BPS380710 - SYDNEY THOMSON - UPDATED PERMIT PLAN SET - 06.30.2024 SSVICINITY MAPCONSTRUCTION NOTESCONSTRUCTION NOTESA.A LADDER SHALL BE IN PLACE FOR ANY INSPECTIONS IN COMPLIANCE WITH OSHA REGULATIONS.B.PV MODULES ARE NON-COMBUSTIBLE IN NATURE.C.THIS SYSTEM IS A UTILITY INTERACTIVE (GRID CONNECTED) SYSTEM AND DOES NOT HAVE STORAGE BATTERIES (UNLESS SPECIFICALLY INDICATED ON SHEET PV3 & PV3.1).D.A GROUND ELECTRODE SYSTEM WILL BE PROVIDED IN ACCORDANCE WITH NEC 690.47 & 250.50 - 250.166. GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BEUSED WHEN BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE OR INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTALGROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8FT GROUND ROD WITH ACORN CLAMP. GROUNDING ELECTRODECONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR ACOMPLETE GROUNDING SYSTEM.E.EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.F.THE EXPOSED METALLIC TABS OF THE SOLAREDGE OPTIMIZERS SHALL BE BONDED AND/OR GROUNDED PER NEC 690.43(A) AND THE MANUFACTURERS' INSTRUCTIONS.G.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER NEC 110.26.H.ALTERNATE POWER SOURCE PLACARD SHALL BE PLASTIC, ENGRAVED IN A CONTRASTING COLOR (WHITE). THIS PLAQUE WILL BE PERMANENTLY ATTACHED & UV RESISTANT.I.ALL PLAQUES AND SIGNS WILL BE INSTALLED AS REQUIRED BY 2020 NEC.J.A SMOKE DETECTOR, APPROVED AND LISTED BY THE STATE FIRE MARSHAL, SHALL BE INSTALLED IN EACH DWELLING WHEN A PERMIT FOR ALTERATIONS, REPAIRS ORADDITIONS EXCEEDS $1,000.00. A BATTERY POWERED SMOKE DETECTOR SATISFIES THE REQUIREMENTS FOR A SMOKE DETECTOR. APPROVED COMBINED SMOKE ALARMSAND CARBON DIOXIDE ALARMS SHALL BE ACCEPTABLE. A CARBON MONOXIDE DETECTOR SHALL BE INSTALLED IN THE SPECIFIC EXISTING DWELLING UNIT THAT HAVEATTACHED GARAGES OR FUEL-BURNING APPLIANCES FOR WHICH A PERMIT IS ISSUED FOR ALTERATIONS, REPAIRS OR ADDITIONS EXCEEDING $1,000.00. LISTED SINGLE- ORMULTI-STATION CARBON MONOXIDE ALARMS SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS AND ONEVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS. COMBINED SMOKE/CARBON MONOXIDE ALARMS MAY BE USED. THE ALARM SHALL RECEIVE ITS PRIMARYPOWER FROM THE BUILDING WIRING EXCEPT IT IS PERMITTED TO BE SOLELY BATTERY OPERATED WHERE REPAIRS OR ALTERATIONS DO NOT RESULT IN THE REMOVAL OFWALL AND CEILING FINISHES OR THERE IS NO ACCESS BY MEANS OF AN ATTIC.K.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IFSMALLER THAN #6 AWG COPPER WIRE AS PER NEC 250-64B. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AS BUSBARSWITHIN LISTED EQUIPMENT AS PER NEC 250.64C.L.ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THE BUILDING CODE OF THE LOCAL JURISDICTION.M.PV SYSTEMS CONNECTION IN THE SWITCH GEAR (PANEL) SHALL BE POSITIONED AT THE OPPOSITE END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION ASPER NEC 705.12(B)(3)(2).N.ALL EQUIPMENT SUPPLIED SHALL BE UL LISTED OR LISTED BY A LISTING AGENCY RECOGNIZED BY THE STATE IN WHICH THE SYSTEM IS CONSTRUCTED.O.AC DISCONNECTS SHALL BE IN COMPLIANCE WITH NEC 690.13.P.ALL DC CONDUCTORS SHALL BE 90° RATED THHW, THWN-2, USE-2 OR PV WIRE. ALL AC CONDUCTORS SHALL BE 75° RATED THWN WIRE.Q.THE UTILITY DISCONNECT HAS VISIBLE BLADES, IS LOCKABLE AND IS ACCESSIBLE TO THE UTILITY 24/7.R.ALL BREAKERS SHALL BE SUITABLE FOR BACKFEED. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION THE BREAKER SHALL NOT READ 'LINE ANDLOAD'.S.COORDINATE ANY POWER OUTAGE WITH LOCAL UTILITY AND PROPERTY OWNER. NOTIFY UTILITY BEFORE ACTIVATION OF PV SYSTEM.T.CITY BUILDING INSPECTOR SHALL INSPECT ACCESSIBLE STRUCTURAL CONNECTIONS AND THE HOUSE CURRENT SIDE OF THE SYSTEM, ALL OTHER EQUIPMENT SHALL BE ULLISTED AND APPROVED.U.PHOTOVOLTAIC MODULES SHALL NOT BE INSTALLED OVER ANY ATTIC, PLUMBING OR MECHANICAL VENT. PLUMBING VENTS TO EXTEND A MIN OF 6" ABOVE ROOF ORMODULE. NO BLDG, PLBG OR MECH VENTS TO BE COVERED, OBSTRUCTED OR ROUTED AROUND MODULES.V.ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER THE OPENINGS SUCH AS WINDOWS OR DOORS, ANDLOCATED AT A STRONG POINT OF BUILDING CONSTRUCTION. FIELD VERIFY EXACT LOCATION.W.THE DISCHARGE OF POLLUTANTS TO ANY STORM DRAINAGE SYSTEM IS PROHIBITED. NO SOLID WASTE, PETROLEUM BYPRODUCTS, SOIL PARTICULATE, CONSTRUCTIONWASTE MATERIAL OR WASTEWATER GENERATED ON CONSTRUCTION SITE OR BY CONSTRUCTION ACTIVITIES SHALL BE PLACED, CONVEYED OR DISCHARGED INTO THESTREET, GUTTER OR STORM DRAIN SYSTEM.X.ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE PERMANENTLY ANDCOMPLETELY HELD OFF OF THE ROOF SURFACE.Y.PAINT SURFACE MOUNTED CONDUIT TO MATCH EXISTING STRUCTURE.------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:16 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:TITLE SHEETPV107/03/2024VSE Project Number: U1932.1364.241651 W. galena park blvd. ste. 101draper, Utah 84020phone (801) 990-1775www.vectorse.com®Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen. 7PV MODULES89CONDUIT RUN IS SURFACE MOUNTED(ACTUAL CONDUIT RUNS TO BEDETERMINED IN THE FIELD)6OPTIMIZER (TYPICAL FOR EACH MODULE)NOT USED5.110NOT USEDJUNCTION BOX ON ROOF (SIZEDETERMINED IN FIELD)SYMBOL LEGEND= FLUE / PLUMBING VENT= MECHANICAL VENTMAIN SERVICE PANELUTILITY METER21INVERTER & INTEGRATED DC DISCONNECT54NOT USEDAC DISCONNECT34.1NOT USEDFIRE CODE PATHWAYS & SETBACKS3'1'-6"WESN0'5'10'ROOF EROOF AROOF CROOF G ROOF F ROOF B2351NEC 110.266897ROOF HROOF D------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:16 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:ROOF/SITE PLANPV207/03/2024VSE Project Number: U1932.1364.241651 W. galena park blvd. ste. 101draper, Utah 84020phone (801) 990-1775www.vectorse.com®Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen. 421J-BOXMODULES/OPTIMIZERS IN A STRING+-REDBLACKSESESE3MODULES/OPTIMIZERS IN A STRING+-REDBLACKSESESEL1L2GL1L253L1L2L1L2GJ-BOXMODULES/OPTIMIZERS IN A STRING+-REDBLACKSESESEGL1L25L1L2G3.11.121INTEGRATED MODULE & RACKING GND METHOD UL 2703 APPROVEDINTEGRATED MODULE & RACKING GND METHOD UL 2703 APPROVED4L1L2GN28.2910.1NGL2L1NTOUTILITYGRID11UTILITYDISCOVISIBLE BLADELOCKABLEW/UTILITYACCESS 24/7TAP LESSTHAN 25'GNDELECT.NOTE 1CONNECTION MADE VIA SUPPLY SIDEPER NEC 705.11(A) & NEC 230.82(6)8FUSED5GN------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:20 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:PV3ELECTRICALLINE DIAGRAM/DETAILS NOTE: PLAQUES SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH NON CORROSIVE, POP-RIVETS, SCREWS, OR APPROVED ADHESIVE.LOCATION: MAIN PANELCONDUIT, RACEWAYS & ENCLOSURESLOCATION: MAIN SERVICE PANEL& AC DISCONNECTLOCATION: MAIN SERVICE PANELPV BACK-FED BREAKERLOCATION: MAIN SERVICE PANELPV BACK-FED BREAKERLOCATION: UTILITY METERLOCATION: PV SUB PANEL (IF USED)15611432LOCATION: MAIN SERVICE PANEL / AC DISCONNECT13LOCATION: AC DISCONNECT14LOCATION: DC DISCONNECT/INVERTER #17LOCATION: MAIN SERVICE PANEL8LOCATION: MAIN SERVICE PANELLOCATION: INVERTER109 FOR ILLUSTRATION ONLY (NOT ACTUAL MSP)PV SUB PANEL (IF USED)MAIN SERVICE PANELACDISCONNECT(IF USED)PLACARDINVERTERCONDUITS/RACEWAYS56101719112311248131413LOCATION: MAIN SERVICE PANELPV BACK-FED BREAKER2------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:25 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:EQUIPMENTLABELSPV4 PLACARD12SOLARINVERTER & DCDISCONNECTUTILITY METERINGUTILITY ACDISCONNECTCAUTION:MULTIPLE SOURCES OF POWER------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:26 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:PLACARDPV4.1 =5'-7"4'STRUCTURAL FRAMINGMEMBER @ 16" O.C.MOUNT ATTACHMENTENDCLAMP, TYP.------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:26 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:ATTACHMENTPLANPV507/03/2024VSE Project Number: U1932.1364.241651 W. galena park blvd. ste. 101draper, Utah 84020phone (801) 990-1775www.vectorse.com®Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen. ECOFASTEN ROCKIT ROOF MOUNT SYSTEMALL DIMENSIONS IN INCHESITEM QTY123PARTS LISTDESCRIPTION1 ROCKIT SMART SLIDE ASSEMBLY2 SELF TAPPING SCREW #12 x 3" LONG W/ A SEALING WASHER ASSEMBLY1 ROCKIT V3 MNT 30 TO 40 MM ASSEMBLY.13Ø0.312.87Ø 0.42Ø 0.553.620.755.250.753.621.192.440.630.810.880.630.810.63SELF TAPPING SCREWBOTTOM VIEWFRONT VIEWSIDE VIEW2.446.75123EXPLODED ISOMETRIC VIEWFRONT VIEWSIDE VIEWNOTE:PLEASE SEE MANUFACTURERS GUIDELINES FOR INSTALLATION REQUIREMENTS.THE PLACEMENT AND NUMBER OF SCREWS SHOWN IS THE MINIMUM NUMBERREQUIRED FOR THE CONNECTION TO THE EXISTING ROOF.CBASEE PV5 FOR STRUCTURALINFORMATION**INSTALLER TO VERIFY RAFTER SIZE & SPACINGROCKIT MOUNT, TYP.SKIRTROOF SURFACEAS OCCURSMANUFACTURER SCREWS FOR ROCKIT SLIDE ASSEMBLYNOTES:·SHALL BE AT LEAST 6" FROM ANY TRUSS JOINTS·#12 X 3" LONG, FULLY THREADED, SELF TAPPING SCREW, PER MANUFACTURER·INSTALL PER MANUFACTURERS GUIDELINESROCKIT MOUNTTOP VIEWABCROCKIT MOUNT SIDEROCKIT COUPLING SIDEROCKIT SMART SLIDE DETAIL SIDEDEFROCKIT COUPLING PLANROCKIT MOUNT PLANROCKIT SMART DETAIL FRONTPV MODULE, TYP.ROCKITSMART SLIDEPV MODULE, TYP.ROCKIT COUPLINGROCKIT MOUNTPV MODULE, TYP.ROOF SURFACEAS OCCURSDFEPV MODULE,TYP.ROCKIT MOUNT,TYP.ROOF SURFACEAS OCCURSLL/3 MAX11/16"1 5/16"BETWEENMODULESBETWEENMODULESPV MODULEFRAME, TYP.PV MODULEFRAMEROCKIT MOUNTROCKIT MOUNTPV MODULEROOF SURFACEAS OCCURS1 5/16"BETWEENMODULESNTSNTSNTSNTSNTSNTSSEE PV5 FOR STRUCTURALINFORMATION**INSTALLER TO VERIFY RAFTER SIZE & SPACING3.751.50TYP.0.31TYP.------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:28 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:STRUCTURALCOMPONENTSPV607/03/2024VSE Project Number: U1932.1364.241651 W. galena park blvd. ste. 101draper, Utah 84020phone (801) 990-1775www.vectorse.com®Vector Structural Engineering has reviewed the existingstructure with loading from the solar array and screwconnections to the existing framing. The design of theracking system, racking connections, and all otherstructural is by others. Mechanical, architectural, and allother nonstructural aspects of the design are by others.Electrical is by others, unless stamped by Dean Levorsen. ROOF EROOF AROOF CROOF G ROOF F ROOF BROOF HROOF DWESN------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:28 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:PROPERTY LINESPV7PROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINEPROPERTY LINE ROOF EROOF AROOF CROOF G ROOF F ROOF BROOF HROOF DINVERTER(S) SERIAL NUMBERS#_______________________#_______________________#_______________________1234578910MAPPING INSTRUCTIONS:121314151. REMOVE THE 'SQUARE' OPTIMIZER STICKERAND PLACE NEATLY ON THE APPROPRIATENUMBERED SPACE.2. WRITE THE CORRESPONDING NUMBER ONTHE APPROPRIATE MODULE WITHIN THE ARRAY.171819202223242527282930323334353738394042434445611162126313641·DO NOT MAKE ANY TIE IN CHANGES UNLESS APPROVED AND DOCUMENTED BY BPS DESIGN TEAM·MAXIMUM WATTAGE ALLOWED IN CIRCUIT/STRING IS 6000W FOR SOLAREDGE INVERTERS 7600-11400·MAXIMUM WATTAGE ALLOWED IN CIRCUIT/STRING IS 5700W FOR SOLAREDGE INVERTERS 3000-6000·MINIMUM OPTIMIZERS IN CIRCUIT/STRING = 8 (6 WITH P405/P505)------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:29 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:OPTIMIZERTRACKINGPV8 ROOF EROOF AROOF CROOF G ROOF F ROOF BROOF HROOF DDATE / FECHA:CREW LEAD / LIDER DE GRUPO:CREW MEMBERS / MIEMBROS DEL GRUPO:EXCLUSION ZONE/ZONARESTRINGIDAELECTRICAL ZONE/ZONA ELECTRICAXXXXXXXXXXXXXLLADDER/ESCALERAAANCHOR/ANCLAJEANCHORWORK ANGLES/ANCLAJETRABAJADO ENANGULOSVVEHICLES/VEHICULOSHAZARD NUMBER&EXPLAIN/RIESGOSNUMERADOSY EXPLICADOSH#TREE / ARBOLHOMEENTRANCES/ENTRADA DE LACASAESITE NOTES (INCLUDE ANY HAZARD, NUMBERED AND EXPLAINED):NOTAS DEL LUGAR (INCLUYE CUALQUIER RIESGO, NUMERADOY EXPLICADO):CLOSEST URGENT CARE / MEDICAL FACILITY:SALA DE EMERGENCIA / HOSPITAL MAS CERCANO:PUBLIC PROTECTION / PROTECION PUBLICA: EXCLUSION ZONES / ZONA RESTRINGIDA MARKED ENTRYWAYS / ENTRADA MARCADAFALL PROTECTION / PROTECCION DE CAIDAS: ANCHORS / ANCLAJE ROPES / CARABINERS & ROPE GRAB / SOGAS CARABINERO Y AGARRE DE SOGA HARNESS / ARNES LANYARDS / SOGAPPE / EPP: SAFETY GLASSES / GAFAS DE SEGURIDAD GLOVES/GUANTES HARD HATS/CASCO DE SEGURIDAD ARC FLASH SUIT / HOT GLOVES / TRAJE AISLANTE/GUANTES PARA ELECTRICIDAD FIRST AID KIT / KIT DE PRIMEROS AUXILIOS COVID-19 PPE ON SITE / EPP POR COVID EN EL LUGAR CREW ADHERING TO BPS COVID-19 PLAN / AJUSTE EN EL GRUPO AL PLAN POR COVID-19 DE BPSLEGEND /LEYENDAJOB HAZARD ANALYSIS /ANALISIS DE RIESGOS LABORALES------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:29 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:JOB HAZARDANALYSISPV9 PICKED BY:RECEIVED BY:------------PROJECT #SYSTEM SIZEDESIGNER:DATE:6/30/2024 6:53:30 PMREVDATEDESCRIPTIONDATE:BRIGHT PLANET SOLAR103A MILLBURY ST,AUBURN MA 01501888-997-4469SIGNATURE:CONTRACTOR LICENSE:BOM SHEETPV10