39-060 Antenna January 14, 2010
162 Ft Monopole Tower Structural Analysis CCI BU No 800530
Project Number 312710, Application 93192, Revision 3 Page 5
4) ANALYSIS RESULTS
Table 5 - Section Capacity (Summary)
Section ( Elevation (ft) Component Critical SF *P_ allow �
Size
No. Type Element (K) Capacity
L1 :162 - 113.227 ; Pole TP25.7021x13x0.1875 1 -5.68 i 759.47 73.0 Pass
L2 113227 Pole TP32.6066x24.36x0.3125 2 -9.23 1604.71 56.1 Pass
84.7969
84.7969 -
L3 1 42.1484 Pole TP42.9634x30.8077x0.375 3 -16.95 2541.78 51.3 Pass
L4 1 42.1484 - 0 Pole TP53x40.7025x0.375 4 -19.10 2588.38 53.2 Pass
Summary
Pole (L1) i 73.0 Pass
1 Rating = i 73.0 i Pass
Table 6 - Tower Component Stresses vs. Capacity - LC1
Notes Component Elevation (ft) % Capacity Pass / Fail
1 1 Anchor Rods 1 0 43.9 Pass
1 Base Plate 0 58.6 I Pass 1
1 I Base Foundation ? 0 51.3 i Pass
Structure Rating (max from all components) = 73%
Notes:
1) See additional documentation in "Appendix C — Additional Calculations" for calculations supporting the % capacity
consumed.
4.1) Recommendations
The tower and its foundation have sufficient capacity to carry the existing, reserved, and proposed
loads. No modifications are required at this time.
RISATower Report - version 5.3.1.0
January 14, 2010
162 Ft Monopole Tower Structural Analysis CCI BU No 800530
Project Number 312710, Application 93192, Revision 3 Page 4
Notes:
1) Existing Equipment
2) Reserved Equipment
3) Equipment to be Removed, Not used in this Analysis
Table 3 - Design Antenna and Cable Information
Center Number Number Feed
Mounting Line Antenna
of Antenna Model of Feed Line
Level (ft) Elevation Antennas Manufacturer Lines Size (in)
(ft)
160 160 2 Decibel DB2246 2 1 -5/8
150 150 12 j Swedcom ALP 9212 [ 12 f 1-5/8
140 140 [ 12 j Swedcom ALP 9212 12 [ 1 -5/8
130 130 i 12 { Swedcom ALP 9212 12 1 -5/8
120 120 I 12 Swedcom ALP 9212 s 12 1-5/8
110 110 12 € Swedcom ALP 9212 12 1 -5/8
3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
Document Remarks Reference Source
4- GEOTECHNICAL REPORTS j Dr. Clarence Welti, P.E., P.C. `, 834886 CCISITES
4 -TOWER FOUNDATION EEI i 834883 CCISITES
DRAWINGS /DESIGN /SPECS
4 -TOWER
AW NGS MANUFACTURER EEI 834878 d CCISITES
4 -TOWER STRUCTURAL
EEI 627272 CCISITES I
ANALYSIS REPORTS
3.1) Analysis Method
RISATower (version 5.3.1.0), a commercially available analysis software package, was used to create
a three - dimensional model of the tower and calculate member stresses for various loading cases.
Selected output from the analysis is included in Appendix A.
3.2) Assumptions
1) Tower and structures were built in accordance with the manufacturer's specifications.
2) The tower and structures have been maintained in accordance with the manufacturer's
specification.
3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings.
4) When applicable, transmission cables are considered as structural components for calculating
wind loads as allowed by TIA/EIA- 222 -F.
This analysis may be affected if any assumptions are not valid or have been made in error. Crown
Castle should be notified to determine the effect on the structural integrity of the tower.
RISATower Report - version 5.3.1.0
January 14, 2010
162 Ft Monopole Tower Structural Analysis CCI BU No 800530
Project Number 312710, Application 93192, Revision 3 Page 3
1) INTRODUCTION
This tower is a 162 ft Monopole tower designed by ENGINEERED ENDEAVORS, INC. in May of 2000. The
tower was originally designed for a wind speed of 75 mph per TIA/EIA- 222 -F.
2) ANALYSIS CRITERIA
The structural analysis was performed for this tower in accordance with the requirements of TIA/EIA -222 -F
Structural Standards for Steel Antenna Towers and Antenna Supporting Structures using a fastest mile wind
speed of 75 mph with no ice, 65 mph with 0.5 inch ice thickness and 50 mph under service loads.
Table 1 - Proposed Antenna and Cable Information
Center Number Number Feed
Mounting Line of Antenna Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size (in)
(ft)
f I 3 ante) i BXA-185063/8CFx2 w/ s 1
Mount Pipe
2 j antel BXA- 70063 /6CF w / Mount ;
I
I Pipe t
LPA- 80063/4CF w/ Mounts
152 153 4 antel Pipe i - _ _
j 2 decibel DB846F65ZAXY w/ Mount'
Pipe '
{ ( APX75- 866514 -CTO w/
3 1 rfs celwave
s j Mount Pipe
I C 6 rfs celwave FDGW5504/1 S -3 1 ,
Table 2 - Existing and Reserved Antenna and Cable Information
Center Number Number Feed
Mounting Line Antenna
of Antenna Model of Feed Line Note
Level (ft) Elevation Antennas Manufacturer Lines Size (in)
(ft) ,
1 telewave I ANT150F2
158 160 !Side Arm Mount [SO 701 - 1 7/8 2
1 tower mounts ' 1]
9 antel } WPA 80090/4CF w/
, Mount Pip e
( DB948F85T2E -M w/ 1 - - 3
152 153 6 decibel ( Mount Pipe I
3 ; generic I TMA _.____ °
1 gps ' GPS_RESERVED I 1 1/2
152 1 1 tower mounts 'Platform Mount [LP 601-1]' i 12 1 -5/8 1
6 kathrein 782 -10250 (
6 kathrein
142 ( 12 kathrein 800 10 122 860V10025 nt Pipe
139 12 1-5/8 1
6 powerwave LGP2140X 4
technologies I
139 1 ! tower mounts Platform Mount [LP 601 -1][
132 132 3 kathrein 742 213 w/ Mount Pipe
kathrein 6 1 1 -5/8 ! 2
1 tower mounts Pipe Mount [PM 601 -3] 1
,
RISATower Report - version 5.3.1.0
January 14, 2010
162 Ft Monopole Tower Structural Analysis CCI BU No 800530
Project Number 312710, Application 93192, Revision 3 Page 2
TABLE OF CONTENTS
1) INTRODUCTION
2) ANALYSIS CRITERIA
Table 1 - Proposed Antenna and Cable Information
Table 2 - Existing and Reserved Antenna and Cable Information
Table 3 - Design Antenna and Cable Information
3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
3.1) Analysis Method
3.2) Assumptions
4) ANALYSIS RESULTS
Table 5 - Tower Component Stresses vs. Capacity
4.1) Recommendations
5) APPENDIX A
RISATower Output
6) APPENDIX B
Base Level Drawing
7) APPENDIX C
Additional Calculations
RISATower Report - version 5.3.1.0
CROW
Date: January 14, 2010 ( ,4 E
Mitzi Parker Crown Castle
Crown Castle 2000 Corporate Drive
3530 Toringdon Way, Suite 300 Canonsburg, PA
Charlotte, NC 28277 724 -416 -2000
Subject: Structural Analysis Report
Carrier Designation: Verizon Wireless Co- Locate
Carrier Site Name: Northhampton 2 MA
Crown Castle Designation: Crown Castle BU Number: 800530
Crown Castle Site Name: MA NORTHAMPTON II CAC 800530
Crown Castle JDE Job Number: 129147
Crown Castle Work Order Number: 312710
Engineering Firm Designation: Crown Castle Project Number: 312710
Site Data: ATWOOD DRIVE, NORTHAMPTON, Hampshire County, MA
Latitude 42° 18' 9.77 ", Longitude -72° 37' 30.74"
162 Foot - Monopole Tower
Dear Mitzi Parker,
Crown Castle is pleased to submit this "Structural Analysis Report" to determine the structural integrity of the
above mentioned tower. This analysis has been performed in accordance with the Crown Castle Structural
'Statement of Work' and the terms of Crown Castle Purchase Order Number 312710, in accordance with
application 93192, revision 3.
The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we
have determined the tower stress level for the structure and foundation, under the following load case, to be:
LC1: Existing + Reserved + Proposed Equipment Sufficient Capacity
Note: See Table 1 and Table 11 for the proposed and existing /reserved loading, respectively.
The analysis has been performed in accordance with the TIA/EIA -222 -F standard and local code requirements
based upon a wind speed of 75 mph fastest mile.
All modifications and equipment proposed in this report shall be installed in accordance with the attached
drawings for the determined available structural capacity to be effective.
We at Crown Castle appreciate the opportunity of providing our continuing professional services to you and
Crown Castle. If you have any questions or need further assistance on this or any other projects please give us
a call.
o ' �.9
Structural analysis prepared by: Jon W. McElroy, Engineer I/ JYK 4`
,,r 4 1 " 4 ,/, 4 /1
0:N.7 _� '"
Respectfully submitted by j ; t ,,s• t
f1a:1
J .�> I:.
n pia P11 (.,
0 / . t� -� . I Mil.
d? NO. 45281
Douglas K. Pineo, P.E. °140itffi°
Manager Structural Design , O �� *144
RISA Tower Report - version 5.3.1.0
(3 6 c b Z e3
C -- N T --- K eng i neeri ng .�
Centered on Solutions"
February 8, 2012
Mr. Louis Hasbrouck
City of Northampton- Office of Building Commissioner
210 Main Street
Northampton, MA 01060
Re: Letter of Compliance
Project: p V� , eriion: Northampton 2- LTE Antenna Upgrade
d Atwood Drive
Northampton, MA
Engineer: Crown Castle
2000 Corporate Drive Canonsburg, PA
Contractor: Berkshire Wireless
39 Velma Avenue Pittsfield, MA 01201
Centek Project No.: 12009.009
Dear Mr. Hasbrouck,
At the request of Verizon Wireless we have reviewed and verified compliance with the structural
analysis prepared by Crown Castle dated 1/14/2010 [Project Number 312710]. The basis of are
findings are as follows:
❑ Review of the above referenced documentation.
❑ Visual inspection of the subject installation conducted byCentekpersonnel on 1/31/2012.
To the best of our information, knowledge and belief, the installation of this project complies with
the above referenced documentation.
Si e ly ',14
/ i f -_ . - y y .rJ , 5
a ,'-S c c:
- -•���► a `�
II lo e r} tt - rtrtpp a�\ ::'. '-.
" I-i NO. 4276j
to F. Centore, PE . \ '0 < ,
Principal —Structural Engineer ` ', -, �c� ` � ,
1
CC: Tim Parks — Verizon Wireless
Steve Schadler- Verizon Wireless
Jeff York- Verizon Wireless
63 -2 North Branford Road, Branford, CT 06405 203 488 0580 Fax 203.488.8587 www.CentekEng.com