31B-287 • • Accessibility 605.1 General. Accessibility requirements shall be in accordance with 521 CMR. There are no additional requirements beyond those identified in Section 706 above. Structural 606: No additional requirements beyond those identified in Section 707 above. Energy Conservation 607: No additional requirements beyond those identified in Section 711 above 10 SECTION IV — CHAPTER 34 ANALYSIS ALTERATIONS — LEVEL I GENERAL 601: The work shall not reduce the level of conformance to building, fire, plumbing, mechanical or electrical codes in effect at the time that the affected areas of the building were constructed. BUILDING ELEMENTS AND MATERIALS 602: All new work shall comply with materials and methods requirements in the International Building Code, International Energy Conservation Code, and International Mechanical Code, as applicable. FIRE PROTECTION 603: Automatic Sprinkler Systems will not be required as a result of the reconfiguration of space as this work does not rise to the level of "major alterations" as defined by The Commonwealth of Massachusetts, Fire Safety Commissioner's Automatic Sprinkler Appeals Board, (see Memorandum and Advisory Guidance Document, dated October 14, 2009), and therefore do not trigger the requirements set forth in M.G.L. c. 148, § 26G. MEANS OF EGRESS 604.1: Alterations shall be done in a manner that maintains the level of protection provided for the means of egress, and in accordance with section 102.2.2.1. 102.2.2.1 Existing Non- Conforming Means of Egress: The following conditions shall be corrected in all existing buildings: 1. Less than the number of means of egress serving every space and/or story, required by Chapter 10 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 10.00); There is a sufficient number of exits serving the second story. 2. Any required means of egress component which is not of sufficient width to provide adequate exit capacity in accordance with section 1005.1 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 1005.1.) The exit component widths are sufficient to provide adequate exit capacity. What is the minimum specified elsewhere in the code? 3. Any means of egress which is not so arranged as to provide safe and adequate means of egress, including exit signage and emergency lighting in accordance with Chapter 10 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 10.00); The existing exit stairway shall comply with 780 CMR 10.00 for door closing, handrails., exit signage and emergency lighting. 9 • ENERGY CONSERVATION 711.1 Minimum requirements. Level 2 alterations to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the International Energy Conservation Code or International Residential Code. The alterations shall conform to the energy requirements of the International Energy Conservation Code or International Residential Code as they relate to new construction only. The alterations, (in the Work Area), shall conform to the energy requirements of the International Energy Conservation Code or International Residential Code as they relate to new construction only. Since the reconfigured space results in the expansion of an existing space by reducing the area of an adjoining space, these spaces should be evaluated as a whole for compliance with the energy provisions. Even though some of the elements in the space have not actually changed, some of the existing mechanical system may be altered and new ductwork installed to re -route the ducts to the various spaces. Only the new elements are required to meet the energy provisions, (not the entire system.) 8 521 CMR 3.3.1 If the work being performed amounts to less than 30% of the full and fair cash value of the building and a. if the work costs less than $100,000, then only the work being performed is required to comply with 521 CMR Only the reconfigured work area is required to comply with 521 CMR because the costs for the work being performed in this work area is less than $100,000 and is less than 30% of the full and fair cash value of the building. STRUCTURAL 707.1 General. Structural elements and systems within buildings undergoing Level 2 alterations shall comply with this section. 707.2 New structural elements. New structural elements in alterations, including connections and anchorage, shall comply with the International Building Code. 707.3 Minimum design loads. The minimum design loads on existing elements of a structure that do not support additional loads as a result of an alteration shall be the loads applicable at the time the building was constructed. 707.4 Existing structural elements carrying gravity loads. Alterations shall not reduce the capacity of existing gravity load - carrying structural elements. 707.5 Existing structural elements resisting lateral loads. N/A 707.6 Voluntary improvement of the seismic force - resisting system. N/A MECHANICAL 709.1 Reconfigured or converted spaces All reconfigured spaces intended for occupancy and all spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the International Mechanical Code. Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 709.2. 709.2 Altered existing systems. In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured, or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m /s) per person of outdoor air and not less than 15 cfm (0.0071 m /s) of ventilation air per person; or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62. ASHRAE 62 minimum overarching ventilation requirements to be determined and provided by the Mechanical contractor. 7 • 704.2 Automatic sprinkler systems. Automatic Sprinkler Systems will not be required because work area does not contain exits or corridors shared by more than one tenant; the shared occupant load for the entire second floor is less than 30; and the work area the work area is less than 50% of the floor area. 704.2.4 Other required suppression systems. In buildings and areas listed in Table 903.2.11:6 of the International Building Code, work areas that have exits or corridors shared by more than one tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with sprinkler protection under the following conditions: N /A, because the work area does not contain exits or corridors shared by more than one tenant:, the shared occupant load for the entire second floor is less than 30; and the building and work area is not listed in Table 903.2.11.6. 704.3 Standpipes. Where the work area includes exits or corridors shared by more than one tenant and is located more than 50 feet (15 240 mm) above or below the lowest level of fire department access, a standpipe system shall be provided. N /A, because the work area does not contain exits or corridors shared by more than one tenant:, the work area is not located more than 50 feet above the lowest level of Fire Department Access. 704.4 Fire alarm and detection. N/A for the B Use Group where the work area is less than 50 % of the floor area MEANS OF EGRESS 705.1 The requirements of this section shall be limited to work areas that include exits or corridors shared by more than one tenant within the work area in which Level 2 alterations are being performed, and where specified they shall apply throughout the floor on which the work areas are located or otherwise beyond the work area. N /A, the Work Area is not shared by more than one tenant, and does not include corridors or exits that affect others. Therefore, the tenant space undergoing this alteration need only comply with the means of egress requirements of section 604, (see below.) ACCESSIBILITY 706.1 General. Accessibility requirements shall be in accordance with 521 CMR. 521 CMR 3.3 EXISTING BUILDINGS: All additions to, reconstruction, remodeling, and alterations or repairs of existing public buildings or facilities, which require a building permit or which are so defined by a state or local inspector, shall be governed by all applicable subsections in 521 CMR 3.00. 6 • "To assist fire officials, building owners and construction project managers in making decisions, the Board has established the following two presumptions that may be used to determine if the scope or the cost of the planned alterations, or modifications are "major" thus requiring sprinklers to be installed throughout the building. 1.) Major alterations or modifications are reasonably considered major in scope when such work affects thirty -three (33)% or more of the "total gross square footage" of the building, calculated in accordance with section 26G. 2.) Major alterations or modifications are reasonably considered major in scope or expenditure, when the total cost of the work (excluding costs relating to sprinkler installation) is equal to or greater then thirty-three (33)% of the assessed value of the subject building, as of the date of permit application. _ It was the conclusion of the board that if the nature of the work is the type of work described in Part A and also meets at least one of the two presumptions described in Part B, then it can reasonable to conclude that the alterations or modifications are "major ", thus requiring sprinklers throughout the building. If the specific permitted alterations or modifications are not considered "Major" as described, but appear to be one phase of a series of modifications being conducted over a reasonably short period (i.e. five years or less), it may be reasonable to conclude that such work could be part of a long range project resulting in "major alterations" to the entire building, or a substantial portion of it, thus triggering the sprinkler requirements. Consideration should be given to determine if there is a series of future and recent past planned projects that, taken together, would be amount to "major" alterations. The proposed reconfigurations for the work area identified in this building permit application do not rise to the level of "major alterations" as defined by The Commonwealth of Massachusetts, Fire Safety Commissioner's Automatic Sprinkler Appeals Board, (see Memorandum and Advisory Guidance Document, dated October 14, 2009). They are also not part of a phase or series alterations or modifications being conducted over a period of five or less years. Ratio of Work Area to total Building Area is: 3 %. Work Area: 85.75 square feet Total Building Area: — 2,807.00 square feet .00305 The total cost of this reconfiguration is less than 33% of the assessed value of the building. Automatic Sprinkler Systems will not be required because they do not trigger the requirements set forth in M.G.L. c. 148, § 26G. 5 FIRE PROTECTION 704.1 Scope the requirements of this section shall be limited to work areas in which Level 2 alterations are being performed, and where specified they shall apply throughout the floor on which the work areas are located or otherwise beyond the work area. 704.1.2 Major Alterations. In addition to the requirement in section 704, automatic sprinkler systems may be required in buildings undergoing major alterations per section 102.2.1.1 102.2.1.1 Major Alterations. When existing buildings or portions thereof undergo additions or alterations, M.G.L. c. 148, § 26G may apply with respect to automatic sprinkler requirements. The requirements of this statute are enforced by the fire official. Applicability of these requirements can be found at the Department of Fire Services web site www.mass.gov /dfs. The Commonwealth of Massachusetts, Fire Safety Commissioner's Automatic Sprinkler Appeals Board, (hereinafter the "Board "), has defined the term "Major Alterations" in its Memorandum and Advisory Guidance Document, dated October 14, 2009. The Board established a two pronged test to determine if the proposed work is rises to the level sufficient to be considered "major alteration" and thereby triggering the requirements of M.G.L. c. 148, § 26G Part A - Nature of the Actual Work. • Is the planned physical work the type of work that would make the effort to install sprinklers substantially less than it would have been if the building were intact? • Is the work merely minor repair or cosmetic vs. major alterations? Examples of "major" alterations or modifications include, but may not be limited to: o The demolition or reconstruction of existing ceilings or installation of suspended ceilings; o The removal and /or installation of sub flooring, not merely the installation or replacement of carpeting or finished flooring; o The demolition and/or reconstruction or repositioning of walls or stairways or doorways; or o The removal or relocation of a significant portion of the building's HVAC, plumbing or electrical systems involving the penetration of walls, floors or ceilings. Part B - Scope of the Work or Cost /benefit of Sprinkler Installation. This involves a review of the scope of the major alterations or modifications to see if they affect a substantial portion of the building. This requires a review to determine how much of the building is being affected by the work; or a determination that the cost of installing sprinklers is moderate in comparison to the total cost of the work. 4 • SECTION III — CHAPTER 34 ANALYSIS GENERAL Level II Alterations include the reconfiguration of space, the addition or elimination of any door or window, the reconfiguration or extension of any system, or the installation of any additional equipment. 701.3 Compliance. All new construction elements, components, systems, and spaces shall comply with the requirements of the International Building Code. Exceptions: 4. The minimum ceiling height of the newly created habitable and occupiable spaces and corridors shall be 7 feet (2134 mm). BUILDING ELEMENTS AND MATERIALS 703.1 Scope. The requirements of this section are limited to work areas in which Level II Alterations are being performed, and shall apply beyond the work area where specified. 703.2 Vertical openings. Existing vertical openings shall comply with the provisions of Sections 703.2.1, 703.2.2, and 703.2.3. N /A, there are no vertical openings in the work area and the total 2 floor area is less than 3,000 square feet, (see exceptions below.) 703.2.1 Existing vertical openings. All existing interior vertical openings connecting two or more floors shall be enclosed with approved assemblies having a fire- resistance rating of not less than 1 hour with approved opening protectives. Exceptions: 5. In Group B occupancies, a minimum 30- minute enclosure shall be provided to protect all vertical openings not exceeding three stories. This enclosure, or the enclosure specified in Section 703.2.1, shall not be required in the following locations: 5.1. Buildings not exceeding 3,000 square feet (279 m per floor. 703.4 Interior finish. The interior finish of walls and ceilings in exits and corridors in any work area shall comply with the requirements of the International Building Code. Exception: Existing interior finish materials that do not comply with the interior finish requirements of the International Building Code shall be permitted to be treated with an approved fire- retardant coating in accordance with the manufacturer's instructions to achieve the required rating. This requirement shall be met. 703.5 Guards. N/A 3 • SECTION 1— HISTORY / SCOPE OF WORK The Work Area Compliance Method has been applied for work performed pursuant to this building permit application, The Classification of this Work is Alteration — Level II. The work pursuant to building permit no. is a limited reconfiguration of office space of an 85.75 square foot area of the second floor. One section of an existing interior partition shall be removed and one new interior partition shall be installed to expand the common area on the floor. There is no change in use for this work space. SECTION II — BUILDING DESCRIPTION — EXISTING The building is a two story building originally constructed as a residence in 1880 and subsequently converted into it current use as business offices. The building construction is as follows: Use Group: B Building height: Two Stories plus Attic Space Number of floors above grade: Two Number of floors below grade: One Square footage per floor: 1 floor: 1451 ft 2 floor: 1356 ft Total aggregate floor area: 2807 ft Type of construction: VB Foundation: Stone Floors: Wood Joists, Hardwood Walls: Post & Beam Wood Framing, Plaster & Lath, Clapboard Wood Siding, Roof: High Pitch Roof, Wooden Rafters, w/ 5/8" sheathing and asphalt shingles 2 • INVESTIGATION AND EVALUATION REPORT Pursuant to Massachusetts State Building Code (780 CMR), Eighth Edition, Base Volume Chapter 34 — The Existing Building code of Massachusetts MAY 20, 2011 40 CENTER STREET NORTHAMPTON, MA RECONFIGURATION OF COMMON SPACE � S -cERED 4 4, Q ( e / I RI y O F I, ND ' ,. SIEGFRIED PORTH, A.I.A. � *° ]/' � MICHAEL J. DUVAL ' �;� 116 PLEASANT STREET, EASTHAMPTON, MA 01027 (413) -529 -9434 1 • Information and Instructions • Massachusetts General Laws chapter 152 requires all employers to provide workers' compensation for their employees. Pursuant to this statute, an employee is defined as "...every person in the service of another under any contract of hire, express or implied, oral or written." . An employer is defined as "an individual, partnership, association, corporation or other legal entity, or any two or more of the foregoing engaged in a joint enterprise, and including the legal representatives of a deceased employer, or the receiver or trustee of an individual, partnership, association or other legal entity, employing employees. However the owner of a dwelling house having not more than three apartments and who resides therein, or the occupant of the . dwelling house of another who employs persons to do maintenance, construction or repair work on such dwelling house or on the grounds or building appurtenant thereto shall not because of such employment be deemed to be an employer." MGL chapter 152, §25C(6) also states that "every state or local licensing agency shall withhold the issuance or renewal of a license or permit to operate a business or to construct buildings in the commonwealth for any applicant who has not produced acceptable evidence of compliance with the insurance coverage required." ; ✓ Additionally, MGL chapter 152, §25C(7) states "Neither the commonwealth nor any of its political subdivisions shall enter into any contract for the performance of public work nntil acceptable evidence of compliance with the insurance requirements of this chapter have been presented to the contracting authority." Applicants Please fill out the workers' compensation affidavit completely, by checking the boxes that apply to your situation and, if necessary, supply sub-contractor(s) name(s), address(es) and phone number(s) along with their certificate(s) of insurance. Limited Liability Companies (LLC) or Limited Liability Partnerships (LLP) with no employees other than the members or partners, are not required to carry workers' compensation insurance. If an LLC or LLP does have employees, a policy is required. Be advised that this affidavit may be submitted to the Department of Industrial Accidents for confirmation of insurance coverage. Also be sure to sign and date the affidavit. The affidavit should be returned to the city or town that the application for the permit or license is being requested, not the Department of Industrial Accidents. Should you have any questions regarding the law or if you are required to obtain a workers' compensation policy, please call the Department at the number listed below. Self-insured companies should enter their self- insurance license number on the appropriate line: City or Town Officials Please be sure that the affidavit is complete and printed legibly. The Department has provided a space at the bottom of the affidavit for you to fill out in the event the Office of Investigations has to contact you regarding the applicant. • Please be sure to fill in the permit/license number which will be used as a reference number. In addition, an applicant that must submit multiple permit/license applications in any given year, need only submit one affidavit indicating current policy information (if necessary) and under "Job Site Address" the applicant should write "all locations in (city or town)." A copy pf the affidavit that has been officially stamped or marked by the city or town may be provided to the applicant as proof that a valid affidavit is on file for future permits or licenses. A new affidavit must be filled out each year. Where a home owner or citizen is obtaining a license or permit not related to any business or commercial venture (i.e. a dog license or permit to burn leaves etc.) said person is NOT required to complete this affidavit. . ' _ The Office of Investigations would like to thank you in advance for your cooperation and should you have any questions, please do not hesitate to give us a call. The Department's address, telephone and fax number. The Commonwealth of Massachusetts Department of Industrial Accidents Office of Investigations 600 Washington Street Boston, MA. 02111 Tel. # 617 -727 -4900 ext 406 or 1- 877- MASSAFE Fax # 617- 727 -7749 Revised 11 -22 -06 '- www.mRS'.goVldia } • • The Commonwealth of Massachusetts Department of Industrial Accidents. _1 _ Office of Investigations • � ' 600 Washington Street _ Boston, MA 02111 www.massgov /dia -Workers' Compensation Insurance Affidavit Builders/ Contractors /Electricians/Plumbers Applicant Information 1 r Please Print Legibly Name ( Business /Organization /Individual): ' /-� � � � CCU ,/ Address: 44 ©2 - , 0, - Cit /State /Zip: (M -4— Phone. #: LL L (E5-3c71-5-a? Are you an employer? Check the appropriate box: Type of project (required): / 1. ❑ I am a employer with 4. 0 I am a general contractor and I 6. ❑ New construction employees (MI and/or part- time).* have hired the sub- contractors 2.p I am a sole proprietor or partner- listed on the attached sheet. 7. i lgji Remodeling ship and have no employees These sub - contractors have. .g. Demolition working for me in any capacity. employees and have workers' Y P n' t 9. ❑ Building addition [No workers' comp. insurance comp. insurance. required] 5. 0 We are a corporation and its 10.0 Electrical repairs or additions 3.0 I am a homeowner doing all work officers have'exercised their . 11.0 Plumbing repairs or additions myself. [No workers' comp. right of exemption per MGL 12.0 Roof repairs insurance required.] t c. 152, §1(4), and we have no employees. [No workers' 13.0 Other comp. insurance required.] *Any applicant that checks box #1 must also fill out the section below showing their workers' compensation policy information. t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such. IContractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have employees. If the sub-contractors have employees, they must provide their workers' comp. policy number. I am an employer that is providing workers' compensation insurance for my employees. Below is the policy and job site information. Insurance Company Name: Policy # or Self-ins. Lic. #: Expiration Date: Job Site Address: City /State/Zip:' Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to $1,500.00 and/or one -year imprisonment; as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do hereby certi u ' = ' e • an penalties of perjury that the information provided abo a is true and correct Signature: Date: L /71// Phone #: ' - f 1 c Official use only. Do not write in this are to be completed by city or town officiaL City or Town: Permit/License # Issuing Authority (circle one): 1. Board of Health 2. Building Department 3. City/Town Clerk 4. Electrical ,Inspector 5. Plumbing Inspector 6. Other Contact Person: Phone #: ' Version1.7 Commercial Building Permit May 15, 2000 SECTION 10- STRUCTURAL PEER REVIEW (780 CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes 0 No 0 SECTION 11 - OWNER AUTHORIZATION - TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT I, K..ln 5 \'e \() , as Owner of the subject property hereby authorize 'T4-JV ., V4]" nt AA to act on my behalf, in all may s rela e to work authorized by this building permit application. f , signature of Owner Date --i I, Z-14- a- Vf lr f \r�TYr , as Owner /Authorized Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge and belief. Signed under the pains and penalties of perjury. ■ 4 ilk .i^ Print N m- , a 5" it.k Signat re o Owner /Ag nt Date SECTION 12 - CON TRUCTION RVICES 10.1 Licensed Construction Sup &visor: Not Applicable ❑ Name of License Holder : t�YY VA ,k iT 6 4- g ifiG - 2.-C> ©I . License Number — • Al fir- - a 1,11 , A, _( >, —► _ j .4 5123' j 1/3 Address Expiration Date h 41ti t z,2- Signa re Telephone SECTION 13 - ORKERS' CO PENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes 0 No \Yersioni .7 Commercial Building Permit May 15.20OO SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 790 CIVIR 116 (CONTAINING MORE 9.1 Registered Architect: NOT Ced-re.e.P^ Not Applicable 0 Name (Registrant): Registration Number Address Expiration Date Signature Telephone 9.2 Registered Professional Engineer (s): Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date 9.3 General Contractor V14 Ni Co , Not Applicable [] Company Name: &-- M Responsible In Charge espmn o n �� t ��«��«�� iv • 1144- muumso 14i3 v " �7 y �� , �/ i� ~ -- v "~~--- v S|8nmun� Telephone J , J � ' Version1.7 Commercial Building Permit May 15, 2000 _ NORTHAMPTON ZONING Existing Proposed Required by Zoning This column to be filled in by Building Department Lot Size Frontage Setbacks Front Side L: R: L: R: Rear Building Height Bldg. Square Footage % Open Space Footage % (Lot area minus bldg & paved parking) # of Parking Spaces Fill: (volume & Location) A. Has a Special Permit /Variance /Finding ever been issued for /on the site? NO 0 DON'T KNOW C4 YES Q IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO 0 DON'T KNOW 0 YES IF YES: enter Book Page and /or Document # B. Does the site contain a brook, body of water or wetlands? NO I?I DON'T KNOW YES IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained Q Obtained , Date Issued: C. Do any signs exist on the property? YES 4 NO IF YES, describe size, type and location: " ' IY3J-(,L t � , �- - ��� f L ti S-j b D. Are there any proposed changes to or additions of signs intended for the property ? YES 0 NO IF YES, describe size, type and location: t{,*11i1&-- Gt-j _ ONL E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan that will disturb over 1 acre? YES 0 NO IF YES, then a Northampton Storm Water Management Permit from the DPW is required. Versionl.7 Commercial Building Permit May 15, 2000 • SECTIOtSL CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE Interior Alterations 0 Existing Wall Signs ❑ Demolition ❑ Repairs ❑ Additions ❑ Accessory Building ❑ Exterior Alteration ❑ Existing Ground Sign ❑ New Signs ❑ Roofing❑ Change of Use ❑ Other ❑ Enter a brief description here. Brief Description A �,.,,,,� Of Proposed Work: 1ZE-' VJ*t -(_ ' J • Ci--� li rr C -L Al�� VI 1... - 11;) U 'NrD N A- t.Xi,nL(. M SECTION 5 - USE GROUP AND CONSTRUCTION TYPE USE GROUP (Check as applicable) CONSTRUCTION TYPE A Assembly ❑ A -1 ❑ A -2 ❑ A -3 ❑ 1A I ❑ A -4 ❑ A -5 ❑ 1B ❑ B Business ❑ 2A ❑ E Educational ❑ 2B I ❑ F Factory ❑ F -1 0 F -2 ❑ 2C ❑ H High Hazard ❑ 3A 1 ❑ I Institutional ❑ 1 -1 ❑ 1 -2 ❑ 1 -3 ❑ 3B ❑ M Mercantile ❑ 4 ❑ R Residential ❑ R -1 ❑ R -2 ❑ R -3 ❑ 5A ❑ S Storage ❑ S -i ❑ S -2 ❑ 5B ❑ U Utility ❑ Specify: M Mixed Use ❑ Specify: S Special Use ❑ Specify: COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS, ADDITIONS AND /OR CHANGE. IN USE Existing Use Group: Proposed Use Group: Existing Hazard Index 780 CMR 34): Proposed Hazard Index 780 CMR 34): SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY Floor Area per Floor (sf) N CA— t — 15t 1 2 nd 2 3rd 3 rd 4th 4 th Total Area (sf) Total Proposed New Construction (sf) Total Height (ft) Total Height ft 7. Water Supply (M.G.L. c. 40, § 54) 7.1 Flood Zone Information: 7.3 Sewage Disposal System: Public ❑ Private ❑ Zone Outside Flood ZoneD Municipal ❑ On site disposal system g f 1 t it; A 1■ j ; Versionl.7 Commercial Building Permit M a i 15 2000 IP.t Vigli of Northampton Sys o1 P� B (ing Department Cirbt�� ierttil . Main Street a '� a�� : , u • ,Room 100 � $t e1 � Y� r �►n'°.°, t orthampton, MA 01060 Tr et t Str i t r { �� t ray ,v r phone 413 -587 -1240 Fax 413 - 587 -1272 o SitePJan ;, Ot APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, CHANGE THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 - SITE INFORMATION 1.1 Property Address: This section to be completed by office Hp CAL i Zy — 2 F-Cce5R Map Lot Unit 4A (2.' / T`I N'11-' Zone Overlay District Elm St. District CS District SECTION 2 - PROPERTY OWNERSHIP /AUTHORIZED AGENT 2.1 Owner of Record: Name (Print) Ken :ow'e v- Current Mailing Address: Signature Telephone 2.2 Authorized Agent: Name (Print) ...,1,4 ! . vot}t\i k[,4--n-7t C urrent Mailing Address: � - NFU tA-4 �. 1 ' irot V ' C L.LC_ 2� t61� 144A— "3 Signature / 4I 1 I A Telephone 4/3 e 2 SECTION Q ES IMATED C 11 NSTRUCTI EP N COSTS Item E.sti ated Cost (Dollars) to be Official Use Only co .feted by permit applicant 1. Building --7 a30 (a) Building Permit Fee 2. Electrical .,f (b) Estimated Total Cost of �c Construction from (6) 3. Plumbing Building Permit Fee 4. Mechanical (HVAC) 5. Fire Protection .�»� r ? ,2 6. Total = (1 + 2 + 3 + 4 + 5) SC) Check Number ". This Section For Official Use Only Building Permit Number Date Issued Signature: Budding Commissioner /inspector of Buildings _ Date File # BP- 2011 -0972 APPLICANT /CONTACT PERSON JAMES VAN NATTA ADDRESS /PHONE 403 SOUTH MOUNTAIN RD NORTHFIELD (413) 834 -5329 Q PROPERTY LOCATION 40 CENTER ST MAP 31B PARCEL 287 001 ZONE CB(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out C,9‘1# Fee Paid Typeof Construction: REMOVE & CONSTRUCT NEW WALL TO EXPAND WAITING ROOM New Construction Non Structural interior renovations Addition to Existing, Accessory Structure Building Plans Included: Owner/ Statement or License 040620 3 sets of Plans / Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON IN ATION PRESENTED: ' Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER: § Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay �. �� 5/246/ f1 Signature of Building 0 ficial Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information. ",, 40 CENTER ST =; r • BP -2011 -0972 s # COMMONWEALTH-Of MASSACHUSETTS 'vl 3 B -„,k,.. 87 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: renovation BUILDING PERMIT Petuwit # BP- 2011 -0972 Project # JS- 2011 - 001593 Est. Cost: $8250.00 Fee: $55.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: JAMES VAN NATTA 040620 Lot Size(sq. ft.): 4748.04 Owner: BOWEN.KENNETH B & CARROLL S Zoning CB( I VU ji _ _ `` ppl,. ?:2t: JAMES VAN i� � NATTA AT: 40 CENTER ST Applicant Address: Phone: Insurance: 403 SOUTH MOUNTAIN RD (413) 834 -5329 O NORTHFIELDMA01360 ISSUED ON:5/27/2011 0:00:00 TO PERFORM THE FOLLOWING WORK: REMOVE & CONSTRUCT NEW WALL TO EXPAND WAITING ROOM POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector U nderground: Service: Meter: _ Footings: Rough: Rough: t /./j f/ House # Foundation: Driveway Final: ,, r Final: Final: (lj /27/ // R r , ough Frame: ' - ( i f ...... . . ' / . „L., t Cas: Fire Department Fireplace /Chimney: Rough: Oil: Insulation: Final: Smoke: Final: OIC9f — //C/VAA- THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND RE ��J ► °, ' t �” f� .�rc�c i 12►�+�1.+ Certificate of Occupanc / , mature: FeeTyp Date Paid: Amount: Building 5/27/2011 0:00:00 $55.00 212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272 Louis Hasbrouck – Building Commissioner