Coffey - Stamped Plan Set 59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
VICINITY MAP
AERIAL MAP PV-1
REV #1:
REV #2:
REV #3:
DATE: 10/30/2024
DRAWN BY: AN
COVER PAGE
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
COFFEY RESIDENCE
PHOTOVOLTAIC SYSTEM
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
PV-1 - COVER PAGE
PV-2 - PROPERTY PLAN
PV-3 - SITE PLAN
PV-3.1 - ROOF PLAN
PV-4 - 1-LINE DIAGRAM
PV-4.1 - 3-LINE DIAGRAM
PV-5 - MOUNTING DETAILS AND BOM
PV-6 - LABELS
PV-7 - STRING MAP
PV-8 - DATASHEETS
PV-9 -PLACARD
SHEET INDEX:
GOVERNING CODES
ALL MATERIALS, EQUIPMENT, INSTALLATION AND
WORK SHALL COMPLY WITH THE FOLLOWING
APPLICABLE CODES:
x
x
x
x
x
xIEEE STANDARD 929
xOSHA 29 CFR 1910.269
xWHERE APPLICABLE, RULES OF THE PUBLIC
UTILITIES COMMISSION REGARDING SAFETY AND
RELIABILITY
xTHE AUTHORITY HAVING JURISDICTION
xMANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS
xANY OTHER LOCAL AMENDMENTS
2023 NATIONAL ELECTRICAL CODE
527 CMR 12.00 MASSACHUSETTS STATE
ELECTRICAL CODE
2015 INTERNATIONAL RESIDENTIAL BUILDING CODE
780 CMR 51.00 9TH EDITION
2021 NFPA 1
527 CMR 1.00 MASSACHUSETTS STATE FIRE CODE
MANUFACTURERS LISTINGS AND INSTALLATION
INSTRUCTIONS UTILITY REQUIREMENTS.
GENERAL
1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF
PHOTOVOLTAIC SYSTEM.
2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL
BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY ACCREDITED BY
THE UNITED STATES OCCUPATIONAL SAFETY HEALTH
ADMINISTRATION
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
PRIOR TO INITIATING CONSTRUCTION.
4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER
INSTALLATION DOCUMENTS PRIOR TO INITIATING
CONSTRUCTION.
5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC,
AND ALL ASSOCIATED WIRING AND
INTERCONNECTIONS SHALL BE INSTALLED ONLY BY
QUALIFIED PERSONNEL.
6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF
ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED
INSPECTIONS. LADDERS MUST BE OSHA APPROVED,
MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD
CONDITION AND DESIGNED FOR ITS INTENDED USE.
7. CONTRACTOR SHALL VERIFY THAT THE ROOF
STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS.
8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO
SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT
EXCEED MANUFACTURER RECOMMENDATIONS FOR
FASTENERS INTO ENGINEERED STRUCTURAL
MEMBERS.
9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES
NOT PLACE THE GROUND LADDER OVER OPENINGS
SUCH AS WINDOWS OR DOORS ARE LOCATED AT
STRONG POINTS OF BUILDING CONSTRUCTION AND IN
LOCATIONS WHERE THE ACCESS POINT DOES NOT
CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS
TREE LIMBS, WIRES, OR SIGNS.
10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING,
THEY SHALL BE CONTAINED IN A METAL RACEWAY;
THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE
ROOF DECKING OR SHEATHING EXCEPT WHERE
COVERED BY THE PV MODULES AND EQUIPMENT.
11. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET
BOXES LOCATED BEHIND MODULES SHALL BE
ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A
MODULE SECURED BY REMOVABLE FASTENERS.
ELECTRICAL
1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM
CONTINUOUS CURRENT OUTPUT AT 25°C AND
MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET
RATED AT 90°C.
2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON
THE ROOF WILL BE USE 2 OR PV-TYPE WIRE.
3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE
IDENTIFIED AND GROUPED. THE MEANS OF
IDENTIFICATION SHALL BE PERMITTED BY SEPARATE
COLOR-CODING, MARKING TAPE, TAGGING OR OTHER
APPROVED MEANS.
4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL
BE RAIN-TIGHT AND APPROVED FOR USE IN WET
LOCATIONS.
5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE
BONDED AND ELECTRICALLY CONTINUOUS.
6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND
CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL
SIZE THEM ACCORDING TO APPLICABLE CODES.
7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR
OTHER EQUIPMENT SHALL NOT DISCONNECT THE
BUILDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PV SOURCE
AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR.
8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC
SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED
WITH A GROUND-FAULT PROTECTION DEVICE OR
SYSTEM THAT DETECTS A GROUND FAULT, INDICATES
THAT FAULT HAS OCCURED AND AUTOMATICALLY
DISCONNECTS ALL CONDUCTORS OR CAUSES THE
INVERTER TO AUTOMATICALLY CEASE SUPPLYING
POWER TO OUTPUT CIRCUITS.
9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED
WITH GROUND FAULT PROTECTION AND A GFI FUSE
PORT FOR GROUND FAULT INDICATION.
10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL
OR BARE COPPER GEC/GEC PER THE MODULE
MANUFACTURER'S LISTED INSTRUCTION SHEET.
11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE
COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN
LUG, OR EQUIVALENT LISTED LUG.
12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741
COMPLIANT.
13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED.
14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR
WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS
AS BUS BARS WITHIN LISTED EQUIPMENT.
15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY
INTERCONNECTION, THE BREAKERS SHALL NOT READ
"LINE AND LOAD".
16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER
TO BE POSITIONED AT THE OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER.
17. THE WORKING CLEARANCE AROUND THE EXISTING
ELECTRICAL EQUIPMENT AS WELL AS THE NEW
ELECTRICAL EQUIPMENT WILL BE MAINTAINED.
SYSTEM SIZE: 7.14 kW-DC | 6.00 kW-AC
MODULE: (17) SEG SOLAR: SEG-420-BTD-BG [420W]
INVERTER: (1) SOLAREDGE SE6000H-US [240V] HOME WAVE INVERTER
x
10-30-2024
N
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
LEGEND:
PROPERTY LINE:
DATE: 10/30/2024
DRAWN BY: AN
PROPERTY PLAN
PV-2
DRIVEWAY:
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
SHED
SCALE: 1/24"=1'-0"
PROPERTY LINE------VERNON ST.------MAI
N
H
O
M
E
DRI
V
E
W
A
Y
FENCE:
DRI
V
E
W
A
Y
65'-10"
72'-3"
85'-9"
55'-11"
154'-3"
17'-2"
15'-8"
84'-5"
9'-5"
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
N
SYSTEM LEGEND
UM
MP
AC
MAIN SERVICE METER AND SERVICE POINT
MAIN SERVICE PANEL
UTILITY AC DISCONNECT
SCALE: 1/8" = 1'-0"
CONDUIT TO BE RUN IN ATTIC IF POSSIBLE,
OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6"
ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES,
AND UNDER EAVES; TO BE PAINTED TO MATCH
EXTERIOR/EXISTING BACKGROUND COLOR OF ITS
LOCATION; TO BE LABELED AT MAX 10' INTERVALS.
CONDUIT RUNS ARE APPROXIMATE AND ARE TO
BE DETERMINED IN THE BY THE INSTALLERS
CONDUIT RUN
(17) SEG SOLAR: SEG-420-BTD-BG [420W]
WITH SOLAREDGE S500 POWER OPTIMIZERS
MOUNTED UNDER EACH MODULE
ROOF SECTION 1: 14 MODULES
AZIMUTH: 210°
PITCH: 34°
ROOF TYPE: ASPHALT SHINGLE
ROOF SECTION 2: 3 MODULES
AZIMUTH: 210°
PITCH: 35°
ROOF DETAIL
1
2
DATE: 10/30/2024
DRAWN BY: AN
SITE PLAN
PV-3
JUNCTION BOX AND CONDUIT
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
I (1) SOLAREDGE SE6000H-US [240V] HOME WAVE
INVERTER
WITH INTEGRATED DC DISCONNECT
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 7.14 kW
AC SYSTEM SIZE: 6.00 kW
MP
AC
I
FIRE CODE SETBACK (18"MIN./ 36" MAX.)
FAC FUSED AC DISCONNECT
FA
CUM
2
13'
3'
1'-6"
1'-6"
1'-6"
1'-6"
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
N
SYSTEM LEGEND
SCALE: 3/16" = 1'-0"
ELEVATION DETAIL
FIRE CODE SETBACK (18" MIN./ 36" MAX.)
ROOF SECTION 1: 14 MODULES
AZIMUTH: 210°
PITCH: 34°
ROOF TYPE: ASPHALT SHINGLE
ROOF SECTION 2: 3 MODULES
AZIMUTH: 210°
PITCH: 35°
ROOF DETAIL
1
2
ROOF ATTACHMENT POINT
DATE: 10/30/2024
DRAWN BY: AN
ROOF PLAN
PV-3.1
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
ROOF FRAMING (RAFTERS/TRUSS)
RACKING
AHJ: NORTHAMPTON CITYMODULE MECHANICAL SPECIFICATIONS
DESIGN WIND SPEED 117 MPH
DESIGN SNOW LOAD 40 PSF
# OF STORIES 2
ROOF PITCH 34° & 35°
TOTAL ARRAY AREA (SQ. FT)357.34
TOTAL ROOF AREA (SQ. FT)1576
ARRAY SQ. FT / TOTAL ROOF SQ. FT 22.67%
1
STRUCTURAL ATTACHMENT
MODULE
ASPHALT SHINGLE
2"X4" :RAFTERS@24" O.C.
2
3'
1'-6"
1'-6"
3'
1'-6"
1'-6"
1'-6"
1'-6"
4' TYP.
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 7.140 kW
AC SYSTEM SIZE: 6.000 kW
INVERTER: (1) SOLAREDGE SE6000H-US
[240V] HOME WAVE INVERTER
MODULE: (17) SEG SOLAR:
SEG-420-BTD-BG [420W]
NOTES:
1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM -
INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE
ATTACHED FOR SPECIFICATIONS IF APPLICABLE
2. PV DC SYSTEM IS UNGROUNDED
3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE
WITH NEC 250.58 AND 690.47(A)
4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS
SHALL COMPLY WITH NEC 690.1(G)
5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE
INSTALLED PER SYSTEM SIGNAGE, PAGE
6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP;
WHEN PRESENT, THE GEC TO BE CONTINUOUS
7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A
8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY
FIELD CONDITIONS
9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY
FIELD CONDITIONS.
DATE: 10/30/2024
DRAWN BY: AN
1-LINE DIAGRAM & CALCULATIONS
PV-4
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
CONDUCTOR AND CONDUIT SCHEDULE
TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE
1 PV WIRE #10 4 - L1 L2 FREE AIR N/A
1 BARE COPPER #6 1 - BARE FREE AIR N/A
2 THWN-2 #10 4 - L1 L2 EMT 3/4"
2 THWN-2 EGC #6 1 - GND EMT 3/4"
3 THWN-2 #8 3 - L1 L2 N EMT 3/4"
3 THWN-2 EGC #6 1 - GND EMT 3/4"
4 THWN-2 #6 3 - L1 L2 N EMT 3/4"
4 THWN-2 EGC #6 1 - GND EMT 3/4"
PV MODULE ELECTRICAL SPECIFICATIONS
MODULE TYPE SEG SOLAR:
SEG-420-BTD-BG [420W]
POWER MAX (PMAX) 420W
OPEN CIRCUIT VOLTAGE (VOC)38.5V
SHORT CIRCUIT CURRENT (ISC)13.83A
MAX POWER VOLTAGE (VMP) 31.90V
MAX POWER CURRENT (IMP)13.77A
SERIES FUSE RATING 30A
AHJ: NORTHAMPTON CITY
NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST
BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT
USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL
TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE
MAY RESULT FROM MISMATCHED CONNECTOR USAGE.
STRING 1: 9 MODULES - SEG SOLAR: SEG-420-BTD-BG [420W]
=
=
=
=
=
=
=
=
=
=
=
=
7
STRING 2: 8 MODULES - SEG SOLAR: SEG-420-BTD-BG [420W]
8
NEMA3R RATED JUNCTION
BOX: SHALL COMPLY W/
NEC 110.3 & 314.6
(N) UTILITY INTERACTIVE SINGLE
PHASE INVERTER
SOLAREDGE SE6000H-US [240V]
HOME WAVE INVERTER
INTEGRATED DC DISCONNECT
UL1741 CERTIFIED
1
1
(N) AC DISCONNECT
240V/60A NEMA 3R
FUSIBLE W/ 40A FUSES,
VISIBLE-LOCKABLE
LABELED
(N) AC DISCONNECT
240V/60A NEMA 3R
NON-FUSIBLE,
VISIBLE-LOCKABLE
LABELED
(E) LOADS
(E) 100A
MAIN
DISCONNECT
UTILITY SERVICE
120/240V
SINGLE PHASE
(E)100A RATED
MAIN SERVICE
PANEL
FACILITY GROUND
(E) GROUND ROD
L1
G N-G
OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS
INVERTER TYPE
SOLAREDGE
SE6000H-US [240V]
HOME WAVE
INVERTER
# OF INVERTERS 1
MAX CONTINUOUS OUTPUT CURRENT 25A
(# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <=
OCPD RATING
(1 x 25A x 1.25)= 31.25A <= 40A, OK
SUPPLY SIDE TAP - ILSCO GTA-250-0-W/C
PARALLEL TAP CONNECTOR
SOLAREDGE S500
OPTIMIZER
INVERTER ELECTRICAL SPECIFICATIONS
INVERTER TYPE
SOLAREDGE SE6000H-US
[240V] HOME WAVE
INVERTER
MAX INPUT DC VOLTAGE 480V
MAX INPUT CURRENT 16.5A
NOMINAL DC INPUT VOLTAGE 380V
MAXIMUM OUTPUT POWER 5000W
NOMINAL AC OUTPUT VOLTAGE 240V
MAXIMUM CONT. OUTPUT CURRENT 25A
CEC EFFICIENCY 99%
POWER OPTIMIZER ELECTRICAL SPECIFICATIONS
OPTIMIZER TYPE SOLAREDGE S500
RATED INPUT DC POWER 500W
MAXIMUM INPUT VOLTAGE (VOC) 125V
MAXIMUM SHORT CIRCUIT CURRENT (ISC) 1.5A
MAXIMUM OUTPUT CURRENT 15A
MAXIMUM OUTPUT VOLTAGE 60V
MINIMUM STRING LENGTH 8
MAXIMUM POWER PER STRING 5700W (6000W WITH
SE7600- SE11400)
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
3-LINE DIAGRAM & CALCULATIONS
PV-4.1
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
NOTES:
1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM -
INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE
ATTACHED FOR SPECIFICATIONS IF APPLICABLE
2. PV DC SYSTEM IS UNGROUNDED
3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE
WITH NEC 250.58 AND 690.47(A)
4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS
SHALL COMPLY WITH NEC 690.1(G)
5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE
INSTALLED PER SYSTEM SIGNAGE, PAGE
6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP;
WHEN PRESENT, THE GEC TO BE CONTINUOUS
7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A
8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY
FIELD CONDITIONS
9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY
FIELD CONDITIONS.
AHJ: NORTHAMPTON CITY
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 7.140 kW
AC SYSTEM SIZE: 6.000 kW
INVERTER: (1) SOLAREDGE SE6000H-US
[240V] HOME WAVE INVERTER
MODULE: (17) SEG SOLAR:
SEG-420-BTD-BG [420W]
NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST
BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT
USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL
TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE
MAY RESULT FROM MISMATCHED CONNECTOR USAGE.
(E) LOADS
(E)100A
MAIN
DISCONNECT
(E)100A RATED
MAIN SERVICE
PANEL
FACILITY GROUND
(E) GROUND ROD
L2
L1
N
G N-G
SUPPLY SIDE TAP - ILSCO GTA-250-0-W/C
PARALLEL TAP CONNECTOR
STRING 1: 9 MODULES - SEG SOLAR: SEG-420-BTD-BG [420W]
=
=
=
=
=
=
=
=
=
=
=
=
7
STRING 2: 8 MODULES - SEG SOLAR: SEG-420-BTD-BG [420W]
8
NEMA3R RATED JUNCTION
BOX: SHALL COMPLY W/
NEC 110.3 & 314.6
(N) UTILITY INTERACTIVE SINGLE
PHASE INVERTER
SOLAREDGE SE6000H-US [240V]
HOME WAVE INVERTER
INTEGRATED DC DISCONNECT
UL1741 CERTIFIED
(N) AC DISCONNECT
240V/60A NEMA 3R
FUSIBLE W/ 40A FUSES,
VISIBLE-LOCKABLE
LABELED
(N) AC DISCONNECT
240V/60A NEMA 3R
NON-FUSIBLE,
VISIBLE-LOCKABLE
LABELED
UTILITY SERVICE
120/240V
SINGLE PHASE
SOLAREDGE S500
OPTIMIZER
CONDUCTOR AND CONDUIT SCHEDULE
TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE
1 PV WIRE #10 4 - L1 L2 FREE AIR N/A
1 BARE COPPER #6 1 - BARE FREE AIR N/A
2 THWN-2 #10 4 - L1 L2 EMT 3/4"
2 THWN-2 EGC #6 1 - GND EMT 3/4"
3 THWN-2 #8 3 - L1 L2 N EMT 3/4"
3 THWN-2 EGC #6 1 - GND EMT 3/4"
4 THWN-2 #6 3 - L1 L2 N EMT 3/4"
4 THWN-2 EGC #6 1 - GND EMT 3/4"
PV MODULE ELECTRICAL SPECIFICATIONS
MODULE TYPE SEG SOLAR:
SEG-420-BTD-BG [420W]
POWER MAX (PMAX) 420W
OPEN CIRCUIT VOLTAGE (VOC) 38.5V
SHORT CIRCUIT CURRENT (ISC)13.83A
MAX POWER VOLTAGE (VMP)31.90V
MAX POWER CURRENT (IMP) 13.77A
SERIES FUSE RATING 30A
OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS
INVERTER TYPE
SOLAREDGE
SE6000H-US [240V]
HOME WAVE
INVERTER
# OF INVERTERS 1
MAX CONTINUOUS OUTPUT CURRENT 25A
(# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <=
OCPD RATING
(1 x 25A x 1.25)= 31.25A <= 40A, OK
INVERTER ELECTRICAL SPECIFICATIONS
INVERTER TYPE
SOLAREDGE SE6000H-US
[240V] HOME WAVE
INVERTER
MAX INPUT DC VOLTAGE 480V
MAX INPUT CURRENT 16.5A
NOMINAL DC INPUT VOLTAGE 380V
MAXIMUM OUTPUT POWER 5000W
NOMINAL AC OUTPUT VOLTAGE 240V
MAXIMUM CONT. OUTPUT CURRENT 25A
CEC EFFICIENCY 99%
POWER OPTIMIZER ELECTRICAL SPECIFICATIONS
OPTIMIZER TYPE SOLAREDGE S500
RATED INPUT DC POWER 500W
MAXIMUM INPUT VOLTAGE (VOC) 125V
MAXIMUM SHORT CIRCUIT CURRENT (ISC) 1.5A
MAXIMUM OUTPUT CURRENT 15A
MAXIMUM OUTPUT VOLTAGE 60V
MINIMUM STRING LENGTH 8
MAXIMUM POWER PER STRING 5700W (6000W WITH
SE7600- SE11400)
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN PV-5
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
MOUNTING DETAILS AND BOM
ATTACHMENT TYPE: SNAPNRACK ULTRA RAIL COMP KIT
WITH SNAPNRACK UR-40 RAILS
ROOF TYPE: ASPHALT SHINGLE , ROOF TILT: 34° & 35°
MODULE WEIGHT: 52.90 LBS
MODULE DIMENSIONS: 5.65' X 3.72'
MODULE WEIGHT/ SQ. FOOT: 2.52 LBS
TOTAL NO. OF MODULES: 17
TOTAL MODULE WEIGHT: 899.30 LBS
ATTACHMENT DETAILS
(N.T.S.)
1
AHJ: NORTHAMPTON CITY
MODULE FRAME
MID CLAMPEND CLAMP
MODULE FRAME
SOLAR CELLS
SNAPANRACK RAIL TOP VIEW TOP VIEW
SIDE VIEW SIDE VIEW
MODULE FRAME
END CLAMP
SNAPNRACK RAILS SNAPNRACK RAILS
MODULE FRAME
MID CLAMP
SOLAR CELLS
SIDE VIEW
SOLAR MODULE
END CLAMP
(E) TRUSS
SNAPNRACK UR-40 RAILS
(E) ASPHALT SHINGLE
SNAPNRACK ULTRA RAIL COMP KIT
3 1/2" x 5/16 WITH 4" MIN
LAG SCREW EMBEDMENT
BILL OF MATERIAL
EQUIPMENT MAKE QUANTITY
MODULE SEG SOLAR: SEG-420-BTD-BG [420W]17
INVERTER SOLAREDGE SE6000H-US [240V] HOME WAVE INVERTER 1
END CLAMPS MODULE END CLAMP STANDARD 12
MID CLAMPS MODULE MIDDLE CLAMP SET STANDARD(INTEGRATED
GROUNDING)28
MOUNTING POINTS SNAPNRACK ULTRA RAIL COMP KIT 38
MOUNTING RAILS SNAPNRACK UR-40 RAILS 12
AC DISCONNECT PV SYSTEM UTILITY AC DISCONNECT 60A RATED 1
AC DISCONNECT PV SYSTEM FUSED AC DISCONNECT 60A RATED WITH 40A
FUSES 1
OPTIMIZER SOLAREDGE S500 POWER OPTIMIZERS 17
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN PV-6
LABELS ARE NOT DRAWN TO SCALE
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 7
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 25 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
DC DISCONNECT
UTILITY
AC DISCONNECT
LABEL 10
AT EACH DC DISCONNECTING MEANS
[NEC 690.13(B)]
LABEL 12
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 13
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVICE
LABEL 14
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
LABEL 9
AT UTILITY METER
[NEC 690.56(B)]
LABEL 4
AT EACH DC DISCONNECTING MEANS
[NEC 690.53]
LABEL 11
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 8
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO SUNLIGHT
LABEL 2
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.15]
MAXIMUM VOLTAGE: 480 V DC
MAXIMUM CIRCUIT CURRENT: 16.5 A DC
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER
OR DC-TO-DC CONVERTER
(IF INSTALLED): 16.5 A DC
LABEL 6
AT RAPID SHUTDOWN DISCONNECT SWITCH
[NEC 690.56(C)(3)].
#03-359 LOCAL CODES
BI-DIRECTIONAL METER
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
WARNING
THIS SERVICE METER
IS ALSO SERVED BY A
PHOTOVOLTAIC SYSTEM
ELECTRICAL LABELS & ELEVATION
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2023
NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE
CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8”
AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER”
WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE
ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW
BACKGROUND. [ANSI Z535]
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS AND
THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF
NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED
FROM EACH OTHER, A DIRECTORY IN ACCORDANCE
WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM
DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS
SHALL NOT BE INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE
WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT
BE HAND-WRITTEN PER NEC 110.21(B)
AHJ: NORTHAMPTON CITY
MAIN SERVICE PANEL
FOR ILLUSTRATION ONLY
(NOT ACTUAL MSP)
MAIN SERVICE
METER
INVERTERJUNCTION
BOX
(IF USED)4
7
8 92
2
2
1
611
14
3
3
TO SOLAR
ARRAY FUSED AC
DISCONNECT
5
2 6
3
UTILITY AC
DISCONNECT
5
2 6
3
10-30-2024
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
FOR INSTALLER USE ONLY
DATE: 10/30/2024
DRAWN BY: AN
OPTIMIZER & STRING MAP
PV-7
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING # 1: 9 MODULES
STRING DETAIL
SOLAREDGE STRINGS
STRING -2
STRING # 2: 8 MODULES
STRING -1
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
MODULE DATASHEET
PV-8.1
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
INVERTER DATASHEET
PV-8.2
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
RAPID SHUTDOWN DATASHEET
PV-8.3
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
ATTACHMENT DATASHEET
PV-8.5
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
DATE: 10/30/2024
DRAWN BY: AN
RACKING DATASHEET
PV-8.6
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
N
DATE: 10/30/2024
DRAWN BY: AN
PLACARD
PV-9
COFFEY, KELLY
38-40 VERNON ST.,
NORTHAMPTON, MA 01060
AHJ: NORTHAMPTON CITY
CAUTION
POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED AS SHOWN
!!
SERVICE 1 OF 1
38-40 VERNON ST., NORTHAMPTON, MA 01060
SOLAR PV
ARRAY
MAIN SERVICE
PANEL
INVERTER
UTILITY AC DISCONNECT
UTILITY METER
FUSED AC DISCONNECT