Loading...
32C-013 (6) D. Install Attic Insulation Shield BEND ALL TABS INWARD 90° WARNING! Fire Risk. DO NOT allow loose materials or TO MAINTAIN CLEARANCE insulation to touch vent. Hearth & Home Technologies AND PREVENT INSULATION Inc. requires the use of an attic shield. FROM FALLING INSIDE The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation. BEND 3 TABS Attic shields must meet specified clearance and be se- OUTWARD TO cured in place. FASTEN TO CEILING Flat Ceiling Installation REMAINING TABS • Remove one shield from box. INWARD 90 DEGREES TO MAINTAIN NOTICE: Cut previously installed batt insulation to make INSERT 3 CLEARANCE room for the attic insulation shield. SCREWS • Wrap shield around pipe if pipe is already installed in area to be insulated. • Match the three holes in each side and fasten with three screws to form a tube. • Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop. Figure 8.5 Attic Insulation Shield • Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop. E. Installing the Optional Heat- Zone -Gas Kit • Bend all tabs inward 90° around the top of the shield. • Remove the knockout from the fireplace and discard it These tabs must be used to prevent blown insulation (see Figure 8.6). from getting between the shield and vent pipe, and to • Center the duct collar around the exposed hole and maintain air space clearance. attach it to the fireplace with 3 screws. Note: Do this BEFORE final positioning of fireplace. • Determine the location for the air register /fan housing assembly. Vaulted Ceiling Installation Reference the Heat - Zone -Gas kit instructions for the • Remove one shield from box. remaining installation steps. NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield. • Cut the attic insulation shield (if application is for vaulted ► ceiling) to fit your ceiling pitch. Snip cut edge to recreate 'e 4. 1 in. bend tabs all the way around the bottom. • Wrap shield around pipe if pipe is already installed in 1k 4 ;) l �. area to be insulated. • Match the three holes in each side and fasten with three screws to form a tube. r; O 0 (I/ • Bend three tabs on the bottom of the shield outward to HEAT - ZONE -GAS d" ATTACHES HERE allow attachment to the ceiling firestop. • Bend the remaining bottom tabs inward 90° to maintain a the air space between the pipe and the shield. Set the 0 shield on the ceiling firestop and attach to the firestop. • • Bend all tabs inward 90° around the top of the shield. ° 1 9 O. 0 These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to Figure 8.6 Heat Zone Knockout maintain air space clearance. 38 Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 C. Install the Ceiling Firestop A ceiling firestop MUST be used between floors and attics. • DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever injill the vent penetrates a ceiling /floor (see Figure 8.3). A iii ATTIC ABOVE • SLP pipe only - Frame opening 9 in. x 9 +/'� 1 in. (229 mm x 229 mm) whenever the vent I II 1 penetrates a ceiling /floor (see Figure 8.3). I 1 1 • Frame the area with the same sized lumber 1 1 A as used in ceiling/floor joist. • The ceiling firestop may be installed above or . "441144% below the ceiling joists when installed with a ' �' . /— attic insulation shield. It must be under joists ' � .' 41111 1 between floors that are not insulated. Refer �1 to Figure 8.4. � • Secure with three fasteners on each side. 4----- A WARNING! Risk of Fire! DO NOT pack insu- lation around the vent. Insulation must be kept back from the pipe to prevent overheating. I PIPE A I DVP 10 in. (254 mm) SLP 9 in. (229 mm) "1 $1,, $14 Figure 8.3 Installing Ceiling Firestop .4. ;Jill INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM 3 FASTENERS i� ;� PER SIDE v' 1 t CEILING FIRESTOP CEILING FIRESTOP INSTALLED BELOW CEILING INSTALLED ABOVE CEILING Figure 8.4 Installing the Attic Shield Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 37 8 Vent Clearances and Framing I A. Pipe Clearances to Combustibles B. Wall Penetration Framing WARNING! Risk of Fire! Maintain air space clearance to Combustible Wall Penetration vent. DO NOT pack insulation or other combustibles: Whenever a combustible wall is penetrated, you must • Between ceiling firestops frame a hole for the wall shield firestop(s). The wall shield • Between wall shield firestops firestop maintains minimum clearances and prevents cold • Around vent system air infiltration. Failure to keep insulation or other material away from • The opening must be framed on all four sides using the vent pipe may cause over heating and fire. same size framing materials as those used in the wall construction. • SLP pipe -A wall shield firestop must be placed on each Note: Heat shields MUST overlap by a minimum of 1 -1/2 in (38 mm). side of an interior wall. A minimum 1 -1 /2 in. (38 mm • DVP heat shield - designed to be used on a wall 4 in. to 7 -1/4 in (102 mm to 184 ( mm) mm) thick. overlap of attached heat shields must be maintained. • If wall thickness is less than 4 in. the existing heat shields must be field trimmed. K wall thickness is greater than 7 -1/4 in. a DVP -HSM -B will be required. • DVP pipe - A wall shield firestop is required on one side • SLP heat shield - designed to be used on a wall 4 -3/8 in. to 7 -5/8 in (111 mm to 194mmthick). only on interior walls. If your local inspector requires a • If wall thidmess is less than 4-3/8 the eidsting heat shields must be field trimmed. wall shield firestop on both sides, then both wall shield If wail thickness is greater tan 7-5/6 in.. Dw+ISM a will be required. firestops must have a heat shield (refer to Section 16.B.) attached to them. (DVP -SLP Pipe Shown) • See Section 10.M. for information for regarding the in- stallation of a horizontal termination cap. Heat 3 in (76 mm) 3 in. (76 mm) Shield top clearance • Non - Combustible Wall Penetration top clearance -- el Heat Shield If the hole being penetrated is surrounded by noncom - 1 in (25 mm) bustible materials such as concrete, a hole with diameter clearance around i __ II .,..I. one inch greater than the pipe is acceptable. vertical sections O-, 7 � I © 1 in (25 mm) Whenever a non - combustible wall is penetrated, the wall — • Wall clearance Shield bottom & sides shield firestop is only required on one side and no heat Firestop shield is necessary. WALL 4.. l i Heat 3 in (76 mm) Shield top clear ance * i k \ 1 • , \___- Heat �� Shield • � l ti �, .- IMO 1 1 �1 in. (25 mm) Wall clearance 1 0 In. 1� 1 2 Fn.. T O Shield bottom & sides C •0 i Firestop D p 068 WALL 1 In 11 1 21n. i ii, • When using SLP or SL -D pipe, minimum clearances from the vent pipe to combus- tible materials at inside wall firestops are: Top: 2 -1/2 in. (64 mm) I Bottom: 1/2 in. (13 mm) A B. : i Sides. 1 in. (25 mm) 1 Figure 8.1 Horizontal Venting Clearances To Combustible Materials A* B* C D in. 42 -3/4 27 -7/8 41 -3/4 26 -7/8 6000 mm 1086 708 1060 683 in. 44 -3/4 29 -7/8 44 -1/8 28 -7/8 8000 mm 1137 759 1111 733 * Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe. Figure 8.2 Wall Penetration 36 Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 D. Mantel and Wall Projections Combustible Mantel Legs or Wall Projections WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing or finishing material closer than 0 the minimums listed must be constructed entirely of noncom- bustible materials (i.e., steel studs, concrete board, etc). the WALL Combustible Mantels TOP VIEW A TO CEILING 181 A • ., B 12) 11 r 101 32 FIREPLACE OPENING 0 91 i ( 25 6 l 71 19 MANTEL LEG OR WALL PROJECTIONS — Tjt 1 I 5l 17 18 41 _ 16 If A minimum is , then B maximum is 31 _ 15 A moms 2 -7/16 3 -7/16 4 -7/16 5 -7/16 6 -7/16 7 -7/16 14 Millimeters 62 87 113 138 164 189 13 0 2 -1/2 Inches 1 2 3 4 5 0 12 B MJlllmeters 25 51 76 102 127 00 11 � f 10 Figure 5.4 Clearances to Mantel Legs or Wall Projections (Acceptable on both sides of opening.) .....E1 i/ MEASUREMENTS FROM TOP EDGE OF THE OPENING Note: All measurements in inches. Note: Measurement is taken from top of the opening, NOT the top of the fireplace. Figure 5.3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles 22 Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 B. Constructing the Appliance Chase stops should be caulked with caulk with a minimum of A chase is a vertical box -like structure built to enclose the 300 °F continuous exposure rating to seal gaps. Gas line gas appliance and/or its vent system. In cooler climates holes and other openings should be caulked with caulk the vent should be enclosed inside the chase. with a minimum of 300 °F continuous exposure rating or stuffed with unfaced insulation. If the appliance is being NOTICE: Treatment of ceiling firestops and wall shield installed on a cement surface, a layer of plywood may be firestops and construction of the chase may vary with the placed underneath to prevent conducting cold up into the type of building. These instructions are not substitutes room. for the requirements of local building codes. Therefore, C. Clearances you MUST check local building codes to determine the requirements to these steps. NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly Chases should be constructed in the manner of all out on carpeting, vinyl, tile or any combustible material other side walls of the home to prevent cold air drafting prob- than wood. lems. The chase should not break the outside building envelope in any manner. WARNING! Risk of Fire! Maintain specified air space clearances to appliance and vent pipe: Walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers • Insulation and other materials must be secured to prevent should be installed in the chase as per regional codes for accidental contact. the rest of the home. Additionally, in regions where cold • The chase must be properly blocked to prevent blown air infiltration may be an issue, the inside surfaces may be insulation or other combustibles from entering and sheetrocked and taped for maximum air tightness. making contact with fireplace or chimney. To further prevent drafts, the wall shield and ceiling fire- • Failure to maintain airspace may cause overheating and a fire. lial t'� A E II 1111111111.1111Pw w il I _^ llll- - •4 I 0 c''';:;!' . 3 ,. 0, r . ice.. .... 7 F , e'� '��j�� . H Immoi ��1 +- r —�► I—y/..— / * it NIMUM FRAM# D1 i SIO A B C ** D E F G H I J mod Rough Rough Rough Rough Clearance Combustible Combustible Behind Sides of Front of Opening Opening Opening Opening to Ceiling Floor Flooring Appliance Appliance Appliance ` - .. , .. (Width) (Height) (Depth) (Width) in 10 40 -1/8 22 42 25 0 0 1/2 1/2 36 6000 mm 254 1019 559 1067 635 0 0 13 13 914 in. 10 42 -1/8 22 49 25 0 0 1/2 1/2 36 8000 mm 254 1019 559 1245 635 0 0 13 13 914 * Adjust framing dimensions for interior sheathing (such as sheetrock) C ** Add 12 inches for rear venting with one 90° elbow. Figure 5.2 Clearances to Combustibles Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 21 5 Framing and Clearances A. Selecting Appliance Location NOTICE: Illustrations reflect typical installations and are When selecting a location for the appliance it is important to FOR DESIGN PURPOSES ONLY. Illustrations /diagrams consider the required clearances to walls (see Figure 5.1). are not drawn to scale. Actual installation may vary due to individual design preference. WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access. Due to high temperatures, the appliance should be locat- ed out of traffic and away from furniture and draperies. NOTE: THE REAR STANDOFF MAY NEED TO BE REMOVED WHEN VENTING AT 45° Lek EA 1/2 IN. G- t O 1 111 1 • ALCOVE • INSTALLATION E B C TOP VENT _. ONE 90° ELBOW 1 REAR VENT, REAR VENT HORIZONTAL TERMINATION ONE ELBOW • TWO ELBOWS REAR VENT • B NO ELBOWS B D 2 B D 'ics 1 • (e \ • • 0 F • ( '�i 1 D d —0. F 4. D > A B C D E F G H 6000 in. 51 42 72 56 -5/8 See Section D 22 17 -3/4 8 mm 1295 1067 1829 1438 Mantel Projections 559 451 203 8000 in. 55 -7/8 49 i 79 61 -112 See Section D. 22 19 -3/4 10 mm 1419 1245 2007 1562 Mantel Projections 559 502 254 Figure 5.1 Appliance Locations - 6000 Models 20 Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 • 3q /aiM Sr 3eI FL 3 2, c _ 13 Para obtener un ejemplar en Espanol de este _ —r Pour demander un exemplaire en fran9ais de ce Manuel Manual del propietario, visite www.heatnglo.com. du proprietaire, visitez www.heatnglo.com. H EAT LC OT L. Owner's Manual � ` � � Installation and Operation No one builds a better fire �� 0 Models: ,1`," 6000CLX -IPI -T GAS-FIRED 6000CLX- IPILP -T t D 6000CLX -IPI -S C YL US 6000CLX- IPILP -S 8000CLX -IPI -T LISTED 8000CLX- IPILP -T 0 8000CLX -IPI -S G �� d 8000CLX- IPILP -S NOTICE Q -41, DO NOT DISCARD THIS MANUAL a C ` oi"' 1 :; . Important operating Leave this manual with ; • Im ortant o eratin • Read, understand and follow b 1 and maintenance these instructions for safe party responsible for use instructions included. installation and operation. and operation. A WARNING: If the information in these A WARNING instructions is not followed exactly, a fire HOT SURFACES! or explosion may result causing property — ` Glass and other surfaces are hot during damage, personal injury, or death. operation AND cool down. i Hot glass will cause burns. • DO NOT store or use gasoline or other flam- • DO NOT touch glass until it is cooled mable vapors and liquids in the vicinity of this • NEVER allow children to touch glass • or any other appliance. Keep children away • CAREFULLY SUPERVISE children in same room as • What to do if you smell gas fireplace. - DO NOT try to light any appliance. • Alert children and adults to hazards of high temperatures. High temperatures may ignite clothing or other flammable - DO NOT touch any electrical switch. DO materials. NOT use any phone in your building. • Keep clothing, furniture, draperies and other flammable materials away. - Immediately call your gas supplier from a neighbor's phone. Follow the gas Sup- This appliance has been supplied with an integral barrier plier's instructions. to prevent direct contact with the fixed glass panel. DO - If you cannot reach your gas supplier, Call NOT operate the appliance with the barrier removed. the fire department. Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one. • Installation and service must be performed by a qualified installer, service agency, or the gas supplier. In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional Commonwealth This appliance may be installed as an OEM installation in of Massachusetts requirements. manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer's instructions and the manufactured home construction and safety standard, Installation and service of this appliance should be Title 24 CFR, Part 3280 or Standard for Installation in Mobile ., `'�► performed by qualified personnel. Hearth & Home Homes, CAN /CSA Z240MH, in Canada. 4 7 \ Technologies suggests NFI certified or factory trained This appliance is only for use with the type(s) of gas indicated N " professionals, p rofessionals, or technicians supervised by an NFI on the rating plate. ' '' certified professional. Heat & Glo • 6000CLX- IPI -S, 6000CLX- IPI -T, 8000CLX -S, 8000CLX -IPI -T • 2166 -900 Rev. P • 3/11 1