17D-020 DWD ENGINEERING, INC. 5 MICHAEL ROAD EAST BRIDGEWATER, MA 02333 (508) 378 -9602 FAX (508) 378 -2922 October 7, 2012 Mr. Louis Hasbrouck - Building Commissioner City of Northampton Building Department Puchalski Municipal Building 212 Main Street Northampton, MA 01060 RE: Capacity of Existing Roof to Support Proposed Solar Panel Array -King Residence 109 Straw Avenue - Florence, MA Dear Mr. Hasbrouck, This office reviewed the above referenced site for the purpose of determining whether the existing roof structure was capable of supporting an additional load introduced by the proposed solar panels. The following is a summation of our observations. There are a total of 17 solar panels proposed for the southern facing section of roof. These panels have a footprint of 64.5" x 38.7° and weigh 44.1 pounds each. This translates into a unit weight of 2.5 psf per panel. The support rails have a minimal unit weight (0.5 psf). The roof structure consists of exterior sheathing over 2x6 rafters at 24" on center spanning approximately 13 feet (horizontal dimension). The 8 Edition of the Massachusetts State Building Code (Residential) states that Northampton is in a 40 psf ground snow load. Assuming the rafters have properties of Spruce- Pine -Fir #2, they can safely support a total load of 22 psf. This includes a dead load of 10 psf and a snow (live) load of 12 psf which is less than the actual live load of 43 psf (40 +3). As such it is the recommendation of this office that 2x8 rafters be sistered (or equally spaced between the existing rafters) at the solar panel locations. The rafters should start within one foot from the outside wall and extend to within one foot of the ridge. They should be nailed to the existing rafters with 10d nails spaced at 4" on center located 2" from the bottom and 2" from the top. By doubling the rafters the live load that they can support is 47 psf in addition to a 10 psf dead load which will be greater than the actual live load of 43 psf. Based on the field observations and the information noted above it is my professional opinion that the existing roof is structurally sound and able to support the additional weight of the solar panels. If you have any questions concerning this letter or if I can be of further assistance, please do not hesitate to contact me. Si erely, Domeni' W DeAn P.E. Prestderit ,' Cc: Real Goods Solar ,.. ' =' 1 'ry ,r, CS6P 2351240/245/250/255M Electrical Data E, s h,.,,.,,04,-,„..,,,,,,,, ; . , . .. . °� , ,% a :', Temperature Characteristics Nominal Maximum Power (Pmax) 235W 240W 245W 250W 255W r— Pmax - 0.45 % /t7 Optimum Operating Voltage (Vmp) 30.1V 30.2V 30.3V 30,4V 30.5V Optimum Operating Current(Imp) 7.82A 7.95A 8.09A 8.22A 8.35A 'Temperature Coefficient Voc 0.35 %/t Open Circuit Voltage (Voc) _ 37.2V 37.3V 37.4V 37,5V 37.7V _ Ise 0.060 %PC Short Circuit Current (Isc) 8.34A 8.46A 8,61A 8.74A 8,74A Normal Operating Cell Temperature 45±2t Module Efficiency _ 14.61% 14.92% 15.23% 15.54% 15.85% Operating Temperature - 40C- +85C Performance at Low Irradiance Maximum System Voltage 1000V (IEC) /600V UL Industry leading performance at low irradiation Maximum Series Fuse Rating 15A environment, +95.5% moduleefficiency from an Application Classification Class A irradiance of 1000w /m to 200w/m Power Tolerance 0 - +5W (AM 1.5, 25r) Under Standard Test Conditions (STC)of Irradiance of 1000W /m',. spectrum AM 1.5 and cell temperature of 25c . Eng Draw . ; fi t Y y r,Tt h 'r k# 'n 'ZrS - �P. i.:: W " ' r :r = Nominal Maximum Power (Pmax) 170W 173W 177W 180W 184W Optimum Operating Voltage (Vmp) 27.5V 27.5V 27.6V 27.7V 27.8V — T `' Optimum Operating Current(Imp) 6.18A 6.29A 6.40A 6.51A 6,62A LI 11 I I I Open Circuit Voltage (Voc) 34.1V 34.2V 34.3V 34.4V 34.6V Short Circuit Current (Isc) 6.75A 6.85A 6.97A 7.O8A 7.18A Under Normal Operating Cell Temperature, Irradiance of 800 W /m', spectrum AM 1,5, amblenttemperature 200. I I I wind speed 1 m/e , Mechanical Data Cell Type Mono - crystalline 156 x 156mm, 2or 3 Busbars I 1 Cell Arrangement — 60 (6 x10) I I I I 1 Dimensions 1638 x 982x 40mm (64.5x 38.7 x 1.57in) I I I Weight 19kg (41.9 lbs) Front Cover 3.2mm Tempered glass Frame Material Anodized aluminium alloy .. I 1 1 J -BOX IP65, 3 diodes 982 Cable 4mm /12AWG(UL), 1000mm Connectors MC4 or MC4 Comparable Standard Packaging (Modules per Pallet) 24pcs Module Pieces per container (40 ft. Container) 672pcs (40'HQ) d -V Curves (CS6P -250M) i t ,.. '. '_..... -.' Section A -A ■ i 35 0 1_ 2 j — ■ Y P• i O ¢p O ,, i �� I _i t � \ 7/ JGa�tUf �'�u'I�IVX `Specifications Included in this datasheet are subject to changewithout prior notice. About Canadian Solar Canadian Solar Inc. is one of the world's largest solar Canadian Solar was founded in Canada in 2001 and was companies. As a leading vertically - integrated successfully listed on NASDAQ Exchange (symbol: CSIQ) in manufacturer of ingots,wafers, cells, solarmodules and November 2006. Canadian Solar has module manufacturing solar systems, Canadian Solar delivers solar power capacity of 2.05GWand cell manufacturing capacity of 1.3GW. products of uncompromising quality to worldwide customers. Canadian Solar's world class team of professionals works closely with our customers to provide them with solutions for alltheir solar needs. Headquarters 1 545Speedvale Avenue West Guelph 1 Ontario N1K 1E6 1Canada Tel +1 519 8371881 Fax +1 519837 2550 Inquire.ca @canadiansolar.com www.canadiansolar.com EN -Rev 3.50 Copyrighto 2012Canadian Solar Inc. CanadianSolar « . « ... J « « « CS6P ` 4 ` ` 235/240/245/250/255M « « « • • • « • • e « « « j CS6P isa robust solarmodule with 60solar cells. .= 4* • 1 These modules can be used foron -grid solar tr • « g applications. Our meticulous design and production techniques ensure a high - yield, long -term 9 9 1' performance for everymodule produced. Our rigorous quality control and in -house testing facilities guarantee Canadian Solar'smodules meet the highest quality standards possible. Best Quality • 235 quality control points in module production Key Features • EL screening to eliminate product defects • High module efficiency upto 15.85% • Current binning to improve system performance • Accredited Salt mist /Ammonia resistant • Positive powertolerance: 0 — +5W Best Warranty Insurance • Robust frame to up to 5400 Pa load • 25 years worldwide coverage • • Anti- reflective with self - cleaning surface 100% warranty term coverage • Providing third party bankruptcy rights • • Outstanding performance at low irradiance Non - cancellable • Immediate coverage ▪ High energy at LowNOCT- • Insured by3 world topinsurance companies Comprehensive Certificates • Backed By Our New 10/25 Linear PowerWarranty • IEC 61215, IEC 61730, IEC61701 ED2, UL1703, Plus our added 25 year insurance coverage KEMCO, CEC Listed, CE, JET and MCS too • IS09001: 2008: Quality Management System s7 Added Vague • ISO/TS16949:2009: The automotive quality 913% (( Fr Om W arranty management system 80% , • 15014001:2004: Standards for Environmental management system 5 10 15 20 25 • QC080000 HSPM: The Certification for • 10 yearproduct warranty on materials and workmanship Hazardous Substances Regulations •25 year linearpower output warranty • OHSAS 18001:2007 International standards for occupational health and safety • Reach Compliance t �. E c SGS ' p www.canadiansolar.com 8 G00I:?S 32 TAUGWONK SPUR, 812 STONINGTON, CT 06378 (860) 535-3370 Module Specs Inverter1 Specs MECHANICAL COMPONENTS: Item Descriptions Part Nam bar Quantity T CANADIAN SOLAR CSeP -245M Enphsse Energy 11216- 60- 2LL -S22 ROOF MOUNT M ATEMAL8 STC Rating 245.0 W Nominal V 240 V SUB -ARRAY 1 0 FTC Rating 218.8 W Max W 280 W UniRac Rails V as 30.3 V Max. W 215 W SM Rai 208" CAR 310208C 7� l 8.09 A Startup Voltage 22 V SM SR ICE BAR SERRATED CLR 303001C 4 d V cr 37.4 V Mn . V 22 V SM BIDCLAMP D. W.MDW, CLR 3020040 12 N Z l 861 A Max V 38 V SMM0CLAMP,ABCDK,HDW.CLR 302101C 28 Q iii A Mounting Brackets 5 Height 64.5 n Max V 45 V 5 ' Width 38.7 h Max. l„. 15 A SM L -FOOT SERRATW VeHDW, CLR 3040000 34 te K m Area 17.3 f1x Max. I 0.90 A Lag Screw, Hex Head, 18-8 SS 5/18" x 3-1!2" Length 1011023 34 co CD Weight 44.1 Ibs CEC Efficiency 96 0 % Flat Washer_ M8_ 18-8 SSTL_ 1000pk 111398 34 Temp. Coef. (Voc) -0 3500 %PC ANCHOR BRACKET - Eco- Fasten Compression Rate_ Square_ 2" x 2" ECO - - 34 Temp Coef (Vmp) - 0.6500 %?'C FLASHING - Eco-Fasten Flashng 8' z 12 "_ ANmnum_ Matte Black ECO -GF1 -ELK -812 34 0o i d System Calw /ations Currents D.C. M ax.: Mod be x 1.25 8.81A x 1.25 = 10,76A LL D.C. Operating : Mod. imp r. 8.09A = 8.09 A j E ~ Source Current : Mod. 5c x 1.25 x 125 0 N o T m 881A z 125 0 1.25 = 13.45A 0� c Q o � A.C. Output : Inverter 8c 8 1.25 6 Inverter Oty CC U - A < u 0.9A x 1.25 x 17 = 19.13A y6 rut 65 fs U s. Wire Sizing a) ip a D.C.: Wire See Allow able Amp x Temp. Derate x Fe Derate 812 30A x 0 82 x 1 = 24.80 A ) 0 - A.C. (A) : Wre Size e Allow able Amp z. Tenp. berate x Derate 612 30A x 082 x 1 = 2400 A = A.C. (B) : Ntre See Allow able An x Temp. Derate x Fe Derate 810 40A x 087 x 1 = 34.80A Voltages JEP D.C. M ax.: Mod. Voc x Temp A x Temp Coef Voc ° ° ,,° 6 -20°C 37 4V a 45 x 0 0035 = 43.3 V CR ▪ D.C. Operating : Module Vmp .- 30.3V = 30.3 V - 2012 - - NTS SYSTEM CALCS PV -E02 FOR CONSTRUCTION y — Equipment Location 2 32 TAUGWONK SPUR, Al2 (E) 200A Service Panel (Interior) STONINGTON, CT 06378 (N) RGS (860) 535 -3370 — Equipment Revenue Location Meter 1 (Interior) . CS6P Zp c,M �� (E) Utility Meter (Exterior) B. C st�t d C °tP° C N O Z a O' z ►• (26 �et@ — _ O r• 2'X6 > - ua cc _m /� m 30' / t] 9' / 19._9.. �/— 1, m © Attachment Profile r 1' Scale: 3/4" = 1' -0" ' 12' -6" 15' Ji = E J O >, m N p W __.. i__ 0 0/) Y ¢ c ;41 tY v m m 2 — (E) Vent (Typ.) t - m m d Ground WEEB & c > p° o E o a Mod Clip - o O LI (N) PV Array — N d Unirac Solarmount (17) Canadian Solar CS6P -245M CC o Bracket w/ L -foot modules w/ Enphase M215- 60- 2LL -S22 t. microinverters s Module (TYP.) r .\ Green Fasten GF1 -CP -SQ Rooftop a 0! 5/16 "x 3 5"S.S. Lag Bolt " — � O G' w/ 2.5 "Minimum Penetration JEP FO" @ Sealed w/ Approved Sealant CR 2X Quantity of Attachments = 34 @ 48" O.C. (Limited by Structural/Wind Characteristics) — z • Maximum Unirac Span = 5' (Maximum Allowable Cantilever is 1/3 The Max Rail Span) 2012 -10 -04 • Racking and Attachment Unirac Solarmount with Eco Fasten Green Fasten W/ CP -SQ Bracket And O Attachment Detail Aluminum Flashing attached with 5/16 X 3.5" SSTL Lag Screws 3/32" = 1' - 0" • UniRac SolarMount Rails require 1 in. Spacing between Modules and an extra 3 in. beyond end Module p Scale: 1" = 1' -0" edges when using the Top Clamp Method. SYSTEM LAYOUT • UniRac Requires one thermal expansion gap for every run of rail greater than 40' iiii. V. • Array Installed according to the UniRac SolarMount Code - Compliant Installation Manual ver. 227.3, �" Pub 110616 -1cc. June 2011 w / , • Attachment Locations, If shown, are approximate. Final adjustment of attachment location may be P V —A02 necessary depending on field conditions. Al) attachments are staggered amongst the framing members. s T FOR CONSTRUCTION — Equipment Location 2 (E) 200A Service Panel (Interior) (N) RGS Revenue Meter (Interior) s (7) O D 'R — Equipment Location 1 — (E) Residence 3 S T C T 0 6 TON INGTO INGTON, R 063778 3 (E) Utility Meter (Exterior) (860) 535 - 3370 c / 156' / g a N N / 86'b' / m o / 16' / Z O N _ _ — — I 04 d \ — 4' -10" I o cc Q I 1 1 54' CD - 111111111111 - . I 60' r ■� ■� I = E 0 a) N i E v > m o co cC 0 Y 3 Q m o m � ° • — 0 O p o c 0 p o - o ,20 o — — I N L / 20' / / 64' -6" / /____ 66 / _. �, / 156' / ... JEP .. F.E. CR 2012 -10 -04 1/16" = 1 _ 0 „ (E) Driveway — (N) PV Array — — (E) Pool (E) Vegetation — (17) Canadian Solar CS6P -245M N SITE PLAN modules w/ Enphase M215- 60- 2LL -S22 microinverters — (E) Detached Garage (E) Property Line (Typ.) — 1 + �E W P, ' PV -AO 1 5 I Residential Roofmount Photovoltaic System DC Rating: 4.165 kW 0 G �D Douglas King TAUGWONK SPUR, 109 Straw Ave 32 NGTON, CT 06378 Florence, MA 01062 (860) 535-3370 Jurisdiction: City of Florence C 0 Scope of Work: General Notes: Sheet List a Real Goods Solar will install a 4.165 kW Grid -tied Photovoltaic System totaling 1. System follows any /all Fire Code Setbacks per Ordinances of the City Sheet No. Sheet Title o (17) Canadian Solar CS6P -245M modules with (17) Enphase Of Florence. Z M215- 60- 2LL -S22 Inverter, Flush mounted on a Composition roof and 2. All projects will comply with the Ordinances of the City Of Florence. PV-000 COVER O Interconnected via Breaker in the Main Service Panel. 3. Construction Hours: 7am -8pm Monday- Friday, 9am -8pm Saturday. No time on Sunday or legal Holidays. PV -A01 SITE PLAN, w 4. Product Data Sheets will be included. PV -A02 SYSTEM LAYOUT m Equipment Specifications: 5. Rooftop penetrations will be completed and sealed per code by a o Module: (17) Canadian Solar CS6P -245M licensed contractor. PV -E01 ELECTRICAL DIAGRAM Inverter 1: (17) Enphase M215 -60- 2LL -S22 6. All Photovoltaic modules will be tested and listed by a recognized PV -E02 SYSTEM CALCS Racking: Unirac Solarmount laborato m laboratory. Attachment Flashing: Eco Fasten Green Fasten W/ CP -SQ 7. Certifications will include UL1703, IEC61646, IEC61730. Bracket And Aluminum Flashing 8. A continuous ground will be provided for the Array and for all Photovoltaic Equipment. Roof Specifications: 9. DC Wiring will be run in metal conduit or raceways within enclosed Root 1: spaces in a building. - -. �.," • Composition 10. Conduit, Wire systems and Raceways wit be located as close as 2 "x 6" Rafter @ 24" O.C. possible to ridges, hips. and outside walls. Pitch: 11. Conduit between Sub Arrays and to DC Combiners /Disconnects will c Azimuth th:190° use guidelines that minimize the total amount of conduit by taking the = E O N r, • shortest path. E m m o 12. Space Requirements for electrical equipment will comply with NEC p (n �" °' � ¢ o E Site Specifications: Article 110. fY o Y a Occupancy: Single Family Dwelling 13. Equipment grounding wit be sized in accordance with Table 250.122. �` ' m m - u cr. Design Wind Speed: 90 MPH 14. Connectors that are not readily accessible and that are used in the - C F 65 u u • Exposure Category: C circuits operating at or over 30V AC or DC shall require a tool for r T ` N o 0 0 'o Roof Height: 30' opening and are required to be marked "Do not disconnect under a • Ground Snow Load: 40 PSF load" or "Not for current interru tin m t LL a p g ", per 690.33 (c) & (e). N 4. 15. All signage to be placed in accordance with local building code. . E Ct • All Work to be in Compliance with: 16. Signs or Directories will be attached to the electrical equipment or City of Florence Building Code located adjacent to the identified equipment. 4 ,11 Mechanical Code 17. Signs should be of sufficient durability to withstand the environment. • City of Florence Mec City of Florence Electrical al Co 18. Any plaques will be metal or plastic with engraved or machine printed City of Florence Plumbing Code letters, or electro- plating, in a red background with white lettering, a ` City of Florence Fire Code minimum of 3/8" height and all capital letters. _ .,a JEP 2011 National Electrical Code .,.�. „, MA 780 CMR, 8th Edition 1 CR - including 2/4/11 revisions to Tables R301.2(4) & R301.2(5) - a r. ASCE /ANSI 7 -05 Minimum Design Loads for Buildings and Other h e = 2012 -10 -04 • Structures .” - = re s NTS COVER t - PV -000 L • ..'.GOOD 32 TAUGWONK SPUR, Al2 STONINGTON, CT 06378 (860) 535 3370 Module Specs Inverter 1 Specs MECHAMCAL COMPONENTS:Item Descriptions v Part Num be Quantity • T CANADIAN SOLAR CS6P -245M Brphase Energy U215- S0- 2LL -S22 ROOF MOUNT MATERIALS STC Rating 245.0 W Nominal V,, 240 V SUB- ARISSY 1 0 FTC Rating 2166 W Max. W 260 W UnIRac Rails 'EL V en 30.3 V Max. W„ 215 W SM Rai 208" CLR 3102080 7 i l 8.09 A Startup Voltage 22 V SM SPLICE BAR SERRATED CLR 303001C 4 SM ENDCtAMP D, W/HDW, CLR 302004C 12 Z 0 V �� 37.4 V Mn. V,.., 22 V Z I 861 A Max V r1p 38 V SMMDQAMP,ABCDK,HEM/CLR 3021010 28 Q Height 64.5 in Max . V, 45 V Anchors & Mounting Brackets W 5 Vvl dth 38.7 in Max. Lc 15 A SM L -FOOT SERRATE) WHEW. CLR 3040000 34 CC 2 Area 17.3 •x Max. Inc 0.90 A Lag Screw., Hex Head, 18-8 SS, 5118" x 3-1:2" Length 1011023 334 4 6 Weight 44.1 as CEC Efficiency 96.0 % Flat Washer_ M8_ 18-8 SSTL_ 1000lpk 111398 , Temp. Caef. (Voc) -0.3500 %PC ANCHOR BRACKET - Eco- Fasten Compression Pate_ Square 2" x 2" ECO - CR r SO 34 Temp. Coef. (Vmp) - 0.4500 %NC FLASHING - Eco-Fasten Fasting 8" x 12 "_ Aturnnum_ Matte Black ECO- GF1- BLK-812 34 °7 d System Calculations Currents D.C. M alt.: Mod. 6c x 1.25 8.61A x 1.25 = 10.76A 0.C. Operating : Mod. Imp 8.09A = 8.09 A 7 E CV Source Current: Mod. 8c x 1.25x 125 0 y co co 8 x 1.25 x 125 = 1345A >' °i m o A.C. Output : Inverter lac x 125 x Inverter Qty 0 U # Q co 0.9A x 125 x 17 = 19.13A O m ° m C > 0 o aE o Wire Sizing m 8 o a D.C. Wire See Allow able Amp z Temp. Derate x Fit berate 'a L LL 812 30A x 0 82 x 1 = 24.60 A _ d A.C. (A) : %Ire See Mow able Anp x. Tenp. Derate x Fit Derate 612 30A x 082 x 1 = 24.60 A A.C. (B) : Wtre Ste Allow able Anp x Temp. Derate z Fa Derate li 910 40A x 0.87 x 1 = 34-80A Voltages JEP O.C. M ax.: Mod. Vac x Temp 6 z Temp Coef Voc " "" rtg -20°C 37 4V x 45 x 0.0035 = 43.3 V CR D.C. Operating : Module Vmp 2012 -10 -04 30.3V = 30.3 V NTS SYSTEM CALCS PV -E02 FOR CONSTRUCTION =' GOODS . — Equipment Location 2 32 TAUGWONK SPUR, 812 (E) 200A Service Panel (Interior) STONINGTON, CT 06378 (N) RGS Revenue Meter (Interior) (860) 535 - 3370 0 . — Equipment Location 1 C56P- 2kbx " �,, (E) Utility Meter (Exterior) 0 a Co mPo s � uo � . cri 2 p OG z lac O Ra T C_ in .. 2•x > w cc N al .I' 30' / al / 9' " / 19. -9•. 4L/- 1. s., m CD Attachment Profile y 1. Ce Scale: 3/4" = l'-0" 1 _- .. 1 12' -6" 15• \ E T m ° CO O Y ¢ o rn ¢ m cc 2 m m 2 # (E Vent (Typ.) 76 rn m u Ground WEEB & C. O> p ° ar i o Module Clip :O O LL o- (N) PV Array — ) L Unirac Solarmount (17) Canadian Solar CS6P -245M d Bracket w/ L -foot modules w/ Enphase M215- 60- 2LL -S22 micro(nverters Module (TYP.) Green Fasten GF1 -CP -SQ Rooftop s, 5 /16 "x 3.5 "S.S. Lag Bolt \ 24 . G- w,! 2.5 "Minimum Penetration .. JEP @ Sealed w/ Approved Sealant 2x 6 Ra het CR • Quantity of Attachments = 34 @ 48" O.C. (Limited by Structural/Wind Characteristics) „„ r • Maximum Unirac Span = 5 (Maximum Allowable Cantilever is 1/3 The Max Rail Span) 2012 - 10 - 04 • Racking and Attachment: Unirac Solarmount with Eco Fasten Green Fasten W/ CP -SQ Bracket And -., C Attachment Detail Aluminum Flashing attached with 5/16 X 3.5" SSTL Lag Screws 3/32" = 1• - 0•' • UniRac SolarMount Rails require 1 in. Spacing between Modules and an extra 3 in. beyond end Module N Scale: 1" = 1' -0" edges when using the Top Clamp Method. f� SYSTEM LAYOUT • UniRac Requires one thermal expansion gap for every run of rail greater than 40' I E • Array Installed according to the UniRac SolarMount Code - Compliant Installation Manual vet. 227.3, .� "- Pub 110616 -1cc, June 2011 w /� • Attachment Locations. If shown, are approximate. Final adjustment of attachment location may be PV -A02 necessary depending on field conditions. All attachments are staggered amongst the framing members. S • FOR CONSTRUCTION — Equipment Location 2 r "- (E) 200A Service Panel ()nterior) (N) RGS Revenue Meter (Interior) ( 0 0 D S 32 TAUGWONK SPUR, Al2 — Equipment Location 1 — (E) Residence STONINGTON, CT 06378 (E) Utility Meter (Exterior) (860) 535 / 156 / 5 — .5 / 1 A 86-6" / m / 16' / z o , (7) w I c4 ru 4'- 10 1 " \ rn 1 ,. 1 >. 0 I > rt < I ---- — -- 2. 54' CtS ( 75 I E cp N CD , I E TA ›, co ; 0 . ...— I o u) .G , : o < - 65 ______ ,= , , .,„.,.,. ., — 1 c‘:, z . ; , .> a) o EL , E 1 - -- - .S' / 20' - - Li - .3 / 64'-6" / "___ 66'-6" / -- / 156' / JEP CR .1' ..., 2012-10-04 .. 1/16" = 1 (E) Driveway — (N) PV Array — — (E) Pool (E) Vegetation — (17) Canadian Solar CS6P-245M modules w/ Enphase M215-60-2LL-S22 1.4 SITE PLAN microinverters — (E) Detached Garage (E) Property Line (Typ.) — „Alb ill/ E Vil PA ' PV—AO 1 s • Residential Roofmount Photovoltaic System y . _ cT 0 (-) o s . DC Rating: 4.165 kW Douglas King 32 TAUGWONK SPUR, 512 109 Straw Ave STONINGTON, CT 06378 Florence, MA 01062 (860) 535 -3370 Jurisdiction: City of Florence O Scope of Work: General Notes: Sheet List Real Goods Solar will install a 4.165 kW Grid -tied Photovoltaic System totaling 1. System follows any /all Fire Code Setbacks per Ordinances of the City Sheet No. Sheet Title o (17) Canadian Solar CS6P -245M modules with (17) Enphase Of Florence. Z M215- 60- 2LL -S22 Inverter, Flush mounted on a Composition roof and 2. All projects will comply with the Ordinances of the City Of Florence. PV -000 COVER 0 Interconnected via Breaker in the Main Service Panel. 3. Construction Hours: 7am -8pm Monday- Friday, 9am -8pm Saturday, rn PV -A01 SITE PLAN > No time on Sunday or legal Holidays. ui ° 4. Product Data Sheets will be included. PV -A02 SYSTEM LAYOUT Equipment Specifications: 5. Rooftop penetrations will be completed and sealed per code by a o Module: (17) Canadian Solar CS6P -245M licensed contractor. PV -E01 ELECTRICAL DIAGRAM Inverter 1: (17) Enphase M215 -60- 2LL -S22 6. All Photovoltaic modules wit be tested and listed by a recognized PV -E02 SYSTEM CALCS CO Racking: Unirac Solarmount laboratory. Attachment Flashing: Eco Fasten Green Fasten W/ CP -SQ 7. Certifications wit include UL1703, IEC61646, IEC61730. g Bracket And Aluminum Flashing 8. A continuous ground will be provided for the Array and for all K Photovoltaic Equipment. Roof Specifications: 9. DC Wiring will be run in metal conduit or raceways within enclosed spaces in a building. . .,� Roof 1: Composition 10. Conduit, Wire systems and Raceways will be located as close as " &'s 2"x 6" Rafter 1 24" O.C. possible to ridges, hips. and outside walls. : Pitch : 11. Conduit between Sub Arrays and to DC Combiners /Disconnects will c Azimuth :190° use guidelines that minimize the total amount of conduit by taking the - . c E 0 y w shortest path. . E m E 12. Space Requirements for electrical equipment will comply with NEC pO Y ¢' o m Site Specifications: Article 110. - a Occupancy: Single Family Dwelling 13. Equipment grounding will be sized in accordance with Table 250.122. � ` 'cp m m 2 at Design Wind Speed: 90 MPH 14. Connectors that are not readily accessible and that are used in the - O N O o Exposure Category: C circuits operating at or over 30V AC or DC shall require a tool for ' r N p o o m o Roof Height: 30 opening a a re required to be marked "Do not disconnect under. , -p ° • o u a x Ground Snow Load: 40 PSF load" or "Not for current interrupting ", per 690.33 (c) & (e). :S:ai , N L 15. All signage to be placed in accordance with local building code. . 0_ All Work to be in Compliance with: 16. Signs or Directories will be attached to the electrical equipment or � = City of Florence Building Code located adjacent to the identified equipment. 17. Signs should be of sufficient durability to withstand the environment. 1 City of Florence Mechanical Code 18. Any plaques will be metal or plastic with engraved or machine printed .7 _ City of Florence Electrical Code letters, or electro- plating, in a red background with white lettering, a City of Florence Plumbing Code minimum of 3/8" height and all capital letters. : —. City of Florence Fire Code f JEP 2011 National Electrical Code i. - „..,.., MA 780 CMR, 8th Edition - CR - including 2/4/11 revisions to Tables R301.2(4) & R301.2(5) _ ASCE /ANSI 7 -05 Minimum Design Loads for Buildings and Other „," - s 2012 -10 -04 Structures - NTS COVER r , PV -000 R ty 1; GOODS i October 11, 2012 City of Northampton Building Department 212 Main Street, Room 100 Northampton, MA 01060 Hello, I have enclosed a building permit application, applicable fee and supporting documents for a residential solar installation in your town. Please let me know if anything else is required to approve our permit. Once the permit is ready please use the enclosed self - addressed stamped envelope to send to the foreman. Thank you and let me know if you need anything else, Kim Hendel Permit Specialist Real Goods Solar Formerly Alteris Renewables Inc. 32 Taugwonk Spur Rd. Al2 Stonington CT 06378 Ph 860- 535 -3370 Fax 413 - 683 -2225 Kimberly.hendel@realgoods.com 32 Taugwonk Spur Rd Al2 Stonington CT 063/ 860 -535 -3370 v,vww.ROalGoodsSolar.cc 3/8 -16 X 3/4" SS HEX BOLT 3/8 -16 I •4 01 SS FLANGE NUT (St 4� 6105-T5 ALUMINUM ■ 1, 4 0 � 000 D 0 0 SolarMount/SunFrame ©2008 UNIRAC, INC. 2" Aluminum 1411 BROADWAY BLVD NE ALBUQUERQUE, NM 87102 USA Serrated PHONE UNIRAC.COM 505.242.6411 L -Foot UNIRAC- 310068 S: AAuto Cad Detail Library \CAD \ UNIRAC — 310068_2in Serrated L. Doot.dwg, 6/24/2008 1: 4a: 32 rM SoLARMOUNT Technical Datasheets :r U N 1 RAC SolarMount Beams Part No. 310132C, 310132C -B, 310168C, 310168C -B, 310168D 310208C, 310208C-B, 310240C, 310240C-B, 310240D, 410144M, 410168M, 410204M, 410240M 1 Properties Units SolarMount SolarMount HD Beam Height in 2.5 3.0 Approximate Weight (per linear ft) ptf 0.811 1.271 Total Cross Sectional Area in 0.676 1.059 Section Modulus (X -Axis) in 0.353 0.898 Section Modulus (xis) in 0.113 0.221 Y A Moment of Inertia (X -Axis) in^ 0.464 1.450 Moment of Inertia (Y -Axis) in° 0.044 0.267 Radius of Gyration (X Axis) in 0.289 1.170 Radius of Gyration (xis) in 0.254 0.502 Y A 1.728 -- • SLOT FOR T-BOLT OR SLOT FOR T -BOLT OR 1 /4" HEX HEAD SCREW I. - -'--j 1 /" HEX HEAD SCREW SLOT FOR 2X SLOT FOR BOTTOM CLIP BOTTOM CLIP IL 2.500 i 3.000 � * 1.316 1111 SLOT FOR L11_ .385 SLOT FOR %" HEX BOLT 3f" HEX BOLT . 387 1.207 -0- .750 1.875 Y Y +1 A ■ X t►X SolarMount HD Beam SolarMount Beam Dimensions specified in inches unless noted 4 ! t �� ,It, P v ';' 3x t °` „. GREENFASTEN'' PRODUCT GUIDE - GF -1 :4, . American Wood Council Lag Bolt Pull-Out Values s1 ,ii� r � � � , . Jr” f ill V''' - .- Lag pull -out (withdrawal) capacities (Ibs) in typical roof lumber (ASD) Lag screw specifications Specific � . ' 5/16" shaft* Gravity g� It g Gravity per inch thread depth _'k c Douglas Fir, Larch .50 266 w L o 4 ' 6 - Douglas Fir, South .46 235 t 1,A a, Engelmann Spruce, lodgepole Pine .46 235 n :� v (MSR 1650 f & higher) 1. V� 4s ° Hem, Fir, Redwod (close grain) .43 212 i ' ° Hem, Fir (North) .46 235 42 1. Thread - x. i , � "" Southern Pine .55 307 De th ° 1 Spruce, Pine, Fir 42 205 P o 1 Spruce, Pine, Fir .50 266 y : (E of 2 million PSI and higher z " r o grades of MSR and MEL) p'. ` e m M faratittp Fri' vrAtrow "ilia W P � F � at C s x 4 i z . O W { i C EcoFast< Solerr) AIt content protected uncle; copyright. All nghts reserved 02 , 16! 1 ! See.6- Phil a r ` ° ', .1 GREENFASTEN`" PRODUCT GUIDE - GF-I Specifications . PART I - GENERAL 1.3 SUBMITTAL B. Fasteners (may be supplied by others) to be !m �l A. Submit manufacturer's written specifications. compatible with chosen roof application and . I.I SUMMARY B. Submit standard p roduct cut sheets. meet specified pull out values as shown in load a - - ' _� A. WORK INCLUDES test data. C. Submit installation instructions. i �'Y I I. GreenFasten solar attachment bracket that ' �H #~ attaches direct) to the roof deck D. Submit product specific load test data, showing C. Base flashing is .032 gauge aluminum embossed y 2. Provide appropriate bracket and fasteners ultimate and allowable load values. to accept EPDM bushing. ' for the roof s stem. D. Bushing is EPDM. y 1.4 QUALITY ASSURANCE B. RELATED SECTIONS Installer to be experienced in the installation of E. Stainless steel bonded washer is 302 stainless I. Section 07600: Flashing and Sheet Metal specified roofing material and snowguards for no less and EPDM. " ` . 2. Section 07500: Roofing than 5 years in the area of the project. g ect. ...itiviia Y P 1 3. Division (:Administrative and procedural 2.3 FINISH - Mill Finish requ 1.5 DELIVERY / STORAGE / HANDLING A. Bracket is mill finish aluminum 4. Division7:Thermal and Moisture Protection Inspect material upon delivery. Notify manufacturer 4 ; B. Base flashing (choose one) VIA , within 24 hours of any missing or defective items. Keep 4 h i , 1.2 SYSTEM DESCRIPTION material dry, covered, and off the ground until installed. 1. Mill Finish Alit, �. ,, = A. COMPONENTS: �: w fla in I. GreenFasten system consists of aluminum 2. Black - kynar painted - PART 2 - PRODUCTS Y , g with integral g EPDM bushing g and one 3. Dark Bronze kynar painted ° bonded stainless steel and EPDM washer. v 2.1 MANUFACTURER ' E 2. Fasteners � A be of metal compatible with aluminum 0 289 Harrel St Morrisville,VT 05661 � _ _ GreenFasten components. 5,) (877) 859 - 3947 3.1 EXAMINATION f` B. Fasteners should be selected for ' i c- www.ecofastensolar.com. A. Substrate: Inspect structure on which brackets l 't t.e a compatibility with the roof deck are to be installed and verify that it will withstand :1 4 C. Fastener strength should exceed or be equal 2.2 MATERIALS any additional loading that it may incurred. Notify 4 to that of the allowable load of the system. 4 3 �~ ��. Z' A. Attachment Bracket General Contractor of any deficiencies before $� v See test data at www.ecofastensolar.com f _ i ,0 6000 Series Aluminum (choose one) installing EcoFasten Solar brackets. 3. Sealant (if required by roof manufacturer): B. Verify that roofin g material has been installed 3l t E to be roof manufacturer approved. 1. F -1 1 1 1 , 4 1 U 4. Aluminum attachment bracket 2. L- 101 -3" v 3 L- 102 -3" � " j a , 3.2 INSTALLATION r, B. DESIGN REQUIREMENTS: 4. CP -R 4 °; 1. Bracket spacing to be recommended by 5. CP -SQ A. Comply with architectural drawings and project engineer. 6. SL- 102 -6" project engineer's recommendations for location of system. Comply with Manufacturer's written R . co 2. Install a minimum of one fastener assembly. 7. Z 101 installation instructions for installation and layout. n 0 3. It is import to design new structures or 8. Custom o assess existing structures to make sure that §, - they can withstand retained loads. E ' .; - `i O w EcoFasten Solari'. All content protected .u'der cocyoght M r ghts reserved. 02,16 I 1 Sec.5- 1 tt AV - 1 4 ::: 141, 11 - I! , ''.• ' 4" ^ 0 P. i ., i .k! ig , ; ..11 14' ' ' ..',14 '41.ki GREENFASTEN'm PRODUCT GUIDE - GF- 1 i , t tit' ir Bracket Options - CP-SQ Ili 10 L • . gi s L' ° 41 '41,1, ' A' t - v-i• - - tittlollt't .4 .375 , .008 '' , O I-4/11 ,„ 3 ft/44.4401 „tali* '1.44 1 1 1.5: 1 1 04.1 g46 1 ,14 1 f 2.000: .025 „.. it'4.14 T . 3 4i , 44. ii4.4 `tti v ;44: * L ,5 I .: .i.ij r ',..?.,' Z '4 : ts,' fa.; ,.',_ ',#,- -1,.... , ,,,• , 1;*.z t ca- til` 6, _. " 2.000 = .025 1 . , . 7, ,,=, , tA , - IN r .*." , •11, 1,, Oti-Z ,Vta r ' kr? IC, l o' N- I; .377-.010 THRU I .875 + .010 X 82 NEAR SIDE Li.... 0 Compression Plate 2" X 2" Mill Aluminum ? / EcoFaster Solar";, Ai content protected ■rd copyrght All , Ights , eser, , d 02 16 I 1 Sec.4-4 i4, It I lgi" i I l'il GREENFASTENTM PRODUCT GUIDE — GF-I GFI-L812 F314.11,111 .,.,..,..,:.:„ .... ,..., 41-4e "Ail I Ve0 '' 'ii' g ' ,. h ` 'I 41-,111, • , - ' 61—.----- — 8.000 - .005 ---0-- - R 38 -1 .032 re kl‘f.) Ar it 14. eilkt:, A 1 '44, , k , lp , 1 ist*A1 lilt l'itlg:1:!:' uj ' z, .882.01 . . '..n i 4 :rIIV- 7 .;:-4 ;',X• - , lk4H1-1.iii 1200 tql / :11 4t,'N'17-. C) , i 4-414.i.lfr!...1 !''',t l :K1:41. t f,t 144 iz.,43-Itl . - .125 , i . 4.,„ -,:i. . .,.,,, -; t'ss 41 ,,..-, ,,..i l.-'! , ,,- Cl t TZ44;i142:414t, 6 1 1 2,_ . ...- 1 --- - t 1 :44 , 11.5Virsilltil - t s ---=*- 3.00 -2 .125 --p-- I E 1 ,--- 4.00 .125 —- .26 4 .011-- f—• -atf 44:z t'alg 4:41 sr '‘ize0'11- g; 1.•--1--•*-- - .05 . Ififfliii o? L°71 '-'. ( . n - ! , 0 ,:*" gt . -/.1 ,3 . Finish Options R ,:=..-Ni-, , ,...g.,, f :,-;,-. , i BLK = Matte Black :- x: ....--t .„, ,-. LY] BRZ = Medium Bronze • MLL = Mill Finish . : 0 EcoFasten Solar:1'1. AU cortent protected Qrder copynght 411 , ghts , eseed 02, 16 '1 I Sec.4-2 E ° , GREENFASTEN PRODUCT GUIDE — 1 a Exploded Product GF- V I • t Fy i : 0 12-fit ;� ft e 44/..._k410641111 , 4 1 1 1:10 '1'iiI44).i.frf1114414' :g P r , ;41 , 4114 , 4f1IN TA v z� -� 4 y Z� i E i k L � i *Note: Numbers correspond with B.O.M, Sec. 3- I i , Ea •F -- te ' r Sc nr' At/ content proteced .ivde' copy'tht All (;fits reserved 02, 6 "1 I Sec. 1- SoLARMOUNT Technical Datasheets :PUN I RA C SolarMount Beam Connection Hardware SolarMount L -Foot Part No. 304000C, 304000D • L -Foot material: One of the following extruded aluminum alloys: 6005 - T5, 6105 -T5, 6061 -T6 --'"" u • Ultimate tensile: 38ksi, Yield: 35 ksi • F Clear o Dark Anodized L -Foot we i g ht: va ba on height: —0.215 Ibs (98g) ,/� • Allowable and design loads are valid when components are Bea �- ! assembled with SolarMount series beams according to authorized - Bolt UNIRAC documents i L -Foot • For the beam to L -Foot connection: • Assemble with one ASTM F593 %' -16 hex head screw and one 0 :,;;,•'; errated ASTM F594 % "serrated flange nut Flange Nu • Use anti -seize and tighten to 30 ft-Ibs of torque l e ' Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third -party test Y results from an IAS accredited laboratory A NOTE: Loads are given for the L -Foot to beam connection only; be P. X sure to check load limits for standoff, lag screw, or other attachment method ■ 3.01 Applied Load Average Safety Design Resistance 3X St OT F00 Direction Ultimate Allowable Load Factor, Load Factor, 'i+ KAA0"`"' Ibs (N) lbs (N) FS Ibs (N) 0 x r 20� Sliding, Z± 1766 (7856) 755 (3356) 2.34 1141 (5077) 0.646 Tension, Y+ 1859 (8269) 707 (3144) 2.63 1069 (4755) 0.575 Dimensions specified in inches unless noted Compression, Y- 3258 (14492) 1325 (5893) 2.46 2004 (8913) 0.615 Traverse, X± 486 (2162) 213 (949) 2.28 323 (1436) 0.664 3 4 SOLARMOUNT Technical Datasheets d' U N I RAC SolarMount Mid Clamp Part No. 302101C, 302101D, 302103C, 302104D, 302105D, 3021060 w�''` Bolt Mid clamp material: One of the following extruded aluminum : - . alloys: 6005 -T5, 6105 -T5, 6061 -T6 Mid w `w..._ • la •e Nu Ultimate tensile: 38ksi, Yield: 35 ksi Clamp "�.. • Finish: Clear or Dark Anodized vw., � Mid clamp weight: 0.050 Ibs (23g) • Allowable and de loads are valid when components are assembled according to authorized UNIRAC documents Values represent the allowable and design load capacity of a single mid clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated • Assemble mid clamp with one Unirac 1 /:' ..20 T -bolt and one %%20 ASTM F594 serrated flange nut Beam • Use anti -seize and tighten to 10 ft-Ibs of torque • Resistance factors and safety factors are determined according to part 1 section 9 of the 2005 Aluminum Design Manual and third- party test results from an IAS accredited laboratory Applied Load Average Allowable Safety Design Resistance 1ooD Direction Ultimate Load Factor, Load Factor, an enraaxes Ibs (N) lbs (N) FS Ibs (N) m Tension, Y+ 2020 (8987) 891 (3963) 2.27 1348 (5994) 0.667 ' . Transverse, Z± 520 (2313) 229 (1017) 2.27 346 (1539) 0.665 Y Sliding, X± 1194 (5312) 490 (2179) 2.44 741 (3295) 0.620 ► X Dimensions specified in inches unless noted SolarMount End Clamp Part No. 302001C, 302002C, 302002D, 302003C, 302003D, 302004C, 3020040, 302005C, 302005D, 302006C, 302006D, 3020070, 302008C, 302008D, 302009C, 3020090, 302010C, 302011C, 302012C • End clamp material: One of the following extruded aluminum alloys: 6005 -T5, 6105 -T5, 6061 -T6 :oft Ultimate tensile: 38ksi, Yield: 35 ksi ,,,.✓' • Finish: Clear or Dark Anodized • End clamp weight: varies based on height: -0.058 Ibs (26g) d Clamp • Allowable and design loads are valid when components are Serrated j assembled according to authorized UNIRAC documents Flange Nut • Values represent the allowable and design Toad capacity of a single end clamp assembly when used with a SolarMount series beam to retain a module in the direction indicated • Assemble with one Unirac % " -20 T -bolt and one' / " -20 ASTM F594 serrated flange nut Be ( ,,; • Use anti -seize and tighten to 10 ft-lbs of torque " • Resistance factors and safety factors are determined according to T part 1 section 9 of the 2005 Aluminum Design Manual and third - Y ,11 party test results from an IAS accredited laboratory 'k N, • Modules must be installed at least 1.5 in from either end of a beam •X is Applied Load Average Allowable Safety Design Resistance 1411'`""" ._ Direction Ultimate Load Factor, Loads Factor, i Ibs (N) Ibs (N) FS Ibs (N) 0 VASES , Tension, Y+ 1321 (5876) 529 (2352) 2.50 800 (3557) 0.605 T"iaW[ss 1, Transverse, Z± 63 (279) 14 (61) 4.58 21 (92) 0.330 Sliding, X± 142 (630) 52 (231) 2.72 79 (349) 0.555 Dimensions specified in inches- unless -noted 2 SOLARMOUNT Technical Datasheets :I U N I RAC SolarMount Technical Datasheet Pub 110818 -ltd V1.0 August 2011 SolarMount Module Connection Hardware 1 Bottom Up Module Clip 1 Mid Clamp 2 End Clamp 2 SolarMount Beam Connection Hardware 3 L -Foot 3 SolarMount Beams 4 SolarMount Module Connection Hardware SolarMount Bottom Up Module Clip Part No. 302000C Washer • Bottom Up Clip material: One of the following extruded aluminum Bottom (hidden.s= - alloys: 6005 -T5, 6105 -T5, 6061 -T6 t° Up Clip " ` no -` • Ultimate tensile: 38ksi, Yield: 35 ksi • F inish: C lear Anodized -` • Bottom Up Clip weight: —0.031 Ibs (14g) Beam /Bolt A llowable and design loads are valid when components are . ,001 assembled with SolarMount series beams according to authorized UNIRAC documents *..,..., • Assemble with one' /4 "-20 ASTM F593 bolt, one'/ " -20 ASTM F594 serrated flange nut, and one '/4" flat washer Use anti -seize and tighten to 10 ft-Ibs of torque • Resistance factors and safety factors are determined according to ,�" part 1 section 9 of the 2005 Aluminum Design Manual and third - `' party test results from an IAS accredited laboratory • Module edge must be fully supported by the beam * NOTE ON WASHER: Install washer on bolt head side of assembly. DO NOT install washer under serrated flange nut Applied Load Average Allowable Safety Design Resistance Direction Ultimate Load Factor, Load Factor, Ibs (N) Ibs (N) FS Ibs (N) 0 Tension, Y+ 1566 (6967) 686 (3052) 2.28 1038 (4615) 0.662 Y � Transverse, X± 1128 (5019) 329 (1463) 3.43 497 (2213) 0.441 — t . x Sliding, Z± 66 (292) 27 (119) 2.44 41 (181) 0.619 Dimensions specified in inches unless noted 1111 DWD ENGINEERING, INC. 5 MICHAEL ROAD EAST BRIDGEWATER, MA 02333 (508) 378 -9602 FAX (508) 378 -2922 October 7, 2012 Mr. Louis Hasbrouck - Building Commissioner City of Northampton Building Department Puchalski Municipal Building 212 Main Street Northampton, MA 01060 RE: Capacity of Existing Roof to Support Proposed Solar Panel Array -King Residence 109 Straw Avenue - Florence, MA Dear Mr. Hasbrouck, This office reviewed the above referenced site for the purpose of determining whether the existing roof structure was capable of supporting an additional load introduced by the proposed solar panels. The following is a summation of our observations. There are a total of 17 solar panels proposed for the southern facing section of roof. These panels have a footprint of 64.5" x 38.7" and weigh 44.1 pounds each. This translates into a unit weight of 2.5 psf per panel. The support rails have a minimal unit weight (0.5 psf). The roof structure consists of exterior sheathing over 2x6 rafters at 24" on center spanning approximately 13 feet (horizontal dimension). The 8 Edition of the Massachusetts State Building Code (Residential) states that Northampton is in a 40 psf ground snow load. Assuming the rafters have properties of Spruce- Pine -Fir #2, they can safely support a total load of 22 psf. This includes a dead load of 10 psf and a snow (live) load of 12 psf which is less than the actual live load of 43 psf (40 +3). As such it is the recommendation of this office that 2x8 rafters be sistered (or equally spaced between the existing rafters) at the solar panel locations. The rafters should start within one foot from the outside wall and extend to within one foot of the ridge. They should be nailed to the existing rafters with 10d nails spaced at 4" on center located 2" from the bottom and 2" from the top. By doubling the rafters the live load that they can support is 47 psf in addition to a 10 psf dead load which will be greater than the actual live load of 43 psf. Based on the field observations and the information noted above it is my professional opinion that the existing roof is structurally sound and able to support the additional weight of the solar panels. If you have any questions concerning this letter or if I can be of further assistance, please do not hesitate to contact me. cerely, le , , DomeniooW, Dei rr ge President Cc: Real Goods Solar :'f The Commonwealth of Massachusetts _ Department of Industrial Accidents >4 Office of Investigations _ 600 Washington Street Boston, MA 02111 www.mass.gov/dia Workers' Compensation Insurance Affidavit: Builders /Contractors /Electricians /Plumbers Applicant Information Please Print Legibly Name ( Business /Organization /Individual): Alteris Renewables, Inc. Address: 32 Taugwonk Spur, Unit A -12 City /State /Zip: Stonington, CT 06378 Phone #: (860) 535 -3370 Are you an employer? Check the appropriate box: Type of project (required): 1. © I am a employer with 120 4. ❑ I am a general contractor and I 6. ❑ New construction employees (full and/or part-time).* have hired the sub - contractors 2. ❑ I am a sole proprietor or partner- listed on the attached sheet. I 7• ❑ Remodeling ship and have no employees These sub - contractors have 8. ❑ Demolition working for me in any capacity. workers' comp. insurance. 9. ❑ Building addition [No workers' comp. insurance 5. ❑ We are a corporation and its required.] officers have exercised their 10.0 Electrical repairs or additions 3. ❑ I am a homeowner doing all work right of exemption per MGL 11.0 Plumbing repairs or additions myself. [No workers' comp. c. 152, §1(4), and we have no 12.0 Roof repairs insurance required.] t employees. [No workers' comp. insurance required.] 13.0 Other solar panels *Any applicant that checks box #1 must also fill out the section below showing their workers' compensation policy information. t Homeowners who submit this affidavit indicating they arc doing all work and then hire outside contractors must submit a new affidavit indicating such. Contractors that check this box must attachcd an additional sheet showing the name of the sub - contractors and their workers' comp. policy information. I am an employer that is providing workers' compensation insurance for my employees. Below is the policy and job site information. Insurance Company Name: National Union Fire Ins. Co. Policy # or Self -ins. Lic. #: WC13978927 -CA Expiration Date: 01/01/13 Job Site Address: 109 Straw Avenu City /State /Zip: Florence, MA 01062 Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to $1,500.00 and /or one -year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do hereby certify unde the pains ndpenalti of perjury that the information provided above is true and correct. Signature: 'L Date: 1 0l I d1 1 Phone #: (860) 535 - 3370 (`((( Official use only. Do not write in this area, to be completed by city or town official City or Town: Permit/License # Issuing Authority (circle one): 1. Board of Health 2. Building Department 3. City /Town Clerk 4. Electrical Inspector 5. Plumbing Inspector 6. Other Contact Person: Phone #: SECTION 8 - CONSTRUCTION SERVICES 8.1 Licensed Construction Supervisor: Not Applicable ❑ Name of License Holder : Dan McLean 105675 License Number 481 Kennedy Drive, Leeds, MA 01053 7/22/13 Address Expiration Date f � 413- 588 -2252 Signature Telephone 9. Registered Home improvement Contractor: Not Applicable ❑ Alteris Renewables dba Real Goods Solar 162709 Company Name Registration Number 32 Taugwonk Spur, A -12, Stonington, CT 06378 4/6/13 Address Expiration Date 4 ct 6419 Telephone 860-535-3370 SECTION 10 WORKERS' COMPENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes No ❑ 11. - Home Owner Exemption The current exemption for "homeowners" was extended to include Owner- occupied Dwellings of one (1) or two(2) families and to allow such homeowner to engage an individual for hire who does not possess a license, provided that the owner acts as supervisor. CMR 780, Sixth Edition Section 108.3.5.1. Definition of Homeowner: Person (s) who own a parcel of land on which he /she resides or intends to reside, on which there is, or is intended to be, a one or two family dwelling, attached or detached structures accessory to such use and/ or farm structures. A person who constructs more than one home in a two -year period shall not be considered a homeowner. Such "homeowner" shall submit to the Building Official, on a form acceptable to the Building Official, that he /she shall be responsible for all such work performed under the building permit. As acting Construction Supervisor your presence on the job site will be required from time to time, during and upon completion of the work for which this permit is issued. Also be advised that with reference to Chapter 152 (Workers' Compensation) and Chapter 153 (Liability of Employers to Employees for injuries not resulting in Death) of the Massachusetts General Laws Annotated, you may be liable for person(s) you hire to perform work for you under this permit. The undersigned "homeowner" certifies and assumes responsibility for compliance with the State Building Code, City of Northampton Ordinances, State and Local Zoning Laws and State of Massachusetts General Laws Annotated. Homeowner Signature SECTION 5- DESCRIPTION OF PROPOSED WORK (check all applicable) New House ❑ Addition ❑ Replacement Windows Alteration(s) igi Roofing IT Or Doors 0 Accessory Bldg. ❑ Demolition ❑ New Signs [El] Decks [M Siding [0] Other [izj Solar Brief Description of Proposed Work: Installation of a 4.1b5kW roof mounted solar array using 17 Canadian Solar CS6P -245M modules, 17 Enphase M215- 60- 2LL -S22 inverters, and all associated electrical work. Alteration of existing bedroom Yes X No Adding new bedroom Yes X No Attached Narrative Renovating unfinished basement Yes X No Plans Attached Roll - Sheet 6a. If New house and or addition to existing housing. complete the following: N/A a. Use of building : One Family Two Family Other b. Number of rooms in each family unit: Number of Bathrooms c. Is there a garage attached? d. Proposed Square footage of new construction. Dimensions e. Number of stories? f. Method of heating? Fireplaces or Woodstoves Number of each g. Energy Conservation Compliance. Masscheck Energy Compliance form attached? h. Type of construction i. Is construction within 100 ft. of wetlands? Yes No. Is construction within 100 yr. floodplain Yes No j. Depth of basement or cellar floor below finished grade k. Will building conform to the Building and Zoning regulations? Yes No . I. Septic Tank City Sewer Private well City water Supply SECTION 7a - OWNER AUTHORIZATION - TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT Douglas King , as Owner of the subject property hereby authorize Alteris Renewables dba Real Goods Solar to act on my behalf, in all matters relative to work authorized by this building permit application. see signed authorization form 'elk 0 1 !)- Signature of Owner Date Alteris Renewables dba Real Goods Solar , as Owner /Authorized Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge and belief. Signed under the pains and penalties of perjury. Kim Hendel , ,, i Print Name , 4 94 ( , 6,,,i4 , Signature of Owne4gent M Date Section 4. ZONING All Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information Existing Proposed Required by Zoning This column to be filled in by N/A N/A Building Department Lot Size Frontage Setbacks Front Side L: R: L: R: Rear Building Height Bldg. Square Footage Open Space Footage (Lot area minus bldg & paved parking) # of Parking Spaces Fill: (volume & Location) A. Has a Special Permit /Variance /Finding ever been issued for /on the site? NO 0 DON'T KNOW Q YES IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO 0 DONT KNOW 0 YES 0 IF YES: enter Book Page and /or Document # B. Does the site contain a brook, body of water or wetlands? NO 0 DON'T KNOW Q YES Q IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained © Obtained ® , Date Issued: C. Do any signs exist on the property? YES © NO Q IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property ? YES © NO ( ) IF YES, describe size, type and location: E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan that will disturb over 1 acre? YES 0 NO IF YES, then a Northampton Storm Water Management Permit from the DPW is required. De{artmentuse onty Fk c, x c City of Northampton Status ofPe Building Department urbC t `i f Pe r mt t 1 5 ZOl 212 Main Street /$ A b t Room 100 Wet 1t Ave ebthty ° _ pT. BUILDING N�FEcT�ONS Northampton, MA 01060 Two ets ot` tr uctur a t Plan s,�. fJOaTP r"" • ne 413 -587 -1240 Fax 413 - 587 -1272 �Pialli Other Spy i APPLICATION TO CONSTRUCT, ALTER, REPAIR, RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING SECTION 1 - SITE INFORMATION 1.1 Property Address: This section to be completed by office 109 Straw Avenue Map Lot Unit Florence, MA 01062 Zone Overlay District Elm St. District CB District SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT 2.1 Owner of Record: Douglas King 109 Straw Avenue, Florence, MA 01062 Name (Print) Current Mailing Address: 413 - 586 -7585 see signed authorization form Telephone Signature 2.2 Authorized Agent: // _ j �t t��# / IAA frill 6 ,/ e $ d � ) 11 L � cc1$ J 6 L f ,s�JkW�,hlhv < s p i,4- A' J a, s4,0, (J ,7Y) crc 3 7s Name (Print) ( Current Mailing Address: ✓) t , ,�.,u e E2 860 -535 -3370 Signature Telephone SECTION 3 - ESTIMATED CONSTRUCTION COSTS Item Estimated Cost (Dollars) to be Official Use Only completed by permit applicant 1. Building 4,000 (a) Building Permit Fee 2. Electrical 18,000 (b) Estimated Total Cost of Construction from (6) 3. Plumbing Building Permit Fee 4. Mechanical (HVAC) 5. Fire Protection �► 6. Total = (1 + 2 + 3 + 4 + 5) 22,000 Check Number 1�UC2 1,0 a This Section For Official Use Only Date Building Permit Number: Issued: Signature: Building Commissioner /Inspector of Buildings Date A. File # BP- 2013 -0451 APPLICANT /CONTACT PERSON ALTERIS RENEWABLES INC DBA REAL GOODS SOLAR INC ADDRESS/PHONE 32 TAUGWONK SPUR RD UNIT Al2 STONINGTON (860) 535 -3370 0 PROPERTY LOCATION 109 STRAW AVE MAP 17D PARCEL 020 001 ZONE URB(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out a Od Fee Paid Typeof Construction: Install 4.165kW roof mounted solar array New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/ Statement or License 105675 3 sets of Plans / Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INF ATION PRESENTED: Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission _ Permit DPW Storm Water Management dic - . ' '. • it elay _Ie ",...r.dir /d ,9 y--- Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information. 109 STRAW AVE BP- 2013 -0451 GIS #: COMMONWEALTH OF MASSACHUSETTS Map:Block: 17D - 020 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: SOLAR ELECTRIC SYSTEM BUILDING PERMIT Permit # BP- 2013 -0451 Project # JS- 2013- 000708 Est. Cost: $22000.00 Fee: $132.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: ALTERIS RENEWABLES INC DBA REAL GOODS SOLAR INC 105675 Lot Size(sq. ft.): 9583.20 Owner: KING DOUGLAS J & ELIZABETH A Zoning: URB(100)/ Applicant: ALTERIS RENEWABLES INC DBA REAL GOODS SOLAR INC AT: 109 STRAW AVE Applicant Address: Phone: Insurance: 32 TAUGWONK SPUR RD UNIT Al2 (860) 535 -3370 0 Workers Compensation STONINGTONCT06378 ISSUED ON:10/31/2012 0:00:00 TO PERFORM THE FOLLOWING WORK: Install 4.165kW roof mounted solar array POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House # Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace /Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Icy i /i i at W/ � 21 Ma Street, P one (413) 587 -1240, Fax: (413) 587 -1272 Louis Hasbrouck — Building Commissioner