Loading...
24B-046 • The Fire Alarm Control Panel and/or Fire Alarm Annunciator must be labeled with red engraved signage with one -inch white lettering "Fire Alarm Control Panel" and /or "Fire Alarm Annunciator". Also engraved signage listing all fire alarm zone locations installed near panels. • A fire alarm annunciator shall be installed by the front entrance • Page 2 i t- S - } Northampton Fire Department __- Memorandum To: Tony Patillo - From: Duane Nichols V% Date: October 14, 2009 CC: Brian Duggan Re: 39 Carlon Drive, Dr Katherine White Secondary to a review of the plans and narrative submitted to me for review, I concur with the issuance of a building permit subject to the following conditions: • Fire alarm work permit shall be obtained for the project. The C/O inspection fee needs to be paid prior to approval of any fire alarm plan. • The graphic map for the building shall be changed to reflect the changes with the renovations. • 5 lb ABC Fire extinguishers are needed located at exits. This shall be in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should be located above • Keys with engraved key tags are required for the Emergency Access Key Box. • Pull Stations shall be double action type. • Page 1 2.16 10/9/09 Countertop bracket - detail reviewed by Fran & Michael. Brackets to be fabricated using birch plywd w /edge tape, for paint. Rough SKs drawn by MW/FG on back of Linda's 11x17 A501 print - in lieu of shop drwgs. Item closed. SUBMITTALS Submittals from Michael White - 10/9/09 Submittal Log to be distributed weekly. Item closed. Submittals from WB - 10/9/09 Submittal Log to be distributed weekly. Item closed. 1.20 10/2/09 Window /glazing shop drwgs - Per Walter, WB ok to cut masonry openings. They are drawn per architectural drwgs. No changes anticipated. Windows - Michael will review today and email approval today. Formal shops to follow. Prelim review at mtg - Per Walter, glass needs to be 3/8" thick at glass wall. Bendheim NELW -208 (MW's preferred choice) comes in 7/32 ". Michael will show Katherine 3 alternate glass samples tonight. Walter to revise submittals to meet intention of design to make glass wall as transparent as possible. Walter to relay intent to glass fabricator (preferred glass only comes 83" ht). Michael and Walter to work on directly. Pete Loshier is glass fabricator "Curved Glass" out of CT. 1.21 10/2/09 Marlite - Fran requested a template for pc of glass and also channels at reception desk so he can make adjustments to substrate as needed. Michael said marlite panels could be shop fabricated as an assembly. With 5/8" baltic birch. Fran to do this work in his shop to help expedite fabrication and, in turn, installation on site. 10/9/09 Michael noted the Marlite to be installed w/VERTICAL GRAIN. Fran noted that the framing as drawn will not be structurally sound enough for the installation of the Marlite soffit. Michael Ok'd for WB and Fran to work out the design of framing as deemed nec for the Marlite install. Next Job Meeting: Friday, October 16th, 9:00 at Wright Builders' Office. Site visit to follow. The above is intended to be a record of meeting items. Please inform the writer of errors or omissions. 2.6 10/9/09 Hogan / Low voltage - Low voltage, IT, data and wiring of wand security at entry doors to be done by Hogan (contracted directly by Dr. White). Michael said they would also like to have Bright Glass Alarm System on windows (not shown on drwgs). Todd suggested this go thru Hogan since they are dealing w /security. Hogan will also be wiring/installing the light signalling system w /paging system at Exam Rms. Todd Warren is contact at Hogan. WB to call them today since framing has started and, also confirm they have pulled their low voltage permit. Todd/ME will send their inspection dates to Hogan for coordination of low voltage inspections at same times. Rough & fmal inspections. (service inspection for new meter affects ME only). 2.7 10/9/09 EMR Electronic Medical Records - will be installed by Ensight Company, not Hogan. Michael will forward contact info to WB. 2.8 10/9/09 Panel / device locations - Michael to do SK elevations of panel / device locations - ht above FF, dimensions from dr casings etc. 2.9 10/9/09 Corridor 111 light fixtures - Todd & Michael reviewed reflected ceiling plan and 4'L clg fixtures confirmed in Corridor 111. Item closed.. 2.10 10/9/09 Fire alarm dialer - Todd asked WB to get letter to the landlord re: dialer. Per Todd, Perry is supplying it. Needed by end of November. Post mtg: Todd /ME to order, install and bill Perry. ARCHITECTURAL 1.16 10/2/09 Reception desk top - Michael brought in a sample of Stone Source "Celador" #851 Polished for top material. Roger to price. 10/9/09 Roger gave Stone Source pc to Tom/Westone for pricing. Tom will bring sample of material originally priced for Michael to see. 2.11 10/9/09 Pay requistion - Roger is requesting invoicing from subs by 20th reflecting work thru end of month. He will present pencil req to Michael & Dino on 10/23. Two (2) notarized AIA invoices to be submitted to Michael on 10/30. 2.12 10/9/09 C.O. Log - Roger gave Michael a copy of the C.O. Log which will be reviewed at end of each job mtg. Michael will prepare the AIA Change Order document based on approved WB C.O. Proposals. Item closed. 2.13 10/9/09 Door change - (2) Two 1'6" drs at Storage closet (near lockers) to be changed to (1) one 2'6" rh dr centered on wall between coat closet and lockers. WB to track cost on CO Log. Michael to note change on door submittal. Item closed. 2.14 10/9/09 Window sill detail - Roger & Jim reviewed A7 window sill detail w/Michael. He Ok'd installation of flashing pan under windows and deletion of weep hole detail. Item closed. 2.15 10/9/09 Wood window sill - Fran to prep poplar (for paint) sill pcs, w/kerf cuts on bottom. Coordinate exact dimensions w /Greenfield Glass windows and reveals per Michael's direction. Item closed. 2.2 10/9/09 Mixing valve - Per Paul, spec is overkill for for 10 gal elec water heater, located on shelf above janitor slop sink. Per Michael, Ok for Paul to review w /Jay/L &S direct, document decision. Discuss with Dino on site today. 2.3 10/9/09 Return & supply layouts - Per Dave, the return & supply layouts in Exam Rms 3 & 4 and Lab 113/Procedure Rm 2 are reversed. Dave will review with Dino on site today and supply as- builts at the end of the project. Post mtg: Dave & Dino reviewed Daves recommendation- ok'd. 2.4 10/9/09 Flex connectors - to diffusers are recommended by Dave. He thinks it could be drawn this way but can't see it. Dave will review w/Dino on site today. 2.5 10/9/09 Dampers - in return duct required? Dave to confirm with Dino on site today. ELECTRICAL 1.11 10/2/09 Elec panels - Todd/ME made request to keep existing panel in closet as "Owners/Landlord" panel and set new "Tenant" panel next to it. Drawings say to remove back to meter and install from existing. Need to keep 100amp for Owner /Landlord and set new 200amp and new meter. Martin Electric to request new service. Adjust layout as necessary for both panels to fit in space per code. 10/9/09 Michael decided to change dr #120.1 to server closet to (2) two 2'w drs (originally two 2'3 "w) biased as far South as possible so there is room for the panel. Also, install a floor stop close to hinge of door so it is not in the way. Michael to note change on door submittal. Rm. Todd waiting for info back from the engineers to request new service. Michael & Todd/ME to talk w/Perry regarding appropriate locations for both bldg & tenant(s) meters, panels etc for access and maintenance. Post mtg: Perry ok with Todd /ME to order & bill him for new service. 1.13 10/2/09 Symbol as fire alarm strobe - Todd/ME thinks a mistake, it should be an emergency light. Clarify with Joel/L &S today. 10/9/09 Review with Dino on site today. 1.14 10/2/09 Can elec transformer be fenced for aesthetics? Todd suggested Michael contact National Grid. 10/9/09 Item closed. 1.15 10/2/09 Existing circuits - Todd found a couple circuits that feed adjacent tenant space. This has been brought up to Perry and Tim to contact their electrician. 10/9/09 WB/Todd to remind Perry or Todd can do the work and bill Perry directly. Post mtg: Perry's electrician has come & disconnected. Item closed. The following items were discussed: Mtg. Item MECHANICAL 1.2 10/2/09 One 4' electric basebd heater - (120V) is planned for Office Bath. Todd/ME and Dave /AS are wondering if this basebd heater is needed? Dino to confirm. 10/9/09 Review with Dino on site today. Post mtg: Dave /AS will install as per plan. Item Closed. 1.3 10/2/09 Office 108 controls - Per Dave, there is nothing in this office to control the rooftop unit. Clarify with Dino, he may want to add another control. So duct heater doesn't come on when in a/c mode. Per Michael, the intent was to make her office a mini zone. The doctor uses her office off hours, evenings and weekends. 10/9/09 Review with Dino on site today. 1.5 10/2/09 Location of cleanout(s) - Confirm with Dino. 10/9/09 Per Paul, cleanout locations were reviewed on site with Jay /L &S. All cleanouts are installed and located in the floor as planned. Item closed. 1.6 10/2/09 Existing Bath vent - has ductwork connecting to adjacent space. It will need to be removed or fire damper added. Michael and Dave think this ductwork is "dead ". To be confirmed w /Perry and removed. 10/9/09 Review with Dino on site today. Post mtg: Dave will check and cap off /re -route if needed. 1.8 10/2/09 Location of shutoff for hose bib - confirm with Dino. 10/9/09 Paul confirmed the shutoff is above the ceiling. Item closed. 1.9 10/2/09 Plumbing venting required at common wall - which is a fire separation wall (one hr separation/one layer 5/8" sheetrock). Procedure Rms 1 & 2 and Bath 118.WB suggested a 3 1/2 " +- chase wall up against fire wall. Per Michael, every inch of open space in Procedure Rms is important for the doctor's practice. Dino to clarify if pipe can go in wall. 10/5/09 Post mtg: Roger confirmed installing vent pipe in fire separation wall is OK w /Larry, the Plumbing Inspector. LG emailed Tony Patillo requesting his review /approval as Building Commissioner. WB awaiting his reply. 1.10 10/2/09 Location of Office 108 wall at jog - Michael to relay exact location of Office 108 /Corridor 121 wall by Friday, 10/9 (prior to start of framing). 10/9/09 Michael gave wall location dimensions to WB. WB forwarded to Monty /framer. Item closed. 2.1 10/9/09 Pipe hangers - Per Paul, spec is overkill for 1" insul copper pipe. Per Michael, Ok for Paul to call Jay /L &S direct, just document decisions. Discuss with Dino on site today. Post mtg: Paul called Jay and was ok to use hanger Paul suggested. 0 7 I/3 Wright Builders, Inc. 48 Bates Street Northampton, MA 01060 Tel: 413 -586 -8287 Fax: 413 -587 -9276 Dr Katherine L. White , 4 Medical Offices Meeting Minutes Date: 10/9/09 Re: Dr. Katherine L. White Medical Offices 39 Carlon Drive Northampton, MA Construction Meeting #2 - 10/9/09 To: Attendees - via email Present: Michael White - Nelligan White Architects PLLC (NWA) Todd Sessions - Martin Electric (ME) Dave Lampron - All Seasons Heating & Air Conditioning (AS) Paul Graham - Paul's Plumbing (PP) Fran Gallo - Francis Gallo Residential Contractor Roger Buzzell, Jim Saucier, Linda Gaudreau - Wright Builders, Inc (WB) Cc: Tony Patillo - Northampton Building Commissioner Dino D'Angelo, Jay Sexton, Joel Patruno - Lindgren & Sharpies (L &S) Perry Messer - Building Owner Bruce Sheible - Westek Architectural Woodworking (WAW) Doug Mercier - Mercier Carpet (MC) Walter Schmalenberg - Greenfield Glass (GG) Owen Lococo - Lococo Painting (LP) Mark Ledwell - Wright Builders, Inc (WB) By: Linda Gaudreau - Wright Builders, Inc. Health & Safety / DEP: 10/9/09 No DEP or Safety issues. Work Progress: Slab plumbing, inspections, backfill & concrete pour complete. Masonry window openings started. To be complete by 10/13/09. Framing & rough plumbing ongoing week of 10/12/09 Submittals returned & material being ordered. y w Operations Manager Wright Builders, Inc. 48 Bates St. Northampton, MA 01060 Ph — 413 - 586 -8287 Fax — 413 - 587 -9276 lgaudreau @wright- builders.com 2 Anthony Patillo From: Linda Gaudreau [Iaudreau @wright- builders.com] Sent: Friday, October 02, 2009 8:50 AM To: Anthony Patillo Subject: Re: Katherine L. White MD PC Medical Offices here it is...must've typed your email address in incorrectly - he sent it on Tues, 9/29 Michael White wrote: > Mr. Patillo & Mr. Lepine, > I understand from Wright Builders that we are required to designate > Men and Women bathrooms for the two public corridor bathrooms on the > subject project. Our intention was to provide two unisex rooms. If > that is not allowed, this email is to confirm that we will designate > one Women and one Men. > Please let me know if you need any confirmation other than this. Thank > you for your prompt review of our documents. > T. Michael White, AIA > /T. Michael White, AIA/ > Nelligan White Architects PLLC > /20 West 20 / ^ /th/ / / /Street // // / /11 / ^ /th/ / / /Floor/ > /New York, New York 10011/// > /212.675.0500// / > /tmw0nelliganwhite.com/ < mailto :tmw()nelliganwhite.com> // > /www.nelliganwhite.com/ < http:// www .nelliganwhitearchitects.com> // > / >/ > /62 Revell Avenue /// > /Northampton, MA 01060/// > /telephone 413.341.3449/// > /cell //646.489.5672/ > /tmwarch(acomcast.net/ <mailto:tmwarch(thcomcast.net> Linda Gaudreau NARRATIVE REPORT FOR FIRE PROTECTION & ALARM SYSTEMS AT Katherine L. White, MC, PC Medical Offices 39 Carlon Drive Northampton, MA 01060 PREPARED BY: LINDGREN & SHARPLES, P.C. CONSULTING ENGINEERS 435 COTTAGE STREET, SUITE 1 SPRINGFIELD, MA 01104 -4005 TEL. 413 - 732 -4336 September 11, 2009 • 3404.19 Energy Conservation Measures New work will maintain or increase energy conservation End of Review fi • 1014.0 Minimum Number of Exits Allowed 1 1 Table Occupancy B, Max load 50 Max load 24 1014.1 1203.1 Ventilation Requirement Mechanical or natural Mechanical CHAPTER 34: Alteration, Addition, and Change of Use of Existing Buildings 3400.3 Applicability Will continue Use Group B 3400.4 Non - conforming egress Existing Existing is conforming therefore not applicable 3400.5 Hazardous Means of Egress Existing Existing does not appear to be hazardous. New work and modifications will comply. 3400.6 Unsafe LightingNentilation Existing Existing does not appear to be unsafe or inadequate. New work and modifications will comply. 3402.1.1 Existing Building Investigation and Will comply Evaluation for Building Permit Application 3402.1.2 Investigation and Evaluation Submittal This report will be submitted for consideration 3404.3 New Building Systems will conform to New work and 780 CMR for new construction modifications will comply with 780 CMR 3404.4 Alterations and Repairs New work and modifications will comply. 3404.5 Means of Egress in compliance with 1 exit exist and will be 1014.0 requires 1 maintained 3404.6 Exit Capacity to comply with 1005.1 New work and modifications will comply. 3404.7 Exit Sign and Lighting to comply with New work and 1023 modifications will comply. 3404.9 Height and Area Limitations to comply Existing complies and with 504, 505, 506 there is no change in height or area. 3404.12 Fire Protection Systems to comply No change in Use with 9 Group. New work and modifications will comply. 3404.18 Accessibility for Persons with The existing complies Disability and all new work and modifications will comply. DETAILED CODE SUMMARY The following is a detailed summary of Code related items as regulated by 780 CMR including Chapter 34 for alterations to an existing building: Zoning: The existing zoning classification for the site is B (Business) and this project will not request any change. Occupant Load: The occupant load allowed for these medical offices is 24 persons based on the 2370 s.f. being partially modified as part of this project. The actual occupant load will more likely be 15 —20 maximum. Construction Classification: The existing construction is 2B and this project intends on matching or improving this classification. Section Item Required Proposed 304.1 Use Group B Existing to remain. 503.1 Height and Area Limitations for 4 stories and 23,000 Existing tenancy 2,370 Table 503 Construction Classification 2B s.f. max s.f. will not be increased 602.1 Protection of Exterior Walls >10ft 0 hour Existing to remain. Table 602 602.2 Protection of Structural Members 0 hour Existing to remain. Table 601 602.2 Roof /Clg, Flr /Clg Assemblies 0 hour Existing to remain. Table 601 704.8 Exterior Wall Allowable Area of >5ft - I Oft = 10% 6% (side) Openings - Unprotected >1Oft — 15ft = 15% 1.3% no change (front) 803.5 Interior finish requirements Table 803.5 Corridors to exits Class B Class B Non Sprink. Rooms or spaces Class C Class C 804.5.1 Interior Floor Finish - Use Group B Class II or better Class II or better 903.2.2 Fire Suppression System Requirement Not required if area None existing. Existing less than 12,000sf Bldg. area approx 9,000sf 906.2 Portable Fire Extinguisher Required Will comply 1003.2 Use Group B Ceiling Heights in exit >7' -0" Ceiling height 9' -0" access and occupiable rooms provided 1004.1 Maximum Floor Area per Occupant in 100 g.s.f. = 24 15 — 20 actual Use Group B 1005.1 Exit Capacity minimum width in Use 0.2 required 4.8" and 48" actual Group B without sprinklers 36" allowed under 1011.3 1011.3 Path of Egress Travel Distance with 100ft 80ft max. one means of egress BACKGROUND INFORMATION: 39 Carlon Drive in Northampton is an existing single story masonry and steel building approximately 16' high. The building contains business offices and will continue that use. The proposed project comprises a new renovation of the existing tenant space to the southwestern corner of the building with the existing entry on Carlon Drive. The building contains no basement and is at grade. The building is serviced and surrounded by its parking lot for 30 cars to the north and east with appropriate existing signage and access points at grade. There is an adjoining parking (not yet paved) lot to the west. The proposed medical offices are expected to draw on the Northampton local area for the bulk of its patients. PROPOSED NEW MEDICAL OFFICE: The new medical offices for Dr. Katherine L. White, MD, PC are for her medical practice that specializes in dermatology. Routine examinations of patients and dermatological procedures will be performed which will occur during normal working hours in the five new exam rooms and two new procedure rooms. The new medical offices will replace the existing offices on the first floor of this building and will enhance the natural lighting by the addition of six new windows in the west facade. The new offices will maintain the existing tenancy area of approximately 2,370 square feet and will comply with all code requirements including fire alarm, egress, ADA compliance, etc, and will maintain the same entry and exit locations. EXECUTIVE SUMMARY: The new medical office that constitutes this renovation, will replace the current offices in this tenancy of the building. Zoning approval for use of the subject office space for medical office was obtained by the Owner on 12 -17 -2008, Hearing No., PLN- 2009 -0012. The existing internal offices will be demolished and the new medical offices constructed as code compliant. No exiting discharge or exterior path of travel will be altered; no existing code compliant components that may remain will be degraded. The new medical offices will maintain or upgrade all existing fire and smoke separations, fire suppression system, exiting lights, exiting paths, contain only metal wall stud framing and Class II or B/C interior finish material, and install fire safing at all penetrations as part of this project. No new services will be required for this project, and there will be no decrease in the public safety, health, and general welfare as a result of this tenancy renovation. 780 CMR NARRATIVE In Compliance with Chapter 34 Dr. Katherine L. White Medical Offices 39 Carlon Drive Northampton, MA 01060 Owner Messer Investments, Inc. 306 King Street Northampton, MA 01060 (413) 585 -8500 Architect Nelligan White Architects PLLC 20 West 20 Street New York, NY 10011 (212) 675 -0500 Engineer Lindgren & Sharples, P.C. 435 Cottage Street Springfield, MA 01104 -4005 Tel: (413) 732 -4336. Fax: (413) 731 -0786 September 14, 2009 Initiation of the fire alarm sequence of events will immediately and simultaneously activate all horns and visual units in the building to notify occupants, and perform all activities as programmed, including annunciator interaction. The red exterior strobe shall be engaged. The Fire Alarm control panel shall send an alarm signal via a digital 2 -line auto - dialer to the 24 -hour UL listed monitoring station. The monitoring station shall sequentially notify the appropriate responders including the Town of Northampton Fire Department. The Fire Alarm System reset button returns the system to its normal state. Display messages shall provide operator assurance of the sequential steps as they occur. The Fire Alarm Control Panel is equipped with a 24 -hour battery back up. The Fire Alarm Control Panel is equipped with visible and audible signals to indicate alarm and trouble conditions. 3.0 Test Criteria: All features, devices, components, and modes of operation shall be tested for acceptance in accordance with the code and NFPA 72. Smoke detectors shall be activated using a magnet per the manufacturer's recommendations. All pull stations shall be activated by opening and upon activation of each device; the Fire Alarm System shall be checked for proper operation including annunciation at the Fire Alarm Control Panel and transmission of an alarm signal to the Fire Department. Proper operation in the emergency power mode shall be demonstrated as well as a check of supervision circuits for opens and shorts. * ** End of Basis of Design Narrative * ** L &S 1774 Page 5 B. The existing fire alarm system features a zone type Fire Alarm Control Panel (FACP) by EST - Fireshield. The FACP is located in this tennant's mechanical room and serves the entire building. The emergency (battery- backup) power supply has been sized to be adequate for both 24 hours of monitoring and a minimum of 15 minutes of alarm and is located at the FACP. C. A fire alarm annunciator is located at the entry vestibule from Carlon Street. This is the Fire Department primary response point and also features an exterior red strobe interlocked to the alarm, and key box. A digital communicator is located adjacent the FACP for external monitoring of the system. D. System connected smoke detectors will be installed at the fire alarm control panel and elsewhere as required by code. The Activation of any system smoke will initiate the fire alarm system sequence of events. E. Manual pull stations are required to be installed and located within 5 feet of each exit door and at all entry points leading to an egress way and shall initiate the fire alarm system sequence of events. F. Fire alarm system notification and signaling devices in this building will include the following features: 1. Audio notification devices in the form of Horn/Strobes to be installed as shown on plans. It is the intent of this design that audible notification devices achieve sound pressure levels of 15 dba above ambient sound levels in all areas of the building in compliance with chapter 4 -3 of NFPA 72. 2. Visual notification devices in the form of Horn/Strobes and Strobe only appliances to be installed as shown on the plans. It is the intent of this design that visual notification devices achieve appropriate coverage for public areas in compliance chapter 4 -4 of NFPA 72. G. System connected duct smoke detectors are not required to be installed at HVAC units as dictated by air handling capacity of the units. H. This project does not include any special design considerations or anticipated deviations from the code requirements. 2.0. Sequence of Operation: A. This fire alarm system is designed to detect fires normally associated with this type of facility. The system can be activated manually through the use of manual pull stations. The system shall be activated automatically via smoke detector. In any of these events the system shall initiate the fire alarm sequence of events. L &S 1774 Page 4 SECTION 2 - APPLICABLE LAWS, REGULATIONS & STANDARDS Systems were designed in compliance with the following: 1. 780 CMR 9, "Fire Protection Systems ". 2. NFPA 13 — 2007, "Installation of Sprinkler Systems ". 3. NFPA 72 — 2007 "National Fire Alarm Code ". 4. 521 CMR 40, "Architectural Access Board 5. 527 CMR 24 6. 780 cmr34 "Existing Buildings" SECTION 3 - DESIGN RESPONSIBILITY Fire Alarm System Lindgren & Sharpes, P.C. Consulting Engineers 435 Cottage Street Springfield, MA 01104 -4005 Phone: 413 - 732 -4336 SECTION 4 — DESIGN METHODOLOGY 1.0 The project consists of minor renovations within the existing building. Under this contract all areas affected by renovation work will be evaluated for code compliance, fire alarm system modification will be made as well as upgrades to much of the existing detection and notification systems. New fire alarm system devices will be addressable and compatible with the existing system.There is no requirement for automatic sprinklers in the renovated tenant space. SECTION 5 - FIRE PROTECTION 1.0 Basis of Design The existing building is not served by an automatic fire protection system and based upon the use group and size of the building, as well as the type of renovation planned, no sprinklers are required. SECTION 5- FIRE ALARM SYSTEMS 1.0 Basis of Design A. New fire alarm system work associated with this project includes the removal of all zone type initiation devices, as well as notification appliances from the tenant space. L &S 1774 Page 3 Tie Co�w...wt4€ 44 K4444444414 N ee, 4 044 4 de 1 P 4& t II t Dec A � hcc, 1301 NItt. . toots., ti444,141444414 02108 -1618 Nom (617) 7273200 fed2 (617) -5732 CONSTRUCTION CONTROL DOCUMENT Project Title: Katherine L. White, MC, PC Medical Offices Date: September 16, 2009 Project Location: 394 Carlon Drive, Northampton, Massachusetts Scope of Project: Renovations to existing space to accommodate new medical offices In accordance with SECTION 116.0 - 116.4.2 of the 7th edition of the Massachusetts State Building Code : I, Charles P. Sharpies, . Mass. Registration Number 28940 being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Entire Project [ ] Architectural [ ] Structural [ X ] Mechanical [ ] Fire Protection [ ] Electrical [ ] Other (specify) for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services and be present on the construction site on a regular and periodic basis to determine that the work is proceeding in accordance with the documents approved by the building permit and shall be responsible for the following as specified in section 116.2.2: 1. Review of shop drawings, samples and other submittals of the contractor as required by the construction contract documents as submitted for the building permit, and approval for the conformance to the design concept. 2. Review and approval of the quality control procedures for all code - required controlled materials. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine, in general, if the work is being performed in a manner consistent with the construction documents. I shall submit periodically, in a form acceptable to the building official, a progress report together with pertinent comments. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory completion and readiness of the project for occupancy. Signature and Seal of registered professional: ` ,"° ' '' g g p `' CHARLE S , ' � \ p ( SH ARPLES (v f, (4' �� 20940 ! i 0 l , 4fe Tic C Kroso.444404 DAtio40444 P 4&e e � a 1301 5� � osslos, M 0210$1615 Nom 607)7n-3200 Fog (617) 7D-S732 CONSTRUCTION CONTROL DOCUMENT Project Title: Katherine L. White, MC, PC Medical Offices Date: September 16, 2009 Project Location: 394 Carlon Drive, Northampton. Massachusetts Scope of Project: Renovations to existing space to accommodate new medical offices In accordance with SECTION 116.0 - 116.4.2 of the 7th edition of the Massachusetts State Building Code : I, Mark W. Felgate, . Mass. Registration Number 47531 being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Entire Project [ ] Architectural [ ] Structural [ ] Mechanical [ ] Fire Protection [ X ] Electrical [ ] Other (specify) for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services and be present on the construction site on a regular and periodic basis to determine that the work is proceeding in accordance with the documents approved by the building permit and shall be responsible for the following as specified in section 116.2.2: 1. Review of shop drawings, samples and other submittals of the contractor as required by the construction contract documents as submitted for the building permit, and approval for the conformance to the design concept. 2. Review and approval of the quality control procedures for all code - required controlled materials. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine, in general, if the work is being performed in a manner consistent with the construction documents. I shall submit periodically, in a form acceptable to the building official, a progress report together with pertinent comments. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory corn • letion and readiness of the project for occupancy. Signature and Seal of registered professional: . MARK W cy I FELGATE r C C,, ELECTRICAL 4 No. 47531 • • 9F„ISTE eglw Wommonavailivo, eliatioadmetwilke O 4 t yastief ester glace; gloosw7307 lk on, eikaoaac az et6' 02408 -7678 Ntoste/ 727 -3200 ,Fax1677) 727 -5782 CONSTRUCTION CONTROL DOCUMENT Project Title: Katherine L. White M.D. PC Medical Office Date: 09.15.2009 Project Location: Carlon Avenue Northampton Massachusetts 06010 _ Scope of Project: Renovation of Medical Office • In accordance with SECTION 116.0 - 116.4.2 of the 6th edition of the Massachusetts State Building Code : I, Bruce G. Nelligan Mass. Registration Number 11158 being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: [ ] Entire Project [x] Architectural [ ] Structural [ ] Mechanical [ ] Fire Protection [ ] Electrical [ ] Other (specify) for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services and be present on the construction site on a regular and periodic basis to determine that the work is proceeding in accordance with the documents approved by the building permit and shall be responsible for the following as specified in section 116.2.2: 1. Review of shop drawings, samples and other submittals of the contractor as required by the construction contract documents as submitted for the building permit, and approval for the conformance to the design concept. 2. Review and approval of the quality control procedures for all code - required controlled materials. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with the progress and quality of the work and to determine, in general, if the work is being performed in a manner consistent with the construction documents. I shall submit periodically, in a form acceptable to the building official, a progress report together with pertinent comments. Upon completion of the work, I shall submit ' .'ng official a final report as to the satisfactory completion and readiness of the project for occupanc . oat.v ARc,, Signature and Seal of registered professional: �4 � N ejir b N ''s r %1 t x: • RYAN S. HELLWIG, PE • STRUCTURAL ENGINEER • August 24, 2009 Michael White Nelligan, White Architects 20 West 20 Street New York, NY 10011 Re: Medical Offices for Katherine White 39 Carlon Drive Northampton, MA LINTEL SCHEDULE Design Criteria: 8" CMU Wall ASTM A36 Steel Angles One Lintel for Each 4" Wythe of Masonry Angles Placed Long Leg Vertical 6 Inches Bearing at Each End of Lintel Masonry Opening Head is 6 ft below roof bar joist bearing Masonry Opening Lintel Size 4ft.max. L3- 1/2x3 - 1/2x5/.16 6ft.max. L 5 x 3-1/2 x 5/16 . RYAN S. C HELLWIG ■ , v STRUCTURAL Z No. A I • /C‘ • Y • 28 ALDRICH STREET • NORTHAMPTON, MA 01060 • • VOICE 413 - 584 -HLWG (4594) • FAX 413 - 584 - HLWFax (4593) • The Commonwealth ofMassachusetts Department of Industrial Accidents --1 Office of Investigations ; 600 Washington Street Boston, MA 02111 WWW. mass.gov /dia Workers' Compensation Insurance Affidavit: Builders/ Contractors /Electricians/Plumbers Applicant Information 't' Please Print Leeibly Name (Business/Organization /Individual): W ervi.)( e I Mk"' Address: rg Pit-1- ( C1 ' City /State /Zip: (Yb tom^ j) /tik Phone #: ' e" Are you an employer? Check the appropriate box: Type of project (required): ' 1.] I am a employer with S 4. ❑ I am a general contractor and I employees (full and/or part- time).* have hired the sub - contractors 6. [] New construction 2. ❑ I am a sole proprietor or partner- listed on the attached sheet. 7.,Remodeiing ship and have no employees These sub - contractors have 8. ❑ Demolition working for me in any capacity. employees and have workers' 9. 0 Building addition [No workers' comp. insurance comp. insurance.$ required.] 5. ❑ We are a corporation and its 10.0 Electrical repairs or additions 3. ❑ I am a homeowner doing all work officers have exercised their 11.0 Plumbing repairs or additions myself. [No workers' comp. right of exemption per MGL 12.0 Roof repairs insurance required.] t c. 152, §1(4), and we have no • employees. [No workers' 13.0 Other comp. insurance required.] *Any applicant that checks box #1 must also fill out the section below showing their workers' compensation policy information. t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such. $Contractors that check this box must attached an additional sheet showing the name of the sub - contractors and state whether or not those entities have employees. If the sub - contractors have employees, they must provide their workers' comp. policy number. I am an employer that is providing workers' compensation insurance for my employees. Below is the policy and job site information. r Insurance Company Name:. ( tl" eNe1 3 11 fANec Policy # or Self-ins. Lic. #: W G L v0t 3')I t Expiration Date: � /1 0 Job Site Address: 3/ e4P-0 NO A,M ('To I" City/State /Zip: / 0 4 , Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date). Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a fine up to $1,500.00 and/or one -year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of Investigations of the DIA for insurance coverage verification. I do hereby certify under the pains and pen flies of perjur y the information provided above is true and correct. Sienature: 1"b telem 1I.. `,6 t at Date: C t K/D I f Phone #: ° Official use only. Do not write in this area, to be completed by city or town official City or Town: Permit/License # Issuing Authority (circle one): 1. Board of Health 2. Building Department 3. City/Town Clerk 4. Electrical Inspector 5. Plumbing Inspector 6. Other Contact Person: _ Phone #: .. ■ Version1.7 Commercial Building Permit May 15, 2000 SECTION 10- STRUCTURAL PEER REVIEW (780.CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes 0 No 38( SECTION 11 - OWNER AUTHORIZATION -TO BE COMPLETED -WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT : MeCt÷ I IV t j N ' C.. 1 : as Owner of the subject property hereby authorize r ...._ . . ,, . . . _ _ ________ .... _ _ _ . .__.# • i to act on m • - alt, in al m Av atter relative to work authorized by this building permit application. _____ Al 1 as "P ,-.:....4.„...„ - Signature of Ov e V Date &itr _AP Li gc-- . _ j , as Ownelkuthorizedi gen hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge na D lief. Signed under tile pains and penalties of pegury. .': 0 - 44-- 4vv _ p. _ , - 1 ._., . . ,. Print Name l 'k- -- [I: W • ill ftit4-- pn,ve- Signature of Owner/Agent Date SECTION 12 - CONSTRUCTION SERVICES 10.1 Licensed Construction Supervisor: Not Applicable El__ 11;141- 1) ---- .1: 4-"--- A 4-' rte3f767. Name of License Holder :1,___ ,_.. . .., .. — • .. •._ License Ny_mb r -- ________ 1 'ft Ukie"Cr ---- F It Address tk-- Expiration Date e-vhe-- 6 (n4/614- -- CIL i 1 1 Signature Telephone SECTION 13 -WORKERS! COMPENSATION INSURANCE AFFIDAVIT;(MALC,. § 2 Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the building permit. Signed Affidavit Attached Yes Igi No 0 .., Version I.7 Commercial Building Permit May 15, 2000 SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTIONSERVICES •- FOR BUILDINGS AND STRUCTURES SUBJECT TO . CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN.35,000 C.F. OF ENCLOSED SPACE) 9.1 Registered Architect: -. —_ -- i Not Applicable • /v5LL /6 A/` 1•✓ir� T�I�CHiTE p L L G _ _ I Name (Registrant) t gut G _ nl� 61-1-1 6-4/4 — — j Registration Nu ber Addres ` ZE3 ?V A I - - - c/ 3 / X/ • k r ti!°f° M — - Expion Date - i gnature Telephone 9:2 Registered Professional Engineer(s): Name Area of Responsibility • _ Address Registration Number 7 e..erT IZ ¢33, ! Signature Telephone Expiration Data Name Area of Responsibility f tNIA -A-1 Fier LZJf _._ _. _._._._-- ___- _.__._.. ____ r_.__— Address > A4, 7Pi . S ez L (l i nki__ _qt /4 or t0J ?G` Re ii stration Number. Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number _ __ Signature Telephone Expiration Date Name Area of Responsibility Add[es Registration Number _ Signature Telephone Expiration Date 9.3 General Contractor . ! . H.0 - • t `� Z. > 1...1` ___ ___ __ -__ _______.._.._.. Not Applicable Company Na Responsible In Charge of Construction �� �� //a Address Signature Telephone , i • i Version1.7 Commercial Building Permit May 15, 2000 8. NORTHAMPTON. ZONING: Existing Proposed Required by Zoning This column to be filled in by Building Department Lot Size .'? _ ._ I r 7.S i 7 ... __- ! Frontage �.. _ ___..= Setbacks Front - 1:111 (_ Side L:..__:.- R:11101 LE L] R:<- -_m i__....,._ ._._ ._.t Rear . 'Q] - -- �� Noe r--n._Tl Building Height Bldg. Square Footage r % ' L - ' ; - ^ Open Space Footage C---] % , (Lot area minus bldg & paved f .,z .._ _ 7 f_._ - - �.-t ] parking) # of Parking Spaces I1 � ---I Fill: i ■ (volume & Location) _ -- - -° _..�. _ A. Has a Special Permit /Variance /Finding ever been issued for /on the site? NO 0 DONT KNOW Q YES er Felt art; . IF YES, date issued: lr)T kNptt. IF YES: Was the permit recorded at the Registry of Deeds? NO Q DONT KNOW (F) YES Q t IF YES: enter Book r Page — _ and/or Document # . B. Does the site contain a brook, body of water or wetlands? NO ei DONT KNOW Q YES 0 W YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained Obtained , Date Issued: 1 1 C. Do any signs exist on the property? YES e( NO Q IF YES, describe size, type and location: Z Ow ft.. t .S, pUS D. Are there any proposed changes to or additions of signs intended for the property ? YES e5 NO Q IF YES, describe size, type and location: te 6 $ fit! + E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan that will disturb over 1 acre? YES Q NO e . IF YES, then a Northampton Storm Water Management Permit from the DPW is required. • Versionl.7 Commercial Building Permit May 15, 2000 • SECTION 4- CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE r — Interior Alterations gl Existing Wall Signs ❑ Demolition ❑ Repairs ❑ Additions ❑ Accessory Building ❑ Exterior Alteration 121 Existing Ground Sign ❑ New Signs 0 Roofing ❑ Change of Use ❑ Other ❑ Brief Description Enter a brief description here. Of Proposed Work: 3 C d7f F-i iJ Wt ( U` SECTION 5 - USE GROUP AND CONSTRUCTION TYPE " USE GROUP (Check as applicable) CONSTRUCTION TYPE A Assembly A -1 ❑ A -2 ❑ A -3 ❑ 1A 1 ❑ A -4 ❑ A -5 ❑ 1B ❑ B Business Ee 2A ❑ E Educational ❑ 213 ' I ig . F Factory 0 F-1 ❑ F -2 ❑ 2C ❑ H High Hazard ❑ 3A I ❑ I Institutional ❑ I-1 ❑ 1-2 ❑ 1-3 ❑ 3B ❑ M Mercantile ❑ 4 ❑ R Residential ❑ R -1 ❑ R -2 ❑ R -3 ❑ 5A ❑ S Storage ❑ 5 -1 ❑ 5 -2 ❑ 5B ❑ U Utility ❑ Specify: r 1 M Mixed Use ❑ Specify: r I S Special Use ❑ Specify: _ -__ _�- �= T .._ � = ..T_,.._ J COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING'RENOVATIONS - °ADDITIONS AND /OR CHANGE IN. USE Existing Use Group: 1. ! ! S_.:...L !.._.. I Proposed Use Group: _. _— i Existing Hazard index 780 CMR 34): ;.__ .:____-__-_......__-_..______! Proposed Hazard index 780 CMR 34): r__________________ .,— _...__Tf SECTION 6 BUILDING HEIGHT AND AREA /b 0 ' t flG.t goe-e- so rr` BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION Z - OFFICE U ONLY Floor Area per Floor (sf) y � I 1 st -- - -- °- ` � 1st ! / .. ' LR-t9� _ . -- .� 2nd ( _ _ �, 2`d, — `— 3,d — — _ 3r1 ____ _ _.. _ t — 4th I Total Area (sf) 4 r 1 Total Proposed New Construction (sf) 1 Total Height (ft) _.. i Total Height ft i 1 7. Water S ppiy (M.G.L. c. 40, § 54) 7.1 Flood-Zone Information: 7.3 Sewage D' posai System: Public ( Private 1:1 Zone _,________-J Outside Flood Zone Municipal Sewage site disposal system{] . ' . , Versionl.7 Commercial Building Permit May 15, 2000 _ ; ::PPP , P 119 1g01#0 9 910 1 :::- ., ::5!.5'..!,::,t,'-'-'• (1,: City Ot"Northampton Status uildfrig Department Oftt?.:ClifigrP)qt014::'F-T.'''"'''''''''''---',',:-:::,::-:::,-;:...7,-ifo.i,,,,].;. c< . /i12 Main Street ig4We6V81)Oililf;iii:4:;I41:.0?...::;:-.F , _ww,;:wa,*-,,,,,,:::„.2 . -,./ : .,A ;: -. , ,s .: :*.: :: ,=,, 77:?..4;:: . : , i , Room 100 waterAiven parabitittf-.----: - - Northampton, MA 01060 Wigegi1;tgfaiik:::oraK;04--5--E,F.-:?:1::,...)-..1:=:,'''',. «C _,=;: - , - '.:;: - ...1 . : - s ' : , phone 413-587-1240 Fax 413-587-1272 viotisite , ouler.40eify. -,-----',, - ',-,',--;),,,,,:::..,-, ii: APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, CHANGE THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 - SITE INFORMATION This section to be completed by office . 1.1 Property Address: .-?" C-#41z6oxi Pta Ve- Map - : Lot Unit ' 42 r rat I itfriA eV() j Zone 6 en . Overlay District • - . . „,.Eliri Si; Ii14116t CB District SECTION 2 - PROPERTY OWNERSHIP/AUTHORIZED AGENT 2.1 Owner of Record: [ 50 .f2_ V. tVVL4J. __51 A- -1-i-r'- Name (Print) Current Marling Address: 0. t 7/7 / c FR _..,.... . 4 -- 5 .. / Signature K al.....e_i__ A.._ Telephone 111, 2.2 Authorized Act t: , ,.....„., ___________ _____ itemo,fritoThr ji 1 tec Sal" Iv 0 ____, : t 1 v P ) ht( I Lemke-6r ...ft(_-.... ,_ ___ -------4---- -----— Name (Print) Current Maiiirigikddressi ___ .,,, , 1 tj r-/ . r .f.._9 ow - Signature P-efty2-- Telephone SECTION 3 - ESTIMATED CONSTRUCTION COSTS Item Estimated Cost (Dollars) to be .. ., . - - Official Use.Only completed by permit applicant . -- _:: ._. _. 1. Building 7------- ---- ,7, --, --",: .(a.). Building Permit Fee .. .. I L _ ____ ___,// lio f..‘,':.'. if. .- .,---. ,. — ' • r: ', ' ' - , 2, Electrical I -------- 7 1 (b) Estimated Total Poet of i . 1-5, etr ,., e'l+ • :- Construction-from (6) 1,------------- .- - - --- ...... _A 3. PlUmbing ' --- ------ --- •:BUilditigF'dernit Fee 1 ! 4. Mechanical (HVAC) - ; . 5 3-4 ' " 1 5. Fire Protection ., 5 = / s 3+ ) 08 )33 1 9 6. To .1 I 65 ,5 , ei Check NUmber / //0 This_Section For Official.Use Only. . • Building Permit mber •Date- Issued Signature: Building Commissioner/Inspector of Buildings Date ... File # BP- 2010 -0315 APPLICANT /CONTACT PERSON NELLIGAN WHITE ARCHITECTS PLLC ADDRESS/PHONE 20 W 20TH ST NEW YORK (212) 675 -0500 PROPERTY LOCATION 39 CARLON DR MAP 24B PARCEL 046 001 ZONE HB(100)/ THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out /�.5� �� 1 � Fee Paid 7 Typeof Construction: CREATE MEDICAL OFFICES, ADD WINDOWS TO WEST WALL New Construction Non Structural interior renovations Addition to Existing I Accessory Structure Building Plans Included: R , Owner/ Statement or License JI&U2‘11241140 3 sets of Plans / Plot Plan THE FO LOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INF ATION PRESENTED: Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay /��.✓ / d L Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information. ` # 1 = BP- 2010 -0315 GIS #: COMMONWEALTH OF MASSACHUSETTS xs * t CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: BUILDING PERMIT Permit # BP- 2010 -0315 Project # JS- 2010 - 000420 Est. Cost: $165500.00 Fee: $993.00 RMISSION IS HEREBY GRANTED TO: Const. Class: 2B Con ctor: License: Use Group: B WRIG T BUILDERS 84280 Lot Size(sq. ft.): 31842.36 Owner: MESSER INVESTMENTS INC Zoning: HB(100)/ Applicant: NELLIGAN WHITE ARCHITECTS PLLC AT: 39 CARLON DR Applicant Address: Phone: Insurance: 20 W 20TH ST (212) 675 -0500 Workers Compensation NEW YORKNY10011 ISSUED ON:10/2/2009 0:00:00 TO PERFORM THE FOLLOWING WORK:CREATE MEDICAL OFFICES, ADD WINDOWS TO WEST WALL POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House # Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace /Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 10/2/2009 0:00:00 $993.00 212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272 Building Commissioner - Anthony Patillo