E. In the event that materials are being delivered to or installed on the job for which Shop Drawings or samples have not been approved and/or which are not in accordance with the Specifications, the Fire Protection Subcontractor will be required to remove such materials and substitute approved materials at his own expense and as directed by the Architect. F. Submit certificate upon completion of fire protection piping work which indicates that work has been tested in accordance with ANSI/NFPA 13, and also that system is operational, complete, and has no defects. 1.09 PERMITS, FEES AND INSPECTIONS A. The Fire Protection Subcontractor shall secure all permits and pay all fees required for his work. He shall be required to secure all other permits and pay all other fees and charges incidental to the proper carrying out of the Contract. He is to assume all responsibility regarding the observance of the rules and regulations so far as they relate to his part of the work. B. The Fire Protection Subcontractor shall arrange and pay for all required inspections of his work. 1.10 TEMPORARY HOOK -UPS A. The General Contractor will provide any temporary hook -ups required for the use of water or sanitary for construction purposes and testing out apparatus as specified in Division 1. 1.11 PLANS AND SPECIFICATIONS A. The Fire Protection Subcontractor shall refer to the Architectural Drawings of interior details, plans, elevations, and structural layout in preparing his estimate. These documents are intended to supplement the Mechanical and Electrical Plans and Specifications and any applicable work indicated or implied thereon is to be FIRE PROTECTION 15300- 7 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA G. The Fire Protection Subcontractor shall be responsible for the proper protection of his work and materials from injury or loss at the hands of others and shall make good such loss or injury at his own expense. All pipes left open during the progress of the work shall be capped or plugged at all times. All instruments and operating apparatus shall be protected by suitable means. H. The Fire Protection Subcontractor shall be responsible for all equipment and materials installed under this Section until the final acceptance of the project by the Owner. I. The Fire Protection Subcontractor shall check all of the Architectural Plans and Specifications and shall field verify all existing conditions before ordering any materials and the installation of work. Any discrepancies shall be called to the attention of the Architect before proceeding with the work. 1.07 PRODUCTS A. With the exception of items specifically noted otherwise, all materials used shall be U.S. made, new, full weight, and first class in every respect, without defects, and designed to function properly in that portion of the work for which they are intended, and with the same brand of manufacturers for each class of material or equipment. Electrical materials and equipment of types for which there are Underwriters Laboratories standard requirements, listings, or labels shall conform to their requirements and be so labeled. 1.08 SUBMITTALS A. Before ordering materials shipped to the job, the Fire Protection Subcontractor shall submit to the Architect eight (8) sets of catalogue cuts or manufacturers' data sheets, giving all details, dimensions, capacities, etc. of all materials to be furnished. B. Submit hydraulic calculations and scaled layout drawings for fire protection pipe and fittings including, but not necessarily limited to, pipe and tube sizes, locations, elevations and slopes of horizontal runs, wall and floor penetrations, and connections. Show interface and spatial relationship between piping and proximate equipment. 1. Shop Drawings are subject to review and will require approval by Owner's insurer's rating organization and the Northampton Fire Department prior to submitting to the Architect for approval. FIRE PROTECTION 15300- 6 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1.06 INSTALLATION REQUIREMENTS A. The Fire Protection Subcontractor shall employ only competent and experienced workmen at a regular schedule in harmony with the other tradesmen on the job. He shall also exercise care and supervision of his employees in regard to proper and expeditious laying out of his work. B. The Fire Protection Subcontractor shall have a Foreman or Superintendent assigned to the Project who shall be authorized to make decisions and receive instructions exactly as if the Fire Protection Subcontractor himself were present. The Foreman or Superintendent shall not be removed or replaced without the express approval of the Architect after construction work begins. C. The Fire Protection Subcontractor shall be held responsible for any injuries or damage done to the building premises or adjoining property or to other Subcontractors' work resulting from the execution of his part of the work in any manner whatsoever; and in case of dispute arising as to the extent or share of responsibility incurred by the Fire Protection Subcontractor, it is agreed between the Owner and the Fire Protection Subcontractor that such liability and extent of damage shall be finally determined by the Architect whose decision shall be final and binding on both parties to the Contract for the work in question. D. The Fire Protection Subcontractor shall co- operate to the fullest extent with all other trades in order to expedite the progress of the work. He shall furnish all information pertaining to his materials as to sizes, locations, and means of support, to all other trades requiring such information. The Fire Protection Subcontractor shall also furnish all sleeves, frames, beams, supports, inserts, etc., hereinafter specified so that the General Contractor may build them in place. In case of failure on the part of the Fire Protection Subcontractor to give proper information as above, he will be required to bear the extra expense involved due to such failure. E. The arrangement of all piping, ductwork, conduit, wire and cable indicated on the Drawings is diagrammatic only, and indicates the minimum requirements of this work. Conditions at the building shall determine the actual arrangement of runs, bends, offsets, etc. The Fire Protection Subcontractor shall lay out all his work and be responsible for the accuracy thereof. Conditions at the building shall be the determining factor for all measurements. F. All work shall be laid out and installed so as to require the least amount of cutting and patching. Drilling of all holes required for the installation of pipes, conduit, and cable runs shall be performed by the Subcontractor installing such items. FIRE PROTECTION 15300- 5 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1.04 QUALITY ASSURANCE A. Manufacturers: Firms regularly engaged in manufacture of fire protection piping systems products, of types, materials, and sizes required, whose products have been in satisfactory use in similar service for not less than 5 years. B. NFPA Code: Comply with ANSI/NFPA 13, "Installation of Sprinkler System ". C. FM Compliance: Comply with Factory Mutual "Approval Guide ". D. FM Labels: Provide sprinkler products bearing FM approval labels. E. UL Labels: Provide fire sprinkler piping products, which have been approved and labeled by Underwriters Laboratories. F. Local Fire Department/Marshall Regulations: Comply with governing regulations pertaining to fire sprinkler piping. Review proposed written system with said offi- cials prior to commencing work. G. Final installation of system is subject to approval by Owner's insurer's rating organization and local Fire Department. H. Equality of materials or articles other than those named or described in this Section will be determined in accordance with the provisions of the General Requirements, except that substitutions will only be considered for items where the words, "or equal" appear in the product specification. I. The Fire Protection Subcontractor shall agree to accept as final the results of tests secured by a qualified testing laboratory engaged by the Owner. Tests will be conducted in accordance with the General Requirements. 1.05 CODES, ORDINANCES AND INSPECTIONS A. All materials and the installation thereof shall conform to the requirements of the Massachusetts State Building Code, Electrical Code, Fuel Gas and Plumbing Code and local laws, rules, regulations, and codes pertaining thereto. Where provisions of the Contract Documents conflict with any codes, rules or regulations, the latter shall govern. Where the Contract requirements are in excess of applicable codes, rules or regulations, the Contract provisions shall govern unless the Architect rules otherwise. B. The Fire Protection Subcontractor shall comply with the Local Code Enforcement Officials' instructions at no additional cost to the Owner. Review proposed system with said officials prior to commencing work. FIRE PROTECTION 15300- 4 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. Related work, to be performed under other sections of this Specification shall include the following: 1. Wiring of flow switches, tamper switches, electric bell, etc. back to the panel shall be by the Electrical Subcontractor, co- ordinated and as directed by the Fire Protection Subcontractor. 2. Cutting and patching of holes larger than 4" dia. 1.03 SYSTEM DESIGN A. The Fire Protection Subcontractor shall perform a water flow test, and with this information, shall calculate the number and location of heads, pipe sizes, and sprinkler head configuration and orifice sizes. B. Sprinkler head and pipe run locations, as shown on the Drawings, are to be interpreted as diagrammatic only and shall not be used for estimating purposes. The Fire Protection Subcontractor shall produce a design based on actual available water pressure and submit it to the Architect for approval before beginning fabrication and installation. C. Design Criteria: Pipe sizing and sprinkler head layout shown on the Drawings is provided to indicate a suggested pipe routing, zoning, and sprinkler head location, and shall not be used for estimating purposes. Location of piping and heads shall be coordinated with all other trades. Actual pipe sizing, types of heads, and layout shall be based on a hydraulically designed system in accordance with the requirements of, the Northampton Fire Department, and the Insurance Underwriter. Location of sprinkler heads, in relation to the ceilings and walls and spacing of the heads, shall not exceed that permitted by NFPA -13 for light hazard occupancy (ordinary hazard occupancies in Boiler Room, Fan Rooms, and Storage Rooms). The Fire Protection Subcontractor shall prepare working drawings and hydraulic calculations per NFPA- 13 and shall obtain Northampton Fire Department and Insurance Underwriter approval prior to start of work. The Fire Protection Subcontractor shall perform water flow tests or obtain water flow data in writing from local authority. Co- ordinate work of this Section with all trades to avoid interference with ductwork, HVAC and plumbing, piping, electrical work, structure, etc. Final sprinkler head locations shall be subject to Architect's approval. The number of heads and pipe sizes shall be increased or reduced due to hydraulic calculations or the installation of revised heads, provided the revised heads are UL listed and F.M. approved and meet NFPA- 13, the Northampton Fire Department, and Insurance Underwriter's criteria FIRE PROTECTION 15300- 3 Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 1- GENERAL 1.01 RELATED DOCUMENTS A. Include General Conditions, Supplementary General Conditions, applicable parts of Division 1, and conditions of the Contract as part of this Section. B. Examine all other Sections of the Specifications for requirements, which affect work under this Section whether or not such work is specifically mentioned in this Section. C. Co- ordinate work with that of all other trades affecting, or affected by the work of this Section. Co- operate with such trades to assure steady progress of all work under the Contract. 1.02 SCOPE OF WORK A. Furnish all labor, materials, appurtenances and services necessary for, and reasonably incidental to, the complete installation of all fire protection work specified herein and/or indicated on the Drawings, including, but not limited to, the following: 1. This contractor shall furnish and install new 6" fire protection service entrance from the existing main located on the site. 2. Provide and install double check valve backflow preventer assembly per DEP requirements. 3. Wet and dry pipe alarm check valve stations and alarm valve station complete with, but not necessarily limited to, line size valve, retarding chamber, electric and hydraulic alarms, full indicating, control, drain trim, and excess pressure pump and air compressor. 4. Complete wet and dry pipe and automatic sprinkler system. System shall be installed in all spaces, unless otherwise noted, with Fire Department connection and system test and drain connections. 5. Sprinkler heads shall be centered in ceiling tiles. Main, cross main, and branch piping shall be installed above ceiling, where ceilings are called for, and all pendant heads shall be semi - recessed type. 6. Provide complete Engineer Drawings and hydraulic calculations stamped and signed by a registered professional engineer. B. Refer to appropriate site work drawings for trenching and backfill required in conjunction with fire protection piping; not work of this Section. FIRE PROTECTION 15300- 2 Agnimmilmaximmage Section 15300 — Fire Protection Gate House Lot 18 Design Build Hospital Hill Northampton, MA SECTION 15300 - FIRE PROTECTION 1.01 RELATED DOCUMENTS 2 1.02 SCOPE OF WORK 2 1.03 SYSTEM DESIGN 3 1.04 QUALITY ASSURANCE 4 1.05 CODES, ORDINANCES AND INSPECTIONS 4 1.06 INSTALLATION REQUIREMENTS 5 1.07 PRODUCTS 6 1.08 SUBMITTALS 6 1.09 PERMITS, FEES AND INSPECTIONS 7 1.10 TEMPORARY HOOK -UPS 7 1.11 PLANS AND SPECIFICATIONS 7 1.12 PRODUCT HANDLING 8 1.13 ENVIRONMENTAL CONDITIONS 8 1.14 WORK CONCEALED 8 1.15 OPERATING AND MAINTENANCE MANUALS 9 1.16 GUARANTEE 9 1.17 RECORD DRAWINGS 10 1.18 CO- ORDINATION OF TRADES 10 PART 2 - PRODUCTS 10 2.01 FIRE PROTECTION PIPING MATERIALS AND PRODUCTS 10 2.02 BASIC IDENTIFICATION 11 2.03 PIPE, TUBE, AND FITTINGS 12 2.04 SUPPORTS AND ANCHORS 16 2.05 VALVES 18 2.06 FIRE PROTECTION SPECIALTIES 19 PART 3 - EXECUTION 21 3.01 CLEANING AND TESTING 21 3.02 CUTTING AND PATCHING 21 3.03 FIRE SAFING 22 3.06 FINAL CLOSEOUT 23 3.07 SERVICES 23 FIRE PROTECTION 15300- 1 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA END OF SECTION 15400 PLUMBING 15400- 12 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. After twenty -four (24) hours, test for residual chlorine. If more than 5 ppm are present, flush out system until all traces are removed. D. After disinfection, flush treated water from system through its extremities. Continue flushing until samples of water are satisfactory to local authorities having jurisdiction. Repeat flushing if samples taken daily over next three (3) days indicate that quality of water is not being maintained. Do not draw samples from hydrants and undisinfected hose. E. Submit test results to Owner. 2.15 FIRE SAF1NG A. Work Included: Provide labor, materials, and equipment necessary to complete the work including, but not limited to the following: 1. Fire safing at all penetrations through fire barriers. 2. Fire safing at all penetrations through smoke barriers. 3. Extent of fire and smoke barriers as indicated on the Architectural Drawings. 4. Fire safing at all penetrations through floors, shafts, corridor walls, stairway walls, mechanical rooms, electrical rooms, vaults, storage rooms, kitchen, machine rooms, outdoor storage rooms, and receiving rooms. B. Sating Insulation 1. Fire safing insulation shall be Thermafiber as manufactured by USG Interiors, Inc. or Architect - Engineer approved equal, 4" minimum thickness by the required full length and width, or as indicated on the Drawings. 2. Provide incidental galvanized steel clip anchors. C. Seal Compound: At "poke- through" openings, apply "Firecode" seal compound as manufactured by USG Interiors, Inc., or approved equal, over Thermafiber fire safing. D. Preparation 1. At all fire rated assemblies, prepare all penetrations for pipes. E. Application 1. Install approved fire safing insulation of proper size leaving no voids. Compress and friction fit fire safing and use attachment clips where necessary. 2. Seal completely around all openings and over the fire safing insulation with sealing compound. PLUMBING 15400- 11 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. The Plumbing Subcontractor shall file and prepare all applications for backflow preventer approval with the Department of Environmental Protection, and pay all fees and charges. D. All certificates of approval and test results shall be sent to the Architect. 2.13 ELECTRICAL WORK A. The Plumbing Contractor shall provide all wiring for the plumbing equipment. B. The Plumbing Contractor shall hire a licensed electrician to perform all control wiring as required by code. Minimum gauge of all control wiring is 18AWG. All control wiring shall be plenum rated. C. The Electrical Contractor shall install and do all power wiring for all motor starter and un- mounted motors, furnished to him a the job site by other trades. D. For all low voltage motors, temperature control wiring and motor control wiring, including wiring for interlocking, shall be provided by the Section providing motors, including the installation of all control devises. E. Furnish all starters and all motor control devices for motor driven equipment required for the work. The Electrical Contractor shall provide all code required disconnect switches for all motors, except where otherwise noted. The setting of all motors required for mechanical equipment shall be included as part of the mechanical work. F. Equipment which includes a number of correlated electrical control devices mounted in a single enclosure or on a common base with equipment, shall be supplied for installation completely wired as a unit with terminal boxes and ample leads ready for external wiring. G. All electrical items called for as part of the mechanical work shall conform to NEMA Standards, to the requirements of the National Fire Protection Association and to the requirements of any local electrical code authority having jurisdiction. Any field modifications required to ensure such conformance shall be included as part of the mechanical work. 2.14 DISINFECTION A. Flush out entire system. B. Introduce chlorine or solution of calcium hypochlorite or sodium hypochlorite. Fill lines slowly and apply agent at rate which will produce 50 parts per million of chloride as determined by residual chlorine tests at end of lines. Open and close valves and hydrants while system is being chlorinated. PLUMBING 15400- 10 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA equipment shall be chrome plated and connected to the rough piping systems at the wall. Wall escutcheons shall be chromium plated or nickel plated brass with polished, bright surfaces. B. The Plumbing Contractor shall furnish all supports, brackets, bolts, etc. for proper installation of all fixtures requiring support. They shall be in accordance with the manufacturer's recommendations, and, if necessary, shall be built into place as the building progresses. This Contractor shall be held responsible for the stability and proper support of all plumbing fixtures. C. General fixture types shall be as follows: 1. Water Closet — Floor mounted tank type, with high efficiency flush. 2. Lavatory — Counter top vanity mounted lavatory with metering faucet. 3. Mop Sink — 12" high 24" x 24" pre -cast terrazzo basing with wall mounted faucet with pale hood, mop hook, and gauge. 4. Drinking Fountain — Water cooler, bi- level. 5. Break Room Kitchen sink — Stainless steel with goose neck faucet and wrist blade handles. 6. Hose bibbs - Anti - siphon with vacuum breaker protected, chrome finish. 7. Wall Hydrant — Anti - siphon freezeless with vacuum breaker, chrome finish. 8. Handicapped accessible fixtures must meet MA AAB. 2.09 TRAP PRIMER A. Furnish and install automatic trap primer with vacuum breaker and adjustment screw. Provide trap primer distribution unit when serving more than on drain. 2.10 HOT WATER HEATERS A. Electric tank type water heater. 2.11 WATER METER A. The Plumbing Contractor shall furnish and install (1) one turbine water meter with remote meter readouts. 2.12 BACKFLOW PREVENTERS A. Furnish and install the following backflow preventers where required by code. B. All backflow preventers shall be approved by the Massachusetts State Plumbing Examiners and shall be installed in strict accordance with manufacturer's recommendations and instructions, and in accordance with Regulation 310CMR 22.22. PLUMBING 15400- 9 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA 2.06 INSULATION A. All water piping shall be insulated with closed cell pipe insulation with self - sealing lap, 1" thick for hot water, and return hot water 12" thick for cold water and condensate drain. Insulation shall be one piece snap -on type. All exposed piping within 10' -0" of finished floor shall be insulated as noted above and shall be fully jacketed with a PVC cover. B. Fittings shall be insulated with mitered cut insulation applied over fittings with joints taped. Cold water piping shall also have mastic applied to all overlapping surfaces to form a vapor barrier. C. Insulation and fitting jackets shall be installed according to the manufacturer's recommendations. Any gaps or fishmouths shall be remade. D. Install a twelve (12 ") inch length of wood blocking at each hanger; insulation shall run continuous through the hanger. Jacket shall match adjacent insulation jacket. E. All exposed drain and water piping at handicapped lavatories shall be insulated with molded insulation kit to meet MA AAB. 2.07 THERMOMETERS A. Thermometers shall be Jay, Moeller, Palmer, Taylor, Trerice, or Weiss, equal to Trerice 80700 with aluminum case, industrial glass, dial type, 4 -1/2" diameter, 2oF subdivisions. Stem length shall be sufficient to assure accurate and fast response, but in no case less than 3 -1/2" nor less than one -third of pipe diameter in which installed. Each thermometer shall be provided with a brass, monel, or stainless steel separable socket of matching length, and with lagging extensions when installed in insulated pipe. Thermometers shall be adjustable angle type, positioned as required to be easily seen and read from normal operator's position. B. Ranges shall be manufacturer's standard closest to the following: 1. Hot water: 30 degrees F — 180 degrees F. 2. Cold water: 0 degrees F- 100 degrees F. C. Provide at inlet and outlet of water heaters. 2.08 PLUMBING FIXTURES AND FIXTURE TRIMMINGS A. General Requirements: Reference made herein to numbers of plumbing fixtures to establish type and quality of materials. Angle stops, straight stops, stops integral with the faucets, or concealed type of lock shield, loose key pattern stops for supplies shall be furnished and installed with fixtures. Exposed traps and supply pipes for all fixtures and PLUMBING 15400- 8 • fi, Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA E. All vertical piping shall be supported at each story height, with a support at the base of vertical cast iron pipe. F. Perforated strap iron hanger or Milford type copper plated steel hangers are not acceptable. G. Where piping is supported from ceiling beams, support parallel pipes from different beams. H. Support pipes sufficiently clear of all part of structure to allow for full thickness of insulation. I. Hangers to be adequate size to include insulation. Furnish and install galvanized steel insulation protection shields outside of insulation on pipe sizes 2" and larger to prevent crushing or indenting of insulation of hangers. J. Provide plastic coated steel hangers to support vent piping at 6 ft. intervals. 2.04 TRAPS A. Traps at fixtures shall be listed in the Fixture Schedule. Exposed traps shall be chrome plated, B. Traps shall be service weight cast -iron where buried in floors or serving floor drains. Where traps are not connected directly under the drain they serve in the floor, they shall be fitted with top cleanouts and extensions to the floor with access covers and plates. C. Furnish and install traps as required for all items of equipment furnished under other Sections. 2.05 CLEANOUTS /ACCESS PANELS A. Cleanouts shall be adjustable floor cleanout, Dura- Coated cast iron body with gas and watertight bronze tapered thread plug and round scoriated cast iron heavy -duty secured top. Where located in areas of finished floors the appropriate top is to be supplied. B. Wall cleanouts shall be brass, recessed head plugs with access frame and cover. C. Access covers shall be flush with finished floors and walls. Where floor cleanouts occur above finish floors above grade, they shall be provided with flange, clamping collar and 24" x 24 ", 16 oz. copper flashing. Copper flashing shall be furnished and installed by the Plumbing Subcontractor. PLUMBING 15400- 7 } Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA cadmium free, "Silberbrite- 100 ", or equal, complying with the latest issue of ANSI A -5.8 publications. All exposed runs to all toilet fixtures and sinks shall be chrome plated. All below slab trap primer feed piping shall be type "K" soft rolled with silver solder joint. F. All gas piping shall be Schedule 40 black steel pipe with malleable pattern fittings, installed in strict compliance with the Massachusetts Fuel Gas Code, 248 CMR 5.00). All piping 2" and below shall be assembled with screwed malleable iron fittings; 2 '/2" and above shall be welded. Provide necessary ball type gas shut -off valves or square head cocks on piping 2" and smaller and drips as required. Piping 2" and larger shall have plug valves. All high pressure gas piping shall be Schedule 40, all welded with flanged plug valves. All gas valves shall be rated for 125 psi working pressure. 2.02 VALVES A. On water lines inside the building, ball valves shall be provided with stainless steel ball, reinforced teflon seats and seals, bronze body, 400 psi wog, positive 100% shut -off. All valves to be furnished with valve handle extension sized to match pipe insulation thickness. B. Drain valves at all low points shall be Y2" or 3 /4" solder by 3 /4 " hose end with attached cap and chain. C. Pressure Reducing Valves 1. Furnish and install on the water service sized to maintain 50 psi and shall include an pressure gauges, complete with petcocks and brass connections on the inlet and the outlet of the pressure reducing valve. 2.03 HANGERS A. Hangers shall be as manufactured by Grinnell Company, Carpenter & Paterson, or Fee & Mason or equal. B. For cast iron and galvanized steel piping - Grinnell Company's Figure No. 260, one to each length of cast iron pipe, at 12 ft. intervals for threaded piping; for copper tubing - Grinnell Co.'s figure CT -65 at 8 ft. intervals for tubing up to 2 "; 10 ft. intervals for tubing 2 -1/2" and above. C. For hot and cold water piping - Grinnell Company's figure No. CT -99 heavily copper plated at 6 ft. intervals for copper tubing 1 1/4" or less, 10 ft. intervals for piping 1 %2" and larger. Provision shall be made to allow for expansion and contraction of all piping. D. Hangers or supports shall be placed within 1 ft. of each horizontal elbow. Vertical runs of pipe not over 5 ft. in length shall be supported on hangers placed not over 12" from the elbow on the connecting horizontal run. PLUMBING 15400- 6 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA B. Piping containing water shall not be installed concealed in walls having an exterior exposure above grade, unless specifically so shown on the Drawings. When pipes are indicated to be installed in exterior walls, the Plumbing Contractor shall be responsible for ensuring that wall and pipe insulation is properly installed to protect them from freezing. 1.07 GUARANTEE A. The Plumbing Contractor shall guarantee the satisfactory operation of his work in all parts for a period of one (1) year after the date of final acceptance, and shall agree to promptly repair or replace any items of his work which are found to be defective during this period. B. The Plumbing Contractor shall pay for repair of damage to the building caused by defects in his work and for repair to plaster, wood, and other materials or equipment caused by replacement or repairs to the entire satisfaction of the Architect. C. Any part of the work installed under this Contract requiring excessive maintenance shall be considered as being defective. PART 2- PRODUCTS 2.01 PIPING MATERIALS A. All soil, waste and vent piping in accessible areas 2" and larger, shall be cast iron "no hub ", ASA Group 022 pipe and fittings, joined with cast iron clamps as manufactured by "Clamp -All ". All soil, waste, and vent below slab shall be service weight, cast iron pipe with oakum and lead, sealed gas and watertight. In lieu of lead and oakum joint piping, below slab may be service weight with push -on rubber rings. Minimum size below slab shall be 2 ". Where it is impractical to install cast iron pipe, as in tight partition work or where sizes are smaller that 2 ", Type "L" copper tubing shall be used conforming to ASTN Specification with sweat type fittings using lead free solder and non - corrosive flux, "Non- Corrode," or approved equal conforming to ASTM Specification B 32 Alloy 50A. Provide extra heavy cast iron for urinal connections. B. All waste lines 2" and smaller shall be Type "L" copper. All vent lines 2" and smaller shall be type "L" copper, or DWV, except minimum size below ground shall be 2 ". Minimum vent terminal through the roof shall be 4 ". Vent flashing at the roof shall be by Roofing Contractor. C. All hot and cold water piping within the building shall be hard copper Type "L" seamless drawn tubing, assembled with sweat fittings. All solders used shall be lead free, PLUMBING 15400- 5 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA 3. Manufacturer catalogs, samples, and other items needed to fully demonstrate the quality of the proposed materials and equipment. In addition to the submittals formerly mention herein equipment specification sheets and dimensional data on the following: a. All plumbing fixtures and fittings. b. Water heaters. c. Water meters and pressure reducing valve. • d. Floor drains. e. All piping material. f. Pipe insulation B. Record Drawings 1. Include a copy of the record drawings (As- builts) in each copy of the operation and maintenance manual described below. C. Operating Instructions 1. Prior to the completion of all work and the final inspection of the installation by the Owner, three (3) copies of a complete Instruction Manual, bound in booklet form and suitably indexed, shall be submitted to the Architect for review and approval. All written material contained in the manual shall be typewritten or printed. 1.04 PERMITS, FEES AND INSPECTIONS A. The Plumbing Contractor shall secure all permits and pay all fees required for his work. He shall be required to secure all other permits and pay all other fees and charges incidental to the proper carrying out of the Contract. He is to assume all responsibility regarding the observance of the rules and regulations so far as they relate to his part of the work. B. The Plumbing Contractor shall arrange and pay for all required inspections of his work. 1.05 TEMPORARY HOOK -UPS A. The General Contractor will provide any temporary hook -ups required for the use of water or sanitary for construction purposes and testing out apparatus. 1.06 WORK CONCEALED A. All piping, hangers and supports shall be installed concealed in all areas except storage rooms and mechanical or electrical equipment rooms. PLUMBING 15400- 4 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1. New sanitary waste and vent systems as required by code. All floor drains to be fitted with trap primers as required by code. All sanitary piping shall be pitched as per code. 2. All water piping shall be designed for a maximum velocity of 10 fps and shall be fitted with isolation valves at all pieces of equipment and at all fixture groups. 3. Gas piping system including gas pressure regulators, isolation valves, and unions at all pieces of equipment. 4. Hot water system capable of providing 110 °F water to all lavatories and 120 °F water to all service sinks. Water heater to be electric tank type. 5. All materials and the installation thereof shall conform to the requirements of the Massachusetts State Building Code, Electrical Code, Fuel Gas and Plumbing Code and local laws, rules, regulations, and codes pertaining thereto. Where provisions of the Contract Documents conflict with any codes, rules or regula- tions, the latter shall govern. Where the Contract requirements are in excess of applicable codes, rules or regulations, the Contract provisions shall govern unless the Architect rules otherwise. 6. The Plumbing Contractor shall comply with the Local Code Enforcement Officials' instructions at no additional cost to the Owner. 7. Related work specified under other divisions: a. Division 16000 — Power Circuiting b. Division 15600 — HVAC 8. This contractor is responsible for sleeving all holes required of his work prior to pouring of the concrete slabs. All holes less than or equal to 4" shall be the responsibility of this contractor to core. Sizes larger shall be cored by the G.C. However, if coring is required due to failure of this contractor to set a sleeve prior to pouring, than this contractor shall be responsible for bearing the cost of any of this additional work required by the G.C. 1.03 SUBMITTALS A. Before ordering materials shipped to the job, the Plumbing Contractor shall submit to the Architect six (6) sets of catalogue cuts, manufacturers' data sheets, or Shop Drawings, giving all details, dimensions, capacities, etc. of all materials to be furnished. 1. It is expected that the contractor shall provide the Architectural design team, with a set of contract drawings stamped by a Professional Engineer registered within the Commonwealth of Massachusetts for permit and construction. For estimating purposes, the contractor shall use the guidelines described herein for sizing and selecting the system components. 2. This contractor shall review the drawings of all other trades and where conflict exists, shall prepare coordinated shop drawings, showing proposed conflict and proposed resolution layout of equipment, piping, ducts, registers, grilles, controls, and other components of the system. Ductwork ship drawings shall be done a 'A: = 1'0 ". Submit cut sheets on ductwork, connections, fittings, air terminals, fire dampers, etc. PLUMBING 15400- 3 Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Include General Conditions, Supplementary General Conditions, and applicable parts of Division 1, as part of this Section. B. Examine all other Sections of the Specifications for requirements, which affect work under this Section whether or not such work is specifically mentioned in this Section. C. Co- ordinate work with that of all other trades affecting, or affected by the work of this Section. Co- operate with such trades to assure steady progress of all work under the Contract. 1.02 SCOPE OF WORK A. Furnish all labor, materials, plant, equipment and services necessary for and reasonably incidental to the complete installation of all plumbing work. Provide complete design build services for the plumbing systems including a complete set of plumbing drawings stamped and signed by a registered professional, including, but not limited to, the following: 1. New sanitary, waste, and vent systems piping inside the building and to 10' -0" outside of the foundation wall. Furnish piping, traps, flanges, seals, cleanouts, fixtures, drains, supports, and roof terminals. 2. New grease waste piping, capped inside the building and to 10' -0" outside building for future Kitchen waste to future exterior grease trap. 3. New hot and cold water distribution and hot water heaters and storage tanks. Furnish piping, fittings, insulation, supports, valves, backflow preventers and pumps. 4. Provide and install water meter and pressure reducing station at domestic water service entrance. 5. Provide back water preventers (point -of -use types) where required by code. 6. Plumbing fixtures and supports. 7. Provide new gas piping system. 8. Arrange for inspections and perform cleaning and testing. 9. All final connections to all items of equipment furnished by others requiring water, drain, and waste connections. 10. Furnish access panels. 11. Guarantee and instructions. B. The work shall include, but is not limited to, the following major items of work in addition to that noted in 1.02A above: PLUMBING 15400- 2 • Section 15400 — Plumbing Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 1 - GENERAL 2 1.01 RELATED DOCUMENTS 2 1.02 SCOPE OF WORK 2 1.03 SUBMITTALS 3 1.04 PERMITS, FEES AND INSPECTIONS 4 1.05 TEMPORARY HOOK -UPS 4 1.06 WORK CONCEALED 4 1.07 GUARANTEE 5 PART 2 - PRODUCTS 5 2.01 PIPING MATERIALS 5 2.02 VALVES 6 2.03 HANGERS 6 2.04 TRAPS 7 2.05 CLEANOUTS /ACCESS PANELS 7 2.06 INSULATION 8 2.07 THERMOMETERS 8 2.08 PLUMBING FIXTURES AND FIXTURE TRIMMINGS 8 2.09 TRAP PRIMER 9 2.10 HOT WATER HEATERS 9 2.11 WATER METER 9 2.12 BACKFLOW PREVENTERS 9 2.13 ELECTRICAL WORK 10 2.14 DISINFECTION 10 2.15 FIRE SAFING 11 PLUMBING 15400- 1 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA E. Application 1. Install approved fire safmg insulation of proper size leaving no voids. Compress and friction fit fire safing and use attachment clips where necessary. 2. Seal completely around all openings and over the fire safing insulation with sealing compound. END OF SECTION ELECTRICAL 16100- 19 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA locations. Secure nameplate to outside surface of door on surface mounted panelboards located in electrical rooms and mechanical spaces. D. Provide embossed adhesive tape labels with 3/16 inch white letters on black background for identification of individual control device stations. Labels shall be installed with for permanent adhesion and sealed with clear lacquer. E. Provide cloth tape, split sleeve, or tubing type_wire marker for each conductor at panelboard gutters, pull boxes, junction boxes, and each load connection. The wire markers shall contain the following information: 1. Provide branch circuit or feeder number for power and lighting circuits. 2. Provide control wire number as indicated on schematic and interconnection diagrams. F. Provide conduit marker for each conduit having a total length exceeding 20 feet. The markers shall be spaced 20 feet on center. Color of markers shall be as follows: 1. Blue marker for Low Voltage Signal and Data Systems. 2. Yellow marker for 208 Volt Systems. 3.10 FIRE SAFING A. Work Included: Provide labor, materials, and equipment necessary to complete the work including, but not limited to the following: 1. Fire safing at all penetrations through fire barriers. 2. Fire safing at all penetrations through smoke barriers. 3. Extent of fire and smoke barriers as indicated on the Architectural Drawings. 4. Fire safing at all penetrations through floors, shafts, corridor walls, stairway walls, mechanical rooms, electrical rooms, vaults, storage rooms, kitchen, machine rooms, outdoor storage rooms, and receiving rooms. B. Safing Insulation 1. Fire safing insulation shall be Thermafiber as manufactured by USG Interiors, Inc. or Architect- Engineer approved equal, 4" minimum thickness by the required full length and width, or as indicated on the Drawings. 2. Provide incidental galvanized steel clip anchors. C. Seal Compound: At "poke- through" openings, apply "Firecode" seal compound as manufactured by USG Interiors, Inc., or approved equal, over Thermafiber fire safing. D. Preparation 1. At all fire rated assemblies, prepare all penetrations for pipes. ELECTRICAL 16100- 18 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA check with the Architectural and Structural Plans for interferences. B. Junction and outlet boxes, where exposed to the weather and wet locations, shall be of the threaded hub type and provided with watertight screw -on cover and gasket. C. Pull boxes shall be adequate size to accommodate the conductors installed therein without excessive bending of the conductors, which would damage the conductor insulation. D. All outlet boxes installed in masonry shall be so set that their outer edges are 1/4" back of finished surface. E. Outlet boxes shall not be supported by the conduit. Suitable means shall be provided to support the outlet box to take the weight of the fixture. F. Fixture outlet boxes used as junction boxes or outlets not used, shall be provided with covers. 3.07 EQUIPMENT INSTALLATION A. All equipment furnished under this Section shall be installed in accordance with its manufacturer's printed installation instructions, whether so shown on the Drawings or not, and all labor and materials required to accomplish this shall be furnished by the Electrical Contractor and be included in his bid. 3.08 TESTING A. Balancing Loads: 1. Circuits shall be connected to the panelboards so that the total load is distributed equally between each line and neutral to within ten percent. Branch circuits shall be balanced on their own panelboards, and feeder loads balanced on the main distribution panel. Reasonable load testing shall be arranged for verification if requested by the Owner and Architect. 3.09 NAMEPLATE AND LABEL INSTALLATION A. Installation of nameplates and labels identifying devices shall be provided after completion of painting. B. Nameplates and labels shall be installed parallel to equipment lines. C. Nameplates shall be provided for each electrical distribution and control equipment enclosure with corrosive - resistant mechanical fasteners, or adhesive unless otherwise noted. Nameplates for each control panel and for major control components shall be located outside panel with corrosive- resistant mechanical fasteners, or adhesive. 1. Secure nameplate to inside surface of door on recessed panelboard in finished ELECTRICAL 16100- 17 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. Ends of all conduits shall be reamed and all joints made waterproof. Connections to junction boxes shall be double locknut and bushing, using insulated bushings on conduit 1 -1/4" or larger. Grounding bushings shall be provided at all panel connections. D. Conduit connections to motor frames shall have minimum of 18" of flexible steel conduit to eliminate vibrations and noise being transferred to other parts of the building, with cable jumper across greenfield and fittings. This flexible conduit shall also be installed at ceiling mounted lighting fixtures to facilitate alignment of fixtures. 3.05 LUMINAIRES A. Installation of all luminaires shall be done by experienced mechanics. Luminaires shall not be installed where finished coat of paint has been applied to ceiling and walls until paint is thoroughly dry. B. Luminaires in equipment rooms shall not be installed until after all piping and ductwork is in place. Luminaire layout shown on the Drawings is typical layout, but may be modified to provide adequate lighting of the equipment space according to final construction conditions. Any relocation of luminaires due to duct or piping interference shall be as directed by the Architect, at no expense to the Owner. C. The Electrical Contractor shall be responsible for proper coordination of all luminaire locations. Provide support for all luminaires mounted on or recessed in hung ceiling. He shall confer with Ceiling Contractor and Heating and Ventilating Contractor to co- ordinate lighting system with other trades. D. Provide and install suitable cover plate or canopy for each luminaire outlet box where the fixture does not provide a suitable cover. E. Luminaires located on exterior of building shall be installed with cadmium- plated brass screws and gasketed. F. All pendant type luminaires in the same room shall be installed at a uniform height from the floor and shall hang plumb unless otherwise specified. G. Upon completion of the installation of the luminaires and lighting equipment, they must be in first -class operating order and in perfect condition as to finish, etc. Check for proper operation and appearance, alignment of luminaire and proper placement of lenses, louvers, lamps and other light controlling or modifying appurtenances. 3.06 OUTLET AND JUNCTION BOXES A. Receptacle boxes, unless otherwise noted, shall be approximately 18" above finished floor, aligned above or below closest block course, except at locations where wall mounted equipment precludes this mounting height. At such locations, receptacle height shall be as directed by the Architect. Switch outlets shall be 48" above finished floor, unless aligned above or below closest block course. The Electrical Contractor shall ELECTRICAL 16100- 16 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA built, or be responsible for the cost of cutting and patching required for pipes where sleeves and inserts were not installed, or where incorrectly located. The Electrical Contractor shall do all drilling required for the installation of his hangers. Patching of all holes, after installation of piping or equipment shall be performed by the General Contractor. 3.03 GROUNDING A. Except where specifically indicated otherwise, all exposed non - current carrying metallic service equipment, distribution panels, lighting panelboards, switch and starter enclosures, motor frames, grounding type receptacles, and other exposed non - current carrying metal parts of electrical equipment, metallic raceway systems, grounding conductor in non - metallic raceways and grounded (neutral) conductor of the wiring system shall be grounded per the Massachusetts Electrical Code and other applicable specification standards. The ground connection shall be made at the main service equipment. B. The Electrical Contractor shall furnish and install all material required for the grounding and/or bonding in the building of all equipment, power and lighting systems installed under this Contract. C. The Electrical Contractor shall make tight and proper all metallic components and equipment to one another and to ground, using a positive foolproof system of connections. Provide and install bonding and grounding conductors with approved termination where required, conforming with the Massachusetts Electrical Code and other applicable specification standards. D. A minimum #12 AWG insulated equipment ground conductor shall be installed in each length of flexible metallic conduit connection to motors, recessed lighting fixtures and other equipment components for continuity. The equipment ground conductor shall be sized for the largest circuit contained in the conduit or enclosure. Positive ground connections with the ground wire shall be made at each outlet box, lighting fixture, motor and other equipment components by means of positively secured ground clamp in each. E. Provide bonding jumper across domestic water check meter.. F. Remove paint, mill oils, and any other surface contaminants at connection points. I. Permanently attach equipment and grounding conductors prior to energizing equipment. 3.04 CONDUIT AND FITTINGS A. All conduit shall be installed so as to provide the straightest possible run with not more than the equivalent of three 90° bends in a single run. Where more bends are necessary, the Electrical Contractor shall provide suitable pull boxes. B. Conduit shall be fished and cleaned and dry before pulling wires and shall be suitably protected against entrance of dirt and moisture during construction. ELECTRICAL 16100- 15 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA in a first floor utility room to serve as the utility company demarcation point. B. Provide 4" conduit with pull string from utility handhole to the demarcation point for telephone and a second 4" conduit with pull string from the utility handhole to the demarcation point for CATV. Coordinate final utility connections with appropriate utility company. C. From the demarcation point plywood back board, provide three 4" conduits to the attic space with bushed end fittings at both ends for telephone and CATV distribution. PART 3 - INSTALLATION 3.01 GENERAL INSTALLATION REQUIREMENTS A. The Electrical Contractor shall endeavor to layout and perform his work in such a manner as to cause no delay in the construction by other trades. B. The Electrical Contractor shall verify all measurements and shall be responsible for the correctness of same. No allowance will be made for differences between actual measurements and those shown on plans. C. If, in laying out his work, the Electrical Contractor finds that the work of other trades might interfere with his, the Architect shall be notified. D. The locations of outlets, apparatus, and equipment are approximate only and the runs of feeders, mains, and branches are not necessarily to be made exactly as shown on the plans. The exact locations of such work shall be determined after full consideration has been given to work of other trades and without changes in the design of the systems. The entire installation shall conform to the latest issue of the Massachusetts Electrical Code and local inspection authorities. E. Electrical equipment, such as junction and pull boxes, control, and apparatus, shall be made accessible. F. All wiring shall be concealed in finished spaces, except as otherwise specified. 3.02 CUTTING, PATCHING, AND DRILLING A. Drilling of all holes 4" diameter and smaller required for the installation of electrical conduit and equipment shall be performed by the Electrical Contractor. Cutting and patching shall be performed by the General Contractor in accordance with the General Conditions. All work and materials shall be installed in such a manner and at such time to keep cutting and patching to a minimum. Location for chases, openings, etc. shall be checked by the Electrical Contractor, and error due to failure to co- ordinate work with other Divisions shall be the responsibility of the Electrical Contractor, who shall make the corrections as his own expense. B. Work shall include furnishing and locating inserts required before the floors and walls are ELECTRICAL 16100 - Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA used in sequence down the left-hand side and even numbers shall be used in sequence down the right -hand side. F. A circuit directory frame and card with a clear plastic covering shall be provided on the inside of the door. The directory card shall provide a space at least 1/4" high by 3" long or equivalent for each circuit. The directory shall be typed to identify the room and load fed by each circuit. G. Each panelboard, as a complete unit, shall have a short circuit current rating equal to or greater than the rating shown on the panelboard schedule on the plans. Panelboards shall have a minimum of 22,000 amp AIC full rating. Series rating shall not be acceptable. H. Panelboard trim shall be door -in -door. I. Panelboards shall be listed by Underwriters' Laboratories and bear the UL label. Panelboards shall be Square D, Type NQOD or equivalent equipment by Cutler - Hammer, General Electric, or Siemens. 2.10 ELECTRICAL SERVICE A. Furnish and install a transformer pad for a utility pad - mounted transformer where indicated on the site plan. Provide provisions for utility company primary feeders from utility company site entry to transformer pad. B. Furnish and install an incoming underground secondary service rated for 800 amps — 208Y/120, 3 phase, 4 wire from the transformer to the service entrance main disconnect. C. Furnish and install an 800 amp enclosed service entrance rated circuit breaker to serve as the building main service disconnect. The load side of the main service disconnect shall serve two combination 400 amp tenant circuit breaker and meter socket for 320 amp line voltage utility meter for future restaurant and Owner loads. The load side of the main service disconnect shall also serve a meter bank with six 200 amp, three pole breakers and meter sockets for 200 amp rated line voltage utility company meters. 2.11 FIRE ALARM SYSTEM A. Furnish and install an addressable fire alarm system, complete with fire alarm control panel, remote fire alarm annunciator panel, audio and visual devices, smoke detection devices, addressable modules for monitoring flow and tamper switches, and manual pull stations. . B. Contractor shall be responsible for coordinating of zoning, location of panels , knox box, exterior strobe light and radio master box for transmission to the Northampton Fire Department. Coordinate locations and transmission equipment with the fire department. 2.12 TELECOMMUNICATIONS SYSTEM A. Furnish and install a 4'x8'x3/4" plywood backboard painted with fire retardant gray paint ELECTRICAL 16100- 13 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA 4. Starters for two speed motors shall be for single winding or two winding as required for the service. E. Equivalent equipment by Cutler - Hammer, General Electric, or Westinghouse will be considered. 2.08 LUMINAIRES A. Furnish and install luminaires on all light outlets shown on plans. All luminaires shall have label of Underwriters Laboratories, Inc. Luminaires shall be complete in all respects with all required glassware and lamps. All lamps shall be new. Furnish and install all required hardware to fit in all type ceilings. Luminaires are to be cleaned after lamps and diffusers are installed. Any chipped, cracked or otherwise defective material shall be replaced. B. Fluorescent ballasts shall be solid state low harmonic electronic type, approvable for use on their system by the local electrical utility company. Fixture /lamp combinations for which electronic ballasts are not available shall be high power factor, energy efficient magnetic type, complete with automatic reset thermal protector, and shall be CBM certified. C. All luminaires shall be installed complete with lamps of the stated type and size; T8 lamps shall be 3500 K. D. All luminaires shall be independently supported from building structure. 2.09 LIGHTING AND POWER PANELBOARDS A. Furnish and install circuit breaker lighting panelboards as required for proper load distribution. Panelboards shall be equipped with thermal- magnetic molded case circuit breakers with frame and trip ratings as required. B. Circuit breakers shall be quick -make, quick - break, thermal- magnetic, trip indicating, and have common trip on all multi -pole breakers. Red trip indication shall be clearly shown by the breaker handle taking position between "ON" and "OFF" when the breaker is tripped. Connections to the bus shall be bolt -on. Furnish circuit breakers UL listed as Type HACR for air conditioning equipment branch circuits C. Bus bar connections to the branch circuit breaker shall be the "distributed phase" or "phase sequence" type. All current - carrying parts of the bus assembly shall be plated. All bus bars shall be copper. Main ratings shall be as shown on the panelboard schedule. D. Terminals for feeder conductors to the panelboard mains and neutral shall be UL listed as suitable for the type of conductor specified. Terminals for branch circuit wiring, both breaker and neutral, shall be UL listed as suitable for the type of conductor specified. E. Panelboard circuit numbering shall be such that starting at the top, odd numbers shall be ELECTRICAL 16100- 12 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA The handle and mechanism shall be an integral part of the box, not the cover, with positive pad - locking provisions in the "OFF" position. 3. Switches shall be furnished in NEMA 1 general purpose enclosures except for switches exposed to weather and in wet location which shall be NEMA 3R or specified on the plans. Enclosures shall have gray enamel, electro- deposited on cleaned phosphatized steel, except as specified in Paragraph 6. 4. Switches shall be horsepower rated for 240 or 600 volts AC, as shown. 5. Fuses shall match source breaker rating unless otherwise indicated on the Drawings. 6. Switches shall be Square D Heavy Duty type in NEMA 1 or NEMA 3R enclosures, or equal. All switches in Kitchen shall have NEMA 4X (stainless steel) enclosures. C. Disconnect switches for 120 volt, single phase motors shall be single or double pole toggle switches as specified. D. Motor starters shall be across - the -line magnetic type rated in accordance with NEMA Standards, sizes and horsepower ratings. Starters shall be mounted in general purpose enclosures unless otherwise indicated on the plans. Starters located in Kitchen shall have NEMA 4X (stainless steel) enclosures. 1. Across -the -line magnetic starters shall be equipped with double break silver alloy contacts. All contacts shall be replaceable without removing power wiring or removing starter from panel. 2. Coils shall be of molded construction, replaceable from the front without removing the starter from the panel. 3. Overload relays shall be the melting alloy type with a replaceable control circuit module. Thermal units shall be of one -piece construction and interchangeable. The starter shall be inoperative if the thermal unit is removed. a. All three phase magnetic starters shall have "Hand- Off - Auto" selector switch, Square D, Class 8536, Form C, three -pole, three -phase of NEMA size applicable, with three melting alloy overload relays and three- position H -O A switch in cover of general purpose enclosure. b. All single phase magnetic starters shall be single pole magnetic contactor without overload protection, with "Hand- Off -Auto" selector switch in cover of general purpose enclosure, Square D, Class 8502. c. A control transformer shall be furnished and installed in each starter, fused, with 24 volt secondary. Starter coils shall be 24 volt. d. Furnish a minimum of one auxiliary normally open and normally closed contact in each starter for use by others for interlocking purposes. ELECTRICAL 16100 -11 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA 5. Where multiple devices are located at one point, gang type boxes shall be used. 6. Pull and junction boxes, whether surface or flush, shall be galvanized code gauge. 7. Pull boxes and wireways shall be standard NEMA -1 enclosures with cover plates and screws, bonderized paint finished. 8. Pull and splice boxes not indicated on the Drawings shall be provided as required by the Massachusetts Electrical Code. 9. Outlet boxes and covers shall be as manufactured by Steel City Electrical Company, General Electric Company, Raco, or approved equal. 2.05 NAMEPLATES A. Furnish and install nameplates identifying all apparatus, controls, panels and safety switches. The nameplates shall be Seton style 2060 engraved plastic, or equal, screw attached. Submit schedule of nameplate lettering for approval. 2.06 WIRING DEVICES A. The Electrical Contractor shall install devices where shown on the plans. Where two or more devices occur at one location, they shall be provided with a gang plate. All unused boxes shall be furnished with blank plates. B. Duplex Receptacles shall be Specification Grade, 20 amp, 125 volt with grounding screw, side and back wired, Leviton Cat. No. 5362I, or equal. C. Ground fault interrupting receptacles shall be Leviton Cat. No. 7899 -HGI Hospital Grade, or equal. D. Weatherproof cover for receptacles shall be lockable, vertical, UL Listed, with Lexan base and lid, 4 screw attachment, Tay Mac Cat. No. 20350, or equal. E. Light Switches, Single Pole - 20 amp, 120/277 volt, back and side wired, Leviton Cat. No. 12212, or equal. F. Wall plates shall be smooth nylon with ivory finish with matching screws. 2.07 MOTOR STARTERS AND SWITCHES A. Furnish and install motor starting, protecting, and controlling devices for motors. B. Furnish and install heavy duty fused safety switches as follows: 1. All switches shall have switch blades which are fully visible in the OFF position with the door open. All current - carrying parts shall be plated to resist corrosion and promote cool operation. 2. Switches shall be quick -make and quick -break such that, during normal operation of the switch, the operation of the contacts shall not be capable of being restrained by the operating handle after the closing or opening action of the contacts has started. ELECTRICAL 16100- 10 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA 2.02 WIREWAYS A. Wireways shall be made to accommodate conductors as required in accordance with applicable rules of the Massachusetts Electrical Code and shall be of code gauge steel and supported as required by Code. Wireways shall be furnished and installed complete with the necessary complement of fittings, connectors, and accessory parts. Wireways shall be of the "lay -in" type with standard knockouts and with screw covers for full channel access. All sheet metal parts shall be coated with a rust inhibitor and finished in grey baked enamel. All hardware shall be plated to prevent corrosion. 2.03 CONDUCTORS A. Conductors shall be 98% conductivity copper, with 600 volt insulation, and shall be of types indicated below unless otherwise shown on the plans. Aluminum conductors shall not be used. B. Conductors #10 AWG and smaller, Type THHN, solid. C. Conductors #4 AWG through #8 AWG, Type THHN, stranded. D. Conductors #3 AWG and larger, Type XHHW, stranded. E. Wire and cable for special systems shall be as specified in those specification sections. F. Metal sheathed Type MC cable shall be steel sheathed interlocking armor equal to AFC "MC Tuff'. Type MC cable shall be permitted in hollow stud wall construction and above hung ceilings after first device in circuit or junction box above the hung ceiling directly above the first device. Wiring from first device or junction box above the hung ceiling directly above the first device to the source panel shall be in conduit. G. Wire and Cable to be by Cerro, Southwire, Triangle/PWC, or equal. 2.04 OUTLET AND JUNCTION BOXES A. Outlet boxes and covers shall be galvanized or sheradized pressed steel unless otherwise noted or required by the Massachusetts Electrical Code, and shall be as required for their use. B. Junction and outlet boxes, where exposed to weather and wet locations shall be of the cast aluminum, threaded hub type and provided with watertight screw -on cover and gasket. C. Outlet boxes shall be of sizes and types to accommodate: 1. Structural conditions. 2. Size and number of raceways and conductors or cables entering. 3. Device of fixture for which required. 4. Boxes occurring at plastered surfaces shall have a suitable plaster ring installed. ELECTRICAL 16100- 9 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA with other divisions shall be the responsibility of the Electrical Contractor failing to coordinate, who shall make the corrections at his own expense. B. Work shall include furnishing and locating sleeves or inserts required before the new walls are built, or be responsible for the cost of cutting and patching required for conduit and equipment where sleeves were not installed or where incorrectly located. The Electrical Contractor shall do all drilling required for the installation of hangers. C. Patching of all holes, after installation of piping or equipment, shall be performed by the General Contractor or appropriate tradesmen. D. All pipe cutting or threading shall be done in a location approved by the Owner. E. No pipe cutting or threading shall be done in areas where completed concrete floor slab is to remain in finishes or be painted later. Should this area be necessary, the Electrical Contractor shall cover the entire working area with canvas tarpaulins in an approved manner. 1.19 RECORD DRAWINGS A. Submit Record Drawings as specified in Division 1. PART 2 - MATERIALS 2.01 RACEWAYS A. Rigid galvanized steel or intermediate steel conduit shall be used for all raceway runs concealed in concrete, run under slabs, run in trenches or pits, exterior exposed above grade, in spaces subject to moisture, and for conduit sweeps below grade or under concrete slab on grade. Conduit shall comply with ANSI C80.1 and the latest applicable Federal Specifications. Fittings and Conduit Bodies shall be steel and comply with NEMA FB 1. B. Electrical metallic tubing may be used for all raceways run in walls or partitions, run exposed inside the building, or run concealed in or above furred spaces unless otherwise specified above. Electrical metallic tubing shall comply with the latest applicable requirements of the National Electrical Manufacturers Association, ANSI C80.3, and applicable Federal Specifications. Couplings, connectors, and fittings for electrical metallic tubing shall be of steel construction, set screw type. Die cast fittings shall not be permitted. C. Flexible Steel Conduit shall be used for final connections to motors, light fixtures and other removable equipment to facilitate removal and connections. Length of flexible steel conduit shall not exceed six feet for light fixture connections. For other equipment connections, length of flexible steel conduit shall not exceed 18 inches. D. Schedule 40 PVC raceway shall be used for all raceways below grade and under slab on grade with solvent welded fittings. Sweeps shall be rigid galvanized steel. ELECTRICAL 16100- 8 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA equipment installed. Supply qualified personnel to operate equipment for sufficient length of time to assure that Owner's representative is properly qualified to take over operation and maintenance procedures. B. Furnish the Architect, for his approval, three (3) copies of an Operation and Maintenance Manual. Inscribe the following identification on the cover: the words, "Operation and Maintenance Manual ", the name and location of the equipment or the building, the name of the Contractor, and the Contract number. The manual shall have a Table of Contents with tab sheets placed before each Section. The instructions shall be legible and easily read, with large sheets of Drawings folded in. The manuals shall be bound in hard binders or an approved equivalent. C. The manual shall include the following information: 1. Description of systems. 2. Description of start up, operation, and shutdown procedures for each item of equipment. 3. Schedule of adjustment, care, and routine maintenance for each item of equipment. 4. Wiring and control diagrams with data to explain detailed operation and control of each item of equipment. 5. Panel schedules. 6. List of recommended spare parts. 7. Copies of all service contracts. 8. List of all names, addresses, and phone numbers of all Contractors as well as the local representative for each item of equipment. 1.17 GUARANTEE A. The Electrical Contractor shall guarantee the satisfactory operation of his work in all parts for a period of one (1) year after date of final acceptance, and shall agree to promptly repair or replace any items of his work which are found to be defective during this period. B. The Electrical Contractor shall pay for repair of damage to the building caused by defects in his work and for repair to plaster, wood, and other materials or equipment caused by replacement or repairs to the entire satisfaction of the Architect. C. Any part of the work installed under this Contract requiring excessive maintenance shall be considered as being defective. 1.18 CUTTING AND PATCHING A. Cutting and/or drilling of all openings and holes required for the installation of electrical apparatus in the building, shall be performed by the General Contractor. All work and materials shall be installed in such a manner and at such time to keep cutting and patching to a minimum. Cutting and/or drilling of structural supports (ie. beams or joists) is not allowed without written approval by the Architect. Location for openings, etc. shall be checked by the Electrical Contractor, and error due to failure to coordinate work ELECTRICAL 16100- 7 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA plans, elevations, and structural layout in preparing his estimate. These documents are intended to supplement the Mechanical and Electrical Plans and Specifications and any applicable work indicated or implied thereon is to be considered a part of the Contract requirements. B. The Specifications are complementary and anything called for, or reasonably implied, in the Plans and not in the Specifications, or vice versa, shall be considered as called for or reasonably implied in both. C. The Electrical Contractor shall not scale the Drawings. D. Because of the small scale of the Drawings, it is not possible to indicate all offsets, fittings and accessories that may be required. The Electrical Contractor shall carefully investigate the structural and finish conditions affecting all his work and shall arrange such work accordingly, furnishing such accessories as may be required to meet such conditions, at no additional cost. 1.13 PRODUCT HANDLING A. The Electrical Contractor shall provide for the delivery of all his materials and fixtures to the building site when required, so as to carry on his work efficiently and to avoid delaying his work and that of other trades. 1.14 ENVIRONMENTAL CONDITIONS A. All necessary tools machinery, scaffolding, and transportation for completion of his Contract shall be provided by the individual Contractor. B. The Electrical Contractor shall provide his own portable extension lines and obtain 120 volt, 60 cycle, single phase electric energy from the General Contractor to drive his machines and light his work. He shall provide his own light bulbs, plugs, sockets, etc. C. All broken or waste material, rags, packing, etc., resulting from his work shall be removed by the individual Contractor. 1.15 WORK CONCEALED A. All piping, duct work, cable, and raceway shall be installed concealed where possible, the majority of all conduit and equipment will be installed exposed and shall be run in a neat and professional manor. B. Exposed runs shall be run straight and level, parallel or perpendicular to the lines of the building. 1.16 OPERATING INSTRUCTIONS A. After all final tests and adjustments have been completed, fully instruct the proper Owner's representative in all details of operation, adjustment and maintenance for ELECTRICAL 16100- 6 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA B. It is expected that the contractor shall provide the Architectural design team with a set of contract drawings stamped by a Professional Engineer registered within the Commonwealth of Massachusetts for permit and construction. For estimating purposes, the contractor shall use the guidelines described herein for sizing and selecting the system components. C. The Electrical Contractor shall check the Shop Drawings thoroughly for compliance with the Plans and Specifications before submitting them to the Architect for review, making any and all changes which may be required. D. The review of Shop Drawings by the Architect shall not relieve the Electrical Contractor from any obligation to perform the work strictly in accordance with the Contract Drawings and Specifications. The responsibility for errors in Shop Drawings shall remain with the Contractor. E. In the event that materials are being delivered to or installed on the job for which Shop Drawings or samples have not been approved and/or which are not in accordance with the Specifications, the Electrical Contractor will be required to remove such materials and substitute approved materials at his own expense and as directed by the Architect. 1.09 PERMITS, FEES, AND INSPECTIONS A. The Electrical Contractor shall secure all permits and pay all fees required for his work. He shall be required to secure all other permits and pay all other fees and charges incidental to the proper carrying out of the Contract. He is to assume all responsibility regarding the observance of the rules and regulations so far as they relate to his part of the work. B. The Electrical Contractor shall arrange and pay for all required inspections of his work. C. The Electrical Contractor shall coordinate with the utility company for any and all rebates available for this project. 1.10 TEMPORARY HOOK -UPS A. The General Contractor will provide any temporary hook -ups required for the use of water or sanitary for construction purposes and testing out apparatus as specified in Division 1. 1.11 TEMPORARY LIGHT AND POWER A. The General Contractor will furnish and install temporary light and power as specified in Division 1. 1.12 PLANS AND SPECIFICATIONS A. The Electrical Contractor shall refer to the Architectural Drawings of interior details, ELECTRICAL 16100- 5 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA F. All work shall be laid out and installed so as to require the least amount of cutting and patching. Drilling of all holes required for the installation of pipes, conduit, and cable runs shall be performed by the Electrical Contractor installing such items. G. The Electrical Contractor shall be responsible for the proper protection of his work and materials from injury or loss at the hands of others and shall make good such loss or injury at his own expense. All pipes left open during the progress of the work shall be capped or plugged at all times. All instruments and operating apparatus shall be protected by suitable means. H. The Electrical Contractor shall be responsible for all equipment and materials installed under this Section until the final acceptance of the project by the Owner. I. Before submitting his bid, the Electrical Contractor shall visit the site with the Drawings and Specifications and shall become thoroughly familiar with all conditions affecting his work since the Electrical Contractor will be held responsible for any assumption he may make in regard thereto. J. The Electrical Contractor shall check the Architectural Plans and Specifications before ordering any materials and the installation of work. Any discrepancies shall be called to the attention of the Architect before proceeding with the work. 1.06 QUALITY ASSURANCE A. Equality of materials or articles other than those named or described in this Section will be determined in accordance with the provisions of the General Requirements, except that substitutions will only be considered for items where the words, "or equal" appear in product specifications and as approved by the Architect and Owner. B. The Electrical Contractor shall agree to accept as final the results of tests secured by a qualified testing laboratory engaged by the Owner. Tests will be conducted in accordance with the General Requirements. 1.07 PRODUCTS A. With the exception of items specifically noted other -wise, all materials used shall be U.S. made, new, full weight, and first class in every respect, without defects, and designed to function properly in that portion of the work for which they are intended, and with the same brand of manufacturers for each class of material or equipment. Electrical materials and equipment of types for which there are Underwriters Laboratories standard requirements, listings, or labels shall conform to their requirements and be so labeled. 1.08 SUBMITTALS A. Before ordering materials shipped to the job, the Electrical Contractor shall submit to the Architect six (6) sets of catalogue cuts, manufacturers' data sheets, or Shop Drawings, giving all details, dimensions, capacities, etc. of all materials to be furnished. ELECTRICAL 16100- 4 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA Code, and local laws, rules, regulations, and codes and state and local energy codes pertaining thereto. Where provisions of the Contract Documents conflict with any codes, rules or regulations, the latter shall govern. Where the Contract requirements are in excess of applicable codes, rules or regulations, the Contract provisions shall govern unless the Architect rules otherwise. B. The Electrical Contractor shall comply with the Local Code Enforcement Officials' instructions at no additional cost to the Owner. C. Design and installation shall be in accordance with the Massachusetts State Building Code and the Stretch Energy Code. 1.05 INSTALLATION REQUIREMENTS A. The Electrical Contractor shall employ only competent and experienced workmen at a regular schedule in harmony with the other tradesmen on the job. He shall also exercise care and supervision of his employees in regard to proper and expeditious laying out of his work. B. The Electrical Contractor shall have a Foreman or Superintendent assigned to the Project who shall be authorized to make decisions and receive instructions exactly as if the Electrical Contractor himself were present. The Foreman or Superintendent shall not be removed or replaced without the express approval of the Architect after construction work begins. C. The Electrical Contractor shall be held responsible for any injuries or damage done to the building premises or adjoining property or to other Contractors' work resulting from the execution of his part of the work in any manner whatsoever; and in case of dispute arising as to the extent or share of responsibility incurred by the Electrical Contractor, it is agreed between the Owner and the Electrical Contractor that such liability and extent of damage shall be finally determined by the Architect whose decision shall be final and binding on both parties to the Contract for the work in question. D. The Electrical Contractor shall cooperate to the fullest extent with all other trades in order to expedite the progress of the work. He shall review the drawings of all other trades and furnish all information pertaining to his materials as to sizes, locations, and means of support, to all other trades requiring such information. The Electrical Contractor shall also furnish all sleeves, frames, beams, supports, inserts, etc., hereinafter specified so that the General Contractor may build them in place. In case of failure on the part of the Electrical Contractor to give proper information as above, he will be required to bear the extra expense involved due to such failure. E. The arrangement of all piping, duct work, conduit, wire and cable indicated on the Drawings is diagrammatic only, and indicates the minimum requirements of this work. Conditions at the building shall determine the actual arrangement of runs, bends, offsets, etc. The Electrical Contractor shall lay out all his work and be responsible for the accuracy thereof. Conditions at the building shall be the determining factor for all measurements. ELECTRICAL 16100- 3 Section 16100 — Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA SECTION 16100 — ELECTRICAL (DESIGN BUILD PERFORMANCE SPECIFICATIONS) PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Include General Conditions, Supplementary General Conditions, and applicable parts of Division 1, as part of this Section. B. Examine all other Sections of the Specifications for requirements which affect work under this Section whether or not such work is specifically mentioned in this Section. C. Completely coordinate work with that of all other trades affecting, or affected by the work of this Section and provide for complete and fully functional installation. Cooperate with such trades to assure steady progress of all work under the Contract. When the word "provide" is used in this specification, it shall mean to furnish and install. 1.02 PARAMETERS OF SCOPE A. All wiring shall be based on copper conductors, with the conduit and raceways accordingly sized. Aluminum conductors are prohibited. B. Perform work and provide materials and equipment as required for a complete and operational Electrical System. Provide complete design/build service for the Electrical Systems including a complete set of drawings signed and stamped by a registered Professional Engineer in the Commonwealth of Massachusetts. 1.03 SCOPE OF WORK A. Furnish all labor, materials, plant, equipment and services necessary for and reasonably incidental to the complete installation of all electrical work specified herein and/or indicated on the Drawings, including, but not limited to, the following: 1. Service Switch and Metering Equipment. 2. Feeders. 3. Lighting and Power Panelboards. 4. Wiring devices and plates. 5. Branch Circuit Wiring and Raceway. 6. Power wiring to motors and equipment furnished by other trades or Owner including final connections to equipment. 7. Lighting fixtures. 8. Inspections. 9. Operating and Maintenance Instructions. 1.04 CODES, ORDINANCES AND INSPECTIONS A. All materials and the installation thereof shall conform to the requirements of the Massachusetts State Building Code, Eighth Edition, the 2011 Massachusetts Electrical ELECTRICAL 16100- 2 • Section 16100 - Electrical Gate House Lot 18 Design Build Hospital Hill Northampton, MA INDEX SECTION 16100 - ELECTRICAL PART 1 - GENERAL PART 3 - INSTALLATION 1.01 RELATED DOCUMENTS 3.01 GENERAL INSTALLATION 1.02 PARAMETERS OF SCOPE REQUIREMENTS 1.03 SCOPE OF WORK 3.02 CUTTING, PATCHING AND DRILLING 1.04 CODES, ORDINANCES AND INSPECTIONS 3.03 GROUNDING 1.05 INSTALLATION REQUIREMENTS 3.04 CONDUIT AND FITTINGS 1.06 QUALITY ASSURANCE 3.05 LIGHTING FIXTURES 1.07 PRODUCTS 3.06 OUTLET AND JUNCTION BOXES 1.08 SUBMITTALS 3.07 EQUIPMENT INSTALLATION 1.09 PERMITS, FEES AND INSPECTIONS 3.08 TESTING 1.10 TEMPORARY HOOK -UPS 3.09 NAME PLATE AND LABEL 1.11 TEMPORARY LIGHT AND POWER INSTALLATION 1.12 PLANS AND SPECIFICATIONS 3.10 FIRE SAFING 1.13 PRODUCT HANDLING 1.14 ENVIRONMENTAL CONDITIONS 1.15 WORK CONCEALED 1.16 OPERATING INSTRUCTIONS 1.17 GUARANTEE 1.18 CUTTING AND PATCHING 1.19 RECORD DRAWINGS PART 2 - MATERIALS 2.01 RACEWAYS 2.02 WIREWAYS 2.03 CONDUCTORS 2.04 OUTLET AND JUNCTION BOXES 2.05 NAMEPLATES 2.06 WIRING DEVICES 2.07 MOTOR STARTER AND SWITCHES 2.08 LIGHTING FIXTURES 2.09 LIGHTING AND POWER PANELBOARDS 2.10 ELECTRICAL SERVICE 2.11 FIRE ALARM SYSTEM 2.12 TELECOMMUNICATIONS SYSTEM ELECTRICAL 16100- 1 • Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA C. The speed, horsepower, type and other essential data for each motor, if not given under paragraphs describing the various motor driven apparatus, or in schedules on the drawings shall be submitted to the Engineer for his/her review. All two speed motors shall be single winding type. D. Contractor shall furnish premium efficient motors eligible for rebate by the local electric utility, when applicable. 2.12 AUTOMATIC TEMPERATURE CONTROLS A. Furnish and install all control components necessary to obtain a fully functional control system as described herein. The contractor is responsible for providing all controls, relays, etc. necessary to accomplish the Sequence of Operations and performance specified, whether or not the items are specifically identified herein. Wherever a setpoint is referred to, this implies that the setting is adjustable by the user. B. The HVAC contractor shall coordinate with the electrical contractor and pay for all electrical power service required to supply the required power voltage to the control systems if not shown on the electrical drawings. All low voltage control wiring shall be minimum of 18 AWG plenum rated. All wiring shall run concealed within walls and ceilings. C. For each of the HVAC units provide a programmable thermostat control system as specified herein by Honeywell, or equal. Coordinate exact location of thermostats with Architect and Owner. D. HVAC contractor shall install duct smoke detectors for all units 2000cfm or greater. HVAC contractor shall wire duct smoke detector to unit circuit to shutdown fan and unit upon activation. Electrical contractor shall power wire duct smoke detector and wire to fire alarm system. Duct smoke detectors shall be installed on all make -up air and gas-fired units of 2000 cfm or greater in capacity. 2.13 SEQUENCE OF OPERATION A. Each new HVAC unit furnish and install with a programmable thermostat with seven day time clock. Unit AHU serving the small dining area and kitchen shall be interlocked with the kitchen exhaust hood to start AHU when hood is started. The bathroom exhaust fan shall be interlocked with a prgrammable time clock to start the fan in the occupied mode and stop the fan in the unoccupied mode. END OF SECTION 15600 HVAC 15600- 12 A Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA exhaust fan such that structure above supports the weight of the fan, not the ceiling system. Coordinate interlock of motorized dampers with electrical contractor. D. Exhaust fans in kitchen hood to be upblast rated for grease application. 2.10 ELECTRICAL WORK A. The HVAC Contractor shall provide all wiring for the Automatic Temperature Controls for the make -up air unit, and split system HVAC units. B. The HVAC Contractor shall hire a licensed electrician to perform all control wiring as required by code. Minimum gauge of all control wiring is 18AWG. All control wiring shall be plenum rated. C. The Electrical Contractor shall install and do all power wiring for all motor starter and un- mounted motors, furnished to him a the job site by other trades. D. For all low voltage motors, temperature control wiring and motor control wiring, including wiring for interlocking, shall be provided by the Section providing motors, including the installation of all control devises. E. Furnish all starters and all motor control devices for motor driven equipment required for the work. The Electrical Contractor shall provide all code required disconnect switches for all motors, except where otherwise noted. The setting of all motors required for mechanical equipment shall be included as part of the mechanical work. F. Equipment which includes a number of correlated electrical control devices mounted in a single enclosure or on a common base with equipment, shall be supplied for installation completely wired as a unit with terminal boxes and ample leads ready for external wiring. G. All electrical items called for as part of the mechanical work shall conform to NEMA Standards, to the requirements of the National Fire Protection Association and to the requirements of any local electrical code authority having jurisdiction. Any field modifications required to ensure such conformance shall be included as part of the mechanical work. 2.11 ELECTRIC MOTORS A. This Contractor shall provide all electric motors necessary for driving all motor driven equipment required to be furnished under this section of the Specification. B. All motors shall be designed for 3 phase, 60 cycle alternating current operation with 208 volts across the motor terminals, except that, unless otherwise specified herein, all motors 1/3 HP and smaller shall be designed for single phase, 60 cycle alternating current at 120 volts across the terminals. HVAC 15600- 11 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA 2.07 HVAC UNITS A. Provide packaged gas-fired heating/electric cooling split system units of the type and capacity need to meet design conditions, to be Carrier, Trane, or equal. Note: High efficiency 2 -stage heating is a requirement of acceptance. B. Unit shall be designed for a minimum of 94% thermal efficiency, power- vented 2 -stage gas heating, arranged for mounting on a field- assemble insulated roof curb furnished by the manufacturer. The units are to be arranged for field duct connection with vertical or horizontal supply and return connections as shown on the plans. Units shall have a SEER rating of at least 11. See schedules for additional options. C. Units shall include a centrifugal blower, premium efficiency open -drip proof motor and a factory- installed adjustable belt drive. Direct drive shall only be acceptable on units smaller than 3 tons in capacity and of which a belt drive fan is not an option. Direct drive units shall have a minimum of 3 speed selections for the blower. D. Units shall be provided with integrated total enthalpy economizers and barometric relief dampers. Provide optional vertical flue vent discharge adapters. 2.08 VRB HEAT PUMP SYSTEM A. Furnish and install where shown of the plans a package VRV heat pump system complete with concealed ducted evaporator units, remote air cooled variable speed compressor, and system controls with remote sensor. 2.09 EXHAUST FANS A. Exhaust fans shall be of the type and capacity shown on the Drawings; Greenheck, Carnes, Penn, or equal. Fan shall be tested in accordance with AMCA and bear the AMCA Certified Performance Rating Seal; fans shall be UL listed. All fans shall come equipped with factory wired and mounted disconnect switches and back draft dampers. B. Centrifugal roof exhaust fans for bathroom exhaust shall be heavy gauge aluminum mounted on a rigid support structure to provide minimal resistance to air flow and minimal noise generation. Fan wheel shall be of the aluminum backward curved centrifugal type belt driven Motorized backdraft dampers shall be provided on each roof exhaust fan. Backdraft damper shall lbe interlocked with operation of exhaust fan to open fully, or modulate as specified, upon fan activation and close completely when fan is disabled. If dampers are not shown connected on the electrical plans, this contractor shall hire the project electrician to wire the dampers to interlock with fan operation. Fans shall come with a factory wired and mounted disconnect switch (weatherproof as required.). C. Ceiling and in -line exhaust fans shall be forward curved centrifugal wheel direct drive. Motor and fan shall be removable from housing, motor shall have ball bearings and have built in overload protection. Housings shall be steel with acoustic insulation; provide ceiling grille. Provide factory mounted disconnect switch and backdraft dampers. Mount ceiling HVAC 15600- 10 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA B. Supply Return & Return Air Ductwork: The following ductwork shall be insulated: 1. All supply air ductwork except that exposed within the space it serves. Supply air ductwork located in a ceiling return air plenum must be insulated. 2. All return air ductwork. Return air ductwork located within a ceiling return air plenum or located within a ceiling cavity sandwiched between two conditioned areas (i.e. return duct above first floor ceiling and below 2n floor slab) need not be externally insulated. Return air ductwork in attic areas or in machine rooms must be insulated. 3. Return and exhaust air ductwork from the discharge point to the back draft or isolation damper (see outdoor air ductwork). Above ductwork shall be insulated with 1 Y2" thick flexible blanket duct insulation with vapor barrier, .75 lbs. Per cubic foot density glass fiber with maximum K factor of 0.28 at 75 degree F. mean temperature with fire retardant foil/draft vapor barrier facing. Product shall be Owens Corning FRK type 75 or equal. All seams and joints shall be taped with matching Kraft paper vapor barrier tape. Exposed supply and return ductwork located within the conditioned space need not be insulated. C. Outdoor Air Ductwork: All outdoor air ductwork including combustion air ductwork and outdoor and relief /exhaust air louver plenums shall be insulated with 2" thick flexible blanket duct insulation with vapor barrier, 1.5 lbs. Per ft. density glass fiber with maximum K factor of 0.28 at 75 degree F. mean temperature with fire retardant foil/draft vapor barrier facing. D. Acoustic insulation: All supply and return ducts shall be lined internally with 1" Insulacoustic liner for a minimum of 15 feet from the equipment. Liner shall have a smooth microbe resistant surface in compliance with NFPA and ASHRAE. Duct dimensions noted on drawings are clear inside dimensions. E. Insulate refrigerant suction and /or hot gas line with closed -cell Armaflex pipe insulation with all joints and seams glued vapor tight. Minimum wall thickness shall be 1 ". Apply UV protectant sealant over all insulation exposed to the weather. F. Piping Insulation: Condensate piping located above ceiling and in unconditioned spaces such as attics shall be insulated as specified above for refrigerant suction lines. 2.06 VIBRATION ISOLATION AND FLEXIBLE CONNECTIONS A. At duct connections to equipment, provide glass -fabric flexible neoprene connections with a minimum of 6 inch full length and approved by the governmental agencies having jurisdiction. B. At refrigerant pipe connections to chiller and condenser provide braided bronze flexible pipe connectors as manufactured by Mercer Rubber Co. model # BBF, or equal. HVAC 15600- 9 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA 2.03 PIPE AND FITTINGS A. All pipes shall be new, free from scale or rust, of the material and weight specified under the various services. Each length of pipe shall be properly marked at the mill or proper identification with name or symbol of manufacturer. B. All copper tubing shall be of weight as required for services specified, with conformance with ASTM B -88 for types "L" and "K" tubing, as manufactured by Chase, Anaconda, Revere, or an approved equal. Tubing and fittings shall be thoroughly cleaned with sand cloth and treated with an approved non - corrosive flux before solder is applied. C. Refrigerant piping shall be hermetically sealed ACR type hard drawn type except that pre - charged, pre - insulated soft roll line sets may be used for lengths less than 25 feet. Extra tubing shall be sealed securely above ceiling. Provide liquid line filter drier and sight glass. Refrigerant piping insulation shall conform to equipment manufacturer recommendations. D. Combustion air and flue vent piping from condensing furnace shall be schedule 40 CPVC pipe. At floor penetrations and other penetrations of rated structure provide expanding fire stop collars listed to protect plastic pipe openings as manufactured by 3M or approved equal. E. All condensate piping shall have serviceable traps. Where condensate from a roof -top unit is within 10 feet of a roof drain, run line to roof drain otherwise provide concrete splash block under outlet. 2.04 PIPE FOR VARIOUS SERVICES A. Solder for each solder type fitting shall be 95% tin and 5% antimony. B. Pipe Schedule: Service - Piping Type Piping Sch. WT. Notes *Refrigerant Piping ACR hard drawn. ACR Type K Silver- brazed joints Condensate Piping Hard Drawn Type L *Provide liquid line filer drier and sight glass on each circuit. 2.05 INSULATION A. General 1. Provide materials complying with NFPAS bulletin 90 -A, as determined by UL method NFPA 225 -ASTM E 84 and complying with the governing code, with flame spread rating under 25 and smoke developed rating under 50. 2. Where vapor barriers are used, provide intact and continuous throughout. 3. Acceptable manufacturers: Owes /Corning Fiberglass, Manville, or Certainteed HVAC 15600- 8 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA 5 feet. Secure with tie straps screwed to duct and duct sealer. Flexible ductwork shall only be allowed at connections to diffusers, registers, and grilles where the ductwork is located above an acoustical ceiling. L. Fire Dampers 1. Construction: UL listed and rated for 1 -1/2 hour fire rating in conformance with NFPA 90A and authorities having jurisdiction. All shall be out -of- stream type. 2. Provide fire dampers with access doors in openings in the following locations. a. Fire rated wall and fire partition. b. Fire rated ceilings and floors. c. When required by local and state codes. M. Kitchen exhaust ducts to be 1Oga welded steel with fire wrap insulation and fire -rated access doors and cleanouts. 2.02 AIR OUTLETS A. Diffusers, registers, and grilles shall be provided in sufficient quantity and location to adequately diffuse, return and/or exhaust air over the entire zone being serviced. Manufacture's shall be Titus, Krueger, or MetalAire. All grilles and registers shall be designed for a maximum noise coefficient of 25. B. Supply registers serving the areas without acoustical ceilings shall be double deflection type similar to Titus Model #301RS. Ceiling diffusers as specified herein may also be used in areas where sidewall supply registers cannot provide adequate air diffusion and coverage such as narrow corridors. Return and exhaust registers in all spaces shall be fixed deflection type similar to Titus Model #350FL (aluminum in bathroom areas). All supply and exhaust registers shall have opposed blade dampers. Where the branch duct damper leading to a return grille is not readily accessible the grille shall be provide with an opposed blade damper. C. Ceiling supply diffusers shall be lay -in module type in acoustical ceiling areas, surface mount in all other areas. Diffusers shall have adjustable pattern blades and shall be similar to Titus Model #TDCA. All diffusers shall have opposed blade dampers. D. On return grilles /registers in the acoustical ceiling areas, provide a sound line plenum box the full duct dimension of the grille /register shall be provided for the connection to the branch duct. For square neck supply diffusers connecting to a round duct, the transition piece shall have a minimum 45 degree angle. E. For all diffusers, registers, and grilles select so as not to exceed a noise criteria of 28. HVAC 15600- 7 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 2 — PRODUCTS 2.01 DUCTWORK A. For the HVAC systems, provide galvanized sheet metal ducts fabricated and installed to pertinent ASHRAE and SMACNA standards, except as otherwise indicated. Galvanized ductwork shall conform to ASTM A527 (G -90) having not less than 1.25 oz. Of zinc on each side of each square foot of sheet. Duct systems shall comply with the pressure velocity classification in compliance with the SMACNA HVAC Duct construction Standards, 1985 first edition. Minimum pressure classifications shall be 2" w.g. B. Design all ductwork using the equal friction method. For all areas, the ductwork shall be designed to not exceed 0.1" /100'. C. Furnish and install the size, connections and run of ducts as indicated on the drawings. Drawings indicate proposed routing. Only this contractor shall size all ductwork at a maximum static of .05/100L.F. D. The sheet metal ductwork shall, whether indicated or not, rise and drop and change in shape to clear lighting fixtures, plumbing and structural framing etc., to maintain the desired clearances within the spaces. E. The ductwork shall be continuous with airtight joints and seams presenting a smooth surface on the inside and neatly finished on the outside. Ducts shall be constructed with curves and bends so as to effect an easy flow of air. Unless otherwise shown on the Drawings, the inside radius of all curves and bends shall be not less than width of ducts in plane of bend. F. All ductwork, unless otherwise noted, shall be built from galvanized sheet steel thoroughly braced and stiffened. All ductwork shall be of the gauge recommended by SMACNA except that the minimum gauge thickness for any duct shall be no less than 24. G. Seal all ducts seams, transverse and longitudinal, air tight with 3M "ED800" or equal duct sealing compound. H. At all branch ducts, provide volume manually operated dampers of the type and arrangement shown on the Drawings, two gauges heavier that the duct in which installed and equipped with locking quadrants. All branch take -offs shall be made with 45 or full Bellmouth type fittings. I. Volume dampers, provide single and multi blade manually adjustable dampers as shown on drawings in all duct splits and branch connection of supply and exhaust air systems. J. Turning vanes, provide and install airfoil vanes at square duct elbows and as noted on drawings. Vane length not to exceed 36 inches. Provide separate equal size sections for greater lengths. K. Flexible duct shall be 1" thick insulated low pressure type with vapor barrier as manufactured by Automation Industries. Thermoflex type MKE or equal. Maximum length of flex duct is HVAC 15600- 6 • r Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA D. Operating Instructions 1. Prior to the completion of all work and the final inspection of the installation by the Owner, three (3) copies of a complete Instruction Manual, bound in booklet form and suitably indexed, shall be submitted to the Architect for review and approval. All written material contained in the manual shall be typewritten or printed. 1.04 INSTRUCTION OF OWNER'S PERSONNEL A. After completion of all work and all tests and at such time as designated by the Owner, provide the necessary skilled personnel to operate the entire installation for a period of sixteen (16) hours. B. During the operating period, fully instruct the Owner's representative in the complete operation, adjustment and maintenance of the entire installation. 1.05 QUALITY ASSURANCE A. Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work in this section. B. The Contractor's superintendent shall conduct all coordination between the Contractor, the Architect, the Engineers, etc., and shall fully represent the Contractor's position in his absence. All decisions by the superintendent shall become the responsibility of the Contractor and binding to the Contract. The Contractor shall be responsible for the drawings, and that which is written or implied in the specifications. C. Without additional cost to the Owner, provide such other labor and materials as are required to complete the work of this Section in accordance with the requirements of governmental agencies having jurisdiction, regardless of whether such materials and associated labor are called for elsewhere in these Contract Documents. D. Before submitting the final proposal examine the site of the proposed work to determine existing conditions that may effect the work, as this section will be help responsible for any assumption in regard thereto. 1.06 GUARANTEE A. The Contractor shall guarantee every component part of each system for a minimum of one- year parts and labor. The contractor shall also provide the Owner with factory warranties for all equipment. For equipment with compressors, provide extended five -year warranty on entire sealed system. HVAC 15600- 5 k Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA 1.03 SUBMITTALS A. Product data: within 15 calendar days after the Contractor has received the Owner's Notice to proceed, submit the following. Refer to Division I requirements for copy quantity of submittals or if not specified submit seven (7) copies. 1. It is expected that the contractor shall provide the Architectural design team, with a set of contract drawings stamped by a Professional Engineer registered within the Commonwealth of Massachusetts for permit and construction. For estimating purposes, the contractor shall use the guidelines described herein for sizing and selecting the system components. 2. This contractor shall review the drawings of all other trades and where conflict exists, shall prepare coordinated shop drawings, showing proposed conflict and proposed resolution layout. 3. Submit schematic control diagram showing all control components, wiring, and locations. Control submittal shall also include sequence of operation for each system. 4. Manufacturer catalogs, samples, and other items needed to fully demonstrate the quality of the proposed materials and equipment. In addition to the submittals formerly mention herein equipment specification sheets and dimensional data on the following: a. Split system HVAC units equal to Train, Carrier, or Lennox. b. Ducted heat pump units equal to Mitsubishi, Dicken, or Sanyo. c. Temperature controls. d. Exhaust fans. e. Controls. f. Refrigerant piping, flue and vent piping and accessories. g. Grilles, registers, and diffuser. B. Record Drawings 1. Include a copy of the record drawings (as- builts) in each copy of the operation and maintenance manual described below. C. Testing and Balancing Reports 1. Submit four (4) copies of a certified testing and balancing report to the Architect for review and approval. Include all airflow and temperature readings as outlined herein. All balancing shall be performed by an NEBB Certified Balancing Contractor. HVAC 15600- 4 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA b. Zoned for each tenant space per the attached plan. Note: The plan is intended to show the HVAC zoning and proposed duct routing. It is not intended to limit or dictate design. 6. Future Kitchen exhaust and make up air system including but not limited provision for future ductwork, fan, and controls. 7. Exhaust fans —In line and/or ceiling, one to serve all bathrooms and janitor closet controlled by a single timeclock controller. 8. An electric cabinet heater at each water service entrance and stairs. 9. Ductless heat pump units to serve common entry lobby. 10. Piping and all related accessories. 11. Insulation, thermal and/or acoustic, for ductwork and piping. 12. Automatic temperature controls. 13. Instruction manuals and startup instructions. 14. Equipment bases and supports. 15. All rigging and hoisting of equipment as required. 16. Access doors on sheet metal ductwork, sheet metal panels and enclosures. 17. Pre - fabricated or field erected curbs. C. Related Work Specified Under Other Divisions 1. Division 16000 — Power Circuiting 2. Division 15400 — Plumbing D. This contractor is responsible for sleeving all holes required of his work prior to pouring of the concrete slabs. All holes less than or equal to 4" shall be the responsibility of this contractor to core. Sizes larger shall be cored the G.C. However, if coring is required due to failure of this contractor to set a sleeve prior to pouring than this contractor shall be responsible for bearing the cost of any of this additional work required of the G.C. E. Contractor is responsible for coring and fire- stopping all rated penetrations of the structure. HVAC 15600- 3 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 1 — GENERAL 1.01 RELATED DOCUMENTS A. All of the Contract documents, including General and Supplementary Conditions and Division 1, General Requirements, are hereby made a part of the work of this Section 1, the more stringent requirements shall govern. B. All work shall comply with all federal, state, and local codes and any other authorities having jurisdiction. 1.02 SUMMARY A. Perform work and provide materials and equipment as required for a complete and operational HVAC system. Provide complete design/build services for the HVAC system including a complete set of drawings stamped and signed by a registered professional engineer. Completely coordinate with work of other trades and provide for complete and fully functional installation. When the word "provide" is used in this specification, it shall mean to furnish and install. B. The work shall include, but is not limited to, the following major items of work: 1. Complete HVAC system for the building. Design and installation shall be in accordance with the Massachusetts State Building Code and the Stretch Energy Code. Systems shall be capable of maintaining spaces at 72 deg. F. in the winter, and 75 deg. F. in the summer. Ventilation requirements shall conform to the more stringent density and ventilation requirements of either BOCA Mechanical Code 1993 or ASHRAE 62 -1989 Standard for Ventilation which dictates 10 cfm per person of outdoor air for assembly space, but in no case shall overall assembly densities be calculated at less than 1 person per 30 SF or as shown on the drawings. Refer to Code and Standard for additional classifications and requirements. 2. Provide Design drawings stamped by a registered professional engineer in the State of Massachusetts. 3. Complete HVAC duct system including diffusers, registers, grilles, dampers, etc... 4. Miscellaneous steel, dunnage, supports, hangers, pads, etc., as shown, and as required. 5. Gas Fired air handling units (AHU) high efficiency gas heating electrical cooling units with remote condensing units. As a minimum, contractors shall assume the building shall incorporate the following quantities of equipment: a. (8) Gas fired single phase split systems units with remote condensing units. HVAC 15600- 2 Section 15600 — Heating, Ventilating, Air Conditioning Gate House Lot 18 Design Build Hospital Hill Northampton, MA PART 1 — GENERAL 2 1.01 RELATED DOCUMENTS 2 1.02 SUMMARY 2 1.03 SUBMITTALS 4 1.04 INSTRUCTION OF OWNER'S PERSONNEL 5 1.05 QUALITY ASSURANCE 5 1.06 GUARANTEE 5 PART 2 — PRODUCTS 6 2.01 DUCTWORK 6 2.02 AIR OUTLETS 7 2.03 PIPE AND FITTINGS 8 2.04 PIPE FOR VARIOUS SERVICES 8 2.05 INSULATION 8 2.06 VIBRATION ISOLATION AND FLEXIBLE CONNECTIONS 9 2.07 HVAC UNITS 10 2.08 VRB HEAT PUMP SYSTEM 10 2.09 EXHAUST FANS 10 2.10 ELECTRICAL WORK 11 2.11 ELECTRIC MOTORS 11 2.12 AUTOMATIC TEMPERATURE CONTROLS 12 2.13 SEQUENCE OF OPERATION 12 HVAC 15600- 1 • Door Finish: Stainless Steel • Sill: Manufacturer's standard • Door Style: Single speed — Provide location as shown on Drawings • Front: Manufacturer's standard • Cab Interior Wall Finish: Plastic Laminate • Ceiling: Manufacturer's standard • Floor: By flooring subcontractor • Provide moving pads and hooks • Elevator Contractor to provide pit ladder • Hoist way beam (W8) by General Contactor See attached: Section 14240 — Hydraulic Elevator See attached for: Section 15300 — Fire Protection, Design Build Section 15400 — Plumbing, Design Build Section 15600 — Heating, Ventilating, Air Conditioning, Design Build Section 16100 — Electrical, Design Build 23 ,E, Finish 2 coats acrylic Sheen Satin Color 1 color only 9907 Handrails, Caps, and Closet Poles Handrails, wall caps, etc., for natural finish use Zip Guard or equal for water based stain. Stain None Finish 3 coats poly Sheen Satin 10000 SPECIALTIES 10165 Plastic Toilet Compartments — Per Plan Brand and Finish TBD. PVC 10800 Toilet & Bathroom Alternate: FRP at Lays 10801 Toilet & Bath Accessories Furnished and Installed by Contractor Item All Baths Towel Bars (1) x Paper Holder (1) x Mirror 18x30 x Grab Bars x 11000 EQUIPMENT /APPLIANCES -N /A (By Tenant) 12000 FURNISHINGS 12490 Window Treatments — By Tenant 12690 Entrance Mats - TBD 14000 CONVEYING SYSTEMS 14200 Elevator ThyssenKrupp elevator or equal • Number of Stops: Three (2) • Travel Distance: See architectural plans (Verify) • Pit Depth: 4 -0" • Overhead Clearance: As per manufacturer's requirements. 22 1 Follow manufacturer's recommendations, utilizing Benjamin Moore or equal standard range of colors. Fully finish all edges. Advise contractor if clearances insufficient prior to application of finish. Prime Factory Finish 2 coats acrylic Sheen Satin Color Per Plans 9903 Interior Doors Follow manufacturer's recommendations, utilizing VOC free Benjamin Moore Eco Spec or equal standard range of colors for paint or Zip Guard or equal for water based stain. Fully fuush all edges. Advise contractor if clearances insufficient prior to application of finish. Finish 3 coats clear acrylic Sheen Satin Color N/A 9904 Interior Walls Interior walls and ceilings receive prime and finish coats, utilizing VOC free Benjamin Moore Eco Spec or equal, in manufacturer's standard color range. Prime One coat acrylic Finish 1 coat acrylic Sheen Flat (no option) Color 1color 9905 Interior Ceilings (Soffits) Interior ceilings receive prime and finish coats, one color throughout, utilizing VOC free Benjamin Moore Eco Spec or equal, in manufacturer's standard color range. Prime One coat acrylic Finish 1 coats acrylic Sheen Flat (no option) Color Ceiling white 9906 Casings, Baseboard, Shelving, Risers, Skirt Boards Casings, baseboards and miscellaneous trim including windows to receive prime and finish coats utilizing VOC free Benjamin Moore Eco Spec or equal in manufacturer's standard range of colors for paint or Zip Guard or equal for water based stain. Prime factory 21 Base vinyl base 9680 Carpet Carpet and pad materials allowance at $22 per yard plus prep, adhesive and labor as indicated on drawings or in the following rooms: See Section 6172 for underlayment requirements. Location: All areas including stairs Brand Shaw or equal Color TBA Weight Comm. 26 oz Install type Direct NOTE: Carpet base except at VCT, tile areas and stairways. 9900 Paints & Coatings NOTE 1: Paint new and disturbed surfaces corner to corner unless otherwise noted. NOTE 2: For all painter's work, regardless or source, sheen levels noted in our specs prevail regardless of who is providing the painter's work. No performance or appearance guarantee is available for other sheens or finishes. NOTE 3: If some or all of the scope of painter's work is provided by owner or owner's contractor, please note that all manufacturer's painting requirements must be met in order to preserve the value of the product's warranties. All doors and windows must be properly and completely sealed, including all coats of finish application on all faces of doors and windows. Seal inside of boring on doors. NOTE 4: Wright Builders has no warranty responsibility for work it does not furnish. Should drywall repairs require painter's work, and painter's work is not part of Wright Builders contracted scope, there will be no compensation for repainting. NOTE 5: For owner supplied painter's work, drywall surfaces are considered acceptable and accepted by the owner when paint is applied. 9901 Exterior Body &Trim NOTE: all field cuts to be primed by carpenter prior to installation Provide oil prime and latex finish coats on all exterior trim, fascia, window sash, etc. Stain and seal knots as required and caulk joints to siding manufacturer /trade standard. Prime Factory pre -primed Finish 2 coats acrylic Sheen Satin Color Field is Roycroft Mist Gray SW 2844, Trim is Titanium OC-49 Ben Moore 9902 Exterior Doors 20 Interior transoms to be single pane installed in field with wood stops. 9000 FINISHES 9200 Drywall Completely review Section 6172 — Subfloor/UnderlaymentBacker for additional responsibilities for this work. 9201 Walls All new interior walls and surfaces to receive 5/8" standard drywall taped with three coats and finished smooth ready for paint by others. This work is not typically painted unless specifically indicated here and in the painting section. Installer will be responsible for repairs around outlets, switches and light boxes as needed. 9202 Ceilings All new ceilings to receive 5/8" standard drywall taped with three coats and finished smooth ready for paint by others. 9301 Floor Tile Material allowance: $5 /sq ft. Layout drawings, bullnose /corners, etc Note 1: Grout sealer is to be included. Note 2: Baseboard is to be installed prior to floor tile Location: 1 floor Entry Lobby Area Brand TBA Color TBA Size 12x12 Type Ceramic/Porcelain Base — cut tile base 6" 9500 Ceiling Suspension Systems Location: Per Plan Grid size 2x4 Color White Tile type Natural Fissure — OPTION: 2x2 semi regressed pattern 9666 Vinyl Flooring Vinyl floors to be: Vinyl material under allowance VCT single color pattern. Locations: All Baths 19 SET 6 (INTERIOR STAIRWELL W/PANIC) (3) HINGE FBB179 4.5 X 4.5 X US32D NRP ST (1) EXIT DEV ED5200A X N955 630 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (1) STOP 409 /441CU X US26D TO SUIT RO (3) SIL 608 RO SET 7 (MECHANICAL ROOM) (3) HINGE FBB179 4.5 X 4.5 X US32D ST (1) STORE CL3357 NZD 626 CT6 (KNURLED WHERE REQ'D) CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (3) SIL 608 RO SET 8 (JANITOR CLOSET) (3) HINGE FBB179 4.5 X 4.5 X US32D ST (1) STORE CL3357 NZD 626 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (3) SIL 608 RO SET 9 (SINGLE USE RESTROOM) (3) HINGE FBB179 4.5 X 4.5 X US32D ST (1) PRIV CL3320 NZD 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K10508 "X2 "LWODXUS32D RO (3) SIL 608 RO SET 10 (PUBLIC RESTROOM) (3) HINGE FBB179 4.5 X 4.5 X US32D ST (1) PASS CL3310 NZD 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (3) SIL 608 RO SET 11 (ENTRY TO SPACE) (3) HINGE FBB179 4.5 X 4.5 X US32D ST (1) ENTRANCE CL3351 NZD 626 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (3) SIL 608 RO 8800 Other Glazing Kawneer or equal Sore Front components per plan, Bronze finish, Low E Argon Glass. 18 SET 1 (ALUM DOOR EXTERIOR) (1) CONT HINGE KCFM HD1 PE (1) EXIT DEV ED4200/5200 X K157 CT6 CR (1) CORE 8000 626 CR (1) PULL BF157 X US32D RO (1) CLOSER DC6210 689 CR (1) THRESH 172A PE (1) BALANCE OF HARDWARE BY ALUM DR MFG SET 2 (ALUM DOOR EXTERIOR W /CR (1) CONT HINGE KCFM HD1 PE (1) EXIT DEV ED4200/5200 X K157 CT6 CR (1) CORE 8000 626 CR (1) PULL BF157 X US32D RO (1) CLOSER DC6210 689 CR (1) THRESH 172A PE (1) STRIKE 9600 X US32D ELECTRIC STRIKE HES (1) BALANCE OF HARDWARE BY ALUM DR MFG (1) CARD RDR CARD READER BY OTHERS SET 3 (EXTERIOR SINGLE W/PANIC) (4) HINGE FBB191 4.5 X 4.5 X US32D NRP ST (1) EXIT DEV ED5200 X N955 630 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (1) TRESH 172A PE (1) WSTRIP 303APK PE (1) SWEEP 315CN PE (3) SIL 608 RO SET 4 (EXTERIOR STOREROOM) (4) HINGE FBB191 4.5 X 4.5 X US32D NRP ST (1) STORE CL3357 NZD 626 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (1) TRESH 172A PE (1) WSTRIP 303APK PE (1) SWEEP 315CN PE (3) SIL 608 RO SET 5 (INTERIOR W/PANIC) (4) HINGE FBB179 4.5 X 4.5 X US32D NRP ST (1) EXIT DEV ED5200 X N955 630 CT6 CR (1) CORE 8000 626 CR (1) CLOSER DC6210 689 CR (1) KICK PL K1050 8" X 2" LWOD X US32D RO (1) STOP 409/441 CU X US26D TO SUIT RO (3) SIL 608 RO 17 Ammimmenwommommonmew Series and Model C500 Light Duty Style straight Door Handing verify in field Finish Brushed Chrome Backset 2 -3/4" Dead Bolt Yes - Matching 8702 Passage Set All hardware to be standard bored -in type. Brand Dorma or Equal Series and Model C500 Light Duty Style straight Door Handing verify in field Finish Brushed Chrome Backset 2 -3/4" 8703 Lav Set All hardware to be standard bored -in type. Brand Dorma or Equal Series and Model C500 Light Duty Style straight Door Handing verify in field Finish Brushed Chrome Backset 2 -3/4" 8704 Other Hardware Door stops Ives basemount #064 brass or hinge type #070 brass or equal Stairway Hand Rail Brackets Challis #3027(See stairway) Basement Hand Post & Rail 2x4 built up post with 2x4 KDS parts HARDWARE SETS FOR THE GATEHOUSE, LOT 18 16 8102 Closet & Passage Doors Material Solid Core Brand JeldWen or Equal Style Flush rotary cut Red Oak Veneer Jamb Double rabbetted P.G. 8400 Entrances & Store Fronts Kawneer or equal Sore Front components per plan, Bronze finish, Low E Argon Glass 8600 Prime Windows Notice to vendors and subcontractors: Vendors and subcontractor shall provide pricing breakdown (material and labor), required company certifications and/or registrations & detailed product information at time of quotation in such a way as to comply with federal standards for tax credits and utility documentation requirements for rebates. Brand Pella 350 Series or Paradigm or Equal Series Premium vinyl, White exterior finish Style Double hung Glazing Insulated glass Low E w /argon gas Muntins 4/1 Inside Glass Screens Full screens, T.B.A. finish Exterior Finish Color White Interior Prefinish White Interior Jamb Extensions Pre finished white Jamb 6- 11/16" Track Color Std Hardware Finish White Special Sill Details NA Manufacturer's warranty see Manufacturer's literature 8700 Finish Hardware 8701 Entry Lock Set All hardware to be standard key in knob, bored -in type, keyed alike. Brand Dorma or Equal 15 7890 Vents and Louvers Location Material Color Style /Size Ridge New only Nylon Charcoal 10" roll vent Soffit New only Aluminum White 2 3 /4" strip Gable New only Aluminum Mill Adjustable 7900 Caulks /Sealants /Adhesives Interior: Latex or paintable silicone Exterior: Latex or paintable silicone Liquid Nails or equal or as required by floor sheathing specifications, when gluing subfloor to joists Elmers or equal when gluing underlayment to subfloor Magnum 44 glue or approved equal for Advantech sheathing 8000 DOORS & WINDOWS 8100 Doors NOTE: All fenestration products must meet or exceed Energy Star requirements. NOTE: U -value and the Solar Heat Gain Coefficient (SHGC) for doors apply to the whole door, not just the glazing portion. NOTE: All window and doors to be flashed with Vicor or equal before trim & siding installation. NOTE: The head flashing is required to be cut into the Housewrap to maintain continuity in the drainage plane. Notice to vendors and subcontractors: Vendors and subcontractor shall provide pricing breakdown (material and labor), required company certifications and/or registrations & detailed product information at time of quotation. in such a way as to comply with federal standards for tax credits and utility documentation requirements for rebates. 8101 Exterior Doors — Kaween or Equal The 190 Narrow Stile Entrance: • Is engineered for moderate traffic in applications such as stores, offices and apartment buildings • Vertical stile measures 2-1/8"; top rail 2 -1/4" and bottom rail 3 -7/8" • Results in a slim look that meets virtually all construction requirements Alternate: The 350 Medium Stile Entrance: • Provides extra strength for applications such as schools, institutions and other high traffic applications • Vertical stiles and top rails measure 3 -1/2" • Bottom rail measures 6 -1/2" for extra durability Alternate: AA ®250 /425 Thermal Entrance Doors 14 Life years 30, Alternate 50 years Brand Tamko or equal Style Architectural Color Weather Wood Valley Closed Cut Pipe Flashings Included Step and kick -out flashing at all roof -wall intersections, extending > 4" on wall surface above roof deck and integrated with drainage plane above. 7310 Metal Work — Drip Edge, Flashing, Caps Install clean unblemished break - formed or premanufactured drip edge, flashing, valleys and wall flashing where required. Material Gauge Color Style /Size Drip Edge Aluminum 0.019 White L +R5 "D Style Step Flashing Aluminum 0.019 Bronze 2- 1/2 "x2- 1/2 "x7" Wall Flashing Aluminum 0.032 Bronze 4 "X5" custom Valleys Closed Cut Plumbing Flanges Aluminum standard mill finish 2-4 ", 1 -3" minimum NOTE: Verb colors NOTE: All flashing to be installed under original siding. NOTE: All plumbing flanges to be located and installed during roofing. 7600 Gutters and Downspouts Install seamless gutters and premium downspouts and discharged at grade. Splash blocks or outflow extension by Owner. Hanger should be spaced and sized for the appropriate condition. Style 6" K- Style, Commercial Gauge .032 Downspouts 3x4 .027 Material Aluminum Color Match Trim, Ben Moore Titanium OC-49 Install gutters and downspouts terminate to an underground catchment system. NOTE: Gutters require maintenance and ongoing repair due to weather condition. 13 Flat ceilings to receive blown cellulose insulation with poly vapor barrier. "Proper- Vent" all vent spaces for continuous air flow. Type and R value Blown cellulose insulation R -50 NOTE: No blown fiberglass. 7205 Scuttle Holes, Attic Doors & Whole House Fans Insulate all scuttle holes and access panels with rigid insulation and weather strip openings. Type and R Value 4" R -Max R30 using three 2" pieces laminated together 7206 Pipe Chase, Vent Ducts Wrap all ducts that are vented to the exterior with insulation duct wrap and tape joints. 7207 Floors — At 1 Floor Ceiling Type and R Value 6" fiberglass to R -19 with wire hoops installed to place insulation in contact with floor sheathing 7208 Runner and Blockers Type and R Value Flash foam with 4" Demilec HeatLok closed cell foam R28.8 7209 Sound Walls (Stairway and Bath Walls) Sound walls , including all duct chases, plumbing chases, bathroom walls and ceilings, mechanical room walls and ceilings, and any joist bay locations with waste or water piping to receive fiberglass insulation. Amount 3 'h" R -11 STC Rating 35 7210 Window and Door Sealing Seal/Insulate around all doors and windows /skylights in controlled space with non - expanding environmentally safe spray foam. 7210Interior Wall top Plate Sealing Sheetrock sealed to top plate at all attic /wall interfaces using caulk, foam, or equivalent material. Before insulating the attic, seal all top plate to interior cladding connections, from the attic above, with latex foam or caulk to stop air leakage between conditioned and unconditioned space. 7300 Roofing 7301 Roof Material — Sloped Install fiberglass roofing shingles atop #15 felt. Regardless of pitch, underlay eaves of all slopes with ice and water barrier to a point 2' beyond the interior plane of the exterior walls. Underlay all slopes under 4/12 with ice and water barrier. Underlay all valleys with ice and water barrier. Flash all skylights, chimneys roof deck penetrations with self - sealing bituminous membrane before installing metal flashings. 12 All poly vapor barriers are 6 mil unless indicated otherwise. 7195 Windblock To be Tyvek or equal in 9' rolls applied in continuous places as permitted by job conditions, with all joints taped with appropriately compatible tape. NOTE: It is important that the drainage plane be continuous and shed water to the exterior at all seams and laps. 7200 Insulation Seal all gaps and holes to unconditioned space with caulk or foam prior to insulation installation. Notice to vendors and subcontractors: Vendors and subcontractor shall provide pricing breakdown (material and labor), required company certifications and/or registrations & detailed product information at time of quotation in such a way as to comply with federal standards for tax credits and utility documentation requirements for rebates. NOTE: All insulation work is to meet or exceed 2012 Energy Star Version 3.0 performance standards as applicable. NOTE: Insulation installers are to assure that AIR BARRIERS are fully aligned. See examples below: Walls: Wall adjoining porch roof Staircase walls Double walls All other exterior walls Floors: Floor above garage Ceilings: Dropped ceiling/soffit below unconditioned attic Sloped ceilings All other ceilings 7201 Floor Insulation — See architectural plans for details Concrete floors to receive rigid insulation under vapor barrier. Step insulation up over foundation ledge to ensure thermal break. Frost Walls: 2" R -10.8 to 4'0" below grade Under slab thickness and R Value 2" Formula -R, R -10.8 7202 Exterior Walls — 2 x 6 Exterior walls to receive closed cell spray foam and Class I cellulose fiber insulation with vapor barrier. Extra measures to be taken to avoid pillowing. Tape all vapor barrier holes and penetrations. Type and R Value 2" flash foam R14.4 plus 3.5" Dense Pack Cellulose R13 for a total of R -27.4 7203 Sloped Ceilings - N/A 7204 Flat Ceilings below Attic Spaces 11 6680 Folding Stairs — NA Furnish and install stair package per manufacturer's recommendations. Box around top of stair to prevent insulation spillage. Build insulated and weather -strip fitted cover. Manufacturer Brosco Model Imperial Size 25 %1 " x 54" Floor/Floor Rise 8'9" 6682 Scuttle Hole & Access Panels Provide framed openings for all designated and code required access panels. Locations and preparation for finishes and insulation. 6694 Stair Treads and Rails NOTE: Treads to be installed by finish carpenter. Other stair parts installed by finish carpentry and finished by painter. Treads Plywood for carpet Risers Plywood for carpet canted Skirts lx10 poplar pre - primed for paint Newel post N/A Rail Continuous wood hand rail, brackets, closed side stair 6696 Rail Wall Caps Closed rails assumed. Cap 1x8 red oak Molding' h" x 11/16" oak scotia 7000 THERMAL & MOISTURE PROTECTION 7150 Damproofing Spray applied bituminous coating on all below grade foundation surfaces down to and over footing at all areas, surrounding or beneath habitable spaces. Coating type Watchdog Application 2 coats Insulation None 7180 Vapor Barriers 10 Handrails 2x10 30" O.C. Thermostats 2x6 60" O.C. Other 6410 Exterior Siding Siding Type Hardi plank, pre primed, Lap siding Exposure 5" to the weather Fasteners stainless steel nails, attached to studs /framing as possible. 6412 Exterior Trim — Per Plans NOTE: All field cuts to be primed by carpenter before installation. Fascia 1x8 w /1x2 Miratec Eave Soffitt 1 @ 1x16 Hardiplank, vented Rake Soffitt 1x16 Hardiplank, vented Window Casing 5/4 x 6 Miratec Sill none Corner Boards and Pilasters 5/4 x Miratec applied on Hardipanel (See details for columns) Frieze Boards 5/4 x Miratec (See details for Frieze) Water Table None Other Horizontal Trim 5/4 x Miratec Fasteners 8p decking style SS nails 6522 Bath Counters —Per Plan — 22 x 37 Laminate tops, Birch edge binder, plywood angle brace and skirt, cut for drop in lay and faucet. See architectural plan. 6599 Interior Trim Jamb type Double rabbetted Baseboard size and type Carpet base at carpet, vinyl at VCT, tile cove at tile Jamb extension By Window Supplier, pre - primed Casing size and type 2 -1/2" Flat pine, pre - primed Window apron size and type 2 -1/2" Flat pine, pre - primed Stool type Poplar paint grade Plinth Block none Casing corner blocks none 9 • Spacing Per Structural Layout Plan 6135 Roof Framing — Per Plan Rafter to be #1 and 2 KDS with nailing as per code and rafter ties at all bearing locations. Ridge boards to be sized to fill complete rafter cut or as noted on plans. Straps as needed at ridge. Size Spacing 2x 10 Per Plan 2x 12 Per Plan 6172 Plywood Subfloor/Underlayment Sub floor glued and nailed to joist per code and according to schedule and good construction practice. Use Material Adhesive Supplied By Installed By NOTES Sub Floor 7/8" T & G PL 400, Liquid Wright Builders Framer Patching by including tub Advantech Nails, Magnum 44 Framer deck/stair Vinyl '/z " underlayment None Vinyl Installer Vinyl Installer Patching sub floor Underlayment multiply or equal, by Framer at wood subflooring ONLY Floor Tile ' /2" UL Plywood at Exterior Wood Wright Builders Finish Carpentry Patching sub floor Underlayment wood subflooring Glue by Framer ONLY 6176 Plywood Wall Sheathing Sheathing installed horizontal with nailing per code. Type I — 7/16 OSB Type II - 1/2" .040 pressure treated if covering concrete 6177 Roof Sheathing Sheathing installed horizontal with nailing per code. Type - 5/8" Zip System 6370 Blocking Location Size Block Height to top of block Base Cabinet 2x N/A Wall Cabinet 2x4 58" Bathrooms 2x12 40" O.C. Drywall Prep 2x All corners, walls and ceiling Stringers 2x10 1/3 span Stairway 2x Fire blocking 2x Each open floor level 8 6010 Miscellaneous Materials Miscellaneous materials not covered in other sections. 6106 Manufactured Joist System — Per Plan Truss or I-joist per plan. Install per manufacturer's directions. 6110 Interior Wall Frame — Per Plan Interior partitions to be #1 and #2 KDS with nailing per code. P.T. plate when in contact with concrete. Caulk top and bottom plates and end studs for sound walls. NOTE: Provide office partition to extend to standard ceiling. Size Spacing Typical 2 x 4 24" OC Sound Wall See plans for wall types 24" OC Plumbing Wall 2 x 4 staggered stud on 2x6 plate 24" OC 6115 Exterior Wall Frame — Per Plan Exterior walls to be #1 and #2 KDS with 2 rows of approved caulk under plates and nailing per code P.T. plate when in contact with concrete. Size Spacing 1st Floor Wall 2x6 19.2" OC 2 11d Floor Wall 2x6 24" OC Fully sealed continuous drainage plane behind exterior cladding that laps over flashing. Window and door openings fully flashed. 6120 Ceiling Framing — Per Plan Ceiling joist to be #1 and #2 KDS with nailing as per code and joist hanger where not supported from below. Size Spacing 2x4 16" 0.C. 2x6 16 "O.C. 6125 Pre - manufactured Raised Heel Roof Truss — Per Plan Roof truss to be installed with diagonal bracing per plan and in conformance with code requirements and manufacture's recommendation. All trusses will include manufacturer's engineering information. All trusses will be carefully lifted into location using manufacturer's recommendation. Truss clips to be installed at all interior walls. 7 windows installed and shimmed including all exterior trim, blocking and housewrap Vicor or equal around windows and doors, installed, but excluding roofing. Cut and frame in all chimney openings, chases, hearth cut outs, scuttle holes and related or similar work. Work includes patching subfloors, ready for underlayment. All cutting and reframing to be ready for drywall, required by the intent of the plans, specifications or documents are to be included. NOTE: All framing is to meet or exceed 2012 Energy Star Version 3.0 requirements or as applicable. See below for some general requirements. NOTE: Framers are to assist insulation installers with assuring that AIR BARRIERS are fully aligned. See section 7200 and examples below for know areas that require attention: Walls: Wall adjoining porch roof Staircase walls Double walls All other exterior walls Ceilings: Dropped ceiling/soffit below unconditioned attic Sloped ceilings All other ceilings All sill plates adjacent to conditioned space sealed to foundation or sub -floor with caulk. Foam gasket also placed beneath sill plate if resting atop concrete or masonry and adjacent to conditioned space. Install a gasket to prevent air leakage and seal all exterior wall sill plates to the sub -floor or foundation to prevent air leakage All exterior corners shall be constructed to allow access for the installation of> R -6 insulation that extends to the exterior wall sheathing. WBI default for Energy Star compliance is standard - density insulation with alternative framing techniques using three studs per corner. Insulated headers shall be minimum R -5 using continuous rigid insulation sheathing except where the framing plan indicates that full -depth solid headers is the only acceptable option because of structural requirements. Framing at windows shall be limited to a maximum of one pair of king studs and one pair jack studs per window opening to support the header and window sill. Additional jack studs shall be used only as required by code or as needed for structural support and cripple studs only as needed to maintain on- center spacing of studs. Install ladder blocking, full length 2x6 or 1x6 furring behind the first partition stud to allow for insulation to run behind interior /exterior wall intersections. Siding Labor — All labor to install siding including drip caps, step flashing, light, silcock and venting blocks and caulking as required. Finish Labor -- All labor to bring project to complete finish or as necessary including baseboard, casing, sills, aprons, built -ins, window seats, stairs, rails, wall caps, mantels, cabinets, vanities, counters, vanity tops, interior doors, door hardware, stops, bath accessories, wood closet shelving and rods, and any interior wood and wainscot or ceilings. Install underlayment per Section 6172. 6002 Carpentry Labor Miscellaneous carpentry labor specifically assigned to WBI. 6 • Install base and finish material upon prepared base. Pitch to properly drain and finish all edges with loam. See Site Design and Documents for details. Include parking lot paint striping per plan 3000 CONCRETE NOTE: Maintain caution tape or fencing barriers installed while on site. 3300 Cast in place 3301 Footings — Per Structural Plans 3302 Walls — Per Structural Plans 3303 Piers — Per Structural Plans 3304 Slabs — Per Structural Plans 3306 Other Slabs, Steps, Walks and Utility Pads — Per Civil Plans 4" (or as noted) reinforced slabs with fiber mesh continuous, graded to drain. Broom finish with tooled 4' grid. Patio slabs, porch slabs, walks, sloped > 0.25 in. per ft. away from building to edge of surface, or 10 ft., whichever is less. 3800 Concrete Cutting and Coring Allowance Saw concrete and remove debris as required. Protect against water damage. 5000 METALS 5100 Structural Steel — Per Structural Plans Metal joist hangers per plans or as required by Code. Other structural steel per plan. 5500 Metal Fabrication Decorative metal per plans. 5700 Steel Rails Per drawings and specifications. 6000 WOOD & PLASTIC 6001 Carpentry Labor Subcontracted rough and finish labor to complete structure. Include all pneumatic nails to fit your equipment. Rough Labor -- All labor to bring project to a weather tight shell with exterior doors and 5 work after C.O. are by Opal Real Estate. 2107 Tree Removal Cut down, remove and dispose of designated trees with any anticipated salvage /lumber /pulp revenues incorporated into net quoted price. Quoted price reflects any revenue from sale of timber. Stumps to be left in place at grade unless specifically indicated for removal under Excavation and such removal is required to complete the excavation work. 2110 Walk and Patio Prep Leave ample site materials for final back filling and coordinated with stone contractor. 2111 Sewer — Install storm and sanitary installation in accordance with design drawings Install new schedule 40 PVC plastic sewer line from 10' outside building and tie in to manhole provided separately by MassDevelopment at front of property per plan. Provide clear, measured as built drawings of installation. 2120 Landscape Installation Supply and install plantings per plan schedule with fertilizer, soil enhancement as needed and deep watering. Install bark mulch atop landscape fabric in all designated area. Plant materials to be watered regularly and thoroughly by owner. 2130 Water Service Water service from street to utility area, with holes and cuts sealed by piping installer using hydraulic cement or other approved method. Shut -off by plumber. Water tie -in and meter fee per Section 1200. 6" Iron 2140 Utility Trench Provide 30" deep utility trench for electric, cable, and telephone and prepare bottom of trench with 8" of sand to cover burial cable. Back fill with site material removing any large stone and restore grade. Caution tape is to be placed in each trench 12 -24" above lines. Surface flagging is to be installed for utilities. Electrician or piping installer is responsible for inspection pictures to be provide to the utility companies and Wright Builders. 2150 Foundation Drainage 4" Flexible plastic perimeter drains set in crushed stone covered m filter fabric and connected to new manhole at the infiltration system outfall, with clean-outs to grade every 100' or as needed. Cover with 3/8" stone and filter fabric before back filling. 2151 Downspout Interceptor Piping — See Site Plan 2400 Driveway Base Install gravel atop existing subsurface once loam has been removed. Prepare for finished paving. See Site Design and Documents for details. 2500 Asphalt Paving/Curb 4 2101 Survey — Civil Engineering- Building and Site, Layout ONLY 2102 Excavation, Back Fill and Finish Grade NOTE: Excavation contractor is responsible for all items and scope of work in these sections. Excavate foundation area as required by drawings, storing loam and sub -grade material separately. Prepare site for foundation, removing stumps in excavated areas. Ledge, boulder, hardpan removal is at extra cost. Back -fill with site materials, except where required for drainage and grade surface for positive run -off away from building and remove excess material. NOTE: Rewash is NOT an acceptable backfill material. Protect waterproofing during back fill. Concealed underground piping/drainage or other articles discovered during excavation to be handled at extra cost unless specifically included in prior estimate. Fill and compact under slabs to 95% in maximum one -foot lifts. Correct all back fill, if required, after settling. Footings to be on 4" of " crushed stone for capillary break or per structural drawings which ever is more. All excavation will be isolated with caution tape or fencing barriers installed and maintained by excavation contractor while on site. Open trenching will be covered or fenced. Trenching at building and excavation for porch concrete piers to be coordinated during backfill or earlier, as practical. Remove stumps. Rough grade to be relatively smooth and hole free, contoured for proper drainage. 2103 Finish Grading Per code, slope grade from the structure per site plan. Adjust final grades for drainage and proper contour, according to site plan, if available or to reasonable trade standard for proper drainage and erosion control. Screen and reuse existing loam and topsoil materials, and augment as needed for sufficient loam material to provide a minimum of 6" coverage on all disturbed areas as noted on site plan. Final loam thickness should be relatively consistent, with material substantially free of debris, and left ready for machine raking and seeding. NOTE: Spread thickness will subsequently compact when raked and prepared for landscaping. 2104 Rake, Fertilize and Seed Machine rake and hand rake finish grade surfaces as needed and hydro seed for sun/shade conditions and such starter fertilizer as is needed. 2105 Watering and Maintenance Opal Real Estate is responsible for maintaining a daily watering schedule in season to ensure proper growth after delivery of property. Seeded areas should be kept wet daily. Areas designated under permitting for erosion control typically require three mowings prior to inspection and approval. 2106 Landscape Repairs Excavation Contractor to repair previously landscaped areas damaged by construction activities by loaming, seeding and adjusting altered grades. All watering, plant materials, installation, mulch and related 3 x Wash New Windows x Clean & Wipe interior & exterior of cabinets x Broom Cleaning x Vacuum Carpets Permits and Fees x Building Permit x Gas Permit by Sub x Plumbing Permit by Sub x Electrical Permit by Sub x Fire Suppression Work Permit by Sub x Water to Curb Allowance x Water Tie In x Sewer Tie -In x 6" Water Meter Fee x Trench Permit(s) x Fire Alarm Work Permit by Sub x Electric Utility Allowance 1203 Temporary Services Provide temporary services consisting of: x Temporary toilet (Port a Potty) x Crane x Temporary warm air furnace with thermostat, see 15500 x Temporary electric service, see 16000 x Temporary Light Strings, see 16000 x Dedicated 20 AMP Circuit at each level, see 16000 2000 SITE CONSTRUCTION and DEMOLITION 2010 General Labor Miscellaneous general labor, clean-up, hauling, etc. 2100 Site Preparation See attached pricing matrix breakdown below for storm water management system and new bus stop structure installation, etc.... Bids must follow this pricing breakdown. Segment A: Drain Line A Segment B: Drain Line B Segment C: Drain Line C Segment D: Drain Line D (as if it were to connect to catch basin at Village Hill Road) Infiltration System: Smaller System Infiltration System: Larger System Demo of existing bus stop (preserve pillars /columns) Bus Stop: Installation of provided prefabricated bus stop structure. Includes excavation and concrete slab Cost to extend 6 inch waterline to lot #19 Cost to extend electric conduit to lot #19 Cubic yard cost for removal and replacement of organic soils 2 vt/ 11".0(/ FINAL Outline Specifications for Use by Wright Builders Inc. only (copyright 2012) Wright Builders, Inc. 48 Bates Street — Northampton, MA 01060 Phone — 413 -586 -8287 Fax — 413 -587 -9276 Customer Name: New Harmony Properties for Opal Real Estate Development Date: September 20, 2012 Customer Address: 48 Bates Street, Northampton, MA 01060 Phone #: 586 -8287 ext 105 Job location: The Gatehouse, Lot 18, Village Hill Rd Job Phone: NA Project Manager: Tom Lucia Foreman: TBD Base Package without custom Tenant Improvements All systems and materials are expected to meet 2012 Energy Star performance standards as applicable and current applicable Massachusetts State Building Code(s). Notice to Vendors: Wright Builders prefers to purchase products that contain tropical wood only if they are certified according to the guidelines of the Forest Stewardship Council (FSC). Please provide the country of manufacture of each product you expect to supply to us. Also please provide a list of FSC- certified products you can supply. Notice to vendors and subcontractors: Vendors and subcontractor shall provide pricing breakdown (material and labor), required company certifications and/or registrations & detailed product information at time of quotation in such a way as to comply with federal standards for tax credits and utility documentation requirements for rebates. All contractors are expected to furnish samples, MSDS, and manuals as appropriate. Set up, start up and maintenance requirements of equipment are to be provided to customer with briefing & operation instructions as needed. All products and installation are guaranteed for one year from substantial completion. All terms of Wright Builders, Inc. contract with the customer apply to all subcontractors and supplies. NOTE: Items in "italics" indicate suggestions but not yet confirmed selections by owner. 1000 GENERAL CONDITIONS 1100 General Requirements Office costs, etc. Design and Engineering provided by New Harmony Properties LLC. 1200 Non - Material Miscellaneous Purchases Permits and fees as noted, cleaning as noted, rubbish removal, general expenses, fuel, temporary power, all purchases and services not subject to Mass. State Sales Tax. Natural gas vendor fee is included. Final Cleaning 1 ' ' ' �, , . l:: it .uI 7- at.-±17 -&,- tali r ✓E::13.7MEV( OF BUILDING INSp_°c- i'IGNS C; ��E 11\1 1 � i OR 2 12 Mai ; Sire•* ' MunicipaI Building Nortarnuton, Mass_ OI060 r • Scuare Footage - Ba_erne:rt @ , 4 . 0 ; f 1 c _ _cor @ ,o X4) S P Y q,-. 3p k 1 2 Dec , per) ches d--° I I ,' a 1 0 • t (5 - 1 3 a'CrP. ter? _ ` V IbL-A kitA, 14 ir, •o oi41.1 . # , a 1) . • 84L-ti sc X , — g, _ ItIttg. • • ri • RYAN S. PE • S'IRUC ENGINEER Sc.cour(larN Cotisti Control Document ti • - . \,1 ... • • KEE-n \I - \ ST1411 ft : hi : 111‘ 1.! pro\ 1 k 111Li: 1 l.i. jeii Ik :‘.k_gl.: INLA [i u all: -n ii !LflLS IWL ;.;1. pet 4 :ttritict.1 in J. riLit :he Al-s,c0„.,:_ rilatit.! t lc:PA i:ontsol ('or.troilcd 1:ceriak. - i t i L a1d Lt.°, IcTilrej shzdi s1.113111 l he r:: Ryan 44111 •Lt .Prot'essional nLitlet,; 37 "z Ott - 1 R 1 t RA , • 28 ALDRICH STREET 0 NORTHAMPTON, MA 01060 • 1 N ()ICE 413-5t43-1 t; (4594) • FAX 411-583-HI AN Fa% 44593 0 'w► Village 11111 Gatehouse Kuhn I iu' \:ccl Ett, :t:§ Stretch I nerg} Code Reiieik t % tyt, r idclle e-in {hernial Performance of I nvelope Assemblies � t . Thermal Bridging Factor 0.078 Conductivity Thickness U Value R Value Material (BTU /h ft °F) (Inches) Inside Air Film 0.68 5/8" gypsum wall board 0.092 0.625 1.77 0.57 2x6 Framing @ 19.2" o.c., weighted 0.08 5.5 0.17 0.45 Cellulose, weighted 0.021 3.5 0.07 12.81 Closed cell spray foam, weighted 0.014 2 0.08 10.98 OSB 0.053 0.625 1.02 0.98 _Fiber cement Siding 0.142 0.787 2.17 0.46 Outside Air Film 0.17 • „.- S m - m a l l ' , q I ' • ra • e+ c ete a t Wald z , . .: . , wt� , , Thermal Bridging Factor 0.06 Conductivity Thickness U Value R Value Material (BTU /h ft °F) (Inches) Inside Air Film 0.61 5/8" gypsum wall board 0.092 0.625 1.77 0.57 2x2 Framing @ 24" o.c., weighted 0.08 1.5 0.64 0.09 Polyiso. Inusul., weighted 0.014 1.5 0.11 8.39 Continuous polyiso. Insul. 0.014 1 0.17 5.95 Concrete 0.74 6 1.48 0.68 Outside Air Film 0.17 r i 0 Copt posite R Value« ' 6 46 t t Composite U V014 Q607504 W all Ass A bo v e G C o y c Retaini W Thermal Bridging Factor 0.06 Conductivity Thickness U Value R Value Material (BTU /h ft °F) (Inches) Inside Air Film 0.61 5/8" gypsum wall board 0.092 0.625 1.77 0.57 2x2 Framing @ 24" o.c., weighted 0.08 1.5 0.64 0.09 Polyiso. Inusul., weighted 0.014 1.5 0.11 8.39 Continuous polyiso. Insul. 0.014 1 0.17 5.95 Concrete 0.74 8 1.11 0.90 Outside Air Film 0.17 e , C R Val � If, 16 69 ' M I-0 _ .,, 1, ' m= ,?,d.. r .t 4 , Composite`U Value :0.059 ; The Gate House -Lot 18 Village Hill Rd, Northampton, MA 10 -04 -12 FIRE ALARM By Others. HVAC By Others. Section 3 — Approval Requirements Hampshire Fire Protection, LLC shall obtain written approval of all acceptance testing from the Northampton Fire Department and will provide the Northampton with copies of NFPA 13 testing certificates, instruction manuals, and record drawings. 4 of 4 The Gate House -Lot 18 Village Hill Rd, Northampton, MA 10 -04 -12 Dry Pipe Sprinkler System: Heat produced from a fire melts the fusible link or glass bulb on a single sprinkler head, or group of sprinkler heads, causing the sprinkler(s) to open. The air is then exhausted from the dry system piping allowing water to enter the system piping and is then discharged from for the open sprinkler head(s) to extinguish the fire. The Fire Department may supplement the system by positioning a Fire Department pumper truck between a fire hydrant and the fire department connection. The sprinkler system water flow switch will activate upon system flow and indicates an alarm condition by sounding an electrical alarm bell located on the exterior of the building. The sprinkler(s) will continue to flow water until the water control valve is manually closed. FIRE ALARM By Others. HVAC By Others. ( 1.c) TESTING CRITERIA FIRE SPRINKLER Hampshire Fire Protection, LLC is responsible for setting up and coordinating all sprinkler system testing including a 2001b. hydrostatic test and testing of all waterflow, tamper, and alarm devices provided under this scope. All testing will be in accordance with NFPA 13, and the Massachusetts State Building Code. FIRE ALARM By Others. HVAC By Others. Section 2 — Equipment and Tools FIRE SPRINKLER Hampshire Fire Protection, LLC is responsible for providing all required equipment and tools, including but not limited to: 2001b. hydrostatic testing equipment, pressure gauges, hoses, manufacturers instructions, etc. 3 of 4 The Gate House -Lot 18 Village Hill Rd, Northampton, MA 10 -04 -12 A water flow switch is located on the wet system riser and will indicate water flow by sending a signal to the local alarm panel and activate the electric alarm bell. An alarm pressure switch is located on the dry system riser and will indicate water flow by sending a signal to the local alarm panel and activate the electric alarm bell. Quick response sprinklers are being utilized throughout the building areas. New pipe and fittings in these areas will consist of black steel & galvanized pipe and cast iron, grooved, and/or threaded fittings. The Fire Department Connection is located in the front of the building immediately outside of the riser room, and meets all requirements of the authority having jurisdiction, including size, type, location, and thread type. System design criteria is based on Light Hazard Occupancy (Ordinary hazard occupancies in Boiler Room, Fan Rooms, and Storage Rooms) and suitable for office space or other Light Hazard use as defined by NFPA -13. Wet and dry sprinkler systems are calculated to provide a density of .10 gpm per square foot over the hydraulic remote areas with an additional 100 gpm outside hose allowance added to the sprinkler demand FIRE ALARMS: By Others. HVAC: By Others. (1.b ) SEQUENCE OF OPERATION FIRE SPRINKLER Wet Pipe Sprinkler System: Heat produced from a fire melts the fusible link or glass bulb on a single sprinkler head, or group of sprinkler heads, causing the sprinkler(s) to open. The water from the water filled pipe is discharged immediately from the sprinkler head(s) to extinguish the fire. The Fire Department may supplement the system by positioning a Fire Department pumper truck between a fire hydrant and the fire department connection. The sprinkler system water flow switch will activate upon system flow and indicates an alarm condition by sounding an electrical alarm bell located on the exterior of the building. The sprinkler(s) will continue to flow water until the water control valve is manually closed. 2 of 4 ` The Gate House -Lot 18 Village Hill Rd, Northampton, MA 10 -04 -12 (1.a) BASIS ( METHODOLOGY) OF DESIGN Section 1 — Building Description Refer to Architect. Section 2 — Applicable Laws, Regulations and Standards Refer to Architect. Section 3 — Design Responsibility for Fire Protection Systems Fire Protection System: Hampshire Fire Protection, LLC 507 Southampton Rd Westfield, MA 01085 413 -642 -3287 Fire Alarms: By Others. HVAC: By Others. Section 4 — Fire Protection Systems to be installed FIRE SPRINKLER System Description: Automatic sprinkler protection is provided throughout all areas of the building in accordance with NFPA 13, 2007 edition. Owner to provide heat throughout the entire building to maintain a minimum temperature of 40 degrees Fahrenheit for all areas of the building protected with a wet pipe sprinkler system. A 6 -inch underground fire service main is capable of providing adequate water pressure and volume to the fire sprinkler system. This fire service main is connected to the city water main in the street. A 6 -inch Double Check Backflow Assembly, with indicating isolation valves, is installed immediately upon the 6 -inch water service main entrance into the building. 1 of 4 AUTOMATIC FIRE SPRINKLER SYSTEM NARRATIVE REPORT 780 CMR — 903.1.1 The Gate House -Lot 18 Village Hill Rd Northampton, MA 01060 Prepared By: HAMPSHIRE FIRE PROTECTION, LLC 507 Southampton Road Westfield, MA 01085 Tel 413 -642 -3287 Prepared For: Northampton Fire Department October 4, 2012 WRIGHT BUILDERS, INC. 41580 DATE INVOICE NO DESCRIPTION INVOICE AMOUNT DEDUCTION BALANCE 1 0 - 03 - 12 100312-323 12-323 4944.00 .00 4944.00 CHECK 1 0 - 09 -12 CHECK 41580 TOTALS 4944.00 .00 4944.00 DATE NUMBER WRIGHT BUILDERS, INC. FLORENCE SAVINGS BANK 41580 48 BATES STREET FLORENCE MA 01062 NORTHAMPTON, MA 01060 53 7168 413-586-8287 Pay: **************Four thousand nine hundred forty-four dollars and no cents DATE CHECK NO AMOUNT October 9, 2012 41580 $******4,944.00 PAY NOT VALID AFTER 90 DAYS TO THE CITY OF NORTHAMPTON TWO SIGNATUR S UIRED ON CHECKS OVER $5000.00 ORDER OF AJTRORIZE0 SIGNATURE — - «o s H 1 : 21,03 ? L6881: 0 25 005606e . t E . ....6.--..„ t ( ,: - • -: : : -- - -I 1-, ;- -. . ..-- : ---: ; --. ......--,_ : i : "..\ ._... --,-.- • - - r... ;., -. • A Eitu of Wariliamilign .... -- 3 ..: ES___27. " : 71 ZZ 31 AC:raittil .--- :I ..... .. ■C i 'IiiiiI5f . .■"..'`).. - I a t ' D EF.- !ENT OF 3 UTLD LNG INS? EC; T IC NS --0 I,- IN 1 212 ISaui SEre..& - 241 Building ........\..,:„.--..--,......--;„. r Northaum ton, Mass_ 01060 . i . .1 • Scuar e Ecatage Amcunt . . .5.0 Ea...sernerit 1st FiCcr @ SO l - ` 1 *I 1( . f i 1 - 2na 7 .- - 1.c. - .:or @ -30 . I t tI Er )-Y Yo I f l i _ 1/2 Floors, Attic, Garage, a ..0 .. _ 1 Deck, Pc.s,rc! ad- , ! - ...... t I .. 4 •S )... tiv I r.1 1 r [ f - , • t ( 9c - rt 3 ._. i TOTAL f - ------ ' .9 i f 7 • i: . -.. I( ...--7/7a-,4zti • i. ot41-.9 ._. . - , . . -. ... . :. - 1 . .. - - i . 1 . i i - 1 - • . i I . . _ - .-...: 1 • B 1M Village Hill Gatehouse Kuhn Riddle Architects Stretch Energy Code Review www.kuhnriddle.com October 1, 2012 502.4.7 Vestibules: Building entrances that separate conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self - closing devices. • All building entrances that separate conditioned spaces from the exterior have vestibules that meet the requirements of this section. • 502.4.8 Recessed Lighting: Per specifications, all recessed lighting in vestibule spaces will be IC -rated and labeled as meeting ASTM E 283 when tested at 1.57 psf pressure differential with no more than 2.0 cfiii of air movement from the conditioned space to the ceiling cavity. All recessed luminaires shall be sealed with a gasket or caulk between the housing and interior wall or ceiling covering. 502.5 Vapor Retarders The use of a vapor barrier at exterior walls that employ cellulose insulation is not recommended by cellulose insulation manufacturers. Sections 503, 504, 505, 506 and 507: o See narrative provided by selected M.E.P. contractor(s) on the energy efficiency of the mechanical and electrical systems. Village Hill Gatehouse 3 Village Hill Gatehouse Kuhn Riddle Architects Stretch Energy Code Review www.kuhnriddle.com October 1, 2012 502.4.0 Air Barriers The building envelope shall be designed and constructed with a continuous air barrier to control air leakage into, or out of the conditioned space. • Per specifications and design details the air barrier will be continuous around the building envelope with all joints taped with manufacturer's approved tape to provide a continuous air barrier at exterior walls. Additionally, a continuous air barrier membrane will be provided at the second floor ceiling, joints will be lapped and sealed as required. • 502.4.0.1 Air Barrier Penetrations The following Air Sealing has been called for in the drawings and /or specifications: • Seal all cracks and joints with caulk and joint fillers. • Caulk joint at interior between window and door unit sills and rough opening. • At Windows and Doors - Spray foam, non - expanding • Provide 4" thick closed cell spray foam coating at band joists. • Seal all wall plates top and bottom two beads per sill plate. 502.4.1 Window and Door Assemblies: The air leakage of window, skylight and door assemblies that are part of the building envelope shall be determined in accordance with AAMA/WDMA/CSA 101 /I.S.2 /A440, or NFRC 400 by an accredited, independent laboratory, and labeled and certified by the manufacturer. Window and skylight air leakage shall not exceed 0.2 cfm/ft2 at 1.57 pounds per square foot (psf) (75Pa), or 0.3 cfm/ft2 at 6.24 psf (300 Pa). Door assembly air leakage shall not exceed 0.3 cfm/ft2 for all other products at 1.57 psf (75Pa). • Proposed window and door assemblies will meet these requirements. There are no skylights. 502.4.2 Curtain Wall, • Storefront Glazing and Commercial Entrance Doors. • All storefront and commercial entrance doors will be tested for air leakage at a pressure of at least 1.57 pounds per square foot in accordance with ASTM E283. The curtain walls will not exceed the maximum leakage rate of .06 cubic feet per minute per square foot of fenestration area and the glazed swinging entrance doors will not exceed 1.00 cubic feet per minute per square foot of door area when tested in accordance with ASTM E 283. 502.4.3 Sealing of the building envelope • See the outline of air sealing requirements noted above under 502.4.0.1 502.4.4 Hot Gas Bypass limitation: • See narrative provided by selected M.E.P. contractor(s) on the energy efficiency of the mechanical and electrical systems. 502.4.5 Outdoor Air Intakes and Exhaust Openings • See narrative provided by selected M.E.P. contractor(s) on the energy efficiency of the mechanical and electrical systems. 502.4.6 Loading Docks — not provided. Village Hill Gatehouse 2 Village Hill Gatehouse Kuhn Riddle Architects Stretch Energy Code Review www.kuhnriddle.com October 1, 2012 The following Stretch Energy Code Review is based on the International Energy Conservation Code (IECC) 2009 with Massachusetts Amendments (780 CMR 115.AA). CHAPTER 5 ADVANCED COMMERCIAL ENERGY EFFICIENCY 501.2 Prescriptive Option for Buildings from 5,000 to 100,000 sq. ft. Buildings from 5,000 to 100,000 sq. ft., and additions to such buildings greater than or equal to 30% of the existing conditioned floor area where the addition has its own heating system, shall comply with the requirements in sections 502, 503, 504, 505, and 507. Compliance with section 507 requires complying with any ONE of the following prescriptive options: 1. 507.2.1 Efficient Mechanical Equipment —Please see narrative provided by selected M.E.P. contractor(s). 2. 507.2.2 Reduced Lighting Power Density — Please see narrative provided by selected M.E.P. contractor(s). 3. 507.2.3 On -Site Supply of Renewable Energy - no on -site supply of renewable energy systems at this time Compliance with section 507 does not remove the requirement to comply with any other mandatory requirements in this code. PER TABLE 502.2 - BUILDING ENVELOPE REQUIREMENTS - OPAQUE ASSEMBLIES o Per Table 502.2, Roof Insulation, Attic must be min. R38 - proposed R -Value is 50 o Per Table 502.1.2, Walls, Above Grade Mass with interior insulation must have a maximum U- factor of .085. Proposed above grade mass walls have a U- factor of .060 or better - see attached table. o Per Table 502.1.2, Walls, Above Grade, Wood Framed must have a maximum U- factor of .051. Proposed above grade wood framed wall have a U- factor of .036 or better- see attached table. o Per Table 502.1.2., Slab on Grade Floors, Unheated must have a maximum F- Factor of .54. Proposed slab on grade has an F- Factor of .36 (R -10 fully insulated slab under entire slab and edge) o Opaque doors must have a maximum U- Factor of 0.37 - proposed insulated fiberglass doors to meet a U- Factor 0.37 or better. PER TABLE 502.3 - BUILDING ENVELOPE REQUIREMENTS: FENESTRATION Framing materials other than metal with or without metal reinforcement or cladding, o U- Factor .35/ SHGC .40 — Proposed Paradigm dual glazed, low -e, argon filled, double hung and awning vinyl windows: • Insulating glass assembly: Two panes of 3/32 -inch glass with 9/16 -inch argon - filled space, solar control low -e coating applied to the 3 surface. SHGC of .36 and U -value of .28 o Per specifications and design details all storefront metal framing to achieve a U- Factor of .42 or better, all entrance doors to achieve a U- Factor of .80 or better and all storefront glazing to achieve a U- Factor of .45 or better and a SHGC of .40 or better. Village Hill Gatehouse 1 City of Northampton • a p t HA p a s — S • h. f = .; "A • Massachusetts �At/ : j ?t " DEPARTMENT O F BUILDING INSPECTIONS SI 4 "' 2 12 Main Street • Municipal Building �;: qb Mfir Northampton, MA 01060 ssx °1 M1 5 INSPECTOR Louis Hasbrouck Fax: 413 - 587 -1272 Chuck Miller Building Commissioner Phone: 413 - 587 -1240 Assistant Commissioner SECONDARY CONSTRUCTION CONTROL DOCUMENT (For professional EngineerslArchitects responsible for a portion of a controlled project) Project Title: 2— '14 a`'S!L Date: / (/// / / 7-- Project Location: 0 r.... t 1 L 1 - 4 4 `P . c t-- 2 P. Map: Parcel: Zone: I Scope of Project: �,rt,t.J m.ty at, V S/ 0 0/ LA In accordance with the Eighth edition Massachusetts State Building Code, 780 CMR Section 107.6: I C/, L 12 h17E -7 4 Mass. Registration # / Pi 4 7 being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Fire Protection [ \i Architectural [ ] Structural [ ] Mechanical [ ] Electrical [ ] Other (specify) for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory Completion of the above mentioned work. Sign = ay�d S: • of ' egistered Professional C � f,� � ��' J Day of e7n/�/F/L_ 20 /Z--- �` 7 (seal) i "„ 'WV .4 10r WRIGHT BUILDERS RECEI MEMO OCT 102012 To: Louis Hasbrouck / Chuck Miller ' Northampton Building Dept. CEPT. NORTHAMPTONOF BUILDING ,MINSPEGTA0106U u Date: 10/10/12 From: Linda / Wright Builders Re: Permitting for: New Commercial Building Gatehouse, Village Hill 11 Village Hill Road Northampton, MA Hi Louis / Chuck, Missing from this permit application are: 1) Planning Board — Major Site Plan Approval Decision — we'll be recording this on 10/11/12. 2) PB Decision (3) three conditions — all are in the works and we'll forward documentation of compliance as soon as we receive it. On the Stormwater O &M, the draft is at Doug McDonald for review & comment. 3) Water & Sewer Availabilities — applications are at the DPW 4) MEP Controlled Construction Affidavits —this project is design /build. MEP subs will provide stamped drawings and affidavits. We'll forward them to the bldg dept as soon as we receive them. As of now, Lindgren & Sharples is doing the electrical design work for M &S Electric. Plumbing, HVAC and Fire Protection will be forthcoming. 5) Property ownership by New Harmony Properties LLC — closing is expected on 11/1/12. The bus shelter work and new signage to be permitted separately. Sincerely, Linda Gaudreau NEW HOMES +WORKPLACES +DESIGN +RENOVATIONS +ENERGY RETROFITS +CONSTRUCTION MANAGEMENT 48 Bates Street, Northampton, MA 01060/413.586.8287 / Fax 413.587.9276 /www.wright- builders.com Wright Builders, Inc. RAEfi L 1 JLn1= 48 Bates Street Northampton, Ma 01060 Date 11/27/2012 'Job No. 12 -323 Attention: (413) 586 -8287 Re: Fax (413) 587 -9276 Gatehouse, Village Hill 11 Village Hill Road To: Louis Hasbrouck / Chuck Miller Northampton, MA 01060 Northampton Bldg Dept We are Sending You Attached Under Separate Cover via The Following Items: Shop Drawings Prints Plans Samples Specifications Copy of Letter Change Order a` Copies Date No. Description 1 10/9/12 $4944 Check #41580 - Building Permit Fee These are Transmitted as checked below: For approval gym. Approved as submitted Resubmit _copies for approval For your use Approved as noted � Submit copies for distribution i4 As Requested Returned for corrections i Return corrected prints For review and comment — FOR BIDS DUE PRINTS RETURNED AFTER LOAN TO US Remarks Copy to File Signed: Linda Gaudreau t Li � I - . e — Itu III c-� i{n'.raDt ri . . . i � ci — .._ _ IS�� LL -R.T MEN"i OF B ILDLNG INSFEC:TICNS . ' f gE IN�rEC T OR 212 Main S ee.t ' Municipal Building �; � • Northampton, Mass. 01060 �. . • • Scuare Fcotace • Arc cunt t 'Easement @ 01" 1st :lccr @ .50 1 2nd Ficor @ .342 . 1/2 Flccrs, Attic, Garace,34 - i Deer, Porches , I t'UC Sib g'? s . I i- • • C f X , - - r-1.4\-{ 'r-- '.. . - . ,.:- AAA-19 'i i kitArr 10? - . , • . i . • • I . 1 I • Versionl .7 Commercial Building Permit May 15. 2000 SECTION 10- STRUCTURAL PEER REVIEW (780 CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes O No SECTION 11 - OWNER AUTHORIZATION - TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT I. N eN" KM111 g ul e po Pint v ('' T WAti , as Owner of the subject property w h'(nt{ hereby authorize V . 6 Y'f - I 6 if i (-b € i-> to act on my .e alf i I afters relative to work authorized by this building permit application. -14 e 1i tL' _; >; Sigr.Cure . (ir N Date I V v r ` - ' t/V' 1 , as Owner ■ uthorized 'gent I ereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge an..elief. Signed under the pains and penalties of perjury. PA Al Q- (. U el` 1r Print Name Ariffliri 10/101 ty SigrAtur- . •wner /Agent Date SECTION 12 - CONSTRUCTION SERVICES 10.1 Licensed Construction Supervisor: Not n / Not Applicable 0 / Name of License Holder : U" PI " 1 so 6" " ,.' i VD l t Aw "' e- c t) e X / p y 0 b License Number I t Y , 0, .' 1 — , �I Pro PI 7 / /( 3 Address iiMy Expiration Date Telephone SECTION 13 - WORKERS' COMPENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes IF) No Version] .7 Commercial Building Permit May 15, 2000 SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE) 9.1 Registered Architect: Not Applicable ❑ Name (Registrant): Registration Number Address Expiration Date Signature Telephone 9.2 Registered Professional Engineer(s): F d, J ttAg. Name Area of Responsibility 2 b v 9,44-* _ t A 1 X13e ' Sr Address Registration Number Signa ;� ' / 4010 Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility • Address Registration Number Signature Telephone Expiration Date 9.3 General Contractor Not Applicable ❑ Company Name: Responsible In Charge of Construction Address Signature Telephone Version1.7 Commercial Building Permit May 15. 2000 ;ECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO : ONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE) , .1 Registered Architect: Charles Roberts Not Applicable ❑ 10107 lame (Registrant): Kuhn Riddle Architects, 28 Amity St,Amherst, MA Registration Number 09/13 ,ddress 413- 259 -1630 Expiration Date :ignature Telephone .2 Registered Professional Engineer(s): lame Area of Responsibility ,ddress Registration Number ;ignature Telephone Expiration Date lame Area of Responsibility ,ddress Registration Number ignature Telephone Expiration Date lame Area of Responsibility ,ddress Registration Number ;ignature Telephone Expiration Date lame Area of Responsibility ,ddress Registration Number ;ignature Telephone Expiration Date ■.3 General Contractor Not Applicable ❑ :ompany Name: tesponsible In Charge of Construction ,ddress ;ignature Telephone Version i . Commercial Building Permit May 15. 2000 SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE) 9.1 Registered Architect: Not Applicable 0 Name (Registrant) Registration Number Address Expiration Date Signature e I ep hone 9.2 Registered Professional Engineer(s): 14C-c E. ltc - ra cAL_ Name Area of Responsibility '-{ 35 Ce. 5 5fri OA. L-4- - 7 5 - 3 I Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date 9.3 General Contractor Not Applicable 0 Company Name: Responsible In Charge of Construction Address Signature Telephone Versionl.7 Commercial Building Permit May 15. 2000 SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE) 9.1 Registered Architect: Not Applicable ❑ Name (Registrant): Registration Number Address Expiration Date Signature Telephone 9.2 Registered Professional Engineer(s): Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date 9.3 General Contractor �� A P; 01K 1 I t � G ' Not Applicable ❑ Company Name: 1J • G I D I CIL AA fel P • (/v Responsible In Charge of Construction • ( (101 1 `f$ &t Nolu- N- 6/vPTV►J Address i / Signatur: W� Telephone t7C Proottv e g d 11>otik , Version1.7 Commercial Building Permit May 15. 2000 8. NORTHAMPTON ZONING Existing Proposed Required by Zoning This column to be f i in h\ Building Depa ent Lot Size Frontage Setbacks Front Side L: R: L: R: Rear Building Height Bldg. Square Footage Open Space Footage (Lot area minus bldg & paced parking) # of Parking S!. es Fill olumc & Location) A. Has a Special Permit /Variance /Finding ever been issued for /on the site? NO Q DON'T KNOW YES IF YES, date issued: o .49 IF YES: Was the permit recorded at the Registry of Deeds? /12(.. ( P NO DON'T KNOW 0 YES (D t 0 I � ( �-W ►i IF YES: enter Book Page and /or Document # B. Does the site contain a brook, body of water or wetlands? NO 15. DON'T KNOW (:) YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained Q Obtained Date Issued: C. Do any signs exist on the property? YES :* NO (3 IF YES, describe size, type and location: i+ V hiikret (4 1 t_ I. t-AW /J SC 1' + fi D. Are there any proposed changes to or additions of signs intended for the property ? YES 9 NO 0 IF YES, describe size, type and location: !VON (AWN Si ( rIJ — 1"0 p- Awl) Sk E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan . (7) that will disturb over 1 acre? YES NO IF YES, then a Northampton Storm Water Management Permit from the DPW is required. / t� P ( C/U f>‹, Version1.7 Commercial Building Permit May 15, 2000 SECTION 4- CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE Interior Alterations ❑ Existing Wall Signs ❑ Demolition❑ Repairs ❑ Additions ❑ Accessory Building ❑ Exterior Alteration ❑ Existing Ground Sign ❑ New Signs ❑ Roofing ❑ Change of Use ❑ Other ❑ Brief Description Enter a brief description here. D- Q Of Proposed Work: kr�i�j '��0 • s..�- M (X CoMMt"(jl / .N' � �V SECTION 5 - USE GROUP AND CONSTRUCTION TYPE •� USE GROUP (Check as applicable) j CONSTRUCTION TYPE A Assembly A -1 ❑ A -2 ,�[ A-3 ❑ 1A ❑ A-4 ❑ A -5 ❑ 1B ❑ B Business 1°L 2A ❑ E Educational ❑ 2B I ❑ F Factory ❑ F -1 ❑ F -2 ❑ 2C ❑ H High Hazard ❑ 3A ❑ I Institutional ❑ 1 -1 ❑ 1 -2 ❑ 1 -3 ❑ 3B ❑ M Mercantile 1Z 4 ❑ R Residential ❑ R -1 ❑ R -2 ❑ R -3 ❑ 5A ❑ S Storage ❑ S -1 ❑ S -2 ❑ 5B ( ❑ • U Utility ❑ Specify: r /�- M Mixed Use ` Specify: A , .S. 6 - A ( Nef' !1�` - l /1 i �Ci - 1, f ' S Special Use ❑ Specify: COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS, ADDITIONS AND /OR CHANGE IN USE A Existing Use Group: /•'A' Proposed Use Group: .Sc 0 ' Existing Hazard Index 780 CMR 34): Proposed Hazard Index 780 CMR 34): SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY • Floor Area per Floor (sf) st 151 Z,) 1 Sr 2nd 3 d 2nd r.-(11 3 I 3rd 4 4m Total Area (sf) Total Proposed New on ucti (sf) p Total Height (ft) t 4; Total Height ft 7. Water Supply (M.G.L. c. 40, § 54) 7.1 Flood Zone Information: 7.3 Sewa•e II 'sposal System: Public Private ❑ Zone Outside Flood Zon' Municipal ►.i On site disposal system❑ t Versionl.7 Commercial BuildinPermit May 15. 2000 - aefortTentik4.sorly r- City of Northampton 3tatutiofPerniit RECEIVED uilding Department Curb G Drh nay 212 Main Street SeWP' epticA it _ ;° 0212 Room 100 WafetANettAvailatgitY N rthampton, MA 01060 TworSeha of Shucturat , Piles •hon: 41 - 587 -1240 Fax 413- 587 -1272 PiottSite Piens OEPZ OF BUILDING INSPECTIONS NORTHAMPTON MA 01060 Other Specify APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, CHANGE THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 - SITE INFORMATION C7 A ' eitl �s' G / I 1 I (A "L ii 1.1 Property Address: This section to be completed by office 11 V�4 i( (I+)t"_ - M 4 Map Lot Unit N �1 0 1a p 1 1 �,, V N y' / I / k Zone Overlay District M A 3 g r/ trr ( o 9 Elm St. District CB District SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT 2.1 Owner of Record: f Y i . a .,0 ` l ON PR.• .),0, ` ' Li l ��� Liz RA-re-c ^ 0 P' Name (Print) / ` I j _ Current Mailing Address: S110 i 9 1p Signature w _ . Telephone • 2.2 Authorize e A. en . 1, k p Luck Yg A s - J), ivbR -I4prb ri ( -4 ) e Name (Print) Current Mailing Address: 7 M g. , Signature Telephone SECTION 3 (MATED CONSTRUCTION COSTS Item Estimated Cost (Dollars) to be Official Use Only completed by permit applicant 1. Building (a) Building Permit Fee 2. Electrical (b) Estimated Total Cost of v Construction from (6) 3. Plumbing (° 5'( 3 Building Permit Fee 4. Mechanical (HVAC) 1 ( 1, i 0 5. Fire Protection 2'7 L i (93 6. Total = (1 + 2 + 3 + 4 + 5) 1. t I (0 LI L 'QC( 9 Check Number L(l6 1 ii9y7 ` This Section For Official Use Only !' 1 Building Permit Number Date -r i (78 i - 1 3 Issued factri Signature: Building Commissioner /Inspector of Buildings Date File # BP- 2013 -0601 APPLICANT /CONTACT PERSON WRIGHT BUILDERS ADDRESS/PHONE 48 Bates St NORTHAMPTON (413) 586-8287 (11"6) PROPERTY LOCATION 11 VILLAGE HILL RD - THE GATEHOUSE MAP 38A PARCEL 107 001 ZONE PV(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid l Permit Filled out Fee Paid tt ACW 0 -R444..4 � �� 1/77 2 / 6 Tvpeof Construction: CONSTRUCT 2 STORY MIXED COMMERCIAL BUILDING (8,241 SQ FT) New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/ Statement or License 16370 3 sets of Plans / Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INFOR PRESENTED: / /Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay • /Z /Iz, iZ Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information. 11 VILLAGE HILL RD - THE GATEHOUSE BP- 2013 -0601 GIS #: COMMONWEALTH OF MASSACHUSETTS Map:Block: 38A - 107 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: NEW COMMERCIAL BUILDING BUILDING PERMIT Permit # BP- 2013 -0601 Project # JS- 2013- 000664 Est. Cost: $1164297.00 Fee: $4969.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: WRIGHT BUILDERS 16370 Lot Size(sq. ft.): 38027.88 Owner: NEW HARMONY PROPERTIES LLC Zoning: PV(100)/ Applicant: WRIGHT BUILDERS AT: 11 VILLAGE HILL RD - THE GATEHOUSE Applicant Address: Phone: Insurance: 48 Bates St (413) 586 -8287 (116) Workers Compensation NORTHAMPTONMA01060 ISSUED ON:3/12/2013 0:00:00 TO PERFORM THE FOLLOWING WORK:CONSTRUCT 2 STORY MIXED COMMERCIAL BUILDING (8,241 SQ FT) POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House # Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace /Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 3/12/2013 0:00:00 $4969.00 212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272 Louis Hasbrouck — Building Commissioner